Bryant 548J-14D User Manual

548J*14D SINGLE PACKAGE ROOFTOP HEAT PUMP WITH WITH PURONR(R--410A) REFRIGERANT SIZE 14
Installation Instructions
the installation.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 1....................
INSTALLATION 4...............................
Jobsite Survey 4................................
Step 1 -- Plan for Unit Location 4..................
Roof Mount 5...............................
Step 2 -- Plan for Sequence of Unit Installation 5......
Curb--Mount Installation 5.....................
Pad--Mount Installation 5......................
Frame--Mount Installation 5....................
Step 3 -- Inspect Unit 5...........................
Step 4 -- Provide Unit Support 5...................
Roof Curb Mount 5..........................
Slab Mount (Horizontal Units Only) 5...........
Alternate Unit Support 5......................
Step 5 -- Field Fabricate Ductwork 7................
For Units with Accessory Electric Heaters 7......
Step 6 -- Rig and Place Unit 7.....................
Step 7 -- Convert to Horizontal & Connect Ductwork 8.
Step 8 -- Install Outside Air Hood 8................
Economizer Hood Removal and Setup 8.........
Two Position Damper Hood Removal and Setup 9..
Economizer Hood and Two--Position Hood 10.....
Step 9 -- Install External Condensate Trap and Line 10.
Step 10 -- Make Electrical Connections 11...........
Field Power Supply 11........................
Units without Factory--Installed Disconnect 13....
Units with Factory--Installed Disconnect 13.......
Convenience Outlets 13.......................
Factory--Option Thru--Base Connections 15.......
Units without Thru--Base Connections 15.........
Field Control Wiring 15.......................
Thermostat 15...............................
Unit without Thru--Base Conversion Kit 16.......
Heat Anticipator Settings 16...................
Electric Heaters 16..............................
Single Point Boxes 17..........................
Heater Low--Voltage Control Connections 17......
Outdoor Air Enthalpy Control 18.................
Differential Enthalpy Control 18................
Return Air Enthalpy Sensor 18.................
RTU--MP Control System 19......................
Supply Air Temperature (SAT) Sensor 21.........
Outdoor Air Temperature (OAT) Sensor 22.......
EconoMi$er2 22.............................
Field Connections 22..........................
Space Temperature (SPT) Sensors 22............
Economizer Controls 23......................
Indoor Air Quality (CO
Outdoor Air Quality Sensor 24.................
Connecting Discrete Inputs 24..................
Communication Wiring -- Protocols 25............
General 25.................................
Local Access 25.............................
RTU--MP Troubleshooting 25..................
Smoke Detectors 27.............................
System 27..................................
Controller 27...............................
Sensor 27..................................
Smoke Detector Locations 28....................
Supply Air 28...............................
Return Air without Economizer 28..............
Return Air with Economizer 28.................
Step 11 -- Adjust Factory--Installed Options 32........
Step 12 -- Install Accessories 33...................
)Sensor 23.............
2
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lockout tag. Unit may have more than one power switch.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.
548J*14D
It is important to recognize safety information. This is the safety--alert symbol
unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
. When you see this symbol on the
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
Puronr (R--410A) refrigerant systems operate at higher pressures than standard R--22 systems. Do not use R--22 service equipment or components on Puron refrigerant equipment.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing heat pump units.
2
Vertical Connections / Economizer
548J*14D
Horizontal Connections / Economizer
Fig. 1 -- Unit Dimensional Drawing – Size 14 Unit
3
C09895
548J*14D
Fig. 1 -- Unit Dimensional Drawing – Size 14 Unit (cont.)
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installa­tion requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb or other) that provides for at least the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 2.
NOTE: Consider also the effect of adjacent units. Unit may be installed directly on wood flooring or on Class
A, B, or C roof--covering material when roof curb is used. Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents , relief valves, or other sources of contaminated air.
C10364
18” (457)
*
42" (1067)
Required bottom condensate drain connection.
*
Otherwise, 36” (914mm) for condensate connection.
42" (1067)
42" (1067)
C09897
Fig. 2 -- Service Clearance Dimensional Drawing
Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.
Select a unit mounting system that provides adequate height to allow for removal and disposal of frost and ice that will form during the heating--defrost mode as well as allow installation of condensate trap per requirements. RefertoStep9—InstallExternalCondensate Trap and Line – for required trap dimensions.
4
Roof Mount —
Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.
Table 1 – Operating Weights
548J*14D UNITS LB (KG)
Component 14D
Base Unit 1370 (620)
Economizer
Vertical 100 (45)
Horizontal 115 (52)
Powered Outlet 32 (15)
Curb
14--- in/356 mm 180 (82)
24--- in/610 mm 235 (107)
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb--mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.
Curb--mounted installation —
Install curb Install field--fabricated ductwork inside curb Install accessory thru--base service connection package
(affects curb and unit) (refer to accessory installation instructions for details)
Prepare bottom condensate drain connection to suit planned condensate line routing (refer to Step 9 for details)
Rig and place unit Install outdoor air hood Install condensate line trap and piping Make electrical connections Install other accessories
Pad--mounted installation —
Prepare pad and unit supports Check and tighten the bottom condensate drain
connection plug Rig and place unit Convert unit to side duct connection arrangement Install field--fabricated ductwork at unit duct openings Install outdoor air hood Install condensate line trap and piping Make electrical connections Install other accessories
Frame--mounted installation —
Frame--mounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan.
Step 3 — Inspect Unit
Inspect unit for transportation damage. File any claim with transportation agency.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
Step 4 — Provide Unit Support
Roof Curb Mount —
Accessory roof curb details and dimensions are shown in Fig. 3. Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
NOTE: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 5. Improperly applied gasket can also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are show in Fig. 4. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and
not to the unit.
If electric and control wiring is to be routed through the basepan, attach the accessory thru--the--base service connections to the basepan in accordance with the accessory installation instructions.
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
Alternate Unit Support (In Lieu of Curb or Slab Mount) —
A non--combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4--in. x 4--in. (102 mm x 102 mm) pads on each side.
548J*14D
5
548J*14D
Fig. 3 -- Roof Curb Details
6
C10365
!
CAUTION
C
A
B
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B
0.5” (13)
B-C
1.0” (25)
A-C
1.0” (25)
C10001
Fig. 4 -- Unit Leveling Tolerances
Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or
0.45 in. wg (112 Pa) without economizer. For vertical ducted applications, secure all ducts to roof curb
and building structure. Do not connect ductwork to unit.
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
For Units with Accessory Electric Heaters —
All installations require a minimum clearance to combustible surfaces of 1--in (25 mm) from duct for first 12--in (305 mm) away from unit.
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage to roofing materials.
Membrane roofs can be cut by sharp sheet metal edges. Be careful when placing any sheet metal parts on such roof.
Step 6 — Rig and Place Unit
When the unit is ready to be rigged and no longer will be lifted by a fork truck, the wood protector under the basepan must be removed. Remove 4 screws from each base rail. Wood protector will drop to the ground. See instructions on the unit base rails.
Keep unit upright and do not drop. Spreader bars are required. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 5 for additional information.
Lifting holes are provided in base rails as shown in Fig. 5. Refer to rigging instructions on unit.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
All panels must be in place when rigging. Unit is not designed for handling by fork truck.
Before setting the unit onto the curb, recheck gasketing on curb.
CAUTION
548J*14D
PLACE ALL GASKET IN PLACE BEFORE PLACING UNIT ON ROOF CURB.
“B”
UNIT
548J*14D 2015 916 116.0 2945 55.5 1410 59.5 1510
NOTES:
1. SPREADER BARS REQUIRED — Top damage will occur if spreader bars are not used.
2. Dimensions in ( ) are in millimeters.
3. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
914 - 1371
( 36” - 54” )
“C”
“A”
SEE DETAIL “A”
MAX WEIGHT
LB KG IN MM IN MM IN MM
A B C
DUCT END
DIMENSIONS
DETAIL “A”
Fig. 5 -- Rigging Details
7
C10281
PositioningonCurb—
For full perimeter curbs CRRFCURB072A00 and 073A00, the clearance between the roof curb and the front
1
and rear base rails should be
/4in (6.4 mm). The
clearance between the curb and the end base rails should
1
/2in (13 mm). For retrofit applications with curbs
be CRRFCURB003A01 and 4A01, the unit should be position as shown in Fig. 6. Maintain the 15.5 in (394
5
/8in (220 mm) clearances and allow the
Fig. 6 -- Retrofit Installation Dimensions
548J*14D
mm) and 8
5
/16in (567 mm) dimension to float if necessary.
22
If the alternative condensate drain location through the bottom of the unit is used in conjunction with a retrofit curb, the hole in the curb must be moved 12.5 in (320 mm) towards the end of the unit.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Remove all shipping materials and top skid. Remove extra center post from the condenser end of the unit so that the condenser end of the unit matches Fig. 16 -- 18. Recycle or dispose of all shipping materials.
Step 7 — Convert to Horizontal and Connect Ductwork (when required)
C10003
C06108
Fig. 7 -- Horizontal Conversion Panels
Step 8 — Install Outside Air Hood
Economizer Hood Removal and Setup -­Factory Option —
1. The hood is shipped in knock--down form and located in the return air compartment. It is attached to the economizer using two plastic tie--wraps.
2. To gain access to the hood, remove the filter access panel. (See Fig. 8.)
3. Locate and cut the (2) plastic tie--wraps, being careful to not damage any wiring. (See Fig. 9.)
4. Carefully lift the hood assembly through the filter access opening and assemble per the steps outlined in Economizer Hood and Two–Position Hood on page 10.
Unit is shipped in the vertical duct configuration. Unit without factory--installed economizer or return air smoke detector option may be field--converted to horizontal ducted configuration using accessory CRDUCTCV001A00. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers.
Discard the supply duct cover. Install accessory CRDUCTCV001A00 to cover the vertical supply duct opening. Use the return duct cover removed from the end panel to cover the vertical return duct opening.
Field--supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative data plate when insulating horizontal ductwork.
FILTER ACCESS PANEL
INDOOR COIL ACCESS PANEL
C10004
Fig. 8 -- Typical Access Panel Locations
8
Remove Hood Parts
Cut Plastic Ties (2) Places
Economizer
Fig. 9 -- Economizer Wiring
C10005
Two Position Damper Hood Removal and Setup -­Factory Option —
1. The hood is shipped in knock--down form and assembled to a metal support tray using plastic stretch wrap. Located in the return air compartment, the assembly’s metal tray is attached to the basepan and also attached to the damper using two plastic tie--wraps.
2. To gain access to the hood, remove the filter access panel. (See Fig. 8.)
3. Locate the (2) screws holding the metal tray to the basepan and remove. In order to remove the screws, it may be necessary to remove the panel underneath the two--position damper. Remove the two screws. Locate and cut the (2) plastic tie--wraps securing the assembly to the damper. (See Fig. 10.) Be careful to not damage any wiring or cut tie--wraps securing any wiring.
4. Carefully lift the hood assembly (with metal tray) through the filter access opening and assemble per the steps outlined in Economizer Hood and Two–Position Hood on page 10.
5. If removed, reattach the panel under the damper.
548J*14D
Screws for Metal Tray Qty (2)
Fig. 10 -- Damper Assembly
Hood Parts
Plastic Tie Wrap Qty (2)
C10006
9
Economizer Hood and Two--Position Hood — NOTE: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of the hood. If the panel is still attached to the unit, re­move the screws along the sides and bottom of the panel. See Fig. 11.
SIDE PAN EL
5. Attach the post that separates the filters with the screws provided.
6. Open the filter clips which are located underneath the hood top. Insert the aluminum filters into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filters into place. See Fig. 13.
7. Install the two rain deflectors on the edge of the hood topasshowninFig.11.
RAIN DEFLECTORS
548J*14D
CAULK
INDOOR COIL ACCESS PAN EL
HERE
Fig. 11 -- Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the
hood sides under the panel (hood top). Be careful not to lift the panel too far as it might fall out. Use the screws provided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 12.
TOP PAN EL
TOP PAN EL
INDOOR COIL ACCESS PAN EL
INDOOR COIL ACCESS PANEL
C10007
BAROMETRIC RELIEF
DIVIDER
CLEANABLE ALUMINUM FILTER
FILTER
OUTSIDE AIR
HOOD
FILTER CLIP
C10009
Fig. 13 -- Economizer Filter Installation
8. Caulk the ends of the joint between the unit top panel and the hood top as shown in Fig. 11.
9. Replace the filter access panel.
Step 9 — Install External Condensate Trap and Line
The unit has one3/4-in. condensate drain connection on the end of the condensate pan and an alternate connection on the bottom. See Fig. 14. Unit airflow configuration does not determine which drain connection to use. Either drain connection can be used with vertical or horizontal applications.
When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain pan can be tightened with a
1
/2--in. square socket drive extension.
SCREW
LEFT HOOD SIDE
HOOD DIVIDER
C10008
Fig. 12 -- Economizer Hood Construction
3. Remove the shipping tape holding the economizer barometric relief damper in place.
4. Insert the hood divider between the hood sides. See Fig. 12 and 13. Secure hood divider with 3 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.
To use the alternate bottom drain connection, remove the red drain plug from the bottom connection (use a
1
/2-- i n . square socket drive extension) and install it in the side drain connection.
CONDENSATE PAN (SIDE VIEW)
STANDARD SIDE DRAIN
DRAIN
PLUG
(FACTORY-INSTALLED)
ALTERNATE BOTTOM DRAIN
C08021
Fig. 14 -- Condensate Drain Pan (Side View)
10
The piping for the condensate drain and external trap can be completed after the unit is in place. See Fig. 15.
MINIMUM PITCH 1” (25mm) PER 10’ (3m) OF LINE
BASE RAIL
OPEN VENT
2˝ (51) MIN
TO ROOF DRAIN
DRAIN PLUG
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4” (102) trap is recommended.
SEE NOTE
ROOF CURB
C08022
Fig. 15 -- Condensate Drain Piping Details
All units must have an external trap for condensate drainage. Install a trap at least 4-in. (102 mm) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do not use a pipe size smaller than the unit connection
3
/4-in.).
(
Step 10 — Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.
C10010
Fig. 16 -- Conduit into Factory Option Disconnect
548J*14D
C10011
Fig. 17 -- Conduit into Control Box
NOTE: Check all factory and field electrical connections
for tightness. Field--supplied wiring shall conform with the limitations of 63_F(33_C) rise.
Field Power Supply —
For those units without through--the--curb power, conduit must be used to route the main power from the condenser end of the unit to either the factory option disconnect, the bottom of the control box or the single point box accessory. 1” conduit is provided behind the access panel located under the control box. For those units that require conduit larger than 1”, it must be field supplied. Figures 16, 17 and 18 show the various wire routings.
C10012
Fig. 18 -- Conduit into Single Point Box
If the field disconnect is larger than 100A, it must be attached to the unit using accessory CRDISBKT001A00 (see Fig. 19). Follow the instructions provided with this accessory. For smaller field disconnects, be sure to use
1
/2” screws to mount the disconnect directly to the end panel (see Fig. 20). In either case, set the disconnect vertical location on the unit so that a 90_ fitting can be used to connect the conduit to the disconnect.
11
Loading...
+ 25 hidden pages