Bryant 548J*08D, 548J*09D, 548J*12D, 548J*14D Submittal Data

548J***D
SINGLE PACKAGE ROOFTOP HEAT PUMP UNITS WITH FIELD--INSTALLED ELECTRIC HEAT SIZES 08--14 WITH PURONR(R--410A) REFRIGERANT
Submittal Data
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual
9001
products, go to www.ahridirectory.org.
STANDARD FEATURES
DESCRIPTION
548J***D units are one--piece, two--stage heat pump units that are low profile, prewired, tested and charged at the factory. These units have field convertible supply and return openings and are intended for installation on a roof curb accessory (ordered separately), or for slab mounting (for horizontal duct connections). Units are designed to accept field--installed electric heaters. Units may be ordered with various factory--installed options. Field--installed accessories are also available.
Base Unit
S Puron (R--410A) HFC refrigerant S SEER’s up to 13.4, EER’s up to 11.2 S IEER’s:
— up to 12.2 with single speed indoor fan motor — up to 12.5 with 2--speed/VFD indoor fan motor
S HSPF’s up to 7.7 and COP’s up to 3.3 S ASHRAE 90.1 compliant S Rated in accordance with AHRI Standard 340 S Designed in accordance with Underwriters’
Laboratories Std 1995 and listed by UL and UL, Canada
S Two--stage cooling capacity control S Non--corrosive composite sloping design; side or center
drain condensate pan. Meets ASHRAE Standard 62
S Cooling operating range from 25_Fupto115_F
(--4_Cupto46_C). Field installed accessory extends the minimum down to --20_F(--29_C)
S Convertible from vertical to horizontal airflow for slab
mounting
S Two--inch disposable return air filters S Thru--the--bottom power entry capability S Single point electric connections on field--installed
electric heat units
S 24--volt control circuit protected with resettable circuit
breaker and 75--VA transformer
S Belt drive, constant torque, permanently lubricated
evaporator--fan motor on all size units.
S Totally enclosed condenser motors with permanently
lubricated bearings
S State--of--the--art defrost control board, easily configured
for defrost cycles of 30, 60, 90, or 120 minutes.
S Central Terminal Board for component and unit wiring
connections.
S Loss of Charge, High--Pressure, and Freeze Protection
switches
S Full perimeter base rail with built--in rigging adapters
andforktruckslots.
Cabinet
S Access panels with easy grip handles S Innovative, easy starting, no strip screw features on unit
access panels.
S Pre--painted exterior panels and primer--coated interior
panels tested to 500 hours salt spray protection
S Fully insulated cabinet S Tool--less filter access door
Refrigerant System
S Acutrolt refrigerant metering system S Liquid line filter drier S Scroll compressors with internal line--break overload
protection
S Indoor and outdoor coils constructed of aluminum fins
mechanically bonded to seamless copper tubes.
S Removable gauge line plugs for reading refrigerant
pressure with unit panels in place
S Four--way reversing valve operation S Suction Line Accumulator standard -- prevents
excessive liquid flood back of refrigerant to the compressor even during the start of the defrost cycle.
Standard Parts Warranty
S 5--year electric heater (field--installed) S 5--year compressor S 1--year parts
Job Name Architect Engineer Contractor
Unit Designation
548J***D
Unit Operating Weight lb
Cooling
Net Total Capacity Btuh Net Sensible Capacity Btuh Compressor Power Input kW
at Outdoor Air Temperature _F Indoor Entering Air db: _Fwb _F Airflow CFM External Static Pressure in.wg
SUBMITTAL DATA
PERFORMANCE DATA
Curb Weight lb
Heating
Power Input to Unit kw Integrated Capacity Btuh Indoor Operating Air Temperature _F
db Outdoor Air Temperature _F (Winter Design) Rating at 70% R.H. Outdoors kW Heater Selected
Heat/Cool Ratio
Electrical Capacity Required Btuh
ELECTRICAL DATA
Power Supply to Unit Volts Phase Hz Minimum Circuit Amps Maximum Overcurrent Protection (Fuse Only)
2
FACTORY--INSTALLED OPTIONS (FIOPs)
j Economizer with DRY BULB sensing and barometric
relief
Standard Air Leak Dampers — f Models with W7212 controller provides standard
non--diagnostic control. EconoMi$er IV.
f Models with W7220 controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements. EconoMi$er X.
f Models with RTU Open controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements. EconoMi$er 2.
j Economizer with E
NTHALPY sensing and barometric
relief
Standard Air Leak Dampers — f Models with W7212 controller provides standard
non--diagnostic control. EconoMi$er IV.
f Models with W7220 controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements. EconoMi$er X.
f Models with RTU Open controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements. EconoMi$er 2.
j Economizer with D
RY BULB sensing and barometric
relief
ULTRA LOW LEAK Air Dampers — f Models with W7220 controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements, has return, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements -­plus 5 year limited parts warranty. EconoMi$er X.
f Models with RTU Open controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements, has return, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements -­plus 5 year limited parts warranty. EconoMi$er 2.
j 2--Speed Indoor Fan Motor system utilizes a Variable
Frequency Drive (VFD) to automatically adjust the indoor fan motor for 2 speed indoor fan motor control. Conforms to ASHRAE 90.1 2010 Standard – section 6.4.3.10.b.
j RTU Open multi--protocol controller communicates to
LON, MODBUS, BACNET and Johnson N2 protocols.
j Through the base connectors electric conduit j Two--position motorized outdoor air damper j Non--fused disconnect switch (80 A Max) j Powered 115--volt convenience outlet j Non--powered 115--volt convenience outlet j High static indoor fan motor and drive j Return Air smoke detector j Supply Air smoke detector j Pre--coated Al/Cu condenser coil j E--coated Al/Cu condenser coil j E--coated Al/Cu condenser and evaporator coil j Cu/Cu condenser coil j Cu/Cu condenser coil and evaporator coil j Condenser hail guard — louvered style j CO
sensor
2
OPTIONAL WARRANTIES
j Complete Unit Parts only up to 5 years j Complete Unit Parts and Labor up to 5 years
Many other optional warranties are available. See the Commercial Start--Up and Optional Extended Warranty Price price pages for further information.
548J***D
j Economizer with E
NTHALPY sensing and barometric
relief
ULTRA LOW LEAK Air Dampers — f Models with W7220 controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements, has return, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements -­plus 5 year limited parts warranty. EconoMi$er X.
f Models with RTU Open controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements, has return, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements -­plus 5 year limited parts warranty. EconoMi$er 2.
3
FIELD INSTALLED ACCESSORIES
j Economizer with DRY BULB sensing and barometric
relief
Standard Air Leak Dampers — f Models with W7212 controller provides standard
non--diagnostic control. EconoMi$er IV.
f Models with W7220 controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements. EconoMi$er X.
f Models with RTU Open controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements. EconoMi$er 2.
j Economizer with E
NTHALPY sensing and barometric
relief
Standard Air Leak Dampers — f Models with W7212 controller provides standard
non--diagnostic control. EconoMi$er IV.
548J***D
f Models with W7220 controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements. EconoMi$er X.
f Models with RTU Open controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements. EconoMi$er 2.
j Economizer with D
RY BULB sensing and barometric
relief
ULTRA LOW LEAK Air Dampers — f Models with W7220 controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements, has return, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements. EconoMi$er X.
f Models with RTU Open controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements, has return, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements. EconoMi$er 2.
j Economizer with E
NTHALPY sensing and barometric
relief
ULTRA LOW LEAK Air Dampers — f Models with W7220 controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements, has return, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements. EconoMi$er X.
f Models with RTU Open controller meets California
Title 24 (section 120.2) Fault Detection and Diagnostic (FDD) requirements, has return, outside air and relief damper leakage that meets Title 24 (section 140.4 and ASHRAE 90.1) requirements. EconoMi$er 2.
j Display Kit for Variable Frequency Drive (VFD),
2--Speed Indoor Fan Motor System. Allows additional set up and diagnostics of the unit VFD controller. Can be unit mounted or used with any other compatible VFD model as a reusable device.
j Power Exhaust — vertical or horizontal j Electric heat j Single point kit j Two--position motorized outdoor air damper j Manual outdoor air damper 25% j Manual outdoor air damper 50% j Roofcurb — 14 inch (356mm) tall j Roofcurb — 24 inch (610mm) tall j Thru--the--bottom utility connection kit j Time Guard II compressor anti--cycle control j Outdoor coil hail guard — louvered style j Low ambient head pressure controller, down to --20_F
(--29_C) j Programmable setback thermostat j Electrical/Mechanical thermostat and subbase j Phase monitor j Head pressure control j Disconnect switch bracket (for size 14 units only) j Supply Duct Cover (for size 14 units only)
Economizer Sensors
j Single Dry bulb control j Differential Dry bulb control j Single enthalpy control j Differential enthalpy control j CO j CO
-- wall mounted
2
-- duct mounted
2
4
C12051
548J***D
CERTIFIED DIMENSION 548J*08 -- 09D
5
548J***D
C12052
CERTIFIED DIMENSION 548J*08 -- 09D
6
C12053
548J***D
CERTIFIED DIMENSION 548J*12D
7
548J***D
C12054
CERTIFIED DIMENSION 548J*12D
8
C14194
548J***D
CERTIFIED DIMENSION 548J*14D
9
548J***D
C14195
CERTIFIED DIMENSION 548J*14D
10
ROOF CURB DETAILS — SIZES 08--12
ACCESSORY CONVENIENCE
OUTLET WIRING CONNECTOR
FITTING
1/2" [12.7] NPT 1/2" [12.7] NPT
CONTROL WIRING
FITTING
POWER WIRING
3/4" [19] NPT 1 1/4" [31.7] NPT
THRU THE CURB
1.00"
[25.4]
12-1/2" [317.5] WIDE
INSULATED DECK PANELS
INSULATED DECK PANEL
9-15/16" [252.4] WIDE
1 3/4"
[44.4]
SEE NOTE #2
2-3/8"
[61]
20-3/4"
[513]
INSIDE
GAS SERVICE PLATE
THRU THE CURB
DRILL HOLE
2" [50.8] @
ASSEMBLY (IF
REQUIRED)
(SEE NOTE #8)
1-3/4"
TYP
[44.5]
RETURN AIR
SUPPLY AIR
C
SHEET 5 OF 5
[1987.5]
6' 6-1/4"
THIS DOCUMENT AND THE INFORMATION CONTAINED THEREIN
IS PROPRIETARY TO CARRIER CORPORATION AND SHALL NOT
BE USED OR DISCLOSED TO OTHERS, IN WHOLE OR IN PART,
WITHOUT THE WRITTEN AUTHORIZATION OF CARRIER CORPORATION.
TOLERANCES ON:
DIMENSIONS ARE IN INCHES
----
UNLESS OTHERWISE SPECIFIED
1 DEC 2 DEC 3 DEC ANG
PRODUCTION
50HJ405012
CURB ASY, ROOF
SIZE DRAWING NUMBER REV
D
-
-
-
1029120
AUTHORIZATION NUMBER TITLE
DRAFTER CHECKER
ENGINEERING MANUFACTURING
-
MMC 12/16/09 - -
CERTIFIED DRAWING
-
T-005, Y-002
WEIGHT:
- PURCH - N/A -
ENGINEERING REQUIREMENTS
SURFACE FINISH MFG/PURCH MODEL (INTERNAL USE ONLY) NEXT DRAWING SCALE DISTRIBUTION
ECN NO.APP'DCHK'DBYDATEREVISION RECORDREV
1067898--MMC4/22/13
4' 2"
[1270.0]
"A"
DRAWING RELEASE LEVEL:
SEE VIEW "B"
MATERIAL
THIRD ANGLE
PROJECTION
---
548J***D
CRBTMPWR004A01 THRU THE BOTTOM
CRBTMPWR002A01
CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING
1 3/4"
[44.5]
NOTES:
1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.
2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.
3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
4. ROOFCURB: 18 GAGE STEEL.
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).
6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
7. DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR002A01 IS FOR THRU-THE-CURB GAS TYPE
PACKAGE CRBTMPWR004A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
53 1/2"
[1358.9]
A
14"
24"
[356]
[610]
14 3/4"
[374.7]
11.42"
[290.0]
2 1/4"
"A"
[57.2]
SECTION THRU SIDE
81 3/4"
1 3/4"
[44.4]
[827.1]
32 9/16"
[2076.3]
40 3/16"
[1020.8]
VIEW "B"
CORNER DETAIL
[585.8]
23 1/16"
OPENING
RETURN AIR
OPENING
SUPPLY AIR
NAIL (FIELD SUPPLIED)
TYPICAL (4) SIDES
UNIT
GASKET
15 15/32
31 17/32"
7/16"
[11]
DUCT
(FIELD SUPPLIED)
(SUPPLIED WITH CURB)
[392.9]
[800.9]
CANT STRIP
ROOFING FELT
(FIELD SUPPLIED)
COUNTER FLASHING
(FIELD SUPPLIED)
ROOFING MATERIAL
(FIELD SUPPLIED)
(FIELD SUPPLIED)
RIGID INSULATION
(FIELD SUPPLIED)
6' 61/4" WAS 6' 7 1/6", 4'2' WAS 4' 2 13/16";
18 GA WAS 16 GA.; 15 13/16" WAS 15 15/16"; NAIL
FIELD SUPPLIED WAS WITH CURB
C
SUPPLY AIR RETURN AIR
6 3/64"
ROOF CURB
ACCESSORY #
CRRFCURB003A01
CRRFCURB004A01
[153.5]
26"
[660.4]
4 3/16"
[106.0]
1 3/4"
[401.6]
15 13/16"
[44.5]
1 3/4"
[44.5]
3"
[76.2]
1/4"
[7.0]
[115.5]
4 9/16"
C13311
11
548J***D
ROOF CURB DETAILS — SIZE 14
E2014 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 06/14
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
12
C10365
Catalog No. SUB548J---8 ---14 ---01
Replaces: SUB548J ---06