SINGLE PACKAGE HEAT PUMP/ELECTRIC HEAT
NOMINAL 3 TO 8.5 TONS
WITH PURON
R
(R--410A) REFRIGERANT
Service and Maintenance Instructions
TABLE OF CONTENTS
SAFETY CONSIDERATIONS1....................
UNIT ARRANGEMENT AND ACCESS3...........
SUPPLY FAN (BLOWER) SECTION4..............
HEAT PUMP REFRIGERATION SYSTEM8.........
PURON
COOLING CHARGING CHARTS14................
CONVENIENCE OUTLETS19....................
HEAT PUMP CONTROLS20......................
PROTECTIVE CONTROLS20.....................
COMMERCIAL DEFROST CONTROL21...........
ELECTRIC HEATERS24.........................
SMOKE DETECTORS26.........................
RTU--MP CONTROL SYSTEM33..................
ECONOMIZER SYSTEMS47.....................
WIRING DIAGRAMS56.........................
PRE--START-UP58..............................
START-UP, GENERAL58.........................
START-UP, RTU--MP CONTROL59................
OPERATING SEQUENCE62......................
FASTENER TORQUE VALUES67.................
APPENDIX I. MODEL NUMBER SIGNIFICANCE68...
APPENDIX II. PHYSICAL DATA69................
APPENDIX III. FAN PERFORMANCE71...........
R
(R--410A) REFRIGERANT13.............
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical
components. Only trained and qualifi ed service personnel
shouldinstall,repair,orserviceair-conditioning
equipment. Untrained personnel can perform the basic
maintenance functions of replacing filters. Trained service
personnel should perform all other operations.
When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to
the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations.
Havefireextinguishersavailableforallbrazing
operations.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have
fireextinguisher available.Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety--alert
symbol
instructions or manuals, be alert to the potential for
personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert
symbol. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies a hazard which could result in
personal injury or death. CAUTION is used to identify
unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
. When you see this symbol on the unit and in
APPENDIX IV. ELECTRICAL INFORMATION82....
APPENDIX V. WIRING DIAGRAM LIST96.........
APPENDIX VI. MOTORMASTER SENSOR
LOCATIONS97.................................
UNIT START-UP CHECKLIST99..................
!
WARNING
!
WARNING
548J
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Before performing service or maintenance operations
on unit, turn off main power switch to unit. Electrical
shock and rotating equipment could cause injury.
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience out let circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Tag--out this switch, if necessary.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
Puron (R--410A) refrigerant systems operate at higher
pressures than standard R--22 system s. Do not use
R--22 service equipment or components on Puron
refrigerant equipment.
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause personal
injury or death. Relieve pressure and recover all
refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling
refrigerants. Keep torches and other ignition sources
away from refrigerants and oils.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts and servicing
air conditioning units.
2
UNIT ARRANGEMENT AND ACCESS
Seasonal Maintenance
General
Fig. 1 and Fig. 2 show general unit arrangement and
access locations.
CONTROL BOX
INDOOR BLOWER
ACCESS
COMPRESSORS
(D08-09 only)
C09190
Fig. 1 -- Typical Access Panel Location (Front)
FILTER ACCESS PANEL
These items should be checked at the beginning of each
season (or more often if local conditions and usage
patterns dictate):
Air Conditioning/Heat
Pump
S Outdoor fan motor mounting bolts tightness
S Compressor mounting bolts
S Outdoor fan blade positioning
S Control box cleanliness and wiring condition
S Wire terminal tightness
S Refrigerant charge level
S Indoor coil cleaning
S Supply blower motor amperage
Electric
Heating
S Power wire connections
S Fuses ready
S Manual--reset limit switch is closed
Economizer or Outside Air
Damper
S Inlet filters condition
S Check damper travel (economizer)
S Check gear and dampers for debris and dirt
Air Filters and Scr
eens
548J
INDOOR COIL ACCESS PANEL
C08449
Fig. 2 -- Typical Access Panel Locations (Rear)
Routine Maintenance
These items should be part of a routine maintenance
program, to be checked every month or two, until a
specific schedule for each can be identified for this
installation:
Quarterly Inspection (and 30 days after initial start
S Return air filter replacement
S Outdoor hood inlet filters cleaned
S Belt tension checked
S Belt condition checked
S Pulley alignment checked
S Fan shaft bearing locking collar tightness chec ked
S Outdoor coil cleanliness checked
S Condensate drain checked
)
Each unit is equipped with return air filters. If the unit has
an economizer, it will also have an outside air screen. If a
manual outside air damper is added, an inlet air screen
will also be present.
Each of these filters and screens will need to be
periodically replaced or cleaned.
Return Air
Filters
Return air filters are disposable fiberglass media type.
Access to the filters is through the small lift--out panel
located on the rear side of the unit, above the
evaporator/return air access panel. (See Fig. 1.)
To remove the filters:
1. Grasp the bottom flange of the upper panel.
2. Lift up and swing the bottom out until the panel disengages and pulls out.
3. Reach inside and extract the filters from the filter
rack.
4. Replace these filters as required with similar replacement filters of same size.
To re--install the access panel:
1. Slide the top of the panel up under the unit top panel.
2. Slide the bottom into the side channels.
3. Push the bottom flange down until it contacts the top
of the lower panel (or economizer top).
IMPORTANT:DONOTOPERATETHEUNIT
WITHOUT THESE FILTERS!
3
Outside Air Hood
Outsideairhoodinletscreensarepermanent
aluminum--mesh type filters. Check these for cleanliness.
Remove the screens when cleaning is required. Clean by
washing with hot low--pressure water and soft detergent
and replace all screens before restarting the unit. Observe
the flow direction arrows on the side of each filter frame.
Economizer Inlet Air Screen
This air screen is retained by spring clips under the top
edge of the hood. (See Fig. 3.)
548J
BAROMETRIC
RELIEF
DIVIDER
CLEANABLE
ALUMINUM
FILTER
OUTSIDE
AIR
FILTER
HOOD
Fig. 3 -- Filter Installation
To remove the filter, open the spring clips. Re--install the
filter by placing the frame in its track, then closing the
spring clips.
FILTER
CLIP
C08634
SUPPLY FAN (BLOWER) SECTION
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause persona l
injury or death.
Before performing service or maintenance operations
on the fan system, shut off all unit power and tag--out
the unit disconnect switch. Do not reach into the fan
section with power still applied to unit.
Supply Fan (Direct--Drive)
For unit sizes 04, 05 and 06, the Standard Static supply
fan system consists of a direct--drive forward--curved
centrifugal blower wheel attached to the motor shaft. The
motor has taps to provide the servicer with the selection of
one of five motor torque/speed ranges to best match wheel
performance with attached duct system. See Fig. 5 (548J
Direct--Drive Fan Assembly) and Fig. 6 (EMC Motor
Connectors).
EMC Motor
95°
Motor Plug Position
(95° from vertical)
EMC Power
Transformer
(460, 575v)
Manual Outside Air Hood Screen
This inlet screen is secured by a retainer angle across the
top edge of the hood. (See Fig. 4.)
C07156
Fig. 4 -- Screens Installed on Outdoor--Air Hood
(Sizes 08D--09D Shown)
To remove the screen, loosen the screws in the top retainer
and slip the retainer up until the filter can be removed.
Re--install by placing the frame in its track, rotating the
retainer back down and tighten all screws.
Fig. 5 -- 548J Direct--Drive Supply Fan Assembly
L2
YEL
Gnd
GRN/YEL
L1
BLU
C
LGN
Com
BRN
Speed
Taps
12345
VIO
Default Connection
Fig. 6 -- EMC Motor Connectors
C09260
Motor
Power
Connections
C09261
4
460, 575-v Units
208/230-v Units
Fig. 7 -- EMC Unit Wiring
548J
C09263
ECM Motor – The direct--drive motor is an X13
Electronically Commutated motor (ECM). An ECM
contains electronic circuitry to convert single--phase line
AC voltage into a 3--phase DC voltage to power the motor
circuit. The motor circuit is a DC brushless design with a
permanent magnet rotor. On the X13 design, the
electronic circuitry is integral to the motor assembly and
cannot be serviced or replaced separately.
208/230--v units use a 230--v motor. 460--v units use a
230--v motor with a stepdown transformer (mounted on
the end of the fan housing, see Fig. 5). 575--v units use a
460--v motor with an autotransformer. Motor power
voltage is connected to motor terminals L and N (see
Fig. 6 and Fig. 7); ground is connected at te rminal G.
The motor power voltage is ALWAYS present; it is not
switched off by a motor contactor.
Motor operation is initiated by the presence of a 24-- v
control signal to one of the fi ve motor communications
terminals. When the 24--v signal is removed, the motor
will stop. The motor control signal is switched by the
defrost board’s IFO output.
Evaluating motor speed – The X13 ECM is a constant
torque motor design. The motor speed is adjusted by the
motor control circuitry to maintain the programmed shaft
torque. Consequently there is no specific speed value
assigned to each control tap setting. At the Position 5 tap,
the motor speed is approximately 1050 RPM (17.5 r/s) but
it will vary depending on fan wheel loading.
Selecting speed tap – The five communications terminals
are each programmed to provide a different motor torque
output. See Table 1. Factory default tap selection is
Position 1 for lowest torque/speed operation.
Table 1 – 548J Standard Static Motor Tap Programing
(percent of full--load torque)
Unit SizeTa p 1Tap 2Ta p 3Ta p 4Tap 5
0432384550100
0546586169100
0673828590100
Factory Default: Tap 1 (VIO)
To select another speed:
1. Disconnect main power to the unit.
2. Remove the motor signal lead (VIO) a t the motor
communications terminal.
3. Reconnect the motor signal lead to the desired speed
terminal.
4. Connect main power to the unit.
Motor “rocking” on start--up – When the motor first starts,
the rotor (and attached wheel) will “rock” back and forth
as the motor tests for rotational direction. Once the correct
rotation direction is determined by the motor circuitry, the
motor will ramp up to specified speed. The “rocking” is a
normal operating characteristic of ECM motors.
Troubleshooting the ECM motor – Troubleshooting the
X13 ECM requires a voltmeter.
1. Disconnect main power to the unit.
2. Remove the motor power plug (including the control
BRN lead) and VIO control signal lead at the motor
terminals.
3. Restore main unit power.
4. Check for proper line vol tage at motor power leads
BLK (from L terminal) and YEL (from N terminal).
5
Table 2 – Motor Test Volts
Unit VoltageMotor VoltageMin ---Max Volts
208/230230190---250
460230210---250
575460420---500
5. Apply a jumper at uni t control terminals R to G to
initiate a demand for motor operation. Check for 24--v
output at defrost board terminal IFO.
6. Check for proper control signal voltage at motor
signal leads VIO and BRN. Signal should be 22 to
28--v.
7. Disconnect unit main power.
8. Reconnect motor power and control signal leads at
the motor terminals.
9. Restore unit main power.
Motor should start and run. If it does not, remove the
548J
motor assembly. Replace with same motor part number;
do not substitute with an alternate design as torque/speed
programming will not be same as on original factory
motor.
Replacing the ECM Motor – Before removing the ECM
belly--band mounting ring, measure the distance between
the base of the motor shaft and the edge of the mounting
ring. Remove the motor mounting band and transfer to the
replacement motor. Position the mounting band at
distance measured in first step. Snug the mounting bolt
but do not tighten yet.
Insert the motor shaft into the fan wheel hub. Then secure
the three motor mount arms to the support cushions.
Torque the arm mounting screws to 60 in--lbs (6.8 N--m).
Center the fan wheel in the fan housing. Torque the fan
wheel hub setscrew to 120 in -- lbs (13.6 N--m).
Ensure the motor terminals are located at a position below
the 3 o’clock position (see Fig. 5). Tighten the motor
belly--band bolt to 80 in--lbs (9.0 N--m).
Supply Fan (Belt--Drive)
Thebelt--drivesupplyfansystemconsistsofa
forward--curved centrifugal blower wheel on a solid shaft
with two concentric type bearings, one on each side of the
blower housing. A fixed--pitch driven pulley is attached to
the fan shaft and an adjustable--pitch driver pulley is on
the motor. The pulleys are connected using a “V” type
belt. (See Fig. 8.)
C07087
Fig. 8 -- Belt Drive Motor Mounting
Belt
Check the belt condition and tension quarterly. Inspect the
belt for signs of cracking, fraying or glazing along the
inside surfaces. Check belt tension by using a spring--force
tool (such as Browning’s Part Number “Belt Tension
Checker” or equivalent tool); tension should be 6--lbs at a
5
/8--in. deflection when measured at the centerline of the
belt span. This point is at the center of the belt when
measuring the distance between the motor shaft and the
blower shaft.
NOTE: Without the spring--tension tool, place a straight
edge across the belt surface at the pulleys, then deflect the
1
belt at mid--span using one finger to a
/2--in. deflection.
Adjust belt tension by loosening the motor mounting plate
front bolts and rear bolt and sliding the plate toward the
fan (to reduce tension) or away from fan (to increase
tension). Ensure the blower shaft and the motor shaft are
parallel to each other (pulleys aligned). Tighten all bolts
when finished.
To replace the belt:
1. Use a belt with same section type or similar size. Do
not substitute a “FHP” type belt. When installing the
new belt, do not use a tool (screwdriver or pry--bar) to
force the be lt over the pulley flanges, this will stress
the belt and cause a reduction in belt life.
2. Loosen the motor mounting plate front bolts and rear
bolts.
3. Push the motor and its mounting plate towards the
blower housing as close as possible to reduce the center distance between fan shaft and motor shaft.
4. Remove the belt by gently lifting the old belt over
one of the pulleys.
5. Install the new belt by gentl y sliding the belt over
both pulleys and then sliding the motor and plate
away from the fan housing until proper tension is
achieved.
6. Check the alignment of the pulleys, adjust if necessary.
7. Tighten all bolts.
8. Check the tension after a few hours of runtime and
re--adjust as required.
6
Adjustable--Pitch Pulley on Motor
The motor pull ey is an adjustable--pitch type that allows a
servicer to implement changes in the fan wheel speed to
match as--installed ductwork systems. The pulley consists
of a fixed flange side that faces the motor (secured to the
motor shaft) and a movable flange side that can be rotated
around the fixe d flange side that increases or reduces the
pitch diameter of this driver pulley. (See Fig. 9.)
4. Recheck belt tension.
Bearings
This fan system uses bearings featuring concentric split
locking collars. The collars are tightened through a cap
screw bridging the split portion of the collar. The cap
screw has a Torx T25 socket head. To tighten the locking
collar: Hold the locking collar tightly against the inner
race of the bearing and torque the cap screw to 65--70
in--lb (7.4--7.9 Nm). See Fig. 10.
548J
C07075
Fig. 9 -- Supply--Fan Pulley Adjustment
As the pitch diameter is c hanged by adjusting the position
of the movable flange, the centerline on this pul ley shifts
laterally (along themotor shaft). This creates a
requirement for a realignment of the pulleys aft er any
adjustment of the movable flange. Also reset the belt
tension after each realignment.
Check the condition of the motor pulley for signs of wear.
Glazing of the belt contact surfaces and e rosion on these
surfaces are signs of improper belt tension and/or belt
slippage. Pulley replacement may be necessary.
To change fan speed:
1. Shut off unit power supply.
2. Loosen belt by loosening fan motor mounting nuts.
(See Fig. 8.)
3. Loosen movable pulley flange setscrew. (See Fig. 9.)
4. Screw movable flange toward fixed flange t o increase
speed and away from fixed flange to decrease speed.
Increasing fan speed increases load on motor. Do not
exceed maximum speed specified.
5. Set movable fla nge at nearest keyway of pulley hub
and tighten setscrew to torque specifications.
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft. Make angular alignment by loosening motor from mounting.
3. Tighten fan pulley setscrews and motor mounting
bolts to torque specifications.
C08121
Fig. 10 -- Tightening Locking Collar
Motor
When replacing the motor, also re place the external--tooth
lock washer (star washer) under the motor mounting base;
this is part of the motor grounding system. Ensure the
teeth on the lock washer are in contact with the motor’s
painted base. Tighten motor mounting bolts to 120 +/-- 12
in--lbs.
Changing fan wheel speed by changing pulleys: The
horsepower rating of the belt is primarily dictated by the
pitch diameter of the smaller pulley in the drive system
(typically the motor pulley in these units). Do not install a
replacement motor pulley with a smaller pitch diameter
than provided on the original factory pulley. Change fan
wheel speed by changing the fan pulley (larger pitch
diameter to reduce wheel speed, smaller pitch diameter to
increase wheel speed) or select a new system (both
pulleys and matching belt(s)).
Before changing pulleys to increase fan wheel speed,
check the fan performance at the target speed and airflow
rate to determine new motor loading (bhp). Use the fan
performance tables or use the Packaged Rooftop Builder
software program. Confirm that the motor in this unit is
capable of operating at the new operating condition. Fan
shaft loading increases dramatically as wheel speed is
increased.
To reduce vibration, replace the motor’s adjustable pitch
pulley with a fixed pitch pulley (after the final airflow
balance adjustment). This will re duce the amount of
vibration generated by the motor/belt--drive system.
7
HEAT PUMP REFRIGERATION
SYSTEM
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause persona l
injury, death and/or equipment damage.
This system uses Puron
higher pressures than R--22 and ot her refrigera nts. No
other refrigerant may be used in this system. Gauge
set, hoses, and recovery system must be designed to
handle Puron refrigerant. If unsure about equipm ent,
consult the equipm ent manufacturer.
R
refrigerant which has
NOTE: Use of a water stream, such as a garden hose,
against a surface loaded coil will drive the fibers and dirt
into the coil. This will make cleaning efforts more
difficult. Surface loaded fibers must be completely
removed prior to using low velocity clean water rinse.
Periodic Clean Water
A periodic clean water rinse is very beneficial for coils
that are appli ed in coastal or industrial environments.
However, it is very important that the water rinse is made
with very low velocity water stream to avoid damaging
the fin edges. Monthly cleaning as described below is
recommended.
!
Rinse
CAUTION
Outdoor Coil
548J
The 548J outdoor coil is fabricated with round tube
copper hairpins and plate fins of various materials and/or
coatings (see “Appendi x I -- Model Number Significance”
to identify the materials provided in this unit). All unit
sizes use composite--type two--row coils. Composite
two--row coils are two single--row coils fabricated with a
single return bend end tubesheet.
Indoor Coil
The indoor coil is traditional round--tube, plate --fin
technology. Tube and fin construction is of various
optional materials and coatings (see Model Number
Format). Coils are multiple--row.
Outdoor Coil Maintenance and Cleaning
Recommendation
Routine cleaning of coil surfaces is essential to maintain
proper operation of the unit. Elimination of contamination
and removal of harmful residues will greatly increase the
life of the coil and extend the life of the unit. The
following maintenance and cleaning procedures are
recommended as part of the routine maintenance activities
to extend the life of the coil.
Remove Surface Loaded
Surface loaded fibers or dirt should be removed with a
vacuum cleaner. If a vacuum cleaner is not available, a
soft non--metallic bristle brush may be used. In either
case, the tool should be applied in the direction of the fins.
Coil surfaces can be easily damaged (fin edges can be
easily bent over and damage the coating of a protected
coil) if the tool is applied across the fins.
Fibers
PERSONALINJURY ANDUNIT DAMAGE
HAZARD
Failure to follow this caution may result in personal
injury or equipment damage.
Only approved cleaning is recommended.
Routine Cleaning of Indoor Coil Surfaces
®
Periodic cleaning with Totaline
coil cleaner is essential to e xtend the life of coils. This
cleaner is available from our Replacement Components
Division as part number P902--0301 for one gallon
container, a nd part number P902--0305 for a 5 gallon
container. It is recommended that all coils, including
standardaluminum,pre--coated,copper/copperor
E--coatedcoilsbecleanedwiththeTotaline
environmentally sound coil cleaner as described below.
Coil cleaning should be part of the unit’s regularly
scheduled maintenance procedures to ensure long life of
the coil. Failure to clean the coils may result in reduced
durability in the environment.
Avoid the use of
S coil brighteners
S acid cleaning prior to painting
S high pressure washers
S poor quality water for cleaning
Totalineenvironmenta llysoundcoilcleaneris
nonflammable, hypoallergenic, non bacterial, and a
USDA accepted biodegradable agent that will not harm
the coil or surrounding components such as electrical
wiring, painted metal surfaces, or insulation. Use of
non--recommended coil cleaners is strongly discouraged
since coil and unit durability could be affected.
environmentally sound
Clean coil as follows:
1. Turn off unit power, tag disconnect.
2. Remove top panel screws on outdoor coil end of unit.
3. Remove coil corner post. See Fig. 11. To hold top
panel open, place coil corner post between top panel
and center post. See Fig. 12.
7. Secure inner a nd outer coil rows together with a
field--supplied fastener.
8. Reposition the outer coil section and remove the coil
corner post from between the top panel and center
post. Reinstall the coil corner post and replace all
screws.
Failure to follow this caution may result in corrosion
and damage to the unit.
Harsh chemicals, household bleach or acid or basic
cleaners should not be used to clean outdoor or indoor
coils of any kind. These cleaners can be very difficult
to rinse out of the coil and can accelerate corrosion at
the fin/tube interface where dissimilar materials are in
contact. If there is dirt below the surface of the coil,
use the Totali ne environmentally sound coil cleaner as
described above.
548J
C08206
Fig. 12 -- Propping Up Top Panel
4. For Sizes 04--07: Remove screws securing coil to
compressor plate and compressor access panel.
5. For Sizes 08--09: Remove fastener holding coil sections together at return end of condenser coil. Ca refully separate the outdoor coil section 3 to 4 in. from
the inner coil section. See Fig. 13.
OUTDOOR
COIL
C09220
Fig. 13 -- Separating Coil Sections
6. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced
unit performance.
High velocity water from a pressure washer, garden
hose, or compressed air should never be used to clean
a coil. The force of the water or air jet will bend the
fin edges and increase airside pressure drop.
1. Proper eye protection such as safety glasses is recommended during mixing and application.
2. Remove all surface loaded fibers and dirt with a vacuum cleaner as described above.
3. Thoroughly wet finned surfaces with clean water and
a low velocity garden hose, being carefull not to bend
fins.
4. Mix Totaline environmentally sound coil cleaner in a
1
/2gallon garden spryer according to the instruc-
2
tions included with the cleaner. The optimum solution
temperature is 100°F(38°C).
NOTE: Do NOT USE water in excess of 130°F(54°C), as
the enzymatic activity will be destroyed.
5. Thoroughly apply Totaline environmentally sound
coil cleaner solution to all coil surfaces including
finned area, tube sheets and coil headers.
6. Hold garden sprayer nozzle close to finned areas and
apply cleaner with a vertical, up--and--down motion.
9
Avoid spraying in horizontal pattern to minimize potential for fin damage.
7. Ensure cleaner thoroughly penetrates deep into finned
areas.
8. Interior and e xterior finned areas must be thoroughly
cleaned.
9. Finned surfaces should remain wet with cleaning
solution for 10 minutes.
10. Ensure surfaces are not allowed to dry before rinsing.
Reapply cleaner as needed to ensure 10--minute saturation is achieved.
11. Thoroghly rinse all surfaces with low velocity clean
water using downward rinsing motion of water spray
nozzle. Protect fins from damage from the spray
nozzle.
Indoor Coil
Cleaning the Indoor Coil
548J
1. Turn unit power off. Install lockout tag. Remove indoor coil access panel.
2. If economizer or two--position damper is installed, remove economizer by disconnecting Molex plug and
removing mounting screws.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister. Wash
both sides of coil and flush with clean water. For best
results, back--flush toward return--air section to remove foreign material. Flush condensate pan after
completion.
Filter
Drier
LPS/LOC
2B
5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.
Refrigeration System
Components
Eachheatpumprefrigerationsystemincludesa
compressor, accumulator, reversing valve, dual--function
outdoor coil with vapor header check valve, cooling liquid
line with filter drier and check valve, dual--function
indoor coil with vapor header check valve, and heating
liquid line with check valve and strainer. Unit sizes
04A--07A have a single compressor--circuit; unit sizes
08D and 09D have two compressor--circuits. See Fig. 14
for typical unit piping schematic (unit size 09D (4--row
indoor coil) with two compressor--circuits is depicted).
Dual--function outdoor and indoor coils are designed to
provide parallel coil circuits during evaporator--function
operationandconvergingcoilcircuitsduring
condenser--function operation.
Refrigerant flow metering in the evaporator--function
sequence is provided by multiple Acutrols – fixed--bore
metering devices that are located in the tee nipples
between the liquid header and the entrance to each coil
circuit. The Acutrol metering device is swaged into the
nipple tube between the liquid header end and the
side--port tube. See Fig. 15. During evaporator--function
operation, flow is straight through the nipple and into each
evaporator circuit. Flow continues through the parallel
evaporator circuits and into the vapor heade r.
DFT 2
Acutrol
DFT 1
Outdoor Coil
1B
1A
ACCUMULATOR
2A
Heating Mode Liquid Lines
Cooling Liquid Lines
HPS
COMPRESSOR
Comp 2
ACCUMULATOR
COMPRESSOR
2C
HPS
Comp 1
2D
1D
Indoor Coil
1C
Strainer
Fig. 14 -- Typical Unit Piping Schematic (09D unit with 4--row indoor coil)
Acutrol
C09228
10
To
r
r
Evaporato
Coil
Circuits
Metering
Orifice
From
Liquid
Header
C09229
Fig. 15 -- Heat Pump Acutrol — Flow as Evaporator
Function
Converging circuitflow inthe condenser--function
operation is accomplished with the check valve in the
vapor header and the liquid transfer header connected to
the side ports on all but one of the Acurator tee nipples in
each circuit. During condenser --function operation, hot gas
from the compressor discharge enters the header until it
reaches the check valve which blocks further flow. The
hot gas exits the header through the tubes above the check
valve and enters these coil circuits. At the outlet of these
desuperheating and condensing circuits, the refrigerant
enters the Acurater tees from the coil end. The refrigerant
exits the tee at the side port and enters the liquid transfer
header (see Fig. 16). The refrigerant moves through the
liquid transfer header and exits through the remai ning
tubes, through the side ports on the Acutrol tees (see
Fig. 17) and back into the coil circuits where additional
condensing occurs. These circuits exit into the vapor
header behind the check valve and exit through the
remaining tube on the vapor header. In this last pass
through the coil, the refrigerant is subcooled. Subcooled
liquid exits at the last Acutrol tee (see Fig. 18) where the
side port is connected to the specific mode liquid line.
From
Condenser
Coil Circuits
To
Condensing
Circuit
From
Transfer
Header
C09231
Fig. 17 -- Heat Pump Acutrol — Flow as Condenser
Function/Entering Second Pass
DFT Location
(Outdoor Coils only)
From
Subcoole
Circuit
To
Liquid
Line
C09232
Fig. 18 -- Heat Pump Acutrol — Flow as Condenser
Function/ Exiting Subcooler Pass
Each liquid line has a check valve to prevent backflow
through the liquid line in its opposite mode. Thi s ensures
correct flow direction through filter driers and strainers
and prevents emptying of off-- mode liquid lines into
evaporator--function coil circuits.
Reversing Valve and Check Valve Position
SeeFig.14onpage10.
Table 3 – Cooling Mode (each circuit)
548J
To
Transfer
Header
Fig. 16 -- Heat Pump Acutrol — Flow as Condenser
Function/ Exiting First Pass
C09230
ComponentStatus/Position
Reversing ValveEnergized
Check Valve AClosed
Check Valve BOpen
Check Valve CClosed
Check Valve DOpen
Table 4 – Heating Mode (each circuit)
ComponentStatus/Position
Reversing ValveDe--- energized
Check Valve AOpen
Check Valve BClosed
Check Valve COpen
Check Valve DClosed
11
Table 5 – Defrost Mode
04A---07A and 08D---09D/Circuit 2:
Component
Defrost ThermostatClosed
Outdoor Fan(s)Off
Reversing ValveEnergized
Check Valve AClosed
Check Valve BOpen
Check Valve CClosed
Check Valve DOpen
Status/Position
Troubleshooting Refrigerant Pressure Problems
and Check Valves
Refer to Fig. 14, on page 10, and t he Cooling Mode and
Heating Mode tables (Tables 3 and 4) on page 11.
548J
Coil Metering
The metering devices are multiple fixed–bore devices
(Acutrolt) swaged into the horizontal outlet tubes from
the liquid header, located at the entrance to each
evaporator coil circuit path. These are non–adjustable.
Service requires replacing the entire liquid header
assembly.
Check for possible blockage of one or more of these
metering devices by creating a low load condition on the
evaporator--function coil and then observing the frosting
pattern on the finned portion of the coil.
To c heck the indoor coil, disconnect the supply fan signal
(04A--06A direct--drive fans) or contactor (IFC) coil, then
Devices
start the circuit in a Cooling Mode (jumper R to Y1 or
Y2) and observe the frosting pattern on the face of the
indoor coil. A frost pattern should develop uniformly
across the face of the indoor coil starting a t each tube at
the Acutrol nipple locations.
To check the outdoor coil, disconnect the outdoor fan
motor. Start the circuit in a Heating Mode (jumper R to
W1 or W2) and observe the frost pattern on the face of the
outdoor coil.
Failure to develop frost at an outlet tube can indicate a
plugged or a missing orifice.
Refrigerant System Pressure Access Ports
There are two access ports in each circuit -- on the suction
tube near the compressor and on the discharge tube near
the compressor. These are brass fittings with black plastic
caps. The hose connection fittings are standard 1/4 SAE
Male Flare couplings.
The brass fittings are two--piece High Flow valves, with a
receptacle base brazed to the tubing and an integral
spring-- closed check valve core screwed into the base.
(See Fig. 19.) This check valve is permanently assembled
into this core body a nd cannot be serviced separately;
replace the entire core body if necessary. Service tools are
available from RCD that allow the replacement of the
check valve core without having to re cover the entire
system refri gerant charge. Apply compressor refrigerant
oil t o the check valve core’s bottom o--ring. Install the
fitting body with 96 +/--10 in--lbs of torque; do not
overtighten.
5/8” HEX
SEAT
.47
1/2-20 UNF RH
0.596
30°
WASHER
O-RING
This surface provides a metal to metal seal when
torqued into the seat. Appropriate handling is
required to not scratch or dent the surface.
Fig. 19 -- CoreMax Access Port Assembly
CORE
(Part No. EC39EZ067)
1/2" HEX
45°
DEPRESSOR PER ARI 720
+.01/-.035
FROM FACE OF BODY
7/16-20 UNF RH
C08453
12
PURONR(R--410A) REFRIGERANT
This unit is designed for use with Puron (R--410A)
refrigerant. Do not use any other refrigerant in this
system.
Puron (R --410A) refrigerant is provided in pink (rose)
colored cylinders. These cylinders are available with and
without dip tubes; cylinders with dip tubes will have a
label indicating this feature. For a cylinder with a dip
tube, place the cylinder in the upright position (access
valve at the top) whe n removing liquid refrigerant for
charging. For a cyli nder without a dip tube, invert the
cylinder (access valve on the bottom) when removing
liquid refrigerant.
Because Puron (R--410A) refrigerant is a blend, it is
strongly recommended that refrigerant always be removed
from the cylinder as a liquid. Admit liquid refrigerant into
the system in the discharge line. If adding refrigerant into
the suction line, use a commercial metering/expansion
device at t he gauge manifold; remove liquid from the
cylinder, pass it through the metering device at the gauge
set and then pass it into the suction line as a vapor. Do not
remove Puron (R--410A) refrigerant from the cylinder as a
vapor.
To Use Cooling Charging
Charts
Take the outdoor ambient temperature and read t he
suction pressure gauge. Refer to chart to determine what
suction temperature should be. If suction temperature is
high, add refrigerant. If suction temperature is low,
carefully recover some of the charge. Recheck the suction
pressure as charge is adjusted.
Amount of refrigerant charge is listed on the unit’s
nameplate. Refer to the GTAC2--5 Charging, Recovery,
Recycling and Reclamation training manual and the
following procedures.
Unit panels m ust be in place when unit is operating during
the charging procedure. If unit is equipped with a head
pressure control device, bypass it to ensure full fan
operation during charging.
Charge checking and adjustments must be made while the
system is operating in Cooling only.
Charge
No
Use standard evacuation techniques for Puron (R--410A)
refrigerant.. After evacuating system, weigh in the
specified amount of refrigerant.
Low--Charge
Using Cooli ng Charging Charts, Fig. 20 vary refrigerant
until the conditions of the appropriate chart are met. Note
the charging charts are different from type normally used.
Charts are based on charging the units to the correct
superheat for the various operating conditions. Accurate
pressure gauge and tempera ture sensing device are
required. Connect the pressure gauge to the service port
on the suction line. Mount the temperature sensing device
on the suction line and insulate it so that outdoor ambient
temperature does not affect the reading. Indoor--a ir cfm
must be within the normal operating range of the unit.
Cooling
Lubrication
Compressors are charged with the correct amount of oil at
the factory.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to
components.
The compressor is in a PuronR refrigerant system and
uses a polyolester (POE) oil. This oil is extremely
hygroscopic, meaning it absorbs water readily. POE
oils can absorb 15 times as much water as other oils
designed for HCFC and CFC refrigerants. Avoid
exposure of the oil to the atmosphere.
Replacing Compressor
The compressor used with Puron refrigerant contains a
POE oil. This oil has a high affinity for moisture. Do not
remove the compressor’s tube plugs until ready to insert
the unit suction and discharge tube ends.
Compressor mounting bolt torque is 65--75 in--lbs (7.3--8.5
Nm).
Failure to follow this caution may result in personal
injury.
On 3--phase units with scroll compressors, it is important
to be certain compressor is rotating in the proper
direction. To determine whether or not compressor is
rotating in the proper direction:
1. Connect service gauges to suction and discharge pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start--up.
NOTE: If the suction pressure does not drop and the
discharge pressure doe s not rise to normal levels:
4. Note that the evaporator fan is probably also rotating
in the wrong direction.
5. Turn off power to the unit.
6. Reverse any two of the unit power leads.
7. Reapply power to the compressor.
The suction and discharge pressure levels should now
move to their normal start--up levels.
NOTE: When the compressor is rotating in the wrong
direction, the unit makes an elevated level of noise and
does not provide cooling.
Replace whenever refrigerant system is exposed to
atmosphere. Only use factory specified liquid--line filter
driers with working pressures no less than 650 psig. Do
not install a suction--line filter drier in liquid line. A
liquid--line filter drier designed for use with Puron
refrigerant is required on every unit.
Outdoor Fan Location
See Fig. 21.
1. Shut off unit power supply. Install lockout tag.
2. Remove condenser --fan assembly (grille, motor, and
fan).
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 21.
5. Tighten setscrews to 84 in--lbs (9.5 Nm).
6. Replace condenser--fan assembly.
Conduit
0.14 in + 0.0 / -0.03
C08448
Fig. 21 -- Outdoor Fan Adjustment
Troubleshooting Cooling System
Refer to Table 6 for additional troubleshooting topics.
548J
17
PROBLEMCAUSEREMEDY
Compressor an d
Outdoor Fan
Will Not Start.
Compressor Will Not
Start But Outdoor
Fan Runs.
548J
Compressor Cycles
(Other Than
Normally Satisfying
Thermostat).
Compressor Operates
Continuously.
Compressor Makes
Excessive Noise.
Excessive Head
Pressure.
Head Pressure
Too L ow.
Excessive Suction
Pressure.
Suction Pressure
Too L ow.
Tabl e 6 – Heating and Cooling Troubleshooting
Power failure.Call power company.
Fuse blown or circuit breaker tripped.Replace fuse or reset circuit breaker. Determine root cause.
Defective thermostat, contactor, transformer,
control relay, or capacitor.
Insufficient line voltage.Determine cause and correct.
Incorrect or faulty wiring.Check wiring diagram and rewire correctly.
Thermostat setting too high.Lower thermostat setting below room temperature.
High pressure switch tripped.See problem ‘‘Excessive head pressure.’’
Low pressure switch tripped.Check system for leaks. Repair as necessary.
Freeze-up protection thermostat tripped.See problem ‘‘Suction pressure too low.’’
Fault y wiring or loose connections in compressor
circuit.
Compressor motor burned out, seized, or
internal overload open.
Outdoor fan motor(s) not operating (heating).Check fan motor operation.
Replace component.
Check wiring and repair or replace.
Determine cause. Replace compressor or allow enough time for
internal overload to cool and reset.
Determine cause and replace compressor.
Determine cause and replace.
Replace.
Start-Up.
18
CONVENIENCE OUTLETS
!
WARNING
Mount the weatherproof cover to the backing plate as
shown in Fig. 23. Remove two slot fillers in the bottom of
the cover to permit servi ce tool cords to exit the cover.
Check for full closing and latching.
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience out let circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Tag--out this switch, if necessary.
Tw o types of convenience outlets are offered on 548J
models: Non--poweredand unit--powered.Both types
provide a 125--volt GFCI (ground--fault circuit--interrupter)
duplex receptacle rated at 15--A behind a hinged waterproof
access cover, located on the end panel of the unit. See
Fig. 22.
Pwd-CO
Convenience
Outlet
GFCI
Pwd-CO
Fuse
Switch
Transformer
COVER – WHILE-IN-USE
WEATHERPROOF
RECEPTACLE
NOT INCLUDED
BASE PLATE FOR
GFCI RECEPTACLE
C09022
Fig. 23 -- Weatherproof Cover Installation
Non--powered type: Thistyperequiresthe field
installation of a general--purpose 125--volt 15--A circuit
powered from a source elsewhere in the building. Observe
national and local codes when selecting wire size, fuse or
breaker requirements and disconnect switch size and
location. Route 125--v power supply conductors into the
bottom of the utility box containing the duplex receptacle.
548J
Control Box
Access Panel
C08128
Fig. 22 -- Convenience Outlet Location
Installing Weatherproof Cover –
Aweatherproofwhile-in-usecoverforthe
factory-installed convenience outlets is now required by
UL standards. This cover cannot be factory-mounted due
its depth; it must be installed at unit installation. For
shipment, the convenience outlet is covere d with a blank
cover plate.
The weatherproof cover kit is shipped in the unit’s control
box. The kit includes the hinged cover, a backing plate
and gasket.
DISCONNECTALLPOWERTOUNITAND
CONVENIENCE OUTLET.
Remove the blank cover plate at the conveni ence out let;
discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until
1
approximately
/2-in (13 mm) under screw heads are
exposed. Press the gasket over the screw heads. Slip the
backing plate over the screw heads at the keyhole slots
and align with the gasket; tighten the two screws until
snug (do not over-tighten).
Unit--powered type: A unit--mounted transformer is
factory--installed to stepdown the main power supply
voltage to the unit to 115--v at the duplex receptacle. This
option also includes a manual switch with fuse, located in
a utility box and mounted on a bracket behind the
convenience outlet; access is through the unit’s control
box access panel. See Fig. 22.
The primary leads to the convenience outlet transformer
are not factory--connected. Selection of primary power
source is a customer--option. If local codes permit, the
transformer primary leads can be connected at the
line--side terminals on the unit--mounted non--fused
disconnect or HACR breaker switch; this will provide
service power to the unit when t he unit disconnect switch
or HACR switch is open. Other connection methods will
result in the convenience outlet circuit being de--energized
when the unit disconnect or HACR switch is open. See
Fig. 24.
Duty Cycle: the unit--powered convenience outlet has a
duty cycle limitation. The transformer is intended to
provide power on an intermittent basis for service tools,
lamps, etc; it is not intended to provide 15--amps loading
for continuous duty loads (such as electric heaters for
overnight use). Observe a 50% limit on circuit loading
above 8--amps (i.e., limit loads exceeding 8--amps to 30
minutes of operation every hour).
Test the GFCI receptacle by pressing the TEST button on
the face of the receptacle to trip and open the receptacle.
Check for proper grounding wires a nd power line phasing
19
if the GFCI receptacle does not trip as required. Press the
RESET button to clear the tripped condit ion.
548J
UNIT
VOLTAGE
208,
230
460480
575600
CONNECT
AS
240
PRIMARY
CONNECTIONS
L1: RED +YEL
L2: BLU + GRA
L1: RED
Splice BLU + YEL
L2: GRA
L1: RED
L2: GRA
TRANSFORMER
TERMINALS
H1 + H3
H2 + H4
H2 + H3
Terminals are clearly marked on the board surface. See
Fig 25.
The CTB contains no software and no logic. But it does
include seven configuration jumpers that are cut to
configure the board to read external optional and
accessory controls, including that the unit is a heat pump.
CO8283
H1
H4
H1
H2
Fig. 24 -- Powered Convenience Outlet Wiring
Maintenance: Periodically test the GFCI receptacle by
pressing the TEST button on the face of the receptacle.
This should cause the internal circuit of the receptacle to
trip and open the receptacle. Check for proper grounding
wires and power line phasing if the GFCI receptacle does
not trip as required. Press the RESET button to clear the
tripped condition.
Fuse on powered type: The factory fuse is a Bussman
“Fusetron” T--15, non--renewable screw--in (Edison base)
type plug fuse.
Using unit--mounted convenience outlets: Units with
unit--mounted convenience outlet circuits will often
require that two disconnects be opened to de--energize all
power to the unit. Treat all units as electrically energized
until the convenience outlet power is al so checked and
de--energization is confirmed. Observe National Electrical
Code Article 210, Branch Circuits, for use of convenience
outlets.
HEAT PUMP CONTROLS
Controls Terminal Board
The Controls Terminal Board (CTB) is a large printed
circuit board that is located in the center of the unit
control box. This printed circuit board contains multiple
termination strips and connectors to simplify factory
control boxwiring and field controlconnections.
Jumpers JMP5, JMP6 and JMP7 are located in notches
across the top of the CTB (see Fig. 25 ). These jumpers
are factory cut on all heat pump units. Visually check
these jumpers to confirm that they have been cut.
PROTECTIVE CONTROLS
Compressor Protection
Overcurrent
The compressor has internal linebreak motor protection.
20
Overtemperature
The compressor has an internal protec tor to protect it
against excessively high discharge gas temperatures.
High Pressure
Switch
The system is provided with a high pressure switch
mountedonthedischargeline.Theswitchis
stem--mounted and brazed into the discharge tube. Trip
setting is 630 psig +/-- 10 psig (4344 +/-- 69 kPa) when
hot. Reset is automatic at 505 psig (3482 kPa).
Loss of Charge
Switch
The system is protected against a loss of charge and low
evaporator coil loading condition by a loss of charge
switch located on the liquid line and a freeze protection
thermostatontheindoorcoil .Theswitchis
stem--mounted. Loss of Charge Switch trip setting is
27 psig +/-- 3 psig (186 +/-- 21 kPa). Re set is automatic at
44 +/-- 3 psig (303 +/-- 21 kPa).
Freeze Protection Thermostat trip setting is 30_F+/--5_F
(-- 1_C+/--3_C). Reset is automatic at 45_F+/--5_F(7_C
+/--3_C).
Supply (Indoor) Fan Motor Protection
Disconnect and lockout power when servicing fan motor.
2.9and3.7 bhpmotorsareequippedwithan
overtemperature or protection device. The type of devi ce
depends on the motor size. See Table 8.
Table 8 – Overload Device per Motor Size
Motor Size (bhp)Overload DeviceReset
1.7Internal LinebreakAutomatic
2.4Internal LinebreakAutomatic
2.9ThermixAutomatic
3.7ThermixAutomatic
4.7
External
(Circuit Breaker)
Manual
Troubleshooting supply fan m otor overload trips: The
supply fan used in 548J units is a forward--c urved
centrifugal wheel. At a constant wheel speed, this wheel
had a characteristic that causes the fan shaft load to
DECREASE when the static pressure in the unit--duct
system increases and to INCREASE when the static
pressure in the unit--duct system decreases (and fan
airflowrateincreases).Motor overloadconditions
typically develop when the unit is operated with an access
panel removed, with unfinished duct work, in an
economizer--open mode, or a leak de velops in the duct
system that allows a bypass back to unit return opening.
Outdoor Fan Motor Protection
The outdoor fan motor is internally protected against
overtemperature.
Control Circuit, 24--V
548J
The control circuit is protected against overcurrent
conditions by a circuit breaker mounted on control
transformer TRAN. Reset is manual.
COMMERCIAL DEFROST CONTROL
TheCommercialDefrostControlBoard(DFB)
coordinates thermostat demands for supply fan control, 1
or 2 stage cooling, 2 stage heating, emergency heating and
defrost control with unit operating sequences. The DFB
also provides an indoor fan off delay feature (user
selectable). See Fig. 26 for board arrangement.
The High Static option supply fan motor is equipped with
a pilot--circuit Thermix combination overtemperature/
overcurrentprotectiondevice.Thisdeviceresets
automatically. Do not bypass this switch to correct
trouble. Determine the cause and correct it.
The Thermix device is a snap--action overtemperature
protection device that is imbedded in the m otor windings.
It is a pilot--circuit device that is wired into the unit’s 24–v
control circuit. When this switch reaches its trip setpoint,
it opens the 24–v control circuit and causes all unit
operation to cease. This device resets automatically when
the motor windings cool. Do not bypass this switch to
correct trouble. Determine the cause and correct it.
TheExternalmotoroverloaddeviceisa
specially--calibrated circuit breaker that is UL recognized
as a motor overload controller. It is an overcurrent device.
When the motor current exceeds the circuit breaker
setpoint, the device opens all motor power le ads and the
motor shuts down. Reset requires a manual reset at the
overload switch. This device (designated IFCB) is located
on the side of the supply fan housing, behind the fan
access panel.
DIP
Switches
Speed-Up
Jumpers
C09275
Fig. 26 -- Defrost Control Board (DFB) Arrangement
The DFB is located in the 548J’s main control box (see
Fig. 27). All connections are factory--made through
harnesses to the unit’s CTB, to IFC (belt--drive mot or) or
to ECM (direct--drive motor), reversing valve solenoids
and to defrost thermostats. Refer to Table 9 for details of
DFB Inputsand Outputs.Detailed unitoperating
sequences are provided in the Operating Sequences
section starting on page 62.
21
548J
C09276
Fig. 27 -- Defrost Control Board (DFB) Location
Table 9 – 548J Defrost Board I/O and Jumper Configurations
Inputs
Point NameType of I/ OConnection Pin NumberUnit ConnectionNote
GFanD I , 2 4 --- v acP 2 --- 3LC T B --- G
Y1 Cool 1D I , 2 4 --- v acP 2 --- 5LC TB --- Y 1
Y2 Cool 2D I , 2 4 --- v acP 2 --- 4LC TB --- Y 2
W1 Heat 1D I , 2 4 --- v acP 2 --- 7L C T B --- W 1
W2 Heat 2D I , 2 4 --- v acP 2 --- 6L C T B --- W 2
RPower2 4 --- v acP 3 --- 1C O N T L B R D --- 8
C Common2 4 --- v acP 3 --- 2C O N T L B R D --- 4
DFT1D I , 2 4 --- v a cD F T --- 1 t o D F T --- 1
DFT 2D I , 2 4 --- v a cD F T --- 2 t o D F T --- 2
Outputs
Point NameType of I/ OConnection Pin NumberUnit ConnectionNote
IFO Fan OnD O , 2 4 --- v a cP 3 --- 9R E H E AT --- 2
OF OD Fan OnDO , 2 4 --- v a cOFOFR
RVS1DO , 2 4 --- v a cP 3 --- 7 t o P 3 --- 5Energize in COOL
RVS2DO , 2 4 --- v a cP 3 --- 6 t o P 3 --- 4Energize in COOL
COMP 1DO , 2 4 --- v acP 3 --- 1 0FP T --- R E H E A T --- 6
COMP 2DO , 2 4 --- v acP 3 --- 8R E H E AT --- 8
HEAT 2D O , 2 4 --- v acE --- H E A THC --- 1 ( T B 4 --- 1 )
COM2 4 --- v acP 3 --- 3H C --- 1 ( T B 4 --- 3 )
Configuration
Point NameType of I/ OConnection Pin NumberUnit ConnectionNote
Select Jumper2 4 --- v acP 1 --- 1
2 Compressor2 4 --- v acP 1 --- 3Use for 548J***D
Speed--Up Configuration
Point NameType of I/ OConnection Pin NumberUnit ConnectionNote
Speed---Up JumperJMP17
Speed---Up JumperJMP18
Jumper for 1--3 secs: Factory Test, defrost runs for 9 secs
Jumper for 5--20 secs: Forced Defrost, defrost runs for 30 secs if DFT2 is open
Reversing valve control — The DFB has two outputs for
unit reversing val ve control. Operation of the reversing
valves is based on internal logic; this application does not
use an “O” or “B” signal to determine reversing valve
position. Re versing valves are energized during the
Cooling stages and de--energized during Heating cycles.
Once energized at the start of a Cooling stage, the
reversing valve will remain energized until the next
Heating cycle demand is received. Once de--energized at
the start of a Heating cycle, the reversing valves will
remain de -- energized until the next Cooling stage is
initiated.
Compressor control—The DFBreceives inputs
indicating Stage 1 Cooling, Stage 2 Cooling (sizes 08 and
09 only) and Stage 1 Heati ng from the space thermostat or
unit control system (RTU--MP); it generates commands to
start compressors with or withoutreversing valve
operation to produce Stage 1 Cooling (one compressor),
Stage 2 Cooling (both compressors run) or Stage 1
Heating (both compressors run).
22
Auxiliary (Electric) Heat control — The 548J unit can be
equipped with one or two auxiliary electric heaters, to
provide a second stage of Heating. The DFB will energize
this Heating system for a Stage 2 Heating command
(heaters operate concurrently with both compressors in the
Stage 2 Heating cycle), for an Emergency Heating
sequence (compressors are off and only the electric
heaters are energized) and also during the Defrost cycle
(to eliminate a “cold blow” condition in the space).
Defrost — The defrost control mode is a time/temperature
sequence.Therearetwotimecomponents:The
continuous run period and the test/defrost cycle period.
The temperature component is provided by the defrost
thermostat(s) (DFT1 and DFT2 (08--09 only) mounted on
the outdoor coil.
still open, the defrost test/run window is closed and the
control repeats the continuous run period. If DFT2 is
closed, the defrost cycle is initiated in Circuit 2. The
defrost period will end when DFT2 opens (indicating the
outdoor coil has been cleared of frost and ice) or a 10
minute elapsed period expires, whic hever comes first.
On sizes 08--09, Circuit 1’s defrost ther mostat DFT1
(located on the upper circuit of the outdoor coil) cannot
initiate a unit defrost cycle; only DFT2 may do this. But
once Circuit 2 is in defrost, the DFB will monitor the
status of DFT1. If DFT1 closes during a Circuit 2 defrost
cycle, Circuit 1 will also enter a defrost cycle. Circuit 1’s
defrost cycle will end when DFT1 opens (indicating the
upper portion of the outdoor coil is cleared of frost and
ice) or the Circuit 2 defrost cycle is terminated.
The continuous run period is a fixed time period between
the end of the last defrost cycle (or start of the current
Heating cycle) during which no defrost will be permitted.
This period can be set at 30, 60, 90 or 120 minutes by
changing the positions of DIP switches SW1 and SW2
(see Fig. 28 and Table 10). The default run periods are 30
minutes for unit sizes 04--07 and 90 minutes for unit sizes
08--09.
C09283
Fig. 28 -- DIP Switch Settings — Defrost Board
At the end of the continuous run period, the defrost
control will test for a need to defrost. On unit sizes 04--07
(single compressor designs), DFT1 controls the start and
termination of the defrost cycle. If DFT1 is still open, the
defrost test/run window is closed and the control repeats
the continuous run period. If DFT1 is closed, the defrost
cycle is initiated. The defrost period will end when DFT1
opens (indicating the outdoor coil has been cleared of
frost and ice) or a 10 minute elapsed period expires,
whichever comes first.
On unit sizes 08 and 09 (two circuit designs), DFT2
(located on the bottom circuit of the outdoor coil) controls
the start and termination of the defrost cycle. If DFT2 is
At the end of the unit defrost cycle, t he unit will be
returned to Heating cycle for a full continuous run period.
If the space heating load is satisfied and compressor
operation is terminated, the defrost control will remember
where the run period was interrupted. On restart in
Heating, the defrost control will resume unit operation at
the point in the run period where it was last operat ing.
Defrost Thermostats — These are temperature switches
that monitor the surface temperature of the outdoor coil
circuits. These switches a re mounted on the liquid tube
exiting the outdoor coil heating circuits. These switches
close on temperature drop at 30_F(--1_C) and reset open
on temperature rise at 80_F(27_C).
Indoor Fan Off Delay — The DFB can provide a 30 sec
delay on Indoor Fan Off if the thermostat’s fan selector
switch is set on AUTO control. DIP Switch SW3 on the
DFB selects use of the fan off time delay feature. Setting
SW3 in the OPEN position turns the Fan Off Delay
feature on; setting SW3 in the CLOSED position disables
this feature. The delay period begins when Y1 demand or
W1 demand by the space thermostat is removed.
Defrost Speedup Functions — The DFB permits the
servicer to speed--up the defrost cycle. There are two
speed--up sequences: relative speed--up and an immediate
forced defrost. Speed-- up sequences are initiated by
shorting jumper wires JMP17 and JMP18 together (see
Fig. 26); use a straight--edge screwdriver.
Shorting the jumpers for a period of 1 to 3 secs reduces
the defrost timer periods by a factor of 0.1 sec/minute.
(For example, the 90 min run period is reduced to 9 secs.)
The DFB will step the unit t hrough a Heating cycle and a
Defrost cycle using these reduced time periods. This mode
ends after the Defrost cycle.
548J
Table 10 – Dip Switch Position
Switch No.
121212123
1
0JJ0J0J00JOff
90 minutes
1J1J1JJ1On
60 minutes30 minutes120 minutesFan Delay
23
Shorting the jumpers for a period of 5 to 20 secs bypasses
the remaining continuous run period and places the unit in
a Forced Defrost mode. If the controlling DFT is closed
when this mode is initiated, the unit will complete a
normal defrost period that will terminate when the
controlling DFT opens or the 10 minute defrost cycle limit
is reached. If the controlling DFT is open when this mode
is initiated, the Defrost cycle will run for 30 secs. Both
modes end at the end of the Defrost cycle.
ELECTRIC HEATERS
548J units may be equipped with field--installed accessory
electric heaters. The heaters are modular in design, with
heater frames holding open coil resistance wires strung
through ceramic insulators, line--break limit switches and
a control contact or. One or two heater modules may be
used in a unit.
548J
DISCONNECT MOUNTING
LOCATION
Unit heaters are marked with Heater Model Numbers. But
heaters are ordered as and shipped in cartons marked with
a corresponding heater Sale s Package part number. See
Table 11 for correlation between heater Model Number
and Sales Package part number.
NOTE: The value in position 9 of the part number differs
between the sales package part number (value is 1) and a
bare heater model number (value is 0).
Heater modules are installed in the compa r tment below
the indoor (supply) fan outlet. Access is through the
indoor access panel. Heater modules slide into the
compartment on tracks along the bottom of the heater
opening. See Fig. 29, Fig. 30 and Fig. 31.
Not all available heater modules may be used in every
unit. Use only those heater modules that are UL listed for
use in a specific size unit. Refe r to t he label on the unit
cabinet re approved heaters.
Fig. 31 -- T ypical Module Installation
Table 11 – Heater Model Number
Bare Heater Model NumberCRHEATER001A00
Heater Sales Package PNO
Includes:
Bare Heater
Carton and packing materials
Installation sheet
CRHEATER101A00
TRACK
FLANGE
C08135
24
Single Point Boxes and Supplementary Fuses — When
the unit MOCP device value exceeds 60--A, unit--mounted
supplementary fuses are required for each heater circuit.
These fuses are included in accessory Single Point Boxes,
with power distribution and fuse blocks. The single point
box will be installed directly under the unit control box,
just to the left of the partition separating the indoor
section (with electric heaters) from the outdoor section.
The Single Point Box has a hinged access cover. See
Fig. 32.
CONTROL
BOX
BUSHING
SINGLE
POINT BOX
MOUNTING
SCREWS
DRIP BOOT
BRACKET
MOUNTING
SCREWS
POWER
WIRES
FOAM
BUSHING
HEATER
RELAYS
HEATER
MOUNTING
SCREWS
2
1
1
1
2
13
3
21
23
11
13
A
L
LIE
D
P
A
C
O
R
P
.
MO
DE
L
N
O
.
O
D
ERI
A
L
N
O.
2
2
.
2
ISTED
AIR
NDITIONING
1
2
3
UIP
ACCESS
346N
.
3
P
/ N
2-
5
6
1
REV
0
4
C08136
Fig. 32 -- Typical Single Point Installation
On 548J units, all fuses are 60--A. Single point boxes
containing fuses for 208/230--V applications use UL Class
RK5 250--V fuses (Bussman FRNR 60 or Shawmut TR
60R). Singlepoint boxes for460--V and575--V
applications use UL Class T 600--V fuses (Bussman JJS
60 or Shawmut A6T 60). (Note that all heaters are
qualified for use with a 60--A fuse, regardless of actual
heater ampacity, so only 60--A fuses are necessary.)
Unit heater applications not requiring supplemental fuses
require a special Single Point Box without any fuses.
Connect power supply conductors to heater conductors
and field--supplied base unit power tap leads (see text
below re: “Completing Heater Installati on”) inside the
empty Single Point Box using UL--approved connec tors.
Safety Devices — Electric heater applications use a
combination of line-- break/auto--reset limit switches and a
pilot--circuit/manual reset limit switch to protect the unit
against over--temperature situations.
Line--break/auto-- reset limit switches are mounted on the
base plate of each heater module. See Fig. 33. These are
accessed through the indoor access panel. Remove the
switch by removing two screws into the base plate and
extracting the existing switch.
Pilot--circuit/manual reset limit switch is located in the
side plate of the indoor (supply) fan housing. See Fig. 30.
Completing Heater Installation
Field Power Connections — Tap conductors must be
installed between the base unit’s field power connection
lugs and the Single Point Box (with or without fuses).
Refer to unit wiring schematic. Use copper wire only. For
connection using the Single Point Box less fuses, connect
the field power supply conductors to the heater power
leads and the field--supplied tap conductors inside the
Single Point Box. Use UL--approved pressure connectors
(field--supplied) for these splice joints.
Line-Break
Limit Switches
21
23
11
13
ALLIED P
A
MODE
L
NO.
OD
ERIAL
NO.
ISTED
AIR
NDITIONING
1
2
3
U
I
P
ACCESS
34
6
N
.
3
P
/ N
2
-
5610-4
RE
V
C08330
Fig. 33 -- Typical Location of Heater Limit Switches
(3--phase heater shown)
Low--VoltageControlConnections—Pullthe
low--voltage control leads from the heater module(s) -VIO and BRN (two of each if two modules are installed;
identify for Module #1) -- to the 4--pole terminal board
TB4 located on the heater bulkhead to the left of Heater
#1. Connect the VIO lead from Heater #1 to terminal
TB4--1. Connect the VIO lead from Heater #2 to terminal
TB4--2. Connect both BRN leads to terminal TB4--3. See
Fig. 34.
DEFROST
BOARD
E-HEAT
P3-3
ORN
BRN
ORNBRN
TB4
Field
Connections
13
VIOBRN BRN
VIO
Elec Htr
VIOHR2
VIOBRN
BRN
HR1
HR1: On Heater 1 in Position #1
HR2: On Heater 2 in Position #2 (if installed)
C09013
Fig. 34 -- Accessory Electric Heater Control
Connections
548J
25
SMOKE DETECTORS
Sensor
Smoke detectors are a vailable as factory-- installed options
on 548J models. Smoke detectors may be specified for
Supply Air only or for Return Air without or with
economizer or in combination of Supply Air and Return
Air. Return Air smoke detectors are arranged for vertical
return configurations only. All compone nts necessary for
operation are fa ctory--provided and mounted. The unit is
factory--configuredforimmediatesmokedetector
shutdown operation; additional wiring or modificati ons to
unit terminal board may be necessary to complete the unit
and smoke detector configuration to meet project
requirements.
System
The smoke detector system consists of a four-- wire
controller and one or two sensors. Its primary function is
548J
to shut down the rooftop unit in order to prevent smoke
from circulating throughout the building. It is not to be
used as a life saving device.
Controller
The controller (see Fig. 35) includes a controller housing,
a printed circuit board, and a clear plastic cover. The
controller can be connected to one or two compatible duct
smoke sensors. The clear plastic cover is secured to the
housing with a single captive screw for easy access to the
wiring terminals. The controller has three LEDs (for
Power, Trouble and Alarm) and a manual test/reset button
(on the cover face).
The sensor (see Fig. 36) includes a pla stic housing, a
printed circuit board, a clear plastic cover, a sampling
tube inlet and an exhaust tube. The sampling tube (when
used) and exhaust tube are attached during installation.
The sampling tube varies in length depending on the size
of the rooftop unit. The clear plastic cover permits visual
inspections without ha ving to disassemble the sensor. The
cover attaches to the sensor housing using four captive
screws and forms an airtight cham ber around the sensing
electronics. Each sensor includes a harness with an RJ45
terminal for connecting to the controller. Each sensor has
four LEDs (for Power, Trouble, Alarm and Dirty) and a
manual test/reset button (on the left--side of the housing).
Duct smoke sensor
Exhaust tube
See
Detail A
Intake
gasket
Plug
TSD-CO2
(ordering option)
Sampling tube
(ordered separately)
Exhaust gasket
Sensor housing
and electr onics
Cover gasket
(ordering option)
Sensor cover
Controll er housing
and electronics
Conduit c ouplings
(supplie d by installer)
Duct smoke sensor
controller
Conduit nuts
(supplie d by installer)
Conduit s upport plate
Terminal block cover
Fastener
(2X)
Alarm
Troub le
Power
Tes t / r e s e t
switch
Fig. 35 -- Controller Assembly
Cover gasket
(ordering option)
Controll er cover
C08208
Magnetic
test/reset
switch
Coupling
Alarm
Troub le
Power
Dirty
C08209
Detail A
Fig. 36 -- Smoke Detector Sensor
Air is introduced to the duct smoke detector sensor’s
sensing chamber through a sampling tube that extends into
the HVAC duct and is directed back into the ventilation
system through a (shorter) exhaust tube. The difference in
air pressure between the two tubes pulls the sampled air
through the sensing chamber. When a sufficient amount of
smoke is detected in the sensing chamber, the sensor
signals an alarm state and the controller automatically
takes the appropriate action to shut down fans and
blowers, change over air handling systems, notify the fire
alarm control panel, etc.
The sensor uses a process called differential sensing to
prevent gradual environmental changes from triggering
false alarms. A rapid change in environmental conditions,
26
such as smoke from a fire, causes the sensor to signal an
alarm state but dust and debris accumulated over time
does not.
For installations using two sensors, the duct smoke
detector does not differentiate which sensor signals an
alarm or trouble condition.
Smoke Detector Locations
Supply Air — The Supply Air smoke detector sensor is
located to the left of the unit’s indoor (supply) fan. See
Fig. 37. Access is through the fan access panel. There is
no sampling tube used at this location. The sampling tube
inlet extends through the side plat e of the fan housing
(into a high pressure area). The controller is located on a
bracket to the right of the return filter, accessed through
the lift--off filter panel.
Return Air with Economizer — The sampling tube is
inserted through the side plates of the economizer
housing, placing it across the return air opening on the
unit basepan. See Fig. 39. The holes in the sampling tube
face downward, into the return air stream. The sampling
tube is connected via tubing t o the return a ir sensor that is
mounted on a bracket high on the partition between return
filter and controller location. (This sensor is shipped in a
flat--mounting location. Installation requires that this
sensor be re located to its operating location and the tubing
to the sampling tube be connected. See “Completing
Installation of Return Air Smoke Sensor” for installation
steps.)
548J
Return Air
Sampling Tube
Smoke Detector Sensor
C08245
Fig. 37 -- T ypical Supply Air Smoke Detector Sensor
Location
Return Air without Economizer — The sampling tube is
located across the return air opening on the unit basepan.
See Fig. 38. The holes in the sampling tube face
downward, into the return air stream. The sampling tube is
connected via tubing to the return air sensor that is
mounted on a bracket high on the partition between return
filter and controller location. (This sensor is shipped in a
flat--mounting location. Installation requires that this
sensor be re located to its operating location and the tubing
to the sampling tube be connected. See “Completing
Installation of Return Air Smoke Sensor” for installation
steps.)
Return Air Detector module
(shipping position shown)*
Controller module
Return Air Detector Sampling Tube
*RA detector must be moved from shipping position to operating position by installer
C07307
Fig. 38 -- Typical Return Air Detector Location
C08129
Fig. 39 -- Return Air Sampling Tube Location
Completing Installation of Return Air Smoke
Sensor:
SCREWS
EXHAUST
TUBE
FLEXIBLE
EXTENSION
TUBE
SAMPLING
C08126
Fig. 40 -- Return Air Detector Shipping Position
1. Unscrew the two screws holding the Return Air
Sensor detector plate. See Fig. 40. Save the screws.
2. Remove the Return Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing outwards and t he sampling tube connecti on is on the bottom. See Fig. 41.
4. Screw the sensor and detector plate into its operating
position using screws from Step 1. Make sure the
sampling tube connection is on the bot tom and the exhaust tube is on the top. See Fig. 41.
5. Connect the flexible tube on the sampling inlet to the
sampling tube on the basepan.
27
6. For units with an economizer, the sampling tube is integrated into the economizer housing but the connection of the flexible tubing to the sampling tube is the
same.
548J
Fig. 41 -- Return Air Sensor Operating Position
FIOP Smoke Detector Wiring and Response
All units: FIOP smokedetector is configured to
automatically shut down all unit ope rations when smoke
condition is detected. See Fig. 42, Typical Smoke
Detector System Wiring.
Highlight A: JMP 3 is factory--cut, transferring unit
control to smoke detector.
C08127
Highlight B: Smoke detector NC contact set will open on
smokeal armcondition,de--energizingtheORN
conductor.
Highlight C: 24--v power signal via ORN lead is removed
at Smoke Detector input on CTB (Control Terminal
Board); all unit operations cease immediately.
Highlight D: On smoke alarm condition, the smoke
detector NO Alarm contact will close, supplying 24 --v
power to GRA conductor.
Highlight E: GRA lead at Smoke Alarm input on CTB
provides 24--v signal to FIOP DDC control.
RTU--MP: The 24--v signal is conveyed to RTU--MP’s
J1--10 input terminal. This signal initiates the FSD
sequence by the RTU--MP control. FSD status is reported
to connected BAS network.
Using Remote Logic: Five conductors are provided for
field use (see Highlight F in Fig. 42) for additional
annunciation functions.
Additional Application Data — Refer to Cat alog No.
HKRNKA--1XA for discussions on additional control
features of these smoke detectors including multiple unit
coordination. See Fig. 42.
B
D
C
F
E
A
Fig. 42 -- Typical Smoke Detector System Wiring
28
C08246
Sensor and Controller Tests
Sensor Alarm Test
The sensor alarm test checks a sensor’s ability to signal an
alarm state. This test requires that you use the factory
provided SD--MAG test magnet. The magnet (which is
approximately 1.0 in. long. x
plastic bag in the unit control box.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system,notifytheproperauthoritiesbefore
performing the test.
Sensor Alarm Test Procedure
1. Hold the test magnet where indicated on the side of
the sensor housing for seven seconds.
2. Verify that the sensor’s Alarm LED turns on.
3. Reset the sensor by holding the t est magnet against
the sensor housing for two seconds.
4. Verify that the sensor’s Alarm LED turns off.
1
/4in. sq.) is located in a
Controller Alarm Test
The controller alarm test checks the controller’s ability to
initiate and indicate an a larm state.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
This test places the duct detector into the alarm state.
Disconnect all auxiliary equipment from the controller
before performing the test. If the duct detector is
connected to a fire alarm system, notify the proper
authorities before performing the test.
Controller Alarm Test Procedure
1. Press the controller’s test/reset switch for seven
seconds.
2. Verify that the controller’s Alarm LED turns on.
3. Reset the sensor by pressing the test/reset switch for
two seconds.
4. Verify that the controller’s Alarm LED turns off.
Dirty Controller Test
The dirty controller test checks the controller’s ability to
initiate a dirty sensor test and indicate its results.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
Pressing the controller’s test/reset switch for longer
than seven seconds will put the duct detector i nto the
alarm state and activate all automatic alarm responses.
Dirty Controller Test Procedure
1. Press the controller’s test/reset switch for two
seconds.
2. Verify that the controller’s Trouble LED flashes.
Dirty Sensor Test
The dirty sensor test provides an indication of the sensor ’s
ability to compensate for gradual environmental changes.
A sensor that can no longer compensate for environmental
changes is considered 100% dirty and requires cleaning or
replacing. You must use the factory provided SD--MAG
test magnet to initiate a sensor dirty test. The sensor’s
Dirty LED indicates the results of the dirty test as shown
in Table 12.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
Holding the test magnet against the sensor housing for
more than seven seconds will put the duct detector
into the alarm state and activate all automatic alarm
responses.
Tabl e 12 – D i rty L ED Te st
FLASHESDESCRIPTION
10---25% dirty. (Typical of a newly installed detector)
225- -- 50% dirty
351- -- 75% dirty
476- -- 99% dirty
Dirty Sensor Test Procedure
1. Hold the test magnet where indicated on the side of
the sensor housing for two seconds.
2. Verify that the sensor’s Dirty LED flashes.
548J
29
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
Changing the dirty sensor test operation will put the
detector into the alarm state and activate all automatic
alarm responses. Before changing dirty sensor test
operation, disconnect all auxiliary equipment from the
controller and notify the proper authorities if
connected to a fire alarm system.
Changing the Dirty Sensor Test
By default, sensor dirty test results are indicated by:
S The sensor’s Dirty LED flashing.
S The controller’s Trouble LED fla shing.
548J
S The controller’s supervision relay contacts toggle.
The operation of a sensor’s dirty test can be changed so
that the controller’s supervision relay is not used to
indicate test results. When two detectors are connected to
a controller, sensor dirty test operation on both sensors
must be configured to operate in the same manner.
To Configure the Dirty Sensor Test
Operation
1. Hold the test magnet where indicated on the side of
the sensor housing until the sensor’s Alarm LED turns
on and its Dirty LED flashes twice (approximately 60
seconds).
2. Reset the sensor by removing the test magnet then
holding it against the sensor housing again until the
sensor’s Alarm LED turns off (approximately 2
seconds).
Remote Station Test
The remote station alarm test checks a test/reset station’s
ability to initiate and indicate an alarm state.
!
CAUTION
Remote Test/Reset Station Dirty Sensor Test
The test/reset station dirty sensor test checks the test/reset
station’s ability to initiate a sensor dirty test and indicate
the results. It must be wired to the controller as shown in
Fig. 43 and configured to operate the controller’s
supervision relay. For more information, see “Changing
the Dirty Sensor Test.”
12
1
3
Wire must be
added by installer
TB3
1
2
14
Supervision relay
contacts [3]
13
19
15
2
20
Fig. 43 -- Remote Test/Reset Station Connections
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
If the test/reset station’s key switch is left in the
RESET/TEST position for longer than seven seconds,
the detector will automatically go into the alarm state
and activate all automatic alarm responses.
Smoke Detector Controller
–
Auxiliary
equipment
+
18 Vdc (+)
18 Vdc (
–
)
CRSDTEST001A00
Tro uble
5
Power
4
Alarm
1
Reset/ Test
3
2
C09326
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system,notifytheproperauthoritiesbefore
performing the test.
CRSDTEST001A00 Remote Alarm Test Procedure
1. Turn the key switch to the RESET/TEST position for
seven seconds.
2. Verify that the test/reset station’s Alarm LED turns
on.
3. Reset the sensor by turni ng the key switch to the
RESET/TEST position for two seconds.
4. Verify that the test/reset station’s Alarm LED turns
off.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
Holding the test magnet to the target area for longer
than seven seconds will put the detector into the alarm
state and activate all automatic alarm responses.
Dirty Sensor T est Using an CRSDTEST001A00
1. Turn the key switch to the RESET/TEST position for
two seconds.
2. Verify that the test/reset stat ion’s Trouble LED
flashes.
30
Table 13 – Detector Indicators
CONTROL OR INDICATORDESCRIPTION
Magnetic test/reset switchResets the sensor when it is in the alarm or trouble state. Activates or tests the sensor when it is in
Alarm LEDIndicates the sensor is in the alarm state.
Troub le LE DIndicates the sensor is in the trouble state.
Dirty LEDIndicates the amount of environmental compensation used by the sensor
Power LEDIndicates the sensor is energized.
the normal state.
(flashing continuously = 100%)
Detector Cleaning
Cleaning the Smoke Detector
Clean the duct smoke sensor when the Dirty LED is
flashing continuously or sooner if conditions warrant.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
If the smoke detector is connected to a fire alarm
system, first notify the proper authorities that the
detector is undergoing maintenance then disable the
relevant circuit to avoid generating a false alarm.
1. Disconnect power from the duct de tector then remove
the sensor’s cover. (See Fig. 44. )
2. Using a vacuum cleaner, clean compressed air, or a
soft bristle brush, remove loose dirt and debris from
inside the sensor housing and cover.
Use isopropyl alcohol and a lint--free cloth to remove
dirt and other contaminants from the gasket on the
sensor’s cover.
3. Squeeze the retainer clips on both sides of the optic
housing then lift the housing away from the printed
circuit board.
4. Gently remove dirt and debris from around the optic
plate and inside the optic housing.
5. Replace the optic housing and sensor cover.
6. Connect power to the duct detector then perform a
sensor alarm test.
Sampling
tube
Airow
HVAC duct
Sensor
housing
Optic
plate
Retainer
clip
Optic
housing
Indicators
Normal State
The smoke detector operates in the normal state in the
absence of any trouble conditions and when its sensing
chamber is fre e of smoke. In the normal state, the Power
LED on both the sensor and the controller are on and all
other LEDs are off.
Alarm
The smoke detector enters the alarm state when the
amount of smoke particulate in the sensor’s sensing
chamber exceeds the alarm threshold value. (See
Table 13.) Upon entering the alarm state:
The SuperDuct duct smoke de tector enters the trouble
state under the following conditions:
An internal sensor fault is detected upon entering the
trouble state:
State
S The sensor’s Alarm LED and the controller’s Alarm
LED turn on.
S The contacts on the controller’s two auxiliary relays
switch positions.
S The contacts on the controller’s alarm initiation relay
close.
S The controller’s remote alarm LED output is a ctivated
(turned on).
S The controller’s high impedance multiple fan shutdown
control line i s pulled to ground Trouble state.
S A sensor’s cover is removed and 20 minutes pass before
it is properly secured.
S A sensor’s environmental compensation limit is reached
(100% dirty).
S A wiring fault between a sensor and the controller is
detected.
S The contacts on the controller’s supervisory relay
switch positions. (See Fig. 45.)
S If a sensor t rouble, the sensor’s Trouble LED and the
controller’s Trouble LED turn on.
S If 100% dirty, the sensor’s Dirty LED turns on and the
controller’s Trouble LED flashes continuously.
S If a wiring fault between a sensor and the controller, the
controller’s Trouble LED turns on but not the sensor’s.
548J
Fig. 44 -- Sensor Cleaning Diagram
C07305
31
Alarm
Fig. 45 -- Controller Assembly
NOTE: All troubles are latched by the duct smoke
detector. The trouble condition must be cleared and then
the duct smoke detector must be reset in order to restore it
to the normal state.
Resetting Alarm and Trouble Condition Trips:
548J
Manual reset is required to restore smoke detector systems
to Normal operation. For installations using two sensors,
the duct smoke detector does not differentiate which
sensor signals an alarm or trouble condition. Check each
sensor for Alarm or Trouble status (indicated by LED).
Clear the condition that has generated the trip at this
sensor. Then reset the sensor by pressing and holding the
reset button (on the side) for 2 seconds. Verify that the
sensor’s Alarm and Trouble L EDs are now off. At the
controller, clea r its Alarm or Trouble state by pressing and
holding the manual reset button (on the front cover) for 2
seconds. Verify that the controller’s Alarm and Trouble
LEDs are now off. Replace all panels.
Troubleshooting
Controller’s Trouble LED is On
1. Check the Trouble LED on each sensor connected to
the controller. If a sensor’s Trouble LED is on, determine the cause and make the necessary repairs.
2. Check the wiring between the sensor and the controller. If wiring is loose or missing, repair or replace as
required.
Tro uble
Power
Test/reset
switch
C07298
Controller’s Trouble LED is
Flashing
1. One or both of the sensors is 100% dirty.
2. Determine which Dirty LED is flashing then clean
that sensor assembly as described in the detector
cleaning section.
Sensor’s Trouble LED is
On
1. Check the sensor’s Dirty LED. If it is flashing, the
sensor is dirty and must be cleaned.
2. Check the sensor’s cover. If it is loose or missing, secure the cover to the sensor housing.
3. Replace sensor assembly.
Sensor’s Power LED is
Off
1. Check the controller’s Power LED. If it is off, determine why the controller does not have power and
make the necessary repairs.
2. Check the wiring between the sensor and the controller. If wiring is loose or missing, repair or replace as
required.
Controller’s Power LED is
Off
1. Make sure the circui t supplying power to the controller is operational. If not, make sure JP2 and JP3 are
set correctly on the controller before applying power.
2. Verify that powe r is applied to the controller’s supply
input terminals. If power is not present, replace or repair wiring as required.
Remote Test/Reset Station’s Trouble LED Does
Not
flash When Performing a Dirty Test, But the Contr
ler’s Trouble LED
Does
1. Verify that the remote test/station is wired as shown
in Fig. 43. Repair or replace loose or missing wiring.
2. Configure the sensor dirty test to activate the controller’s supervision relay. See “To Configure the Dirty
Sensor Test Operation” for details.
Sensor’s Trouble LED is On, But the Controller’
Tr ouble LED is
OFF
s
Remove JP1 on the controller.
ol-
32
RTU--MP CONTROL SYSTEM
The RTU--MP controller, see Fig. 46, provides expanded
stand--aloneoperationoftheHVACsystemplus
connection and control through communication with
several Building Automation Systems (BAS) through
popular third--party network systems. The available
network systems are BACnet MP/TP, Modbus and
Johnson J2. Communication with LonWorks is also
possible by adding an accessory interface card to the
RTU--MP. Selection of the communication protocol and
baud rate are made at on--board DIP switches.
Bryant’s diagnostic display tools BACviewer6 Handheld
and Virtual BACview (loaded on a portable PC) must be
used with the RTU--MP controller. Connection to the
RTU--MP board is at the J12 access port, see Fig. 46.
The RTU--MP control is factory--mounted in the 548J
unit’s main control box, to the left of the CTB. See Fig. 47
(or Fig. 48). Factory wiring is complet ed through
harnesses connected to the CTB. Field connections for
RTU--MP sensors will be made at the Phoenix connectors
on the RTU--MP board. The factory--installed RTU--MP
control includes the supply--air temperature (SAT) sensor.
The outdoor air temperature (OAT) sensor is included in
the FIOP/accessory EconoMi$er 2 package.
Refer to Table 14, RTU--MP Controller Inputs and Outputs
for locations of al l connections to the RTU--MP board.
548J
Fig. 46 -- RTU--MP Multi--Protocol Control Board
33
C07129
548J
C099015
34
Fig. 47 -- RTU--MP System Control Wiring Diagram – 548J*04A — 548J*07A Units
C099025
548J
35
Fig. 48 -- RTU--MP System Control Wiring Diagram – 548J*08D & 548J*09D Units
Table 14 – RTU--MP Controller Inputs and Outputs
POINT NAME
Space Temperature SensorsptsensAI (10K Thermistor)J2 0 --- 1 , 2
Supply Air TemperaturesatAI (10K Thermistor)J 2 --- 1 , 2
Local Outside Air Temperature SensoroatsensAI (10K Thermistor)J 2 --- 3 , 4
Space Temperature Offset PotsptopotAI (100K Potentiometer)J 20 --- 3
Indoor Air QualityiaqA I ( 4 --- 2 0 m a)J4 --- 2 , 3
Outdoor Air QualityoaqAI ( 4 --- 2 0 m a)J4 --- 5 , 6
Safety Chain FeedbacksafetyDI (24 VAC)J 1 --- 9
Compressor SafetycompstatDI (24 VAC)J 1 --- 2
Fire ShutdownfiredownDI (24 VAC)J 1 --- 1 0
Enthalpy SwitchenthalpyDI (24 VAC)J 2 --- 6 , 7
Humidistat Input StatushumstatDI (24 VAC)J 5 --- 7 , 8
548J
Space Relative HumiditysprhA I ( 4 --- 2 0 m a)
Outside Air Relative HumidityoarhA I ( 4 --- 2 0 m a )
Supply Fan StatusfanstatDI (24 VAC)
Filter StatusfiltstatDI (24 VAC)
Remote Occupancy InputremoccDI (24 VAC)
LEGEND
AI --- A n a l o g I n p u t
AO --- A n a l o g O u t p u t
DI --- D is c r e t e I np ut
DO --- Discrete Output
* These inputs (if installed) take the place of the default input on the specific channel according to schematic.
P a r a ll el p i n s J 5 --- 1 = J 2 --- 6 , J 5 --- 3 = J 1 --- 1 0, J 5 --- 5 = J 1 --- 2 a re u se d f o r f i e l d --- i n s t a l la ti o n .
Refer to the input configuration and accessory sections for more detail.
BACnet OBJECT
NAME
INPUTS
CONFIGURABLE INPUTS*
OUTPUTS
TYPE OF I/O
CONNECTION PIN
NUMBERS
J4--- 2,3 or J4---5,6
J 5 --- 1 , 2 o r J 5 --- 3 , 4 o r
J5 5,6 or J5 ---7,8
The RTU--MP controller requires the use of a Bryant
space sensor. A standard thermostat cannot be used with
the RTU--MP system.
SupplyAirTemperature(SAT)Sensor—On
FIOP--equipped 548J unit, the unit is supplied with a
supply--air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6--inches
(153 mm) in length. It is a nominal 10-- k ohm thermistor.
See Table 15 for temperature-- resistance characteristic.
The SAT is factory--wired. The SAT probe is wire--tied to
the supply--air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re--position the sensor in the flange of the supply--a ir
opening or in the supply air duct (as required by local
1
codes). Drill or punch a
/2--in. (12.7 mm) hole in the
flange or duct. Use two field--supplied, self--drilling
screws to secure the sensor probe in a horizontal
orientation. See Fig. 49.
SUPPLY AIR
TEMPERATURE
SENSOR
SUPPLY AIR
RETURN AIR
Fig. 49 -- T ypical Mounting Location for Supply Air
Temperature (SAT) Sensor on Small Rooftop Units
36
ROOF
CURB
C08200
Table 15 – Thermistor Resistance vs Temperature
Values for Space Temperature Sensor, Supply Air
NOTE:The sensor must be mounted in the discharge
airstream downstream of the cooling coil and any heating
devices. Be sure the probe tip does not come in contact
with any of the unit’s heater surfaces.
Outdoor Air T emperature (OAT) Sensor — The OAT is
factory--mounted in the EconoMi$er 2 (FIOP or accessory).
It is a nominal 10k ohm thermistor attached to an eyelet
mounting ring. See Table 15 for temperature--resistance
characteristic.
EconoMi$er 2 — The RTU--MP control is used with
EconoMi$er2 (option or accessory) for outdoor air
management. The damper position is controlled directly
by the RTU--MP control; EconoMi$er 2 has no i nternal
logic device.
HOLE IN END PANEL (HIDDEN)
C08027
Fig. 50 -- Field Control Wiring Raceway
Space Temperature (SPT) Sensors
A field-- supplied Bryant space temperature sensor is
required with the RTU--MP to monitor space temperature.
There are 3 sensors available for this application:
S 33ZCT55SPT, space temperature sensor with override
button
S 33ZCT56SPT, space temperature sensor with override
button and setpoint adjustment
S 33ZCT59SPT, space tempe rature sensor wit h LCD
(liquid crystal display) screen, ove rride button, and
setpoint adjustment
Use 20 gauge wire to connect the sensor to the cont roller.
The wire is suitable for distances of up to 500 ft. Use a
three--conductor shielded cable for the sensor and setpoint
adjustmentconnections.If thesetpoint adjustment
(slidebar) is not required, then an unshielded, 18 or 20
gauge, two--conductor, twisted pair cable may be used.
Connect T--55 -- See Fig. 51 for typical T--55 internal
connections.Connect theT--55SEN terminals to
RTU--MP J20--1 and J20--2. See Fig. 52.
548J
Outdoor air management functions can be enhanced with
field--installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
Outdoor air CO
sensor
2
sensor
2
Field Connections — Field connections for accessory
sensors and input devices are made the RTU--MP, at plugs
J1, J2, J4, J5, J11 and J20. All field control wiring that
connects to the RTU--MP must be routed through the
raceway built into the corner post as shown in Fig. 50.
The raceway provides the UL required clearance between
high-- and low--voltage wiring. Pass the control wires
through the hole provided in the corner post, then feed the
wires thorough the raceway to the RTU--MP. Connect to
the wires to the removable Phoenix connectors and then
reconnect the connectors to the board.
2
3
SW1
45
SEN
61
RED(+)
WHT(GND)
BLK(-)
BRN (GND)
BLU (SPT)
CCN COM
SENSOR WIRING
Fig. 51 -- T--55 Space Temperature Sensor Wiring
37
C08201
SEN
SEN
J20-1
J20-2
Fig. 52 -- RTU--MP T--55 Sensor Connections
C08460
ORSET SEN
BRN (COM)
BLK (STO)
BLU (SPT)
SENSOR
WIRING
Connect T--56--See Fig.53 for T--56 internal
connections. Install a jumper between SEN and SET
terminals a s illustrated. Connect T--56 terminals to
RTU--MP J20--1, J20--2 and J20--3 per Fig. 54.
548J
2
3
SW1
CoolWarm
45
SEN
61
RED(+)
WHT(GND)
BLK(-)
SET
BLK
(T56)
BRN (GND)
BLU (SPT)
CCN COM
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
Fig. 53 -- T--56 Internal Connections
SENJ20-1
C08202
OPBCOM- PWR+
POWER
24 VAC
NOTE: Must use a separate isolated transformer.
WIRING
C07132
Fig. 55 -- Space Temperature Sensor Typical Wiring
(33ZCT59SPT)
Economizer controls —
Outdoor Air E nthalpy Control (PNO 33CSENTHSW) --
The enthalpy control (33CSENTHSW) is available as a
field--installed accessory to be used with the EconoMi$er2
damper system. The outdoor air enthalpy sensor is part of
theenthalpycontrol.(Theseparatefield--installed
accessory return air enthalpy sensor (33CSENTSEN) is
required for differential enthalpy control. See “Return Air
Enthalpy Sensor” for details.)
Locate the enthalpy control in the economizer next to the
Actuator Motor. Locate two GRA leads in the factory
harness and connect the gray lead labeled “ESL” to the
terminal labeled “LOW”. See Fig. 56. Connect the
enthalpy control power input terminals to economizer
actuator power leads RED (connect to 24V) and BLK
(connect to GND).
SEN
Jumper
J20-2
SET
SET
J20-3
C08461
Fig. 54 -- RTU--MP T--56 Sensor Connections
Connect T--59 -- The T--59 space sensor requires a
separate, isolated power supply of 24 VAC. See Fig. 55
for internal connections at the T--59. Connect the SEN
terminal (BLU) to RTU--MP J20--1. Connect the COM
terminal (BRN) to J20--2. Connect the SET terminal (STO
or BLK) to J20--3.
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
The enthalpy control receives the outdoor air enthalpy
from the outdoor air enthalpy sensor and provides a dry
contact switch input to the RTU--MP controller. A closed
contact indicates that outside air is preferred to the return
air. An open contact indicates that the economizer should
remain at minimum position.
38
Differential Enthalpy Control — Differential enthalpy
control is provided by sensing and comparing the outside
air and return air enthalpy condi tions. Install the outdoor
air enthalpy control as described above. Add and install a
return air enthalpy sensor.
Return Air Enthalpy Sensor — Mount the return--air
enthalpy sensor (33CSENTSEN) in the return--air section
of the ecomomizer. The return air sensor is wired to the
enthalpy controller (33CSENTHSW). See Fig. 57.
24V
– 4-20
Main
+ VDC
Out
GND
LOW
RED
BLK
GRA
ESL
ECONO
MOTOR
HG
+
24 VAC
OR
-
24 VDC
+
0-10VDC
-
SIG COM (J4-6)
+
4-20mA (J4-5)
ALARM
NC
COM
RELAY
}
CONTACTS
NO
2
1
5
1
4
32
7
6
8
548J
+ 24-36
VDC In
– 4-20 Main
Out
C09027
Fig. 57 -- Outside and Return Air Enthalpy Sensor
Wiring
To wire the return air enthalpy sensor, perform the
following:
1. Use a 2 --conductor, 18 or 20 AWG, twisted pair cable
to connect the return air enthalpy sensor to the
enthalpy controller.
2. Connect the field--supplied RED wire to (+) spade
connector on the return air enthalpy sensor and the
(+) terminal on the enthalpy controller. Connect the
BLK wire to (--) spade connector on the return air
enthalpy sensor and the (--) terminal on the enthalpy
controller.
Indoor Air Quality (CO
sensor) — The indoor air quality
2
sensor accessory monitors space carbon dioxide (CO
levels. This information is used to monitor IAQ levels.
Several types of sensors are available, for wall mounting
in the space or in return duct, with and without LCD
display, and in combination with space temperature
sensors. Sensors use infrared t echnology to measure the
levels of CO
The CO
present in the space air.
2
sensors are all factory set for a range of 0 to
2
2000 ppm and a linear mA output of 4 to 20. Refer to the
instructions supplied with the CO
sensor for electrical
2
requirements and terminal locations. See Fig. 58 for
typical CO
sensor wiring schematic.
2
C07134
Fig. 58 -- Indoor/Outdoor Air Quality (CO2)Sensor
(33ZCSENCO
) -- Typical Wiring Diagram
2
To accurately monitor the quality of the air in the
conditioned air space, locate the sensor near a return--air
grille (if present) so it senses the concentration of CO
2
leaving the space. The sensor should be mounted in a
location to avoid direct breath contact.
Do not mount the IAQ sensor in drafty areas such as near
supply ducts, open windows, fans, or over heat sources.
Allow at least 3 ft (0.9 m) between the sensor and any
corner. Avoid mounting the sensor where it is influenced
by the supply air; the sensor gives inaccurate readings if
the supply air is blown directly onto the sensor or if the
supply air does not have a chance to mix with the room air
before it is drawn i nto the return airstream.
Wiring the Indoor Air Quality Sensor —
For each sensor, use two 2--conductor 18 AWG (American
)
2
Wire Gage) twisted--pair cables (unshielded) to connect
the separate isolated 24 vac power source to the sensor
and to connect the sensor to the control board terminals.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
sensor. See Fig. 58. Connect the 4--20 mA terminal to
RTU--MP J4--2 and connect the SIG COM terminal to
RTU--MP J4--3. See Fig. 59.
IAQ Sensor
SEN
J4-2
39
COM
24 VAC
Fig. 59 -- RTU--MP / Indoor CO2Sensor
(33ZCSENCO2) Connections
J4-3
C08462
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus
weatherproof enclosure) — The outdoor air CO
designed to monitor carbon dioxide (CO
) levels in the
2
outside ventilation air and interface with the ventilation
damper in an HVAC system. The OAQ sensor is packaged
with an outdoor cover. See Fig. 60. The outdoor air CO
sensor must be located in the economizer outside air hood.
548J
COVER REMOVEDSIDE VIEW
Fig. 60 -- Outdoor Air Quality Sensor Cover
Wiring the Outdoor Air CO
Sensor — A dedicated power
2
supply is required for this sensor. A two--wire ca ble is
required to wire the dedicated power supply for the sensor.
The two wires should be connected to the power supply
and terminals 1 and 2.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 58. Connect the 4--20 mA terminal
to RTU--MP J4--5. Connect the SIG COM terminal to
RTU--MP J4--6. See Fig. 61.
sensor is
2
C07135
Alarm state is reset when the smoke detector alarm
condition is cleared and reset at the smoke detector in the
unit.
Connecting Discrete Inputs
Filter Status
2
The filter status accessory is a field--installed accessory.
This accessory detects plugged filters. When installing
this accessory, the unit must be configured for filter status
by setting MENU
→
Config→Inputs→input3,5,8,or9
to Filter Status and normally open (N/O) or normally
closed (N/C). Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 46, Fig. 47 and Fig. 48 for wire
terminations at J5.
Status
Fan
The fan status accessory is a field--installed accessory.
This accessory detects when the indoor fan i s blowing air.
When installing this accessory, the unit must be
configuredforfanstatusbysetting
→
MENU
Config→Inputs→input3,5,8,or9to Fan
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 46, Fig. 47, and Fig. 48 for wire terminations at J5.
Remote
Occupancy
The remote occupancy accessory is a field -- installed
accessory. This accessory overrides the unoccupied mode
and puts the unit in occupied mode. When installing this
accessory, the unit must be configured for remote
→
occupancy by setting MENU
Config→Inputs→input 3,
5, 8, or 9 to Remote Occupancy and normall y open (N/O)
or normally closed (N/C).
→
Also set MENU
Schedules→occupancy source to DI
on/off. Input 8 or 9 is recomme nded for easy of
installation. Refer to Fig. 46 and Table 14 for wire
terminations at J5.
Power Exhaust (output)
OAQ Sensor/RH Sensor
SEN
COM
24 VAC
J4-5
J4-6
C08463
Fig. 61 -- RTU--MP / Outdoor CO2Sensor
(33ZCSENCO2) Connections
On 548J units equipped with factory--installed Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit’s CTB input. The FSD function is initiated via the
smoke detector’s Alarm NO contact set. The RTU--MP
controller communicates the smoke detector’s tripped
status to the BAS building control. See Fig. 42 for unit
smoke detector wiring.
TheFireShutdownSwitchconfiguration,
→
MENU
Config→Inputs→input5,identifiesthe
normally open status of this input when there is no fire
alarm.
Connect the accessory Power Exhaust contactor coil(s) per
Fig. 62.
Power Exhaust
PEC
TAN
J11-3
CTB
THERMOSTAT
GRA
Fig. 62 -- RTU--MP Power Exhaust Connections
Space Relative Humidity Sensor -- The RH sensor is not
used with 548J models at this time.
Communication Wiring -- Protocols
General
Protocols are the communicati on languages spoken by
control devices. The main purpose of a protocol is to
communicate information in the most efficient method
possible. Different protocols exist to provide different
kinds of information for different applications. In the BAS
application, many different protocols are used, depending
C
C08464
40
on manufacturer. Protocols do not change the function of
a controller; just make the front end user different.
The RTU--MP can be set to communicate on four different
protocols: BACnet, Modbus, N2, and LonWorks. Switch 3
(SW3) on the board is used to set protocol and baud rate.
Switches 1 and 2 (SW1 and SW2) are used to set the
board’s network address. See Fig. 63 for the switch setting
per protocol. The 3rd party connection to the RTU--MP is
through plug J19.
NOTE: Power must be cycled after changing the SW1--3
switch settings.
BACnet
MS/TP
BACnet Master Slave/Token Passing (MS/TP) is used for
communicatingBACnetoverasub--networkof
BACnet--only controllers. This is the default Bryant
communications protocol. Each RTU--MP module acts as
an MS/TP Master. The speed of an MS/TP network can
range from 9600 to 76.8K baud. Physical Addresses ca n
be set from 01 to 99.
Modbus
The RTU--MP module can speak the Modicon Modbus
RTU Protocol as described in the Modi con ModbusProtocol Reference Guide, PI--MBUS--300 Rev. J.The
speed of a Modbus network can range from 9600 to 76.8K
baud. Physical Addresses can be set from 01 to 99.
Johnson
N2
N2 is not a standard protocol, but one that was created by
Johnson Controls, Inc. that has been made open and
available to the public. The speed of N2 network is
limited to only 9600 baud. Physical addresses can be set
from 01 to 99.
orks
LonW
LonWorks is an open protocol that requires the use of
Echelon’s Neuron microprocessor to encode and decode
the LonWorks packets. In order to reduce the cost of
adding that hardware on every module, a separate
LonWorks Option Card (LON--OC) was designed to
connect to the RTU-- MP.
This accessory card is needed for LonWorks and has to be
ordered and connected using the ribbon cable to plug J15.
The RTU--MP’s baud rate must be set to 38.4k to
communicate with the LON--OC. The address switches
(SW1 & SW2) are not used with LonWorks.
Access
Local
BACview
The BACview
6
Handheld
6
is a keypad/display interface used to
connect to the RTU-- MP to access the control information,
read sensor values, and test the RTU, see Fig. 64. This is
an accessory interface that does not come with the MP
controller and can only be used at the unit. Connect the
6
BACview
to the RTU--MP’s J12 local access port. There
are 2 password protected levels in the display (User and
Admin). The user password is defaulte d to 0000 but can
be changed. The Admin password is 1111 and cannot be
changed. There is a 10 minute auto logout if a screen is left
idle. Contact your Bryant applications engineer for details
on navigation and screen content.
Virtual BACview
Virtual BACview is a freeware computer program that
6
functions as the BACview
Handheld. The USB Link
interface (USB--L) is required to connect a computer to
the RTU--MP board. The link cable connects a USB port
to the J12 local access port. This program functions and
operates identical to the handheld.
548J
SW3 Protocol Selection
PROTOCOLDS8DS7DS6DS5DS4DS3DS2DS1
BACnet MS/TP
(Master)
Modbus
(Slave)
N2
(Slave)
LonWorksUnusedONONOFFONOFFOFFOFF
NOTE:
DS = Dip Switch
BACnet MS/TP SW3 example shown
BAUD RATEDS2DS1
9600OFFOFF
19,200ONOFF
38,400OFFON
76,800ONON
UnusedOFFOFFOFFONOFFSelect BaudSelect Baud
UnusedOFFOFFONONOFFSelect BaudSelect Baud
UnusedOFFOFFOFFONONOFFOFF
Baud Rate Selections
Fig. 63 -- RTU--MP SW3 Dip Switch Setti ngs
C07166
41
548J
Fig. 64 -- BACview6Handheld Connections
RTU--MP Troubleshooting
Communication LEDs
The LEDs on the RTU--MP (see Fig. 46) indicate if the
controller is speaking to the devices on the network. The
LEDs should reflect communicati on traffic based on t he
The LEDs on the RTU --- MP show the status of certain functions
C07170
baud rate set. The higher the baud rate the more solid the
LEDs will appear. See Table 16 for further information.
Table 16 – RTU--MP LEDs
If this LED is on...
PowerThe RTU MP has power
RxThe RTU MP is receiving data from the network segment
TxThe RTU MP is transmitting data over the network segment
DO#The digital output is active
The Run and Error LEDs indicate control module and network status
If Run LED shows...
2 flashes per secondOffNormal
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per secondOn
5 flashes per secondOnExec start---up aborted, Boot is running
5 flashes per secondOff
7 flashes per second
14 flashes per second
OnOn
Status is...
And Error LED shows...Status is...
2flashes,
alternating with Run LED
3flashes,
then off
4flashes,
then pause
7 flashes per second, alternating with
Run LED
14 flashes per second,
alternating with Run LED
Five minute auto ---restart delay after
system error
Control module has just been
formatted
Two or more devices on this network
havethesameARC156networkaddress
Exec halted after frequent system errors
or control programs halted
Firmware transfer in progress, Boot is
running
Ten second recovery period after
brownout
Brownout
Failure. Try the following solutions:
STurn the RTU --- MP off, then on.
SF o r m a t th e R TU --- M P .
SDownload memory to the RTU ---MP.
SReplace the RTU---MP.
42
Table 17 – Troubleshooting Alarms
BACnet
POINT NAME
Safety Chain Alarmsafety_chain
Fire Shutdown Alarmfire_alarm
Space Temp Sensor
Failure
SAT Sensor Alarmsat_alarm
High Space Temp Alarmspt_hiAlarm GeneratedAutomatic
Low Space Temp Alarmspt_loAlarm GeneratedAutomatic
High Supply Air Tempsat_hiAlarm GeneratedAutomatic
Low Supply Air Tempsat_loAlarm GeneratedAutomatic
Supply Fan Failed to
Start
Supply Fan in Handsf_hand
Compressor Safety
Alarm
Setpoint Slider Alarmslide_alarm
Dirty Filter AlarmfilterAlarm Generated
Switch Configuration
Alarm
Misconfigured Analog
Input
OAT Sensor Alarmoat_alarm
Space RH Sensor Alarmsprh_alarm
Outdoor RH Sensor
Alarm
High Space Humiditysprh_hiAlarm GeneratedAutomatic
Low Space Humiditysprh_loAlarm GeneratedAutomaticIRH is less then 35% for more then 10 minutes.
IAQ Sensor Alarmiaq_alarm
OAQ Sensor Alarmoaq_alarm
High Carbon Dioxide
Level
Supply Fan Runtime
Alarm
Compressor 1 Runtime
Alarm
Compressor 2 Runtime
Alarm
OBJECT
NAME
spt_alarm
sf_fail
dx_compstatAlarm GeneratedAutomaticCompressor would not start.
sw_cfg_alarm
an_cfg_alarm
oarh_alarmAlarm GeneratedAutomatic
co2_hiAlarm GeneratedAutomaticCO2 reading is above 1200ppm.
Alarm Generated
Disable 4 selectable
analog inputs
Alarm Generated
Economizer and Low
ambient DX cooling
lockout disabled.
Alarm Generated
Dehumidification
disabled
Alarm Generated
Disables IAQ Operation
Economizer moves to
minimum position
Alarm Generated
Set OAQ to 400
RESET
METHOD
AutomaticOver load Indoor Fan or Electric Heater overheat.
Automatic
Automatic
Automatic
Automatic
AutomaticBad Fan Status Switch, Configuration incorrect.
Automatic
Automatic/
reset timer
when
configured
with or
without
switch
Configure
correctly
Configure
correctly
Automatic
Automatic
Automatic
Automatic
clear the
timer
clear the
timer
clear the
timer
Smoke detected by smoke detector or
configuration incorrect
Faulty, shorted, or open thermistor caused by
wiring error or loose connection.
Faulty, shorted, or open thermistor caused by
wiring error or loose connection.
Thespacetemperaturehasrisenabovethecool
setpoint by more than the desired amount.
The space temperature has dropped below the
heat setpoint by more than the desired amount.
SAT is greater then 160 degrees for more than 5
minutes.
Thesupplyairtemperatureisbelow35_Ffor
more than 5 minutes.
Tripped Circuit Breaker, Broken belt, Bad indoor
fan motor, Configuration incorrect, Bad fan status
switch.
STOsensorisopenorshortedformorethen5
seconds.
Dirty Filter, supply fan run time exceeded, filter
switch configuration wrong.
More than one binary input is configured for the
same purpose. More then one discrete input is
configured to provide the same function.
More then one analog input is configured to
provide the same function.
Faulty, shorted, or open thermistor caused by
wiring error or loose connection.
Sensor reading is out of range. Bad sensor, bad
wiring, or sensor configured incorrectly.
Sensor reading is out of range. Bad sensor, bad
wiring, or sensor configured incorrectly.
IRH is greater then 70% for more then 10
minutes.
Sensor reading is out of range. Bad sensor, bad
wiring, or sensor configured incorrectly.
Sensor reading is out of range. Bad sensor, bad
wiring, or sensor configured incorrectly.
Supply fan run time exceeded user defined limit.
Compressor run time limit is exceeded.
Compressor run time limit is exceeded.
PROBABLE CAUSE
548J
43
Alarms
Alarms can be checked through the network and/or the
local access. All the alarms are listed in Table 17 with
name, object name, action taken by control, reset method,
and probable cause. There are help screens for each alarm
on the local access displayand listed in Form
48--50H--T--2T, Appendix A: Help Screens. Some alarms
are explained in detail below.
Safety Chain
This alarm occurs immediately if the supply--fan internal
overload trips or if an electric--heat limit switch trips. The
Unit Status will be Shutdown and the System Mode will
be Disable. When this happens CTB (R terminal) will not
have 24 VAC, but the RTU--MP board will still be
powered. All unit operations stop immediately and will
not restart until the alarm automatically clears. There are
no configurations for this alarm; it is all based on i nternal
548J
wiring. This alarm will never occur if Fire Shutdown
Alarm is active.
Fire Shutdown
This alarm occurs immediately when the smoke detector
senses smoke. The Unit Status will be Shutdown and the
System Mode will be Disable. All unit operations stop
immediately and will not restart until the alarm
automatically clears. If there is not a smoke detector
installed or the smoke detector did not trip, check input
configurations.
Space Temp Sensor Failur
This alarm occurs if the space sensor wired to the
RTU--MP is disconnected or shorted for more then 10
seconds. When this occurs the Unit Status will be
Shutdown and the System Mode will be Run. Sensor,
sensorconnections,wiring, boardconnection,and
configurations should be checked for faults or errors.
Alarm will reset automatically when cause is fixed.
SA T Sensor
This alarm occurs immediately when the supply air
temperature sensor wired to the RTU-- MP is disconnected
or shorted. When this occurs the Unit Status will be
Shutdown and the System Mode will be Run. Sensor,
sensorconnections,wiring, boardconnection,and
configurations should be checked for faults or errors.
Alarm will reset automatically when cause is fixed.
Switch Configuration
This occurs if more than one binary input (inputs 3, 5, 8,
and 9) is configured for the same function. When this
happens the two inputs (or more) c onfigured wrong will
be disabled as an inputs. This alarm will automatically be
cleared when configuration is corrected.
An example of this would be: Input 3 = Compressor
Safety, input 5 = Fan Status, input 8 = Fan Status, and
input 9 = Humidistat; the alarm would be act ive, unit
would run, compressor safety and humidistat would
function normally, and Fan Status (inputs 5 & 8) will be
interpreted as “No Function.”
Alarm
Alarm
e
Alarm
Alarm
Misconfigured Analog
Input
This occurs if more than one analog input (inputs 1 & 2)
is configured for the same sensor. When this happens the
two inputs will be disabl ed as inputs. This alarm will
automatically be cleared when configuration is corrected.
An example of this would be: Input 1 = IAQ Sensor, input
2 = IAQ Sensor; the alarm would be active, unit would
run, but the IAQ Sensor (inputs 1 & 2) will be interpreted
as “No Funct ion.”
Third Party
Networking
Thirdpartycommunicationandnetworking
troubleshooting should be done by or with assistance from
the front end 3rd party te chnician. A Module Status
Report (Modstat) (see Fig. 65) can be run from the
6
BACview
, see Table 18 to perform. This lists information
about the board status and networking state. For basic
troubleshooting, see Table 19. Refer to the RTU--MP 3rd
Party Integration Guide for additional information.
BACnet MS/TP
1. Verify that the BAS and controller are both set to
speak the BACnet MS/TP protocol. The protocol of
the controller is set via SW3 (switches 3, 4, 5, and 6).
The protocol can also be verified by getting a Modstat
of the controller through the BACview. Hit the “FN”
key and the “.” key at the same time to pull up a
Modstat. Scroll to the bottom of the page and there is
a section entitled “Network Communications.” The
active protocol and baud rate will be shown in this
section.
2. Verify that the BAS and controller are set for the
same baud rate. The baud rate of the controller is set
via SW3 (switches 1 and 2). The baud rate can also
be verified via the BACview by obtaining a Modstat.
(See Fig. 65.)
3. Verify that the BAS is configured to speak 2 -- wire
EIA--485 to the controller. The BAS may have to
configure jumper or DIP switches on their end.
4. Verify that the BAS and the controller have the same
communication settings (8 data bits, No Parity, and 1
stop bit).
5. Verify that the controller has a unique MAC address
on the MS/TP bus. The controller’s MS/TP MAC
address is set by its rotary address switches.
6. Verify proper wiring between the BAS and the
controller.
7. Verify that the BAS is reading or writing to the proper
BACnet objects in the controller. Download the latest
points list for the controller to verify.
8. Verify that the BAS is sending his requests to the
proper MS/TP MAC address of our controller.
9. Present the BAS company with a copy of our
controller’s BACnet PICS so that they know which
BACnet commands are supported. See below.
10. In certain situations, it may be necessary to tweak the
MS/TPProtocoltimingsettingsthroughthe
BACview
tweaked:
6
. There are two settings that may be
44
S Max Masters: Defines the highest MS/TP Master MAC
address on this MS/TP network. For example, if there are
3 master nodes on an MS/TP network, and their MAC
addresses are 1, 8, and 16, then Max Masters would be set
to 16 (since this is the highest MS/TP MAC address on
the network). This property optimizes MS/TP network
communications by preventing token passes and “poll for
master” requests to non--existent Master nodes (i.e., in
the above example, MAC address 16 would know to pass
the token back to MAC address 1 instead of count ing up
to MAC address 127). Each MS/TP master node on the
network must have their Max Masters set to this same
value. The default is 127.
Device Instance: 0160001
S MaxInfo Frames: This property defines the maximum
number of responses that will be sent whe n our controller
gets the token. A valid number is any positive integer.
The default is 10 and should be ideal for the majority of
applications. In cases where the controller is the target of
many requests, this number could be increased as high as
100 or 200.
NOTE: MS/TP networks can be comprised of both Master
and Slave nodes. V alid MAC addresses for Master nodes are
0 -- 127 and valid addresses for Slave nodes are 0 -- 254.
NOTE:See RTU--MP 3rd Party Integration Guide for
Protocol Maps.
1 PRGs loaded. 1 PRGs running.
Module status:
Firmware sections validated in flash memory
============================================
Boot16-H - v2.06:001 Jun 19 2007
RTU-MP DRIVER - v2.09:050 Jun 26 2007
System error message history: Type Specific
Warning message history:
Information message history:
POWERUP: BACnet reinitialize warmstart 06/29/07 10:49:40
Menu file not found. 06/29/07 10:48:35
ARC156 reconfigurations during the last hour (cleared upon reset):
Total ....................... 0
Initiated by this node ...... 0
548J
Core board hardware:
Type=147, board=34, manufactured on 05/14/2007, S/N 21A740188N
RAM: 1024 kBytes; FLASH: 1024 kBytes, type = 3
Base board hardware:
Type=147, board=71, manufactured on 05/14/2007, S/N RMP750037N
When troubleshooting, you may need to know a control module’s manufacture date.
Obtain the manufacture date from
a...
Module status report (modstat)To obtain a modstat with BACview6:
Sticker on the back of the main control
module board
“Serial No: RMPYMxxxxN”
(Bar Coded & Typed Number)
548J
ProblemPossible causeCorrective action
No communication with 3rd
party vendor
Notes
1. Press Function (FN) key and hold.
2. Then press period (.)
3. Release both buttons.
ThereportshowsthedateunderMain board hardware.
The serial numbers are unique and contain embedded information:
“RMP”---These first three digits are unique to RTU --- MP and are used as an identifier.
“YM”---These two digits identify the last digit of the year and month (in hex, A=10/Oct)
“xxxx”---These four digits represent the sequential number of units produced for a given
“N”---This final digit represents the decade and toggles between “N” and “M” every
of manufacture. “74” would represent a date of manufacture of “April 2007”.
product for the mentioned manufacturing time period.
ten years.
Table 19 – Basic Protocol Troubleshooting
Incorrect settings on SW1, SW2 and SW3Verify and correct switch settings. Cycle
RS485 Port has no voltage output
(check with RTU---MP disconnected from RS485
communication bus):
• Bacnet @ 9600/19.2K --- .01 to .045vdc
• Bacnet @ 38.4K --- .06 to .09vdc
• Bacnet @ 76.8K --- .1vdc
• Modbus @ 9600 --- 76.8K --- .124vdc
• N2 @ 9600 --- .124vdc
• LON @ 9600 --- .124vdc
Verify devices are daisy chained and repeaters and bias
terminators are correctly installed.
powertoRTU---MPafterchangingswitch
settings.
Verify RTU--- MP has correct power supply.
Possible bad driver on board.
Check RS485 bus for external voltage,
shorts or grounding before reconnecting
to the bus.
Check 3rd party vendor RS485
communication wiring guidelines and
troubleshooting procedures.
Table 20 – Modbus Exception Codes that May be
Returned From This Controller
CODENAMEMEANING
The Modbus function code used
01Illegal Function
02Illegal Data Address
04SlaveDeviceFailure
in the query is not supported by
the controller.
The register address used in the
query is not supported by the
controller.
The Modbus Master has
attempted to write to a
non--- existent register or a
read---only register in the
controller.
Modbus
1. Verify that the BAS and controller are both set to
speak the Modbus RTU protocol. The protocol of the
controller is set via SW3 (switches 3, 4, 5, and 6).
The protocol can also be verified by getting a Modstat
of the controller through the BACview. Hit the “FN”
key and the “.” key at the same time to pull up a
Modstat. Scroll to the bottom of the page and there is
a section entitled “Network Communications.” The
active protocol and baud rate will be shown in this
section.
2. Verify that the BAS and controller are set for the
same baud rate. The baud rate of the controller is set
via SW3 (switches 1 and 2). The baud rate can also
be verified via the BACview by obtaining a Modstat
(see above).
3. Verify that the BAS is configured to speak 2 -- wire
EIA--485 to the controller. The BAS may have to
configure jumper or DIP switches on their end.
4. Verify that the BAS and the controller have the same
communication settings (8 data bits, No Parity, and 1
stop bit).
5. Verify that the controller has a unique Modbus slave
address. The controller’s Modbus slave address is set
by its rotary address switches.
6. Verify that the BAS is using the proper Modbus
function codes to access data from our controller.
Supported function codes are shown above.
7. Verify proper wiring between the BAS and the
controller.
8. Verify that the BAS is reading or writing to the proper
Modbus register numbers on the controller. Download
the latest points list for the controller to verify.
9. Verify that the BAS is sending his requests to the
proper slave address of our controller.
NOTE:See RTU--MP 3rd Party Integration Guide (or
alternatively Form 48--50H--T--1T, Appendix) for Modbus
Protocol Conformance Statement.
46
N2
A
1. Verify that the BAS and controller are both set to
speak the N2 protocol. The protocol of the controller
is set via SW3 (switches 3, 4, 5, and 6). The protocol
can also be verified by getting a Modstat of the
controller through the BACview. Hit t he “FN” key
and the “.” key at the same time to pull up a Modstat.
Scroll to the bottom of the page and there is a section
entitled “Network Communications.” The active
protocol and baud rate will be shown in this section.
2. Verify that the BAS and controller are set for 9600
baud. The baud rate of the controller is set via SW3
(switches 1 and 2). The baud rate can also be verified
via the BACview by obtaining a Modstat (see above).
3. Verify that the BAS is configured to speak 2 -- wire
EIA--485 to the controller. The BAS may have to
configure jumper or DIP switches on their end.
4. Verify that the BAS and the controller have the same
communication settings (8 data bits, No Parity, and 1
stop bit).
5. Verify that the controller has a unique N2 slave
address on the N2 bus. The controller’s N2 slave
address is set by its rotary address switches.
6. Verify proper wiring between the BAS and the
controller.
7. Verify that the BAS is reading or writing to the proper
network point addresses on the controller. Download
the latest points list for the controller to verify.
8. Verify that the BAS is sending his requests to the
proper slave address of our controller.
NOTE:See RTU--MP 3rd Party Integration Guide (or
alternatively Form 48--50H--T--1T Appendix) for N2
Protocol Conformance Statement.
ECONOMIZER SYSTEMS
The 548J units may be equipped with a factory--installed
or accessory (field--installed) economizer system. Two
types areavailable:with a logiccontrol system
(EconoMi$erIV)andwithoutacontrolsystem
(EconoMi$er2). See Fig. 66 and Fig. 67 for component
locations on each type. See Fig. 68 and Fig. 69 for
economizer section wiring diagrams.
Both economizers use direct-- drive damper actuators.
ECONOMI$ER IV
CONTROLLER
WIRING
HARNESS
CTUATOR
Fig. 66 -- EconoMi$er IV Component Locations
ECONOMI$ER2
PLUG
OUTSIDE AIR
TEMPERATURE SENSOR
LOW AMBIENT
SENSOR
OUTDOOR
AIR HOOD
HOOD
SHIPPING
BRACKET
C06021
548J
BAROMETRIC
RELIEF
DAMPER
GEAR DRIVEN
DAMPER
C06022
Fig. 67 -- EconoMi$er2 Component Loc ations
47
548J
Economizer2 Position Damper
Unit Without Economizer or
2 Position Damper
C08631
Fig. 68 -- EconoMi$er IV Wiring
BLACK
BLUE
500 OHM
RESISTOR
VIOLET
NOTE 1
NOTE 3
50HJ540573
ACTUATOR
ASSEMBLY
RUN
DIRECT DRIVE
ACTUATOR
OAT SENSOR
4-20mA SIGNAL
PINK
YELLOW
WHITE
NOTES:
1. Switch on actuator must be in run position for economizer to operate.
2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sen
sor or HH57A077 enthalpy sensor.
3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.
4
TRANSFORMER
GROUND
3
5
2
8
6
7
RED
24 VAC
1
10
11
9
12
ECONOMISER2 PLUG
4-20 mA
TO J9 ON
PremierLink
BOARD
C08310
Fig. 69 -- EconoMi$er2 with 4 to 20 mA Control Wiring
48
Table 21 – EconoMi$er IV Input/Output Logic
INPUTSOUTPUTS
Demand Control
Ventilation (DCV)
Below set
(DCV LED Off)
Above set
(DCV LED On)
*For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.
†Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply-air sensor signal.
††Modulation is based on the DCV signal.
*** Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV)
or fully open (supply-air signal).
††† Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully
open (supply-air signal).
(Free Cooling LED Off)
(Free Cooling LED On)
(Free Cooling LED Off)
(Free Cooling LED On)
Enthalpy*
OutdoorReturn
High
Low
High
Low
Low
High
Low
High
Y1Y2
On OnOnOn
Off OffOffOff
On OnOnOff
On OffOffOff
Off OffOffOffMinimum positionClosed
On OnOnOn
On OffOnOff
Off OffOffOff
On OnOnOff
Off OffOffOff
CompressorNTerminal†
Stage1Stage
2
Modulating** (between min.
Modulating†† (between min.
OccupiedUnoccupied
Damper
Minimum positionClosedOn OffOnOff
position and full-open)
position and DCV
maximum)
Modulating***Modulating†††On OffOffOff
Modulating** (between
closed and full-open)
Modulating†† (between
closed and DCV
maximum)
548J
Fig. 70 -- EconoMi$er IV Functional View
EconoMi$er IV
Table 21 provides a summary of EconoMi$er IV.
Troubleshooting instructions are enclosed.
A functional view of the EconoMi$er is shown in Fig. 70.
Typical settings, sensor ranges, and jumper positions are
also shown.
EconoMi$er IV Standard
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10
to 20 mA device used to measure the outdoor-air
Sensors
C06053
temperature. The outdoor-air temperature is used to
determine when the EconoMi$er IV can be used for free
cooling.Thesensorisfactory-installedonthe
EconoMi$er IV in the outdoor airstream. (See Fig. 66.)
The operat ing range of temperature measurement is 40_ to
100_F(4_ to 38_C). See Fig. 73.
Supply Air Temperature (SAT) Sensor
The supply air temperature sensor is a 3 K thermistor
located at the inlet of t he indoor fan. (See Fig. 71.) This
sensor is factory installed. The operating range of
temperature measurement is 0° to 158_F(--18_ to 70_C).
See Table 15 for sensor temperature/resistance values.
49
SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
LOCATION
SUPPLY AIR
TEMPERATURE
SENSOR
Fig. 71 -- Supply Air Sensor Location
The temperature sensor looks like an eyelet terminal with
wires running to it. The sensor is located in the “crimp
end” and is sealed from moisture.
Outdoor Air Lockout Sensor
548J
The EconoMi$er IV is equipped with an ambient
temperature lockout switch located in the outdoor
airstream which is used to lock out the compressors below
a42_F(6_C) ambient temperature. (See Fig. 66. )
EconoMi$er IV Control
IMPORTANT: The optional EconoMi$er2 does not include
Modes
a controller. The EconoMi$er2 is operated by a 4 to 20
mA signal from an existing field-supplied controller. See
Fig. 69 for wiring information.
Determine the EconoMi$er IV control mode before set up
of the control. Some modes of operation may require
different sensors. (See Table 22.) The EconoMi$er IV is
supplied from the factory with a supply--air temperature
sensor and an outdoor-- air temperat ure sensor. This allows
for operation of the EconoMi$er IV with outdoor air dry
bulb changeover control. Additional accessories can be
added to allow for different types of changeover control
and operation of the EconoMi$er IV and unit.
Table 22 – EconoMi$er IV Sensor Usage
ECONOMI$ER IV WITH OUTDOOR AIR DRY
APPLICATION
Outdoor Air
Dry Bulb
Differential
Dry Bulb
Single EnthalpyHH57AC078
Differential
Enthalpy
CO2for DCV
Control using a
Wall-Mounted
CO
Sensor
2
CO2for DCV
Control using a
Duct-Mounted
CO
Sensor
2
* CRENTDIF004A00 and CRTEMPSN002A00 accessories are
used on many different base units. As such, these kits may
contain parts that will not be needed for installation.
† 33ZCSENCO2 is an accessory CO
** 33ZCASPCO2 is an accessory aspirator box required for
duct-mounted applications.
†† CRCBDIOX005A00 is an accessory that contains both
33ZCSENCO2 and 33ZCASPCO2 accessories.
None. The outdoor air dry bulb sensor is
HH57AC078 and CRENTDIF004A00*
33ZCSENCO2† and
33ZCASPCO2**OR
BULB SENSOR
Accessories Required
factory installed.
CRTEMPSN002A00*
33ZCSENCO2
CRCBDIOX005A00††
sensor.
2
C06033
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory
configured for outdoor dry bulb changeover cont rol. The
outdoor air and supply air temperature sensors are
included as standard. For this control mode, the outdoor
temperature is compared to an adjustable set point selec ted
on the control. If the outdoor-air temperature is above the
setpoint, the EconoMi$er IV will adjust the outside air
dampersto minimumposition.If theoutdoor-air
temperature is below the setpoint, the position of the
outside air dam pers will be controlled to provided free
cooling using outdoor air. When in this mode, the LED
next to the free cooling setpoint potentiometer will be on.
The changeover temperature setpoint is controlled by the
free cooling setpoint potentiometer located on the control.
(See Fig. 72.) The scale on the potentiometer is A, B, C,
and D. See Fig. 73 for the corresponding temperature
changeover values.
C06034
Fig. 72 -- EconoMi$er IV Controller Potentiometer
and LED Locations
19
LED ON
17
mA
14
13
12
11
18
16
15
10
9
40
LED OFF
45
D
50
60
55
DEGREES FAHRENHEIT
LED ON
LED OFF
65
C
LED ON
B
LED ON
A
LED OFF
100
90
95
85
80
C06035
70
LED OFF
75
Fig. 73 -- Outside Air Temperature Changeover
Setpoints
50
30
25
20
15
10
5
0
0.13 0.20 0.22 0.25 0. 30 0. 35 0.40 0.45 0.50
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
C06031
Fig. 74 -- Outdoor--Air Damper Leakage
Differential Dry Bulb Control
For differential dry bulb control the standard outdoor dry
bulb sensor is used in conjunction with an additional
accessorydrybulbsensor(partnumber
CRTEMPSN002A00). The accessory sensor must be
mounted in the return airstream. (See Fig. 75.) Wiring is
provided in the EconoMi$er IV wiring harness.
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part
number HH57AC078) is required. Replace the standard
outdoor dry bulb temperature sensor with the accessory
enthalpy sensor in the sam e mounting location. (See
Fig. 66.) When the outdoor air enthalpy rises above the
outdoor enthalpy changeover setpoint, the outdoor-air
damper moves to its minimum position. The outdoor
enthalpy changeover setpoint is set with the outdoor
enthalpy setpoint potentiometer on the EconoMi$er IV
controller. The setpoints are A, B, C, and D. (See Fig. 76.)
The factory-installed 620-ohm jumper must be in place
across terminals S
and SR+ on the EconoMi$er IV
R
controller (see Fig. 68).
In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower
temperature airstream is used for cooling. When using this
mode of change over control, turn the enthalpy setpoint
potentiometer fully clockwise to the D setting. (See
Fig. 72.)
ECONOMI$ERIV
CONTROLLER
ECONOMI$ERIV
GROMMET
RETURN AIR
SENSOR
RETURN DUCT
(FIELD-PROVIDED)
C07085
Fig. 75 -- Return Air Temperature or Enthalpy Sensor
Mounting Location
548J
CONTROL
CURVE
4
1
2
1
A
B
C
D
6
1
(29)90(32)95(35)
46
8
3
A
(18)
4
4
80
42
(21)
1
(27)
75
(24)
70
0
0
0
9
80
70
0
6
50
A
B
C
D
70
75
80
(24)
(21)
(27)
(29)90(32)95(35)
40
65
65
(18)
CONTROL POINT
deg. F (deg. C)
APPROX.
AT 50% RH
73 (23)
70 (21)
67 (19)
63 (17)
28
ENTHALPY BTU PER POUND DRY AIR
26
4
2
2
2
0
2
8
1
45
(7)
40
(4)
35
(2)
35
40
45
(2)
(4)
(7)
APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)
6
3
4
3
32
30
60
(16)
55
(13)
B
50
C
(10)
D
50
55
60
(10)
(13)
(16)
Fig. 76 -- Enthalpy Changeover Setpoints
85
RELATIVE HUMIDITY (%)
0
4
30
20
85
100
(38)
100
(38)
105
110
(41)
(43)
0
1
HIGH LIMIT
110
(43)
CURVE
105
(41)
C06037
51
N1
P1
T1
AQ1
SO+
SR+
CO SENSOR MAX RANGE SETTING
TR1
EXH
2V10V
EXH
Open
2V10V
DCV
2V10V
Free
Cool
B
A
DCV
DCV
C
D
Set
Min
Pos
Max
Set
N
P
T
AQ
SO
SR
TR
24
24 Vac
Va c
COM
HOT
_
+
12
5
4
3
EF1
EF
6000
5000
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
Fig. 78 -- CO2Sensor Maximum Range Settings
2
800 ppm
900 ppm
1000 ppm
1100 ppm
2345678
DAMPER VOLTAGE FOR MAX VENTILATION RATE
C06039
548J
Fig. 77 -- EconoMi$er IV Control
Differential Enthalpy Control
For differential enthalpy control, the EconoMi$er IV
controller uses two enthalpy sensors (HH57AC078 and
CRENTDIF004A00), one in t he outside air and one in the
return air duct. The EconoMi$er IV c ontroller compares
the outdoor air enthalpy to the return air enthalpy to
determine EconoMi$er IV use. The controller selects the
lower enthalpy air (return or outdoor) for cooling. For
example, whe n the outdoor air has a lower enthalpy than
the return air, the EconoMi$er IV opens to bring in
outdoor air for free cooling.
Replace the standard outside air dry bulb temperature
sensor with the accessory enthalpy sensor in the same
mounting location. (See Fig. 66.) Mount the return air
enthalpy sensor in the return air duct. (See Fig. 75.)
Wiring is provided in the EconoMi$er IV wiring harness.
(See Fig. 66.) The outdoor enthalpy changeover setpoint is
set with the outdoor enthalpy setpoint potentiometer on
the EconoMi$er IV controller. When using this mode of
changeovercontrol,turntheenthalpysetpoint
potentiometer fully clockwise to the D setting.
Indoor Air Quality (IAQ) Sensor Input
The IAQ input can be used for demand control ventilation
control based on the level of CO
measured in the space
2
or return air duct.
MounttheaccessoryIAQsensoraccordingto
manufacturer specifications. The IAQ sensor should be
wired to the AQ and AQ1 terminals of the controller.
Adjust the DCV potentiometers to correspond to the DCV
voltage output of the indoor air quality sensor at the
user-determined setpoint. (See Fig. 78.)
C06038
If a separate field-supplied transformer is used to power
the IAQ sensor, the sensor must not be grounded or the
EconoMi$er IV control board will be damaged.
When using demand ventilation, the minimum damper
position represents the minimum ventilation position for
VOC(volatileorganiccompounds)ventilation
requirements. The maximum demand ventilation position
is used for fully occupied ventilation.
When demand ventilation control is not being used, the
minimum position potentiometer should be used to set the
occupied ventilation position. The maximum demand
ventilation position should be turned fully clockwise.
Exhaust Setpoint Adjustment
The exhaust setpoint will determine when the exhaust fan
runs based on damper position (if accessory power
exhaust is installed). The setpoint is modified with the
Exhaust Fan Setpoint (EXH SET) potentiometer. (See
Fig. 72.) The setpoint represents the damper position
above which the exhaust fans will be turned on. When
there is a call for exhaust, the EconoMi$er IV controller
provides a 45 ±15 second delay before exhaust fan
activation to allow the dampers to open. This delay allows
the damper to reach the appropriate position to avoid
unnecessary fan overload.
Minimum Position Control
There is a minimum damper position potentiometer on the
EconoMi$er IV controller. (See Fig. 72.) The minimum
damper position maintains the minimum airflow into the
building during the occupied period.
When using demand ventilation, the minimum damper
position represents the minimum ventilation position for
VOC(volatileorganiccompound)ventilation
requirements. The maximum demand ventilation position
is used for fully occupied ventilation.
When demand ventilation control is not being used, the
minimum position potentiometer should be used to set the
occupied ventilation position. The maximum demand
ventilation position should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the
minimum amount of outdoor air, as required by local
codes, to enter the building. Make minimum position
adjustments with at least 10_F temperature difference
between the outdoor and return-air t emperatures.
52
To determine the minimum position setting, perform the
following procedure:
1. Calculate the appropriate mixed air temperature using
the following formula:
OA
(T
Ox
100100
)+(T
RA
x
R
)=T
M
TO= Outdoor-Air Temperature
OA = Perce nt of Outdoor Air
T
= Return-Air Temperature
R
RA = Percent of Return Air
T
= Mixed-Air Temperature
M
As an example , if local codes require 10% outdoor
airduringoccupiedconditions,outdoor-air
temperature is 60_F, and return-air temperature is
75_F.
(60 x .10) + (75 x .90) = 73.5_F
2. Disconnect the supply air sensor from terminals T and
T1.
3. Ensure that the factory-installed jumper is in place
across terminals P and P1. If remote damper
positioning is being used, make sure that the
terminals are wired according to Fig. 68 and that the
minimum position potentiometer is turned fully
clockwise.
4. Connect 24 vac across termina ls TR and TR1.
5. Carefully adjust the minimum position potentiometer
until the measured mixed air temperature matches the
calculated value.
6. Reconnect the supply air sensor to terminals T and
T1.
Remote control of the EconoMi$er IV damper is desirable
when requiring additional temporary ventilation. If a
field-supplied remote potentiometer (Honeywell part
number S963B1128) is wired to the EconoMi$er IV
controller, the minimum position of the damper can be
controlled from a remote location.
To control the minimum damper position remotely,
remove the factory-installed jumper on the P and P1
terminals on the EconoMi$e r IV controller. Wire the
field-supplied potentiometer to the P and P1 terminals on
the EconoMi$er IV controller. (See Fig. 77.)
Damper Movement
Damper movement from full open to full closed (or vice
1
versa) takes 2
/2minutes.
Thermostats
The EconoMi$er IV control works with conventional
thermostats that have a Y1 (cool stage 1), Y2 (cool stage
2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The
EconoMi$erIVcontroldoesnotsupportspace
temperaturesensors .Connectionsaremadeatthe
thermostat terminal connection board located in the main
control box.
Occupancy Control
The factory default configuration for the EconoMi$er IV
control is occupied mode. Occupie d status is provided by
the black jumper from terminal TR to terminal N. When
unoccupied mode is desired, i nstall a field --supplied
timeclock function in place of the jumper between TR
and N. When the timeclock contacts are closed, the
EconoMi$er IV control will be in occupied mode. When
the timeclock contacts are open (removing the 24--v signal
from terminal N), the EconoMi$er IV will be in
unoccupied mode.
Demand Control Ventilation (DCV)
When using the EconoMi$er IV for demand controlled
ventilation, there are some equipment selection criteria
which should be considered. When selecting the heat
capacity and cool capacity of the equipment, the
maximum ventilation rate must be evaluated for design
conditions. The maximum damper position must be
calculated to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to
10% more than the typical cfm required per person, using
normal outside air design criteria.
A proportional anticipatory strategy should be taken with
the following conditions: a zone wit h a large area, varied
occupancy, and equipment that cannot exceed the required
ventilation rate at design conditions. Exceeding the
required ventilation rate means the equipment can
condition air at a maximum ventilation rate that is greater
thantherequiredventilationrateformaximum
occupancy. A proportional-anticipatory strategy will cause
the fresh air supplied to increase as the room CO
increases even though the CO
reached. By the time the CO
setpoint has not been
2
level reaches the setpoint,
2
2
level
the damper will be at maximum ventilation and should
maintain the setpoint.
In order to have the CO
sensor control the economizer
2
damper in this manner, first determine the damper voltage
output for minimum or base ventilation. Base ventilation
is the ventilation required to remove contaminants during
unoccupied periods. The following equation may be used
to determine the percent of outside air entering the
building for a given damper position. For best results there
should be at least a 10 degree difference in outside and
return-air temperatures.
OA
(T
Ox
100100
)+(T
RA
x
R
)=T
M
TO= Outdoor-Air Temperature
OA = Perce nt of Outdoor Air
T
= Return-Air Temperature
R
RA = Percent of Return Air
T
= Mixed-Air Temperature
M
Once base ventilation has been determined, set the
minimum damper position potentiometer to the correct
position.
The same equation can be used to determine the occupied
or maximum ventilation rate to the building. For example,
an output of 3.6 volts to the actuator provides a base
ventilation rate of 5% and an output of 6.7 volts provides
the maximum ventilation rate of 20% (or base plus 15 cfm
per person). Use Fig. 78 to determine the maximum
setting of the CO
sensor. For example, an 1100 ppm
2
setpoint relates to a 15 cfm per person design. Use the
1100 ppm curve on Fig. 78 to find the point when t he CO
sensor output will be 6.7 volt s. Line up the point on the
548J
2
53
graph with the left side of the chart to determine that the
range configuration for the CO
sensor should be 1800
2
ppm. The EconoMi$er IV controller will output the 6.7
volts from the CO
sensor to the actuator when the CO
2
concentration in the space is at 1100 ppm. The DCV
setpoint may be left at 2 volts since the CO
voltage will be ignored by the EconoMi$er IV controller
until it rises a bove the 3.6 volt setting of the minimum
position potentiometer.
Once the fully occupied damper position has been
determined, set the maximum damper demand control
ventilation potentiometer to this position. Do not set to the
maximum position as this can result in over-ventilation to
the space and potential high humidity levels.
Sensor Configuration
CO
2
The CO
548J
can be selected anytime after the sensor is powered up.
sensor has preset standard voltage settings that
2
(See Table 23.)
Use setting 1 or 2 for Bryant equipment. (See Table 23.)
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number.
(See Table 23.)
2
sensor
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
2
The custom settings of the CO
sensor can be changed
2
anytime after the sensor is energized. Follow the steps
below to change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD
menu and press Enter.
4. Use the Up/Down button to toggle through each of
the nine variables, starting with Altitude, until the
desired setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode
to continue to the next variable.
Dehumidification of Fresh Air with DCV (Demand
Controlled Ventilation) Control
If normal rooftop heating and cooling operation is not
adequate for the outdoor humidity level, an energy
recovery unit and/or a dehumidification option should be
considered.
SETTINGEQUIPMENTOUTPUT
1
2
3
4
5
6
7
8
9
LEGEND: ppm — Parts Per Million
Interface w/Standard
Building Control System
Economizer
Health & SafetyProportional—
Parkin g/ Air In ta kes/
Loading Docks
ProportionalAny
ProportionalAny
ExponentialAny
Proportional15
Proportional20
Exponential15
Exponential20
Proportional—
Table 23 – CO2 Sensor Standard Settings
VENTILATION
RATE
(cfm/Person)
ANALOG
OUTPUT
0-10V
4-20 mA
2-10V
7-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
CO
CONTROL RANGE
(ppm)
0-2000100050
0-2000100050
0-2000110050
0-1100110050
0- 90090050
0-1100110050
0- 90090050
0-99995000500
0-200070050
2
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
54
EconoMi$er IV Preparation
This procedure is used to prepare the E conoMi$er IV for
troubleshooting. No troubleshooting or te sting is done by
performing the following procedure.
NOTE:This procedure requires a 9--v battery, 1.2
kilo--ohm resistor, and a 5.6 kilo--ohm resistor which are
not supplied with the EconoMi$er IV.
IMPORTANT: Be sure to record the positions of all
potentiometers before starti ng troubleshooting.
1. Disconnect power at TR and TR1. All LEDs should
be off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo--ohm
resistor across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals SO and + .
Connect 1.2 kilo--ohm 4074EJM checkout resistor
across terminals SO and +.
8. Put 620--ohm resistor across terminals SR and +.
9. Set minimum position, DCV setpoint, and exhaust
potentiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW
(clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
Differential
Enthalpy
To check differential enthalpy:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Place 620--ohm resistor across SO and +.
3. Place 1.2 kilo--ohm resistor across SR and +. The
Free Cool LED should be lit.
4. Remove 620--ohm resistor across SO and +. The Free
Cool LED should turn off.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
Enthalpy
Single
To check single enthalpy:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Set the enthalpy potentiometer to A (fully CCW). The
Free Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The
Free Cool LED should turn off.
4. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
DCV (Demand Controlled Ventilation) and
Power
Exhaust
To check DCV and Power Exhaust:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Ensure terminals AQ and AQ1 are open. The LED for
both DCV and Exhaust should be off. The actuator
should be fully closed.
3. Connect a 9--v battery to AQ (positive node) and AQ1
(negative node). The LED for both DCV and Exhaust
should turn on. The actuator should drive to between
90 and 95% open.
4. Turn the Exhaust potentiometer CW until the Exhaust
LED turns off. The LED should turn off when the
potentiometer is approximately 90%. The actuator
should remain in position.
5. Turn the DCV setpoint potentiometer CW until the
DCV LED turns off. The DCV LED should turn off
when the potentiometer is approximately 9--v. The
actuator should drive fully closed.
6. Turn the DCV and Exhaust potentiometers CCW until
the Exhaust LED turns on. The exhaust contacts will
close 30 to 120 seconds after the Exhaust LED turns
on.
7. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
DCV Minimum and Maximum
Position
To check the DCV minimum and maximum position:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Connect a 9--v battery to AQ (positive node) and AQ1
(negative node). The DCV LED should turn on. The
actuator should drive to between 90 and 95% open.
3. Turn the DCV Maximum Position potentiometer to
midpoint. The actuator should drive to between 20
and 80% open.
4. Turn the DCV Maximum Position potentiometer to
fully CCW. The actuator should drive fully closed.
5. TurntheMinimumPositionpotentiometerto
midpoint. The actuator should drive to between 20
and 80% open.
6. Turn the Minimum Position Potentiometer fully CW.
The actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator
should drive fully closed.
8. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
Supply--Air Sensor
Input
To check supply--air sensor input:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Set the Enthal py potentiometer to A. The Free Cool
LED turns on. The actuator should drive to between
20 and 80% open.
3. Remove the 5.6 kil o--ohm resistor and jumpe r T to
T1. The actuator should drive fully open.
4. Remove the jumper across T and T1. The actuator
should drive fully closed.
548J
55
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
EconoMi$er IV Troubleshooting
Completion
This procedure is used to return the EconoMi$er IV to
operation. No troubleshooting or testing is done by
performing the following procedure.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
3. SetDCV maximum positionpotentiometer to
previous setting.
4. Set minimum position, DCV setpoint, and exhaust
potentiometers to previous settings.
5. Remove 620--ohm resistor from terminals SR and +.
WIRING DIAGRAMS
6. Remove1.2kilo--ohmcheckoutresistorfrom
terminals SO and +. If used, reconnect sensor from
terminals SO and +.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo--ohm resistor from T and T1.
Reconnect wires at T and T1.
10. Remove jumper from P to P1. Reconnect device at P
and P1.
11. Apply power (24 vac) to terminals TR and TR1.
548J
See Fig. 79 and Fig. 80 for typical wiring diagrams.
Fig. 79 -- 548J Typical Unit Wiring Diagram -- Power (08D, 208/230--3--60)
56
C09199
C09200
548J
57
Fig. 80 -- 50TCQ Typical Unit Wiring Diagram -- Control (D08, 208/230--3--60)
PRE--START--UP
!
WARNING
!
WARNING
PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal
injury or death.
1. Follow recognized safety pra ctices and wear
protective goggles when checking or servicing
refrigerant system.
2. Do not operate compressor or provide any electric
power to unit unless compressor terminal cover is
in place and secured.
3. Do not remove compressor terminal cover until
all electrical sources are disconnected.
548J
4. Relieve all pressure from system before touching
or disturbing anything inside terminal box if
refrigerant leak is suspected around compressor
terminals.
5. Never attempt to repair soldered connection while
refrigerant system is under pressure.
6. Do not use torch to remove any component.
Systemcontainsoilandrefrigerantunder
pressure.Toremoveacomponent,wear
protective goggles and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from
system using both high--pressure and low
pressure ports.
c. Cut component connection tubing with tubing
cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs
when necessary. Oil can ignite when exposed
to torch flame.
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
The unit must be electrically grounded in accordance
with local codes and NEC ANSI/NFPA 70 (American
National Standards Institute/National Fire Protection
Association.)
Proceed as follows to inspect and prepare the unit for
initial start--up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING,
CAUTION, and INFORMATION labels attached to,
or shipped with, unit.
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could result in personal
injury or death.
Relieve pressure and recover all refrigerant before
system repair or final unit disposal.
Wear safety glasses and gloves when handling
refrigerants.
Keep torches and other ignition sources away from
refrigerants and oils.
3. Make the following inspections:
a. Inspect for shipping and handling damages such
as broken lines, loose parts, or disconnected
wires, etc.
b. Inspect for oil at all refrigerant tubing
connections and on unit base. Detecting oil
generally indicates a refrigerant leak. Leak--test
all refrigerant tubing connections using
electronic leak detector, halide torch, or
liquid--soap solution.
c. Inspect all field--wiring and factory--wiring
connections. Be sure that connections are
completed and tight. Be sure that wires are not
in contact with refrigerant tubing or sharp edges.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin
comb.
4. Verify the following conditions:
a. Make sure that condenser--fan blade are correctly
positioned in fan orifice. See Condenser--Fan
Adjustment section for more details.
b. Make sure that air filter(s) is in place.
c. Make sure that condensate drain trap is filled
with water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose
parts have been removed.
START--UP, GENERAL
Unit Preparation
Make sure that unit has been installed in accordance with
installation instructions and applicable codes.
Return--Air Filters
Make sure correct filters are installed in unit (see
Appendix II -- Physical Data). Do not operate unit without
return--air filters.
Outdoor--Air Inlet Screens
Outdoor--air inlet sc reen must be in place before operating
unit.
Compressor Mounting
Compressors are internally spring mounted. Do not loosen
or remove compressor hold down bolts.
58
Internal Wiring
Check all electrical connections in unit control boxes.
Tighten as required.
Refrigerant Service Ports
Each unit system has two1/4” SAE flare (with check
valves) service ports: one on the suction line, and one on
the compressor discharge line. Be sure that caps on the
ports are tight.
Compressor Rotation
On 3--phase units with scroll compressors, it is important
to be certain compressor is rotating in the proper
direction. To determine whether or not compressor is
rotating in the proper direction:
1. Connect service gauges to suction and discharge
pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start--up.
If the suction pressure does not drop and the discharge
pressure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating
in the wrong direction.
2. Turn off power to the unit and install lockout tag.
3. Reverse any two of the unit power leads.
4. Re--energize to the compressor. Check pressures.
The suction and discharge pressure levels should now
move to their normal start--up levels.
NOTE: When the compressor is rotating in the wrong
direction, the unit will make an elevated level of noise
and will not provide cooling.
Cooling
Set space thermostat to OFF position. To start unit, turn on
main power supply. Set system selector switch at COOL
position and fan switch at AUTO. position. Adjust
thermostat toasetting belowroom temperature.
Compressor starts on closure of contactor. (08D–09D:
Second stage of thermostat will energize Circuit 2
contactor, start Compressor 2.)
Check unit charge. Refer to Refrigerant Charge section.
Reset thermostat at a position above room temperature.
Compressor will shut off. Evaporator fa n will shut off
after a 30--second delay.
To shut off unit -- set system selector switch at OFF
position. Resetting thermostat at a position above room
temperatureshuts unit off temporarily until space
temperature exceeds thermostat setting.
Heating
To start unit, turn on main power supply.
Set system selector switch at HEAT position and set
thermostat at a setting above room temperature. Set fan at
AUTO position.
First stage of thermostat energizes compressor heating
(08D–09D: both compressors will start). Second stage of
thermostat energizes electric heaters (if installed). Check
heating effects at air supply grille(s).
If electric heaters do not energize, reset limit switch
(located on supply--fan scroll) by pressing button locate d
between terminals on the switch.
To shut off unit -- set system selector switch at OFF
position. Resetting thermostat at a position below room
temperaturetemporarily shuts unit off until space
temperature falls below thermostat setting.
Ventilation (Continuous Fan)
Set fan and system selector switches at ON and OFF
positions, respectively. Supply fan operates continuously
to provide constant air circulation.
548J
START--UP, RTU--MP CONTROL
Field Service Test, explained below, will assist in proper
start--up. Configuration of unit parameters, scheduling
options, and operation a re also discussed in this section.
Field Service Test
The Field Service Test function can be used to verify
proper operation of compressors, heating stages, indoor
fan,powerexhaustfans,economizer,and
dehumidification.UseofFieldServiceTestis
recommended at initial system start up and during
troubleshooting.
Field Service Test mode has the following changes from
normal operation:
S Outdoor air temperature limits for cooling circuits,
economizer, and heating are ignored.
S Normal compressor time guards and other staging delays
are ignored.
S The status of Alarms (except Fire and Safety chain) is
ignored but all alerts and alarms are still broadcasted on
the network.
Field Service Test can be turned ON/OFF at the unit
display or from the network. Once turned ON, other
entries may be made with the display or through the
network. To turn Field Service Test on, change the value
of Test Mode to ON, to turn Field Service Test off, cha nge
the value of Test Mode to OFF.
NOTE: Service Test mode is password protected when
accessing from the display. Depending on the unit model,
factory--installed options, and field--installed accessories,
some of the Field Service Test functions may not apply.
The independent outputs (IndpOutputs) submenu is used
to change output status for the supply fan, economizer,
and Power Exhaust. These independe nt outputs can
operate simultaneously with other Field Service Test
modes. All outputs return to normal operation when Field
Service Test is turned off.
The Cooling submenu is used to change output status for
the individual compressors and the dehumidification relay.
Compressor starts are not staggered. The fans and heating
service test outputs are reset to OFF for the cooling
59
service test. Indoor fans and outdoor fans are controlled
normally to maintain proper unit operat ion. All normal
cooling alarms and alerts are functional.
NOTE: Circuit A is always operated with Circuit B due
to outdoor fan control on Circuit A. Always test Circuit A
first, and leave it on to test other Circuits.
The Heating submenu is used to change output status for
the individual heat stages, gas or electric. The fans and
cooling service test outputs are reset to OFF for the
heating service test. All normal heating alarms and alerts
are functional.
Configuration
The RTU--MP controller configuration points affect the
unit operation and/or control. Review and understand the
meaning and purpose of each configuration point before
changing it from the factory default value. The submenus
containing configuration points are as follows: Unit,
548J
Cooling, Heating, Inputs, Economizer, IAQ, Clock--Set,
and User Password (USERPW). Each configuration point
is described below under its according submenu.
Unit
Start Delay
This refers to the time delay the unit will wait after power
up before it pursues any specific operation.
Factory Default = 5 sec
Range = 0--600 sec
Filter Service Hours
This refers to the timer set for the Dirty Filter Alarm.
After the number of runtime hours set on this point is
exceeded the corresponding alarm will be generated, and
must be manually cleared on the alarm reset screen after
the maintenance has been completed. The timer will then
begin counting its runtime again for the next maintenance
interval.
Factory Default = 600 hr
NOTE: Setting this configuration timer to 0, disables the
alarm.
Supply Fan Service Hours
This refers to the timer set for the Supply Fan Runtime
Alarm. After the number of runtime hours set on this point
is exceeded the corresponding alarm will be generated,
and must be manually cleared on the alarm reset screen
after the maintenance has been completed. The timer will
then begin counting its runtime again for the next
maintenance interval.
Factory Default = 0 hr
NOTE: Setting this configuration timer to 0, disables the
alarm.
Compressor1 Service Hours
This refers to the timer set for the Compressor 1 Runtime
Alarm. After the number of runtime hours set on this point
is exceeded the corresponding alarm will be generated,
and must be manually cleared on the alarm reset screen
after the maintenance has been completed. The timer will
then begin counting its runtime again for the next
maintenance interval.
Factory Default = 0 hr
NOTE: Setting this configuration timer to 0, disables the
alarm.
Compressor2 Service Hours
This refers to the timer set for the Compressor 2 Runtime
Alarm. After the number of hours set on this point is
exceeded the corresponding alarm will be generated, and
must be manually cleared on the alarm rest screen after
the maintenance has been completed. The timer will then
begin counting its runtime again for the next maintenance
interval
Factory Default = 0 hr
NOTE: Setting this configuration timer to 0, disables the
alarm.
Cooling
Number of Compressor Stages
This refers to the number of mechanical cooling stages
available on a specific unit. Set this point t o “One Stage”
if there is one compressor in the specific unit, set to “Two
Stage” if there are two compressors in the unit, and set to
“None” if economizer cooling ONLY is desired.
Factory Default = One Stage for 1 compressor units
Two Stage for 2 compressor units
Cooling/Econ SAT Low Setpt
The supply air temperature must remain above this value
to allow cooling with the economizer and/or compressors.
There is 5_F plus and minus deadba nd to this point. If the
SAT falls below this value during cooling, all compressors
will be staged off. The economizer will start to ramp
down to minimum position when the SAT = this
configuration +5_F.
Factory Default = 50_F
Range = 45--75_F
Cooling Lockout Temp
This defines the minimum outdoor air temperature that
cooling mode can be enabled and run. If the OAT falls
below this threshold during cooling, then compressor
cooling will not be allowed.
Factory Default = 45_F
Range = 0--65_F
Heating
Heating SAT High Setpt
The supply air temperature must remain below this value
to allow heating. There is 5_F plus and minus deadband to
this point. If the SAT rises above this value during heating
the heat stages will begin to decrease until the SAT has
dropped below this value.
Factory Default = 120_F
Range = 95--150_F
Heating Lockout Temp
This defines the maximum outdoor air temperature that
heating mode can be enabled and run. If the OAT rises
above this threshold during heating, then heating will not
be allowed.
Factory Default = 65_F
Range = 49--95_F
60
Inputs
NOTE:For installation of inputs and field installed
accessories, refer to the appropriate sections.
Input 3
This input is a discrete input and can be configured to be
one of five different inputs: No Function, Compressor
Safety, Fan Status, Filter Status, or Remote Occupancy.
This input can also be configured t o be eit her Normally
Open (N/O) or Normally Closed (N/C). Input 3 is factory
wired to pin J1--2. Field accessories get wired to its
parallel pin J5--5. Do not connect inputs to both locations,
one function per input.
Factory Default = Compressor Safety and N/O
NOTE: Compressor Safety input comes from the CLO
board. J1--2 is always factory wired to TB1--8 (X) terminal
on the unit. If the unit has a CLO board, do not configure
input 3 for anything but Compressor Safety.
Input 5
This input is a discrete input and can be configured to be
one of five different inputs: No Function, Fire Shutdown,
Fan Status, Filter Status, or Remote Occupancy. This
input can also be configured to be either Normally Open
(N/O) or Normally Closed (N/C). Input 5 is factory wired
to pin J1--10. Field accessories get wired to its parallel pin
J5--3. Do not connect inputs to both locations, one
function per input.
Factory Default = Fire Shutdown and N/C
NOTE: Fire Shutdown input comes from TB4--7. J1--10
is always factory wired to TB4 --7. Only change input 5s
function if absolutely needed.
Input 8
This input is a discrete input and can be configured to be
one of five different inputs: No Function, Enthalpy
Switch, Fan Status, Filter Status, or Remote Occupancy.
This input can also be configured t o be eit her Normally
Open (N/O) or Normally Closed (N/C). Input 8 is factory
wired to pin J2--6. Field accessories get wired to its
parallel pin J5--1. Do not connect inputs to both locations,
one function per input.
Factory Default = No Function and N/O
Input 9
This input is a discrete input and can be configured to be
one of five different inputs: No Function, Humidistat, Fan
Status, Filter Status, or Remote Occupancy. This input can
also be configured to be either Normally Open (N/O) or
Normally Closed (N/C). Input 9 is factory and field wired
to pin J5--7. Do not connect inputs to both locations, one
function per input.
Factory Default = Humidistat and N/O
Space Sensor Type
This tells the controller what type of space sensor is
installed to run the unit. The three types that can be used
are the T55 space sensor, the T56 space sensor, or the RS
space sensor.
Factory Default = T55 Type
Input 1 Function
This input is an analog input and can be configured to be
one of five different inputs: No Sensor, IAQ Sensor, OAQ
Sensor, Space RH Sensor, or Outdoor RH Sensor. Input 1
iswiredtopinJ4--5.
Factory Default = No Sensor
Input 2 Function
This input is an analog input and can be configured to be
one of five different inputs: No Sensor, IAQ Sensor, OAQ
Sensor, Space RH Sensor, or Outdoor RH Sensor. Input 2
iswiredtopinJ4--2.
Factory Default = No Sensor
Setpoint Slider Range
This sets the slider range of the space sensor (with this
built in function). The slider is used to offset the current
control setpoint.
Factory Default = 5 n_F
Range = 0--15 n_F
T55/56 Override Duration
This sets the occupancy override duration when the
override button is pushed on the space sensor.
Factory Default = 1 hr
Range = 0--24 hr
IAQ Low Reference @ 4mA
This is used when an IAQ sensor is insta lled on Input 1 or
2. This value is displayed and used when 4mA is seen at
the input.
Factory Default = 0 PPM
Range = 0--400 PPM
IAQ High Reference @ 20mA
This is used when an IAQ sensor is insta lled on Input 1 or
2. This value is displayed and used when 20mA is seen at
the input.
Factory Default = 2000 PPM
Range = 0--5000 PPM
NOTE:IAQ low Reference @ 4mA and IAQ High
Reference @ 20mA are used to set the linear c urve of mA
vs. PPM.
OAQ Low Reference @ 4mA
This is used when an OAQ sensor is installed on Input 1
or 2. This value is displayed and used when 4mA is seen
at the input.
Factory Default = 0 PPM
Range = 0--400 PPM
OAQ High Reference @ 20mA
This is used when an OAQ sensor is installed on Input 1
or 2. This value is displayed and used when 20mA is seen
at the input.
Factory Default = 2000 PPM
Range = 0--5000 PPM
NOTE:OAQ low Reference @ 4mA and OAQ High
Reference @ 20mA are used to set the linear c urve of mA
vs. PPM.
548J
61
Economizer
Economizer Exists
This point tells the controller if there is an economizer
installed on the unit.
Factory Default = NO if no economizer
YES if there is an economizer installed
Economizer Minimum Positi on
This defines the lowest economizer position when the
indoor fan is running and the building is occupied.
Factory Default = 20%
Range = 0--100 %
Economizer High OAT Lockout
If the outdoor air temperature rises above this value,
economizer cooling will be disabled and dampers will
return and stay at minimum position.
548J
Factory Default = 75_F
Range = 55--80_F
Power Exhaust Setpt
When the economizer damper position opens above this
point the power exhaust operation will begin. When the
damper position falls 10% below the setpoint, the power
exhaust will shutdown.
Factory Default = 50%
Range = 20--90 %
NOTE: This point is only used when Continuous Occ
Exhaust = NO
Continuous Occ Exhaust
This point tells the controller when to run the power
exhaust if equi pped on the unit. If set to YES, the power
exhaust will be on all the time when in occupied mode
and will be off when in unoccupied mode. If set to NO the
power exhaust will be controlled by the Power Exhaust
Setpoint.
Factory Default = NO
IAQ
Max Differential CO
2
Setpt
If the difference between indoor an outdoor air quality
becomes greater then this value the damper position will
stay at the IAQ Greatest Min Dmpr Pos. configuration
point
Factory Default = 650 PPM
Range = 300--950 PPM
IAQ Greatest Min Dmpr Pos.
This is the greatest minimum position t he economizer will
open to while trying to control the indoor air quality, CO
differential.
Factory Default = 50% open
Range = 10--60% open
Clockset
This submenu screen allows you to set the date and time
manually. The Daylight Savings Time (DST) can also be
changed here. The date and time is automatically set when
ever software is downloaded. The clock is a 24 hour clock
and not am/pm. The time should be verified (and maybe
changed) according to unit location and time zone.
Factory Default = Eastern Standard Time
USERPW
This submenu screen allows you to change the user
password to a four number password of choice. The User
password change screen is only accessible with the
Administrator Password (1111). The ADMIN password
will always override the user password.
OPERATING SEQUENCE
Indoor (Supply) Fan
Continuous fan operation is selected at the thermostat.
Terminal G is energized. Defrost Board (DFB) receives
this signal at P2--3 and it issues an output at P3--9.
04A--06A, Standard Static Drive option: 24--v signal at
P3--9 is applied to direct --drive motor communication
signal terminal. Direct--drive motor starts and runs.
All Belt--Drive Fan options: Contactor coil IFC is
energized; indoor fan motor starts.
Fan runs continuously until fan selection a t thermostat is
changed to AUTO. When the selector switch is switched
to AUTO, the input at P2--3 is removed and the output at
P3--9 is removed; IFC is de--energized and IFM stops. If
the fan selection is AUTO, indoor fan operation will be
initiated by the DFB through P3--9 when Cooling or
Heating sequence is initiated. Terminationof fan
operation will be delayed by 30 secs (if Fan Delay is
configured to ON) after Cooling or Heating sequence is
ended
Base Unit Controls
Cooling, Units Without Economizer
Continuous fan operation is selected at the thermostat.
Terminal G is energized. Defrost Board (DFB) receives
this signal at P2--3 and it issues an output at P3--9.
04A--06A, Standard Static Drive option: 24--v signal at
P3--9 is applied to direct --drive motor communication
signal terminal. Direct--drive motor starts and runs.
All Belt--Drive Fan options: Contactor coil IFC is
energized; indoor fan motor starts.
Fan runs continuously until fan selection a t thermostat is
changed to AUTO. When the selector switch is switched
to AUTO, the input at P2----3 is removed and the output at
P3--9 is removed; IFC is de--energized and IFM stops. If
the fan selection is AUTO, indoor fan operation will be
initiated by the DFB through P3----9 when Cooling or
2
Heating sequence is initiated. Terminationof fan
operation will be delayed by 30 secs (if Fan Delay is
configured to ON) after Cooling or Heating sequence is
ended.
The outdoor fan motors run continuously while unit is in
Stage 1 or Stage 2 cooling.
08D–09D: If Stage 1 cooling does not satisfy the space
load, the space temperature will rise until thermostat calls
for Stage 2 cooling (Y2 closes). DFB receives this input
at P2--4.It issues outputs at P3--6 (RVS2) and P3--8
(COMP2). Reversing valve 2 switches to Cooling
62
position. Compressor 2 contactor (C2) is energized;
Compressor 2 starts and Circuit 2 operates in Cooling
mode.
When Cooling Stage 2 is satisfied, thermostat Y2 opens.
Compressor 2 c ontactor (C2) is de--energized; Compressor
2 stops. RVS2 remains energized.
When Cooling Stage 1 is satisfied, thermostat Y1 opens.
Compressor 1 c ontactor (C1) is de--energized; Compressor
1 stops. Outdoor fan relay OFR is de--energize d; outdoor
fans stop. After the Fan Delay period, the Indoor fan
contactor IFC is de--energized; indoor fan stops (unless
Continuous Fan operation has been selected). RVS1
remains energized.
Reversing valve solenoids are energized in Cooling
modes.Each solenoid will remain energized until the
next Heating mode is initiated for this circuit.
Heating, Units Without Economizer
04A--07A(singlecompressormodel):Whenthe
thermostat calls for heating, terminal W1 is energized.
DFB receives this input at P2–7. The DFB removes the
output at P3–7 (RVS1)reversing valve solenoid is
de--energized and reversing valve moves to Heating
position. DFB issues outputs at P3–9 (IFO), OF, and
P3–10 (COMP1). The indoor fan motor or contactor (IFC)
is energized; indoor fan mot or starts. Outdoor fan relay
OFR is energized; outdoor fan motor runs. Compressor
contactor C1 is energized; refrigeration circuit operates in
Heating mode.
08D--09D (two compressor model): When the thermostat
calls for heating, terminal W1 is energized. DFB receives
this input at P2–7. The DFB removes the outputs at P3–7
(RVS1) and P3–6 (RVS2)); both reversing valve solenoids
are de--energized and reversing valves move to Heating
position. DFB issues outputs at P3–9 (IFO), OF, P3–10
(COMP1) and P3–8 (COMP2)). The indoor fan contactor
(IFC) is energized; indoor fan motor starts. Outdoor fan
relay OFR is energized; both outdoor fan motors run.
Compressor contactors C1 and C2 are energized; both
refrigeration circuits operate in Heating mode.
If Stage 1 heating does not satisfy the space load, the
space temperature will fall until thermostat calls for Stage
2 heating (W2 closes). Terminal W2 is energized. DFB
receives input at P2--6. DFB issues an output at EHEAT.
Heater contactor 1 (HC1) and heater contactor 2 (HC2) (if
installed) are energized; all electric heaters are energized.
When space heating load is partially satisfied, thermostat
terminal W2 is de--energized; this signal is removed at
DFB P2--6. DFB output at EHEAT is removed; heater
contactors HC1 and HC2 are de--energized and all electric
heat is terminated. Stage 1 heating continues.
When the space heating load is fully satisfied, thermostat
terminal W1 is also de--energized. DFB removes outputs
at P3--10 (COMP1), P3--8 (COMP2) and OF. All
compressor and outdoor fan operations cease. After the
Fan Delay period, output P3--9 is removed and IFM
operations cease (unless Continuous Fan operation has
been selected).
Reversing valve solenoids remain de--energized until the
next call for Cooling mode is initiated.
Cooling, Unit With EconoMi$er IV
For Occupied mode operation of EconoMi$er IV, there
must be a 24--v signal at terminal N (provided through
harness plug PL6--3 from the unit’s IFC coil). Removing
the signal at N places the EconoMi$er IV control in
Unoccupied mode. During Occupied mode operation,
indoor fan operation will be accompanied by economizer
dampers moving to Minimum Position setpoint for
ventilation. If indoor fan is off, dampers will close. During
Unoccupied mode operation, dampers will remain closed
unless a Cooling (by free cool ing) or DCV dema nd is
received.
When free cooling using outside air is not available, the
unit cooling sequence will be controlled directly by the
space thermostat as described above in Cooling, UnitWithout Economizer. Outside air damper position will be
closed or Minimum Position as determined by occupancy
mode and fan signal.
When free cooling is available as determined by the
appropriate changeover command (dry bulb, outdoor
enthalpy, differential dry bulb or differential enthalpy), a
call for cooling (Y1 closes at the thermostat, signal
through PL6--2 to Econo--1) will cause the economizer
control to modulate the dampers open and closed to
maintain the unit supply air temperature at 50_Fto55_F
(10_C to 12.8_C). Compressor will not run.
During free cooling operation, a supply air temperature
(SAT) above 50_F(10_C) will cause the dampers to
modulate between Minimum Position setpoint and 100%
open. With SAT from 50_Fto45_F(10_Cto7.2_C), the
dampers will maintain at the Minimum Position setting.
With SAT below 45_F (7.2_C), the outside air dampers
will be closed. When SAT rises to 48_F (8.9_C), the
dampers will re--open to Minimum Position setting.
Should 100% outside air not be capable of satisfying the
space temperature, space temperature will rise until Y2 is
closed. The economizer control will call for compressor
operation. Y2 signal is transferred to the DFB’s Y1 input
(P2--5). Stage 1 Cooling is initiated as described above in
Cooling,UnitWithoutEconomizer.Damperswill
modulate to maintain SAT at 50_Fto55_F(10_Cto
12.8_C) concurrent with Compressor 1 operation. When
thermostat Stage 2 cooling is satisfied, DFB outputs for
COMP1 and OF will be removed and mechanical cooling
sequence will terminate.
The Low Ambient Lockout Thermostat will block
compressor operation with economizer operation below
42_F (5.6_C ) outside air temperature.
When space temperature demand is satisfied (thermostat
Y1 opens), the dampers will return to Minimum Damper
position if indoor fan is running or fully closed if fan is
off.
If accessory power exhaust is installed, the power exhaust
fan motors will be energized by the economizer control as
the dampers open above the PE--On setpoint and will be
548J
63
de--energized as the dampers close below the PE-- On
setpoint.
Damper movement from full closed to full open (or vice
versa) will take between 1
1
/2and 21/2minutes.
Heating With E conoMi$er IV
During Occupied mode operation, indoor fan operati on
will be accompanied by economizer dampers m oving to
Minimum Position setpoint for ventilation. If indoor fan is
off, dampers will close. During Unoccupied mode
operation, dampers will remain closed unless a DCV
demand is received.
When the room temperature calls for heat (W1 closes), the
heating controls are energized as described in Heating,Unit Without Economizer above.
Defrost Cycle
548J
During the Heating Mode, frost and ice can develop on
the outdoor coil. Defrost sequence will clear the frost and
ice from the coil by briefly reversing the Heating
sequence periodically.
A window to test for a need to run the Defrost cycle opens
30 minutes after the end of the last Defrost cycle or the
previous test window closed. If DFT2 is closed, the
Defrost cycle will start. Output at OF is re moved; outdoor
fans stop during the Defrost cycle. Output P3--6 (RVS2) is
energized; reversing valve solenoid RVS2 is energized and
reversing valve 2 changes position, placing Circuit 2 in a
Cooling mode flow, directing hot gas into the outdoor coil
where its heat melts the frost and looses the ice on the coil
face.
During the Defrost cycle, output EHEAT is also energized
(if not already energized by a thermostat W2 demand);
electric heaters will be energized.
During the Defrost Cycle, LED1 on the DFB will be
illuminated.
The Defrost cycle ends when DFT2 opens (as liquid
temperature exiting the coil rises above DFT2 setpoint) or
the defrost cycle runs for 10 m inutes. Output at EHEAT is
removed; electric heaters will be de--energized (unless
thermostat has a W2 dem and). Output at OF is restored;
outdoor fans start again. Output at P3--6 (RVS2) is
removed; reversing valve 2 returns to Heating position.
During the Circuit 2 defrost cycle, Circuit 1 may also
enter defrost cycle if DFT1 closes. When DFT1 closes,
DFB output P3--7 (RVS1) is energized; reversing valve
solenoid 1 is energized, causingreversing valve 1 to
switch position and place Circuit 1 in a Cooling mode
flow. Defrost in Circuit 1 ends when DFT1 opens or
defrost cycle in Circuit 2 is terminated.
Defrost cycle is fixed at a maximum 10 minute duration
limit. The period to test and initiate a Defrost cycle can be
selected at 30, 60, 90 or 120 minutes.
Emergency Heat
Emergency Heat is a non-- staged heating cycle that uses
the unit’s electric heaters only (no compression heating is
energized). Emergency Heat is initiated when the defrost
board receives an input signal at W2 (P2--6) but there is
no input signal at W1 (P2--7). This signal combination can
be provided by thermostat configuration, manual external
switch selection or by servicer disconnecting the W1 field
connection.
Upon initiation of the Emergency Heat sequence, the DFB
will issue output signals at IFO (P3--9) and EHEAT; IFM
will run and electric heaters will be energized.
When space heating load is satisfied, the input signal at
W2 (P2--6) will be removed. Output at EHEAT is
removed; electric heaters are de--energized. After the Fan
Delay period, the signal at IFO (P3--9) is removed; IFM
stops.
Demand Controlled Ventilation
If a field--installed sensor is connected to the EconoMi$er
IV control, a Demand Controlled Ventilation strategy will
operate automatically. As the level in the space increases
above the setpoi nt (on the EconoMi$er IV controller), the
minimum position of the dampers will be increased
proportionally, until the Maximum Ventilation setting is
reached. As the space level decreases because of the
increase in fresh air, the outdoor--dam per will follow the
higher demand condition from the DCV mode or from the
free--cooling mode.
DCV operation is available in Occupied and Unoccupied
periods withEconoMi$er IV.However,a control
modification will be required on the 50TC unit to
implement the Unoccupied period function.
Supplemental Controls
Compressor Lockout Relay ( CLO) – The CLO is available
as a factory-installed option or as a field-installed
accessory. Each compressor has a CLO. The CLO
compares the demand for compressor operation (via a
24-v input from Y at CL O terminal 2) to operat ion of the
compressor (determined via compressor current signal
input at the CLO’s current transformer loop); if the
compressor current signal is lost while the demand input
still exists, the CLO will trip open and prevent the
compressor from restarting until the CLO has been
manually reset. In the lockout condition, 24-v will be
available at terminal X. Reset is accomplished by
removing the input signal at terminal 2; open the
thermostat briefly or c ycle the main power to the unit.
Phase Monitor Relay (PMR) – The PMR protects the unit
in the event of a loss of a phase or a reversal of power line
phase in the three-phase unit power supply. In normal
operation, the relay K1 is energized (contact set closed)
and red LED indicator is on steady. If the PMR detects a
loss of a phase or a phase sequence reversal, the relay K1
is energized, its contact set is opened and unit operation is
stopped; red LED indicator will blink during lockout
condition. Reset of the PMR is automatic when al l phases
64
are restored and phase sequence is correct. If no 24-v
control power is available to the PMR, the red LED will
be off.
RTU--MP Sequence of Operation
The RTU--MP will control the compressor, economizer
and heating outputs based on its own space temperature
input and setpoints. An optional CO
in the space can influence the economizer minimum
position. The RTU--MP has its own hardware clock that is
set automatically when the software is installed on the
board. The RTU--MP’s default is to control to occupied
setpoints all the time, until a type of occupancy control is
set. Occupancy types are described in the scheduling
section. The following sections describe the operation for
the functions of the RTU--MP. All point objects that are
referred to in this sequence will be in reference to the
objects as viewed in BACview
Scheduling
Scheduling is used to start heating or cooling (become
occupied) based upon a day of week and a time period and
control to the occupied heating or cooling setpoints.
Schedulingfunctions arelocatedunder occupancy
determination and the schedule menu accessed by the
Menu softkey (see Form 48--50H--T--2T, Appendix -- for
menu structure). Your local time and date should be set
for these functions to operate properly. Five scheduling
functions are available by changing the Occupancy Source
to one of the following selections:
Always Occupied (Default Occupancy)
The unit will run continuously. RTU--MP ships from the
factory with this setting.
Local Schedule
The unit will operate according to the schedule configured
and stored in the unit. The local schedule is made up of
three hierarchy levels that consist of two Override
schedules, twelve Holiday and four Daily schedules, and
are only accessible by the BACview screen (handheld or
virtual).
The Daily schedule is the lowest schedule in the hierarchy
and is overridden by both the Holiday and Override
schedule. It consists of a start time, a stop time (both in 24
hour mode) and the seven days of the week, starting with
Monday and ending in Sunday. To sel ect a daily schedule
scroll to the Schedules menu off of the Menu selection.
Enter the User password and change the Occupancy
Source to Local Schedule. Scroll down a nd over to the
Daily menu and press enter. Choose one of the four Daily
schedules by pressing the Next softkey and change t he
Use? point from NO to YES by selecting the point and
pressing the INCR or DECR softkey. Press the OK softkey
and scroll to the start and stop times. Edit these times
following the same steps as the Use? point. Finally scroll
down to the Days: section and highlight the days required
for the Daily schedule by INCR or DECR softkeys and
press OK softkey.
The Holiday schedule is created to override the Daily
schedule and identify a specific day and month of the year
to start and stop the unit and change control to the
unoccupied heating and cooling setpoints. Follow the
same steps to turn on one of the twelve Holiday schedules
IAQ sensor mounted
2
6
Handheld.
and start and stop times. Next, select one out of the twelve
months and one out of the thirty--one days of that month.
The RTU--MP will now ignore the Daily schedule for the
specific day and time you selected and follow the Holiday
Schedule for this period.
The Override schedules primary purpose is to provide a
temporary change in the occupied heating and cooling
setpoints and force the unit to control to the unoccupied
heating and cooling setpoints. This would occur on a set
day in a particular month and last during the start a nd stop
time configured. The Override schedule is enabled by
following the same steps to create the Holiday schedule.
NOTE:Push button override is only available when
running a local or BACnet Schedule.
BACnet Schedule
For use with a Building Automation System that supports
native BACnet scheduling is scheduling the unit. With the
Occupancy Source set to BACnet schedule the BAS will
control the unit through network communi cation and it’s
own scheduling function.
BAS On/Off
The Building Automation System is scheduling the unit
via an On/Off command to the BAS ON/OFF software
point. The Building Automation System can be speaking
BACnet, Modbus, or N2 and is writing t o the BAS On/Off
point in the open protocol point map.
NOTE:If theBAS supports NATIVE BACnet
scheduling, then set the Occupancy Source to BACnet
schedule. If the BAS is BACnet but does NOT support
NATIVE BACnet scheduling, then set the Occupancy
Source to BAS On/Off.
DI On/Off
A hard--wired input on the RTU--MP will command the
unit to start/stop. Inputs 3, 5, 8, and 9 on plug J5 can be
hard--wired to command the unit to start/stop.
NOTE: Scheduling can either be controlled via the unit
or the BAS, but NOT both.
Indoor
Fan
The indoor fan will be turned on whenever any one of the
following conditions is true:
S It is in the occupied mode. This will be determined by its
own internal occupancy schedule.
S Whenever there is a demand for cooling or heating in the
unoccupied mode.
S Whenever the remote occupancy switch is closed during
DI On/Off schedule type or if occupa ncy is forced
occupied by the BAS during BAS On/Off schedule type.
When transitioning from unoccupied to occupied, there
will be a configured time delay of 5 to 600 seconds before
starting the fan. The fan will continue to run as long as
compressors, heating stages, or the dehumidification
relays are on when transitioning from occupied to
unoccupied with t he exception of Shutdown mode. If Fire
Shutdown, safety chain, SAT alarm or SPT alarm are
active; the fan will be shutdown immediately regardless of
the occupancy state or demand.
The RTU--MP has an optional Supply Fan Status input t o
provide proof of airflow. If this is enabled, t he point will
548J
65
look for a contact closure whenever the Supply Fan Relay
is on. If it is not enabled then it will always be the same
state as the Supply Fan Relay. The cooling, economizer,
heating, dehumidification,CO
and power exha ust
2
routines will use this input point for fan status.
Cooling
The compressor outputs are controlled by the Cooling
Control PID Loop and Cooling Stages Capacity algorithm.
They will be used to calculate the desired number of
stages needed to satisfy the space by comparing the Space
Temperature (SPT) to the Occupied Cool Setpoint plus the
T56 slider offset when occupied and the Unoccupied Cool
Setpoint (UCSP) plus the T56 slider offset, if unoccupied.
The economizer, if available, will be used for cooling in
addition to the compressors. The following conditions
must be true in order for this algorithm to run:
S Indoor Fan has been ON for at least 30 seconds.
548J
S Heat mode is not active and the time guard between
modes equals zero.
S If occupied and the SPT >(occupied cool setpoint plus
the T56 slider offset).
S Space Temperature reading is available.
S If it is unoccupi ed and the SPT > (unoccupied cool
setpoint plus the T56 slider offset). The indoor fan will be
turned on by the staging algorithm.
S If economizer is available and active and economizer
open > 85% and SAT > (SAT low limit + 5_F) and SPT >
effective setpoint + 0.5_F.
OR
Economizer is available, but not active
OR
Economizer is not available
S OAT > DX Lockout temperature.
If all of the above conditions are met, the compressors
will be energized as required, otherwise they will be
de--energized.
There is a fixed 3--minute minimum on time and a
5--minute off time for each compressor output and a
3--minute minimum time delay between staging up or
down.
Any time the compressors are running the RTU--MP will
stage down the compressors if the SAT becomes less than
the cooling low supply air setpoint.
After a compressor is staged off, it may be started again
after a normal time--guard period and the supply air
temperature has increased above the low supply air
setpoint.
Economizer
The Economizer dampers are used to provide free cooling
and Indoor Air Quality, if optional CO
sensor is installed,
2
when the outside conditions are suitable.
The following conditions must be true for economizer
operation:
S Indoor Fan has been on for at least 30 seconds.
S Enthalpy is Low if the Enthalpy input is ena bled.
S SAT reading is available.
S OAT reading is available.
S SPT reading is available.
S OAT <= High OAT economizer lockout configuration
(default = 75).
S OAT <= SPT
If any of the mentioned conditions are not true, the
economizer will be set to its configured minimum
position.Theminimumdamperpositioncanbe
overridden by the IAQ routine described later in this
section.
If the above conditions are true, the Economizer Control
Master Loop will calculate a damper position value based
on the following calculation:
Damper Position = minimum position + PID (SPT -- econ
setpoint). Econ setpoint is half way between the effective
cool and heat setpoints. If the SAT drops below the
cooling low supply air setpoint (+ 5_F), the economizer
will ramp down to minimum position.
Exhaust
Power
If RTU-- MP is also controlling an exhaust fan, it can be
enabled based on damper position or by occupancy. If
configured for continuous occupied operation, it will be
energized whenever the controller is in the occupied mode
and disabled when in the unoccupied mode. If configured
for damper position control, it will be energized whenever
the economizer exceeds the power exhaust setpoint and
disabled when t he economizer drops below the setpoint by
a fixed hysteresis of 10%.
Heating
The heating outputs are controlled by the Heating Control
PID Loop and Heating Stages Capacity algorithm. They
will be used to calculate the desired number of stages
needed to satisfy the space by comparing the SPT to the
Occupied Heat Setpoint plus the T56 slider offset when
occupied and the Unoccupied Heat Setpoint plus the T56
slider offset if unoccupied. The following conditions must
be true in order for this algorithm to run:
S Indoor Fan has been ON for at least 30 seconds.
S Cool mode is not active and the time guard between
modes equals zero.
S If occupied and SPT <(occupied heat setpoint plus T56
slider offset)
S SPT reading is available
S If it is unoccupi ed and the SPT < (unocc upied he at
setpoint plus T56 slider offset). The indoor fan will be
turned on by the staging algorithm.
S OAT < High OAT lockout temperature.
If all of the above conditions are met, the heating outputs
will be energized as required, otherwise they will be
de--energized. If the SAT begins to exceed the high supply
air setpoint, a ramping function will cause the Heat Stages
Capacity algorithm to decrease the number of stages until
the SAT has dropped below the setpoint.
There is a fixed one minute minimum on time and a one
minute off time for each heat output. Heat staging has a 3
minute stage up and 30 second stage down delay.
Indoor Air
Quality
If the optional indoor air quality sensor is installed, the
RTU--MP will maintain indoor air quality within the space
at the user configured differential setpoint. The setpoint is
66
the difference between the indoor air quality and an
optional outdoor air quality sensor. If the outdoor air
quality is not present then a fixed value of 400ppm is
used. The following conditions must be true in order for
this algorithm to run:
S The mode is occupied.
S Indoor Fan has been ON for at least 30 seconds.
S Indoor Air Quality sensor has a valid reading
As air quality within the space changes, the minimum
position of the economizer damper will be changed thus
allowing more or less outdoor air into the space depending
on the relationship of the indoor air quality to the
greatest value becomes the final minimum damper
position of the economizer output.
If the calculated IAQ minimum position is greater than
the IAQ maximum damper position configuration then it
will be clamped to the configured value.
Demand
Limit
If the RTU--MP receives a level 1 (one degree offset), 2
(two degree offset), or a 3 (4 degree offset) to the BACnet
demand limit variable, the controller will expand the
heating and cooling setpoints by the configured demand
limit setpoint value and remain in effect until the BACnet
demand limit variable receives a 0 value.
differential setpoint. If all the above conditions are true,
the IAQ algorithm will run and calculates an IAQ
FASTENER TORQUE VALUES
minimum position value using a PID loop. The IAQ
minimum damper position is then compared against the
See Table 24 for torque value s.
user configured economizer minimum position and the
Table 24 – T orque Values
Supply fan motor mounting120 ¦ 12 in --- lbs13.6 ¦ 1.4 Nm
Supply fan motor adjustment plate120 ¦ 12 in ---lbs13.6 ¦ 1.4 Nm
Motor pulley setscrew72 ¦ 5 i n --- l bs8.1 ¦ 0.6 Nm
Fan pulley setscrew72 ¦ 5 i n --- l b s8.1 ¦ 0.6 Nm
Blower wheel hub setscrew72 ¦5in---lbs8.1 ¦0.6 Nm
Bearing locking collar setscrew65 to70 in --- lbs7.3 to 7.9 Nm
Compressor mounting bolts65 to75 in --- lbs7.3 to 7.9 Nm
Condenser fan motor mounting bolts65 to75 in ---lbs7.3 to 7.9 Nm
Condenser fan motor mounting bolts20 ¦ 2 i n --- l bs2.3 ¦ 0.2 Nm
Condenser fan hub setscrew84 ¦ 1 2 i n --- l bs9.5 ¦ 1.4 Nm
548J
04A ---06A Direct - -- Drive:
Motor mount arm60 ¦ 5 i n --- l b s6.8 ¦ 0.5 Nm
Fan wheel hub setscrew120 ¦ 12 in --- lbs13.6 ¦ 1.4 Nm
Motor belly band bolt80 ¦ 5 i n --- l bs9.0 ¦ 0.6 Nm
67
APPENDIX I. MODEL NUMBER SIGNIFICANCE
MODEL NUMBER NOMENCLATURE
123456789101112131415161718
548J P06 A000 A0 B 0A A--
________________________________
Unit TypeDesign Revision
548J = High Eff. Heat Pump--- = First Revision
VoltagePackaging
E = 4 6 0 --- 3 --- 6 0A=Standard
J = 208/230 --- 1 --- 60B=LTL
P = 208/230 - -- 3 --- 60
T = 5 7 5 --- 3 --- 6 0
Cooling Tons
548J
04=3Ton07=6TonOutdoor Air Options
05 = 4 Ton08 = 7.5 TonA=None
06 = 5 Ton09 = 8.5 TonB=Tempeconow/barorelief
Refrig. System OptionsH = Enthalpy econo w/ baro relief
A = One---Stage Cooling ModelsL = Enthalpy econo w/ baro relief & CO
Cu / AI: Copper Tube / Aluminum Fin
RTPF: Round Tube / Plate Fin
70
APPENDIX III. FAN PERFORMANCE
General Fan Performance Notes:
1. Interpolation is permissible. Do not extrapolate.
2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static
pressure caused by any FIOPs or accessories.
3. Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories
may add static pressure losses.
4. The Fan Performance tables offer motor/drive rec ommendations. In cases when two motor/drive combinations would
work, Bryant recommended the lower horsepower option.
5. For information on the electrical properties of Bryant’s motors, please see the Electrical information section of this
book.
548J
71
APPENDIX III. FAN PERFORMANCE
Table 25 – 548J*04A ELECTRIC DRIVE, X13
MOTOR, 3 TON HORIZONTAL SUPPLY
CO--- Convenient outlet
DISC--- Disconnect
FLA--- Full load amps
IFM--- Indoor fan motor
LRA--- Locked rotor amps
MCA--- Minimum circuit amps
MOCP--- Maximum over current protection
P E--- P ow er e xh au st
UNPWR CO- -- Unpowered convenient outlet
NOTES:
1. In compliance with NEC requirements for multimotor and
combination load equipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. Canadian units may b e fuse or circuit
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.
548J
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
Example: Supply voltage is 230-3-60
AB = 224 v
BC = 231 v
AC = 226 v
(224 + 231 + 226)
=227
= 1.76%
average voltage
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance= 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
NOTE: Component arrangement on Control; Legend on Power Schematic
* The RTU-- MP control label overlays a portion of the base unit control label. The base unit label drawing and the control option drawing are required to
provide a complete unit control diagram.
96
APPENDIX VI. MOTORMASTER SENSOR LOCATIONS
Sensor
Sensor
Location
Location
548J
Fig. 81 -- 548J*04A Outdoor Circuiting
Sensor
Location
C09191
C09193
Fig. 83 -- 548J*06A Outdoor Circuiting
Sensor
Location
Fig. 82 -- 548J*05A Outdoor Circuiting
C09192
C09194
Fig. 84 -- 548J*07A Outdoor Circuiting
97
548J
APPENDIX VI. (cont) MOTORMASTER SENSOR LOCATIONS
Sensor
Location
Fig. 85 -- 548J*08D/09D Outdoor Circuiting
C09195
E2009 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231Printed in U.S.A.Edition Date: 06/09
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
98
Catalog No. SM548J---01
Replaces: NEW
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.:SERIAL NO.:
DA TE:TECHNICIAN:
II. PRE-START-UP (insert checkmark in box as each item is completed)
jVERIFY THA T JOBSITE VOLT AGE AGREES WITH VOLT AGE LISTED ON RA TING PLATE
jVERIFY THA T ALL P ACKAGING MA TERIALS HA VE BEEN REMOVED FROM UNIT
jREMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS
jVERIFY THA T CONDENSA TE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
jCHECK REFRIGERANT PIPING FOR INDICA TIONS OF LEAKS; INVESTIGATE AND REP AIR IF NECESSARY
jCHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
jCHECK THA T RETURN (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE
jVERIF Y THAT UNIT INST ALLATION IS LEVEL
jCHECK FAN WHEELS AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW
TIGHTNESS
jCHECK TO ENSURE THA T ELECTRICAL WIRING IS NOT IN CONTACT WITH REFRIGERANT LINES
OR SHARP METAL EDGES
j CHECK PULLEY ALIGNMENT AND BEL T TENSION PER INSTALLATION INSTR UCTIO NS
III. START-UP
548J
ELECTRICAL
SUPPLY VOLT AGEL1-L2L2-L3L3-L1
CIRCUIT 1 COMPRESSOR AMPSL1
CIRCUIT 2 COMPRESSOR AMPSL1
INDOOR-FAN AMPS
OUTDOOR-FAN AMPSNO. 1NO. 2
TEMPERATURES
OUTDOOR-AIR TEMPERATUREDBWB
RETURN-AIR TEMPERATURE
COOLING SUPPLY AIR
PRESSURES (Cooling Mode)
REFRIGERANT SUCTION, CIRCUIT 1PSIGF
REFRIGERANT SUCTION, CIRCUIT 2
REFRIGERANT DISCHARGE, CIRCUIT 1
REFRIGERANT DISCHARGE, CIRCUIT 2
DBWB
DBWB
PSIGF
PSIGF
PSIGF
L2L3
L2L3
jVERIFY THA T 3-PHASE FAN MOTOR AND BLOWER ARE ROTATING IN CORRECT DIRECTION.
jVERIFY THA T 3-PHASE SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION
jVERIFY REFRIGERANT CHARGE USING CHARGING CHARTS
GENERAL
j SET ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO MATCH JOB REQUIREMENTS
(IF EQUIPPED)
99
548J
E2009 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231Printed in U.S.A.Edition Date: 06/09
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
100
Catalog No. SM548J---01
Replaces: NEW
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.