SINGLE PACKAGE HEAT PUMP/ELECTRIC HEAT
NOMINAL 3 TO 8.5 TONS
WITH PURON
R
(R--410A) REFRIGERANT
Service and Maintenance Instructions
TABLE OF CONTENTS
SAFETY CONSIDERATIONS1....................
UNIT ARRANGEMENT AND ACCESS3...........
SUPPLY FAN (BLOWER) SECTION4..............
HEAT PUMP REFRIGERATION SYSTEM8.........
PURON
COOLING CHARGING CHARTS14................
CONVENIENCE OUTLETS19....................
HEAT PUMP CONTROLS20......................
PROTECTIVE CONTROLS20.....................
COMMERCIAL DEFROST CONTROL21...........
ELECTRIC HEATERS24.........................
SMOKE DETECTORS26.........................
RTU--MP CONTROL SYSTEM33..................
ECONOMIZER SYSTEMS47.....................
WIRING DIAGRAMS56.........................
PRE--START-UP58..............................
START-UP, GENERAL58.........................
START-UP, RTU--MP CONTROL59................
OPERATING SEQUENCE62......................
FASTENER TORQUE VALUES67.................
APPENDIX I. MODEL NUMBER SIGNIFICANCE68...
APPENDIX II. PHYSICAL DATA69................
APPENDIX III. FAN PERFORMANCE71...........
R
(R--410A) REFRIGERANT13.............
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical
components. Only trained and qualifi ed service personnel
shouldinstall,repair,orserviceair-conditioning
equipment. Untrained personnel can perform the basic
maintenance functions of replacing filters. Trained service
personnel should perform all other operations.
When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to
the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations.
Havefireextinguishersavailableforallbrazing
operations.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have
fireextinguisher available.Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety--alert
symbol
instructions or manuals, be alert to the potential for
personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert
symbol. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies a hazard which could result in
personal injury or death. CAUTION is used to identify
unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
. When you see this symbol on the unit and in
APPENDIX IV. ELECTRICAL INFORMATION82....
APPENDIX V. WIRING DIAGRAM LIST96.........
APPENDIX VI. MOTORMASTER SENSOR
LOCATIONS97.................................
UNIT START-UP CHECKLIST99..................
!
WARNING
!
WARNING
548J
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Before performing service or maintenance operations
on unit, turn off main power switch to unit. Electrical
shock and rotating equipment could cause injury.
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience out let circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Tag--out this switch, if necessary.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
Puron (R--410A) refrigerant systems operate at higher
pressures than standard R--22 system s. Do not use
R--22 service equipment or components on Puron
refrigerant equipment.
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause personal
injury or death. Relieve pressure and recover all
refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling
refrigerants. Keep torches and other ignition sources
away from refrigerants and oils.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts and servicing
air conditioning units.
2
UNIT ARRANGEMENT AND ACCESS
Seasonal Maintenance
General
Fig. 1 and Fig. 2 show general unit arrangement and
access locations.
CONTROL BOX
INDOOR BLOWER
ACCESS
COMPRESSORS
(D08-09 only)
C09190
Fig. 1 -- Typical Access Panel Location (Front)
FILTER ACCESS PANEL
These items should be checked at the beginning of each
season (or more often if local conditions and usage
patterns dictate):
Air Conditioning/Heat
Pump
S Outdoor fan motor mounting bolts tightness
S Compressor mounting bolts
S Outdoor fan blade positioning
S Control box cleanliness and wiring condition
S Wire terminal tightness
S Refrigerant charge level
S Indoor coil cleaning
S Supply blower motor amperage
Electric
Heating
S Power wire connections
S Fuses ready
S Manual--reset limit switch is closed
Economizer or Outside Air
Damper
S Inlet filters condition
S Check damper travel (economizer)
S Check gear and dampers for debris and dirt
Air Filters and Scr
eens
548J
INDOOR COIL ACCESS PANEL
C08449
Fig. 2 -- Typical Access Panel Locations (Rear)
Routine Maintenance
These items should be part of a routine maintenance
program, to be checked every month or two, until a
specific schedule for each can be identified for this
installation:
Quarterly Inspection (and 30 days after initial start
S Return air filter replacement
S Outdoor hood inlet filters cleaned
S Belt tension checked
S Belt condition checked
S Pulley alignment checked
S Fan shaft bearing locking collar tightness chec ked
S Outdoor coil cleanliness checked
S Condensate drain checked
)
Each unit is equipped with return air filters. If the unit has
an economizer, it will also have an outside air screen. If a
manual outside air damper is added, an inlet air screen
will also be present.
Each of these filters and screens will need to be
periodically replaced or cleaned.
Return Air
Filters
Return air filters are disposable fiberglass media type.
Access to the filters is through the small lift--out panel
located on the rear side of the unit, above the
evaporator/return air access panel. (See Fig. 1.)
To remove the filters:
1. Grasp the bottom flange of the upper panel.
2. Lift up and swing the bottom out until the panel disengages and pulls out.
3. Reach inside and extract the filters from the filter
rack.
4. Replace these filters as required with similar replacement filters of same size.
To re--install the access panel:
1. Slide the top of the panel up under the unit top panel.
2. Slide the bottom into the side channels.
3. Push the bottom flange down until it contacts the top
of the lower panel (or economizer top).
IMPORTANT:DONOTOPERATETHEUNIT
WITHOUT THESE FILTERS!
3
Outside Air Hood
Outsideairhoodinletscreensarepermanent
aluminum--mesh type filters. Check these for cleanliness.
Remove the screens when cleaning is required. Clean by
washing with hot low--pressure water and soft detergent
and replace all screens before restarting the unit. Observe
the flow direction arrows on the side of each filter frame.
Economizer Inlet Air Screen
This air screen is retained by spring clips under the top
edge of the hood. (See Fig. 3.)
548J
BAROMETRIC
RELIEF
DIVIDER
CLEANABLE
ALUMINUM
FILTER
OUTSIDE
AIR
FILTER
HOOD
Fig. 3 -- Filter Installation
To remove the filter, open the spring clips. Re--install the
filter by placing the frame in its track, then closing the
spring clips.
FILTER
CLIP
C08634
SUPPLY FAN (BLOWER) SECTION
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause persona l
injury or death.
Before performing service or maintenance operations
on the fan system, shut off all unit power and tag--out
the unit disconnect switch. Do not reach into the fan
section with power still applied to unit.
Supply Fan (Direct--Drive)
For unit sizes 04, 05 and 06, the Standard Static supply
fan system consists of a direct--drive forward--curved
centrifugal blower wheel attached to the motor shaft. The
motor has taps to provide the servicer with the selection of
one of five motor torque/speed ranges to best match wheel
performance with attached duct system. See Fig. 5 (548J
Direct--Drive Fan Assembly) and Fig. 6 (EMC Motor
Connectors).
EMC Motor
95°
Motor Plug Position
(95° from vertical)
EMC Power
Transformer
(460, 575v)
Manual Outside Air Hood Screen
This inlet screen is secured by a retainer angle across the
top edge of the hood. (See Fig. 4.)
C07156
Fig. 4 -- Screens Installed on Outdoor--Air Hood
(Sizes 08D--09D Shown)
To remove the screen, loosen the screws in the top retainer
and slip the retainer up until the filter can be removed.
Re--install by placing the frame in its track, rotating the
retainer back down and tighten all screws.
Fig. 5 -- 548J Direct--Drive Supply Fan Assembly
L2
YEL
Gnd
GRN/YEL
L1
BLU
C
LGN
Com
BRN
Speed
Taps
12345
VIO
Default Connection
Fig. 6 -- EMC Motor Connectors
C09260
Motor
Power
Connections
C09261
4
460, 575-v Units
208/230-v Units
Fig. 7 -- EMC Unit Wiring
548J
C09263
ECM Motor – The direct--drive motor is an X13
Electronically Commutated motor (ECM). An ECM
contains electronic circuitry to convert single--phase line
AC voltage into a 3--phase DC voltage to power the motor
circuit. The motor circuit is a DC brushless design with a
permanent magnet rotor. On the X13 design, the
electronic circuitry is integral to the motor assembly and
cannot be serviced or replaced separately.
208/230--v units use a 230--v motor. 460--v units use a
230--v motor with a stepdown transformer (mounted on
the end of the fan housing, see Fig. 5). 575--v units use a
460--v motor with an autotransformer. Motor power
voltage is connected to motor terminals L and N (see
Fig. 6 and Fig. 7); ground is connected at te rminal G.
The motor power voltage is ALWAYS present; it is not
switched off by a motor contactor.
Motor operation is initiated by the presence of a 24-- v
control signal to one of the fi ve motor communications
terminals. When the 24--v signal is removed, the motor
will stop. The motor control signal is switched by the
defrost board’s IFO output.
Evaluating motor speed – The X13 ECM is a constant
torque motor design. The motor speed is adjusted by the
motor control circuitry to maintain the programmed shaft
torque. Consequently there is no specific speed value
assigned to each control tap setting. At the Position 5 tap,
the motor speed is approximately 1050 RPM (17.5 r/s) but
it will vary depending on fan wheel loading.
Selecting speed tap – The five communications terminals
are each programmed to provide a different motor torque
output. See Table 1. Factory default tap selection is
Position 1 for lowest torque/speed operation.
Table 1 – 548J Standard Static Motor Tap Programing
(percent of full--load torque)
Unit SizeTa p 1Tap 2Ta p 3Ta p 4Tap 5
0432384550100
0546586169100
0673828590100
Factory Default: Tap 1 (VIO)
To select another speed:
1. Disconnect main power to the unit.
2. Remove the motor signal lead (VIO) a t the motor
communications terminal.
3. Reconnect the motor signal lead to the desired speed
terminal.
4. Connect main power to the unit.
Motor “rocking” on start--up – When the motor first starts,
the rotor (and attached wheel) will “rock” back and forth
as the motor tests for rotational direction. Once the correct
rotation direction is determined by the motor circuitry, the
motor will ramp up to specified speed. The “rocking” is a
normal operating characteristic of ECM motors.
Troubleshooting the ECM motor – Troubleshooting the
X13 ECM requires a voltmeter.
1. Disconnect main power to the unit.
2. Remove the motor power plug (including the control
BRN lead) and VIO control signal lead at the motor
terminals.
3. Restore main unit power.
4. Check for proper line vol tage at motor power leads
BLK (from L terminal) and YEL (from N terminal).
5
Table 2 – Motor Test Volts
Unit VoltageMotor VoltageMin ---Max Volts
208/230230190---250
460230210---250
575460420---500
5. Apply a jumper at uni t control terminals R to G to
initiate a demand for motor operation. Check for 24--v
output at defrost board terminal IFO.
6. Check for proper control signal voltage at motor
signal leads VIO and BRN. Signal should be 22 to
28--v.
7. Disconnect unit main power.
8. Reconnect motor power and control signal leads at
the motor terminals.
9. Restore unit main power.
Motor should start and run. If it does not, remove the
548J
motor assembly. Replace with same motor part number;
do not substitute with an alternate design as torque/speed
programming will not be same as on original factory
motor.
Replacing the ECM Motor – Before removing the ECM
belly--band mounting ring, measure the distance between
the base of the motor shaft and the edge of the mounting
ring. Remove the motor mounting band and transfer to the
replacement motor. Position the mounting band at
distance measured in first step. Snug the mounting bolt
but do not tighten yet.
Insert the motor shaft into the fan wheel hub. Then secure
the three motor mount arms to the support cushions.
Torque the arm mounting screws to 60 in--lbs (6.8 N--m).
Center the fan wheel in the fan housing. Torque the fan
wheel hub setscrew to 120 in -- lbs (13.6 N--m).
Ensure the motor terminals are located at a position below
the 3 o’clock position (see Fig. 5). Tighten the motor
belly--band bolt to 80 in--lbs (9.0 N--m).
Supply Fan (Belt--Drive)
Thebelt--drivesupplyfansystemconsistsofa
forward--curved centrifugal blower wheel on a solid shaft
with two concentric type bearings, one on each side of the
blower housing. A fixed--pitch driven pulley is attached to
the fan shaft and an adjustable--pitch driver pulley is on
the motor. The pulleys are connected using a “V” type
belt. (See Fig. 8.)
C07087
Fig. 8 -- Belt Drive Motor Mounting
Belt
Check the belt condition and tension quarterly. Inspect the
belt for signs of cracking, fraying or glazing along the
inside surfaces. Check belt tension by using a spring--force
tool (such as Browning’s Part Number “Belt Tension
Checker” or equivalent tool); tension should be 6--lbs at a
5
/8--in. deflection when measured at the centerline of the
belt span. This point is at the center of the belt when
measuring the distance between the motor shaft and the
blower shaft.
NOTE: Without the spring--tension tool, place a straight
edge across the belt surface at the pulleys, then deflect the
1
belt at mid--span using one finger to a
/2--in. deflection.
Adjust belt tension by loosening the motor mounting plate
front bolts and rear bolt and sliding the plate toward the
fan (to reduce tension) or away from fan (to increase
tension). Ensure the blower shaft and the motor shaft are
parallel to each other (pulleys aligned). Tighten all bolts
when finished.
To replace the belt:
1. Use a belt with same section type or similar size. Do
not substitute a “FHP” type belt. When installing the
new belt, do not use a tool (screwdriver or pry--bar) to
force the be lt over the pulley flanges, this will stress
the belt and cause a reduction in belt life.
2. Loosen the motor mounting plate front bolts and rear
bolts.
3. Push the motor and its mounting plate towards the
blower housing as close as possible to reduce the center distance between fan shaft and motor shaft.
4. Remove the belt by gently lifting the old belt over
one of the pulleys.
5. Install the new belt by gentl y sliding the belt over
both pulleys and then sliding the motor and plate
away from the fan housing until proper tension is
achieved.
6. Check the alignment of the pulleys, adjust if necessary.
7. Tighten all bolts.
8. Check the tension after a few hours of runtime and
re--adjust as required.
6
Adjustable--Pitch Pulley on Motor
The motor pull ey is an adjustable--pitch type that allows a
servicer to implement changes in the fan wheel speed to
match as--installed ductwork systems. The pulley consists
of a fixed flange side that faces the motor (secured to the
motor shaft) and a movable flange side that can be rotated
around the fixe d flange side that increases or reduces the
pitch diameter of this driver pulley. (See Fig. 9.)
4. Recheck belt tension.
Bearings
This fan system uses bearings featuring concentric split
locking collars. The collars are tightened through a cap
screw bridging the split portion of the collar. The cap
screw has a Torx T25 socket head. To tighten the locking
collar: Hold the locking collar tightly against the inner
race of the bearing and torque the cap screw to 65--70
in--lb (7.4--7.9 Nm). See Fig. 10.
548J
C07075
Fig. 9 -- Supply--Fan Pulley Adjustment
As the pitch diameter is c hanged by adjusting the position
of the movable flange, the centerline on this pul ley shifts
laterally (along themotor shaft). This creates a
requirement for a realignment of the pulleys aft er any
adjustment of the movable flange. Also reset the belt
tension after each realignment.
Check the condition of the motor pulley for signs of wear.
Glazing of the belt contact surfaces and e rosion on these
surfaces are signs of improper belt tension and/or belt
slippage. Pulley replacement may be necessary.
To change fan speed:
1. Shut off unit power supply.
2. Loosen belt by loosening fan motor mounting nuts.
(See Fig. 8.)
3. Loosen movable pulley flange setscrew. (See Fig. 9.)
4. Screw movable flange toward fixed flange t o increase
speed and away from fixed flange to decrease speed.
Increasing fan speed increases load on motor. Do not
exceed maximum speed specified.
5. Set movable fla nge at nearest keyway of pulley hub
and tighten setscrew to torque specifications.
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft. Make angular alignment by loosening motor from mounting.
3. Tighten fan pulley setscrews and motor mounting
bolts to torque specifications.
C08121
Fig. 10 -- Tightening Locking Collar
Motor
When replacing the motor, also re place the external--tooth
lock washer (star washer) under the motor mounting base;
this is part of the motor grounding system. Ensure the
teeth on the lock washer are in contact with the motor’s
painted base. Tighten motor mounting bolts to 120 +/-- 12
in--lbs.
Changing fan wheel speed by changing pulleys: The
horsepower rating of the belt is primarily dictated by the
pitch diameter of the smaller pulley in the drive system
(typically the motor pulley in these units). Do not install a
replacement motor pulley with a smaller pitch diameter
than provided on the original factory pulley. Change fan
wheel speed by changing the fan pulley (larger pitch
diameter to reduce wheel speed, smaller pitch diameter to
increase wheel speed) or select a new system (both
pulleys and matching belt(s)).
Before changing pulleys to increase fan wheel speed,
check the fan performance at the target speed and airflow
rate to determine new motor loading (bhp). Use the fan
performance tables or use the Packaged Rooftop Builder
software program. Confirm that the motor in this unit is
capable of operating at the new operating condition. Fan
shaft loading increases dramatically as wheel speed is
increased.
To reduce vibration, replace the motor’s adjustable pitch
pulley with a fixed pitch pulley (after the final airflow
balance adjustment). This will re duce the amount of
vibration generated by the motor/belt--drive system.
7
HEAT PUMP REFRIGERATION
SYSTEM
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause persona l
injury, death and/or equipment damage.
This system uses Puron
higher pressures than R--22 and ot her refrigera nts. No
other refrigerant may be used in this system. Gauge
set, hoses, and recovery system must be designed to
handle Puron refrigerant. If unsure about equipm ent,
consult the equipm ent manufacturer.
R
refrigerant which has
NOTE: Use of a water stream, such as a garden hose,
against a surface loaded coil will drive the fibers and dirt
into the coil. This will make cleaning efforts more
difficult. Surface loaded fibers must be completely
removed prior to using low velocity clean water rinse.
Periodic Clean Water
A periodic clean water rinse is very beneficial for coils
that are appli ed in coastal or industrial environments.
However, it is very important that the water rinse is made
with very low velocity water stream to avoid damaging
the fin edges. Monthly cleaning as described below is
recommended.
!
Rinse
CAUTION
Outdoor Coil
548J
The 548J outdoor coil is fabricated with round tube
copper hairpins and plate fins of various materials and/or
coatings (see “Appendi x I -- Model Number Significance”
to identify the materials provided in this unit). All unit
sizes use composite--type two--row coils. Composite
two--row coils are two single--row coils fabricated with a
single return bend end tubesheet.
Indoor Coil
The indoor coil is traditional round--tube, plate --fin
technology. Tube and fin construction is of various
optional materials and coatings (see Model Number
Format). Coils are multiple--row.
Outdoor Coil Maintenance and Cleaning
Recommendation
Routine cleaning of coil surfaces is essential to maintain
proper operation of the unit. Elimination of contamination
and removal of harmful residues will greatly increase the
life of the coil and extend the life of the unit. The
following maintenance and cleaning procedures are
recommended as part of the routine maintenance activities
to extend the life of the coil.
Remove Surface Loaded
Surface loaded fibers or dirt should be removed with a
vacuum cleaner. If a vacuum cleaner is not available, a
soft non--metallic bristle brush may be used. In either
case, the tool should be applied in the direction of the fins.
Coil surfaces can be easily damaged (fin edges can be
easily bent over and damage the coating of a protected
coil) if the tool is applied across the fins.
Fibers
PERSONALINJURY ANDUNIT DAMAGE
HAZARD
Failure to follow this caution may result in personal
injury or equipment damage.
Only approved cleaning is recommended.
Routine Cleaning of Indoor Coil Surfaces
®
Periodic cleaning with Totaline
coil cleaner is essential to e xtend the life of coils. This
cleaner is available from our Replacement Components
Division as part number P902--0301 for one gallon
container, a nd part number P902--0305 for a 5 gallon
container. It is recommended that all coils, including
standardaluminum,pre--coated,copper/copperor
E--coatedcoilsbecleanedwiththeTotaline
environmentally sound coil cleaner as described below.
Coil cleaning should be part of the unit’s regularly
scheduled maintenance procedures to ensure long life of
the coil. Failure to clean the coils may result in reduced
durability in the environment.
Avoid the use of
S coil brighteners
S acid cleaning prior to painting
S high pressure washers
S poor quality water for cleaning
Totalineenvironmenta llysoundcoilcleaneris
nonflammable, hypoallergenic, non bacterial, and a
USDA accepted biodegradable agent that will not harm
the coil or surrounding components such as electrical
wiring, painted metal surfaces, or insulation. Use of
non--recommended coil cleaners is strongly discouraged
since coil and unit durability could be affected.
environmentally sound
Clean coil as follows:
1. Turn off unit power, tag disconnect.
2. Remove top panel screws on outdoor coil end of unit.
3. Remove coil corner post. See Fig. 11. To hold top
panel open, place coil corner post between top panel
and center post. See Fig. 12.
7. Secure inner a nd outer coil rows together with a
field--supplied fastener.
8. Reposition the outer coil section and remove the coil
corner post from between the top panel and center
post. Reinstall the coil corner post and replace all
screws.
Failure to follow this caution may result in corrosion
and damage to the unit.
Harsh chemicals, household bleach or acid or basic
cleaners should not be used to clean outdoor or indoor
coils of any kind. These cleaners can be very difficult
to rinse out of the coil and can accelerate corrosion at
the fin/tube interface where dissimilar materials are in
contact. If there is dirt below the surface of the coil,
use the Totali ne environmentally sound coil cleaner as
described above.
548J
C08206
Fig. 12 -- Propping Up Top Panel
4. For Sizes 04--07: Remove screws securing coil to
compressor plate and compressor access panel.
5. For Sizes 08--09: Remove fastener holding coil sections together at return end of condenser coil. Ca refully separate the outdoor coil section 3 to 4 in. from
the inner coil section. See Fig. 13.
OUTDOOR
COIL
C09220
Fig. 13 -- Separating Coil Sections
6. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced
unit performance.
High velocity water from a pressure washer, garden
hose, or compressed air should never be used to clean
a coil. The force of the water or air jet will bend the
fin edges and increase airside pressure drop.
1. Proper eye protection such as safety glasses is recommended during mixing and application.
2. Remove all surface loaded fibers and dirt with a vacuum cleaner as described above.
3. Thoroughly wet finned surfaces with clean water and
a low velocity garden hose, being carefull not to bend
fins.
4. Mix Totaline environmentally sound coil cleaner in a
1
/2gallon garden spryer according to the instruc-
2
tions included with the cleaner. The optimum solution
temperature is 100°F(38°C).
NOTE: Do NOT USE water in excess of 130°F(54°C), as
the enzymatic activity will be destroyed.
5. Thoroughly apply Totaline environmentally sound
coil cleaner solution to all coil surfaces including
finned area, tube sheets and coil headers.
6. Hold garden sprayer nozzle close to finned areas and
apply cleaner with a vertical, up--and--down motion.
9
Avoid spraying in horizontal pattern to minimize potential for fin damage.
7. Ensure cleaner thoroughly penetrates deep into finned
areas.
8. Interior and e xterior finned areas must be thoroughly
cleaned.
9. Finned surfaces should remain wet with cleaning
solution for 10 minutes.
10. Ensure surfaces are not allowed to dry before rinsing.
Reapply cleaner as needed to ensure 10--minute saturation is achieved.
11. Thoroghly rinse all surfaces with low velocity clean
water using downward rinsing motion of water spray
nozzle. Protect fins from damage from the spray
nozzle.
Indoor Coil
Cleaning the Indoor Coil
548J
1. Turn unit power off. Install lockout tag. Remove indoor coil access panel.
2. If economizer or two--position damper is installed, remove economizer by disconnecting Molex plug and
removing mounting screws.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister. Wash
both sides of coil and flush with clean water. For best
results, back--flush toward return--air section to remove foreign material. Flush condensate pan after
completion.
Filter
Drier
LPS/LOC
2B
5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.
Refrigeration System
Components
Eachheatpumprefrigerationsystemincludesa
compressor, accumulator, reversing valve, dual--function
outdoor coil with vapor header check valve, cooling liquid
line with filter drier and check valve, dual--function
indoor coil with vapor header check valve, and heating
liquid line with check valve and strainer. Unit sizes
04A--07A have a single compressor--circuit; unit sizes
08D and 09D have two compressor--circuits. See Fig. 14
for typical unit piping schematic (unit size 09D (4--row
indoor coil) with two compressor--circuits is depicted).
Dual--function outdoor and indoor coils are designed to
provide parallel coil circuits during evaporator--function
operationandconvergingcoilcircuitsduring
condenser--function operation.
Refrigerant flow metering in the evaporator--function
sequence is provided by multiple Acutrols – fixed--bore
metering devices that are located in the tee nipples
between the liquid header and the entrance to each coil
circuit. The Acutrol metering device is swaged into the
nipple tube between the liquid header end and the
side--port tube. See Fig. 15. During evaporator--function
operation, flow is straight through the nipple and into each
evaporator circuit. Flow continues through the parallel
evaporator circuits and into the vapor heade r.
DFT 2
Acutrol
DFT 1
Outdoor Coil
1B
1A
ACCUMULATOR
2A
Heating Mode Liquid Lines
Cooling Liquid Lines
HPS
COMPRESSOR
Comp 2
ACCUMULATOR
COMPRESSOR
2C
HPS
Comp 1
2D
1D
Indoor Coil
1C
Strainer
Fig. 14 -- Typical Unit Piping Schematic (09D unit with 4--row indoor coil)
Acutrol
C09228
10
To
r
r
Evaporato
Coil
Circuits
Metering
Orifice
From
Liquid
Header
C09229
Fig. 15 -- Heat Pump Acutrol — Flow as Evaporator
Function
Converging circuitflow inthe condenser--function
operation is accomplished with the check valve in the
vapor header and the liquid transfer header connected to
the side ports on all but one of the Acurator tee nipples in
each circuit. During condenser --function operation, hot gas
from the compressor discharge enters the header until it
reaches the check valve which blocks further flow. The
hot gas exits the header through the tubes above the check
valve and enters these coil circuits. At the outlet of these
desuperheating and condensing circuits, the refrigerant
enters the Acurater tees from the coil end. The refrigerant
exits the tee at the side port and enters the liquid transfer
header (see Fig. 16). The refrigerant moves through the
liquid transfer header and exits through the remai ning
tubes, through the side ports on the Acutrol tees (see
Fig. 17) and back into the coil circuits where additional
condensing occurs. These circuits exit into the vapor
header behind the check valve and exit through the
remaining tube on the vapor header. In this last pass
through the coil, the refrigerant is subcooled. Subcooled
liquid exits at the last Acutrol tee (see Fig. 18) where the
side port is connected to the specific mode liquid line.
From
Condenser
Coil Circuits
To
Condensing
Circuit
From
Transfer
Header
C09231
Fig. 17 -- Heat Pump Acutrol — Flow as Condenser
Function/Entering Second Pass
DFT Location
(Outdoor Coils only)
From
Subcoole
Circuit
To
Liquid
Line
C09232
Fig. 18 -- Heat Pump Acutrol — Flow as Condenser
Function/ Exiting Subcooler Pass
Each liquid line has a check valve to prevent backflow
through the liquid line in its opposite mode. Thi s ensures
correct flow direction through filter driers and strainers
and prevents emptying of off-- mode liquid lines into
evaporator--function coil circuits.
Reversing Valve and Check Valve Position
SeeFig.14onpage10.
Table 3 – Cooling Mode (each circuit)
548J
To
Transfer
Header
Fig. 16 -- Heat Pump Acutrol — Flow as Condenser
Function/ Exiting First Pass
C09230
ComponentStatus/Position
Reversing ValveEnergized
Check Valve AClosed
Check Valve BOpen
Check Valve CClosed
Check Valve DOpen
Table 4 – Heating Mode (each circuit)
ComponentStatus/Position
Reversing ValveDe--- energized
Check Valve AOpen
Check Valve BClosed
Check Valve COpen
Check Valve DClosed
11
Table 5 – Defrost Mode
04A---07A and 08D---09D/Circuit 2:
Component
Defrost ThermostatClosed
Outdoor Fan(s)Off
Reversing ValveEnergized
Check Valve AClosed
Check Valve BOpen
Check Valve CClosed
Check Valve DOpen
Status/Position
Troubleshooting Refrigerant Pressure Problems
and Check Valves
Refer to Fig. 14, on page 10, and t he Cooling Mode and
Heating Mode tables (Tables 3 and 4) on page 11.
548J
Coil Metering
The metering devices are multiple fixed–bore devices
(Acutrolt) swaged into the horizontal outlet tubes from
the liquid header, located at the entrance to each
evaporator coil circuit path. These are non–adjustable.
Service requires replacing the entire liquid header
assembly.
Check for possible blockage of one or more of these
metering devices by creating a low load condition on the
evaporator--function coil and then observing the frosting
pattern on the finned portion of the coil.
To c heck the indoor coil, disconnect the supply fan signal
(04A--06A direct--drive fans) or contactor (IFC) coil, then
Devices
start the circuit in a Cooling Mode (jumper R to Y1 or
Y2) and observe the frosting pattern on the face of the
indoor coil. A frost pattern should develop uniformly
across the face of the indoor coil starting a t each tube at
the Acutrol nipple locations.
To check the outdoor coil, disconnect the outdoor fan
motor. Start the circuit in a Heating Mode (jumper R to
W1 or W2) and observe the frost pattern on the face of the
outdoor coil.
Failure to develop frost at an outlet tube can indicate a
plugged or a missing orifice.
Refrigerant System Pressure Access Ports
There are two access ports in each circuit -- on the suction
tube near the compressor and on the discharge tube near
the compressor. These are brass fittings with black plastic
caps. The hose connection fittings are standard 1/4 SAE
Male Flare couplings.
The brass fittings are two--piece High Flow valves, with a
receptacle base brazed to the tubing and an integral
spring-- closed check valve core screwed into the base.
(See Fig. 19.) This check valve is permanently assembled
into this core body a nd cannot be serviced separately;
replace the entire core body if necessary. Service tools are
available from RCD that allow the replacement of the
check valve core without having to re cover the entire
system refri gerant charge. Apply compressor refrigerant
oil t o the check valve core’s bottom o--ring. Install the
fitting body with 96 +/--10 in--lbs of torque; do not
overtighten.
5/8” HEX
SEAT
.47
1/2-20 UNF RH
0.596
30°
WASHER
O-RING
This surface provides a metal to metal seal when
torqued into the seat. Appropriate handling is
required to not scratch or dent the surface.
Fig. 19 -- CoreMax Access Port Assembly
CORE
(Part No. EC39EZ067)
1/2" HEX
45°
DEPRESSOR PER ARI 720
+.01/-.035
FROM FACE OF BODY
7/16-20 UNF RH
C08453
12
PURONR(R--410A) REFRIGERANT
This unit is designed for use with Puron (R--410A)
refrigerant. Do not use any other refrigerant in this
system.
Puron (R --410A) refrigerant is provided in pink (rose)
colored cylinders. These cylinders are available with and
without dip tubes; cylinders with dip tubes will have a
label indicating this feature. For a cylinder with a dip
tube, place the cylinder in the upright position (access
valve at the top) whe n removing liquid refrigerant for
charging. For a cyli nder without a dip tube, invert the
cylinder (access valve on the bottom) when removing
liquid refrigerant.
Because Puron (R--410A) refrigerant is a blend, it is
strongly recommended that refrigerant always be removed
from the cylinder as a liquid. Admit liquid refrigerant into
the system in the discharge line. If adding refrigerant into
the suction line, use a commercial metering/expansion
device at t he gauge manifold; remove liquid from the
cylinder, pass it through the metering device at the gauge
set and then pass it into the suction line as a vapor. Do not
remove Puron (R--410A) refrigerant from the cylinder as a
vapor.
To Use Cooling Charging
Charts
Take the outdoor ambient temperature and read t he
suction pressure gauge. Refer to chart to determine what
suction temperature should be. If suction temperature is
high, add refrigerant. If suction temperature is low,
carefully recover some of the charge. Recheck the suction
pressure as charge is adjusted.
Amount of refrigerant charge is listed on the unit’s
nameplate. Refer to the GTAC2--5 Charging, Recovery,
Recycling and Reclamation training manual and the
following procedures.
Unit panels m ust be in place when unit is operating during
the charging procedure. If unit is equipped with a head
pressure control device, bypass it to ensure full fan
operation during charging.
Charge checking and adjustments must be made while the
system is operating in Cooling only.
Charge
No
Use standard evacuation techniques for Puron (R--410A)
refrigerant.. After evacuating system, weigh in the
specified amount of refrigerant.
Low--Charge
Using Cooli ng Charging Charts, Fig. 20 vary refrigerant
until the conditions of the appropriate chart are met. Note
the charging charts are different from type normally used.
Charts are based on charging the units to the correct
superheat for the various operating conditions. Accurate
pressure gauge and tempera ture sensing device are
required. Connect the pressure gauge to the service port
on the suction line. Mount the temperature sensing device
on the suction line and insulate it so that outdoor ambient
temperature does not affect the reading. Indoor--a ir cfm
must be within the normal operating range of the unit.
Cooling
Lubrication
Compressors are charged with the correct amount of oil at
the factory.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to
components.
The compressor is in a PuronR refrigerant system and
uses a polyolester (POE) oil. This oil is extremely
hygroscopic, meaning it absorbs water readily. POE
oils can absorb 15 times as much water as other oils
designed for HCFC and CFC refrigerants. Avoid
exposure of the oil to the atmosphere.
Replacing Compressor
The compressor used with Puron refrigerant contains a
POE oil. This oil has a high affinity for moisture. Do not
remove the compressor’s tube plugs until ready to insert
the unit suction and discharge tube ends.
Compressor mounting bolt torque is 65--75 in--lbs (7.3--8.5
Nm).
Failure to follow this caution may result in personal
injury.
On 3--phase units with scroll compressors, it is important
to be certain compressor is rotating in the proper
direction. To determine whether or not compressor is
rotating in the proper direction:
1. Connect service gauges to suction and discharge pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start--up.
NOTE: If the suction pressure does not drop and the
discharge pressure doe s not rise to normal levels:
4. Note that the evaporator fan is probably also rotating
in the wrong direction.
5. Turn off power to the unit.
6. Reverse any two of the unit power leads.
7. Reapply power to the compressor.
The suction and discharge pressure levels should now
move to their normal start--up levels.
NOTE: When the compressor is rotating in the wrong
direction, the unit makes an elevated level of noise and
does not provide cooling.
Replace whenever refrigerant system is exposed to
atmosphere. Only use factory specified liquid--line filter
driers with working pressures no less than 650 psig. Do
not install a suction--line filter drier in liquid line. A
liquid--line filter drier designed for use with Puron
refrigerant is required on every unit.
Outdoor Fan Location
See Fig. 21.
1. Shut off unit power supply. Install lockout tag.
2. Remove condenser --fan assembly (grille, motor, and
fan).
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 21.
5. Tighten setscrews to 84 in--lbs (9.5 Nm).
6. Replace condenser--fan assembly.
Conduit
0.14 in + 0.0 / -0.03
C08448
Fig. 21 -- Outdoor Fan Adjustment
Troubleshooting Cooling System
Refer to Table 6 for additional troubleshooting topics.
548J
17
PROBLEMCAUSEREMEDY
Compressor an d
Outdoor Fan
Will Not Start.
Compressor Will Not
Start But Outdoor
Fan Runs.
548J
Compressor Cycles
(Other Than
Normally Satisfying
Thermostat).
Compressor Operates
Continuously.
Compressor Makes
Excessive Noise.
Excessive Head
Pressure.
Head Pressure
Too L ow.
Excessive Suction
Pressure.
Suction Pressure
Too L ow.
Tabl e 6 – Heating and Cooling Troubleshooting
Power failure.Call power company.
Fuse blown or circuit breaker tripped.Replace fuse or reset circuit breaker. Determine root cause.
Defective thermostat, contactor, transformer,
control relay, or capacitor.
Insufficient line voltage.Determine cause and correct.
Incorrect or faulty wiring.Check wiring diagram and rewire correctly.
Thermostat setting too high.Lower thermostat setting below room temperature.
High pressure switch tripped.See problem ‘‘Excessive head pressure.’’
Low pressure switch tripped.Check system for leaks. Repair as necessary.
Freeze-up protection thermostat tripped.See problem ‘‘Suction pressure too low.’’
Fault y wiring or loose connections in compressor
circuit.
Compressor motor burned out, seized, or
internal overload open.
Outdoor fan motor(s) not operating (heating).Check fan motor operation.
Replace component.
Check wiring and repair or replace.
Determine cause. Replace compressor or allow enough time for
internal overload to cool and reset.
Determine cause and replace compressor.
Determine cause and replace.
Replace.
Start-Up.
18
CONVENIENCE OUTLETS
!
WARNING
Mount the weatherproof cover to the backing plate as
shown in Fig. 23. Remove two slot fillers in the bottom of
the cover to permit servi ce tool cords to exit the cover.
Check for full closing and latching.
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience out let circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Tag--out this switch, if necessary.
Tw o types of convenience outlets are offered on 548J
models: Non--poweredand unit--powered.Both types
provide a 125--volt GFCI (ground--fault circuit--interrupter)
duplex receptacle rated at 15--A behind a hinged waterproof
access cover, located on the end panel of the unit. See
Fig. 22.
Pwd-CO
Convenience
Outlet
GFCI
Pwd-CO
Fuse
Switch
Transformer
COVER – WHILE-IN-USE
WEATHERPROOF
RECEPTACLE
NOT INCLUDED
BASE PLATE FOR
GFCI RECEPTACLE
C09022
Fig. 23 -- Weatherproof Cover Installation
Non--powered type: Thistyperequiresthe field
installation of a general--purpose 125--volt 15--A circuit
powered from a source elsewhere in the building. Observe
national and local codes when selecting wire size, fuse or
breaker requirements and disconnect switch size and
location. Route 125--v power supply conductors into the
bottom of the utility box containing the duplex receptacle.
548J
Control Box
Access Panel
C08128
Fig. 22 -- Convenience Outlet Location
Installing Weatherproof Cover –
Aweatherproofwhile-in-usecoverforthe
factory-installed convenience outlets is now required by
UL standards. This cover cannot be factory-mounted due
its depth; it must be installed at unit installation. For
shipment, the convenience outlet is covere d with a blank
cover plate.
The weatherproof cover kit is shipped in the unit’s control
box. The kit includes the hinged cover, a backing plate
and gasket.
DISCONNECTALLPOWERTOUNITAND
CONVENIENCE OUTLET.
Remove the blank cover plate at the conveni ence out let;
discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until
1
approximately
/2-in (13 mm) under screw heads are
exposed. Press the gasket over the screw heads. Slip the
backing plate over the screw heads at the keyhole slots
and align with the gasket; tighten the two screws until
snug (do not over-tighten).
Unit--powered type: A unit--mounted transformer is
factory--installed to stepdown the main power supply
voltage to the unit to 115--v at the duplex receptacle. This
option also includes a manual switch with fuse, located in
a utility box and mounted on a bracket behind the
convenience outlet; access is through the unit’s control
box access panel. See Fig. 22.
The primary leads to the convenience outlet transformer
are not factory--connected. Selection of primary power
source is a customer--option. If local codes permit, the
transformer primary leads can be connected at the
line--side terminals on the unit--mounted non--fused
disconnect or HACR breaker switch; this will provide
service power to the unit when t he unit disconnect switch
or HACR switch is open. Other connection methods will
result in the convenience outlet circuit being de--energized
when the unit disconnect or HACR switch is open. See
Fig. 24.
Duty Cycle: the unit--powered convenience outlet has a
duty cycle limitation. The transformer is intended to
provide power on an intermittent basis for service tools,
lamps, etc; it is not intended to provide 15--amps loading
for continuous duty loads (such as electric heaters for
overnight use). Observe a 50% limit on circuit loading
above 8--amps (i.e., limit loads exceeding 8--amps to 30
minutes of operation every hour).
Test the GFCI receptacle by pressing the TEST button on
the face of the receptacle to trip and open the receptacle.
Check for proper grounding wires a nd power line phasing
19
if the GFCI receptacle does not trip as required. Press the
RESET button to clear the tripped condit ion.
548J
UNIT
VOLTAGE
208,
230
460480
575600
CONNECT
AS
240
PRIMARY
CONNECTIONS
L1: RED +YEL
L2: BLU + GRA
L1: RED
Splice BLU + YEL
L2: GRA
L1: RED
L2: GRA
TRANSFORMER
TERMINALS
H1 + H3
H2 + H4
H2 + H3
Terminals are clearly marked on the board surface. See
Fig 25.
The CTB contains no software and no logic. But it does
include seven configuration jumpers that are cut to
configure the board to read external optional and
accessory controls, including that the unit is a heat pump.
CO8283
H1
H4
H1
H2
Fig. 24 -- Powered Convenience Outlet Wiring
Maintenance: Periodically test the GFCI receptacle by
pressing the TEST button on the face of the receptacle.
This should cause the internal circuit of the receptacle to
trip and open the receptacle. Check for proper grounding
wires and power line phasing if the GFCI receptacle does
not trip as required. Press the RESET button to clear the
tripped condition.
Fuse on powered type: The factory fuse is a Bussman
“Fusetron” T--15, non--renewable screw--in (Edison base)
type plug fuse.
Using unit--mounted convenience outlets: Units with
unit--mounted convenience outlet circuits will often
require that two disconnects be opened to de--energize all
power to the unit. Treat all units as electrically energized
until the convenience outlet power is al so checked and
de--energization is confirmed. Observe National Electrical
Code Article 210, Branch Circuits, for use of convenience
outlets.
HEAT PUMP CONTROLS
Controls Terminal Board
The Controls Terminal Board (CTB) is a large printed
circuit board that is located in the center of the unit
control box. This printed circuit board contains multiple
termination strips and connectors to simplify factory
control boxwiring and field controlconnections.
Jumpers JMP5, JMP6 and JMP7 are located in notches
across the top of the CTB (see Fig. 25 ). These jumpers
are factory cut on all heat pump units. Visually check
these jumpers to confirm that they have been cut.
PROTECTIVE CONTROLS
Compressor Protection
Overcurrent
The compressor has internal linebreak motor protection.
20
Overtemperature
The compressor has an internal protec tor to protect it
against excessively high discharge gas temperatures.
High Pressure
Switch
The system is provided with a high pressure switch
mountedonthedischargeline.Theswitchis
stem--mounted and brazed into the discharge tube. Trip
setting is 630 psig +/-- 10 psig (4344 +/-- 69 kPa) when
hot. Reset is automatic at 505 psig (3482 kPa).
Loss of Charge
Switch
The system is protected against a loss of charge and low
evaporator coil loading condition by a loss of charge
switch located on the liquid line and a freeze protection
thermostatontheindoorcoil .Theswitchis
stem--mounted. Loss of Charge Switch trip setting is
27 psig +/-- 3 psig (186 +/-- 21 kPa). Re set is automatic at
44 +/-- 3 psig (303 +/-- 21 kPa).
Freeze Protection Thermostat trip setting is 30_F+/--5_F
(-- 1_C+/--3_C). Reset is automatic at 45_F+/--5_F(7_C
+/--3_C).
Supply (Indoor) Fan Motor Protection
Disconnect and lockout power when servicing fan motor.
2.9and3.7 bhpmotorsareequippedwithan
overtemperature or protection device. The type of devi ce
depends on the motor size. See Table 8.
Table 8 – Overload Device per Motor Size
Motor Size (bhp)Overload DeviceReset
1.7Internal LinebreakAutomatic
2.4Internal LinebreakAutomatic
2.9ThermixAutomatic
3.7ThermixAutomatic
4.7
External
(Circuit Breaker)
Manual
Troubleshooting supply fan m otor overload trips: The
supply fan used in 548J units is a forward--c urved
centrifugal wheel. At a constant wheel speed, this wheel
had a characteristic that causes the fan shaft load to
DECREASE when the static pressure in the unit--duct
system increases and to INCREASE when the static
pressure in the unit--duct system decreases (and fan
airflowrateincreases).Motor overloadconditions
typically develop when the unit is operated with an access
panel removed, with unfinished duct work, in an
economizer--open mode, or a leak de velops in the duct
system that allows a bypass back to unit return opening.
Outdoor Fan Motor Protection
The outdoor fan motor is internally protected against
overtemperature.
Control Circuit, 24--V
548J
The control circuit is protected against overcurrent
conditions by a circuit breaker mounted on control
transformer TRAN. Reset is manual.
COMMERCIAL DEFROST CONTROL
TheCommercialDefrostControlBoard(DFB)
coordinates thermostat demands for supply fan control, 1
or 2 stage cooling, 2 stage heating, emergency heating and
defrost control with unit operating sequences. The DFB
also provides an indoor fan off delay feature (user
selectable). See Fig. 26 for board arrangement.
The High Static option supply fan motor is equipped with
a pilot--circuit Thermix combination overtemperature/
overcurrentprotectiondevice.Thisdeviceresets
automatically. Do not bypass this switch to correct
trouble. Determine the cause and correct it.
The Thermix device is a snap--action overtemperature
protection device that is imbedded in the m otor windings.
It is a pilot--circuit device that is wired into the unit’s 24–v
control circuit. When this switch reaches its trip setpoint,
it opens the 24–v control circuit and causes all unit
operation to cease. This device resets automatically when
the motor windings cool. Do not bypass this switch to
correct trouble. Determine the cause and correct it.
TheExternalmotoroverloaddeviceisa
specially--calibrated circuit breaker that is UL recognized
as a motor overload controller. It is an overcurrent device.
When the motor current exceeds the circuit breaker
setpoint, the device opens all motor power le ads and the
motor shuts down. Reset requires a manual reset at the
overload switch. This device (designated IFCB) is located
on the side of the supply fan housing, behind the fan
access panel.
DIP
Switches
Speed-Up
Jumpers
C09275
Fig. 26 -- Defrost Control Board (DFB) Arrangement
The DFB is located in the 548J’s main control box (see
Fig. 27). All connections are factory--made through
harnesses to the unit’s CTB, to IFC (belt--drive mot or) or
to ECM (direct--drive motor), reversing valve solenoids
and to defrost thermostats. Refer to Table 9 for details of
DFB Inputsand Outputs.Detailed unitoperating
sequences are provided in the Operating Sequences
section starting on page 62.
21
548J
C09276
Fig. 27 -- Defrost Control Board (DFB) Location
Table 9 – 548J Defrost Board I/O and Jumper Configurations
Inputs
Point NameType of I/ OConnection Pin NumberUnit ConnectionNote
GFanD I , 2 4 --- v acP 2 --- 3LC T B --- G
Y1 Cool 1D I , 2 4 --- v acP 2 --- 5LC TB --- Y 1
Y2 Cool 2D I , 2 4 --- v acP 2 --- 4LC TB --- Y 2
W1 Heat 1D I , 2 4 --- v acP 2 --- 7L C T B --- W 1
W2 Heat 2D I , 2 4 --- v acP 2 --- 6L C T B --- W 2
RPower2 4 --- v acP 3 --- 1C O N T L B R D --- 8
C Common2 4 --- v acP 3 --- 2C O N T L B R D --- 4
DFT1D I , 2 4 --- v a cD F T --- 1 t o D F T --- 1
DFT 2D I , 2 4 --- v a cD F T --- 2 t o D F T --- 2
Outputs
Point NameType of I/ OConnection Pin NumberUnit ConnectionNote
IFO Fan OnD O , 2 4 --- v a cP 3 --- 9R E H E AT --- 2
OF OD Fan OnDO , 2 4 --- v a cOFOFR
RVS1DO , 2 4 --- v a cP 3 --- 7 t o P 3 --- 5Energize in COOL
RVS2DO , 2 4 --- v a cP 3 --- 6 t o P 3 --- 4Energize in COOL
COMP 1DO , 2 4 --- v acP 3 --- 1 0FP T --- R E H E A T --- 6
COMP 2DO , 2 4 --- v acP 3 --- 8R E H E AT --- 8
HEAT 2D O , 2 4 --- v acE --- H E A THC --- 1 ( T B 4 --- 1 )
COM2 4 --- v acP 3 --- 3H C --- 1 ( T B 4 --- 3 )
Configuration
Point NameType of I/ OConnection Pin NumberUnit ConnectionNote
Select Jumper2 4 --- v acP 1 --- 1
2 Compressor2 4 --- v acP 1 --- 3Use for 548J***D
Speed--Up Configuration
Point NameType of I/ OConnection Pin NumberUnit ConnectionNote
Speed---Up JumperJMP17
Speed---Up JumperJMP18
Jumper for 1--3 secs: Factory Test, defrost runs for 9 secs
Jumper for 5--20 secs: Forced Defrost, defrost runs for 30 secs if DFT2 is open
Reversing valve control — The DFB has two outputs for
unit reversing val ve control. Operation of the reversing
valves is based on internal logic; this application does not
use an “O” or “B” signal to determine reversing valve
position. Re versing valves are energized during the
Cooling stages and de--energized during Heating cycles.
Once energized at the start of a Cooling stage, the
reversing valve will remain energized until the next
Heating cycle demand is received. Once de--energized at
the start of a Heating cycle, the reversing valves will
remain de -- energized until the next Cooling stage is
initiated.
Compressor control—The DFBreceives inputs
indicating Stage 1 Cooling, Stage 2 Cooling (sizes 08 and
09 only) and Stage 1 Heati ng from the space thermostat or
unit control system (RTU--MP); it generates commands to
start compressors with or withoutreversing valve
operation to produce Stage 1 Cooling (one compressor),
Stage 2 Cooling (both compressors run) or Stage 1
Heating (both compressors run).
22
Auxiliary (Electric) Heat control — The 548J unit can be
equipped with one or two auxiliary electric heaters, to
provide a second stage of Heating. The DFB will energize
this Heating system for a Stage 2 Heating command
(heaters operate concurrently with both compressors in the
Stage 2 Heating cycle), for an Emergency Heating
sequence (compressors are off and only the electric
heaters are energized) and also during the Defrost cycle
(to eliminate a “cold blow” condition in the space).
Defrost — The defrost control mode is a time/temperature
sequence.Therearetwotimecomponents:The
continuous run period and the test/defrost cycle period.
The temperature component is provided by the defrost
thermostat(s) (DFT1 and DFT2 (08--09 only) mounted on
the outdoor coil.
still open, the defrost test/run window is closed and the
control repeats the continuous run period. If DFT2 is
closed, the defrost cycle is initiated in Circuit 2. The
defrost period will end when DFT2 opens (indicating the
outdoor coil has been cleared of frost and ice) or a 10
minute elapsed period expires, whic hever comes first.
On sizes 08--09, Circuit 1’s defrost ther mostat DFT1
(located on the upper circuit of the outdoor coil) cannot
initiate a unit defrost cycle; only DFT2 may do this. But
once Circuit 2 is in defrost, the DFB will monitor the
status of DFT1. If DFT1 closes during a Circuit 2 defrost
cycle, Circuit 1 will also enter a defrost cycle. Circuit 1’s
defrost cycle will end when DFT1 opens (indicating the
upper portion of the outdoor coil is cleared of frost and
ice) or the Circuit 2 defrost cycle is terminated.
The continuous run period is a fixed time period between
the end of the last defrost cycle (or start of the current
Heating cycle) during which no defrost will be permitted.
This period can be set at 30, 60, 90 or 120 minutes by
changing the positions of DIP switches SW1 and SW2
(see Fig. 28 and Table 10). The default run periods are 30
minutes for unit sizes 04--07 and 90 minutes for unit sizes
08--09.
C09283
Fig. 28 -- DIP Switch Settings — Defrost Board
At the end of the continuous run period, the defrost
control will test for a need to defrost. On unit sizes 04--07
(single compressor designs), DFT1 controls the start and
termination of the defrost cycle. If DFT1 is still open, the
defrost test/run window is closed and the control repeats
the continuous run period. If DFT1 is closed, the defrost
cycle is initiated. The defrost period will end when DFT1
opens (indicating the outdoor coil has been cleared of
frost and ice) or a 10 minute elapsed period expires,
whichever comes first.
On unit sizes 08 and 09 (two circuit designs), DFT2
(located on the bottom circuit of the outdoor coil) controls
the start and termination of the defrost cycle. If DFT2 is
At the end of the unit defrost cycle, t he unit will be
returned to Heating cycle for a full continuous run period.
If the space heating load is satisfied and compressor
operation is terminated, the defrost control will remember
where the run period was interrupted. On restart in
Heating, the defrost control will resume unit operation at
the point in the run period where it was last operat ing.
Defrost Thermostats — These are temperature switches
that monitor the surface temperature of the outdoor coil
circuits. These switches a re mounted on the liquid tube
exiting the outdoor coil heating circuits. These switches
close on temperature drop at 30_F(--1_C) and reset open
on temperature rise at 80_F(27_C).
Indoor Fan Off Delay — The DFB can provide a 30 sec
delay on Indoor Fan Off if the thermostat’s fan selector
switch is set on AUTO control. DIP Switch SW3 on the
DFB selects use of the fan off time delay feature. Setting
SW3 in the OPEN position turns the Fan Off Delay
feature on; setting SW3 in the CLOSED position disables
this feature. The delay period begins when Y1 demand or
W1 demand by the space thermostat is removed.
Defrost Speedup Functions — The DFB permits the
servicer to speed--up the defrost cycle. There are two
speed--up sequences: relative speed--up and an immediate
forced defrost. Speed-- up sequences are initiated by
shorting jumper wires JMP17 and JMP18 together (see
Fig. 26); use a straight--edge screwdriver.
Shorting the jumpers for a period of 1 to 3 secs reduces
the defrost timer periods by a factor of 0.1 sec/minute.
(For example, the 90 min run period is reduced to 9 secs.)
The DFB will step the unit t hrough a Heating cycle and a
Defrost cycle using these reduced time periods. This mode
ends after the Defrost cycle.
548J
Table 10 – Dip Switch Position
Switch No.
121212123
1
0JJ0J0J00JOff
90 minutes
1J1J1JJ1On
60 minutes30 minutes120 minutesFan Delay
23
Shorting the jumpers for a period of 5 to 20 secs bypasses
the remaining continuous run period and places the unit in
a Forced Defrost mode. If the controlling DFT is closed
when this mode is initiated, the unit will complete a
normal defrost period that will terminate when the
controlling DFT opens or the 10 minute defrost cycle limit
is reached. If the controlling DFT is open when this mode
is initiated, the Defrost cycle will run for 30 secs. Both
modes end at the end of the Defrost cycle.
ELECTRIC HEATERS
548J units may be equipped with field--installed accessory
electric heaters. The heaters are modular in design, with
heater frames holding open coil resistance wires strung
through ceramic insulators, line--break limit switches and
a control contact or. One or two heater modules may be
used in a unit.
548J
DISCONNECT MOUNTING
LOCATION
Unit heaters are marked with Heater Model Numbers. But
heaters are ordered as and shipped in cartons marked with
a corresponding heater Sale s Package part number. See
Table 11 for correlation between heater Model Number
and Sales Package part number.
NOTE: The value in position 9 of the part number differs
between the sales package part number (value is 1) and a
bare heater model number (value is 0).
Heater modules are installed in the compa r tment below
the indoor (supply) fan outlet. Access is through the
indoor access panel. Heater modules slide into the
compartment on tracks along the bottom of the heater
opening. See Fig. 29, Fig. 30 and Fig. 31.
Not all available heater modules may be used in every
unit. Use only those heater modules that are UL listed for
use in a specific size unit. Refe r to t he label on the unit
cabinet re approved heaters.
Fig. 31 -- T ypical Module Installation
Table 11 – Heater Model Number
Bare Heater Model NumberCRHEATER001A00
Heater Sales Package PNO
Includes:
Bare Heater
Carton and packing materials
Installation sheet
CRHEATER101A00
TRACK
FLANGE
C08135
24
Single Point Boxes and Supplementary Fuses — When
the unit MOCP device value exceeds 60--A, unit--mounted
supplementary fuses are required for each heater circuit.
These fuses are included in accessory Single Point Boxes,
with power distribution and fuse blocks. The single point
box will be installed directly under the unit control box,
just to the left of the partition separating the indoor
section (with electric heaters) from the outdoor section.
The Single Point Box has a hinged access cover. See
Fig. 32.
CONTROL
BOX
BUSHING
SINGLE
POINT BOX
MOUNTING
SCREWS
DRIP BOOT
BRACKET
MOUNTING
SCREWS
POWER
WIRES
FOAM
BUSHING
HEATER
RELAYS
HEATER
MOUNTING
SCREWS
2
1
1
1
2
13
3
21
23
11
13
A
L
LIE
D
P
A
C
O
R
P
.
MO
DE
L
N
O
.
O
D
ERI
A
L
N
O.
2
2
.
2
ISTED
AIR
NDITIONING
1
2
3
UIP
ACCESS
346N
.
3
P
/ N
2-
5
6
1
REV
0
4
C08136
Fig. 32 -- Typical Single Point Installation
On 548J units, all fuses are 60--A. Single point boxes
containing fuses for 208/230--V applications use UL Class
RK5 250--V fuses (Bussman FRNR 60 or Shawmut TR
60R). Singlepoint boxes for460--V and575--V
applications use UL Class T 600--V fuses (Bussman JJS
60 or Shawmut A6T 60). (Note that all heaters are
qualified for use with a 60--A fuse, regardless of actual
heater ampacity, so only 60--A fuses are necessary.)
Unit heater applications not requiring supplemental fuses
require a special Single Point Box without any fuses.
Connect power supply conductors to heater conductors
and field--supplied base unit power tap leads (see text
below re: “Completing Heater Installati on”) inside the
empty Single Point Box using UL--approved connec tors.
Safety Devices — Electric heater applications use a
combination of line-- break/auto--reset limit switches and a
pilot--circuit/manual reset limit switch to protect the unit
against over--temperature situations.
Line--break/auto-- reset limit switches are mounted on the
base plate of each heater module. See Fig. 33. These are
accessed through the indoor access panel. Remove the
switch by removing two screws into the base plate and
extracting the existing switch.
Pilot--circuit/manual reset limit switch is located in the
side plate of the indoor (supply) fan housing. See Fig. 30.
Completing Heater Installation
Field Power Connections — Tap conductors must be
installed between the base unit’s field power connection
lugs and the Single Point Box (with or without fuses).
Refer to unit wiring schematic. Use copper wire only. For
connection using the Single Point Box less fuses, connect
the field power supply conductors to the heater power
leads and the field--supplied tap conductors inside the
Single Point Box. Use UL--approved pressure connectors
(field--supplied) for these splice joints.
Line-Break
Limit Switches
21
23
11
13
ALLIED P
A
MODE
L
NO.
OD
ERIAL
NO.
ISTED
AIR
NDITIONING
1
2
3
U
I
P
ACCESS
34
6
N
.
3
P
/ N
2
-
5610-4
RE
V
C08330
Fig. 33 -- Typical Location of Heater Limit Switches
(3--phase heater shown)
Low--VoltageControlConnections—Pullthe
low--voltage control leads from the heater module(s) -VIO and BRN (two of each if two modules are installed;
identify for Module #1) -- to the 4--pole terminal board
TB4 located on the heater bulkhead to the left of Heater
#1. Connect the VIO lead from Heater #1 to terminal
TB4--1. Connect the VIO lead from Heater #2 to terminal
TB4--2. Connect both BRN leads to terminal TB4--3. See
Fig. 34.
DEFROST
BOARD
E-HEAT
P3-3
ORN
BRN
ORNBRN
TB4
Field
Connections
13
VIOBRN BRN
VIO
Elec Htr
VIOHR2
VIOBRN
BRN
HR1
HR1: On Heater 1 in Position #1
HR2: On Heater 2 in Position #2 (if installed)
C09013
Fig. 34 -- Accessory Electric Heater Control
Connections
548J
25
SMOKE DETECTORS
Sensor
Smoke detectors are a vailable as factory-- installed options
on 548J models. Smoke detectors may be specified for
Supply Air only or for Return Air without or with
economizer or in combination of Supply Air and Return
Air. Return Air smoke detectors are arranged for vertical
return configurations only. All compone nts necessary for
operation are fa ctory--provided and mounted. The unit is
factory--configuredforimmediatesmokedetector
shutdown operation; additional wiring or modificati ons to
unit terminal board may be necessary to complete the unit
and smoke detector configuration to meet project
requirements.
System
The smoke detector system consists of a four-- wire
controller and one or two sensors. Its primary function is
548J
to shut down the rooftop unit in order to prevent smoke
from circulating throughout the building. It is not to be
used as a life saving device.
Controller
The controller (see Fig. 35) includes a controller housing,
a printed circuit board, and a clear plastic cover. The
controller can be connected to one or two compatible duct
smoke sensors. The clear plastic cover is secured to the
housing with a single captive screw for easy access to the
wiring terminals. The controller has three LEDs (for
Power, Trouble and Alarm) and a manual test/reset button
(on the cover face).
The sensor (see Fig. 36) includes a pla stic housing, a
printed circuit board, a clear plastic cover, a sampling
tube inlet and an exhaust tube. The sampling tube (when
used) and exhaust tube are attached during installation.
The sampling tube varies in length depending on the size
of the rooftop unit. The clear plastic cover permits visual
inspections without ha ving to disassemble the sensor. The
cover attaches to the sensor housing using four captive
screws and forms an airtight cham ber around the sensing
electronics. Each sensor includes a harness with an RJ45
terminal for connecting to the controller. Each sensor has
four LEDs (for Power, Trouble, Alarm and Dirty) and a
manual test/reset button (on the left--side of the housing).
Duct smoke sensor
Exhaust tube
See
Detail A
Intake
gasket
Plug
TSD-CO2
(ordering option)
Sampling tube
(ordered separately)
Exhaust gasket
Sensor housing
and electr onics
Cover gasket
(ordering option)
Sensor cover
Controll er housing
and electronics
Conduit c ouplings
(supplie d by installer)
Duct smoke sensor
controller
Conduit nuts
(supplie d by installer)
Conduit s upport plate
Terminal block cover
Fastener
(2X)
Alarm
Troub le
Power
Tes t / r e s e t
switch
Fig. 35 -- Controller Assembly
Cover gasket
(ordering option)
Controll er cover
C08208
Magnetic
test/reset
switch
Coupling
Alarm
Troub le
Power
Dirty
C08209
Detail A
Fig. 36 -- Smoke Detector Sensor
Air is introduced to the duct smoke detector sensor’s
sensing chamber through a sampling tube that extends into
the HVAC duct and is directed back into the ventilation
system through a (shorter) exhaust tube. The difference in
air pressure between the two tubes pulls the sampled air
through the sensing chamber. When a sufficient amount of
smoke is detected in the sensing chamber, the sensor
signals an alarm state and the controller automatically
takes the appropriate action to shut down fans and
blowers, change over air handling systems, notify the fire
alarm control panel, etc.
The sensor uses a process called differential sensing to
prevent gradual environmental changes from triggering
false alarms. A rapid change in environmental conditions,
26
such as smoke from a fire, causes the sensor to signal an
alarm state but dust and debris accumulated over time
does not.
For installations using two sensors, the duct smoke
detector does not differentiate which sensor signals an
alarm or trouble condition.
Smoke Detector Locations
Supply Air — The Supply Air smoke detector sensor is
located to the left of the unit’s indoor (supply) fan. See
Fig. 37. Access is through the fan access panel. There is
no sampling tube used at this location. The sampling tube
inlet extends through the side plat e of the fan housing
(into a high pressure area). The controller is located on a
bracket to the right of the return filter, accessed through
the lift--off filter panel.
Return Air with Economizer — The sampling tube is
inserted through the side plates of the economizer
housing, placing it across the return air opening on the
unit basepan. See Fig. 39. The holes in the sampling tube
face downward, into the return air stream. The sampling
tube is connected via tubing t o the return a ir sensor that is
mounted on a bracket high on the partition between return
filter and controller location. (This sensor is shipped in a
flat--mounting location. Installation requires that this
sensor be re located to its operating location and the tubing
to the sampling tube be connected. See “Completing
Installation of Return Air Smoke Sensor” for installation
steps.)
548J
Return Air
Sampling Tube
Smoke Detector Sensor
C08245
Fig. 37 -- T ypical Supply Air Smoke Detector Sensor
Location
Return Air without Economizer — The sampling tube is
located across the return air opening on the unit basepan.
See Fig. 38. The holes in the sampling tube face
downward, into the return air stream. The sampling tube is
connected via tubing to the return air sensor that is
mounted on a bracket high on the partition between return
filter and controller location. (This sensor is shipped in a
flat--mounting location. Installation requires that this
sensor be re located to its operating location and the tubing
to the sampling tube be connected. See “Completing
Installation of Return Air Smoke Sensor” for installation
steps.)
Return Air Detector module
(shipping position shown)*
Controller module
Return Air Detector Sampling Tube
*RA detector must be moved from shipping position to operating position by installer
C07307
Fig. 38 -- Typical Return Air Detector Location
C08129
Fig. 39 -- Return Air Sampling Tube Location
Completing Installation of Return Air Smoke
Sensor:
SCREWS
EXHAUST
TUBE
FLEXIBLE
EXTENSION
TUBE
SAMPLING
C08126
Fig. 40 -- Return Air Detector Shipping Position
1. Unscrew the two screws holding the Return Air
Sensor detector plate. See Fig. 40. Save the screws.
2. Remove the Return Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing outwards and t he sampling tube connecti on is on the bottom. See Fig. 41.
4. Screw the sensor and detector plate into its operating
position using screws from Step 1. Make sure the
sampling tube connection is on the bot tom and the exhaust tube is on the top. See Fig. 41.
5. Connect the flexible tube on the sampling inlet to the
sampling tube on the basepan.
27
6. For units with an economizer, the sampling tube is integrated into the economizer housing but the connection of the flexible tubing to the sampling tube is the
same.
548J
Fig. 41 -- Return Air Sensor Operating Position
FIOP Smoke Detector Wiring and Response
All units: FIOP smokedetector is configured to
automatically shut down all unit ope rations when smoke
condition is detected. See Fig. 42, Typical Smoke
Detector System Wiring.
Highlight A: JMP 3 is factory--cut, transferring unit
control to smoke detector.
C08127
Highlight B: Smoke detector NC contact set will open on
smokeal armcondition,de--energizingtheORN
conductor.
Highlight C: 24--v power signal via ORN lead is removed
at Smoke Detector input on CTB (Control Terminal
Board); all unit operations cease immediately.
Highlight D: On smoke alarm condition, the smoke
detector NO Alarm contact will close, supplying 24 --v
power to GRA conductor.
Highlight E: GRA lead at Smoke Alarm input on CTB
provides 24--v signal to FIOP DDC control.
RTU--MP: The 24--v signal is conveyed to RTU--MP’s
J1--10 input terminal. This signal initiates the FSD
sequence by the RTU--MP control. FSD status is reported
to connected BAS network.
Using Remote Logic: Five conductors are provided for
field use (see Highlight F in Fig. 42) for additional
annunciation functions.
Additional Application Data — Refer to Cat alog No.
HKRNKA--1XA for discussions on additional control
features of these smoke detectors including multiple unit
coordination. See Fig. 42.
B
D
C
F
E
A
Fig. 42 -- Typical Smoke Detector System Wiring
28
C08246
Sensor and Controller Tests
Sensor Alarm Test
The sensor alarm test checks a sensor’s ability to signal an
alarm state. This test requires that you use the factory
provided SD--MAG test magnet. The magnet (which is
approximately 1.0 in. long. x
plastic bag in the unit control box.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system,notifytheproperauthoritiesbefore
performing the test.
Sensor Alarm Test Procedure
1. Hold the test magnet where indicated on the side of
the sensor housing for seven seconds.
2. Verify that the sensor’s Alarm LED turns on.
3. Reset the sensor by holding the t est magnet against
the sensor housing for two seconds.
4. Verify that the sensor’s Alarm LED turns off.
1
/4in. sq.) is located in a
Controller Alarm Test
The controller alarm test checks the controller’s ability to
initiate and indicate an a larm state.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
This test places the duct detector into the alarm state.
Disconnect all auxiliary equipment from the controller
before performing the test. If the duct detector is
connected to a fire alarm system, notify the proper
authorities before performing the test.
Controller Alarm Test Procedure
1. Press the controller’s test/reset switch for seven
seconds.
2. Verify that the controller’s Alarm LED turns on.
3. Reset the sensor by pressing the test/reset switch for
two seconds.
4. Verify that the controller’s Alarm LED turns off.
Dirty Controller Test
The dirty controller test checks the controller’s ability to
initiate a dirty sensor test and indicate its results.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
Pressing the controller’s test/reset switch for longer
than seven seconds will put the duct detector i nto the
alarm state and activate all automatic alarm responses.
Dirty Controller Test Procedure
1. Press the controller’s test/reset switch for two
seconds.
2. Verify that the controller’s Trouble LED flashes.
Dirty Sensor Test
The dirty sensor test provides an indication of the sensor ’s
ability to compensate for gradual environmental changes.
A sensor that can no longer compensate for environmental
changes is considered 100% dirty and requires cleaning or
replacing. You must use the factory provided SD--MAG
test magnet to initiate a sensor dirty test. The sensor’s
Dirty LED indicates the results of the dirty test as shown
in Table 12.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
Holding the test magnet against the sensor housing for
more than seven seconds will put the duct detector
into the alarm state and activate all automatic alarm
responses.
Tabl e 12 – D i rty L ED Te st
FLASHESDESCRIPTION
10---25% dirty. (Typical of a newly installed detector)
225- -- 50% dirty
351- -- 75% dirty
476- -- 99% dirty
Dirty Sensor Test Procedure
1. Hold the test magnet where indicated on the side of
the sensor housing for two seconds.
2. Verify that the sensor’s Dirty LED flashes.
548J
29
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
Changing the dirty sensor test operation will put the
detector into the alarm state and activate all automatic
alarm responses. Before changing dirty sensor test
operation, disconnect all auxiliary equipment from the
controller and notify the proper authorities if
connected to a fire alarm system.
Changing the Dirty Sensor Test
By default, sensor dirty test results are indicated by:
S The sensor’s Dirty LED flashing.
S The controller’s Trouble LED fla shing.
548J
S The controller’s supervision relay contacts toggle.
The operation of a sensor’s dirty test can be changed so
that the controller’s supervision relay is not used to
indicate test results. When two detectors are connected to
a controller, sensor dirty test operation on both sensors
must be configured to operate in the same manner.
To Configure the Dirty Sensor Test
Operation
1. Hold the test magnet where indicated on the side of
the sensor housing until the sensor’s Alarm LED turns
on and its Dirty LED flashes twice (approximately 60
seconds).
2. Reset the sensor by removing the test magnet then
holding it against the sensor housing again until the
sensor’s Alarm LED turns off (approximately 2
seconds).
Remote Station Test
The remote station alarm test checks a test/reset station’s
ability to initiate and indicate an alarm state.
!
CAUTION
Remote Test/Reset Station Dirty Sensor Test
The test/reset station dirty sensor test checks the test/reset
station’s ability to initiate a sensor dirty test and indicate
the results. It must be wired to the controller as shown in
Fig. 43 and configured to operate the controller’s
supervision relay. For more information, see “Changing
the Dirty Sensor Test.”
12
1
3
Wire must be
added by installer
TB3
1
2
14
Supervision relay
contacts [3]
13
19
15
2
20
Fig. 43 -- Remote Test/Reset Station Connections
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
If the test/reset station’s key switch is left in the
RESET/TEST position for longer than seven seconds,
the detector will automatically go into the alarm state
and activate all automatic alarm responses.
Smoke Detector Controller
–
Auxiliary
equipment
+
18 Vdc (+)
18 Vdc (
–
)
CRSDTEST001A00
Tro uble
5
Power
4
Alarm
1
Reset/ Test
3
2
C09326
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system,notifytheproperauthoritiesbefore
performing the test.
CRSDTEST001A00 Remote Alarm Test Procedure
1. Turn the key switch to the RESET/TEST position for
seven seconds.
2. Verify that the test/reset station’s Alarm LED turns
on.
3. Reset the sensor by turni ng the key switch to the
RESET/TEST position for two seconds.
4. Verify that the test/reset station’s Alarm LED turns
off.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result i n personnel
and authority concern.
Holding the test magnet to the target area for longer
than seven seconds will put the detector into the alarm
state and activate all automatic alarm responses.
Dirty Sensor T est Using an CRSDTEST001A00
1. Turn the key switch to the RESET/TEST position for
two seconds.
2. Verify that the test/reset stat ion’s Trouble LED
flashes.
30
Loading...
+ 70 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.