Bryant 542J User Manual

installation, start-up and service instructions
SINGLE PACKA GE ROOFT OP HEAT PUM P UNITS
Cancels: II 542J-150-3 II 542J-150-4
Dura
542J
Plus Series
Sizes 150,180
12 and 15 Tons
3/15/06
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-18
I. Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 — Rig and Place Unit. . . . . . . . . . . . . . . . . . . 1
III. Step 3 — Field Fabricate Ductwork . . . . . . . . . . . . . 1
IV. Step 4 — Make Unit Duct Connections . . . . . . . . . . 3
V. Step 5 — Trap Condensate Drain. . . . . . . . . . . . . . . 3
VI. Step 6 — Make Electrical Connections . . . . . . . . . . 7
VII. Step 7 — Make Outdoor-Air Inlet Adjustments. . . 10
VIII. Step 8 — Install Outdoor-Air Hood. . . . . . . . . . . . . 10
IX. Step 9 — Install All Accessories . . . . . . . . . . . . . . 10
X. Step 10 — Adjust Factory-Installed Options. . . . . 11
XI. Step 11 — Defrost Cycle . . . . . . . . . . . . . . . . . . . . . 18
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-22
SERVICE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23-29
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .30-35
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained se rvice per­sonnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety pre c au ti ons th at ma y a ppl y.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
WARNING: Before performing service or mainte­nance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
INSTALLATION
IMPORTANT: Units have high ambient operating limits. If
limits are exceeded , the un it will au tomatica lly lock the com­pressor out of operation. Manual reset will be required to restart the compressor.
I. STEP 1 — PROVIDE UNIT SUPPORT A. Roof Curb
Assemble and install a ccessory roof curb in accordanc e with instructions shipped with the curb. Accessory roof curb and information required to field fabricate a roof curb are shown
in Fig. 1 and 2. Install insulation, cant strips, roofing, and counter flashing as shown. Du ctwork can be secured to roof curb before unit is set in pl ace. Horizontal adapter installa­tion is shown in Fig. 2.
IMPORTANT: Th e gasketing of the unit to the roof curb is crit­ical for watert ight seal. Install ga sket suppli ed with the ro of curb as shown in Fig. 1. Improp erly applied gasket can result in air leaks and poor unit performance.
Curb should be level. This is necessary to permit unit drain to function properly. Unit leveling tolerances is ± ear ft in any dire ction . Refe r to Accessory Roof Curb Installa­tion Instructions for addition al information as required.
B. Alternate Unit Support
When the curb cannot be used, support unit with sleepers using unit curb support area. If sleepers cannot be used, sup­port long sides of unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
II. STEP 2 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright, and do not drop. Use spreader bars over unit to prevent sl ing or cabl e damage. Rollers may be used to move unit across a roof. Level by using unit frame as a reference; leveling tolerance is ± linear ft in any direction. See Fig. 1 for additional leveling tol­erance information. Unit weight is shown in Table 1.
Four lifting holes are provided in ends of unit base rails as shown in Fig. 3. Refer to rigging inst ructions on unit.
A. Positioning
Provide clearance around and above unit for airflow, safety, and service access (Fig. 4 and 5).
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air .
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
B. Roof Mount
Check building codes for weight distribution requirements.
III. STEP 3 — FIELD FABRICATE DUCTWORK
Secure all ducts to buildi ng structure. Use flexible duct con­nectors between unit and ducts as required. Insulate and weatherproof all external ductwo rk, join ts, and roof openings with counter flashing and mastic in accordanc e with applica­ble codes.
Ducts passing through an unconditioned space must be insu­lated and covered with a vapor barrier.
The 542J units with electric heat requi r e a 1-in. clearance for the first 24 in. of ductwork.
1
/16 in. per lin-
1
/
in. per
16
lb density.
2
/
1
AB
Deg. in. Deg. in.
DIMENSIONS (degrees and inches)*
ALL .28 .45 .28 .43
UNIT
below the unit discharge for units equipped with electric heaters.
1. Roof curb accessory is shipped disassembled.
2. Insulated panels: 1thick neoprene coated 1
3. Dimensions in ( ) are in millimeters.
NOTES:
4. Direction of airflow.
the indoor section, unit can only be pitched as shown.
5. Roof curb: 16 ga. (VA03-56) stl.
6. A 90 degree elbow must be installed on the supply ductwork
7. To prevent the hazard of stagnant water build-up in the drain pan of
DESCRIPTION
CURB
HEIGHT
Fig. 1 — Roof Curb Details
Standard Curbfor Units
Requiring High Installation
Side Supply and Return
Curb for High Installation
PKG. NO. REF.
CRRFCURB010A00 1-2 (305) Standard Curb 14 High
CRRFCURB011A00 2-0 (610)
CRRFCURB012A00 2-0 (610)
2
3 1/2"
2" X 1/4 SUPPORT TYP. STITCH WELDED
FULLY INSULATED SUPPLY PLENUM 1" INSULATION 1 1/2 # DENSITY, STICK PINNED & GLUED
NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated transition duct. The pressure drop through the adapter curb is negligible.
For horizontal return applications: The power exhaust and barometric
relief dampers must be installed in the return air duct.
Fig. 2 — Horizontal Supply/Return Adapter Installation
MAXIMUM
UNIT 542J
150 1895 860 3-1 948 180 2205 1000 3-6 1059
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Refer to Table 1 for unit operating weights.
3. Remove boards at ends of unit and runners prior to rigging.
4. Rig by inserting hooks into unit base rails as shown. Use corner post from packaging to protect coil from damage. Use bumper boards for spreader bars.
5. Weights do not include optional EconoMi$erIV. See Table 1 for EconoMi$erIV weight.
6. Weights given are for aluminum indoor coil plate fins and copper outdoor coil plate fins. Weights of other metal combinations are listed in Table 1.
SHIPPING WEIGHT
lb kg ft-in. mm
DIMENSION A
CAUTION: All panels must be in place when rigging.
Fig. 3 — Rigging Details
14 3/4"
6"
ACCESSORY
PACKAGE NO.
CRRFCURB013A00
12" WIDE STANDING SEAM PANELS
CURB
HEIGHT
1-11
(584)
DESCRIPTION
Pre-Assembled, Horizontal
Adapter Roof Curb
23"
Outlet grilles must not lie directly below unit discharge. NOTE: A 90-degree elbo w must be provid ed in the du ctwork
to comply with UL (Underwriters Laboratori es ) co d e s f or use with electric heat.
WARNING: For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Insta ll a 90-de gree t urn in th e return ductwor k between the unit and the conditioned space. If a 90-degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space. Due to electric heater, supply duct will require 90-degree elbow.
IV. STEP 4 — MAKE UNIT DUCT CONNECTIONS
Unit is shipped for thru-the-bottom duct connections. Duct­work openings are shown in Fig. 6. Field-fabricated concen­tric ductwork may be connected as shown in Fig. 7 and 8.
Attach all ductwork to roof curb and roof curb basepans. Refer to installation instructions shipped with accessory roof curb for more information.
V. STEP 5 — TRAP CONDENSATE DRAIN
See Fig. 4 or 5 and 9 for drain location. Plug is provided in drain hole and must be removed when unit is operating. One
3
/4-in. half coupling is provided inside unit indoor air section for condensate drain connection. An 81/2 in. x 3/4-in. diameter nipple and a 2-in. x
3
/4-in. diameter pipe nipple are coupled to standard 3/4-in. diameter elbows to provide a straight path down through holes in unit base rails (see Fig. 10). A trap at least 4-in. deep must be used.
3
Table 1 — Physical Data
UNIT SIZE 542J 150 180 NOMINAL CAPACITY (tons) 12
1
/
2
15
OPERATING WT (lb)
Al/Al* 1615 1925 Al/Al Coated* 1615 1925 Unit Al/Cu* 1745 2075
Cu/Cu* 1815 2165 Electric Heat 65 65 EconoMi$erIV 90 90 Roof Curb† 200 200
COMPRESSOR Semi-Hermetic
Type (Number) 06D-328 (1) 06D-818 (2) Cylinders 64 Oil Change (oz.) (each circuit) 115 88
REFRIGERANT TYPE R-22
Charge (lb)
System 1 26.0 16.5 System 2 16.5
3
OUTDOOR COIL
Rows 33
/8 in., Internally Grooved Copper T ubes, Aluminum or Copper Lanced Fins
Fins/in. 15 15 Total Face Area (sq ft) 21.7 21.7
OUTDOOR FAN Propeller Type, Direct Drive
Nominal Cfm 9,000 9,000 Number...Diameter (in.) 3...22 3...22 Motor Hp (1075 rpm) Watts Input (Total) 1090 1090
INDOOR CO IL
Expansio n D ev i c e Fixed Orifice
3
/8 in., Internally Grooved Copper Tubes, Aluminum or Copper Lanced Fins, Face Split
1
/
2
1
/
2
Rows 33 Fins/in. 15 15 Total Face Area (sq ft) 17.5 17.5
INDOOR FAN Centrifugal, Adjustable Pitch Belt Drive
Quantity...Size (in.) Nominal Cfm 5000 6000
2...10 x 10 2...12 x 12
Maximum Continuous Bhp 4.25 5.90 Fan Rpm Range 862-1132 799-1010 Maximum Allowable Rpm 1550 1550 Motor Pulley Pitch Diameter (in.) 3.1/4.1 3.7/4.7 Fan Pulley Pitch Diameter (in.) Belt, Quantity...Type...Length (in.) 1...BX...42 1...BX...46 Pulley Center Line Distance (in.) 13.5-15.5 13.3-14.8 Speed Change Per Turn (rpm)
6.0 11.4
54 42
Pulley Maximum Full Turns 6** 6** Factory Pulley Turns Setting 33 Factory Speed Setting (rpm) 1024 926 Fan Shaft Diameter (in.) Motor Hp (Service Factor) 3.7 (1.15) 5.0 (1.15) Motor Frame Size 56H 184T Motor Efficiency 0.84 0.84
3
/
1
16
17/
16
HIGH-PRESSURE SWITCH
Cutout (psig) 426 Reset (psig) 320
LOW-PRESSURE/LOSS-OF-CHARGE SWITCH
Cutout (psig) 7 Reset (psig) 22
AIR INLET SCREENS Cleanable
Economi zer, Quantity...Size (in.)
RETURN-AIR FILTERS (TYPE) 10% Efficient — 2-in. Throwaway Fiberglass
Quantity...Size (in.)
DEFROST THERMOSTAT
Defrost Time 30 min (Adjustable to 50 or 90 min)
2...20 x 25 x 1
1...20 x 20 x 1
4...20 x 20 x 2
4...16 x 20 x 2
Closes (F) 28 Opens (F) 65
LEGEND
Al — Aluminum Cu — Copper
*Indoor coil fin material/outdoor coil fin material.
†Weight of 14 in. roof curb.
**Pulley cannot be run at 0 or
1
/2 turns open.
4
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3. Center of Gravity.
4. Direction of airflow.
5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:
•Rear: 7′-0″ (2 134) for coil removal. This dimension can be reduced to 4′-0″ (1219) if conditions per mit coil removal from the top.
• Left side: 4′-0″ (1219) for proper outdoor coil airflow.
• Front: 4′-0″ (1219) for control box access.
• Right side: 4′-0″ (1219) for proper operation of damper and power exhaust (if so equipped).
• Top: 6′-0″ (1829) to assure proper outdoor fan operation.
• Local codes or jurisdiction may prevail.
7. With the exception of clearance for the outdoor coil and the damper/power exhaust as stated in note no. 6, a removable fence or barricade requires no clearance.
8. Dimensions are from outside of cor ner post. Allow
5
/
(8) on each side for top cover drip edge.
0-
16
9. A 90 degree elbow must be installed on the supply ductwork below the unit discharge for units equipped with electric heat.
STANDARD UNIT
WEIGHT
ECONOMI$ERIV
WEIGHT
1615 lb (733 kg) 90 lb (41 kg)
Fig. 4 — Base Unit Dimensions — 542J150
5
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3. Center of Gravity.
4. Direc tion of airflow.
5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:
• Rear: 7′-0″ (2134) for coil removal. This dimension can be reduced to 4′-0″ (1219) if conditions per mit coil removal from the top.
• Left side: 4′-0″ (1219) for proper outdoor coil airflow.
•Front: 4′-0″ (1219) for control box access.
• Right side: 4′-0″ (1219) for proper operation of damper and power exhaust (if so equipped).
• Top: 6′-0″ (1829) to assure proper outdoor fan operation.
• Local codes or jurisdiction may prevail.
7. With the exception of clearance for the outdoor coil and the damper/power exhaust as stated in note no. 6, a removable fence or barricade requires no clearance.
8. Dimensions are from outside of corner post. Allow
5
/
(8) on each side for top cover drip edge.
0-
16
9. A 90 degree elbow must be installed on the supply ductwork below the unit discharge for units equipped with electric heat.
STANDARD UNIT
WEIGHT
ECONOMI$ERIV
WEIGHT
1925 lb (874 kg) 90 lb (41 kg)
Fig. 5 — Base Unit Dimensions — 542J180
6
NOTE: Do not drill in this area, as damage to basepan may result in water leak.
Fig. 6 — Air Distribution — Thru-the-Bottom
(542J180 Shown)
VI. STEP 6 — MAKE ELECTRIC CONNECTIONS A. Field Power S upply
Unit is factory wired for voltage shown on nameplate. When installing units, provide a disconnect of adequate size
per NEC (National Electrical Code) requirements (Table 2). All field wiring must comply with NEC and local
requirements. Route power lines through control box access panel or unit
basepan (Fig. 4 and 5) to connections as shown on unit wir­ing diagram and Fig. 11.
Transformers no. 1 and 2 are wired for 230-v unit. If 208/ 203-v unit is to be run with 208-v power supply, the trans­formers must be rewired as follows:
1. Remove cap from red (208 v) wire.
2. Remove cap from orange (230 v) spliced wire.
3. Replace orange wire with red wire.
4. Recap both wires.
IMPORTANT: BE CERTAIN UNUSED WIRES ARE CAPPED. Failure to do so may damage the transformers.
Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, volt­ages between phases must be balanced within 2% and the current must be balanced w ith in 10%.
Use the following formula to determine the percentage of voltage imbalance.
Perce nt ag e of Voltage Imbalance
NOTE: Do not drill in this area, as damage to basepan may result in water leak.
Fig. 7 — Concentric Duct Air Distribution
(542J180 Shown)
Shaded area indicates block-off panels.
NOTE: Dimensions A, A′ and B, B are obtained from field-supplied ceiling diffuser.
Fig. 8 — Concentric Duct Details
= 100 x
max voltage deviation from average voltage
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
455 + 464 + 455
1371
=
3
3
= 457
Determine maximum deviation from average voltage:
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine the percent voltage imbal ance:
Percentage of Voltage Imbalance= 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
Unit failure as a res ult of ope ra tio n o n imp ro per line volt age or excessive phase imbalance constitutes abuse and may cause damage to electrical components.
7
INDOOR FAN MOTOR ACCESS
FILTER ACCESS
3/4" FPT DRAIN CONNECTION
1-3/8" DRAIN HOLE
Fig. 9 — Condensate Drain Details
Fig. 10 — Condensate Drain Piping Details
LEGEND
EQUIP GND — Equipment Ground kcmil Thousand Circular Mils NEC National Electrical TB Terminal Block
NOTE: The maximum wire size for TB1 is 350 kcmil f or all unit v olt ages.
Fig. 11 — Field Power Wiring Connections
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly according to th e installation instru ctions included with the accessory. Refer to unit Price Pages or contact your local Bryant representative for more information. Locate
thermostat assembly on a solid wall in the conditioned space to sense average temperature.
Route thermostat cable or equivalent single leads of no. 18 AWG (American Wire Gage) colored wire from subbase te r­minals through conduit in unit to low-voltage connections as shown on unit label wiring diagram and in Fig. 12.
NOTE: For wire runs up to 50 ft, use no. 18 AWG insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insu­lated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wi re larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
Set heat anticipator settings as indicated in T able 3. Settings may be changed sligh tly to pr ovide a great er degree of com­fort for a particular installation.
C. Optional Non-Fused Disconnect
On units with the optional non-fused disconnect, incoming power will be wired into the disconnect switch. Refer to Fig. 13 for wiring for 100 and 200 amp disconnect switches. Units with an MOCP (maximum overcurrent protection) under 100 will use the 100 amp disconnect switch. Units with an MOCP over 100 will use the 200 amp disconnect switch. Refer to the applicable disconnect wiring diagram.
To prevent breakage during shipping, the disconnect handle and shaft are shipped and packaged inside the unit control box. Install the disconnect handle before unit operation. To install the handle and shaft, perform the following procedure:
1. Open the control box door and r e mo ve t he handle and shaft from shipping location.
2. Loosen the Allen bolt located on the disconnect switch. The bolt is locat ed on the sq uare hole a nd is used to hold the shaft in place. The shaft cannot be inserted until the Allen bolt is moved.
3. Insert the disconnect shaft into the square hole on the disconnect switch. The end of the shaft is spe­cially cut and the shaft can only be inserted in the correct orientation.
4. Tighten the Allen bolt to lock the shaft into position.
5. Close the control bo x door.
6. Attach the handle to the external access door with the two screws provided. When the handle is in the ON position, the handle will be vertical. When the handle is in the OFF position, the handle will be horizontal.
7. Turn the handle to the OFF position and close the door. The handle should fit over th e end of the shaf t when the door is closed.
8. The handle must be in the OFF position to open the control box door.
D. Optional Convenience Outlet
On units with optional convenience outlet, a 115-v GFI (ground fault interrupt) convenience outl et rece ptacle is pr o­vided for field wiring. Field wiring should be run thro ugh th e
7
/8-in. knockout provided in the basepan near the return air
opening.
8
Table 2 — Electrical Data
UNIT
542J
150
180
VOLTAGE
(3 Ph,
60 Hz)
208/230 187 253 39.7 228 3 1.7 3.7 10.5/10.5
208/230 187 253 28.2 160 28.2 160 3 1.7 5 15.8/15.8
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA Qty
460 414 508 19.9 114 3 0.8 3.7 4.8
460 414 508 14.1 80 14.1 80 3 0.8 5 7.9
LEGEND
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration LRA Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — M aximum Overcurrent Protection NEC National Electrical Code RLA Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, and
480 v. If po wer distribution voltage to unit varies from rated heater volt­age, heater kW will vary accordingly.
†Fuse or HACR circuit breaker. This is the maximum size permissible;
smaller fuse size may be used where conditions permit.
COMPRESSOR OUTDOOR
No. 1 No. 2
FAN
MOTOR
FLA
(ea)
INDOOR FAN
MOTOR
Hp FLA FLA LRA FLA kW MCA MOCP† RLA LRA
POWER
EXHAUST
——
4.6 18.8
——
2.3 6.0
——
4.6 18.8
——
2.3 6.0
ELECTRIC HEAT* POWER SUPPLY
—/— —/— 65/ 65 100/100 64/ 64 39/ 45 14/19 114/122 125/150 64/ 64 72/ 82 26/34 155/168 175/175 94/107
117/135 42/56 211/200 225/225 147/167
—/— —/— 70/ 70 100/100 69/ 69 39/ 45 14/19 119/126 125/150 69/ 69 72/ 82 26/34 159/173 175/175 100/112
117/135 42/56 216/205 225/225 152/173
32 50 31 18 15 54 60 31 39 32 81 90 50 66 55 98 110 82
34 50 34 18 15 57 70 34 39 32 83 90 53 66 55 100 110 84
—/— —/— 84/ 84 110/110 89/ 89
117/135 42/56 231/219 250/225 153/173
—/— —/— 89/ 89 110/110 94/ 94
117/135 42/56 235/224 250/225 158/179
42 50 44 66 55 108 110 85
44 50 47 66 55 110 125 88
DISCONNECT
SIZING
387/387
406/406
189
195
499/48572/ 82 26/34 174/187 175/200 101/112
518/50472/ 82 26/34 179/191 200/200 106/118
23839 32 91 100 54
24439 32 93 100 57
NOTES:
1. In compliance with NEC requirements for multimotor and combina­tion load equipment (refer to NEC Articles 430 and 440), the over­current protective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker.
2. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) + (1.00 x heater FLA).
Fig. 12 — Field Control Thermostat Wiring
Table 3 — Heat Anticipator Settings
UNIT 542J
150
180
UNIT
VOLTAGE
208/230-3-60
460
208/230
460
HEATER
kW
14/19 .40 — 26/34 .40 .40 42/56 .66 .40
15 .40 — 32 .40 .40 55 .40 .66
26/34 .40 .66 42/56 .66 .40
32 .40 .40 55 .40 .66
6T3 4T2 2T1 LOAD
5L3 3L2 1L1 LINE
STAGE 1 STAGE 2
NOTE: The disconnect takes the place of TB-1 as shown on the unit
wiring diagram label and the component arrangement label.
Fig. 13 — Optional Non-Fused Disconnect Wiring
9
VII. STEP 7 — MAKE OUTDOOR-AIR INLET ADJUSTMENTS A. Manual Outdoor-Air Damper
All units (except those equipped with a factory-installed EconoMi$erIV ) h ave a ma nual out door-air damper to provide ventilation air . Damper can be preset to admit up to 25% out­door air into return-air compartment. To adjust, loosen securing screws and move damper to desired setting. Then retighten screws to secure damper (Fig. 14).
VIII. STEP 8 — INSTALL OUTDOOR-AIR HOOD IMPORTANT: If the unit is equipped with the optional
EconoMi$erIV component, move the outdoor-air tempera­ture sensor prior to installing the outdoor-air hood. See the Optional EconoMi$erIV section for more information.
The same type of factory-installed hood is used on units with 25% air ventilation and units with an EconoMi$erIV.
NOTE: The hood top panel, upper and lower filter retainers, hood drain pan, and filter support bracket are secured oppo­site the outdoor coil end of the unit. The screens, hood side panels, remaining section of filter support bracket, seal strip, and all other hardware ar e in a package located inside t he return-air filter access panel (Fig. 15).
1. Attach seal strip to upper filter retainer. See Fig. 16.
2. Assemble hood top panel and side panels, upper filter retainer, and hood drain pan (Fig. 17).
3. Secure lower filter retainer and long section of filter support bracket to unit. See Fig. 17.
4. Loosen sheet metal screws for base unit top panel located above o utdoor-air inlet opening, and remove
screws for hood side panels located on the sides of the outdoor-air inlet opening.
5. Match notches in hood top panel to unit top panel screws. Insert hood flange between unit top panel flange and unit. Tighten screws.
6. Hold hood side panel flanges flat against unit, and install screws removed in Step 4.
7. Insert outdoor-air inlet screens and spacer in channel created by lower filter retainer and filter support bracket.
8. Attach remaining short section of filter support bracket.
IX. STEP 9 — INSTALL ALL ACCESSORIES
After all the factory-installed options have been adjusted, install all field-instal led accessories. Refer to the accessory installation instructions included with each accessory.
Fig. 14 — 25% Outdoor-Air Section Details
HOOD TOP PANEL
Fig. 16 — Seal Strip Location
(Air Hood Cross-Sectional View)
LOWER FILTER RETAINER
FILTER SUPPORT BRACKET
FILTER SUPPORT BRACKET
HOOD SIDE PANELS (2)
LOWER FILTER RETAINER
Fig. 15 — Outdoor-Air Hood Component Location
HOOD DRAIN PAN
UPPER FILTER RETAINER
NOTE: The outdoor-air hood comes with a baffle which is not used on these units. Discard the baffle.
Fig. 17 — Outdoor-Air Hood Details
10
A. Motormaster® I Control Installation
Install Field-Fabricated Wind Baffles Wind baffles must be field-fabricated for all units to ensure
proper cooling cycle operation at low ambient temperatures. See Fig. 18 for baffle details. Use 20-gage, galvanized sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to at tach baffles t o unit. Screws shou ld
1
be
/4-in. diameter and 5/8-in. long. Drill required screw holes
for mounting baffles.
CAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care when drilling holes.
Install Motormaster I Controls Only one Motormaster I control is required per unit. The
Motormaster I control must be used in c onjunction with the accessory 0° F low ambien t kit (purchased separately). The Motormaster I device controls outdoor fan no. 1 while ou t­door fans no. 2 and 3 are sequenced off by the accessory 0° F low ambient kit.
Accessory 0° F Low Ambient K it — Install the accessory 0° F low ambient kit per instruction supplied with accessory.
Sensor Assembl y — Install the sensor assembly in the loca­tion shown in Fig. 19.
Motor Mount — To ensure proper fan height, replace the existing motor mount with the new motor m ount provided with accessory .
Transfor mer (460-V Units On ly) — On 460-volt units a trans­former is required. The transformer is provided with the accessory and must be field-installed.
Motormaster I Control — Recommended mounting location is on the inside of the panel to the left of the control box. The control should be mounted on the inside of the panel, verti­cally, with leads protruding from bottom of extrusion.
MOTORMASTER SENSOR LOCATION
NOTES:
1. All sensors are located on the eighth hairpin up from the bottom.
2. Field-installed tubing insulation is required to be installed over the TXV bulb and capillary tube for proper operation at low ambients. Tubing insulation is only required on the por­tion of suction line located between indoor and outdoor section.
HAIRPIN END
Fig. 19 — Motormaster I Sensor Locations
X. STEP 10 — ADJUST FACTORY-INSTALLED OPTIONS A. Optional EconoMi$erIV
See Fig. 20 and 21 for EconoMi$erIV component locati ons. NOTE: These instructions are for installing the optional
EconoMi$erIV only. Refer to the accessory EconoMi$erIV or EconoMi$er2 installation instructions when field in stalling an EconoMi$erIV or EconoMi$er2 accessory.
To complete installation of t he optional EconoMi$erIV, per­form the following procedure.
1. Remove the EconoMi$er IV hood. Refer to Step 8 — Install Outdoor-Air Hood on page 10 for info rmation on removing and in stalling the outdoor-air hood.
2. Relocate outdoor air temperature sensor from ship­ping position to operation pos ition on EconoMi $erIV. See Fig. 20.
IMPORTANT: Failure to relocate the sensor w ill res ult in the EconoMi$erIV not operating properly.
3. Re-install economizer hood.
4. Install all EconoMi$erIV accessories. EconoMi$erIV wiring is shown in Fig. 22.
Outdoor air leakage is shown in Table 4. Return air pressure drop is shown in Tabl e 5.
Table 4 — Out door Air Damper Leakage
NOTE: Dimensions in ( ) are in mm.
Fig. 18 — Wind Baffle Details
DAMPER STATIC PRESSURE (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2
LEAKAGE (cfm) 35 53 65 75 90 102
Table 5 — Return Air Pressure Drop (in. wg)
CFM
4500 5000 5400 6000 7200 7500
0.040 0.050 0.060 0.070 0.090 0.100
11
SCREWS
ECONOMI$ERIV
FRAME
TOP
SCREWS
OUTDOOR AIR TEMPERATURE SENSOR (INSTALLED OPERATION POSITION)
LOW TEMPERATURE COMPRESSOR LOCKOUT SWITCH
ECONOMI$ERIV
SUPPLY AIR TEMPERATURE SENSOR LOCATION
Fig. 20 — EconoMi$erIV Component Locations —
End View
ACTUATOR
CONTROLLER FLANGE
AND SCREWS (HIDDEN)
1 R T
R T
c a V 4
2
M O C
4 2
_
c a V
T
O
H
H X E
+
t e
S
V 0
2
1
V 2
1
1
N
5
N
n
H
i
X
M
E
s o
P
4
n
P1
e p
P
O
3
V C
1
D
x a
EF
T1
M
T
V 0
1
EF
V 2
V C
D
V
t
C
e
D
S
V
1
0
Q
1
A
Q A
V 2
+
e
O
e r
S
C
F
l o
O
o
S
C
B
D
+ R S
A
R
S
Fig. 21 — EconoMi$erIV Component Locations —
Side View
DCV — Demand Controlled Ventilation
LEGEND
IAQ — Indoor Air Quality LALS— Low Temperature Compressor
Lockout Switch
OAT — Outdoor-Air Temperature POT — Potentiometer
Potentiometer Default Settings: Power Exhaust Middle Minimum Pos. Fully Closed DCV Max. Middle DCV Set Middle Enthalpy C Setting
Fig. 22 — EconoMi$erIV Wiring
NOTES:
1. 620 ohm, 1 watt 5% resistor should be rem oved only when using differential enthalpy or dry bulb.
2. If a separate field -supplied 24 v transform er is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT to the minimum position.
12
Loading...
+ 28 hidden pages