Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained se rvice personnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the
unit, and other safety pre c au ti ons th at ma y a ppl y.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguisher available for all brazing operations.
WARNING: Before performing service or maintenance operations on unit, turn off main power switch to
unit. Electrical shock could cause personal injury.
INSTALLATION
IMPORTANT: Units have high ambient operating limits. If
limits are exceeded , the un it will au tomatica lly lock the compressor out of operation. Manual reset will be required to
restart the compressor.
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install a ccessory roof curb in accordanc e with
instructions shipped with the curb. Accessory roof curb and
information required to field fabricate a roof curb are shown
in Fig. 1 and 2. Install insulation, cant strips, roofing, and
counter flashing as shown. Du ctwork can be secured to roof
curb before unit is set in pl ace. Horizontal adapter installation is shown in Fig. 2.
IMPORTANT: Th e gasketing of the unit to the roof curb is critical for watert ight seal. Install ga sket suppli ed with the ro of
curb as shown in Fig. 1. Improp erly applied gasket can result
in air leaks and poor unit performance.
Curb should be level. This is necessary to permit unit drain to
function properly. Unit leveling tolerances is ±
ear ft in any dire ction . Refe r to Accessory Roof Curb Installation Instructions for addition al information as required.
B. Alternate Unit Support
When the curb cannot be used, support unit with sleepers
using unit curb support area. If sleepers cannot be used, support long sides of unit with a minimum of 3 equally spaced
4-in. x 4-in. pads on each side.
II. STEP 2 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with
transportation agency. Keep unit upright, and do not drop.
Use spreader bars over unit to prevent sl ing or cabl e damage.
Rollers may be used to move unit across a roof. Level by using
unit frame as a reference; leveling tolerance is ±
linear ft in any direction. See Fig. 1 for additional leveling tolerance information. Unit weight is shown in Table 1.
Four lifting holes are provided in ends of unit base rails as
shown in Fig. 3. Refer to rigging inst ructions on unit.
A. Positioning
Provide clearance around and above unit for airflow, safety,
and service access (Fig. 4 and 5).
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated air .
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
B. Roof Mount
Check building codes for weight distribution requirements.
III. STEP 3 — FIELD FABRICATE DUCTWORK
Secure all ducts to buildi ng structure. Use flexible duct connectors between unit and ducts as required. Insulate and
weatherproof all external ductwo rk, join ts, and roof openings
with counter flashing and mastic in accordanc e with applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
The 542J units with electric heat requi r e a 1-in. clearance for
the first 24 in. of ductwork.
1
/16 in. per lin-
1
/
in. per
16
lb density.
2
/
1
AB
Deg.in.Deg.in.
DIMENSIONS (degrees and inches)*
ALL.28.45.28.43
UNIT
below the unit discharge for units equipped with electric heaters.
1. Roof curb accessory is shipped disassembled.
2. Insulated panels: 1″ thick neoprene coated 1
3. Dimensions in ( ) are in millimeters.
NOTES:
4.Direction of airflow.
the indoor section, unit can only be pitched as shown.
5. Roof curb: 16 ga. (VA03-56) stl.
6. A 90 degree elbow must be installed on the supply ductwork
7. To prevent the hazard of stagnant water build-up in the drain pan of
NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal
adapter and includes an insulated transition duct. The pressure drop
through the adapter curb is negligible.
For horizontal return applications: The power exhaust and barometric
relief dampers must be installed in the return air duct.
3. Remove boards at ends of unit and runners prior to rigging.
4. Rig by inserting hooks into unit base rails as shown. Use corner
post from packaging to protect coil from damage. Use bumper
boards for spreader bars.
5. Weights do not include optional EconoMi$erIV. See Table 1 for
EconoMi$erIV weight.
6. Weights given are for aluminum indoor coil plate fins and copper
outdoor coil plate fins. Weights of other metal combinations are
listed in Table 1.
SHIPPING WEIGHT
lbkgft-in.mm
DIMENSION A
CAUTION: All panels must be in place when rigging.
Fig. 3 — Rigging Details
14 3/4"
6"
ACCESSORY
PACKAGE NO.
CRRFCURB013A00
12" WIDE STANDING
SEAM PANELS
CURB
HEIGHT
1′-11″
(584)
DESCRIPTION
Pre-Assembled, Horizontal
Adapter Roof Curb
23"
Outlet grilles must not lie directly below unit discharge.
NOTE: A 90-degree elbo w must be provid ed in the du ctwork
to comply with UL (Underwriters Laboratori es ) co d e s f or use
with electric heat.
WARNING: For vertical supply and return units,
tools or parts could drop into ductwork and cause an
injury. Insta ll a 90-de gree t urn in th e return ductwor k
between the unit and the conditioned space. If a
90-degree elbow cannot be installed, then a grille of
sufficient strength and density should be installed to
prevent objects from falling into the conditioned space.
Due to electric heater, supply duct will require
90-degree elbow.
IV. STEP 4 — MAKE UNIT DUCT CONNECTIONS
Unit is shipped for thru-the-bottom duct connections. Ductwork openings are shown in Fig. 6. Field-fabricated concentric ductwork may be connected as shown in Fig. 7 and 8.
Attach all ductwork to roof curb and roof curb basepans.
Refer to installation instructions shipped with accessory roof
curb for more information.
V. STEP 5 — TRAP CONDENSATE DRAIN
See Fig. 4 or 5 and 9 for drain location. Plug is provided in
drain hole and must be removed when unit is operating. One
3
/4-in. half coupling is provided inside unit indoor air section
for condensate drain connection. An 81/2 in. x 3/4-in. diameter
nipple and a 2-in. x
3
/4-in. diameter pipe nipple are coupled
to standard 3/4-in. diameter elbows to provide a straight path
down through holes in unit base rails (see Fig. 10). A trap at
least 4-in. deep must be used.
—3—
Table 1 — Physical Data
UNIT SIZE 542J150180
NOMINAL CAPACITY (tons)12
1
/
2
15
OPERATING WT (lb)
Al/Al*16151925
Al/Al Coated*16151925
Unit Al/Cu*17452075
Cu/Cu*18152165
Electric Heat6565
EconoMi$erIV9090
Roof Curb†200200
COMPRESSORSemi-Hermetic
Type (Number)06D-328 (1)06D-818 (2)
Cylinders64
Oil Change (oz.) (each circuit)11588
REFRIGERANT TYPER-22
Charge (lb)
System 126.016.5
System 2—16.5
3
OUTDOOR COIL
Rows33
/8 in., Internally Grooved Copper T ubes, Aluminum or Copper Lanced Fins
Fins/in.1515
Total Face Area (sq ft)21.721.7
OUTDOOR FANPropeller Type, Direct Drive
Nominal Cfm9,0009,000
Number...Diameter (in.)3...223...22
Motor Hp (1075 rpm)
Watts Input (Total)10901090
INDOOR CO IL
Expansio n D ev i c eFixed Orifice
3
/8 in., Internally Grooved Copper Tubes, Aluminum or Copper Lanced Fins, Face Split
1
/
2
1
/
2
Rows33
Fins/in.1515
Total Face Area (sq ft)17.517.5
INDOOR FANCentrifugal, Adjustable Pitch Belt Drive
Quantity...Size (in.)
Nominal Cfm50006000
2...10 x 102...12 x 12
Maximum Continuous Bhp4.255.90
Fan Rpm Range862-1132799-1010
Maximum Allowable Rpm15501550
Motor Pulley Pitch Diameter (in.)3.1/4.13.7/4.7
Fan Pulley Pitch Diameter (in.)
Belt, Quantity...Type...Length (in.)1...BX...421...BX...46
Pulley Center Line Distance (in.)13.5-15.513.3-14.8
Speed Change Per Turn (rpm)
6.011.4
5442
Pulley Maximum Full Turns6**6**
Factory Pulley Turns Setting33
Factory Speed Setting (rpm)1024926
Fan Shaft Diameter (in.)
Motor Hp (Service Factor)3.7 (1.15)5.0 (1.15)
Motor Frame Size56H184T
Motor Efficiency0.840.84
*Indoor coil fin material/outdoor coil fin material.
†Weight of 14 in. roof curb.
**Pulley cannot be run at 0 or
1
/2 turns open.
—4—
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3.Center of Gravity.
4.Direction of airflow.
5. Ductwork to be attached to accessory roof curb
only.
6. Minimum clearance:
•Rear: 7′-0″ (2 134) for coil removal. This dimension
can be reduced to 4′-0″ (1219) if conditions per mit
coil removal from the top.
• Left side: 4′-0″ (1219) for proper outdoor coil airflow.
• Front: 4′-0″ (1219) for control box access.
• Right side: 4′-0″ (1219) for proper operation of
damper and power exhaust (if so equipped).
• Top: 6′-0″ (1829) to assure proper outdoor fan
operation.
• Local codes or jurisdiction may prevail.
7. With the exception of clearance for the outdoor coil
and the damper/power exhaust as stated in note
no. 6, a removable fence or barricade requires no
clearance.
8. Dimensions are from outside of cor ner post. Allow
5
/
″ (8) on each side for top cover drip edge.
0′-
16
9. A 90 degree elbow must be installed on the supply
ductwork below the unit discharge for units
equipped with electric heat.
STANDARD UNIT
WEIGHT
ECONOMI$ERIV
WEIGHT
1615 lb (733 kg)90 lb (41 kg)
Fig. 4 — Base Unit Dimensions — 542J150
—5—
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3.Center of Gravity.
4.Direc tion of airflow.
5. Ductwork to be attached to accessory roof curb
only.
6. Minimum clearance:
• Rear: 7′-0″ (2134) for coil removal. This dimension
can be reduced to 4′-0″ (1219) if conditions per mit
coil removal from the top.
• Left side: 4′-0″ (1219) for proper outdoor coil airflow.
•Front: 4′-0″ (1219) for control box access.
• Right side: 4′-0″ (1219) for proper operation of
damper and power exhaust (if so equipped).
• Top: 6′-0″ (1829) to assure proper outdoor fan
operation.
• Local codes or jurisdiction may prevail.
7. With the exception of clearance for the outdoor coil
and the damper/power exhaust as stated in note
no. 6, a removable fence or barricade requires no
clearance.
8. Dimensions are from outside of corner post. Allow
5
/
″ (8) on each side for top cover drip edge.
0′-
16
9. A 90 degree elbow must be installed on the supply
ductwork below the unit discharge for units
equipped with electric heat.
STANDARD UNIT
WEIGHT
ECONOMI$ERIV
WEIGHT
1925 lb (874 kg)90 lb (41 kg)
Fig. 5 — Base Unit Dimensions — 542J180
—6—
NOTE: Do not drill in this area, as damage to basepan may result in
water leak.
Fig. 6 — Air Distribution — Thru-the-Bottom
(542J180 Shown)
VI. STEP 6 — MAKE ELECTRIC CONNECTIONS
A. Field Power S upply
Unit is factory wired for voltage shown on nameplate.
When installing units, provide a disconnect of adequate size
per NEC (National Electrical Code) requirements (Table 2).
All field wiring must comply with NEC and local
requirements.
Route power lines through control box access panel or unit
basepan (Fig. 4 and 5) to connections as shown on unit wiring diagram and Fig. 11.
Transformers no. 1 and 2 are wired for 230-v unit. If 208/
203-v unit is to be run with 208-v power supply, the transformers must be rewired as follows:
1. Remove cap from red (208 v) wire.
2. Remove cap from orange (230 v) spliced wire.
3. Replace orange wire with red wire.
4. Recap both wires.
IMPORTANT: BE CERTAIN UNUSED WIRES ARE
CAPPED. Failure to do so may damage the transformers.
Operating voltage to compressor must be within voltage
range indicated on unit nameplate. On 3-phase units, voltages between phases must be balanced within 2% and the
current must be balanced w ith in 10%.
Use the following formula to determine the percentage of
voltage imbalance.
Perce nt ag e of Voltage Imbalance
NOTE: Do not drill in this area, as damage to basepan may result in
water leak.
Fig. 7 — Concentric Duct Air Distribution
(542J180 Shown)
Shaded area indicates block-off panels.
NOTE: Dimensions A, A′ and B, B′ are obtained from field-supplied
ceiling diffuser.
Fig. 8 — Concentric Duct Details
= 100 x
max voltage deviation from average voltage
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
455 + 464 + 455
1371
=
3
3
= 457
Determine maximum deviation from average voltage:
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine the percent voltage imbal ance:
Percentage of Voltage Imbalance= 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below
the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
Unit failure as a res ult of ope ra tio n o n imp ro per line volt age
or excessive phase imbalance constitutes abuse and may
cause damage to electrical components.
NOTE: The maximum wire size for TB1 is 350 kcmil f or all unit v olt ages.
Fig. 11 — Field Power Wiring Connections
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly
according to th e installation instru ctions included with the
accessory. Refer to unit Price Pages or contact your
local Bryant representative for more information. Locate
thermostat assembly on a solid wall in the conditioned space
to sense average temperature.
Route thermostat cable or equivalent single leads of no. 18
AWG (American Wire Gage) colored wire from subbase te rminals through conduit in unit to low-voltage connections as
shown on unit label wiring diagram and in Fig. 12.
NOTE: For wire runs up to 50 ft, use no. 18 AWG insulated
wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG
insulated wire (35 C minimum). All wi re larger than no. 18
AWG cannot be directly connected to the thermostat and will
require a junction box and splice at the thermostat.
Set heat anticipator settings as indicated in T able 3. Settings
may be changed sligh tly to pr ovide a great er degree of comfort for a particular installation.
C. Optional Non-Fused Disconnect
On units with the optional non-fused disconnect, incoming
power will be wired into the disconnect switch. Refer to
Fig. 13 for wiring for 100 and 200 amp disconnect switches.
Units with an MOCP (maximum overcurrent protection)
under 100 will use the 100 amp disconnect switch. Units
with an MOCP over 100 will use the 200 amp disconnect
switch. Refer to the applicable disconnect wiring diagram.
To prevent breakage during shipping, the disconnect handle
and shaft are shipped and packaged inside the unit control
box. Install the disconnect handle before unit operation.
To install the handle and shaft, perform the following
procedure:
1. Open the control box door and r e mo ve t he handle and
shaft from shipping location.
2. Loosen the Allen bolt located on the disconnect
switch. The bolt is locat ed on the sq uare hole a nd is
used to hold the shaft in place. The shaft cannot be
inserted until the Allen bolt is moved.
3. Insert the disconnect shaft into the square hole on
the disconnect switch. The end of the shaft is specially cut and the shaft can only be inserted in the
correct orientation.
4. Tighten the Allen bolt to lock the shaft into position.
5. Close the control bo x door.
6. Attach the handle to the external access door with
the two screws provided. When the handle is in
the ON position, the handle will be vertical. When
the handle is in the OFF position, the handle will be
horizontal.
7. Turn the handle to the OFF position and close the
door. The handle should fit over th e end of the shaf t
when the door is closed.
8. The handle must be in the OFF position to open the
control box door.
D. Optional Convenience Outlet
On units with optional convenience outlet, a 115-v GFI
(ground fault interrupt) convenience outl et rece ptacle is pr ovided for field wiring. Field wiring should be run thro ugh th e
7
/8-in. knockout provided in the basepan near the return air
opening.
—8—
Table 2 — Electrical Data
UNIT
542J
150
180
VOLTAGE
(3 Ph,
60 Hz)
208/230187 253 39.7 228——31.7 3.7 10.5/10.5
208/230187 253 28.2 160 28.2 16031.75 15.8/15.8
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA Qty
460414 508 19.9 114——30.8 3.74.8
460414 508 14.1 8014.1 8030.857.9
LEGEND
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA— Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — M aximum Overcurrent Protection
NEC— National Electrical Code
RLA— Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, and
480 v. If po wer distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
†Fuse or HACR circuit breaker. This is the maximum size permissible;
smaller fuse size may be used where conditions permit.
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR
breaker. The Canadian units may be fuse or circuit breaker.
2. MCA calculation for units with electric heaters over 50 kW = (1.25 x
IFM amps) + (1.00 x heater FLA).
Fig. 12 — Field Control Thermostat Wiring
Table 3 — Heat Anticipator Settings
UNIT 542J
150
180
UNIT
VOLTAGE
208/230-3-60
460
208/230
460
HEATER
kW
14/19.40—
26/34.40.40
42/56.66.40
15.40—
32.40.40
55.40.66
26/34.40.66
42/56.66.40
32.40.40
55.40.66
6T3 4T2 2T1 LOAD
5L3 3L2 1L1 LINE
STAGE 1STAGE 2
NOTE: The disconnect takes the place of TB-1 as shown on the unit
wiring diagram label and the component arrangement label.
Fig. 13 — Optional Non-Fused Disconnect Wiring
—9—
VII. STEP 7 — MAKE OUTDOOR-AIR INLET ADJUSTMENTS
A. Manual Outdoor-Air Damper
All units (except those equipped with a factory-installed
EconoMi$erIV ) h ave a ma nual out door-air damper to provide
ventilation air . Damper can be preset to admit up to 25% outdoor air into return-air compartment. To adjust, loosen
securing screws and move damper to desired setting. Then
retighten screws to secure damper (Fig. 14).
VIII. STEP 8 — INSTALL OUTDOOR-AIR HOOD
IMPORTANT: If the unit is equipped with the optional
EconoMi$erIV component, move the outdoor-air temperature sensor prior to installing the outdoor-air hood. See the
Optional EconoMi$erIV section for more information.
The same type of factory-installed hood is used on units with
25% air ventilation and units with an EconoMi$erIV.
NOTE: The hood top panel, upper and lower filter retainers,
hood drain pan, and filter support bracket are secured opposite the outdoor coil end of the unit. The screens, hood side
panels, remaining section of filter support bracket, seal strip,
and all other hardware ar e in a package located inside t he
return-air filter access panel (Fig. 15).
1. Attach seal strip to upper filter retainer. See Fig. 16.
2. Assemble hood top panel and side panels, upper filter
retainer, and hood drain pan (Fig. 17).
3. Secure lower filter retainer and long section of filter
support bracket to unit. See Fig. 17.
4. Loosen sheet metal screws for base unit top panel
located above o utdoor-air inlet opening, and remove
screws for hood side panels located on the sides of the
outdoor-air inlet opening.
5. Match notches in hood top panel to unit top panel
screws. Insert hood flange between unit top panel
flange and unit. Tighten screws.
6. Hold hood side panel flanges flat against unit, and
install screws removed in Step 4.
7. Insert outdoor-air inlet screens and spacer in channel
created by lower filter retainer and filter support
bracket.
8. Attach remaining short section of filter support
bracket.
IX. STEP 9 — INSTALL ALL ACCESSORIES
After all the factory-installed options have been adjusted,
install all field-instal led accessories. Refer to the accessory
installation instructions included with each accessory.
Fig. 14 — 25% Outdoor-Air Section Details
HOOD TOP
PANEL
Fig. 16 — Seal Strip Location
(Air Hood Cross-Sectional View)
LOWER FILTER
RETAINER
FILTER SUPPORT
BRACKET
FILTER SUPPORT
BRACKET
HOOD SIDE
PANELS (2)
LOWER
FILTER
RETAINER
Fig. 15 — Outdoor-Air Hood Component Location
HOOD DRAIN PAN
UPPER FILTER RETAINER
NOTE: The outdoor-air hood comes with a baffle which is not used on
these units. Discard the baffle.
Fig. 17 — Outdoor-Air Hood Details
—10—
A. Motormaster® I Control Installation
Install Field-Fabricated Wind Baffles
Wind baffles must be field-fabricated for all units to ensure
proper cooling cycle operation at low ambient temperatures.
See Fig. 18 for baffle details. Use 20-gage, galvanized sheet
metal, or similar corrosion-resistant metal for baffles. Use
field-supplied screws to at tach baffles t o unit. Screws shou ld
1
be
/4-in. diameter and 5/8-in. long. Drill required screw holes
for mounting baffles.
CAUTION: To avoid damage to the refrigerant coils
and electrical components, use recommended screw sizes
only. Use care when drilling holes.
Install Motormaster I Controls
Only one Motormaster I control is required per unit. The
Motormaster I control must be used in c onjunction with the
accessory 0° F low ambien t kit (purchased separately). The
Motormaster I device controls outdoor fan no. 1 while ou tdoor fans no. 2 and 3 are sequenced off by the accessory 0° F
low ambient kit.
Accessory 0° F Low Ambient K it — Install the accessory 0° F
low ambient kit per instruction supplied with accessory.
Sensor Assembl y — Install the sensor assembly in the location shown in Fig. 19.
Motor Mount — To ensure proper fan height, replace the
existing motor mount with the new motor m ount provided
with accessory .
Transfor mer (460-V Units On ly) — On 460-volt units a transformer is required. The transformer is provided with the
accessory and must be field-installed.
Motormaster I Control — Recommended mounting location
is on the inside of the panel to the left of the control box. The
control should be mounted on the inside of the panel, vertically, with leads protruding from bottom of extrusion.
MOTORMASTER
SENSOR
LOCATION
NOTES:
1. All sensors are located on the eighth
hairpin up from the bottom.
2. Field-installed tubing insulation is
required to be installed over the TXV
bulb and capillary tube for proper
operation at low ambients. Tubing
insulation is only required on the portion of suction line located between
indoor and outdoor section.
HAIRPIN END
Fig. 19 — Motormaster I Sensor Locations
X. STEP 10 — ADJUST FACTORY-INSTALLED OPTIONS
A. Optional EconoMi$erIV
See Fig. 20 and 21 for EconoMi$erIV component locati ons.
NOTE: These instructions are for installing the optional
EconoMi$erIV only. Refer to the accessory EconoMi$erIV or
EconoMi$er2 installation instructions when field in stalling an
EconoMi$erIV or EconoMi$er2 accessory.
To complete installation of t he optional EconoMi$erIV, perform the following procedure.
1. Remove the EconoMi$er IV hood. Refer to Step 8 —
Install Outdoor-Air Hood on page 10 for info rmation
on removing and in stalling the outdoor-air hood.
2. Relocate outdoor air temperature sensor from shipping position to operation pos ition on EconoMi $erIV.
See Fig. 20.
IMPORTANT: Failure to relocate the sensor w ill res ult in the
EconoMi$erIV not operating properly.
3. Re-install economizer hood.
4. Install all EconoMi$erIV accessories. EconoMi$erIV
wiring is shown in Fig. 22.
Outdoor air leakage is shown in Table 4. Return air pressure
drop is shown in Tabl e 5.
Table 4 — Out door Air Damper Leakage
NOTE: Dimensions in ( ) are in mm.
Fig. 18 — Wind Baffle Details
DAMPER STATIC PRESSURE (in. wg)
0.20.40.60.81.01.2
LEAKAGE (cfm)3553657590102
Table 5 — Return Air Pressure Drop (in. wg)
CFM
450050005400600072007500
0.0400.0500.0600.0700.0900.100
—11—
SCREWS
ECONOMI$ERIV
FRAME
TOP
SCREWS
OUTDOOR AIR
TEMPERATURE SENSOR
(INSTALLED OPERATION
POSITION)
LOW TEMPERATURE
COMPRESSOR
LOCKOUT SWITCH
ECONOMI$ERIV
SUPPLY AIR
TEMPERATURE SENSOR
LOCATION
Fig. 20 — EconoMi$erIV Component Locations —
End View
ACTUATOR
CONTROLLER
FLANGE
AND SCREWS
(HIDDEN)
1
R
T
R
T
c
a
V
4
2
M
O
C
4
2
_
c
a
V
T
O
H
H
X
E
+
t
e
S
V
0
2
1
V
2
1
1
N
5
N
n
H
i
X
M
E
s
o
P
4
n
P1
e
p
P
O
3
V
C
1
D
x
a
EF
T1
M
T
V
0
1
EF
V
2
V
C
D
V
t
C
e
D
S
V
1
0
Q
1
A
Q
A
V
2
+
e
O
e
r
S
C
F
l
o
O
o
S
C
B
D
+
R
S
A
R
S
Fig. 21 — EconoMi$erIV Component Locations —
Side View
DCV — Demand Controlled Ventilation
LEGEND
IAQ — Indoor Air Quality
LALS— Low Temperature Compressor
1. 620 ohm, 1 watt 5% resistor should be rem oved only when using differential
enthalpy or dry bulb.
2. If a separate field -supplied 24 v transform er is used for the IAQ sensor power
supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper
between P and P1 and set control minimum position POT to the minimum
position.
—12—
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.