Bryant 541A User Manual

installation, start-up and service instructions
SPLIT SYSTEM HEAT PUMP UNITS
Cancels: II 541A-120-1 II 541A-120-2
541A
Sizes 120,180 10 to 15 Tons
12/15/98
CONTENTS
Page
SAFETY CONSIDERATIONS ........................1
INSTALLATION ................................1-10
I. Step 1 — Complete Pre-Installation Checks .....1
II. Step 2 — Rig and Mount Unit .................1
III. Step 3 — Complete Refrigerant Piping
Connections ...............................2
PRE-START-UP ................................10-12
START-UP ....................................12-14
SERVICE .....................................14,15
TROUBLESHOOTING ...........................16-19
START-UP CHECKLIST ....................CL-1, CL-2
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical components and location of equipment (roofs, elevated structures, etc.).
Only trained, qualified installers and servicemechanicsshould install, start up, and service this equipment.
Untrained personnel can perform basic maintenance func­tions, such as cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Keep a quenching cloth and fire extinguisher handy.
• Use care in handling, rigging, and setting bulky
equipment.
WARNING:
to equipment is shut off before performing mainte­nance or service.
IMPORTANT: Follow unit location, height proximity, and pip­ing requirements in this booklet carefully to enhance system efficiency and to avoid system failure. Read entire booklet be­fore starting installation.
I. STEP 1 — COMPLETE PRE-INSTALLATION CHECKS A. Uncrate Unit
Remove unit packaging except for thetopskidassembly, which should be left in place until after the unit is rigged into position.
To prevent electric shock, be sure power
INSTALLATION
B. Inspect Shipment
File claim with shipping company if shipment is damaged or incomplete.
C. Consider System Requirements
• Consult local building and electrical codes for special in­stallation requirements.
• Allow sufficient space for airflow clearance, wiring, refrig­erant piping, and servicing unit. See Fig. 1 and 2.
• Ensure unit weight will be properly supported. See Table 1.
• Unit may be mounted on a level pad directly on the base channels or mounted on raised pads at support points. See Fig. 3 and Table 2 for weight distribution based on recom­mended support points.
NOTE: If vibration isolators are required for a particular in­stallation, use data in Table 2 to make proper selection.
• Accessory mounting legs (Part No. 309273-227) are recom­mended for elevation of unit for improved air circulation and better condensate drainage. Legs also minimize inter­ference from ice build-up, snow, leaves, and debris. See Fig. 1.
II. STEP 2 — RIG AND MOUNT UNIT
CAUTION:
prior to rigging. Be careful rigging, handling, and in­stalling unit. Improper unit location can cause system malfunction and material damage. Inspect base rails for any shipping damage and make sure they are fastened securely to unit before rigging.
A. Rigging
Units are designed for overhead rigging only. For this pur­pose, the transverse base rails extend beyond sides of unit, with holes provided in end plates to attach clevis for secur­ing cables. Rig with top skid packaging assembly in place to prevent unit damage by rigging cable. For coil face protec­tion, place plywood sheets against the sides of unit, behind cables. Run cables to a central suspension point so that the angle from the horizontal is not less than 45 degrees. Raise and set unit down carefully.
If it is necessary to roll unit into position, mount unit on field­supplied longitudinal rails using a minimum of 3 rollers.AP­PLY FORCE TO THE RAILS, NOT THE UNIT. If unit is to be skidded into position, place it on a large pad and drag the pad. DO NOT APPLY ANY FORCE TO THE UNIT.
Raise from above to lift unit from rails or pad when placing unit in final position.
Be sure unit panels are securely in place
Table 1 — Physical Data
UNIT 541A 120 180
OPERATING WEIGHT (lb) 750 803 REFRIGERANT R-22 R-22
Operating Charge (lb)* 30 37
COMPRESSOR Recip Hermetic; 1750 Rpm
Model No. 06DF824 06DF537 Cylinders 66 Oil (pts) 10 10 Crankcase Heater (Watts) 180 180
OUTDOOR AIR FANS Direct Drive — Axial Flow
Number 22 Speed (rpm) 1075 1075 Diameter (in.) 26 26 Motor Hp Airflow (cfm) 11,000 11,000 kW (total) 1.46 1.46
OUTDOOR COIL Plate Fins; 15 Per Inch
Rows Deep 23 Face Area (sq ft) 29.2 29.2 Storage Capacity (lb)† 27.2 40.1
CONTROLS
High-Pressure Switch (HPS)
Cutout (psig) 400 Cut-in (psig) 300
Loss-of-Charge Switch
(Liquid Line)
Cutout (psig) 7 6 3 Cut-in (psig) 22 6 5
Head Pressure
(No. 2 Fan Cycling)**
Opens (psig) 160±10 Closes (psig) 255±10
Oil Pressure Switch (Differential)
Set Point (psig)
(Close on Rise) 9.5 6 1 (Open on Fall) 5
Defrost Pressure Switch (HPS2)
Opens (psig) 280 6 10 Closes (psig) 180 6 2
THERMOSTAT
Defrost Switch
Opens (F) 65 80 Closes (F) 27 27
*Approximate charge with 25 ft of interconnecting piping. Use
appropriate charging charts for actual charging of unit.
†Refrigerant storage capacity at 120 F condensing temperature with
condenser 80% full of liquid.
**Head pressure control on cooling cycle only.
1
2
1
2
B. Locate Unit
For service access and unrestricted airflow,provide2 ft clear­ance on each end of unit and 3 ft clearance on each side of unit. Position unit so that there is unrestricted airflow above unit.
NOTE: Before mounting unit, remove 4 holddown brackets and release skid.
If conditions or local codes require unit to be fastened to pad, use the mounting holes in the 4 unit mounting feet (see Fig. 1).
C. Mount Unit
The unit may be mounted on a solid, level concrete pad, on accessory mounting legs, or on field-supplied raised supports at each mounting position. (Note that mounting hardware is field supplied.)
Weightdistribution (shown in Fig. 3 and Table 2) determines the type of support required. Bolt unit securely to pad or sup­ports after unit is in position and is level. Be sure to mount unit level to ensure proper oil return to compressors. Mount­ing holes on unit can be used to secure unit to vibration iso­lators, if required.
D. Compressor Mounting
As shipped, compressor is held down by 4 bolts. After unit is installed, loosen each bolt using locknut shown in Fig. 4 un-
3
til flat washer (
⁄8in.) can be moved with finger pressure.
III. STEP 3 — COMPLETE REFRIGERANT PIPING
CONNECTIONS
Refrigerant lines must be carefully designed and constructed to ensure equipment reliability and efficiency. Line length, pressure drop, compressor oil return, and vertical separation are several of the design criteria that must be evaluated. See the following sections.
IMPORTANT: Piping must be properly sized and installed for the system to operate efficiently.
A. Check Vertical Separation
If there is any vertical separation between the indoor and out­door units, checkT able3 to ensure that the separation is within allowable limits. Relocate equipment if necessary.
—2—
Fig. 1 — Dimensions
—3—
12 3 45 6 78 9101112
13
14 15
28
27
26
1—Defrost Board/Time GuardT II Control 2—Fuse 3—Fan No. 1 4—Signal-LOC™ Device 5—Outdoor-Fan Relay 6—Outdoor-Fan Contactor 7—Compressor Contactor 8—Fan Motor Capacitors 9—Circuit Breaker
10 — Fan No. 2
38 1/4"
2
LEGEND
11 — Power Terminal Block 12 — Control Terminal Block 13 — Compressor Lockout (CLO2 for
Crankcase Heater)
14 — Control Relay (CR3) 15 — Liquid Line Solenoid 16 — Control Relay (CR2) 17 — No Dump Relay (NDR) 18 — Oil Pressure Switch 19 — Fusible Plug (hidden)
Fig. 2 — Component Locations
4
26 11/16"
UNIT
541A
120 750 147 228 228 147 180 803 158 243 244 158
19202122232425
20 — High-Pressure Switch 21 — Compressor 22 — Capacity Control Solenoid 23 — Filter Drier 24 — Muffler 25 — Oil Solenoid 26 — Reversing Valve 27 — Accumulator 28 — Coil
Table2—Weight Distribution
WEIGHT — lb
Total
Operating
Weight
1234
Support Point
(Fig. 3)
16
17
18
541A120, 180
1
3
Fig.3—Weight Distribution
Table 3 — Maximum Vertical Separation*
OUTDOOR
UNIT 541A
INDOOR
UNIT
524A-H
Above Outdoor
DISTANCE — FT
Unit
Indoor Unit
Below Outdoor
Unit
120 120 50 50 180 180 80 80
*Vertical distance between indoor and outdoor units.
—4—
Fig. 4 — Compressor Mounting
B. Refrigerant Line Design and Sizing
Consider the length of the piping required between the out­door and indoor units. The maximum allowable line length is 100 ft. Select proper liquid and vapor line sizes from Table 4. Contact your local representative if assistance is required for design details and proper piping practices.
Table 4 — Piping Selection and Refrigerant
Charge Data
OUTDOOR
UNIT 541A
120 180
120 30 38 46 48 180 37 45 59 62
LEGEND
L—Liquid Line V—Vapor Line
*Approximately 4 elbows assumed in determining pipe sizes.
Maximum length of interconnecting piping is 100 ft.
**Approximate system charge is for estimating only. It includes charge
requirements for one outdoor unit, matching indoor coil, and intercon­necting piping. See Preliminary Charge section on page 10.
NOTE: If there is a vertical separation between indoor and outdoor units, see Table 3. Double vapor line riser may be required.
LENGTH 0F PIPING — FT*
0-25 25-60 60-100†
Line Size (in. OD)
LVLVLV
5
⁄811⁄
5
⁄813⁄
Approximate System Charge
5
8
⁄813⁄
3
8
⁄415⁄
lb**
8 8
5
⁄815⁄
3
⁄415⁄
8 8
MAXIMUM
LIQUID
LINE OD
(in.)
5
8
3
4
Maximum
Charge —
lb
Carefully evaluate any vapor risers at minimum load condi­tions to ensure proper compressor oil return. If the indoor unit is above the outdoor unit, the riser will function as a hot gas riser.If the outdoor unit is above the indoor unit, the riser is a suction riser. Design and construct a double riser if nec­essary. Contact your local representative if assistance is required.
C. Liquid Line Piping Procedure
Pipe the system liquid line as follows:
WARNING:
Unit is pressurized with a holding charge of refrigerant. Recover R-22 holding charge before re­moving runaround liquid piping loop. Failure to re­cover holding charge before removing piping loop could result in equipment damage and severe injury.
1. Open service valves in sequence: a. Discharge service valve on compressor. b. Suction service valve on compressor. c. Liquid line valve.
2. Remove
1
⁄4-in. flare cap from liquid valve Schrader port.
3. Attach refrigerant recovery device and recover holding charge.
4. Remove runaround loop.
5. Connect system liquid line from liquid connection of out­door (541A) unit to indoor unit liquid line connections. See Fig. 5 for typical piping and wiring. Select proper field-supplied bi-flow filter driers and install in the liq­uid line. See Fig. 6. Install a field-supplied liquid mois­ture indicator between the filter drier(s) and the liquid connections on the indoor (524A-H) unit. Braze or silver alloy solder all connections. Pass nitrogen or other inert gas through piping while making connections to pre­vent formation of copper oxide. (Copper oxides are ex­tremely active under high temperature and pressure. Failure to prevent collection of copper oxides may re­sult in system component failures.)
D. Vapor Line Piping Procedure
Connect system vapor line to the vapor line stub on the out­door unit and the vapor stubs on the indoor unit. At the in­door unit, construct vapor piping branches as shown in Fig. 7 for good mixing of the refrigerant leaving the indoor coil dur­ing cooling. This will ensure proper TXV (thermostatic ex­pansion valve) bulb sensing.
Where vapor line is exposed to outdoor air, line must be in­sulated. See Table 5 for insulation requirements.
—5—
LEGEND
NEC — National Electrical Code TXV — Thermostatic Expansion Valve
*Field supplied.
Piping
NOTES:
1. All piping must follow standard refrigerant piping techniques.
2. All wiring must comply with applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include, all details for a spe­cific installation.
4. Filter driers must be bi-flow type suited for heat pump duty.
5. Internal factory-supplied TXVs and check valves not shown.
Fig.5—Typical System Piping and Wiring
—6—
BI-FLOW FILTER DRIER
LIQUID LINE
TXV
A
B
REDUCING TEE
UNIT
541A
120
180
LIQUID
LINE
SIZE (in.)
1
2
5
8
1
2
5
8
LEGEND
TXV — Thermostatic Expansion Valve
Fig. 6 — Recommended Filter Driers and Installation Locations
A
INDOOR COIL
PART NO.
QUANTITY
REQUIRED
FIGURE
REFERENCE
P504-8084S 2 A P504-8165S 1 B P504-8084S 2 A P504-8085S 2 A
LEGEND
TXV — Thermostatic Expansion Valve
Fig.7—Vapor Line Branch Piping Details
Table 5 — Insulation for Vapor Line Exposed to Outdoor Conditions
LENGTH OF EXPOSED
VAPOR LINE*
ft in. 10 25 35 50
*Recommended vapor line insulation for piping exposed to outdoor conditions to
prevent loss of heating during heating cycle. When vapor line goes through inte­rior spaces, insulation should be selected to prevent condensation on cooling cycle. Heating capacity should be reduced 1000 Btuh if over 35 ft of vapor line with
3
⁄4in. insulation is exposed to outdoor conditions.
†Closed cell foam insulation with a thermal conductivity of:
0.28 Btu • in/ft2•h•°F.
INSULATION THICKNESS†
3
8
1
2
3
4
3
4
—7—
E. Provide Safety Relief
A fusible plug is located on the compressor crankcase (Fig. 8). Do not cap this plug. If local code requires additional safety devices, install as directed.
Head Pressure Control Fan cycling for head pressure control is a standard offering
but is functional on the cooling cycle only. Number 2 fan cycles as a function of liquid pressure. Fan cycling pressure switch cycles the fan off at 160 ± 10 psig as pressure decreases and cycles back on at 255 ± 10 psig. Switch is automatically by­passed in heating cycle. Table 6 shows minimum outdoor am­bient air temperature for full cooling capacity.
C. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to de­termine the percentage of voltage imbalance:
% Voltage Imbalance: = 100 x
max voltage deviation from average voltage
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Fig. 8 — Location of Fusible Plug
Table 6 — Minimum Outdoor Air
Operating Temperature
UNIT 541A
120
180
*Applies to Cooling mode of operation only.
%
COMPRESSOR
CAPACITY
100 90 35
67 80 45
100 90 23
67 80 36
OUTDOOR COIL
TEMP — F
MINIMUM
OUTDOOR
TEMP — F*
Standard Unit
IV. STEP 4 — COMPLETE ELECTRICAL CONNECTIONS A. Power Supply
Electrical characteristics of available power supply must agree with nameplate rating. Supply voltage must be within toler­ances shown in Table 7. Phase unbalance must not exceed 2%. Operation of unit on improper supply voltage or with ex-
cessive phase imbalance constitutes abuse and is not covered by warranty.
Per local code requirements, provide an adequate fused dis­connect switch within sight of unit and out of reach of chil­dren. Provision for locking switch open (off) is advisable to prevent power from being turned on while unit is being ser­viced. The disconnect switch, fuses, and field wiring must com­ply with local requirements. Refer to Table 7 for electrical data. Route power wiring through entrance in right-hand cor­ner post of unit. The power terminal block is sized to handle either copper or aluminum wires. Unit must be grounded. Af­fix crankcase heater warning sticker to unit disconnect switch.
B. Power Wiring
All power wiring must comply with applicable local require­ments. Install a field-supplied branch circuit disconnect switch that can be locked off or open. Run power wires from discon­nect switch through unit power opening and connect to ter­minal block inside the unit control box. See Fig. 9.
Average Voltage =
452 + 464 + 455
3
= 457 v
Determine maximum deviation from average voltage:
(AB) 457 − 452 = 5 v (BC) 464 − 457 = 7 v (AC) 457 − 455 = 2 v
Maximum deviation is 7 v. Determine percentage of voltage imbalance:
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable of 2%.
IMPORTANT: Contact your local electric utility company immediately if the supply voltage phase imbalance is more than 2%.
WARNING:
Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur.This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit ap­proved for electrical ground when installed in accor­dance with NEC (National Electrical Code), ANSI/ NFPA(AmericanNational Standards Institute/National Fire Protection Association), and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury of others.
IMPORTANT: Operation of unit on improper power supply volt­age or with excessive phase imbalance constitutes abuse and is not covered by Bryant warranty.
D. General Wiring Notes
1. A crankcase heater is wired in the control circuit so it is always operable as long as power supply disconnect is on, even if any safety device is open or unit stop/start switch is off.
2. The power-circuit field supply disconnect should never
be open except when unit is being serviced or is to be down for a prolonged period. When operation is resumed, crankcase heater should be energized for 24 hours before start-up. If system is to be shut down for a pro­longed period, it is recommended that the suction and discharge valves be closed to prevent an excessive accumulation of refrigerant in the compressor oil.
3. Terminalsfor field power supply are suitable for copper, copper-clad aluminum, or aluminum conductors.
—8—
Loading...
+ 16 hidden pages