SERVICE .....................................14,15
TROUBLESHOOTING ...........................16-19
START-UP CHECKLIST ....................CL-1, CL-2
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components and
location of equipment (roofs, elevated structures, etc.).
Only trained, qualified installers and servicemechanicsshould
install, start up, and service this equipment.
Untrained personnel can perform basic maintenance functions, such as cleaning coils and filters and replacing filters.
All other operations should be performed by trained service
personnel.
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the
equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Keep a quenching cloth and fire extinguisher handy.
• Use care in handling, rigging, and setting bulky
equipment.
WARNING:
to equipment is shut off before performing maintenance or service.
IMPORTANT: Follow unit location, height proximity, and piping requirements in this booklet carefully to enhance system
efficiency and to avoid system failure. Read entire booklet before starting installation.
I. STEP 1 — COMPLETE PRE-INSTALLATION CHECKS
A. Uncrate Unit
Remove unit packaging except for thetopskidassembly, which
should be left in place until after the unit is rigged into
position.
To prevent electric shock, be sure power
INSTALLATION
B. Inspect Shipment
File claim with shipping company if shipment is damaged or
incomplete.
C. Consider System Requirements
• Consult local building and electrical codes for special installation requirements.
• Allow sufficient space for airflow clearance, wiring, refrigerant piping, and servicing unit. See Fig. 1 and 2.
• Ensure unit weight will be properly supported. See
Table 1.
• Unit may be mounted on a level pad directly on the base
channels or mounted on raised pads at support points. See
Fig. 3 and Table 2 for weight distribution based on recommended support points.
NOTE: If vibration isolators are required for a particular installation, use data in Table 2 to make proper selection.
• Accessory mounting legs (Part No. 309273-227) are recommended for elevation of unit for improved air circulation
and better condensate drainage. Legs also minimize interference from ice build-up, snow, leaves, and debris. See
Fig. 1.
II. STEP 2 — RIG AND MOUNT UNIT
CAUTION:
prior to rigging. Be careful rigging, handling, and installing unit. Improper unit location can cause system
malfunction and material damage. Inspect base rails for
any shipping damage and make sure they are fastened
securely to unit before rigging.
A. Rigging
Units are designed for overhead rigging only. For this purpose, the transverse base rails extend beyond sides of unit,
with holes provided in end plates to attach clevis for securing cables. Rig with top skid packaging assembly in place to
prevent unit damage by rigging cable. For coil face protection, place plywood sheets against the sides of unit, behind
cables. Run cables to a central suspension point so that the
angle from the horizontal is not less than 45 degrees. Raise
and set unit down carefully.
If it is necessary to roll unit into position, mount unit on fieldsupplied longitudinal rails using a minimum of 3 rollers.APPLY FORCE TO THE RAILS, NOT THE UNIT. If unit is to
be skidded into position, place it on a large pad and drag the
pad. DO NOT APPLY ANY FORCE TO THE UNIT.
Raise from above to lift unit from rails or pad when placing
unit in final position.
Be sure unit panels are securely in place
Table 1 — Physical Data
UNIT 541A120180
OPERATING WEIGHT (lb)750803
REFRIGERANTR-22R-22
Operating Charge (lb)*3037
COMPRESSORRecip Hermetic; 1750 Rpm
Model No.06DF82406DF537
Cylinders66
Oil (pts)1010
Crankcase Heater (Watts)180180
OUTDOOR AIR FANSDirect Drive — Axial Flow
Number22
Speed (rpm)10751075
Diameter (in.)2626
Motor Hp
Airflow (cfm)11,00011,000
kW (total)1.461.46
OUTDOOR COILPlate Fins; 15 Per Inch
Rows Deep23
Face Area (sq ft)29.229.2
Storage Capacity (lb)†27.240.1
CONTROLS
High-Pressure Switch (HPS)
Cutout (psig)400
Cut-in (psig)300
Loss-of-Charge Switch
(Liquid Line)
Cutout (psig)7 6 3
Cut-in (psig)22 6 5
Head Pressure
(No. 2 Fan Cycling)**
Opens (psig)160±10
Closes (psig)255±10
Oil Pressure Switch (Differential)
Set Point (psig)
(Close on Rise)9.5 6 1
(Open on Fall)5
Defrost Pressure Switch (HPS2)
Opens (psig)280 6 10
Closes (psig)180 6 2
THERMOSTAT
Defrost Switch
Opens (F)6580
Closes (F)2727
*Approximate charge with 25 ft of interconnecting piping. Use
appropriate charging charts for actual charging of unit.
†Refrigerant storage capacity at 120 F condensing temperature with
condenser 80% full of liquid.
**Head pressure control on cooling cycle only.
1
⁄
2
1
⁄
2
B. Locate Unit
For service access and unrestricted airflow,provide2 ft clearance on each end of unit and 3 ft clearance on each side of
unit. Position unit so that there is unrestricted airflow above
unit.
NOTE: Before mounting unit, remove 4 holddown brackets
and release skid.
If conditions or local codes require unit to be fastened to
pad, use the mounting holes in the 4 unit mounting feet (see
Fig. 1).
C. Mount Unit
The unit may be mounted on a solid, level concrete pad, on
accessory mounting legs, or on field-supplied raised supports
at each mounting position. (Note that mounting hardware is
field supplied.)
Weightdistribution (shown in Fig. 3 and Table 2) determines
the type of support required. Bolt unit securely to pad or supports after unit is in position and is level. Be sure to mount
unit level to ensure proper oil return to compressors. Mounting holes on unit can be used to secure unit to vibration isolators, if required.
D. Compressor Mounting
As shipped, compressor is held down by 4 bolts. After unit is
installed, loosen each bolt using locknut shown in Fig. 4 un-
3
til flat washer (
⁄8in.) can be moved with finger pressure.
III. STEP 3 — COMPLETE REFRIGERANT PIPING
CONNECTIONS
Refrigerant lines must be carefully designed and constructed
to ensure equipment reliability and efficiency. Line length,
pressure drop, compressor oil return, and vertical separation
are several of the design criteria that must be evaluated. See
the following sections.
IMPORTANT: Piping must be properly sized and installed for
the system to operate efficiently.
A. Check Vertical Separation
If there is any vertical separation between the indoor and outdoor units, checkT able3 to ensure that the separation is within
allowable limits. Relocate equipment if necessary.
—2—
Fig. 1 — Dimensions
—3—
12 3 456 78 9101112
13
14
15
28
27
26
1—Defrost Board/Time GuardT II Control
2—Fuse
3—Fan No. 1
4—Signal-LOC™ Device
5—Outdoor-Fan Relay
6—Outdoor-Fan Contactor
7—Compressor Contactor
8—Fan Motor Capacitors
9—Circuit Breaker
10 — Fan No. 2
38 1/4"
2
LEGEND
11 — Power Terminal Block
12 — Control Terminal Block
13 — Compressor Lockout (CLO2 for
Crankcase Heater)
14 — Control Relay (CR3)
15 — Liquid Line Solenoid
16 — Control Relay (CR2)
17 — No Dump Relay (NDR)
18 — Oil Pressure Switch
19 — Fusible Plug (hidden)
*Vertical distance between indoor and outdoor units.
—4—
Fig. 4 — Compressor Mounting
B. Refrigerant Line Design and Sizing
Consider the length of the piping required between the outdoor and indoor units. The maximum allowable line length is
100 ft. Select proper liquid and vapor line sizes from Table 4.
Contact your local representative if assistance is required for
design details and proper piping practices.
Table 4 — Piping Selection and Refrigerant
Charge Data
OUTDOOR
UNIT
541A
120
180
12030384648
18037455962
LEGEND
L—Liquid Line
V—Vapor Line
*Approximately 4 elbows assumed in determining pipe sizes.
†Maximum length of interconnecting piping is 100 ft.
**Approximate system charge is for estimating only. It includes charge
requirements for one outdoor unit, matching indoor coil, and interconnecting piping. See Preliminary Charge section on page 10.
NOTE: If there is a vertical separation between indoor and outdoor units,
see Table 3. Double vapor line riser may be required.
LENGTH 0F PIPING — FT*
0-2525-6060-100†
Line Size (in. OD)
LVLVLV
5
⁄811⁄
5
⁄813⁄
Approximate System Charge
5
8
⁄813⁄
3
8
⁄415⁄
lb**
8
8
5
⁄815⁄
3
⁄415⁄
8
8
MAXIMUM
LIQUID
LINE OD
(in.)
5
⁄
8
3
⁄
4
Maximum
Charge —
lb
Carefully evaluate any vapor risers at minimum load conditions to ensure proper compressor oil return. If the indoor
unit is above the outdoor unit, the riser will function as a hotgas riser.If the outdoor unit is above the indoor unit, the riser
is a suction riser. Design and construct a double riser if necessary. Contact your local representative if assistance is
required.
C. Liquid Line Piping Procedure
Pipe the system liquid line as follows:
WARNING:
Unit is pressurized with a holding charge
of refrigerant. Recover R-22 holding charge before removing runaround liquid piping loop. Failure to recover holding charge before removing piping loop could
result in equipment damage and severe injury.
1. Open service valves in sequence:
a. Discharge service valve on compressor.
b. Suction service valve on compressor.
c. Liquid line valve.
2. Remove
1
⁄4-in. flare cap from liquid valve Schrader port.
3. Attach refrigerant recovery device and recover holding
charge.
4. Remove runaround loop.
5. Connect system liquid line from liquid connection of outdoor (541A) unit to indoor unit liquid line connections.
See Fig. 5 for typical piping and wiring. Select proper
field-supplied bi-flow filter driers and install in the liquid line. See Fig. 6. Install a field-supplied liquid moisture indicator between the filter drier(s) and the liquid
connections on the indoor (524A-H) unit. Braze or silver
alloy solder all connections. Pass nitrogen or other inert
gas through piping while making connections to prevent formation of copper oxide. (Copper oxides are extremely active under high temperature and pressure.
Failure to prevent collection of copper oxides may result in system component failures.)
D. Vapor Line Piping Procedure
Connect system vapor line to the vapor line stub on the outdoor unit and the vapor stubs on the indoor unit. At the indoor unit, construct vapor piping branches as shown in Fig. 7
for good mixing of the refrigerant leaving the indoor coil during cooling. This will ensure proper TXV (thermostatic expansion valve) bulb sensing.
Where vapor line is exposed to outdoor air, line must be insulated. See Table 5 for insulation requirements.
—5—
LEGEND
NEC — National Electrical Code
TXV — Thermostatic Expansion Valve
*Field supplied.
Piping
NOTES:
1. All piping must follow standard refrigerant piping techniques.
2. All wiring must comply with applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides
only and are not intended for, or to include, all details for a specific installation.
4. Filter driers must be bi-flow type suited for heat pump duty.
5. Internal factory-supplied TXVs and check valves not shown.
Fig.5—Typical System Piping and Wiring
—6—
BI-FLOW FILTER DRIER
LIQUID LINE
TXV
A
B
REDUCING TEE
UNIT
541A
120
180
LIQUID
LINE
SIZE (in.)
1
⁄
2
5
⁄
8
1
⁄
2
5
⁄
8
LEGEND
TXV — Thermostatic Expansion Valve
Fig. 6 — Recommended Filter Driers and Installation Locations
Table 5 — Insulation for Vapor Line Exposed to Outdoor Conditions
LENGTH OF EXPOSED
VAPOR LINE*
ftin.
10
25
35
50
*Recommended vapor line insulation for piping exposed to outdoor conditions to
prevent loss of heating during heating cycle. When vapor line goes through interior spaces, insulation should be selected to prevent condensation on cooling cycle.
Heating capacity should be reduced 1000 Btuh if over 35 ft of vapor line with
3
⁄4in. insulation is exposed to outdoor conditions.
†Closed cell foam insulation with a thermal conductivity of:
0.28 Btu • in/ft2•h•°F.
INSULATION THICKNESS†
3
⁄
8
1
⁄
2
3
⁄
4
3
⁄
4
—7—
E. Provide Safety Relief
A fusible plug is located on the compressor crankcase
(Fig. 8). Do not cap this plug. If local code requires additional
safety devices, install as directed.
Head Pressure Control
Fan cycling for head pressure control is a standard offering
but is functional on the cooling cycle only. Number 2 fan cycles
as a function of liquid pressure. Fan cycling pressure switch
cycles the fan off at 160 ± 10 psig as pressure decreases and
cycles back on at 255 ± 10 psig. Switch is automatically bypassed in heating cycle. Table 6 shows minimum outdoor ambient air temperature for full cooling capacity.
C. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance:
% Voltage Imbalance:
= 100 x
max voltage deviation from average voltage
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Fig. 8 — Location of Fusible Plug
Table 6 — Minimum Outdoor Air
Operating Temperature
UNIT
541A
120
180
*Applies to Cooling mode of operation only.
%
COMPRESSOR
CAPACITY
1009035
678045
1009023
678036
OUTDOOR COIL
TEMP — F
MINIMUM
OUTDOOR
TEMP — F*
Standard Unit
IV. STEP 4 — COMPLETE ELECTRICAL CONNECTIONS
A. Power Supply
Electrical characteristics of available power supply must agree
with nameplate rating. Supply voltage must be within tolerances shown in Table 7. Phase unbalance must not exceed
2%. Operation of unit on improper supply voltage or with ex-
cessive phase imbalance constitutes abuse and is not covered
by warranty.
Per local code requirements, provide an adequate fused disconnect switch within sight of unit and out of reach of children. Provision for locking switch open (off) is advisable to
prevent power from being turned on while unit is being serviced. The disconnect switch, fuses, and field wiring must comply with local requirements. Refer to Table 7 for electrical
data. Route power wiring through entrance in right-hand corner post of unit. The power terminal block is sized to handle
either copper or aluminum wires. Unit must be grounded. Affix crankcase heater warning sticker to unit disconnect switch.
B. Power Wiring
All power wiring must comply with applicable local requirements. Install a field-supplied branch circuit disconnect switch
that can be locked off or open. Run power wires from disconnect switch through unit power opening and connect to terminal block inside the unit control box. See Fig. 9.
Average Voltage =
452 + 464 + 455
3
= 457 v
Determine maximum deviation from average voltage:
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v. Determine percentage of voltage
imbalance:
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is
below the maximum allowable of 2%.
IMPORTANT: Contact your local electric utility company
immediately if the supply voltage phase imbalance is more
than 2%.
WARNING:
Unit cabinet must have an uninterrupted,
unbroken electrical ground to minimize the possibility
of personal injury if an electrical fault should occur.This
ground may consist of electrical wire connected to unit
ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/
NFPA(AmericanNational Standards Institute/National
Fire Protection Association), and local electrical codes.
Failure to follow this warning could result in the
installer being liable for personal injury of others.
IMPORTANT: Operation of unit on improper power supply voltage or with excessive phase imbalance constitutes abuse and
is not covered by Bryant warranty.
D. General Wiring Notes
1. A crankcase heater is wired in the control circuit so it is
always operable as long as power supply disconnect is
on, even if any safety device is open or unit stop/start
switch is off.
2. The power-circuit field supply disconnect should never
be open except when unit is being serviced or is to
be down for a prolonged period. When operation is
resumed, crankcase heater should be energized for 24 hours
before start-up. If system is to be shut down for a prolonged period, it is recommended that the suction and
discharge valves be closed to prevent an excessive
accumulation of refrigerant in the compressor oil.
3. Terminalsfor field power supply are suitable for copper,
copper-clad aluminum, or aluminum conductors.
—8—
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.