Bryant 53DFS250-SL-BRY Installation Instructions

Su
AUTO
Installation Instructions
DIGITAL THERMOSTAT 53DFS250-SL-BRY
Cooling Only, Heat Cool, and Heat Pump
Cancels: New IIK 53-1
10/1/04
STEP #1 PREPARATION
A. Proper installation of the thermostat will be ac-
complished by following these step by step in­structions. If you are unsure about any of these steps, call a qualified technician for assistance.
B. Assemble tools:
COOL
HEAT
o
o
Am
:
MULTI-STAGE • SEVEN DAY PROGRAMMABLE
Table of Contents
STEP #1 PREPARATION 1 STEP #2 WIRE CONNECTIONS 1 SAMPLE WIRING DIAGRAMS 2 STEP #3 TEST OPERATION 2 TROUBLESHOOTING 2 CALIBRATION 2
IMPORTANT:
CAUTION: DISCONNECT POWER TO THE SYS-
TEM BEFORE
This device complies with Part 15 of the FCC rules. Opera­tion is subject to the following 2 conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interfer­ence that may cause undesired operation.
Follow
Installation Instructions
INSTALLING THE THERMOSTAT.
carefully.
Flat Blade
Screwdriver
Wire Cutter
and Stripper
C. Carefully unpack the thermostat. Save the screws,
bracket, and instructions.
D. Turn off the power to the system at the main fuse
panel. Most systems have a separate breaker for disconnecting power to the indoor and outdoor units.
STEP #2 WIRE CONNECTIONS
Refer to the chart below, or the wiring diagrams that follow for thermostat functions and corresponding thermostat connectors.
INSTALL ON THE
FUNCTION
Lo Fan G1
Compressor Y
Heating H2
24 v Power R
Common C
Rev. Valve O*
Hi Fan G2
Remote Sensor +5vdc RS+5
Remote Sensor Signal RS
Remote Sensor Ground RS GND
Dry Contact Switch 1 CK1 Dry Contact Switch 2 CK2
Defrost H1
*Only used with Heat Pump Systems.
NEW THERMOSTAT
CONNECTOR MARKED
LISTED
Sample Wiring Diagrams HEAT PUMP
3 conductor 18 ga unshielded cable from the thermostat to the remote sensor.
RS-GND
COMPRESSOR
REVERSING
AUX HEAT
g
RS
RS+V
COMMON
POWER
LO FAN
VALVE
HIGH FAN
DEFROST
H2
e
G1 R CY
OH2
G2
H1
G2
RS+5 RS RS GND
8 Conductor 18 gage unshielded cable from the thermostat to the equipment.
CK1
CK2
G1 H1
O Y
R C
STEP #3 TEST OPERATION
Turn the power on to the HVAC (heating, ventilation,
A.
and air conditioning) system.
B.
Press the
MODE
button until the HEAT icon appears on the display. Press the Up or Down buttons until the set temperature is 10 degrees above room tempera­ture. The unit should turn on and supply heat.
C.
Press the
MODE
button until the COOL icon appears on the display. Press the Up or Down buttons until the set temperature is 10 degrees below room tempera­ture. The unit should turn on.
NOTE: Most equipment has a time delay between cy­cles. This feature is defeatable on the thermostat. Consult the Owner's Manual under Setup: Cycles per hour.
D.
Press the
MODE
button repeatedly until OFF is dis­played on the thermostat.
TROUBLESHOOTING
SYMPTOM CAUSE REMEDY
When not using a com­mon wire the air condi­tioning equipment tries repeatedly to tur n on, but cannot. At times the display dims or dis­appears.
There is not enough power available to “power share”.
Connect a 270 ohm, 10 watt power resistor at the unit as shown below.
For Probl em A/C
RH2 YC
TR300-10w
For Probl em Heat
RH2 Y C
Sample Wiring Diagrams HEAT-COOL/
COOLING ONLY
H2
3 conductor 18 gag unshielded cable from the thermostat to the remote sensor.
RS-GND
COMMON
24vPOWER
COMPRESSOR
AUX HEAT
HIGH FAN
e
RS
RS+V
LO FAN
G1 R CY
OH2
G2
G2
RS+5 RS RS GND
8 Conductor 18 gage unshielded cable from the thermostat to the equipment.
NOTE: For cooling only, the H2 connection is not required.
CK1
CK2
G1 H1
O Y
R C
TR300-10w
The air conditioning does not attempt to turn on.
The display is blank. Lack of proper power. Make sure power is
The air conditioning does not attempt to turn on.
The heating does not attempttoturnon.
The strip heater turns off well before reaching set point.
The compressor timer lock­out may prevent the air conditioner from turning on, for a period of time.
The cooling set point is set too high.
The heating set point is set too low.
Heat pump is incorrectly selected “on”inthe Advanced Setup.
Consult the Owner’s Manual in the Setup sec­tion to defeat the cycles per hour and compressor timeguard.
turned on to the HVAC unit and there is 24 vac between R and H2. If the HVAC unit is cool­ing only, check there is 24 vac between R and C.
Press the down arrow until the cooling set point is 10 degrees lower than the room temperature.
Press the up arrow until the heating set point is 10 degrees higher than the room temperature.
Select heat pump “off” during Advanced Setup programming. Consult the Owner’s Manual.
CALIBRATION
Every thermostat is calibrated before it leaves the factory. Un­der normal circumstances there will never be a need to recali­brate the thermostat again. To accommodate s the thermostat may be recalibrated following these steps:
1. While holding the Mode button in, press the fan button for 5 seconds. After all the icons in the display appear, release the buttons.
2. Press the Up and Down arrow buttons simultaneously, twice.
3. Press the up or down buttons until the flashing number equals the current room temperature.
4. Press the Mode button to return to normal operation.
pecial needs
,
Copyright 2004 Bryant Heating & Cooling Systems Printed in U.S.A. CATALOG NO. 5353-000
Loading...