Bryant 538J-18-1 User Manual

installation, start-up and service instructions
LIGHT COMMERCIAL CONDENSING UNITS
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-7
I. Complete Pre-Installation Checks . . . . . . . . . . . . . . 1
II. Rig and Mount Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 3
IV. Make Electrical Connections
V. Accessory Installation. . . . . . . . . . . . . . . . . . . . . . . . 4
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
I. Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
II. Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
III. Cleaning Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
. . . . . . . . . . . . . . . . 4
538J
Sizes 018-060
Cancels: New II 538J-18-1
1/15/02
I. COMPLETE PRE-INSTALLATION CHECKS
A. Unpack Unit
Move unit to final location. Remove unit packaging being careful not to damage service valves or grilles.
B. Inspect Shipment
File claim with shipping company if shipment is damaged or incomplete. Check unit nameplate to ensure unit matches job requirements.
C. Consider System Requirements
Consult local b uilding codes and NEC for special installation requirements.
Allow sufficient space for air flow clearance, wiring, refriger­ant piping, and servicing unit. See Fig. 1 and 2. Unit can be mounted on a level pad directly on base legs or mounted on raised pads at support points. See Fig. 2 for center of gravity.
SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install or service air-conditioning equipment.
Untrained personnel may perform basic maintenance such as cleaning an d rep l ac ing f ilt er s. All oth er ope ra tio n s sho ul d be performed by trained service personnel. When working on air-conditioning equipment, observe safety precautions in literature, and on tags and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have a fire extin­guisher available. Read these instructions thoroughly. Con­sult local building codes and National Electrical Cod e (NEC, U.S.A. Standard) for special installation requirements.
INSTALLATION
WARNING: Before installing or servicing system,
always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable. Electrical shock can cause personal injury.
C
O
O
LIN
G
Fig. 1 — Typical Condensing Unit
WEIGHT
OPERATING
15.88 130 58.9
15.88 136 61.6
19.05 161 73.0
19.05 185 83.9
22.22 222 100.5
22.22 249 112.9
8
8
4
4
8
/
/
/
5
5
3
285.8 0-0
295.3 0-0
295.3 0-0
4
8
8
/
/
/
1
5
5
168.3 0-11
171.5 0-11
171.5 0-11
8
4
4
/
/
/
5
3
3
8
/
/
/
3
7
7
295.3 0-0
403.2 0-0
8
8
/
/
5
7
171.5 0-11
209.5 0- 4 406.4 0-0
206.4 0- 3
4
4
8
/
/
/
3
1
1
352.4 0-8
347.7 0-8
16
/
8
/
7
11
Support Feet
MINIMUM MOUNTING PAD DIMENSIONS
ft-in. mm
538J
511.2 1-1 330.2 0-6
511.2 1-1 330.2 0-6
511.2 1-1 330.2 0-6
511.2 1-1 330.2 0-6
817.6 1-1
817.6 1-1
8
8
8
8
16
/
/
/
1
1
1
444.5 1-8
444.5 1-8
444.5 1-8
2
2
2
/
/
/
1
1
1
16
/
/
/
1
3
3
444.5 1-8
752.5 2-8
752.5 2-8
2
8
8
/
/
/
1
5
5
UNIT SIZE
048 and 060 2- 0 x 4-2 609.6 x 1270.0
018,024,030 and 036 1-11 x 3-6 584.2 x 1066.8
clearance on compressor end and coil side. With multi-unit application, arrange units so discharge of
one does not enter inlet of another.
coil end, and 3 ft (914.4 mm) minimum clearance on compressor end and fan side. With fan facing
wall, allow 8(203.2 mm) minimum clearance on fan side and coil end, and 3 ft (914.4 mm) minimum
2. Dimensions in parenthesis are in millimeters.
NOTES:
1. Required clearances: With coil facing wall, allow 6(156.4 mm) minimum clearance on coil side and
3. Center of gravity .
436.6 1-5
436.6 1-5
436.6 1-5
16
16
/
/
/
3
3
3
595.3 1-5
595.3 1-5
595.3 1-5
16
16
/
/
/
7
7
7
369.9 1-4 406.4 1-11
369.9 1-4 406.4 1-11
369.9 1-4 406.4 1-11
16
16
/
/
/
9
9
9
938.2 1-2
938.2 1-2
938.2 1-2
16
16
/
/
/
15
15
15
638.2 3-0
638.2 3-0
ABCD E FGHJKLM
ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm lb kg
638.2 3-0
8
8
/
/
/
1
1
1
436.6 1-5
498.5 2-5
498.5 2-5
8
16
16
16
16
8
8
16
/
/
/
5
5
3
595.3 1-5
774.7 1-7
774.7 1-7
2
2
16
/
/
/
1
1
7
468.3 2- 6
468.3 2- 6
16
16
/
/
7
7
369.9 1-4 406.4 1-11
433.4 1-6
433.4 1-6
16
16
16
/
/
/
9
1
1
938.2 1-2
1131.9 1-5
1131.9 1-5
16
/
16
16
/
/
15
9
9
638.2 3-0
944.6 3-8
944.6 3-8
8
16
16
/
/
/
1
3
3
Fig. 2 — 538J018-060 — Dimensional Drawing
SIZE
UNIT
538J
024 2-1
030 2-1
036 2-1
048 3-1
018 2-1
060 3-1
—2—
II. RIG AND MOUNT UNIT
A. Mounting on Ground
Mount unit on a solid, level concrete pad. Position unit so water or ice from roof does not fall directly i nto unit. Field­fabricated stacking kits can be used when units are to be stacked. If conditions or local codes require unit to be fas­tened to a pad, 6 field-supplied tiedown bolts should be used and fastened through slots provided in unit mounting feet.
B. Mounting on Roof
Mount unit on level platform or frame at least 6 in. above roof surface. Isolate unit and tubing from structure.
C. Rigging
CAUTION: Be sure unit panels are securely in
place prior to rigging.
Keep unit upright. Lift unit using sling. Use cardboard or padding under sling, and spreader bars to prevent sling damage to unit. See Fig. 3. See Fig. 2 for center of gravity ref­erence. Install unit so coil does not face into prevailing winds. If this is not possible and constant winds above 25 mph are expected, use field-fabricat ed wind baffle.
NOTE: Accessory wind baffles should be used on all units with accessory low-ambient control.
Field-fabricat ed snow stan d may be used to rai se unit when operation will be required during the winter. Units may also be wall mounted using the accessory wall mounting kit.
III. COMPLETE REFRIGERATION PIPING CONNECTIONS
Outdoor units may be connected to indoor units using field­supplied tubing of refrigerant grade and condition. See Tables 1A and 1B for correct line sizes. Do not use less than 10 ft (3 m) of interconnecting tubing.
CAUTION: DO NOT BURY MORE THAN 36 IN. (922 mm) OF REFRIGERANT PIPE IN THE GROUND. If any section of pipe is buried, there must be a 6 in. (154 m) ver tic al r ise to the valv e con nec tion s on the outdoor unit. If more than the recommended length is buried, refrigerant m ay migra te to the coole r, buried section duri ng extended periods of system shut­down. This causes refrigerant slugging and could dam­age compressor at start-up.
Fig. 3 — Lifting Unit with Sling
A. Check AccuRater® Control
The AccuRater refrigerant control is required for cooling sys­tem capacity optimization. An AccuRater device with field­replaceable piston should be supplied with the indoor unit. Refer to AccuRater metering de vice table in separate indoor unit installation instructi ons to determine the corre ct Accu­Rater piston size required for the condenser/evaporator sys­tem being installed.
Note that one of 2 types of the AccuRater devices can be used. Use Type A only if Type B is unavailable. See Fig. 4. Do not interchange components between AccuRater device types. Matching of outdoor unit with indoor unit may require field replacement of piston. Replace piston, if required, before connecting refrigerant lines. Piston replacement instructions are included in the indoor unit installation instructions. After system installation is complete, see Refrigerant Charging section on page 8 to check and/or adjust refrigerant charge.
The 538J series units may also be installed with units using a thermostatic expansion valve (TXV). If a TXV is used, be sure to remove the pi ston from the i ndoor coil. See i nstalla­tion instruction s shipped with the TXV for proper posi tion­ing and adjustment.
When more than 50 ft (15.2 m) of interconnecting tubing and more than 30 ft (9.1 m) of vertical lift is used, refer to Part 3 of the System Desig n Manual for design details, or contac t your local distributor.
If either refrig era nt tu b ing or i ndoor co il is e xp ose d to a tmo ­spheric condit ions for long er than 5 minu tes , it must be evac ­uated to 1000 microns to eliminate contamination and moisture in the system.
Run refrigerant tubes as directly as possible, avoiding unnecessary turns and bend s. Suspend refrigerant tubes so they do not damage insulation on vapor tube and do not transmit vibration to the structure. Also, when passing refrigerant tubes through the wall, seal opening so that vibration is not transmitted to structure. Leave some slack in refrigerant tubes between structure and outdoor unit to absorb vibration. Refer to separate indoor unit installati on instructions for additiona l information.
TYPE A (FIELD-INSTALLED BYPASS TYPE)
TYPE B (RECOMMENDED)
NOTE: Arrow on AccuRater body points in free-flow direction, away
from the indoor coil.
Fig. 4 — AccuRater Metering Device Components
—3—
B. Make Piping Sweat Connections
Remove plastic caps from liquid and suction service valves. Use refrigerant gr ade tubi ng. Service val ves are closed from the factory and ready for brazing. After wrapping the service valve with a wet cloth, the tubing set can be brazed to the service valve using either silver bearing or non-silver bear­ing brazing material. Consult local code requirements. Refrigerant tubing and indoor coil are ready for leak testing.
NOTE: Unit is shipped with a full factory charge of R-22 refrigerant as indicated on nameplate.
Pass nitrogen or other inert gas through piping while braz­ing to prevent formation of copper oxide.
CAUTION: To avo id da ma ge whil e b ra zing, serv ice valves should be wrapped in a heat-sinking material such as a wet cloth .
CAUTION: When brazing tubing sets to the ser­vice valves, a brazing shield must be used to prevent damage to the painted unit surface.
C. Provide Safety Relief
A fusible plug is located in unit suction line; do not cap this plug. If local code requires addition al safety devices, insta ll as directed.
IV. MAKE ELECTRIAL CONNECTIONS
WARNING: Unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground ma y co nsist of electrical wir e connected to the unit ground lug in control compart­ment, or conduit approved for electrical ground when installed in accordance with NEC, ANSI/NFP A (Ame ri­can National Standards Institute/National Fire Protec­tion Association) 70, and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury to others.
CAUTION: Unit failu re as a result of oper ation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation will invalidate any appli­cable warranty.
A. Power Wiring
Unit is factory-w ired for voltage shown on nameplate. Pro­vide adequate, fused disconnect switch within sight of unit, readily accessible but out of reach of children. Provi sion for locking the switch open (off) is advisable to prevent power from being turn ed on w hile unit is be ing s erviced . Di sco nnect
switch, fuses, and field wiring must be in compliance with NEC (U.S.A. Standard) and applicable local codes. Use mini­mum 60 C wire for field power connection.
Route power wires through opening in the unit side panel and connect in unit control box as shown on unit label dia­gram and Fig. 5 and 6. Unit must be grounded.
B. Control Circuit Wiring
Control voltage is 24 v. See Fig. 5 and unit label diagram for field-supplied wiring details. Route control wire through opening in the unit side panel to connection in unit control box.
NOTE: For wire runs up to 50 ft (15 m), use no. 18 AWG (American Wire Gage) insulate d wire (35 C minimum). For 50 to 75 ft (15 to 23 m), use no. 16 AWG insulated wire. For more than 75 ft (23 m), use no. 14 AWG insulated wire. See Table 2 for conversion to European wire sizes.
NOTE: Oper ation of unit on imp rope r lin e vol tage c onst itute s abuse and co uld af fect any appl ic able warran ty. See Table 3. Do not install unit in system where voltage may fluctuate above or below permissible limits.
See Table 3 for recommended fuse sizes. When making elec­trical connections, provide cle arance at unit for refrigerant piping connections.
Use indoor unit transfo rmer a s 24-v (40-v a min imum) supply for system as shown in Fig. 5 or use accessory transformer.
WARNING: Before performing service or mainte­nance, be sure the indoor unit main power switch is off and indoor blower has completely stopped. Failure to do so may result in electrical shock or injury from rotating fan blades.
C. Connections to Duct-Free Fan Coil Units
The 538J units are designed for easy match-up to 619C, 619F, 619ENX018 and 619ENX024 duct-free fan coils. These units provide 24 -v power for the outdoor u nit from the fan coil. Connect the Y and C terminals of the indoor unit to the blue and brown wires of the outdoor unit with 20 gage (mini­mum) thermostat wire.
V. ACCESSORY INSTALLATION
Install all unit a ccessories per accessory installation instruc­tions prior to start-up.
Do not use accessory Time Guard® II device when combining a 538J unit with 619E indoor units.
When ambient temp erature will fall be low 55 F (1 3 C), a cces­sory low ambient controller (part no. 53DS900060) is required. When accessory low ambient kit is used, unit should also be equipped with accessory winter start kit and field-fabricated wind baffles.
—4—
Table 1A — Physical Data (English)
UNIT 538J 018 024 030 036 048 060 NOMINAL CAPACITY (Btuh) 18,000 24,000 30,000 36,000 48,000 60,000 UNIT OPERATING WEIGHT (lb) 130 136 161 185 222 249 COMPRESSOR Hermetic
Typ e Copeland
Model ZR18KC-PFV ZR24KC-PFV ZR28KC-PFV ZR34KC-PFV ZR47KC-PFV ZR57KC-PFV
Scroll
Copeland
Scroll
Copeland
Scroll
Copeland
Scroll
Copeland
Scroll
Copeland
Scroll
Oil (oz) Initial/Recharge 25/21 25/21 38/34 42/38 42/38 56/52
OUTDOOR FAN Propeller Type, Direct Drive, Horizontal
Rpm 850 850 850 850 850 850 Diameter (in.)...No. of Blades 18...3 18...3 18...3 18...3 24...3 24...3 Fan Pitch (Deg) 25 27 27 31 24 24 Motor Hp Nominal Airflow (Cfm) 1720 1720 1720 1720 3900 3900
OUTDOOR COIL Copper Tube, Aluminum Plate Fin
Face Area (sq ft)...No. of Rows 6.1...1 6.1...1.5 6.1...2 6.1...2 12.3...1.5 12.3...1.75
1
/
8
1
/
8
1
/
8
1
/
8
1
/
4
1
Fins per in. 20 20 20 20 20 20
CONTROLS PRESSURESTAT SETTINGS
Low Pressure
Cutout (psig) 7 ± 3 Cut-In (psig) 22 ± 5
Fusible Plug 210 F
NOTE: Line sizes are for runs up to 25 feet.
Table 1B — Physical Data (SI)
UNIT 538J 018 024 030 036 048 060 NOMINAL CAPACITY (kW) 5.3 7.0 8.8 10.5 14.1 17.6 UNIT OPERATING WEIGHT (kg) 58.9 61.6 73.0 83.9 100.6 112.9 COMPRESSOR Hermetic
Typ e Copeland
Scroll
Model ZR18KC-PFV ZR24KC-PFV ZR28KC-PFV ZR34KC-PFV ZR47KC-PFV ZR57KC-PFV Oil (L) Initial/Recharge .74/.62 .74/.62 1.13/1.00 1.25/1.13 1.25/1.13 1.66/1.54
OUTDOOR FAN Propeller Type, Direct Drive, Horizontal
R/s 14.2 14.2 14.2 14.2 14.2 14.2 Diameter (mm)...No. of Blades 457...3 457...3 457...3 457...3 610...3 610...3 Fan Pitch (Deg) 25 27 27 31 24 24 Motor kW .13 .09 .09 .09 .19 .19 Nominal Airflow (L/s) 812 812 812 812 1840 1840
OUTDOOR COIL Copper Tube, Aluminum Plate Fin
Face Area (m
2
)...No. of Rows .57...1 .57...1.5 .57...2 .57...2 1.14...1.5 1.14...1.75
Fins per mm .8 .8 .8 .8 .8 .8
CONTROLS PRESSURESTAT SETTINGS
Low Pressure
Cutout (kPa) 48 ± 21 Cut-In (kPa) 152 ± 34
Fusible Plug 99 C
NOTE: Line sizes are for runs up to 7.6 m.
Copeland
Scroll
Copeland
Scroll
Copeland
Scroll
Copeland
Scroll
Copeland
Scroll
/
4
—5—
LEGEND
C—Contactor (12-va) HC Heating Control IFM Indoor-Fan Motor IFR Indoor-Fan Relay TRANS — Transformer
Field Wiring Factory Wiring
*The IFR and IFM are located in indoor unit on heating-cooling applications. If accessory
IFR is required for cooling-only applications, locate (IFR) in fan coil.
NOTES:
1. Refer to unit wiring label for wire colors: BRN to BLU and C to Y connections.
2. Arrangement A, B and C are for use with residential fan coils.
Fig. 5 — Typical Control Circuit Connections
NEC National Electrical Code
TB Terminal Board
Fig. 6 — Line Power Connections
LEGEND
(U.S.A. Standard)
Transformer
Field Wiring Factory Wiring
—6—
Table 2 — American/European Wire Conversions
SERVICE
AMERICAN EUROPEAN
Industry
Standard Size
18 AWG 0.82 1.0 16 AWG 1.30 1.5 14 AWG 2.08 2.5 12 AWG 3.30 4.0 10 AWG 5.25 6.0
8 AWG 6.36 10.0 6 AWG 13.29 16.0 4 AWG 21.14 25.0 3 AWG 26.65 2 AWG 33.61 35.0
1 AWG 42.39 50.0 1/0 AWG 53.49 2/0 AWG 67.42 70.0 3/0 AWG 85.00 95.0 4/0 AWG 107.19 120.0
250 kcmil 126.64 150.0 300 kcmil 151.97 350 kcmil 177.90 185.0 400 kcmil 202.63 240.0 500 kcmil 253.29 300.0 600 kcmil 303.95
LEGEND
AWG American Wire Gage kcmil — Thousand Circular Mils
American Conversion
(mm)
Industry Standard
Size (mm
2
)
START-UP
I. PRELIMINARY CHECKS
1. Check that all internal wiring connections are tight and that barriers, covers, and panels are in place.
2. Make certain field electrical power source agrees with unit nameplate rating.
3. Open all service valves.
II. LEAK TEST
Field piping and fan coil must be leak tested by the pressure method. Use R-22 at appr oxi mat e ly 25 psi g (1 72 k Pa) backed up with an inert gas to a total pressure not to exceed 245 psig (1690 kPa).
III. EVACUATE AND DEHYDRATE
Field piping and fan coil must be evacuated and dehydrated.
IV. CHARGE SYSTEM
Release factory charge i nto system by opening ( backseati ng) liquid and suction line service valves. Add charge amount as required for the total system. Refer to separate indoor unit installation instructions for the required total system charge when connected to the indoor unit.
V. TO START UNIT
NOTE: When using 538J unit in conjunction with 619 series
fan coils, refer to start-up instructions include d with fan coil for correct start-up procedures.
Be sure that field disconn ect is closed. Set roo m thermostat below ambient temperature. Operate unit for 15 minutes, then check system refrigerant charge. See Refrigerant Charging section on page 8.
Unit compressor starts after a 5-minute delay if equipped with accessory Time Guar d® II device.
WARNING: Before performing recommended main­tenance, be sure unit main power switch is off. F ail ure to do so may result in electrical shock or injury from rotat­ing fan blade.
I. OUTDOOR FAN
A reinforced wire mount holds the outdoor fan assembly in place. See Fig. 7 for proper mounting positions.
UNIT 538J DIMENSIONS — in. (mm)
018 024-036 048-060
0.433 (11) 0.709 (18) 0.16 (4)
Fig. 7 — Condenser Fan Mounting Positions
II. HIGH-PRESSURE RELIEF VALVE
Valve is located in compressor. Relief valve opens at a pressure differential of approximately 450 ± 50 psig (3100 ± 345 kPa) between suction (low side) and discharge (high side) to allow pressure equalization.
III. INTERNAL CURRENT AND TEMPERATURE SENSITIVE OVERLOAD
Control resets automatically when internal compressor motor temperature drops to a safe level (overloads may require up to 45 minutes to reset). When an internal over­load is suspected of being open, check by using an ohmmeter or continuity tester.
IV. PUMPDOWN PROCEDURE
The system may be pumped down in order to make repairs on low side without losing complete refrigerant charge.
To pump down:
1. Attach pressure gage to suction service valve gage port.
2. Fronts ea t the liq uid lin e valve.
CAUTION: The 538J unit coils hold only the factory-designated amount of refrigerant. Additional refrigerant may cause units to relieve pressure through compressor internal pressure relief valve (indicated by sudden rise of suction pressure) before suction pressure reaches 5 psig (34 kPa). If this occurs, shut off unit immediately, then frontseat the suction valve and remove and reclaim excess refrigerant fol­lowing accepted practice.
3. Start unit and run until suction pressure reaches 5 psig (34 kPa).
4. Shut unit off and frontseat suction valve.
5. Depressurize low side of unit and recover refrigerant following accepted practice.
—7—
Table 3 — Electrical Data
OPERATIONAL
538J V-PH-Hz
018 024 030 036 048 060
FLA — HACR — LRA — MCA — NEC — RLA —
*Permissible limits of the voltage range at which unit will operate
satisfactorily.
†Time-delay fuse.
NOTES:
1. Control circuit is 24 v on all units and requires an external power source.
Full Load Amps Heating, Air Conditioning, Refrigeration Locked Rotor Amps Minimum Circuit Amps per NEC Section 430-24 National Electrical Code (U.S.A. Standard) Rated Load Amps (Compressor)
208/230-1-60 187 254
LEGEND
VOLTAGE*
Min Max RLA LRA Fan FLA MCA
COMPRESSOR POWER SUPPLY
10.7 47.0 .70 14.1 25
13.2 59.0 .70 17.2 30
15.7 73.0 .70 20.3 35
15.7 93.0 .70 20.3 35
24.3 131.0 .45 31.8 50
28.6 170.0 .45 37.2 65
V. LOW PRESSURE SWITCH
This switch, mounted on the suction line, has fixed non­adjustable settings. To check pressure switch, attach pres­sure gage to suction service valve gage port. Slowly close liquid shutoff valve and allow compressor to pump down. Do not allow compre ssor to pump down below 2 psi g (14 kPa). Compressor should shut down when suction pressure drops to cutout pressure in Tables 1A and 1B, and should restart when pressure builds up to cut-in pressure shown after accessory CLO (compressor lockout) switch has been reset and accessory Time Guard® II device has completed its tim­ing cycle.
VI. SERVICE VALVES
The service valves in the outdoor unit come from the factory frontseated. This means the refrigerant charge is isolated from the line-set connection po rts. To prevent damage to the valve, use a wet cloth or other acceptable heat sink material on the valve befor e brazing.
The service valves must be backseated (turned counterclock­wise until seated) before the service port caps can be removed and the hoses of the gage manifold connected. In this position, refrigerant has access from the through out­door and indoor unit. The service valve cannot be field repaired; only a complete valve or valve stem seal and service port caps are available for replacement.
VII. ACCURATER® (BYPASS TYPE) DEVICE
See Fig. 4 for bypass type AccuRater device components. The piston has a refrigerant metering hole through it. The retainer forms a stop f or the pi sto n in the ref rige ran t by pass mode and a sealing surface for liquid line flare connection. To check, clean or replace piston:
1. Shut off power to unit.
2. Pump down using Pumpdown Procedure section on page 7.
3. Remove liquid line fl are connection from AccuRater device.
4. Pull retainer out of body, being careful not to scrat ch flare sealing surface. If retainer does not pull out easily, carefully use locking pliers to remove retainer.
5. Slide piston out by inserting a small soft wire, with small kinks, through metering hole. Ensure metering
Max Fuse† or HACR-Type
Ckt Bkr Amps
2. All motors and compressors contain internal overload protection.
3. In compliance with NEC (U.S.A. Standard) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
4. Motor RLA values are established in accordance with UL (Underwriters’ Laboratories) Standard 465 (U.S.A. Standard).
hole, sealing surface around piston cones, and fluted portion of piston are not damaged.
6. Clean piston refrigerant metering hole.
7. Replace retainer O-ring before reassembling Accu­Rater device (O-ring part no. 99CC501052).
VIII. REFRIGERANT CHARGING
WARNING: To prevent personal injury, wear
safety glasses and gloves when handling refrigerant. Do not overcharge system — this can cause com pressor flooding.
NOTE: Do not vent or depressuri ze uni t ref riger ant to a tmo­sphere. Remove and recover refrigeran t following practice.
A. Superheat Method (Cooling, Non-TXV)
To check and adjust charge during cooling season, use Tables 4A-5B and the following procedure:
1. Operate unit a minimum of 15 minutes before check­ing charge.
2. Measure suction pressure by attaching a gage to suc­tion valve service port.
3. Measure suction line temperature by attaching a ser­vice thermometer to unit suction line near suction valve. Insulate thermomete r for accurate readings.
4. Measure outdoor coil inlet-air dry bulb temperature with a second thermometer.
5. Measure indoor coil inlet-air wet bulb temperature with a sling psychrometer.
6. Refer to Tables 4A and 4B. Find air temperature enter­ing outdoor coil and wet-bulb temperature entering indoor coil. At this intersection, note the superheat temperature.
7. Refer to Tables 5A and 5B. Find superheat tempera­ture and suction pressure and note suction line temperature.
8. If unit has higher suction line temperature than charted temperature, add refrigerant until charted temperature is reached.
9. If unit has lower suction line temperature than charted temperature, remove and recover re frigerant until charted temperature is reached.
—8—
10. If air temperature entering outdoor coi l or pressure at suction valve changes, charge to ne w suction line temperature indicated on chart.
NOTE: The above procedure is independent of indoor air quantity.
B. Subcooling Method (Cooling, TXV)
To check and adjust charge during cooling season, use Tables 6A and 6B and the following procedure:
1. Operate unit a minimum of 15 minutes before check­ing charge.
2. Measure liquid line temperature near liquid line ser­vice valve, and measure liquid pressure at liquid line service valve. Use a digital thermo meter for all tem­perature measurements. DO NOT use mercury or dial-type th ermometers.
3. Refer to Tables 6A and 6B. Find temperature point at which the required subcooling temper at ur e inte rsects the measured liquid line pressure.
4. If the measured liquid line temperature does not agree with the required liquid line temperature, ADD refrigerant to lower the temperature, or REMOVE refrigerant to raise the temperature (allow a toler­ance of ± 3 F).
Table 4A — Superheat Charging Table — English
(Superheat Entering Suction Service Valve)
OUTDOOR
TEMP (F)
55 60 65 70 75 80 85 90
95 100 105 110 115
LEGEND
Wet Bulb
WB —
*Do not attempt to charge system under these conditions or refrigerant slug-
ging may occur.
50 52 54 56 58 60 62 64 66 68 70 72 74 76
INDOOR COIL ENTERING AIR (F) WB
9 12141720232629323537404245 7 10121518212427303335384043 * 6 10 13 16 19 21 24 27 30 33 36 38 41 * * 71013161921242730333639 * * * 6 9 12 15 18 21 24 28 31 34 37 **** 581215182125283135 ****** 811151922263033 ****** 59131620242731 ******* 6101418222529 ******** 81215202327 ******** 5913172226 ********* 611152025 ********** 8141823
Table 4B — Superheat Charging Table — SI (Superheat Entering Suction Service Valve)
OUTDOOR
TEMP (C)
13 16 18 21 24 27 29 32 35 38 41 43 46
LEGEND
Wet Bulb
WB —
*Do not attempt to charge system under these conditions or refrigerant slug-
ging may occur.
10 11 12 13 14 16 17 18 19 20 21 22 23 24
INDOOR COIL ENTERING AIR (C) WB
578911131416181921222325 467810121315171819212224 * 3 6 7 9111213151718202123 * * 4 6 7 9 11 12 13 15 17 18 20 22 * * * 3 5 7 8 10 12 13 16 17 19 21 **** 3478101214161719 ****** 4681112141718 ****** 357911131517 ******* 36810121416 ******** 478111315 ******** 35791214 ********* 3681114 ********** 481013
Table 5A — Required Suction-Tube Temperature (F)
— English (Entering Suction Service Valve)
SUPERHEAT
TEMP (F)
0 2 4 6
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
SUCTION PRESSURE AT SERVICE PORT (psig)
61.5 64.2 67.1 70.0 73.0 76.0 79.2 82.4 85.7
35 36 39 41 43 45 47 49 51 37 39 41 43 45 47 49 51 53 39 41 43 45 47 49 51 53 55 41 43 45 47 49 51 53 55 57 43 45 47 49 51 53 55 57 59 45 47 49 51 53 55 57 59 61 47 49 51 53 55 57 59 61 63 49 51 53 55 57 59 61 63 65 51 53 55 57 59 61 63 65 67 53 55 57 59 61 63 65 67 69 55 57 59 61 63 65 67 69 71 57 59 61 63 65 67 69 71 73 59 61 63 65 67 69 71 73 75 61 63 65 67 69 71 73 75 77 63 65 67 69 71 73 75 77 79 65 67 69 71 73 75 77 79 81 67 69 71 73 75 77 79 81 83 69 71 73 75 77 79 81 83 85 71 73 75 77 79 81 83 85 87 73 75 77 79 81 83 85 87 89 75 77 79 81 83 85 87 89 91
Table 5B — Required Suction-Tube Temperature (C)
— SI (Entering Suction Service Valve)
SUPERHEAT
TEMP (C)
0 1 2 3 4 6 7 8
9 10 11 12 13 14 16 17 18 19 20 21 22
SUCTION PRESSURE AT SERVICE PORT (kPa)
424 443 463 483 503 524 546 568 591
2345678911 34567891112 456789111213 5678911121314 67891112131415 7 8 9 11 12 13 14 15 16 8 9 11 12 13 14 15 16 17
91112131415161718 11 12 13 14 15 16 17 18 19 12 13 14 15 16 17 18 19 21 13 14 15 16 17 18 19 21 22 14 15 16 17 18 19 21 22 23 15 16 17 18 19 21 22 23 24 16 17 18 19 21 22 23 24 25 17 18 19 21 22 23 24 25 26 18 19 21 22 23 24 25 26 27 19 21 22 23 24 26 26 27 28 21 22 23 24 25 26 27 28 29 22 23 24 25 26 27 28 29 31 23 24 25 26 27 28 29 31 32 24 25 26 27 28 29 31 32 33
—9—
MAINTENANCE
Clean coil annually or as required by location and outdoor air conditions. Inspect coil monthly and clean as required.
WARNING: Before performing recommended main­tenance, be sure unit main power is off. Failure to do so may result in electrica l shock or injury from rot ating fan blades.
I. LUBRICATION
The outdoor fan motor is factory lubricated and requires no oil.
II. COMPRESSOR
Fins are NOT continuous through coil sections. Dirt and debris may pass through the first section, become trapped between the rows of fins, and restrict co ndenser ai rflow. Use a flashlight to determine if dirt or debris has collected between coil sections. Clean coil as follows:
1. Turn off unit power.
2. Use a garden hose or other suitable equipment to flush coil from the outside to remove dirt. Be sure to flush all dirt and debris from drain holes in the base of unit. Fan motors are waterproof.
The compress or con tains fac tory oil c har ges ; rep lac e oil w hen lost. See Tables 1A and 1B for oil recharge. Recommended oil is Sontex 200LT for all units.
III. CLEANING COILS
Coil should be washed out with water or blown out with com­pressed air. Note that the blow-thru design causes dirt and debris to build up on the inside of the coils.
Table 6A — Required Liquid Line Temperature (F) — English (At Service Valve)
REQUIRED
SUBCOOLING
(F)
0 76 79 82 85 88 91 94 97 100 103 106 109 112 115 118 121 124 127 130 133 136 139 142 145
5 71 74 77 80 83 86 89 92 95 98 101 104 107 110 113 116 119 122 125 128 131 134 137 140 10 66 69 72 75 78 81 84 87 90 93 96 99 102 105 108 111 117 120 123 126 129 129 132 135 15 61 64 67 70 73 76 79 82 85 88 91 94 97 100 103 106 109 112 115 118 121 124 127 130 20 56 59 62 65 68 71 74 77 80 83 86 89 92 95 98 101 104 107 110 113 116 119 122 125 25 51 54 57 60 63 66 69 72 75 78 81 84 87 90 93 96 99 102 105 108 111 114 117 120
134 141 148 156 163 171 179 187 196 205 214 223 233 243 253 264 274 285 297 309 321 331 346 359
LIQUID PRESSURE AT SERVICE VALVE (PSIG)
Table 6B — Required Liquid Line Temperature (C) — SI (At Service Valve)
REQUIRED
SUBCOOLING
(C)
0 24 26 28 29 31 33 34 36 38 39 41 43 44 46 48 49 51 53 54 56 58 59 61 63 2 22 24 26 27 29 31 32 34 36 37 39 41 42 44 46 47 49 51 52 54 56 57 59 61 4 20 22 24 25 27 29 30 32 34 35 37 39 40 42 44 45 47 49 50 52 54 55 57 59 6 18 20 22 23 25 27 28 30 32 33 35 37 38 40 42 43 45 47 48 50 52 53 55 57 8 16 18 20 21 23 25 26 28 30 31 33 35 36 38 40 41 43 45 46 48 50 51 53 55
10 14 16 18 19 21 23 24 26 28 29 31 33 34 36 38 39 41 43 44 46 48 49 51 53 12 12 14 16 17 19 21 22 24 26 27 29 31 32 34 36 37 39 41 42 44 46 47 49 51 14 10 12 14 15 17 19 20 22 24 25 27 29 30 32 34 35 37 39 40 42 44 45 47 49
911 969 1030 1061 1121 1186 1219 1286 1360 1397 1471 1547 1588 1671 1755 1800 1885 1976 2026 2125 2222 2264 2379 2475
LIQUID PRESSURE AT SERVICE VALVE (PSIG)
—10—
TROUBLESHOOTING
TROUBLESHOOTING CHART — COOLING CYCLE
—11—
Copyright 2002 Bryant Heating & Cooling Systems Printed in Mexico CATALOG NO. 5353-802
Loading...