Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical
shock or other conditions which may cause personal
injury or property damage. Consult a qualified installer,
service agency, or your distributor or branch for
information or assistance. The qualified installer or
agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual
instructions package
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloths for brazing operations and
have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and appropriate
nationalelectricalcodes (in USA, ANSI/NFPA70,
National Electrical Code (NEC); in Canada, CSA C22.1)
for special requirements.
It is important to recognize safety information. This is the
safety--alert symbol
unit and in instructions or manuals, be alert to the
potential for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety--alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or
death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify
unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
. When you see this symbol on the
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause in personal
injury or death.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lockout tag. Unit may have more than one
power switch.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause in personal
injury,death and/or equipment damage.
R
524J
Puron
higher pressures than standard R--22 systems. Do not
use R--22 service equipment or components on Puron
refrigerant equipment.
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause in personal
injury or death.
Relieve pressure and recover all refrigerant before
system repair or final unit disposal.
Wear safety glasses and gloves when handling
refrigerants. Keep torches and other ignition sources
away from refrigerants and oils.
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts and servicing
524J units.
(R--410A) refrigerant systems operate at
!
WARNING
!
CAUTION
PRE--INSTALLATION
1. The power supply (v, ph, and Hz) must correspond to
that specified on unit rating plate.
2. The electrical supply provided by the utility must be
sufficient to handle load imposed by this unit.
3. Refer to Installation, General section (page 2) and
Fig. 1 and Fig. 2 for locations of electrical inlets, condensate drain, duct connections, and required clearances before setting unit in place.
4. This installation must conform with local building
codes and with the NEC (National Electrical Code) or
ANSI (American National Standards Institute)/NFPA
(National Fire Protection Association) latest revision.
Refer to provincial and local plumbing or wastewater
codes and other applicable local codes.
Moving and Storage -- To transfer unit from truck to
storage site, use a fork truck. Do not stack units more than
2 high during storage. If unit is to be stored for more than
2 weeks before installation, choose a level, dry storage
site free from vibration. Do not remove plastic wrap or
skid from unit until final installation.
Rigging -- All 524J Series units can be rigged by using the
shipping skid. Units are shipped fully assembled. Do not
remove shipping skids or protective covering until unit is
ready for final placement; damage to bottom panels can
result. Use slings and spreader bars as applicable to lift
unit.
INSTALLATION
General -- Allow the following clearances for service
access and airflow:
1
S Rear: 3 ft (914 mm) [2
accessory]
1
S Front: 2
S Right Side: 3
S Left Side: 2
For units equipped with an economizer, refer to the
accessory installation instructions for additional clearance
requirements. Be sure floor, wall, or ceiling can support
unit weight (Tables 1A – 1D). See Fig. 1 and Fig. 2 for
dimensions.
Uncrating -- Move unit as near as possible to final
location before removing shipping skid.
/2ft (762 mm)
1
/2ft (1067 mm)
1
/2ft (762 mm)
/2ft (762 mm) with electric heat
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment
damage.
Ensure voltage listed on unit data plate agrees with
electrical supply provided for the unit.
Remove metal banding, top skid, and plastic wrap.
Examine unit for shipping damage. If shipping damage is
evident, file claim with transportation agency. Remove
base skid just prior to actual installation.
Check nameplate information against available power
supply and model number description in Fig. 3.
NOTE: Be sure to remove the styrofoam shipping pad
from the thermostatic expansion valve (TXV). Verify that
it has been removed. See Fig. 5.
Accessories -- Refer to instructions shipped with each
accessory for specific information.
2
Table 1A — 524J***A Physical Data, English — Cooling Units
UNIT 524J*25A28A30A
NOMINAL CAPACITY (Tons)202530
OPERATING WEIGHT (lb)
Base Unit with TXV73010501062
Plenum225325325
FANS
Qty...Diam. (in.)2...152...182...18
Nominal Airflow (cfm)80001000012000
Airflow Range (cfm)6000 – 100007500 – 125009000 – 15000
Nominal Motor Hp (Standard Motor)
208/230--- 3 ---60 and 460 --- 3---605.07.510.0
5 7 5 --- 3 --- 6 05.07.510.0
Motor Speed (rpm)
208/230--- 3 ---60 and 460 --- 3---60174517451745
5 7 5 --- 3 --- 6 0174517551755
REFRIGERANTR--- 410A
Operating charge (lb)
(approx per circuit)*
DIRECT--- EXPANSION COILEnhanced Copper Tubes, Aluminum Sine---Wave Fins
Max Working Pressure (psig)650
Face Area (sq ft)19.8824.8629.83
No. of Splits222
No. of Circuits per Split182024
Split Type...PercentageFace...50/50
Rows...Fins/in.4...154...154...15
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF)2...11/
DX Coil — Liquid Refrigerant (ODF)2...5/
Steam Coil, In (MPT)1...21/
Steam Coil, Out (MPT)1...1/
Hot Water Coil, In (MPT)1...2
Hot Water Coil, Out (MPT)1...2
Condensate (PVC)1...11/4ODM/1 IDF
FILTERSThrowaway — Factory Supplied
Quantity...Size (in.)
Access LocationEither Side
STEAM COIL**
Max Working Pressure (psig at 260° F)20
Tota l F a ce Ar e a ( s q ft)13.3315.015.0
Rows...Fins/in.1...101...101...10
HOT WATER COIL**
Max Working Pressure (psig)150
Tota l F a ce Ar e a ( s q ft)13.3315.015.0
Rows...Fins/in.2...8.52...12.52...12.5
Water Volume
(gal)13.914.3
(ft3)1.90
LEGEND
DX — Direct Expansion
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.
**Field installed accessory only.
3.5
8
4...16 x 20 x 2
4...16 x 24 x 2
4.55.0
2...13/
8
8
2
2
4...20 x 24 x 2
4...20 x 25 x 2
2...13/
8
524J
3
524J
Table 1B —524J***A Physical Data, SI — Cooling Units
UNIT 524J*25A28A30A
NOMINAL CAPACITY (kW)7087105
OPERATING WEIGHT (kg)
Base Unit with TXV331477482
Plenum102148148
FANS
Qty...Diam. (mm)2...3812...4572...457
Nominal Airflow (L/s)377541195663
Airflow Range (L/s)2831 – 47193539 – 58994247 – 7079
Nominal Motor kW (St andard Motor)
208/230--- 3 ---60 and 460 --- 3---603.735.607.46
5 7 5 --- 3 --- 6 03.735.607.46
Motor Speed (r/s)
208/230--- 3 ---60 and 460 --- 3---6029.129.129.1
5 7 5 --- 3 --- 6 029.129.329.3
REFRIGERANTR--- 410A
Operating charge (kg)
(approx per circuit)*
DIRECT--- EXPANSION COILEnhanced Copper Tubes, Aluminum Sine---Wave Fins
Max Working Pressure (kPag)4481
Face Area (sq m)1.852.302.77
No. of Splits222
No. of Circuits per Split182024
Split Type...PercentageFace...50/50
Rows...Fins/m4...5914...5914...591
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF)2...11/
DX Coil — Liquid Refrigerant (ODF)2...5/
Steam Coil, In (MPT)1...21/
Steam Coil, Out (MPT)1...1/
Hot Water Coil, In (MPT)1...2
Hot Water Coil, Out (MPT)1...2
Condensate (PVC)1...11/4ODM/1 IDF
FILTERSThrowaway — Factory Supplied
Quantity...Size (mm.)
Access LocationEither Side
STEAM COIL**
Max Working Pressure (kPag at 126°C)138
Tota l F a ce Ar e a ( s q m)1.241.391.39
Rows...Fins/m1...3941...3941...394
HOT WATER COIL**
Max Working Pressure (kPag)1034
Tota l F a ce Ar e a ( s q m)1.241.391.39
Rows...Fins/m2...3352...3352...335
Water Volume
(L)52.654.1
(m3)0.0520.054
LEGEND
DX — Direct Expansion
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.
**Field installed accessory only.
1.59
8
4...406 x 508 x 51
4...406 x 610 x 51
2.042.27
2...13/
8
8
2
2
2...13/
4...508 x 610 x 51
4...508 x 635 x 51
8
4
Table 1C — 524J*25H Physical Data, English — Heat Pump Units
UNIT 524J*25H
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
Base Unit with TXV720
Plenum140
FANS
Qty...Diam. (in.)2...15
Nominal Airflow (cfm)8000
Airflow Range (cfm)6000 --- 10000
Nominal Motor Hp (Standard Motor)
208/230--- 3 ---60 and 460 --- 3---605.0
5 7 5 --- 3 --- 6 05.0
Motor Speed (rpm)
208/230--- 3 ---60 and 460 --- 3---601745
5 7 5 --- 3 --- 6 01745
REFRIGERANT
Operating charge (lb)
(approx per circuit)*
DIRECT--- EXPANSION COIL
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
Max Working Pressure (psig)650
Face Area (sq ft)19.9
No. of Splits2
No. of Circuits per Split2
Split Type...PercentageFace....50/50
Rows...Fins/in.4...15
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF)2...1
DX Coil — Liquid Refrigerant (ODF)2...
Steam Coil, In (MPT)1...2
Steam Coil, Out (MPT)1...1
Hot Water Coil, In (MPT)1...2
Hot Water Coil, Out (MPT)1...2
Condensate (PVC)1...1
FILTERS
Throwaway — Factory Supplied
Quantity...Size (in.)4...16 x 20 x 2
Access LocationRightorLeftSide
STEAM COIL**
Max Working Pressure (psig at 260° F)20
Tota l F a ce Ar e a ( s q ft)13.33
Rows...Fins/in.1...10
HOT WATER COIL**
Max Working Pressure (psig)150
Tota l F a ce Ar e a ( s q ft)13.33
Rows...Fins/in.2...8.5
Water Volume
(gal)13.9
(ft3)1.85
LEGEND
DX — Direct Expansion
TXV — Thermostatic Expansion Valve
*
Units are shipped without refrigerant charge.
**Field installed accessory only.
20
R--- 410A
3.5/3.5
1/
8
5/
8
1/
2
1/
2
1/
ODM/1 IDF
4
4...16 x 24 x 2
524J
5
524J
Table 1D — 524J*25H Physical Data, SI — Heat Pump Units
UNIT 524J*25H
NOMINAL CAPACITY (kW)
OPERATING WEIGHT (kg)
Base Unit with TXV326
Plenum44
FANS
Qty...Diam. (mm)2...381
Nominal Airflow (L/s)3775
Airflow Range (L/s)2831--- 4719
Nominal Motor kW (St andard Motor)
208/230--- 3 ---60 and 460 --- 3---603.73
5 7 5 --- 3 --- 6 03.73
Motor Speed (r/s)
208/230--- 3 ---60 and 460 --- 3---6029.1
5 7 5 --- 3 --- 6 029.1
REFRIGERANT
Operating charge (kg)
(approx per circuit)*
DIRECT--- EXPANSION COIL
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
Max Working Pressure (kPag)4482
Face Area (sq m)1.85
No. of Splits2
No. of Circuits per Split2
Split Type...PercentageFace...50/50
Fins/m591
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF)2...1
DX Coil — Liquid Refrigerant (ODF)2...
Steam Coil, In (MPT)1...2
Steam Coil, Out (MPT)1...1
Hot Water Coil, In (MPT)1...2
Hot Water Coil, Out (MPT)1...2
Condensate (PVC)1...1
FILTERS
Throwaway — Factory Supplied
Quantity...Size (mm)
Access LocationRightorLeftSide
STEAM COIL**
Max Working Pressure (kPag at 126°C)138
Tota l F a ce Ar e a ( s q m)1.24
Rows...Fins/m1...394
HOT WATER COIL**
Max Working Pressure (kPag)1034
Tota l F a ce Ar e a ( s q m)1.24
Rows...Fins/m2...335
Water Volume
(L)52.6
(m3)0.052
LEGEND
DX — Direct Expansion
TXV — Thermostatic Expansion Valve
*
Units are shipped without refrigerant charge.
**Field installed accessory only.
70
R--- 410A
1.59/1.59
1/
8
5/
8
1/
2
1/
2
1/
ODM/1 IDF
4
4...406 x 610 x 51
4...406 x 508 x 51
6
LEGEND
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. [914 mm] (2 ft, 6 in. [762 mm]
with electric heat accessory)
• Front: 2 ft, 6 in. [762 mm]
• Right Side: 2 ft, 6 in. [762 mm]
• Left Side: 2 ft, 6 in. [762 mm]
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
524J
Fig. 1 -- Dimensions – Size 25
7
UNIT
524J*25A730 (331)
524J*25H720 (326)
UNIT WEIGHT
lb (kg)
C10834
524J
LEGEND
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. [914 mm] (2 ft, 6 in. [762 mm]
with electric heat accessory)
• Front: 2 ft, 6 in. [762 mm]
• Right Side: 2 ft, 6 in. [762 mm]
• Left Side: 2 ft, 6 in. [762 mm]
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
6. 40RUS may require alternate or additional
field favricated poping access holes
Fig. 2 -- Dimensions – Sizes 28 and 30
8
UNIT
524J*28A
524J*30A
lb (kg)
1050 (477)
1062 (482)
C10835
Model Type
524J = Bryant Fan Coil
Puronr R--- 410A Refrigerant
Voltage
E = 460/3/60
P = 208 / 230/3/60
T = 575/3/60
123456789 10 11 12 13 14 15 16 17
5 2 4 J E 2 5 A 0 0 0 A 2 0 A A A
_____________
____
Not Used
A = Not Used
Service Options
A=None
B = Painted Cabinet
Packa ging
A=Standard
Nominal Tonnage
25 = 20 Tons
28 = 25 Tons
30 = 30 Tons
Typ e o f C oi l
A = Standard DX Coil
B = High Capacity DX Coil
H = DX Coil for Heat Pump Duty
Not Used
0=Not Used
Not Used
0=Not Used
POSITION NUMBER
TYPICAL
Not Used
0 = Not Used
Indoor Fan Options
1 = Fan Drive and Motor - Low / Motor Efficency - Standard
2 = Fan Drive and Motor - Med / Motor Efficency - Standard
3 = Fan Drive and Motor - High / Motor Efficency - Standard
Coil Options
A=Al/Cu
Not Used
0 = Not Used
C10837
Fig. 3 -- Model Number Nomenclature
12345678910
2610G12345
SETANGISEDNOITISOP
)radnelac lacsif( erutcafunam fo keeW1−2
Year of manufacture (“10” = 2010)3−4
)ASU ,saxeT ,PTE = G( noitacol gnirutcafunaM5
rebmun laitneuqeS6−10
C!0725
Fig. 4 -- Serial Number Nomenclature
524J
TXVCOIL
REMOVE FOAM BLOCK
LEGEND
TXV — Thermostatic Expansion Valve
C10683
Fig. 5 -- Foam Block Location
Unit Positioning -- The unit can be mounted on the floor
for vertical application with return air entering the face of
the unit and supply air discharging vertically through the
top of the unit. The unit can also be applied in a
horizontalarrangementwithreturnairentering
horizontally and the supply air discharging horizontally.
When applying the unit in a horizontal arrangement,
ensure the condensate drain pan is located at the bottom
center of the unit for adequate condensate disposal. See
Fig. 6 for condensate connections for each unit position.
PLUG
PLUG
Note: Maintain recommended clearances
CONDENSATE
DRAIN
LEGEND
Accessory Line
Alternate Air Intake and Discharge
Air Intake and Discharge
per Fig. 1 and Fig. 2
C10684
Fig. 6 -- Typical Unit Positioning
9
Typical positioning and alternate return air locations are
shown in Fig. 6. Alternate return air locations can be used
by moving the unit panel from the alternate return air
location to the standard return air location. Refer to
overhead suspension accessory drawing (Fig. 7) for
OVERHEAD SUSPENSION ACCESSORY — UNIT SIZE 25
524J
preferred suspension technique. The unit needs support
underneath to prevent sagging.
IMPORTANT: Do NOT attempt to install unit with return
air entering top panel of unit. Condensate will not drain from
unit.
OVERHEAD SUSPENSION ACCESSORY — UNIT SIZES 28, 30
NOTE: Dimensions in [ ] are millimeters
Fig. 7 -- Preferred Suspension Technique
C10728
10
Unit Isolation -- Where extremely quiet operation is
essential, install isolators between floor and base of unit,
or between ceiling and top section of unit.
Be sure that unit is level and adequately supported. Use
channels at front and sides of unit for reference points
when leveling.
Refrigerant Piping Access -- The 524J Series units come
with standard knockouts for refrigerant piping. These
knockouts are located on both sides of the unit for
installation flexibility. The standard knockouts provide
sufficient access to the unit’s coils for all 524J*25A, 28A
and 30A units. The 524J*25H requires additional holes
which must be field--fabricated to accommodate the
piping. See Fig. 8 for positions and dimensions for the
additional access holes required. Recommended access
hole use is also listed for all units. Note that Fig. 8 shows
the access holes on the control--box side of the unit; this is
the side of the unit with the coil headers, so it is used most
often for piping access.
IMPORTANT:Donotburyrefrigerantpiping
underground.
Refrigerant Piping -- See Tables 1A–1D for refrigerant
pipe connection sizes. For ease in brazing, it is
recommended that all internal solder joints be made
before unit is placed in final position.
The524Jdirect--expansionunitshaveinternal
factory--installed thermostatic expansion valves (TXVs),
distributors, and nozzles for use with R--410A. See Table 2
for part numbers. Knockouts are provided in the unit corner
posts for 524J refrigerant piping. See Fig. 8, which also lists
recommended knockouts and access holes to use for each
524J unit size. Recommended fittings are listed in Table 3.
The sensor bulb capillary tubes must be routed from the
TXVs inside the unit through one of the piping access
holes. Clamp the TXV sensor bulb on a vertical portion of
the suction line, outside the unit. See Fig. 9.
NOTE: Be sure to remove the styrofoam shipping pad
from the TXV. Verify that it has been removed. See Fig. 5.
IMPORTANT: Never attach the sensor to the suction
manifold. Do NOT mount the sensor on a trapped portion
of the suction line.
The 524J Series evaporator coils have a face--split design.
Ensure that lower circuit of coil is first on/last off when
connected to the condensing unit and/or system controls.
See Fig. 10.
External TXV equalizer connections are provided and
factory--brazed into the coil suction manifolds.
If suction line must be horizontal, clamp bulb to suction
line at least 45 degrees above bottom, at approximately
the 4 o’clock or 8 o’clock position. See Fig.11.
Condensate Drain -- Install a trapped condensate drain line
524J
to unit connection as shown in Fig. 12. The unit drain
connection is a PVC stub. See Fig. 13. Some areas may
require an adapter to connect to either galvanized steel or
copper pipe. For these applications, install a field--supplied
threaded PVC adapter.
3” MIN.
[76]
Install clean--out plugs in trap. Pitch drain line downward
to an open floor drain or sump. Provide service clearance
around drain line to permit removal of unit panels.
Observe all local sanitary codes.
C10692
Fig. 13 -- Drain Pan Slope Adjustment
NOTE: Dimensions in [ ] are in millimeters
Fig. 12 -- Condensate Drains
NOTE:A trap must be installed in the condensate drain
line to ensure that the static pressure of fans is balanced with
the water column in the drain line and that condensate can
drain completely from pan. Without a trap, air can be drawn
up drain line until water level in condensate pan becomes
equal to static pressure created by fans, preventing complete
drainage. Conditions will worsen as filters become dirty.
C10691
As shipped, the unit’s condensate drain pan is NOT sloped
towards the drain connection. The pan slope must be
changed to pitch towards the side of the unit with the
drain connection. See Fig. 13. Loosen the 2 screws next to
the drain outlet at both ends of the unit, push drain pan
down in the slots near the drain connection, and up in the
slots on the opposite end. Re--tighten screws. The pan
1
should have a pitch of at least
/4--in. over its length
toward the drain connection.
14
Fan Motors and Drives -- Motor and drive packages are
A
factory installed in all units. The motor and drive
packages consist of the following items:
1 — fan motor
Install disconnect switch and power wiring in accordance
with all applicable local codes. See Fig. 14--16 and the
1
unit label diagram. Connect power wiring with
/4-- i n .
ring terminal.
1 — adjustable motor pulley
1—fanpulley
2 — matched fan belts (524J*25A--30A units)
For instructions on changing fan rotation, changing drive
speeds and adjusting drives, see Pulley and Drive
Adjustment in the Service section.
Power Supply and Wiring -- Check the unit data plate to
ensure that available power supply matches electrical
characteristics of the unit. Provide a disconnect switch
with an integrated lock--out feature of size required to
provide adequate fan motor starting current. See Tables
4--6 for unit electrical data.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Do not use gas piping as an electrical ground. Unit
cabinet must have an uninterrupted, unbroken electrical
ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist
of electrical wire connected to unit ground lug in control
compartment, or conduit approved for electrical ground
when installed in accordance with NEC (National
Electrical Code); ANSI/NFPA 70, latest edition (in
Canada, Canadian Electrical Code CSA [Canadian
Standards Association] C22.1), and local electrical
codes.
FAN SCROLL
MOTOR
ND DRIVE
CONDENSATE
DRAIN
CONNECTION
(HORIZONTAL)
FILTER
ELEMENTS
FILTER
RETAINER
CLIP
TXV — Thermostatic Expansion Valve
LEGEND
FAN
CONTACTOR
BOX
WIRE
ACCESS
FAN DRIVE
PULLEY
COIL
TXV BULB
ACCESS
REFRIGERANT
PIPING ACCESS
CONDENSATE
DRAIN
CONNNECTION
(VERTICAL)
C10693
Fig. 15 -- Wiring and Service Access
(Side Panel Removed)
Fan motors are factory--installed on all units. Indoor--fan
contactors are located in the fan contactor box behind the
side access panel (see Fig. 15 and 16). Wire the thermostat
to the 24--v control circuit terminal block located in the
side of the fan contactor control box, according to Fig. 17
or the unit label diagram. If the air handler is part of a
split system, complete the wiring from the condensing
unit to the thermostat shown in Fig. 17.
524J
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in intermittent
operation or performance satisfaction.
Do not connect aluminum wire between disconnect
switch and fan coil unit. Use only copper wire.
(See Fig. 14)
F L A--- F u l l L o a d A m p s
MOCP --- Maximum Overcurrent Protection
{ Motors are designed for satisfactory operation within 10% of
normal voltage shown. Voltages should not exceed the limits
shown in the Voltage Limits column.
NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calculated in accordance with The NEC. Article 440.
2. Motor FLA values are established in accordance with Underwriters’ Laboratories (UL). Standard 1995.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the formula in the example
(see column to the right) to determine the percentage of voltage imbalance.
4. Installation with Accessory Electric Heaters
Size the Field Power Wiring between the heater TB1 and the
524J indoor fan motor per NEC Article 430 ---28 (1) or (2)
(depends on length of conduit between heater enclosure and
524J power entry location). Install wires in field ---installed
conduit.
Example: Supply voltage is 230-3-60
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
average voltage
AB = 393 v
BC = 403 v
AC = 396 v
Average Voltage =
(393 + 403 + 396)
3
=397
1192
=
3
Determine maximum deviation from average voltage.
(AB) 397 – 393 = 4 v
(BC) 403 – 397 = 6 v
(AC) 397 – 396 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance= 100 x
=1.5%
6
397
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
16
Fig. 17 -- Unit Wiring
524J
C10695
Table 6 – Fan Contactor Coil Data
UNIT
524J*
25A, 25H, 28A, 30A2410
VOLTAGE
(vac)
MAXIMUM
HOLDING VA
Connecting Ductwork -- Refer to the System Design
Manual for the recommended design and layout of
ductwork. Fig. 18 shows recommended duct connection to
units with 2 fans.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment
damage.
Do not operate unit without ductwork or discharge
plenum unless fan speed has been adjusted for
external static pressure of zero in. wg. Failure to do so
may result in motor overload.
DISCHARGE CONNECTIONS — Duct flanges are
factory--supplied; they are shipped inside the unit attached
to the hairpin end of the coil tube sheet for field
installation. Using the existing screws, install the duct
flanges on the unit’s fan deck. Each fan discharge requires
2 flanges; each flange must be bent in the middle to
conform to the discharge opening. See Fig. 19. After
flanges are installed, connect them to the supply duct
using a canvas connection to prevent vibration. It is
important that this connection be properly fabricated to
prevent high air friction losses and air noise.
RETURN CONNECTIONS — When using return--air
ductwork, route return--air duct to the unit’s return air inlet
near the filter rack, using a canvas connection to prevent
transmission of unit vibration. If the duct blocks off the
unit’s access panel, provide a slip joint in the ductwork to
permit removal for servicing.
OUTDOOR--AIR INLET CONNECTIONS — Connect
outdoor--air inlet to field--installed accessory economizer.
Refer to Economizer Installation Instructions.
Return--Air Filters -- Type and size of filters are shown
in Tables 1A – 1D and are factory--supplied and
factory--installed. In all units with 2 fans, a filter
replacement tool (hook) is shipped inside the unit for field
use when replacing filters. See the Service section for
instructions on filter element replacement.
17
524J
C10696
Fig. 18 -- Typical Fan Discharge Connections for Multiple Fan Units
C10697
Fig. 19 -- Duct Flange Installation
18
START--UP
Before starting unit, check the following and correct as
necessary:
S Is unit solidly supported?
S Is fan adjusted for speed and pulley alignment?
S Are pulleys, motor, and bearings securely mounted?
S Are there any loose parts that will rattle or vibrate?
S Is condensate drain pan pitched for correct drainage?
S Are coil baffle plates tight against coil to prevent air
bypass?
S Are all panels securely fastened?
S Are all electrical connections correct and tight?
S Is TXV bulb located on suction tube per Fig. 20?
S Is the capillary tube to the bulb free of kinks and not
subject to pinching?
S Is the bulb well secured to the suction tube with strap?
2. To increase superheat, turn the stem clockwise. To decrease the superheat, turn the stem counterclockwise.
Do not turn the stem more than one full turn.
3. Wait until suction pressure and superheat stabilize.
This may take more than 30 minutes.
4. Continue adjustment until superheat reaches 10_Fto
15_F (5.5_Cto8.3_C).
5. Replace the seal cap; tighten.
INSTALLER / INSTALLATEUR
TXV superheat must be checked at initial
unit start-up and adjusted if necessary.
Superheat must be 10 - 15 deg F.
La surchauffe TXV doit être vérifiée au
moment de la mise en route initiale et
ajustée si nécessaire. La surchauffe doit
être comprise entre 10 et 15 degrés F.
40RU500073 2.0
C10828
Fig. 21 -- Label, TXV Adjustment
524J
Also refer to condensing unit or outdoor heat pump section
instructions before starting a split system. A split system
start--up checklist is provided at the end of these instructions.
40RU500072 2.0
IMPORTANT! / IMPORTANT
TXV
UPPER SPLIT
BLOC SUPÉRIEUR
AIR FLOW
CIRCULATION
D'AIR
LOWER
SPLIT
BLOC
INFÉRIEUR
AIR FLOW
CIRCULATION
The sensor bulb capillary tubes must be routed from the TXVs inside the unit through one of the piping
access holes. Clamp the TXV sensor bulb on a vertical portion of the suction line, outside the unit.
See Fig. 7 in the installation, start-up and service instruction. Super heat must be adjusted in field.
Les tubes capillaires du capteur doivent être acheminé à partir du détendeur thermostatique situé à l'intérieur
de l'appareil au travers de l'un des trous d'accès de conduites. Attacher le capteur sur une portion verticale
de la conduite de succion, à l'extérieur de l'appareil. Voir la Figure 7 dans le manuel d'installation, de mise
SENSING
BULB
CAPTEUR TXV
10 DIAMS
15 DIAMS MIN
10 x DIA. MIN
15 x DIA. MIN
TXV SENSING
BULB
CAPTEUR TXV
D'AIR
15 DIAMS MIN
en marche, et d'entretien. La surchauffe doit être ajustée sur place.
15 x DIA. MIN
10 DIAMS
10 x DIA. MIN
Fig. 20 -- Label, TXV Bulb Location
EQUALIZER LINE
CONDUITE D'ÉQUILIBRAGE
TXV
8 DIAMS MIN
8 x DIA. MIN
TXV
8 DIAMS MIN
8 x DIA. MIN
SIGHT GLASS
HUBLOT
SOLENOID
VALVE
VANNE
SOLÉNOÏDE
DESSICCATEUR
EQUALIZER LINE
CONDUITE D'ÉQUILIBRAGE
INDOOR COIL
ÉCHANGEUR INTÉRIEUR
FILTER
DRIER
FILTRE
C10827
SERVICE
Inspection and maintenance should be performed at
regular intervals and should include the following:
S Complete cleaning of cabinet, fan wheel, cooling coil,
condensate pan and drain, heating coils, and return--air
grille (if present).
S Inspection of panels and sealing of unit against air
leakage.
S Adjustment of fan motor, belt, bearings, and wheels.
S Cleaning or replacement of filters.
S Testing for cooling/heating system leaks.
S Checking of all electrical connections.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lockout tag. Unit may have more than one
power switch.
Adjusting TXV for Superheat —
The unit--mounted thermostatic expansion valve(s) is/are
factory set to provided superheat at the bulb location in
10_Fto15_F (5.5_Cto8.3_C) range. Actual system load
conditions may require adjustment of the factory setting.
To adjust the TXV superheat setting:
1. Remove the seal cap from the bottom of the TXV
body.
Most unit service can be performed by removing one or
both of the unit’s side panels. Coil cleaning or removal or
insulation cleaning may require removal of a rear, top, or
bottom panel, depending on the unit’s orientation. When
service is completed, replace unit panels.
Panels -- Panels are fastened to unit frame with sheet
metal screws. Fan and coil compartment must be sealed
tightly after service to prevent air from bypassing the
cooling coil.
19
Fan Motor Lubrication -- Fan motor supplied with unit is
permanentlylubricatedandrequiresnofurther
lubrication.
Fan Shaft Bearings -- Size 25--30 units have pillow--block
bearings (Fig. 22) that must be lubricated with suitable
bearing grease approximately every 3 months. See Table 7
for suitable lubricants.
Table 7 – Lubricant Data
MANUFACTURERLUBRICANT
MobilMobilplex EP No. 2
SunocoPrestige 42
TexacoMultifak 2
TexacoR e g a l A F B --- 2 *
*Preferred lubricant, contains rust and oxidation inhibitors.
524J
Centering Fan Wheel -- If fan and fan shaft assembly are
not properly centered, blades may scrape against the
blower side scroll plate or may create an objectionable
whistling noise. It may be necessary to adjust individual
fan wheels or move entire fan shaft. See the following two
sections.
Fan Shaft Position Adjustment -- Loosen setscrew or
locking collar of each fan shaft bearing. Slide shaft into
correct position and replace locking collar (Fig. 23). To
replace locking collar, push collar up against inner face of
bearing. Turn collar in direction of fan rotation until tight,
and tighten setscrew. Tightening locking collar in
direction of fan rotation results in further tightening of
collar should setscrew work itself loose.
C10698
Fig. 22 -- Fan Shaft, Bearings, and Fan Wheel (Typical)
C10699
Fig. 23 -- Fan Shaft Bearing
Fig. 24 -- Fan Motor Mounting
C10700
20
Individual Fan Wheel Adjustment -- Loosen the 2
locking bolts holding fan wheel hub to shaft. See Fig. 22.
Position fan wheel in center of the fan housing and tighten
locking bolts. Clearance between wheel and housing
should be the same on both sides.
Fan Belts -- Motor mounting plate and motor support
angles are slotted to permit both vertical and horizontal
adjustment. Adjust belt(s) for correct deflection by
loosening motor plate mounting bolts, moving motor/plate
assembly forward or back, and re--tightening bolts. Press
down on belt with one finger midway between fan and
motor pulleys to check deflection. The correct deflection
1
/8--in. (3.2 mm). See Fig. 24.
is
If complete belt replacement is required during servicing,
loosen the motor plate mounting bolts (Fig. 24), move
motor/plate assembly towards fan pulley, and pull belt(s)
off pulleys. Reverse the procedure with new bolts and
readjust deflection.
Fan Rotation -- Correct fan rotation with respect to fan
outlet is shown in Fig. 25.
C10701
Fig. 25 -- Fan Rotation
To reverse the direction of rotation of a 3--phase fan
motor, reverse any 2 of the power leads. Refer to the
connection diagram on the inside of motor terminal box
cover for proper reversing procedure of single--phase
motor.
Fan Pulley Alignment -- Align as follows:
1. Loosen setscrews on pulleys.
2. Align pulleys visually and tighten setscrews on fan
pulley to lock it in place.
3. Use the methods shown in Fig. 26 to check proper
pulley alignment.
4. If pulleys are not in correct alignment, loosen the motor holddown bolts and slide the motor axially until
the pulleys are aligned.
5. Tighten motor holddown bolts.
C10702
Fig. 26 -- Fan Pulley Adjustments
Pulley and Drive Adjustment -- To obtain desired fan
speed, refer to the fan motor and drive data in Tables
8A--11D and adjust fan motor pulley as follows:
1. Remove belt from fan motor pulley after loosening
motor from motor base.
2. Loosen setscrew in moveable flange of pulley. Screw
moveable flange toward fixed flange to increase the
fan speed and away from fixed flange to reduce
speed. Before tightening setscrew, make certain that
setscrew is over nearest flat surface of pulley hub
(Fig. 26).
!
UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment
damage.
Increasing fan speed produces a greater load on motor.
Do not exceed rated capacity of motor.
Condensate Drains -- Keep condensate drains free of dirt
and foreign matter.
Return--Air Filters -- Refer to Replacing Filters section
for filter accessibility and removal. Replace with clean
filters of the sizes listed in Tables 1A--1F.
S After draining as much water as possible from coils, add
sufficient antifreeze to prevent residual water in the coil
from freezing.
CAUTION
524J
S Add a sufficient quantity of non--corrosive antifreeze to
the entire system to prevent all water within the system
from freezing.
21
Coil Removal -- Remove unit panels and corner posts as
required. Disconnect coil connections and remove fastening
screws. Remove coil through end or side sections of unit.
Cleaning Cooling Coil -- Remove return--air filters.
Remove any heavy dirt that may have accumulated on
underside of coil. Coil can be cleaned more easily with a
stiff brush, vacuum cleaner, or compressed air when coil
is dry. If coil is wet or if water is to be used for cleaning,
guard against splashing water on electrical components or
damaging surrounding area.Clean coil baffles as
applicable and check for tight fit to be sure air does not
bypass coil.
Cleaning Insulation -- The insulation contains an
immobilized antimicrobial agent that helps prevent the
growth of bacteria and fungi. Clean the inner surface of
the insulation according to the separate maintenance
instructions shipped with the unit.
Replacing Filters -- Filters can be removed and installed
524J
from either side of the unit. Install new filters in units that
have one fan as follows:
1. Remove the side access panel (retain screws).
2. Remove the filter retainer clip (see Fig. 27).
3. Remove old filters by lifting and tilting them out of
the filter track. See Fig. 15 and 28. Use the factory-supplied filter hook to slide filters within reach for removal. The filter hook is shipped inside the unit in
the filter track
4. Reverse the procedure to install new filters.
SLIDE
Fig. 27 -- Remove Filter Retainer Clip
FILTER
RETAINER
CLIP
C10703
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment
damage.
Do not operate unit without air filters.
C10704
Fig. 28 -- Filter Removal/Replacement
22
Table 8A -- Fan Motor Data, Standard Motor — English
UNIT
524J*25A
524J*25H
524J*28A524J*30A
208/230--- 3 ---60 and 460 --- 3---60
Speed (rpm)174517451745
Hp5.07.510.0
Frame (NEMA)S184TS213TS215T
Shaft Dia (in.)11/
8
13/
8
5 7 5 --- 3 --- 6 0
Speed (rpm)174517551755
Hp5.07.510.0
Frame (NEMA)184TS213TD215T
Shaft Dia (in.)11/
LEGEND
NEMA — National Electrical Manufacturers Association
8
13/
8
Table 8B -- Fan Motor Data, Alternate Motor — English
UNIT
208/230--- 3 ---60 and 460 --- 3---60
Speed (rpm)174517451745
Hp7.510.010.0
Frame (NEMA)S213TS215TS215T
Shaft Dia (in.)13/
5 7 5 --- 3 --- 6 0
Speed (rpm)175517501750
Hp7.510.010.0
Frame (NEMA)S213TD215TD215T
Shaft Dia (in.)13/
LEGEND
NEMA — National Electrical Manufacturers Association
524J*25A
524J*25H
8
8
524J*28A524J*30A
13/
8
13/
8
13/
13/
13/
13/
8
8
524J
8
8
23
Table 8C -- Fan Motor Data, Standard Motor — SI
524J
UNIT
208/230--- 3 ---60 and 460 --- 3---60
Speed (r/s)29.0829.0829.08
Shaft kW3.735.607.46
Frame (NEMA)S184TS213TS215T
Shaft Dia (mm)28.634.934.9
5 7 5 --- 3 --- 6 0
Speed (r/s)29.0829.2529.25
Shaft kW3.735.607.46
Frame (NEMA)184TS213TS215T
Shaft Dia (mm)28.634.934.9
LEGEND
NEMA — National Electrical Manufacturers Association
524J*25A
524J*25H
524J*28A524J*30A
Table 8D -- Fan MotorData, Alternate Motor — SI
UNIT
208/230--- 3 ---60 and 460 --- 3---60
Speed (r/s)29.0829.1729.17
Shaft kW5.607.467.46
Frame (NEMA)S213TS215TS215T
Shaft Dia (mm)34.934.934.9
5 7 5 --- 3 --- 6 0
Speed (r/s)29.2529.1729.17
Shaft kW5.607.467.46
Frame (NEMA)S213TD215TD215T
Shaft Dia (mm)34.934.934.9
524J*25A
524J*25H
524J*28A524J*30A
LEGEND
NEMA — National Electrical Manufacturers Association
24
Table 9A -- Standard Drive Data, 60 Hz — English
UNIT
524J*25A
524J*25H
524J*28A524J*30A
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)3.7 ---4.74.3---5.34.3--- 5.3
Pulley Factory Setting
Full Turns Open
3.03.03.0
FAN DRIVE
Pulley Pitch Dia (in.)9.411.011.0
Pulley Bore (in.)17/
16
Belt No. — Section2—B2—B
Belt Pitch (in.)41.8
115/
16
(2) 42.8
(2) 43.8
115/
16
†
2—B
†
(2) 42.8
(2) 43.8
FAN SPEEDS (rpm)
Factory Setting771752752
Range679--- 863682--- 841674--- 831
Max Allowable Speed (rpm)120011001100
Change per1/2Turn of
Moveable Motor Pulley
15.313.113.1
Flange
MAX FULL TURNS FROM
CLOSED POSITION
666
SHAFTS CENTER DISTANCE (in.)9.12--- 10.996.67 --- 9.436.67 --- 9.43
†
Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
524J
Table 9B -- Medium--Static Drive Data, 60 Hz — English
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)4.3 ---5.34.3---5.34.3--- 5.3
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)9.49.49.4
Pulley Bore (in.)17/
Belt No. — Section1—B2—B
Belt Pitch (in.)41.8
FAN SPEEDS (rpm)
Factory Setting881881881
Range798--- 984798--- 984798--- 984
Max Allowable Speed (rpm)120011001100
Change per1/2Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)9.16--- 10.996.67 --- 9.436.67 --- 9.43
†
Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
524J*25A
524J*25H
524J*28A524J*30A
3.03.03.0
16
115/
16
†
(2) 38.8
(2) 39.8
15.315.315.3
666
115/
16
2—B
(2) 38.8
(2) 39.8
†
25
Table 9C -- High--Static Drive Data, 60 Hz — English
524J
UNIT
524J*25A
524J*25H
524J*28A524J*30A
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)4.3--- 5.34.3 --- 5.34.3 --- 5.3
Pulley Factory Setting
Full Turns Open
3.03.03.0
FAN DRIVE
Pulley Pitch Dia (in.)7.48.68.6
Pulley Bore (in.)17/
16
115/
16
115/
16
Belt No. — Section2—B2—B2—B
Belt Pitch (in.)36.837837.8
FAN SPEEDS (rpm)
Factory Setting111810241024
Range1014 --- 1200Ă
†
873--- 1075873 ---1075
Max Allowable Speed (rpm)120011001100
Change per1/2Turn of
Moveable Motor Pulley
19.416.716.7
Flange
MAX FULL TURNS FROM
CLOSED POSITION
666
SHAFTS CENTER DISTANCE (in.)8.16-- -10.026.67 --- 9.436.67---9.43
†
It is possible to adjust drive so that fan speed exceeds maximum all owable. DO NOT exceed 1200 rpm.
Table 9D-- Standard Drive Data, 60 Hz — SI
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)94.0--- 119.4109.2 ---134.6109.2--- 134.6
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)239279279
Pulley Bore (mm)36.549.249.2
Belt No. — Section2—B2—B
Belt Pitch (mm)1062
FAN SPEEDS (r/s)
Factory Setting12.912.512.5
Range11.3--- 14.411.4 ---14.011.2- -- 13.9
Max Allowable Speed (r/s)20.018.318.3
Change per1/2Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (mm)232 ---279169--- 240169 ---240
†
Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
524J*25A
524J*25H
524J*28A524J*30A
3.03.03.0
†
(2) 1987
(2) 1113
0.2550.2180.218
666
†
2—B
(2) 1987
(2) 1113
26
Table 9E -- Medium--Static Drive Data, 60 Hz — SI
UNIT
524J*25A
524J*25H
524J*28A524J*30A
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)109.2--- 134.6109.2--- 134.6109.2 --- 134.6
Pulley Factory Setting
Full Turns Open
3.03.03.0
FAN DRIVE
Pulley Pitch Dia (mm)239239239
Pulley Bore (mm)36.549.249.2
Belt No. — Section1—B2—B
Belt Pitch (mm)1062
(2) 986
(2) 1011
†
†
2—B
(2) 986
(2) 1011
FAN SPEEDS (r/s)
Factory Setting14.714.714.7
Range13.3 ---16.413.3--- 16.413.3 --- 16.4
Max Allowable Speed (r/s)20.018.318.3
Change per1/2Turn of
Moveable Motor Pulley
0.2550.2550.255
Flange
MAX FULL TURNS FROM
CLOSED POSITION
666
SHAFTS CENTER DISTANCE (mm)232--- 279169 ---240169- -- 240
†
Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
524J
Table 9F -- High--Static Drive Data, 60 Hz — SI
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)109.2 ---134.6109.2--- 134.6109.2---134.6
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)188203
Pulley Bore (mm)36.549.249.2
Belt No. — Section2—B2—B2—B
Belt Pitch (mm)935935960
FAN SPEEDS (r/s)
Factory Setting18.617.117.1
Range16.9--- 20.0
Max Allowable Speed (r/s)20.018.318.3
Change per1/2Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (mm)207 ---255169--- 240169 ---240
†
It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s
524J*25A
524J*25H
524J*28A524J*30A
3.03.03.0
†
†
14.6--- 17.914.6--- 7.9
0.3230.2780.278
666
203
27
Table 10A -- 524J Standard Fan Performance Data —
0.0--2.4 in. wg External Static Pressure — English
Bhp --- Brake Horsepower Input to Fan
ESP --- External Static Pressure
NOTES:
1. Maximum allowable f a n speed for size 25 units is 1200 rpm . Maximum
allowable fan speed for size 28 and 30 units is 1100 rpm.
2. Fan performance is based on deduct ions for wet coil, clean 2-in. filters,
and unit casing. See table at right for fact ory-s up pli ed filter pressure drop.
3. Refer to fan motor and drive tables for additional data.
LEGEND
Legend and Notes for Tables 10B and 10D
524J
ESP --- External Static Pressure
NOTES:
1. Maximumallowablefanspeedforsize25unitsis20r/s.Maximum
allowable fan speed f or size 28 and 30 units is 18.3 r/s.
2.Fanperformanceisbasedondeductionsforwetcoil,clean51---mm
filters, and unit casing. See table at right for factory-supplied filter
pressure drop.
3. Refer to fan motor and drive tables for additional data.
LEGEND
FACTORY-SUPPLIED PRESSURE DROP — ENGLISH
UNIT
524J*25A
524J*25H
524J*28A
524J*30A
AIRFLOW
(Cfm)
6,0000.12
8,0000.19
10,0000.26
7,5000.15
10,0000.22
12,5000.30
9,0000.19
12,0000.29
15,0000.40
PRESSURE DROP
(in. wg)
FACTORY-SUPPLIED PRESSURE DROP — SI
UNIT
524J*25A
524J*25H
524J*28A
524J*30A
AIRFLOW
(L/s)
290032
380047
470064
350036
470055
590076
425047
565071
705098
PRESSURE DROP
(Pa)
32
524J
33
524J
2011 Bryant Heating and Cooling Systems. D 7310 W. Morris St. D Indianapolis, IN 46231Printed in U.S.A.Edition Da te: 01/11
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
34
Catalog No: II524J---07
Replaces: II524J--- 05
START--UP CHECKLIST
(SPLIT SYSTEMS WITH 524J UNITS)
I. PRELIMINARY INFORMATION
OUTDOOR: MODEL NO.INDOOR: MODEL NO.
SERIAL NO.SERIAL NO.
ADDITIONAL ACCESSORIES
II. PRE--START--UP
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? (Y/N)
IF SO, WHERE:
WILL THIS DAMAGE PREVENT UNIT START--UP? (Y/N)
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N)
HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N)
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N)
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED? (Y/N)
CONTROLS
ARE THERMOSTAT(S) & INDOOR FAN CONTROL WIRING CONNECTIONS MADE & CHECKED? (Y/N)
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N)
HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS? (Y/N)
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N)
ARE PROPER AIR FILTERS IN PLACE? (Y/N)
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N)
DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)
PIPING
HAS FOAM SHIPPING BLOCK BEEN REMOVED FROM THE TXV (Thermostatic Expansion Valve)? (Y/N)
524J
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR UNIT (524J***A) OR OUTDOOR UINT
(524J*25H) COILS AS REQUIRED? (Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, INDOOR COILS,
TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR? (Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED) (Y/N)
ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING CORRECT LEVELS? (Y/N)
35
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS:ABVACVBCV
(AB + AC + BC)/3 = AVERAGE VOLTAGE =V
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
III. START--UP
CHECK INDOOR FAN MOTOR SPEED AND RECORD.
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: