Bryant 524J25A, 524J28A, 524J30A, 524J Series Installation, Start-up And Service Instructions Manual

524J PACKAGED AIR--HANDLING UNITS, 60 Hz WITH PURONR(R--410A) REFRIGERANT SIZES 25, 28, 30
Installation, Start--Up
and Service Instructions
SAFETY CONSIDERATIONS 1...................
PRE--INSTALLATION 2.........................
Moving and Storage 2..........................
Rigging 2....................................
INSTALLATION 2–18..........................
General 2....................................
Uncrating 2..................................
Accessories 2.................................
Unit Positioning 9.............................
Unit Isolation 11..............................
Refrigerant Piping Access 11....................
Refrigerant Piping 11..........................
Condensate Drain 14...........................
Fan Motors and Drives 15.......................
Power Supply and Wiring 15....................
Connecting Ductwork 17.......................
Return--Air Filters 17..........................
START--UP 19.................................
SERVICE 19–32...............................
Panels 19....................................
Fan Motor Lubrication 20.......................
Fan Shaft Bearings 20..........................
Centering Fan Wheel 20........................
Fan Shaft Position Adjustment 20................
Individual Fan Wheel Adjustment 21..............
Fan Belts 21.................................
Fan Rotation 21...............................
Fan Pulley Alignment 21.......................
Pulley and Drive Adjustment 21..................
Condensate Drains 21..........................
Return--Air Filters 21..........................
Coil Removal 22..............................
Cleaning Cooling Coil 22.......................
Cleaning Insulation 22.........................
Replacing Filters 22...........................
START--UP CHECKLIST 35--36..................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions package
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the safety--alert symbol
unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
. When you see this symbol on the
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause in personal injury or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lockout tag. Unit may have more than one power switch.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause in personal injury,death and/or equipment damage.
R
524J
Puron higher pressures than standard R--22 systems. Do not use R--22 service equipment or components on Puron refrigerant equipment.
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing 524J units.
(R--410A) refrigerant systems operate at
!
WARNING
!
CAUTION
PRE--INSTALLATION
1. The power supply (v, ph, and Hz) must correspond to that specified on unit rating plate.
2. The electrical supply provided by the utility must be sufficient to handle load imposed by this unit.
3. Refer to Installation, General section (page 2) and Fig. 1 and Fig. 2 for locations of electrical inlets, con­densate drain, duct connections, and required clear­ances before setting unit in place.
4. This installation must conform with local building codes and with the NEC (National Electrical Code) or ANSI (American National Standards Institute)/NFPA (National Fire Protection Association) latest revision. Refer to provincial and local plumbing or wastewater codes and other applicable local codes.
Moving and Storage -- To transfer unit from truck to storage site, use a fork truck. Do not stack units more than 2 high during storage. If unit is to be stored for more than 2 weeks before installation, choose a level, dry storage site free from vibration. Do not remove plastic wrap or skid from unit until final installation.
Rigging -- All 524J Series units can be rigged by using the shipping skid. Units are shipped fully assembled. Do not
remove shipping skids or protective covering until unit is ready for final placement; damage to bottom panels can result. Use slings and spreader bars as applicable to lift unit.
INSTALLATION
General -- Allow the following clearances for service
access and airflow:
1
S Rear: 3 ft (914 mm) [2
accessory]
1
S Front: 2 S Right Side: 3 S Left Side: 2
For units equipped with an economizer, refer to the accessory installation instructions for additional clearance requirements. Be sure floor, wall, or ceiling can support unit weight (Tables 1A – 1D). See Fig. 1 and Fig. 2 for dimensions.
Uncrating -- Move unit as near as possible to final location before removing shipping skid.
/2ft (762 mm)
1
/2ft (1067 mm)
1
/2ft (762 mm)
/2ft (762 mm) with electric heat
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment damage.
Ensure voltage listed on unit data plate agrees with electrical supply provided for the unit.
Remove metal banding, top skid, and plastic wrap. Examine unit for shipping damage. If shipping damage is evident, file claim with transportation agency. Remove base skid just prior to actual installation.
Check nameplate information against available power supply and model number description in Fig. 3.
NOTE: Be sure to remove the styrofoam shipping pad from the thermostatic expansion valve (TXV). Verify that it has been removed. See Fig. 5.
Accessories -- Refer to instructions shipped with each accessory for specific information.
2
Table 1A — 524J***A Physical Data, English — Cooling Units
UNIT 524J* 25A 28A 30A
NOMINAL CAPACITY (Tons) 20 25 30
OPERATING WEIGHT (lb)
Base Unit with TXV 730 1050 1062
Plenum 225 325 325
FANS
Qty...Diam. (in.) 2...15 2...18 2...18
Nominal Airflow (cfm) 8000 10000 12000
Airflow Range (cfm) 6000 – 10000 7500 – 12500 9000 – 15000
Nominal Motor Hp (Standard Motor)
208/230--- 3 ---60 and 460 --- 3---60 5.0 7.5 10.0
5 7 5 --- 3 --- 6 0 5.0 7.5 10.0
Motor Speed (rpm)
208/230--- 3 ---60 and 460 --- 3---60 1745 1745 1745
5 7 5 --- 3 --- 6 0 1745 1755 1755
REFRIGERANT R--- 410A
Operating charge (lb) (approx per circuit)*
DIRECT--- EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine---Wave Fins
Max Working Pressure (psig) 650
Face Area (sq ft) 19.88 24.86 29.83
No. of Splits 2 2 2
No. of Circuits per Split 18 20 24
Split Type...Percentage Face...50/50
Rows...Fins/in. 4...15 4...15 4...15
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 2...11/
DX Coil — Liquid Refrigerant (ODF) 2...5/
Steam Coil, In (MPT) 1...21/
Steam Coil, Out (MPT) 1...1/
Hot Water Coil, In (MPT) 1...2
Hot Water Coil, Out (MPT) 1...2
Condensate (PVC) 1...11/4ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.)
Access Location Either Side
STEAM COIL**
Max Working Pressure (psig at 260° F) 20
Tota l F a ce Ar e a ( s q ft) 13.33 15.0 15.0
Rows...Fins/in. 1...10 1...10 1...10
HOT WATER COIL**
Max Working Pressure (psig) 150
Tota l F a ce Ar e a ( s q ft) 13.33 15.0 15.0
Rows...Fins/in. 2...8.5 2...12.5 2...12.5
Water Volume
(gal) 13.9 14.3
(ft3) 1.90
LEGEND
DX — Direct Expansion TXV — Thermostatic Expansion Valve
* Units are shipped without refrigerant charge. ** Field installed accessory only.
3.5
8
4...16 x 20 x 2
4...16 x 24 x 2
4.5 5.0
2...13/
8
8
2
2
4...20 x 24 x 2
4...20 x 25 x 2
2...13/
8
524J
3
524J
Table 1B —524J***A Physical Data, SI — Cooling Units
UNIT 524J* 25A 28A 30A
NOMINAL CAPACITY (kW) 70 87 105
OPERATING WEIGHT (kg)
Base Unit with TXV 331 477 482
Plenum 102 148 148
FANS
Qty...Diam. (mm) 2...381 2...457 2...457
Nominal Airflow (L/s) 3775 4119 5663
Airflow Range (L/s) 2831 – 4719 3539 – 5899 4247 – 7079
Nominal Motor kW (St andard Motor)
208/230--- 3 ---60 and 460 --- 3---60 3.73 5.60 7.46
5 7 5 --- 3 --- 6 0 3.73 5.60 7.46
Motor Speed (r/s)
208/230--- 3 ---60 and 460 --- 3---60 29.1 29.1 29.1
5 7 5 --- 3 --- 6 0 29.1 29.3 29.3
REFRIGERANT R--- 410A
Operating charge (kg)
(approx per circuit)*
DIRECT--- EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine---Wave Fins
Max Working Pressure (kPag) 4481
Face Area (sq m) 1.85 2.30 2.77
No. of Splits 2 2 2
No. of Circuits per Split 18 20 24
Split Type...Percentage Face...50/50
Rows...Fins/m 4...591 4...591 4...591
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 2...11/
DX Coil — Liquid Refrigerant (ODF) 2...5/
Steam Coil, In (MPT) 1...21/
Steam Coil, Out (MPT) 1...1/
Hot Water Coil, In (MPT) 1...2
Hot Water Coil, Out (MPT) 1...2
Condensate (PVC) 1...11/4ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (mm.)
Access Location Either Side
STEAM COIL**
Max Working Pressure (kPag at 126°C) 138
Tota l F a ce Ar e a ( s q m) 1.24 1.39 1.39
Rows...Fins/m 1...394 1...394 1...394
HOT WATER COIL**
Max Working Pressure (kPag) 1034
Tota l F a ce Ar e a ( s q m) 1.24 1.39 1.39
Rows...Fins/m 2...335 2...335 2...335
Water Volume
(L) 52.6 54.1
(m3) 0.052 0.054
LEGEND
DX — Direct Expansion TXV — Thermostatic Expansion Valve
* Units are shipped without refrigerant charge. ** Field installed accessory only.
1.59
8
4...406 x 508 x 51
4...406 x 610 x 51
2.04 2.27
2...13/
8
8
2
2
2...13/
4...508 x 610 x 51
4...508 x 635 x 51
8
4
Table 1C — 524J*25H Physical Data, English — Heat Pump Units
UNIT 524J* 25H
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
Base Unit with TXV 720
Plenum 140
FANS
Qty...Diam. (in.) 2...15
Nominal Airflow (cfm) 8000
Airflow Range (cfm) 6000 --- 10000
Nominal Motor Hp (Standard Motor)
208/230--- 3 ---60 and 460 --- 3---60 5.0
5 7 5 --- 3 --- 6 0 5.0
Motor Speed (rpm)
208/230--- 3 ---60 and 460 --- 3---60 1745
5 7 5 --- 3 --- 6 0 1745
REFRIGERANT
Operating charge (lb) (approx per circuit)*
DIRECT--- EXPANSION COIL
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
Max Working Pressure (psig) 650
Face Area (sq ft) 19.9
No. of Splits 2
No. of Circuits per Split 2
Split Type...Percentage Face....50/50
Rows...Fins/in. 4...15
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 2...1
DX Coil — Liquid Refrigerant (ODF) 2...
Steam Coil, In (MPT) 1...2
Steam Coil, Out (MPT) 1...1
Hot Water Coil, In (MPT) 1...2
Hot Water Coil, Out (MPT) 1...2
Condensate (PVC) 1...1
FILTERS
Throwaway — Factory Supplied
Quantity...Size (in.) 4...16 x 20 x 2
Access Location RightorLeftSide
STEAM COIL**
Max Working Pressure (psig at 260° F) 20
Tota l F a ce Ar e a ( s q ft) 13.33
Rows...Fins/in. 1...10
HOT WATER COIL**
Max Working Pressure (psig) 150
Tota l F a ce Ar e a ( s q ft) 13.33
Rows...Fins/in. 2...8.5
Water Volume
(gal) 13.9
(ft3) 1.85
LEGEND
DX — Direct Expansion TXV — Thermostatic Expansion Valve
*
Units are shipped without refrigerant charge.
** Field installed accessory only.
20
R--- 410A
3.5/3.5
1/
8
5/
8
1/
2
1/
2
1/
ODM/1 IDF
4
4...16 x 24 x 2
524J
5
524J
Table 1D — 524J*25H Physical Data, SI — Heat Pump Units
UNIT 524J* 25H
NOMINAL CAPACITY (kW)
OPERATING WEIGHT (kg)
Base Unit with TXV 326
Plenum 44
FANS
Qty...Diam. (mm) 2...381
Nominal Airflow (L/s) 3775
Airflow Range (L/s) 2831--- 4719
Nominal Motor kW (St andard Motor)
208/230--- 3 ---60 and 460 --- 3---60 3.73
5 7 5 --- 3 --- 6 0 3.73
Motor Speed (r/s)
208/230--- 3 ---60 and 460 --- 3---60 29.1
5 7 5 --- 3 --- 6 0 29.1
REFRIGERANT
Operating charge (kg) (approx per circuit)*
DIRECT--- EXPANSION COIL
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
Max Working Pressure (kPag) 4482
Face Area (sq m) 1.85
No. of Splits 2
No. of Circuits per Split 2
Split Type...Percentage Face...50/50
Fins/m 591
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 2...1
DX Coil — Liquid Refrigerant (ODF) 2...
Steam Coil, In (MPT) 1...2
Steam Coil, Out (MPT) 1...1
Hot Water Coil, In (MPT) 1...2
Hot Water Coil, Out (MPT) 1...2
Condensate (PVC) 1...1
FILTERS
Throwaway — Factory Supplied
Quantity...Size (mm)
Access Location RightorLeftSide
STEAM COIL**
Max Working Pressure (kPag at 126°C) 138
Tota l F a ce Ar e a ( s q m) 1.24
Rows...Fins/m 1...394
HOT WATER COIL**
Max Working Pressure (kPag) 1034
Tota l F a ce Ar e a ( s q m) 1.24
Rows...Fins/m 2...335
Water Volume
(L) 52.6
(m3) 0.052
LEGEND
DX — Direct Expansion TXV — Thermostatic Expansion Valve
*
Units are shipped without refrigerant charge.
** Field installed accessory only.
70
R--- 410A
1.59/1.59
1/
8
5/
8
1/
2
1/
2
1/
ODM/1 IDF
4
4...406 x 610 x 51
4...406 x 508 x 51
6
LEGEND
TXV — Thermostatic Expansion Valve NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. [914 mm] (2 ft, 6 in. [762 mm] with electric heat accessory)
• Front: 2 ft, 6 in. [762 mm]
• Right Side: 2 ft, 6 in. [762 mm]
• Left Side: 2 ft, 6 in. [762 mm]
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field installed.
524J
Fig. 1 -- Dimensions – Size 25
7
UNIT
524J*25A 730 (331) 524J*25H 720 (326)
UNIT WEIGHT
lb (kg)
C10834
524J
LEGEND
TXV — Thermostatic Expansion Valve NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. [914 mm] (2 ft, 6 in. [762 mm] with electric heat accessory)
• Front: 2 ft, 6 in. [762 mm]
• Right Side: 2 ft, 6 in. [762 mm]
• Left Side: 2 ft, 6 in. [762 mm]
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field installed.
6. 40RUS may require alternate or additional field favricated poping access holes
Fig. 2 -- Dimensions – Sizes 28 and 30
8
UNIT
524J*28A 524J*30A
lb (kg)
1050 (477) 1062 (482)
C10835
Model Type
524J = Bryant Fan Coil Puronr R--- 410A Refrigerant
Voltage
E = 460/3/60 P = 208 / 230/3/60 T = 575/3/60
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
5 2 4 J E 2 5 A 0 0 0 A 2 0 A A A
_____________
____
Not Used
A = Not Used
Service Options
A=None
B = Painted Cabinet
Packa ging
A=Standard
Nominal Tonnage
25 = 20 Tons 28 = 25 Tons 30 = 30 Tons
Typ e o f C oi l
A = Standard DX Coil B = High Capacity DX Coil H = DX Coil for Heat Pump Duty
Not Used
0=Not Used
Not Used
0=Not Used
POSITION NUMBER TYPICAL
Not Used
0 = Not Used
Indoor Fan Options
1 = Fan Drive and Motor - Low / Motor Efficency - Standard 2 = Fan Drive and Motor - Med / Motor Efficency - Standard 3 = Fan Drive and Motor - High / Motor Efficency - Standard
Coil Options
A=Al/Cu
Not Used
0 = Not Used
C10837
Fig. 3 -- Model Number Nomenclature
12345678910 2610G12345
SETANGISEDNOITISOP
)radnelac lacsif( erutcafunam fo keeW1−2
Year of manufacture (“10” = 2010)3−4
)ASU ,saxeT ,PTE = G( noitacol gnirutcafunaM5
rebmun laitneuqeS6−10
C!0725
Fig. 4 -- Serial Number Nomenclature
524J
TXV COIL
REMOVE FOAM BLOCK
LEGEND
TXV — Thermostatic Expansion Valve
C10683
Fig. 5 -- Foam Block Location
Unit Positioning -- The unit can be mounted on the floor
for vertical application with return air entering the face of the unit and supply air discharging vertically through the top of the unit. The unit can also be applied in a horizontal arrangement with return air entering
horizontally and the supply air discharging horizontally. When applying the unit in a horizontal arrangement, ensure the condensate drain pan is located at the bottom center of the unit for adequate condensate disposal. See Fig. 6 for condensate connections for each unit position.
PLUG
PLUG
Note: Maintain recommended clearances
CONDENSATE DRAIN
LEGEND
Accessory Line Alternate Air Intake and Discharge
Air Intake and Discharge
per Fig. 1 and Fig. 2
C10684
Fig. 6 -- Typical Unit Positioning
9
Typical positioning and alternate return air locations are shown in Fig. 6. Alternate return air locations can be used by moving the unit panel from the alternate return air location to the standard return air location. Refer to overhead suspension accessory drawing (Fig. 7) for
OVERHEAD SUSPENSION ACCESSORY — UNIT SIZE 25
524J
preferred suspension technique. The unit needs support underneath to prevent sagging.
IMPORTANT: Do NOT attempt to install unit with return air entering top panel of unit. Condensate will not drain from unit.
OVERHEAD SUSPENSION ACCESSORY — UNIT SIZES 28, 30
NOTE: Dimensions in [ ] are millimeters
Fig. 7 -- Preferred Suspension Technique
C10728
10
Unit Isolation -- Where extremely quiet operation is essential, install isolators between floor and base of unit, or between ceiling and top section of unit.
Be sure that unit is level and adequately supported. Use channels at front and sides of unit for reference points when leveling.
Refrigerant Piping Access -- The 524J Series units come with standard knockouts for refrigerant piping. These knockouts are located on both sides of the unit for installation flexibility. The standard knockouts provide sufficient access to the unit’s coils for all 524J*25A, 28A and 30A units. The 524J*25H requires additional holes which must be field--fabricated to accommodate the piping. See Fig. 8 for positions and dimensions for the additional access holes required. Recommended access hole use is also listed for all units. Note that Fig. 8 shows the access holes on the control--box side of the unit; this is the side of the unit with the coil headers, so it is used most often for piping access.
IMPORTANT: Do not bury refrigerant piping underground.
Refrigerant Piping -- See Tables 1A–1D for refrigerant pipe connection sizes. For ease in brazing, it is recommended that all internal solder joints be made before unit is placed in final position.
The 524J direct--expansion units have internal factory--installed thermostatic expansion valves (TXVs), distributors, and nozzles for use with R--410A. See Table 2 for part numbers. Knockouts are provided in the unit corner posts for 524J refrigerant piping. See Fig. 8, which also lists recommended knockouts and access holes to use for each 524J unit size. Recommended fittings are listed in Table 3.
The sensor bulb capillary tubes must be routed from the TXVs inside the unit through one of the piping access holes. Clamp the TXV sensor bulb on a vertical portion of the suction line, outside the unit. See Fig. 9.
NOTE: Be sure to remove the styrofoam shipping pad from the TXV. Verify that it has been removed. See Fig. 5.
IMPORTANT: Never attach the sensor to the suction manifold. Do NOT mount the sensor on a trapped portion of the suction line.
The 524J Series evaporator coils have a face--split design. Ensure that lower circuit of coil is first on/last off when connected to the condensing unit and/or system controls. See Fig. 10.
External TXV equalizer connections are provided and factory--brazed into the coil suction manifolds.
If suction line must be horizontal, clamp bulb to suction line at least 45 degrees above bottom, at approximately the 4 o’clock or 8 o’clock position. See Fig.11.
524J
7 6 5
4 3
2 1
UNIT
524J*25A, 28A, 30A 1,2, 3, 4
524J*25H 3*,5,6,7 11/8(28.6) 11/8(28.6) 13/4(44.5) 3.25 (82.6) 6.125 (155.6) 10.38 (263.7)
*Must be enlarge d from 11/8in. (28.6mm) to 13/4in. (44.5mm) N O TE : Acc e s s ho l e k no cko u t s 1 --- 4 ar e fact o r y --- s u p p l i e d .
USE HOLE NUMBERS
FIELD-- FABRIC ATED HOLE DIAMATERS
in. ( mm)
No. 5 No. 6 No. 7 A B C
A
FIELD-- FABRIC ATED HOLE POSITION DIMENSIONS
B
C
in. ( mm)
Fig. 8 -- Refrigerant Piping Access Holes
11
C10838
UPPER SPLIT
AIRFLOW
LOWER SPLIT
TXV SENSING BULB
15 DIAMS
MIN
TXV SENSING BULB
10
DIAMS
8 DIAMS
MIN
EQUALIZER LINE
TXV
EQUALIZER
LINE
FILTER
DRIER
SOLENOID
VALV E
SIGHT
GLASS
524J
8 DIAMS
MIN
TXV
INDOOR COIL
AIRFLOW
15 DIAMS
MIN
10
DIAMS
LEGEND:
TXV – Thermostatic Expansion Valve NOTE: Component location arrangemetshown for field installation of
sight glasses, solenoid valves, filter driers, and TXV sensing bulbs. The TXVs and equilizer lines are factory installed.
Fig. 9 -- Face--Split Coil Suction and Liquid Line Piping (Typical)
C10726
FIRST ON/LAST OFF = B
VERTICAL INSTALLATION
FIRST ON/LAST OFF = A
HORIZONTAL INSTA LLATIO N
Fig. 10 -- Typical Evaporator Coil Connections (524J)
LEGEND
TXV — Thermostatic Expansion Valve NOTE: The 8 o’clock position is shown above.
C10689
Fig. 11 -- TXV Sensing Bulb Location
C10688
12
Table 2 – Factory--Installed Nozzle and Distributor Data
UNIT
COIL TYPE
STD
524J*25A 4Row 2 . . . B B I Z E --- 8 --- G A 2...D196--- 18---3/
TXV
Qty...Part No.
DISTRIBUTOR
Qty...Part No.
16
524J*28A 4Row 2 . . . B B I Z E --- 15 --- G A 2...1126 20...3/
524J*30A 4Row 2 . . . B B I Z E --- 15 --- G A 2...1126 24...3/
524J*25H 4Row 2 . . . B B I Z E --- 12 . 5 --- G A 2...113 --- 12 ---3/
]
Feeder tu be size is1/4in. (6.35 mm).
NOTE: Hot gas bypass applications require field -- -supplied auxiliary side connector.
16
Table 3 – Fitting Requirements
UNIT ACCESS HOLE NO.
1 Suction Lower
2 Liquid Lower
524J*25A
3 Liquid Upper
4 Suction Upper
3 Suction Lower
5 Suction Lower
524J*25H
6 Liquid Upper
7 Suction Upper
1 Suction Lower
2 Liquid Lower
524J*28A
3 Liquid Upper
4 Suction Upper
]
See Fig. 8 for access hole location by number.
† Fittings are listed in order from header or tee stub connection out to access hole in corner support post.
]
CONNECTION TYPE CIRCUIT FITTINGS REQUIRED†(in.)
FEEDER TUBES
PER DISTRIBUTOR
Qty...Size (in.)
18...3/
16
16
16
2 --- 1 2 . . .3/
16
11/8Street Elbow
11/8Nipple, 75/8L
11/8Long Radius Elbow
5
/8Street Elbow
5
/8Nipple, 61/2L
5
/8Long Radius Elbow
5
/8Street Elbow
5
/8Nipple, 91/2L
5
/8Long Radius Elbow
11/8Nipple, 55/8L
11/8Long Radius Elbow
11/8Nipple, 11 L
11/8Long Radius Elbow
11/8Nipple, 3 L
11/8Long Radius Elbow
5
/8Nipple, 27/8L
5
/845_ Elbow
5
/8Nipple, 15/8L
5
/8Long Radius Elbow
5
/8Nipple, 27/8L
5
/845_ Elbow
5
/8Nipple, 41/4L
5
/8Long Radius Elbow
11/8Nipple, 5 L
11/845_ Elbow
11/8Nipple, 83/4L
11/8Long Radius Elbow
13/8Street Elbow
13/8Nipple, 11 L
13/8Long Radius Elbow
5
/8Street Elbow
5
/8Nipple, 11/2L
5
/8Long Radius Elbow
5
/8Street Elbow
5
/8Nipple, 191/2L
5
/8Long Radius Elbow
13/8Nipple, 43/16L
13/8Long Radius Elbow
13/8Nipple, 231/4L
13/8Long Radius Elbow
]
NOZZLE
Qty...Part No.
2...G6
2...C15
2...C17
2...G8
524J
13
Table 3 — Fitting Requirement (cont)
UNIT ACCESS HOLE NO.
1 Suction Lower
2 Liquid Lower
524J*30A
3 Liquid Upper
4 Suction Upper
]
See Fig. 8 for access hole location by number.
† Fittings are listed in order from header or tee stub connection out to access hole in corner support post.
]
CONNECTION TYPE CIRCUIT FITTINGS REQUIRED†(in.)
13/8Street Elbow 13/8Nipple, 3 L 13/8Long Radius Elbow
5
/8Street Elbow
5
/8Nipple, 73/4L
5
/8Long Radius Elbow
5
/8Street Elbow
5
/8Nipple, 181/2L
5
/8Long Radius Elbow 13/8Nipple, 43/16L 13/8Long Radius Elbow 13/8Nipple, 191/4L 13/8Long Radius Elbow
Condensate Drain -- Install a trapped condensate drain line
524J
to unit connection as shown in Fig. 12. The unit drain connection is a PVC stub. See Fig. 13. Some areas may require an adapter to connect to either galvanized steel or copper pipe. For these applications, install a field--supplied threaded PVC adapter.
3” MIN.
[76]
Install clean--out plugs in trap. Pitch drain line downward to an open floor drain or sump. Provide service clearance around drain line to permit removal of unit panels. Observe all local sanitary codes.
C10692
Fig. 13 -- Drain Pan Slope Adjustment
NOTE: Dimensions in [ ] are in millimeters
Fig. 12 -- Condensate Drains
NOTE: A trap must be installed in the condensate drain
line to ensure that the static pressure of fans is balanced with the water column in the drain line and that condensate can drain completely from pan. Without a trap, air can be drawn up drain line until water level in condensate pan becomes equal to static pressure created by fans, preventing complete drainage. Conditions will worsen as filters become dirty.
C10691
As shipped, the unit’s condensate drain pan is NOT sloped towards the drain connection. The pan slope must be changed to pitch towards the side of the unit with the drain connection. See Fig. 13. Loosen the 2 screws next to the drain outlet at both ends of the unit, push drain pan down in the slots near the drain connection, and up in the slots on the opposite end. Re--tighten screws. The pan
1
should have a pitch of at least
/4--in. over its length
toward the drain connection.
14
Fan Motors and Drives -- Motor and drive packages are
A
factory installed in all units. The motor and drive packages consist of the following items:
1 — fan motor
Install disconnect switch and power wiring in accordance with all applicable local codes. See Fig. 14--16 and the
1
unit label diagram. Connect power wiring with
/4-- i n .
ring terminal.
1 — adjustable motor pulley 1—fanpulley 2 — matched fan belts (524J*25A--30A units) For instructions on changing fan rotation, changing drive
speeds and adjusting drives, see Pulley and Drive Adjustment in the Service section.
Power Supply and Wiring -- Check the unit data plate to ensure that available power supply matches electrical characteristics of the unit. Provide a disconnect switch with an integrated lock--out feature of size required to provide adequate fan motor starting current. See Tables 4--6 for unit electrical data.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.
FAN SCROLL
MOTOR
ND DRIVE
CONDENSATE DRAIN CONNECTION (HORIZONTAL)
FILTER ELEMENTS
FILTER RETAINER CLIP
TXV — Thermostatic Expansion Valve
LEGEND
FAN CONTACTOR BOX
WIRE ACCESS
FAN DRIVE PULLEY
COIL
TXV BULB ACCESS
REFRIGERANT PIPING ACCESS
CONDENSATE DRAIN CONNNECTION (VERTICAL)
C10693
Fig. 15 -- Wiring and Service Access
(Side Panel Removed)
Fan motors are factory--installed on all units. Indoor--fan contactors are located in the fan contactor box behind the side access panel (see Fig. 15 and 16). Wire the thermostat to the 24--v control circuit terminal block located in the side of the fan contactor control box, according to Fig. 17 or the unit label diagram. If the air handler is part of a split system, complete the wiring from the condensing unit to the thermostat shown in Fig. 17.
524J
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in intermittent operation or performance satisfaction.
Do not connect aluminum wire between disconnect switch and fan coil unit. Use only copper wire. (See Fig. 14)
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
ALUMINUM
WIRE
FAN CONTACTOR
24V TERMINAL BLOCK
POWER WIRING KNOCKOUT
Fig. 16 -- Fan Contactor Box and Terminal Block
A J
VR 00
6
C
°
5 0 1
23
22
21
W
3
1
2
1
1
1
C10694
(Cover Removed) (Typical)
A93033
Fig. 14 -- Disconnect Switch and Unit
15
Table 4 – Electrical Data, Standard Motors
524J
UNIT V --- PH --- H z
208/230--- 3 --- 60 187--- 253 5.0 (3.73) 14.7/13.6 18.4/17.0 30/25
524J*25A 524J*25H
208/230--- 3 --- 60 187--- 253 7.5 (5.59) 21.4/19.4 26.9/24.3 45/40
524J*28A
208/230--- 3 --- 60 187--- 253 10.0 (7.46) 28.0/25.2 35.0/31.5 60/50
524J*30A
See Legend and Notes below.
UNIT V --- PH --- H z *
208/230--- 3 --- 60 187--- 253 7.5 (5.59) 21.4/19.4 26.9/24.3 45/40
524J*25A 524J*25H
208/230--- 3 --- 60 187--- 253 10.0 (7.46) 28.0/25.2 35.0/31.5 60/50
524J*28A 524J*30A
See Legend and Notes below.
{
VOLTAGE
LIMITS
FAN MOTOR POWER SUPPLY
Hp (kW) FLA
Minimum
Circuit Amps
MOCP
4 6 0 --- 3 --- 60 414---506 5.0 (3.73) 6.8 8.5 15
5 7 5 --- 3 --- 60 518---632 5.0 (3.73) 5.1 6.4 15
4 6 0 --- 3 --- 60 414---506 7.5 (5.59) 9.7 12.1 20
5 7 5 --- 3 --- 60 518---632 7.5 (5.59) 7.8 9.8 15
4 6 0 --- 3 --- 60 414---506 10.0 (7.46) 12.6 15.8 25
5 7 5 --- 3 --- 60 518---632 10.0 (7.46) 10.3 12.9 20
Table 5 – Electrical Data, Alternate Motors
VOLTAGE
LIMITS
4 6 0 --- 3 --- 60 414---506 7.5 (5.59) 9.7 12.1 20
5 7 5 --- 3 --- 60 518---632 7.5 (5.59) 7.8 9.8 15
4 6 0 --- 3 --- 60 414---506 10.0 (7.46) 12.6 15.8 25
5 7 5 --- 3 --- 60 518---632 10.0 (7.46) 10.3 12.9 20
FAN MOTOR POWER SUPPLY
Hp (kW) FLA
Minimum
Circuit Amps
MOCP
Legend and Notes for Tables 4 and 5
LEGEND:
F L A --- F u l l L o a d A m p s MOCP --- Maximum Overcurrent Protection { Motors are designed for satisfactory operation within 10% of
normal voltage shown. Voltages should not exceed the limits shown in the Voltage Limits column.
NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calcu­lated in accordance with The NEC. Article 440.
2. Motor FLA values are established in accordance with Under­writers’ Laboratories (UL). Standard 1995.
3. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the formula in the example (see column to the right) to determine the percentage of volt­age imbalance.
4. Installation with Accessory Electric Heaters Size the Field Power Wiring between the heater TB1 and the 524J indoor fan motor per NEC Article 430 ---28 (1) or (2) (depends on length of conduit between heater enclosure and 524J power entry location). Install wires in field ---installed conduit.
Example: Supply voltage is 230-3-60
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
average voltage
AB = 393 v BC = 403 v AC = 396 v
Average Voltage =
(393 + 403 + 396)
3
= 397
1192
=
3
Determine maximum deviation from average voltage. (AB) 397 – 393 = 4 v (BC) 403 – 397 = 6 v (AC) 397 – 396 = 1 v Maximum deviation is 4 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
=1.5%
6
397
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
16
Fig. 17 -- Unit Wiring
524J
C10695
Table 6 – Fan Contactor Coil Data
UNIT
524J*
25A, 25H, 28A, 30A 24 10
VOLTAGE
(vac)
MAXIMUM
HOLDING VA
Connecting Ductwork -- Refer to the System Design Manual for the recommended design and layout of ductwork. Fig. 18 shows recommended duct connection to units with 2 fans.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment damage. Do not operate unit without ductwork or discharge plenum unless fan speed has been adjusted for external static pressure of zero in. wg. Failure to do so may result in motor overload.
DISCHARGE CONNECTIONS — Duct flanges are factory--supplied; they are shipped inside the unit attached to the hairpin end of the coil tube sheet for field
installation. Using the existing screws, install the duct flanges on the unit’s fan deck. Each fan discharge requires 2 flanges; each flange must be bent in the middle to conform to the discharge opening. See Fig. 19. After flanges are installed, connect them to the supply duct using a canvas connection to prevent vibration. It is important that this connection be properly fabricated to prevent high air friction losses and air noise.
RETURN CONNECTIONS — When using return--air ductwork, route return--air duct to the unit’s return air inlet near the filter rack, using a canvas connection to prevent transmission of unit vibration. If the duct blocks off the unit’s access panel, provide a slip joint in the ductwork to permit removal for servicing.
OUTDOOR--AIR INLET CONNECTIONS — Connect outdoor--air inlet to field--installed accessory economizer. Refer to Economizer Installation Instructions.
Return--Air Filters -- Type and size of filters are shown in Tables 1A – 1D and are factory--supplied and factory--installed. In all units with 2 fans, a filter replacement tool (hook) is shipped inside the unit for field use when replacing filters. See the Service section for instructions on filter element replacement.
17
524J
C10696
Fig. 18 -- Typical Fan Discharge Connections for Multiple Fan Units
C10697
Fig. 19 -- Duct Flange Installation
18
START--UP
Before starting unit, check the following and correct as necessary:
S Is unit solidly supported? S Is fan adjusted for speed and pulley alignment? S Are pulleys, motor, and bearings securely mounted? S Are there any loose parts that will rattle or vibrate? S Is condensate drain pan pitched for correct drainage? S Are coil baffle plates tight against coil to prevent air
bypass?
S Are all panels securely fastened? S Are all electrical connections correct and tight? S Is TXV bulb located on suction tube per Fig. 20? S Is the capillary tube to the bulb free of kinks and not
subject to pinching?
S Is the bulb well secured to the suction tube with strap?
2. To increase superheat, turn the stem clockwise. To de­crease the superheat, turn the stem counterclockwise. Do not turn the stem more than one full turn.
3. Wait until suction pressure and superheat stabilize. This may take more than 30 minutes.
4. Continue adjustment until superheat reaches 10_Fto 15_F (5.5_Cto8.3_C).
5. Replace the seal cap; tighten.
INSTALLER / INSTALLATEUR
TXV superheat must be checked at initial unit start-up and adjusted if necessary. Superheat must be 10 - 15 deg F.
La surchauffe TXV doit être vérifiée au moment de la mise en route initiale et ajustée si nécessaire. La surchauffe doit être comprise entre 10 et 15 degrés F.
40RU500073 2.0
C10828
Fig. 21 -- Label, TXV Adjustment
524J
Also refer to condensing unit or outdoor heat pump section instructions before starting a split system. A split system start--up checklist is provided at the end of these instructions.
40RU500072 2.0
IMPORTANT! / IMPORTANT
TXV
UPPER SPLIT BLOC SUPÉRIEUR
AIR FLOW CIRCULATION D'AIR
LOWER SPLIT BLOC INFÉRIEUR
AIR FLOW
CIRCULATION
The sensor bulb capillary tubes must be routed from the TXVs inside the unit through one of the piping
access holes. Clamp the TXV sensor bulb on a vertical portion of the suction line, outside the unit. See Fig. 7 in the installation, start-up and service instruction. Super heat must be adjusted in field.
Les tubes capillaires du capteur doivent être acheminé à partir du détendeur thermostatique situé à l'intérieur
de l'appareil au travers de l'un des trous d'accès de conduites. Attacher le capteur sur une portion verticale
de la conduite de succion, à l'extérieur de l'appareil. Voir la Figure 7 dans le manuel d'installation, de mise
SENSING BULB CAPTEUR TXV
10 DIAMS
15 DIAMS MIN
10 x DIA. MIN
15 x DIA. MIN
TXV SENSING BULB CAPTEUR TXV
D'AIR
15 DIAMS MIN
en marche, et d'entretien. La surchauffe doit être ajustée sur place.
15 x DIA. MIN
10 DIAMS
10 x DIA. MIN
Fig. 20 -- Label, TXV Bulb Location
EQUALIZER LINE CONDUITE D'ÉQUILIBRAGE
TXV
8 DIAMS MIN 8 x DIA. MIN
TXV
8 DIAMS MIN 8 x DIA. MIN
SIGHT GLASS HUBLOT
SOLENOID VALVE VANNE SOLÉNOÏDE
DESSICCATEUR
EQUALIZER LINE
CONDUITE D'ÉQUILIBRAGE
INDOOR COIL ÉCHANGEUR INTÉRIEUR
FILTER DRIER FILTRE
C10827
SERVICE
Inspection and maintenance should be performed at regular intervals and should include the following:
S Complete cleaning of cabinet, fan wheel, cooling coil,
condensate pan and drain, heating coils, and return--air grille (if present).
S Inspection of panels and sealing of unit against air
leakage.
S Adjustment of fan motor, belt, bearings, and wheels. S Cleaning or replacement of filters. S Testing for cooling/heating system leaks. S Checking of all electrical connections.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lockout tag. Unit may have more than one power switch.
Adjusting TXV for Superheat —
The unit--mounted thermostatic expansion valve(s) is/are factory set to provided superheat at the bulb location in 10_Fto15_F (5.5_Cto8.3_C) range. Actual system load conditions may require adjustment of the factory setting. To adjust the TXV superheat setting:
1. Remove the seal cap from the bottom of the TXV
body.
Most unit service can be performed by removing one or both of the unit’s side panels. Coil cleaning or removal or insulation cleaning may require removal of a rear, top, or bottom panel, depending on the unit’s orientation. When service is completed, replace unit panels.
Panels -- Panels are fastened to unit frame with sheet metal screws. Fan and coil compartment must be sealed tightly after service to prevent air from bypassing the cooling coil.
19
Fan Motor Lubrication -- Fan motor supplied with unit is permanently lubricated and requires no further lubrication.
Fan Shaft Bearings -- Size 25--30 units have pillow--block bearings (Fig. 22) that must be lubricated with suitable bearing grease approximately every 3 months. See Table 7 for suitable lubricants.
Table 7 – Lubricant Data
MANUFACTURER LUBRICANT
Mobil Mobilplex EP No. 2
Sunoco Prestige 42
Texaco Multifak 2
Texaco R e g a l A F B --- 2 *
*Preferred lubricant, contains rust and oxidation inhibitors.
524J
Centering Fan Wheel -- If fan and fan shaft assembly are not properly centered, blades may scrape against the blower side scroll plate or may create an objectionable whistling noise. It may be necessary to adjust individual fan wheels or move entire fan shaft. See the following two sections.
Fan Shaft Position Adjustment -- Loosen setscrew or locking collar of each fan shaft bearing. Slide shaft into correct position and replace locking collar (Fig. 23). To replace locking collar, push collar up against inner face of bearing. Turn collar in direction of fan rotation until tight, and tighten setscrew. Tightening locking collar in direction of fan rotation results in further tightening of collar should setscrew work itself loose.
C10698
Fig. 22 -- Fan Shaft, Bearings, and Fan Wheel (Typical)
C10699
Fig. 23 -- Fan Shaft Bearing
Fig. 24 -- Fan Motor Mounting
C10700
20
Individual Fan Wheel Adjustment -- Loosen the 2 locking bolts holding fan wheel hub to shaft. See Fig. 22. Position fan wheel in center of the fan housing and tighten locking bolts. Clearance between wheel and housing should be the same on both sides.
Fan Belts -- Motor mounting plate and motor support angles are slotted to permit both vertical and horizontal adjustment. Adjust belt(s) for correct deflection by loosening motor plate mounting bolts, moving motor/plate assembly forward or back, and re--tightening bolts. Press down on belt with one finger midway between fan and motor pulleys to check deflection. The correct deflection
1
/8--in. (3.2 mm). See Fig. 24.
is
If complete belt replacement is required during servicing, loosen the motor plate mounting bolts (Fig. 24), move motor/plate assembly towards fan pulley, and pull belt(s) off pulleys. Reverse the procedure with new bolts and readjust deflection.
Fan Rotation -- Correct fan rotation with respect to fan outlet is shown in Fig. 25.
C10701
Fig. 25 -- Fan Rotation
To reverse the direction of rotation of a 3--phase fan motor, reverse any 2 of the power leads. Refer to the connection diagram on the inside of motor terminal box cover for proper reversing procedure of single--phase motor.
Fan Pulley Alignment -- Align as follows:
1. Loosen setscrews on pulleys.
2. Align pulleys visually and tighten setscrews on fan pulley to lock it in place.
3. Use the methods shown in Fig. 26 to check proper pulley alignment.
4. If pulleys are not in correct alignment, loosen the mo­tor holddown bolts and slide the motor axially until the pulleys are aligned.
5. Tighten motor holddown bolts.
C10702
Fig. 26 -- Fan Pulley Adjustments
Pulley and Drive Adjustment -- To obtain desired fan
speed, refer to the fan motor and drive data in Tables 8A--11D and adjust fan motor pulley as follows:
1. Remove belt from fan motor pulley after loosening motor from motor base.
2. Loosen setscrew in moveable flange of pulley. Screw moveable flange toward fixed flange to increase the fan speed and away from fixed flange to reduce speed. Before tightening setscrew, make certain that setscrew is over nearest flat surface of pulley hub (Fig. 26).
!
UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment damage.
Increasing fan speed produces a greater load on motor. Do not exceed rated capacity of motor.
Condensate Drains -- Keep condensate drains free of dirt and foreign matter.
Return--Air Filters -- Refer to Replacing Filters section for filter accessibility and removal. Replace with clean filters of the sizes listed in Tables 1A--1F.
S After draining as much water as possible from coils, add
sufficient antifreeze to prevent residual water in the coil from freezing.
CAUTION
524J
S Add a sufficient quantity of non--corrosive antifreeze to
the entire system to prevent all water within the system from freezing.
21
Coil Removal -- Remove unit panels and corner posts as required. Disconnect coil connections and remove fastening screws. Remove coil through end or side sections of unit.
Cleaning Cooling Coil -- Remove return--air filters. Remove any heavy dirt that may have accumulated on underside of coil. Coil can be cleaned more easily with a stiff brush, vacuum cleaner, or compressed air when coil is dry. If coil is wet or if water is to be used for cleaning, guard against splashing water on electrical components or damaging surrounding area. Clean coil baffles as applicable and check for tight fit to be sure air does not bypass coil.
Cleaning Insulation -- The insulation contains an immobilized antimicrobial agent that helps prevent the growth of bacteria and fungi. Clean the inner surface of the insulation according to the separate maintenance instructions shipped with the unit.
Replacing Filters -- Filters can be removed and installed
524J
from either side of the unit. Install new filters in units that have one fan as follows:
1. Remove the side access panel (retain screws).
2. Remove the filter retainer clip (see Fig. 27).
3. Remove old filters by lifting and tilting them out of the filter track. See Fig. 15 and 28. Use the factory-­supplied filter hook to slide filters within reach for re­moval. The filter hook is shipped inside the unit in the filter track
4. Reverse the procedure to install new filters.
SLIDE
Fig. 27 -- Remove Filter Retainer Clip
FILTER RETAINER CLIP
C10703
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment damage.
Do not operate unit without air filters.
C10704
Fig. 28 -- Filter Removal/Replacement
22
Table 8A -- Fan Motor Data, Standard Motor — English
UNIT
524J*25A 524J*25H
524J*28A 524J*30A
208/230--- 3 ---60 and 460 --- 3---60
Speed (rpm) 1745 1745 1745
Hp 5.0 7.5 10.0
Frame (NEMA) S184T S213T S215T
Shaft Dia (in.) 11/
8
13/
8
5 7 5 --- 3 --- 6 0
Speed (rpm) 1745 1755 1755
Hp 5.0 7.5 10.0
Frame (NEMA) 184T S213T D215T
Shaft Dia (in.) 11/
LEGEND NEMA — National Electrical Manufacturers Association
8
13/
8
Table 8B -- Fan Motor Data, Alternate Motor — English
UNIT
208/230--- 3 ---60 and 460 --- 3---60
Speed (rpm) 1745 1745 1745
Hp 7.5 10.0 10.0
Frame (NEMA) S213T S215T S215T
Shaft Dia (in.) 13/
5 7 5 --- 3 --- 6 0
Speed (rpm) 1755 1750 1750
Hp 7.5 10.0 10.0
Frame (NEMA) S213T D215T D215T
Shaft Dia (in.) 13/
LEGEND
NEMA — National Electrical Manufacturers Association
524J*25A 524J*25H
8
8
524J*28A 524J*30A
13/
8
13/
8
13/
13/
13/
13/
8
8
524J
8
8
23
Table 8C -- Fan Motor Data, Standard Motor — SI
524J
UNIT
208/230--- 3 ---60 and 460 --- 3---60
Speed (r/s) 29.08 29.08 29.08
Shaft kW 3.73 5.60 7.46
Frame (NEMA) S184T S213T S215T
Shaft Dia (mm) 28.6 34.9 34.9
5 7 5 --- 3 --- 6 0
Speed (r/s) 29.08 29.25 29.25
Shaft kW 3.73 5.60 7.46
Frame (NEMA) 184T S213T S215T
Shaft Dia (mm) 28.6 34.9 34.9
LEGEND
NEMA — National Electrical Manufacturers Association
524J*25A 524J*25H
524J*28A 524J*30A
Table 8D -- Fan MotorData, Alternate Motor — SI
UNIT
208/230--- 3 ---60 and 460 --- 3---60
Speed (r/s) 29.08 29.17 29.17
Shaft kW 5.60 7.46 7.46
Frame (NEMA) S213T S215T S215T
Shaft Dia (mm) 34.9 34.9 34.9
5 7 5 --- 3 --- 6 0
Speed (r/s) 29.25 29.17 29.17
Shaft kW 5.60 7.46 7.46
Frame (NEMA) S213T D215T D215T
Shaft Dia (mm) 34.9 34.9 34.9
524J*25A 524J*25H
524J*28A 524J*30A
LEGEND NEMA — National Electrical Manufacturers Association
24
Table 9A -- Standard Drive Data, 60 Hz — English
UNIT
524J*25A 524J*25H
524J*28A 524J*30A
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.) 3.7 ---4.7 4.3---5.3 4.3--- 5.3
Pulley Factory Setting Full Turns Open
3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 9.4 11.0 11.0
Pulley Bore (in.) 17/
16
Belt No. — Section 2—B 2—B
Belt Pitch (in.) 41.8
115/
16
(2) 42.8 (2) 43.8
115/
16
2—B
(2) 42.8 (2) 43.8
FAN SPEEDS (rpm)
Factory Setting 771 752 752
Range 679--- 863 682--- 841 674--- 831
Max Allowable Speed (rpm) 1200 1100 1100
Change per1/2Turn of Moveable Motor Pulley
15.3 13.1 13.1
Flange
MAX FULL TURNS FROM CLOSED POSITION
6 6 6
SHAFTS CENTER DISTANCE (in.) 9.12--- 10.99 6.67 --- 9.43 6.67 --- 9.43
Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
524J
Table 9B -- Medium--Static Drive Data, 60 Hz — English
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.) 4.3 ---5.3 4.3---5.3 4.3--- 5.3
Pulley Factory Setting Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.) 9.4 9.4 9.4
Pulley Bore (in.) 17/
Belt No. — Section 1—B 2—B
Belt Pitch (in.) 41.8
FAN SPEEDS (rpm)
Factory Setting 881 881 881
Range 798--- 984 798--- 984 798--- 984
Max Allowable Speed (rpm) 1200 1100 1100
Change per1/2Turn of Moveable Motor Pulley Flange
MAX FULL TURNS FROM CLOSED POSITION
SHAFTS CENTER DISTANCE (in.) 9.16--- 10.99 6.67 --- 9.43 6.67 --- 9.43
Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
524J*25A 524J*25H
524J*28A 524J*30A
3.0 3.0 3.0
16
115/
16
(2) 38.8 (2) 39.8
15.3 15.3 15.3
6 6 6
115/
16
2—B
(2) 38.8 (2) 39.8
25
Table 9C -- High--Static Drive Data, 60 Hz — English
524J
UNIT
524J*25A 524J*25H
524J*28A 524J*30A
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.) 4.3--- 5.3 4.3 --- 5.3 4.3 --- 5.3
Pulley Factory Setting Full Turns Open
3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 7.4 8.6 8.6
Pulley Bore (in.) 17/
16
115/
16
115/
16
Belt No. — Section 2—B 2—B 2—B
Belt Pitch (in.) 36.8 378 37.8
FAN SPEEDS (rpm)
Factory Setting 1118 1024 1024 Range 1014 --- 1200Ă
873--- 1075 873 ---1075
Max Allowable Speed (rpm) 1200 1100 1100
Change per1/2Turn of Moveable Motor Pulley
19.4 16.7 16.7
Flange
MAX FULL TURNS FROM CLOSED POSITION
6 6 6
SHAFTS CENTER DISTANCE (in.) 8.16-- -10.02 6.67 --- 9.43 6.67---9.43
It is possible to adjust drive so that fan speed exceeds maximum all owable. DO NOT exceed 1200 rpm.
Table 9D-- Standard Drive Data, 60 Hz — SI
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm) 94.0--- 119.4 109.2 ---134.6 109.2--- 134.6
Pulley Factory Setting Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm) 239 279 279
Pulley Bore (mm) 36.5 49.2 49.2
Belt No. — Section 2—B 2—B
Belt Pitch (mm) 1062
FAN SPEEDS (r/s)
Factory Setting 12.9 12.5 12.5
Range 11.3--- 14.4 11.4 ---14.0 11.2- -- 13.9
Max Allowable Speed (r/s) 20.0 18.3 18.3
Change per1/2Turn of Moveable Motor Pulley Flange
MAX FULL TURNS FROM CLOSED POSITION
SHAFTS CENTER DISTANCE (mm) 232 ---279 169--- 240 169 ---240
Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
524J*25A 524J*25H
524J*28A 524J*30A
3.0 3.0 3.0
(2) 1987 (2) 1113
0.255 0.218 0.218
6 6 6
2—B
(2) 1987 (2) 1113
26
Table 9E -- Medium--Static Drive Data, 60 Hz — SI
UNIT
524J*25A 524J*25H
524J*28A 524J*30A
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm) 109.2--- 134.6 109.2--- 134.6 109.2 --- 134.6
Pulley Factory Setting Full Turns Open
3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (mm) 239 239 239
Pulley Bore (mm) 36.5 49.2 49.2
Belt No. — Section 1—B 2—B
Belt Pitch (mm) 1062
(2) 986 (2) 1011
2—B
(2) 986 (2) 1011
FAN SPEEDS (r/s)
Factory Setting 14.7 14.7 14.7
Range 13.3 ---16.4 13.3--- 16.4 13.3 --- 16.4
Max Allowable Speed (r/s) 20.0 18.3 18.3
Change per1/2Turn of Moveable Motor Pulley
0.255 0.255 0.255
Flange
MAX FULL TURNS FROM CLOSED POSITION
6 6 6
SHAFTS CENTER DISTANCE (mm) 232--- 279 169 ---240 169- -- 240
Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
524J
Table 9F -- High--Static Drive Data, 60 Hz — SI
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm) 109.2 ---134.6 109.2--- 134.6 109.2---134.6
Pulley Factory Setting Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm) 188 203
Pulley Bore (mm) 36.5 49.2 49.2
Belt No. — Section 2—B 2—B 2—B
Belt Pitch (mm) 935 935 960
FAN SPEEDS (r/s)
Factory Setting 18.6 17.1 17.1
Range 16.9--- 20.0
Max Allowable Speed (r/s) 20.0 18.3 18.3
Change per1/2Turn of Moveable Motor Pulley Flange
MAX FULL TURNS FROM CLOSED POSITION
SHAFTS CENTER DISTANCE (mm) 207 ---255 169--- 240 169 ---240
It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s
524J*25A 524J*25H
524J*28A 524J*30A
3.0 3.0 3.0
14.6--- 17.9 14.6--- 7.9
0.323 0.278 0.278
6 6 6
203
27
Table 10A -- 524J Standard Fan Performance Data —
0.0--2.4 in. wg External Static Pressure — English
UNIT
524J*25A 524J*25H
524J*28A
524J
524J*30A
See Legend and Notes on page 36.
AIRFLOW
(Cfm)
6,000 532 1.25 569 1.39 639 1.69 711 2.06 781 2.48 846 2.93 905 3.60
7,000 608 1.93 641 2.09 702 2.42 763 2.08 824 3.23 885 3.71 943 4.23
8,000 686 2.83 716 3.01 770 3.38 823 3.77 876 4.21 930 4.70 983 5.24
9,000 764 3.97 791 4.18 841 4.59 888 5.02 935 5.47 982 5.96 1030 6.51
10,000 843 5.38 868 5.62 914 6.09 957 6.55 1000 7.02 1042 7.53 1084 8.08
7,500 456 1.29 490 1.47 556 1.85 621 2.25 678 2.64 729 3.06 778 3.60
8,750 521 1.98 551 2.18 608 2.61 664 3.07 720 3.53 770 3.99 816 4.45
10,000 587 2.88 614 3.11 664 3.59 714 4.09 763 4.62 812 5.15 857 5.68
11,250 653 4.03 678 4.29 724 4.82 768 5.37 812 5.95 856 6.54 899 7.14
12,500 720 5.46 743 5.75 785 6.33 825 6.93 865 7.55 904 8.20 944 8.86
15,000 829 8.84 850 9.19 888 9.88 924 10.57 958 11.27 991 11.99 1024 12.73
9,000 521 1.99 550 2.25 616 2.77 676 3.23 731 3.72 782 4.20 829 4.70
10,500 596 3.16 623 3.40 672 3.89 720 4.40 767 4.94 814 5.50 859 6.05
12,000 673 4.63 698 4.90 743 5.45 785 6.02 826 6.62 867 7.23 908 7.87
13,500 751 6.51 773 6.82 815 7.44 853 8.06 890 8.71 927 9.38 963 10.07
15,000 829 8.84 850 9.19 888 9.88 924 10.57 958 11.27 991 11.99 1024 12.73
EXTERNAL STATIC PRESSURE (in. wg)
0.0 0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
Table 10A -- 524J Standard Fan Performance Data —
0.0--2.4 in. wg External Static Pressure — English (cont)
UNIT
524J*25A
524J*25H
524J*28A
524J*30A
See Legend and Notes on page 36.
AIRFLOW
(Cfm)
6,000 954 3.83 1005 4.27 1052 4.72 1098 5.22 1142 5.67
7,000 990 4.74 1040 5.24 1090 5.80 1135 6.30 1176 6.84
8,000 1028 5.79 1078 6.38 1130 7.00 1173 7.60
9,000 1073 7.11 1120 7.72 1169 8.37
10,000 1126 8.75 1166 9.37
7,500 831 4.41 870 5.10 913 5.90 950 6.88 985 7.70
8,750 859 4.97 901 5.59 944 6.42 980 7.20 1020 8.10
10,000 900 6.20 939 6.74 976 7.33 1013 8.00 1050 8.82
11,250 941 7.73 980 8.32 1017 8.90 1052 9.51 1088 10.16
12,500 984 9.53 1022 10.19 1058 10.84 1093 11.49
15,000 1057 13.49 1090 14.28
9,000 866 5.20 899 5.85 950 6.65 989 7.38 1029 8.32 1077 9.74
10,500 902 6.60 942 7.14 980 7.70 1016 8.31 1051 8.99 1085 9.77
12,000 949 8.50 988 9.14 1026 9.76 1062 10.38 1095 11.01
13,500 1000 10.78 1036 11.49 1073 12.21
15,000 1057 13.49 1090 14.28
EXTERNAL STATIC PRESSURE (in. wg)
1.4 1.6 1.8 2.0 2.2 2.4
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
28
Table 10B -- 524J Standard Fan Performance Data —
0--600 kPa External Static Pressure — SI
UNIT
524J*25A
524J*25H
524J*28A
524J*30A
See Legend and Notes on page 36.
AIRFLOW
(L/s)
r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
2830 8.86 0.94 9.48 1.04 10.65 1.26 11.84 1.53 13.01 1.85 14.10 2.19 15.08 2.53
3300 10.14 1.44 10.69 1.56 11.70 1.81 12.71 2.08 13.73 2.41 14.74 2.77 15.71 3.15
3780 11.43 2.11 11.93 2.25 12.84 2.52 13.71 2.81 14.60 3.14 15.49 3.51 16.39 3.91
4250 12.74 2.96 13.19 3.12 14.02 3.43 14.81 3.74 15.59 4.08 16.37 4.45 17.17 4.85
4720 14.05 4.01 14.47 4.19 15.23 4.54 15.96 4.88 16.66 5.24 17.36 5.62 18.07 6.03
3540 7.60 0.96 8.16 1.09 9.27 1.38 10.34 1.68 11.30 1.97 12.15 2.28 12.97 2.68
4130 8.68 1.47 9.18 1.62 10.13 1.94 11.07 2.29 11.99 2.63 12.84 2.97 13.60 3.32
4720 9.78 2.15 10.23 2.32 11.07 2.67 11.89 3.05 12.72 3.45 13.53 3.84 14.29 4.23
5310 10.89 3.01 11.30 3.20 12.06 3.59 12.80 4.00 13.53 4.43 14.27 4.88 14.99 5.33
5900 12.00 4.07 12.38 4.29 13.09 4.72 13.75 5.17 14.41 5.63 15.07 6.11 15.74 6.61
4250 8.68 1.48 9.17 1.68 10.27 2.07 11.27 2.41 12.19 2.77 13.03 3.13 13.81 3.50
4960 9.93 2.35 10.38 2.53 11.21 2.90 11.99 3.28 12.78 3.68 13.56 4.10 14.32 4.51
5660 11.21 3.45 11.63 3.66 12.38 4.07 13.08 4.49 13.76 4.93 14.45 5.39 15.14 5.87
6370 12.51 4.85 12.89 5.08 13.58 5.54 14.22 6.01 14.83 6.49 15.44 6.99 16.05 7.51
7080 13.82 6.59 14.17 6.85 14.81 7.36 15.40 7.88 15.97 8.40 16.52 8.94 17.06 9.49
EXTERNAL STATIC PRESSURE (kPa)
0 50 100 150 200 250 300
524J
Table 10B -- 524J Standard Fan Performance Data —
0--600 kPa External Static Pressure — SI (cont)
UNIT
524J*25A 524J*25H
524J*28A
524J*30A
See Legend and Notes on page 36.
AIRFLOW
(L/s)
2830 15.90 2.86 16.75 3.18 17.53 3.52 18.30 3.89 19.03 4.23
3300 16.50 3.53 17.33 3.91 18.17 4.32 18.92 4.70 19.60 5.10
3780 17.13 4.32 17.97 4.76 18.83 5.22 19.55 5.67
4250 17.88 5.30 18.67 5.76 19.48 6.24
4720 18.77 6.52 19.43 6.99
3540 13.85 3.29 14.50 3.80 15.22 4.40 15.83 5.13 16.42 5.74
4130 14.31 3.71 15.01 4.17 15.74 4.79 16.33 5.37 17.00 6.04
4720 14.99 4.62 15.65 5.02 16.27 5.46 16.88 5.97 17.50 6.57
5310 15.68 5.77 16.34 6.20 16.95 6.64 17.53 7.09 18.09 7.58
5900 16.39 7.10 17.03 7.60 17.64 8.08 18.22 8.57
4250 14.43 3.88 14.98 4.36 15.84 4.96 16.48 5.50 17.16 6.21 17.96 7.26
4960 15.04 4.92 15.71 5.32 16.33 5.74 16.93 6.20 17.51 6.70 18.09 7.29
5660 15.81 6.34 16.47 6.81 17.10 7.28 17.69 7.74 18.26 8.21
6370 16.66 8.04 17.27 8.57 17.88 9.10
7080 17.61 10.06 18.16 10.64
EXTERNAL STATIC PRESSURE (kPa)
350 400 450 500 550 600
r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
29
Table 10C -- 524J High--Capacity Fan Performance Data —
0.0--2.4 in. wg External Static Pressure — English
UNIT
524J*25A 524J*25H
524J*28A
524J
524J*30A
See Legend and Notes on page 36.
AIRFLOW
(Cfm)
6,000 542 1.29 577 1042 646 1.72 716 2.09 785 2.51 849 2.95 907 3.40
7,000 620 1.99 652 2.15 711 2.48 771 2.85 831 3.28 890 3.76 947 4.27
8,000 700 2.92 728 3.10 781 3.46 833 3.85 885 4.29 938 4.78 990 5.32
9,000 781 4.10 806 4.30 854 4.71 900 5.13 946 5.58 993 6.08 1039 6.62
10,000 862 5.56 885 5.79 929 6.24 971 6.70 1012 7.18 1054 7.69 1096 8.24
7,500 476 1.39 510 1.58 579 1.99 644 2.40 701 2.81 752 3.29 804 3.96
8,750 545 2.14 574 2.35 633 2.81 691 3.29 747 3.77 797 4.25 842 4.76
10,000 615 3.12 641 3.36 692 3.87 743 4.41 794 4.96 843 5.51 888 6.05
11,250 685 4.37 709 4.64 754 5.20 800 5.79 845 6.40 891 7.02 935 7.64
12,500 756 5.92 778 6.22 819 6.83 860 7.47 901 8.14 942 8.83 983 9.52
9,000 539 2.18 569 2.39 626 2.85 683 3.34 739 3.83 791 4.32 837 4.82
10,500 620 3.37 646 3.62 695 4.13 744 4.68 793 5.25 842 5.83 888 6.41
12,000 701 4.94 724 5.22 769 5.80 811 6.40 854 7.04 897 7.69 940 8.36
13,500 783 6.95 804 7.27 844 7.91 883 8.57 920 9.26 958 9.97 996 10.71
15,000 865 9.45 884 9.81 921 10.52 956 11.24 991 11.98 1025 12.75 1059 13.54
0.0 0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
EXTERNAL STATIC PRESSURE (in. wg)
Table 10C -- 524J High--Capacity Fan Performance Data —
0.0--2.4 in. wg External Static Pressure — English (cont)
UNIT
524J*25A 524J*25H
524J*28A
524J*30A
See Legend and Notes on page 36.
AIRFLOW
(Cfm)
6,000 961 3.86 1011 4.31 1058 4.77 1104 5.24 1147 5.71
7,000 1000 4.79 1050 5.32 1097 5.85 1142 6.38 1184 6.91
8,000 1041 5.88 1090 6.47 1137 7.07 1181 7.67
9,000 1086 7.21 1133 7.82 1178 8.47
10,000 1138 8.83 1180 9.46
7,500 874 5.33 897 5.91 940 6.80 990 7.50
8,750 886 5.36 930 6.13 982 7.32 1020 8.10
10,000 930 6.60 969 7.20 1007 7.89 1045 8.71
11,250 976 8.25 1014 8.86 1051 9.49 1086 10.17
12,500 1023 10.20 1061 10.88 1097 11.56
9,000 881 5.37 923 6.03 967 6.89 1020 8.25
10,500 930 6.97 970 7.55 1008 8.17 1045 8.86
12,000 981 9.02 1021 9.67 1058 10.32 1094 10.97
13,500 1035 11.45 1072 12.20
15,000 1093 14.35
EXTERNAL STATIC PRESSURE (in. wg)
1.4 1.6 1.8 2.0 2.2 2.4
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
30
Table 10D -- 524J High--Capacity Fan Performance Data —
0--600 kPa External Static Pressure — SI
UNIT
524J*25A 524J*25H
524J*28A
524J*30A
See Legend and Notes on page 36.
AIRFLOW
(L/s)
r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
2830 9.03 0.96 9.62 1.06 10.77 1.29 11.94 1.56 13.08 1087 14.15 2.20 15.12 2.54
3330 10.34 1.48 10.86 1.60 11.85 1.85 12.84 2.12 13.85 2.45 14.84 2.80 15.78 3.18
3780 11.67 2.17 12.14 2.31 13.02 2.58 13.88 2.87 14.75 3.20 15.63 3.56 16.50 3.96
4250 13.01 3.05 13.44 3.21 14.23 3.51 15.00 3.82 15.77 4.16 16.54 4.53 17.32 4.94
4720 14.36 4.15 14.75 4.32 15.48 4.66 16.18 4.99 16.87 5.35 17.56 5.73 18.26 6.14
3540 7.94 1.04 8.51 1.18 9.65 1.48 10.73 1.79 11.68 2.10 12.53 2.46 13.40 2.95
4130 9.08 1.59 9.57 1.75 10.55 2.10 11.52 2.46 12.45 2.81 13.28 3.17 14.04 3.55
4720 10.24 2.33 10.68 2.51 11.53 2.88 12.39 3.29 13.24 3.70 14.05 4.11 14.80 4.51
5310 11.42 3.26 11.81 3.46 12.57 3.88 13.33 4.32 14.09 4.77 14.85 5.24 15.58 570
5900 12.60 4.42 12.96 4.64 13.65 5.09 14.33 5.57 15.01 6.07 15.40 6.58 16.38 7.10
4250 8.99 1.62 9.49 1.78 10.44 2.12 11.39 2.49 12.32 2.86 13.18 3.22 13.95 3.59
4960 10.33 2.51 10.77 2.70 11.59 3.08 12.40 3.49 13.22 3.92 14.03 4.35 14.79 4.78
5660 11.68 3.68 12.07 3.90 12.81 4.33 13.52 4.77 14.23 5.25 14.95 5.74 15.66 6.23
6370 13.04 5.18 13.40 5.42 14.07 5.90 14.71 6.39 15.34 6.90 15.97 7.44 16.61 7.98
7080 14.42 7.05 14.74 7.31 15.36 7.84 15.94 8.38 16.51 8.93 17.08 9.51 17.65 10.10
EXTERNAL STATIC PRESSURE (kPa)
0 50 100 150 200 250 300
524J
Table 10D -- 524J High--Capacity Fan Performance Data —
0--600 kPa External Static Pressure — SI (cont)
UNIT
524J*25A 524J*25H
524J*28A
524J*30A
See Legend and Notes on page 36.
AIRFLOW
(L/s)
2830 16.01 2.88 16.85 3.22 17.64 3.56 18.39 3.91 19.12 4.26
3300 16.67 3.57 17.50 3.96 18.28 4.36 19.03 4.75 19.73 5.15
3780 17.35 4.39 18.17 4.82 18.95 5.27 19.68 5.72
4250 18.11 5.37 18.88 5.83 19.63 6.31
4720 18.96 6.58 19.67 7.05
3540 14.57 3.97 14.95 4.41 15.67 5.07 16.50 5.59
4130 14.76 3.99 15.51 4.57 16.36 5.46 17.00 6.04
4720 15.49 4.92 16.15 5.37 16.78 5.88 17.42 6.50
5310 16.26 6.15 16.91 6.61 17.51 7.08 18.10 7.58
5900 17.04 7.61 17.68 8.11 18.28 8.62
4250 14.68 4.00 15.38 4.49 16.12 5.14 17.00 6.15
4960 15.51 5.20 16.17 5.63 16.80 6.09 17.41 6.61
5660 16.35 6.72 17.01 7.21 17.64 7.69 18.23 8.18
6370 17.24 8.54 17.87 9.10
7080 18.22 10.70
EXTERNAL STATIC PRESSURE (kPa)
350 400 450 500 550 600
r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
31
Legend and Notes for Tables 10A and 10C
Bhp --- Brake Horsepower Input to Fan ESP --- External Static Pressure
NOTES:
1. Maximum allowable f a n speed for size 25 units is 1200 rpm . Maximum allowable fan speed for size 28 and 30 units is 1100 rpm.
2. Fan performance is based on deduct ions for wet coil, clean 2-in. filters, and unit casing. See table at right for fact ory-s up pli ed filter pressure drop.
3. Refer to fan motor and drive tables for additional data.
LEGEND
Legend and Notes for Tables 10B and 10D
524J
ESP --- External Static Pressure
NOTES:
1. Maximumallowablefanspeedforsize25unitsis20r/s.Maximum allowable fan speed f or size 28 and 30 units is 18.3 r/s.
2.Fanperformanceisbasedondeductionsforwetcoil,clean51---mm filters, and unit casing. See table at right for factory-supplied filter pressure drop.
3. Refer to fan motor and drive tables for additional data.
LEGEND
FACTORY-SUPPLIED PRESSURE DROP — ENGLISH
UNIT
524J*25A 524J*25H
524J*28A
524J*30A
AIRFLOW
(Cfm)
6,000 0.12
8,000 0.19
10,000 0.26
7,500 0.15
10,000 0.22
12,500 0.30
9,000 0.19
12,000 0.29
15,000 0.40
PRESSURE DROP
(in. wg)
FACTORY-SUPPLIED PRESSURE DROP — SI
UNIT
524J*25A 524J*25H
524J*28A
524J*30A
AIRFLOW
(L/s)
2900 32
3800 47
4700 64
3500 36
4700 55
5900 76
4250 47
5650 71
7050 98
PRESSURE DROP
(Pa)
32
524J
33
524J
2011 Bryant Heating and Cooling Systems. D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Da te: 01/11
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
34
Catalog No: II524J---07
Replaces: II524J--- 05
START--UP CHECKLIST
(SPLIT SYSTEMS WITH 524J UNITS)
I. PRELIMINARY INFORMATION
OUTDOOR: MODEL NO. INDOOR: MODEL NO. SERIAL NO. SERIAL NO. ADDITIONAL ACCESSORIES
II. PRE--START--UP
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE:
WILL THIS DAMAGE PREVENT UNIT START--UP? (Y/N) CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N) HAS THE GROUND WIRE BEEN CONNECTED? (Y/N) HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N) ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N) HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED? (Y/N)
CONTROLS
ARE THERMOSTAT(S) & INDOOR FAN CONTROL WIRING CONNECTIONS MADE & CHECKED? (Y/N) ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N) HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS? (Y/N)
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N) ARE PROPER AIR FILTERS IN PLACE? (Y/N) HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N) DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)
PIPING
HAS FOAM SHIPPING BLOCK BEEN REMOVED FROM THE TXV (Thermostatic Expansion Valve)? (Y/N)
524J
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR UNIT (524J***A) OR OUTDOOR UINT (524J*25H) COILS AS REQUIRED? (Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, INDOOR COILS, TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS WITH A LEAK DETECTOR? (Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED) (Y/N) ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING CORRECT LEVELS? (Y/N)
35
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS: AB V AC V BC V (AB + AC + BC)/3 = AVERAGE VOLTAGE = V MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = V VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM! CALL LOCAL POWER COMPANY FOR ASSISTANCE.
III. START--UP
CHECK INDOOR FAN MOTOR SPEED AND RECORD.
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
524J
COMP A1 COMP B1
OIL PRESSURE
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGELINETEMP
ENTERING OUTDOOR UNIT AIR TEMP
LEAVING OUTDOOR UNIT AIR TEMP
INDOOR UNIT ENTERING AIR DB TEMP
INDOOR UNIT ENTERING AIR WB TEMP
INDOOR UNIT LEAVING AIR DB TEMP
INDOOR UNIT LEAVING AIR WB TEMP
COMPRESSOR AMPS (L1/L2/L3) ____/____/____ ____/____/____
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES, ARE THE SIGHT GLASSES SHOWING
1
OIL LEVEL AT
/8to1/3FULL? (Y/N)
NOTES:
2011 Bryant Heating and Cooling Systems. D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Da te: 01/11
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
36
Catalog No: II524J---07
Replaces: II524J--- 05
Loading...