Model 517G Fan-Coil Units are packaged air handlers that are
specifically designed for horizontal right-hand discharge for
split-system applications—both conventional air conditioning and
heat pump.
These fan-coil units are available In nominal coil sizes 042, 048,
and 060. Fan-Coil units with electric heaters and the accessory
heat packages for field-installation into the fan-coil units without
heaters are available in sizes ranging from 7.5 to 30KW.
Model 517G
Sizes 042, 048,
&060
FEATURES
WRAPAROUND FULLY INSULATED CABINET—One-piece
heavy-duty steel construction helps eliminate casing noise. Fully
insulated interior provides both thermal and acoustic isolation.
The cabinet exterior is finished with an attractive silver sage
enamel.
SPECIAL DESIGN FEATURES—Designed for horizontal-right
mounting attitude. Refrigerant and condensate connections are
provided on the front of the fan-coil units for ease of installation.
Knockouts are provided for optional horizontal suspension,
using suspension rods. Separate access panels for the coil sec
tion and blower/control section on the cabinet front make these
units totally serviceable from the front. A third front access panel
provides easy access to the permanent-type air filter furnished
with each unit.
DIRECT-DRIVE MULTISPEED, PSC, BLOWER MOTORS have
been carefully selected to minimize energy consumption while
providing the airflow to meet the requirements of a wide variety
of applications. A blower speed-tap-changer simplifies speed
changes. Blower and motor assembly is resiliently mounted to
minimize vibration, and slides out for easy servicing.
COMPUTER-DESIGNED INDOOR COILS provide for optimum
heat transfer and cooling and/or heat pump heating efficiency.
Flare refrigerant connections enable quick leak-proof connec
tions, using our precharged refrigerant tubing sets. All coils have
a condensate drain pan with primary and secondary connec
tions, and a holding charge of R-22 refrigerant.
CHECK-FLO-RATER—All coils have a Check-Flo-Rater for effi
cient and dependable refrigerant metering, and to eliminate the
potential service requirements of other metering devices.
Located external to the unit, the Check-Flo-Rater is readily
accessible for piston changeout or maintenance. For added sys
tem reliability, all coils have a liquid-tube strainer to help maintain
clean, unrestricted operation.
ELECTRIC HEAT PACKAGES are available either as factoryinstalled in the heating/cooling fan-coil units or as a field-instalied
accessory for the fan-coil units. The application flexibility of
these heaters is increased with the availability of single- and
three-phase power supply options. The 10-, 15-, and 20-KW
single-phase heaters are available with or without circuit break
ers for internal circuit protection. Sequencer control is used for
incremental energizing and deenergizing of the heater elements.
Field-installation of a heater into a unit has been made extremely
easy—simply slide in the heater, secure with three screws, and
plug-in three leads for blower motor control.
Form No. PDS517G.42.1B
¿OD FLARE--------3 LIQUID CONN
Vi
'32^
DIMENSIONAL DRAWING
517G SizeB
04222-3/4
048 & 06026-7/16
(FIELD POWER-COOL)
^2 DIA KO
/ (FIELD POWER-HEAT)
I-Di A KO
S LOW-VOLTAGE
517G DIMENSIONS (Inches)
DE
13-13/1621
17-9/3224-1/2
Shipping Weights (lbs)
042
.......................................
048 .........................................185*
060 ........................................
*Add heater weights shown in
heater table to determine ap
proximate weights of fan-coil
units with heaters.
REQUIRED CLEARANCES
Recommended service clearance from front
of unit..........................................................21
*See condensing unit or heat pump outdoor section PDS for cooling and/or heating capacity ratings with 517G Fan Coils.
tSee air delivery table in this PDS.
JKW values shown are nominal rated heater outputs at 240V and do not Include blower motor heat. Capacity values shown are calculated using KW
outputs at 208V/230V.
♦♦Single-phase 10-, 15-, or 20-KW electric heaters have the internal circuit protection options shown. Single-phase 12-, 15-, or 20-KW heaters are
wired for dual-circuit operation. The optionai single-circuit kit may be field-installed In units with a 12-, 15-, or 20-KW single-phase fused heater for
single-circuit operation.
ttCB = circuit breakers
ttUsed for right-angle refrigerant connections to the coil.
♦♦♦A 60-VA control transformer for units without factory-supplied heaters is supplied with the accessory electric heat package or control package. The
control package must be field-installed when a heater is not being used.
HWire sizes and lengths are based on copper conductor at 86 ° F (30 ° C) ambient temperature and ampacity shown in table. Insulation must be 90 ° C
on conductor used between the disconnect switch and the heater and at least 75 °C on the conductor used between the disconnect and the serv
ice panel. If other than copper conductor Is used, or if ambient temperature is above 86 ° F, determine wire size from ampacity shown and the Na
tional Electrical Code. Wire lengths shown are measured one way along the wire path between the disconnect and service panel for minimum 2%
voltage drop.
5170
N042015P042015 P042018
42,000
42,00042,00042,000
208/230-3
CBtr
6/4
39.8/43.8
18/20
None
_
35.0/38.541.4/45.4
—
46/50.4
_
—160/161
—50/6060/60100/110—
6/66/63/2
__
_
_
22.5/25
6/6
102/102
60
3&13
32.5x19.4
4.4
Check-Flo-Rater
76
3/4 MPT-3/4 FPT
10x9
20 X 21 X1
1/2
3 & DD(PSC)
3.8
P651-1066
P651-1068
—
——6/6
—
—
—
—
6060
- 1 - 1 - 1 301820-4001 1 - 1 - 1 301820-4001
N042020
208/230-3208/230-1
NoneFuses
75.8/83.8
54/5997/107
136/137
120/152—
39.8/43.8
-
_
—
—
—
—
—
—
36/40
52/57
45/50
8/6
115/115
81/126
60/60
45/50
60
CBtt
_
—
—
CERTIFICATION APPLIES ONLY WHEN
USED WITH PROPER COMPONENTS
AS USTED WITH ARI
SSC-67
SPECIFICATIONS—UNITS WITH ELECTRIC HEATER
MODEL
SIZE
1 RATINGS & PERFORMANCE
Nominal Capacity (Btuh)»
Nominal Airflow (Fts/Min)t1600
Electric Heating Output (KW)t
Electric Heating Capacity (MBtuh)t
1 ELECTRICAL
Unit Voits—Phase (60 Hz)
Operating Voltage Range
Internal Circuit Protection»»
N048075 IN048010
48,000
48,000
1600
7.510.0
19.2/23.5
25.6/31.3
208/230-1208/230-1
187-253187-253
None
None 1 CBtt
P048010N048012N048015P048015P048018
48,00048,000
16001600160016001600
10.012.0
25.6/31.3
208/230-3208/230-1208/230-1
187-253
NoneFuses
Single-Circuit Operation
Rated Load Amps
Minimum Ampacity for Wire Sizing
Minimum Wire Size»»»
Maximum Wire Length (Ft)»»»
Maximum Fuse Size (Amps)
31.8/34.8
40.8/44.5
8/8
92/93
45/45
40.8/44.8
52/57
6/6
112/113
60/60
25.6/27.648.2/52.8
33/35.7561.25/67
8/86/4
140/14495/15178/123
35/4070/70
Dual-Circuit Operation
Rated Load Amps LI & L2
L3&L4
—
——
Minimum Ampacity for Wire Sizing
LI &L2
Minimum Wire Size»»» LI. & L2
L3 & L4
L3&L4--
Maximum Wire Length (Ft)»»» LI & L2
L3&L4
Maximum Fuse Size (Amps) LI & L2—
L3&L4
Control Transformer—24V (VA)
——
—
—
—
———
—
——
—
6060
-
—
—
_
—
6060
INDOOR COIL
Rows & Fins Per Inch
Height X Width (In.)
Face Area (Sg Ft)
R-22 Refrigerant Metering Device
Piston ID Number
Condensate Drain Connection (Pri-Sec)
INDOOR BLOWER & MOTOR
Wheel Diameter x Width (In.)
Filter Size—Cleanable (In.)
Blower Motor HP
Blower Motor Speeds & Type
Rated Load Amps
»See condensing unit or heat pump outdoor section PDS for cooiing and/or heating capaoity ratings with 517G Fan Coils.
fSee air delivery table in this PDS.
tKW values shown are nominal rated heater outputs at 240V and do not include blower motor heat. Capacity values shown are calculated using KW
outputs at 208V/230V.
»»Single-phase 10-, 15-, or 20-KW electric heaters have the internal circuit protection options shown. Single-phase 12-, 15-, or 20-KW heaters are
wired for dual-oirouit operation. The optional single-circuit kit may be field-installed in units with a 12-, 15-, or 20-KW single-phase fused heater for
single-circuit operation.
ttCB = circuit breakers.
ttUsed for right-angle refrigerant connections to the coil.
»»»Wire sizes and lengths are based on copper conductor at 86 ° F (30 ° C) ambient temperature and ampacity shown in table. Insulation must be 90 ° C
on conductor used between the disconnect switch and the heater and at least 75 “ C on the conductor used between the disconnect and the serv
ice panel. If other than copper oonductor is used, or is ambient temperature is above 86 °F, determine wire size from ampacity shown and the Na
tional Electrical Code. Wire lengths shown are measured one way along the wire path between the disoonnect and service panel for minimum 2%
voltage drop.
517G
48,000
15.0
30.8/37.6
38.5/47.038.5/47.046.1/56.4
187-253187-253
Fuses
58.8/64.8
74.5/82
6/4
80/90
33.7/36.840.8/44.8
14.5/16
18/20
43.1/4752/57
18/20
22.5/25
8/66/6
12/1210/10
87/137
112/113
80/80102/102
45/50
20/20
60/60
25/25
606060
3&13
32.5x22.8
5.1
Check-Flo-Rater
82
3/4 MPT-3/4 FPT
10x9
20 X 25 X1
1/2
3 & DD(PSC)
4.8
P651-1066
P651-1068
48,000, -48,000
15.018.0
208/230-3208/230-3
187-253187-253
CBtt
NoneNone
36.0/39.542.4/46.4
46/50.4
_
—
156/157132/134
—
50/6060/60
6/66/6
54/59
—
——
——
_
—
——
■ —
—
—
SSC-68
SPECIFICATIONS—UNITS WITH ELECTRIC HEATER
I
MODEL
SIZE
1 RATINGS & PERFORMANCE
Nominal Capacity (Btuh)*
Nominal Airflow (FF/Min)t160016001600
Electric Heating Output (KW)t20.025.030.0
Electric Heating Capacity (MBtuh)f:51.3/62.764.1/78.4
1 ELECTRICAL ^
Unit Volts-Phase (60 Hz)208/230-1208/230-3 1 208/230-1 ■208/230-3 1 208/230-1B208/230-1208/230-1
Operating Voltage Range
Internal Circuit Protection**Fuses
Single-Circuit Operation
Rated Load Amps76.8/84.8
Minimum Ampacity for Wire Sizing97/107
Minimum Wire Size***3/2
Maximum Wire Length (Ft)***119/151—156/157154/194167/168
Maximum Fuse Size (Amps)100/110
Dual-Circuit Operation
Rated Load Amps L1 & L2
Minimum Ampacity for Wire Sizing
Minimum Wire Size*** L1 & L2
Maximum Wire Length (Ft)*** Lt &L2
Maximum Fuse Size (Amps) L1 & L260/60
Control Transformer—24V (VA)60606060
INDOOR COIL .
Rows & Fins Per Inch3&.13
Height X Width (In.)32.5 x22.8
Face Area (Sq Ft)5.15.1
R-22 Refrigerant Metering DeviceCheck-Flo-Rater
Piston ID Number8288
Condensate Drain Connection (Pri-Sec)3/4 MPT-3/4 FPT
INDOOR BLOWER & MOTOR
Wheel Diameter x Width (In.)10x911x9
Filter Size—Cleanable (In.)20x25 x1
Blower Motor HP1/2
Blower Motor Speeds & Type3 & DD(PSC)
Rated Load Amps4.8
*See condensing unit or heat pump section PDS for cooling and/or heating capacity ratings with 517G Fan Coils.
tSee air delivery table in this PDS.
$KW values shown are nominal rated heater outputs at 240V and do not include blower motor heat. Capacity values shown are calculated using KW
outputs at 208V/230V.
**Single-phase 10-, 15-, or 20-KW electric heaters have the internal circuit protection options shown. Single-phase 12-, 15-, or 20-KW heaters are
wired for dual-circuit operation. The optional single-circuit kit may be field-installed in units with a 12-, 15-, or 20-KW single-phase fused heater for
single-circuit operation.
ttCB = circuit breakers.
ttUsed for right-angle refrigerant connections to the coil.
***Wire sizes and lengths are based on copper conductor at 86 ° F (30 ° C) ambient temperature and ampacity shown in table. Insulation must be 90 ° C
on conductor used between the disconnect switch and thé heater and at least 75 °C on the conductor used between the disconnect and the serv
ice panel. If other than copper conductor is used, or if ambient temperature is above 86 ° F, determine wire size for ampacity shown and the National
Electric Code. Wire lengths shown are measured one way along the wire path between the disconnect and service panel for minimum 2%
voltage drop.
■Units with 25- and 30-KW electric heaters are wired for 3-phase operation. These units are field-convertible for single-phase operation by moving
two factory high-voltage wires.
*See condensing unit or heat pump outdoor section PDS for cooiing and/or heating capacity ratings with 517G Fan Coils.
tSee air delivery table in this PDS.
tKW values shown are nominal rated heater outputs at 240V and do not include blower motor heat. Capacity values shown are calculated using KW
outputs at 208V/230V.
♦♦Single-phase 10-, 15-, 20-KW electric heaters have the internal circuit protection options shown. Single-phase 12-, 15-, or 20-KW heaters are
wired for dual-circuit operation. The optional single-circuit kit may be field-installed in units with a 12-, 15-, or 20-KW single-phase fused heater for
single-circuit operation.
tfCB = circuit breakers.
ttUsed for right-angle refrigerant connections to the coil.
♦♦♦Wire sizes and lengths are based on copper conductor at 86 ° F (30 ° C) ambient temperature.and ampacity shown in table. Insulation must be 90 ° C
on conductor used between the disconnect switch and the heater and at least 75 °C on the conductor used between the disconnect and the serv
ice panel. If other than copper conductor is used, or if ambient temperature is above 86° F, determine wire size from ampacity shown and the Na
tional Electrical Code. Wire lengths shown are measured one way along the wire path between the disconnect and service panel for minimum 2%
voltage drop.
■Units with 25- and 30-KW electric heaters are wired for 3-phase operation. These units are field-convertible for single-phase operation by moving
two factory high-voltage wires.
517Б
N060020P060025I
60,00060,000
2000
25.0
208/230-3 1 208/230-1 ■
187-253
CBtt
_
187-253
Fuses
57.6/63.3
72/79.1
4/41/0
-
154/155
80/80
_
36/40
52/57
45/50
6/68/6
81/126
60/60
45/50
6060
4&12
32.5 X 22.8
5.1
Check-Flo-Rater
88
3/4 MPT-3/4 FPT
11x9
20x25 x1
3/4
3 & DD (PSC)
5.6
P651-1066
P651-1068
-
_
_
--
-
--
--
208/230-3 1 208/230-1 ■
95.6/105.6
68.0/74.9.113.6/125.6
119.5/13285/93.6
3/3
153/192165/166
125/15090/100
Р060030И
60,000
2000
30,0
76.9/86.0
187-253
Fuses
142/157
0/00 ■
161/203
150/175
_
-
_
-
-
-
60
SSC-70
517E
Size
042
(Without Heater)
042
(With Heater)
048
(Without Heater)
048
(With Heater)
060
(Without Heater)
060
(With Heater)
AIR DELIVERY (Ft^/Min) AT INDICATED EXTERNAL STATIC PRESSURE (With Filter)
♦Refer to the appropriate unit/factory-installed heater combinations in the specifications tabies in this PDS for the eiectrical appiication data for these
heat packages.
fAli heat packages are used with Modei 517G Fan Units.
^Operating voitage range is 187—253V.
**KW vaiues shown are nominai rated heater outputs at 240V. Capacity vaiues shown are caicuiated using nominai KW outputs.
ttThese heaters are fieid-convertibie for singie-phase operation by moving two factory high-voltage wires.
ttThese heaters are factory-supplied for dual-circuit operation. Optional single-circuit kit P/N 301820-4001 is available to provide for single-circuit
AutochangeoverP271-2782
Heat Pump Heating & Cooling
Without Electric Heater
Manual Changeover
Autochangeover
P271-3773
♦P271-34540.15-0.7t
♦P271-3453
Heat Pump Heating & Cooling
With Electric Heater
Manual Changeover
Autochangeover
♦P271-3454
♦P271-34530.15-0.7*
♦These thermostats have a Bryant logo—all others have a Honeywell logo,
tField-supplied relay P/N P283-1203 must be installed as shown in unit Instaiiation Instructions to energize the indoor blower during electric heat
ing operation.
JThe heat pump heating mode anticipator is fixed. Range shown is for adjustable electric heater second-stage heating anticipator.
♦♦These thermostats also have an emergency heat switch and indicator light.