Bryant 189BNV EVOLUTION, 288BNV EVOLUTION Service Manual

288BNV EVOLUTIONRV VARIABLE SPEED HEAT PUMP 189BNV EVOLUTION
R
V VARIABLE SPEED AIR CONDITIONER
WITH PURONr REFRIGERANT
Service Manual
TABLE OF CONTENTS
REFRIGERANT PIPING LENGTH LIMITATIONS 3...........................................................
ELECTRICAL 5..........................................................................................
MAJOR COMPONENTS 5--7...............................................................................
AOC Board 5..........................................................................................
Inverter 5..............................................................................................
Variable Speed Compressor 5..............................................................................
Electronic Expansion Valve (EXP) 6.........................................................................
Outdoor Fan Motor 6.....................................................................................
Pressure Transducer (SPT) 6...............................................................................
Pressure Equalizer Valve (PEV) 6...........................................................................
Outdoor Coil Thermistor (OCT) 6...........................................................................
Suction Thermistor (OST) 7...............................................................................
Discharge Thermistor (ODT) 7.............................................................................
Crankcase Heater 7......................................................................................
Time--Delays 7.........................................................................................
COMMUNICATION AND STATUS FUNCTION LIGHTS 7.....................................................
CHECK CHARGE 9.......................................................................................
TROUBLESHOOTING 9--13................................................................................
Service Tool 14-- 31......................................................................................
System Communication Failure 14..........................................................................
Model Plug 14..........................................................................................
Status Codes 14.........................................................................................
Variable Speed Compressor Winding Resistance 14.............................................................
Fan Motor 15...........................................................................................
Control Fault 15........................................................................................
Brown Out Protection 15..................................................................................
230v Line (Power Disconnect) Detection 15...................................................................
Pressure Switch Protection 15..............................................................................
Suction Pressure Transducer (SPT) 15........................................................................
Temperature Thermistors 16...............................................................................
Fault Code Action Table 18................................................................................
Variable Speed Drive LED Location and Description 25..........................................................
Compressor Power Harness Assembly Replacement 26..........................................................
Inverter Assembly with Shield Gasket Installation 28............................................................
Compressor Replacement 31...............................................................................
WIRING DIAGRAMS 34-- 35.................................................................................
REFRIGERATION SYSTEM 36-- 40..........................................................................
Refrigerant 36..........................................................................................
Compressor Oil 36.......................................................................................
Servicing Systems on Roofs With Synthetic Materials 36.........................................................
Brazing 36.............................................................................................
Service Valves and Pump down 36..........................................................................
Liquid Line Filter Drier 39................................................................................
Suction Line Filter Drier 39................................................................................
Thermostatic Expansion Valve (TXV) 39.....................................................................
Accumulator 40.........................................................................................
REFRIGERATION SYSTEM REPAIR 40.....................................................................
PAGE
UNIT IDENTIFICATION
The unit is identified using a 16 digit model number structure. It is recommended providing the complete 16 digit model number when ordering replacement parts to insure receiving the correct parts.
MODEL NUMBER NOMENCLATURE -- HEAT PUMP
12 3 4 5 6 78910 11 12 14
N N N A A/N N N N N A/N A/N N A
28 8 B N V 0360 0 0 A
Product
Famil y
2=HP 8=
Tier SEER Major
Evolution
8 = 18 SEER B=Puron N= 208---230 --- 1
Series
Series
Voltage V ariations Cooling Capacity Open Open Open Series
or 208/230 ---1
V=Variable
Speed
0=Not
Defined
0=Not
Defined
0=Not
DefinedA=Original
Series
MODEL NUMBER NOMENCLATURE -- AIR CONDITIONER
12 3 4 5 6 78910 11 12 14
N N N A A/N N N N N A/N A/N N A
18 9 B N V 0360 0 0 A
Product
Famil y
1=AC 8=
Tier SEER Major
Evolution
9 = 19 SEER B=Puron N= 208---230 --- 1
Series
Series
Voltage V ariations Cooling Capacity Open Open Open Series
or 208/230 ---1
V=Variable
Speed
0=Not
Defined
0=Not
Defined
0=Not
DefinedA=Original
Series
SERIAL NUMBER NOMENCLATURE
Week of Manufacture
01 06
E
00001
Serial Number
Year of Manufacture
Manufacturing Site E = Collierville TN X = Monterrey Mexico
2
REFRIGERANT PIPING LENGTH LIMITATIONS
Maximum Line Lengths:
The maximum allowable total equivalent length varies depending on the vertical separation. See the tables below for allowable lengths depending on whether the outdoor unit is on the same level, above or below the outdoor unit.
Maximum Line Lengths
MAXIMUM ACTUAL LENGTH
Units on equal level 100 (30.5) 100 (30.5) N/A
Outdoor unit ABOVE
indoor unit
Outdoor unit BELOW
indoor unit
{ Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
ft (m)
100 (30.5) 100 (30.5) 100 (30.5)
See Table ’Maximum Total Equivalent Length: Outdoor Unit BELOW Indoor Unit’
Maximum Total Equivalent Length{-- Outdoor Unit BELOW Indoor Unit
Liquid Line
Size
1 --- T o n 3/8 100* 100* 100* 100* 100* 100* 100* 2 --- T o n 3/8 100* 100* 100* 100* 100* 100* 100* 3 --- T o n 3/8 100* 100* 100* 100* 100* 100* 100* 4 --- T o n 3/8 100* 100* 100* 100* 100 100 --- --­5 --- T o n 3/8 100* 100* 100* 100* 100 100 --- ---
* Maximum actual length not to exceed 100 ft (30.5 m) { Total equivalent length accounts for losses due to elbows or fitting.
--- --- = o u t s i d e a c c e p t a b l e r a n g e
Diameter
w/ TXV
0 --- 2 0
(0 --- 6.1)
21---30
(6.4 --- 9.1)
HP with Puronr Refrigerant --- Maximum Total Equivalent Length{
Vertical Separation ft (m) Outdoor unit BELOW indoor unit;
31---40
(9.4 --- 12.2)
MAXIMUM EQUIVALENT LENGTH{
41---50
(12.5 --- 15.2)
ft (m)
51---60
(15.5 --- 18.3)
MAXIMUM VERTICAL SEPARA-
61---70
(18.6 --- 21.3)
TION ft (m)
71---80
(21.6 --- 24.4)
LONG LINE APPLICATIONS
Unit is approved for up to 100 ft (30.5 m) equivalent length and vertical separations shown above with no additional accessories.
Longer line set applications are not permitted.
3
SAFETY CONSIDERATIONS
Installation, service, and repair of these units should be attempted only by trained service technicians familiar with standard service instruction and training material.
All equipment should be installed in accordance with accepted practices and unit Installation Instructions, and in compliance with all national and local codes. Power should be turned off when servicing or repairing electrical components. Extreme caution should be observed when troubleshooting electrical components with power on. Observe all warning notices posted on equipment and in instructions or manuals.
!
ELECTRICAL HAZARD -- HIGH VOLTAGE!
Failure to follow this warning could result in personal injury or death.
Electrical components may hold charge. DO NOT remove control box cover for 2 minutes after power has been removed from unit.
PRIOR TO TOUCHING ELECTRICAL COMPONENTS:
Verify zero (0) voltage at inverter connections shown on inverter cover.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
!
WARNING
WARNING
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
Refrigeration systems contain refrigerant under pressure. Extreme caution should be observed when handling refrigerants. Wear safety glasses and gloves to prevent personal injury. During normal system operations, some components are hot and can cause burns. Rotating fan blades can cause personal injury. Appropriate safety considerations are posted throughout this manual where potentially dangerous techniques are addressed.
If you do not understand any of the warnings, contact your product distributor for better interpretation of the warnings.
GENERAL INFORMATION
The 288BNV & 189BNV split system heat pump and air conditioners features a new outdoor cabinet design that uses a four--sided coil design to minimize the unit footprint and provide the best heat exchange taking full advantage of the latest variable speed technology.
The heart of the system is the variable speed rotary compressor powered through the use of the variable speed drive (VSD) inverter control. Through the use of Puron refrigerant, compact ECM outdoor fan motor, VSD and variable speed scroll compressor, along with the new outdoor cabinet, the unit achieves a Seasonal Energy Efficiency Ratio (SEER) of up to 19 and up to 11 Heating Seasonal Performance Factor (HSPF).
To ensure ultimate comfort, these units should be combined with either the FE fan coil or Variable Speed Gas furnace controlled with a two wire communication Evolutionr Connext Control SYSTXBBITC01, SYSTXBBITW01 or SYSTXBBITN01 with version 11 software or newer. Version 12 software or newer required for model size 13. This combination will ensure achievement of comfort with the convenience of fingertip trouble shooting and diagnostic capability. These units can also use a standard, 2--stage or single--stage thermostat, for limited functionality. However, 1 --ton models will require the use of an Evolution Control.
!
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
Puronr (R--410A) systems operate at higher pressures than standard R --22 systems. Do not use R--22 service equipment or components on Puronr equipment. Ensure service equipment is rated for Puronr.
WARNING
4
ELECTRICAL
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Exercise extreme caution when working on any electrical components. Shut off all power to system prior to troubleshooting. Some troubleshooting techniques require power to remain on. In these instances, exercise extreme caution to avoid danger of electrical shock. ONLY TRAINED SERVICE PERSONNEL SHOULD PERFORM ELECTRICAL TROUBLESHOOTING.
Aluminum Wire
WARNING
MAJOR COMPONENTS
Application Operational Control Board (AOC)
!
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Aluminum wire may be used in the branch circuit (such as the circuit between the main and unit disconnect), but only copper wire may be used between the unit disconnect and the unit.
Whenever aluminum wire is used in branch circuit wiring with this unit, adhere to the following recommendations.
Connections must be made in accordance with the National Electrical Code (NEC), using connectors approved for aluminum wire. The connectors must be UL approved (marked Al/Cu with the UL symbol) for the application and wire size. The wire size selected must have a current capacity not less than that of the copper wire specified, and must not create a voltage drop between service panel and unit in excess of 2 of unit rated voltage. To prepare wire before installing connector, all aluminum wire must be “brush--scratched” and coated with a corrosion inhibitor such as Pentrox A. When it is suspected that connection will be exposed to moisture, it is very important to cover entire connection completely to prevent an electrochemical action that will cause connection to fail very quickly. Do not reduce effective size of wire, such as cutting off strands so that wire will fit a connector. Proper size connectors should be used. Check all factory and field electrical connections for tightness. This should also be done after unit has reached operating temperatures, especially if aluminum conductors are used.
CAUTION
Unit Electrical Power
Power wires from the unit’s disconnect should be routed through the power wiring hole provided at the bottom of the unit’s control box.
Connect the ground wire to the ground connection in the control box and connect the power wiring to the terminal block as shown on the wiring and Installation Instructions supplied with the unit. The unit does not require a contactor or outdoor unit transformer in order to operate.
A13361
Fig. 1 – AOC (Application Operational Control) Board
The AOC board is located in the lower right hand side of inverter tray. It’s functions include:
S Compressor speed control S Outdoor fan motor control S Reversing valve operation S Defrost operation S Crankcase heater operation S Pressure switch monitoring S Time Delays S Pressure Transducer measurements S PEV control (pressure equalizer valve) S Temperature measurements S EXV (Electronic Expansion Valve) operation control S Inverter communication and control
Inverter
The inverter is located inside the control box. This is an air--cooled device that communicates with the control board and drives the compressor and fan motor to the demanded RPM. The inverter is always powered with line voltage since no contactor is used. The inverter changes the line voltage to DC volts and then recreates 3 phase sine waves that vary in frequency to drive the compressor and fan motor at the desired RPM.
NOTE: The unit may be operated with an Evolution Connex Control or a standard 2--stage HP thermostat. However, 1 --ton models will require the use of an Evolution Control. Evolution Connex Control will utilize 5 stages of heating and cooling, while 2--stage HP thermostat will only allow 2 discrete stages of heating and cooling operation.
Variable Speed Compressor
This unit contains a variable speed rotary compressor that has a wide operating range. It operates on a variable 3 phase sine wave provided by the inverter. This compressor can only be operated by the specific inverter supplied with the unit.
5
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage and/or improper operation.
Do not attempt to apply line voltage directly to the compressor. This will destroy the compressor.
Electronic Expansion Valve (EXV)
This unit uses an electronic expansion valve for refrigerant metering in the heating mode. The control board drives the EXV to its proper position based on the operating mode and conditions. The Evolution Connex Control Service mode allows for manual opening and closing of the EXV for troubleshooting and pump down.
Outdoor Fan Motor
The compact ECM outdoor fan motor is a variable--speed brushless DC (BLDC) motor that operates at speeds from 400 to 1050 RPM. The motor is a 3--phase permanent magnet--type motor. Just like the compressor, this motor speed is determined by the inverter output frequency and amplitude.
Motor speed is controlled through the inverter board in the outdoor unit and no electronic module is attached. Motor speed is slowed as the building load decreases, maintaining the proper condensing temperature for both cooling and dehumidification. As the building load increases, the motor will increase speed until it is at maximum speed at the maximum building load.
At unit start--up, there is a slight delay and thrust motion of the fan motor/blade in the reverse direction, prior to ramping--up the fan assembly.
Pressure Transducer (SPT)
A 5 VDC output low pressure transducer that provides a 0--5 VDC data for interpretation by the control board for a 0 to 200 psig range of pressure at the suction tube. This interpreted pressure data is then intelligently used by the AOC control board for low pressure cut--out, loss of charge management, compressor protection, oil circulation management, lubrication management and EXV control.
Pressure Equalizer Valve (PEV)
At the end of every compressor operation (after the 3.5 minute Time Guard period), the equalizer valve opens for 150 seconds plus an additional 15 seconds of protection before allowing the compressor to start ramping up.
The PEV is located next to the suction and discharge of the compressor. The function of this valve is to prevent the compressor from starting with a high refrigerant pressure differential, thus helping the reliability of the compressor.
NOTE: A hissing sound may be heard during the equalization process. This is normal.
Outdoor Coil Thermistor (OCT)
The outdoor coil thermistor is a 10Kohm resistor used for multiple system operations. It provides the coil/liquid line temperature to the heat pump board and user interface. Low ambient operation, defrost initiation, defrost termination and assistance with OAT temperature measurement of some of the functions (see Fig.4) . The sensor must be securely mounted to the tube connecting the EXV and distributor. See Fig. 2 and Fig. 3 for proper placement. See Table 5 for proper resistances.
A14302
Fig. 2 – HP Outdoor Coil Thermistor (OCT) Attachment
Fig. 3 – AC Outdoor Coil Thermistor (OCT) Attachment
OAT Thermistor must be locked in place with spherical nib end f acing towards the f ront of the control box
Fig. 4 – OAT Thermistor Location (Bottom of Control Box)
(On Distributor Tube)
A14328
(On Distributor Tube)
A11142
6
Suction Thermistor (OST)
Suction Thermistor is used for assisting in EXV control and must be secured on the suction tube and aligned longitudinally to the vertical surface of the tube axis (see Fig. 5).
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
In order to minimize the ambient influence, make sure the thermistor curved surface hugs the pipe surface and is secured tight using the wire tie fished through the original slot insulating polymer body.
CAUTION
Crankcase Heater Operation
This unit has an internal crankcase heater that will be energized during the off cycle and is intelligently demanded by the system to prevent the compressor from being the coldest part of the system thus enhancing the reliability. The crankcase heater will function as needed any time the outdoor unit is powered. The indoor unit and UI do not need to be installed for the crankcase heater to operate properly.
The compressor windings will occasionally be energized during the OFF cycle (depending on the length of the OFF cycle) to start the stator heat operation, thus maintaining a sump temperature that is essential for compressor reliability. The compressor will not run during this process.
Time Delays
The unit time delays include:
S 3.5 minute time delay after last cycle, initial power up, return
from brown--out condition. To bypass this feature, momentarily short and release Forced Defrost pins.
S At the end of every compressor ON cycle, there will be 150
seconds of PEV open period for pressure equalization followed by 15 seconds of PEV Off period before the next compressor ON cycle. This delay cannot be bypassed as it helps compressor reliability.
S 15 second delay at termination of defrost before the auxiliary
heat is de--energized.
S See Table 6 for other delay information. S 10 minute sump warm--up delay. This delay is at the beginning
of each high voltage power up.
A14023
Fig. 5 – Suction Thermistor (OST) Attachment
(On Suction Tube)
Discharge Thermistor (ODT)
Discharge Thermistor is used for protection against over temperature of the compressor. The ODT is located on the compressor discharge stub--out (see Fig. 6).
A14024
Fig. 6 – Discharge Thermistor (ODT)
7
COMMUNICATION AND STATUS FUNCTION LIGHTS
Evolution Connex Control, Green Communications (COMM) Light
A green LED (COMM light) on the outdoor board (see Fig. 7 and
8) indicates successful communication with the other system products. The green LED will remain OFF until communication is established. Once a valid command is received, the green LED will turn ON continuously. If no communication is received within 2 minutes, the LED will be turned OFF until the next valid communication. The green LED will be turned off when using a standard 2--stage non--communicating heat pump thermostat.
Amber Status Light
Amber colored STATUS light indicates operation and error status. See Table 6 for definitions.
S Two minute time delay to return to standby operation from last
valid communication.
Defrost
This user interface (UI) offers 4 possible defrost interval times: 30, 60 and 90 minutes, or AUTO. The default is AUTO.
Defrost interval times: 30, 60, and 90 minutes or AUTO are selected by the Evolution Connex Control User Interface if using UI. The 90 minute selection will default to 60 minutes at ambient below 37 degrees. The UI setting will supersede the dip switch settings on the control board if not the same.
If using non--communicating thermostat, defrost intervals are set using dip switches on outdoor control board (see Fig. 7 and 8). AUTO defrosts adjusts the defrost interval time based on the last defrost time as follows:
S When defrost time <5 minutes, the next defrost interval=90
minutes. (outdoor temperature above 37_F)
S When defrost time 5--7 minutes, the next defrost interval=60
minutes.
S When defrost time >7 minutes, the next defrost interval=30
minutes. The control board accumulates compressor run time. As the accumulated run time approaches the selected defrost interval time, the control board monitors the coil temperature sensor for a defrost demand. If a defrost demand exists, a defrost cycle will be initiated at the end of the selected time interval. A defrost demand exists when the coil temperature is at or below 32_F(0_C) for 4 minutes during the interval. If the coil temperature does not reach 32_F (0_C) within the interval, the interval timer will be reset and start over.
S Upon initial power up the first defrost interval is defaulted to 30
minutes. Remaining intervals are at selected times.
S Defrost is only allowed to occur below 50_F(10_C) outdoor
ambient temperature. The defrost cycle is terminated as described below.
S When O AT is > 25_F(+3.89_C), defrost terminates if outdoor
coil temperature (OCT) > 60_F (+15.6_C). And a minimum of
one (1) minute defrost length.
S When OAT 25_F(+3.89_C), defrost will terminate if OCT is
>45_F(+4.4_C) and a minimum of 2 minutes defrost length.
S Or 10 minutes has passed.
At the defrost termination, the outdoor fan will turn on 10 seconds before the reversing valve switching.
NOTE: Compressor speed during defrost will go to defrost speed.
Fig. 7 – AOC Control Board for 1 and 2 Ton
A150034
Fig. 8 – AOC Control Board for 3, 4 and 5 Ton
A14021
8
CHECK CHARGE
Charge in CHARGING mode (communicating only)
Unit is factory charged for 15ft (4.57 m) of lineset. If any refrigerant charge adjustment is required due to the user inputted line set length, the UI will calculate and display the target subcooling and the amount of additional charge to be added. Therefore, the UI is your source of information for charging the system correctly. Refrigerant charge adjustment amount for adding or removing 0.6 oz/ft (17.74 g/m) of 3/8 liquid line above or below 15ft (4.57 m) respectively. Perform a final charge check only when in cooling and OD is between 65_F(18_C) and 100_F(38_C).
The use of a commercial charge metering device (restrictor) such as Imperial liquid low side charger model 535--C or Watsco ChargeFaster model CH200 is recommended when adding refrigerant to an operating system. This prevents potential damage of liquid slugging of the compressor and allows the subcooling to stabilize quicker.
Charging using the subcooling method optimizes charge volume and is preferred if possible. If the outdoor temperature is between 65_F -- 100_F (18.3_C -- 37.8_C) and indoor temperature is 70_F
-- 8 0 _F (21.1_C -- 26.7_C), the option to further adjust charge using “service valve subcool” will be available in the “charging mode selection” screen. If temperatures are outside of range, this option will be greyed out and not selectable. Inaccurate charging may result in nuisance fault codes.
Initial start--up can be performed using calculated charge only and once conditions are within range, the ”Service Valve Subcool” option will become selectable.
Once start is selected the system will operate in a preset mode until “done” is selected. Wait for required stabilization time then check subcooling at service valve.
Adjust charge as required to meet target service valve subcooling shown on screen --3/+0 degree. If any adjustment is necessary, add or remove the charge slowly (no greater than .5 lb per minute) and allow system to operate for 25 minutes to stabilize, before declaring a properly charged system.
Fig. 11 – Stabilization Time
A14575
Charging Non--Communicating Systems
Charging Procedure: Force system to operate in high stage
cooling by creating a large differential between room temperature and set point on thermostat. Use multi-- meter to verify that 24 VAC is present between C, Y1 /Y2 terminals at outdoor unit.
Factory charge amount is shown on unit rating plate for high stage. Target subcooling chart is provided on back of control box door see Fig. 12 -- 26 for example. To properly check or adjust charge, condition must be favorable for subcooling charging. Favorable conditions exists when outdoor temperature is between 65_F (18_C) and 100_F(38_C), and the indoor temperature is between 70_F(21_C) and 80_F(27_C). Follow the procedure below:
Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge by adding or removing 0.6 oz/ft (17.7 g/m) of 3/8 liquid line above or below 15ft (4.57 m) respectively.
For standard refrigerant line lengths (80ft/24.4 m or less), allow system to operate in cooling mode at least 25 minutes. If conditions are favorable, check system charge by subcooling method. If any adjustment is necessary, adjust charge slowly and allow system to operate for 25 minutes to stabilize before declaring a properly charged system.
If the indoor temperature is below 70°F (21.11°C), or the outdoor temperature is not in the favorable range, adjust charge for line set length above or below 15ft (4.57 m) and indoor fan coil /furnace coil per Table 1 and 2. Charge level should then be appropriate for
the system to achieve rated capacity. The charge level should then be checked at another time when the both indoor and outdoor temperatures are in a more favorable range.
NOTE: If the line length is beyond 80ft (24.38 m) or greater than 20ft (6.10 m) vertical separation see Long line guideline for special charging requirement.
Fig. 9 – Adjusting Charge Using Service Valve Subcool
Fig. 10 – Service Valve Subcool Target Value
A14573
A14574
9
Table 1—Required Charge Adjustment for Indoor Coil Model -- HP
Furnace or Fan Coil Model Number
13 24B 25 36 37 48 60
CNPV*18** --- / / / / / /
CAP**18** --- / / / / / /
CNP**24 --- / / / / / /
CNPV*19** --- / / / / / /
CAP**24 --- / / / / / /
CSPH*24 --- / / / / / /
CSPH* 30** / / / / / / /
F(E,V)4(A,B,C)NF002 +0.19 --- --- --- --- / /
CAP**30 / --- / / / / /
CNP**30 / --- / / / / /
CNP**36 / --- --- --- --- / /
F(E,V)4(A,B,C)N(B,F)003 / --- --- --- --- / /
CAP**36 / --- --- --- --- / /
CNP**42 / +.50 --- --- +.75 / /
CAP**42 / +.50 --- --- +.75 / /
CSPH*36 / / --- --- +.75 / /
CSPH* 42** / / +.75 +.7 5 +.75 / /
CNP**31* * / / +.75 +.75 +.75 / /
CNP**48 / / +.75 +.75 +.75 --- /
CSPH* 48** / / +.75 +.7 5 +1.00 --- /
CNP**37 / / / / / / /
CNP**43 / / / / / / /
CAP**48 / / / +.75 +1.00 --- /
CNP**60 / / / / +1.00 --- ---
CSPH*60 / / / / +1 .00 --- ---
F(E,V)4(A,B,C)N(B,F)005 / / +.75 +.75 +1.00 --- /
F(E,V)4(A,B,C)NB006 / / / / +1.00 +2.2 +1.00
CAP**60 / / / / / +2.2 +1.00
CNP**61 / / / / / / /
/ = Comb. not allowed
--- = No charge adjust for ID
Outdoor Model Size
Table 2—Required Charge Adjustment for Indoor Coil Model -- AC
Furnace or Fan Coil Model Number
CNPV*18** ---
CAP**18** ---
13 24B 25 36 37 48 49 60
/ / / / / / /
/ / / / / / /
CNP**24 --- --- ---
CNPV*19** ---
/ / / / / / /
CAP**24 --- --- ---
CSPH*24 --- --- ---
CSPH* 30**
/
--- ---
F(E,V)4(A,B,C)NF002 +0.19 --- --- ---
CAP**30
CNP**30
CNP**36
F(E,V)4(A,B,C)N(B,F)003
CAP**36
CNP**42
CAP**42
CSPH*36
CSPH* 42**
CNP**31* *
CNP**48
CSPH* 48**
CNP**37
CNP**43
CAP**48
CNP**60
CSPH*60
F(E,V)4(A,B,C)N(B,F)005
F(E,V)4(A,B,C)NB006
CAP**60
CNP**61
/ = Comb. not allowed
--- = No charge adjust for ID
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/ / /
/ / / /
/ / / /
/
/ / /
/ / / / /
/ / / / /
--- ---
--- ---
--- --- --- ---
--- --- --- ---
--- +.50 --- ---
+.50 +.50 --- +.75
+.50 +.50 --- +.75
+.50 +.50 --- +.75
+.50 +.50 +.75 +.75
+.50 +1.25 +.75 +.75
+.50 +1.25 +.75 +.75 --- ---
+.625 +1.25 +.75 +1.00 --- ---
+.625 +1.25 +.75 +1.00 --- ---
+.625 +1.25 +.75 +1.00 --- ---
+.625 +1.25 +.75 +1.00 --- +0.125
Outdoor Model Size
/ / / / /
/ / / / /
/ / / / /
/ / / / /
/ / / /
/ / / / /
/ / / / /
/ / /
/ / /
/ / /
/ / /
/ / /
/ / /
/ / /
/ / /
+.75 +1.00 --- ---
+1.00 --- +0.125 ---
+1.00 --- +0.125 ---
+.75 +1.00 +1.5 +.625 +1.00
+1.5 +.625 +1.00
+1.5 +.625 +1.00
/
/
/
/
/
/
10
Fig. 12 – Charging in Cooling Mode 288BNV013
Fig. 16 – Charging in Cooling Mode 288BNV037
Fig. 13 – Charging in Cooling Mode 288BNV024
Fig. 14 – Charging in Cooling Mode 288BNV025
Fig. 15 – Charging in Cooling Mode 288BNV036
Fig. 17 – Charging in Cooling Mode 288BNV048
Fig. 18 – Charging in Cooling Mode 288BNV060
11
Fig. 19 – Charging in Cooling Mode 189BNV013
Fig. 23 – Charging in Cooling Mode 189BNV037
Fig. 20 – Charging in Cooling Mode 189BNV024B
Fig. 21 – Charging in Cooling Mode 189BNV025
Fig. 24 – Charging in Cooling Mode 189BNV048
Fig. 25 – Charging in Cooling Mode 189BNV049
Fig. 22 – Charging in Cooling Mode 189BNV036
Fig. 26 – Charging in Cooling Mode 189BNV060
12
Heating Check Chart Procedure (See Fig.27 -- 33) (Communicating / Non--communicating Systems)
In heating mode, the required charging method is by weigh--in. On new installations or complete recharge, refer to the unit 0 and indoor fan coil / furnace coil per Table 1 for additional charge needed. Refrigerant charge adjustment amount for adding or removing 0.6 oz/ft (17.74 g/m) of 3/8 liquid line above or below 15ft (4.57 m) respectively.
Use the Defrost CHECKOUT mode to remove ice or frost from coil, if present, prior to checking the heating pressures.
To use the Heating Check Chart, the user interface (UI) must be in Refrigerant Charging mode selected from the Installation and Service screen. The Charging Mode Selection screen will show selections for Weigh-- In Charge Method or Heating Check Charge Method. Select Heating Check Charge Method. The Heating Check Charge method will only be displayed if the conditions are right for checking the charge in heating mode. When Heating Check Charge Method is selected, the system will operate by running in stage 5 with appropriate outdoor fan speed and indoor airflow. Upon completion of a countdown period for system stabilization, check refrigerant pressures for the appropriate ambient temperatures shown in Fig. 27 through 33 based the OD unit size.
To use the Heating Check Chart in non--communicating systems, operate system at Y1+Y2–high stage. These charts indicate whether a correct relationship exists between system operating pressure and air temperature entering indoor and outdoor units. If pressure and temperature do not match on chart, system refrigerant charge may not be correct. DO NOT USE CHART TO ADJUST
REFRIGERANT CHARGE. NOTE: High pressure is at vapor service valve. Add 12 psig if
high pressure is taken from liquid service valve. NOTE: When charging is necessary during heating season, charge
must be weighed in accordance with unit rating plate, (
±17.74 g/m). of 3/8--in. liquid--line above or below 15 ft (4.57
m), respectively.
±0.6 oz./ft
Fig. 29 – Heating Pressure Check Chart 288BNV025
Fig. 30 – Heating Pressure Check Chart 288BNV036
Fig. 27 – Heating Pressure Check Chart 288BNV013
Fig. 28 – Heating Pressure Check Chart 288BNV024
Fig. 31 – Heating Pressure Check Chart 288BNV037
Fig. 32 – Heating Pressure Check Chart 288BNV048
Fig. 33 – Heating Pressure Check Chart 288BNV060
13
Loading...
+ 29 hidden pages