Bryant 189BNV EVOLUTION, 288BNV EVOLUTION Service Manual

288BNV EVOLUTIONRV VARIABLE SPEED HEAT PUMP 189BNV EVOLUTION
R
V VARIABLE SPEED AIR CONDITIONER
WITH PURONr REFRIGERANT
Service Manual
TABLE OF CONTENTS
REFRIGERANT PIPING LENGTH LIMITATIONS 3...........................................................
ELECTRICAL 5..........................................................................................
MAJOR COMPONENTS 5--7...............................................................................
AOC Board 5..........................................................................................
Inverter 5..............................................................................................
Variable Speed Compressor 5..............................................................................
Electronic Expansion Valve (EXP) 6.........................................................................
Outdoor Fan Motor 6.....................................................................................
Pressure Transducer (SPT) 6...............................................................................
Pressure Equalizer Valve (PEV) 6...........................................................................
Outdoor Coil Thermistor (OCT) 6...........................................................................
Suction Thermistor (OST) 7...............................................................................
Discharge Thermistor (ODT) 7.............................................................................
Crankcase Heater 7......................................................................................
Time--Delays 7.........................................................................................
COMMUNICATION AND STATUS FUNCTION LIGHTS 7.....................................................
CHECK CHARGE 9.......................................................................................
TROUBLESHOOTING 9--13................................................................................
Service Tool 14-- 31......................................................................................
System Communication Failure 14..........................................................................
Model Plug 14..........................................................................................
Status Codes 14.........................................................................................
Variable Speed Compressor Winding Resistance 14.............................................................
Fan Motor 15...........................................................................................
Control Fault 15........................................................................................
Brown Out Protection 15..................................................................................
230v Line (Power Disconnect) Detection 15...................................................................
Pressure Switch Protection 15..............................................................................
Suction Pressure Transducer (SPT) 15........................................................................
Temperature Thermistors 16...............................................................................
Fault Code Action Table 18................................................................................
Variable Speed Drive LED Location and Description 25..........................................................
Compressor Power Harness Assembly Replacement 26..........................................................
Inverter Assembly with Shield Gasket Installation 28............................................................
Compressor Replacement 31...............................................................................
WIRING DIAGRAMS 34-- 35.................................................................................
REFRIGERATION SYSTEM 36-- 40..........................................................................
Refrigerant 36..........................................................................................
Compressor Oil 36.......................................................................................
Servicing Systems on Roofs With Synthetic Materials 36.........................................................
Brazing 36.............................................................................................
Service Valves and Pump down 36..........................................................................
Liquid Line Filter Drier 39................................................................................
Suction Line Filter Drier 39................................................................................
Thermostatic Expansion Valve (TXV) 39.....................................................................
Accumulator 40.........................................................................................
REFRIGERATION SYSTEM REPAIR 40.....................................................................
PAGE
UNIT IDENTIFICATION
The unit is identified using a 16 digit model number structure. It is recommended providing the complete 16 digit model number when ordering replacement parts to insure receiving the correct parts.
MODEL NUMBER NOMENCLATURE -- HEAT PUMP
12 3 4 5 6 78910 11 12 14
N N N A A/N N N N N A/N A/N N A
28 8 B N V 0360 0 0 A
Product
Famil y
2=HP 8=
Tier SEER Major
Evolution
8 = 18 SEER B=Puron N= 208---230 --- 1
Series
Series
Voltage V ariations Cooling Capacity Open Open Open Series
or 208/230 ---1
V=Variable
Speed
0=Not
Defined
0=Not
Defined
0=Not
DefinedA=Original
Series
MODEL NUMBER NOMENCLATURE -- AIR CONDITIONER
12 3 4 5 6 78910 11 12 14
N N N A A/N N N N N A/N A/N N A
18 9 B N V 0360 0 0 A
Product
Famil y
1=AC 8=
Tier SEER Major
Evolution
9 = 19 SEER B=Puron N= 208---230 --- 1
Series
Series
Voltage V ariations Cooling Capacity Open Open Open Series
or 208/230 ---1
V=Variable
Speed
0=Not
Defined
0=Not
Defined
0=Not
DefinedA=Original
Series
SERIAL NUMBER NOMENCLATURE
Week of Manufacture
01 06
E
00001
Serial Number
Year of Manufacture
Manufacturing Site E = Collierville TN X = Monterrey Mexico
2
REFRIGERANT PIPING LENGTH LIMITATIONS
Maximum Line Lengths:
The maximum allowable total equivalent length varies depending on the vertical separation. See the tables below for allowable lengths depending on whether the outdoor unit is on the same level, above or below the outdoor unit.
Maximum Line Lengths
MAXIMUM ACTUAL LENGTH
Units on equal level 100 (30.5) 100 (30.5) N/A
Outdoor unit ABOVE
indoor unit
Outdoor unit BELOW
indoor unit
{ Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
ft (m)
100 (30.5) 100 (30.5) 100 (30.5)
See Table ’Maximum Total Equivalent Length: Outdoor Unit BELOW Indoor Unit’
Maximum Total Equivalent Length{-- Outdoor Unit BELOW Indoor Unit
Liquid Line
Size
1 --- T o n 3/8 100* 100* 100* 100* 100* 100* 100* 2 --- T o n 3/8 100* 100* 100* 100* 100* 100* 100* 3 --- T o n 3/8 100* 100* 100* 100* 100* 100* 100* 4 --- T o n 3/8 100* 100* 100* 100* 100 100 --- --­5 --- T o n 3/8 100* 100* 100* 100* 100 100 --- ---
* Maximum actual length not to exceed 100 ft (30.5 m) { Total equivalent length accounts for losses due to elbows or fitting.
--- --- = o u t s i d e a c c e p t a b l e r a n g e
Diameter
w/ TXV
0 --- 2 0
(0 --- 6.1)
21---30
(6.4 --- 9.1)
HP with Puronr Refrigerant --- Maximum Total Equivalent Length{
Vertical Separation ft (m) Outdoor unit BELOW indoor unit;
31---40
(9.4 --- 12.2)
MAXIMUM EQUIVALENT LENGTH{
41---50
(12.5 --- 15.2)
ft (m)
51---60
(15.5 --- 18.3)
MAXIMUM VERTICAL SEPARA-
61---70
(18.6 --- 21.3)
TION ft (m)
71---80
(21.6 --- 24.4)
LONG LINE APPLICATIONS
Unit is approved for up to 100 ft (30.5 m) equivalent length and vertical separations shown above with no additional accessories.
Longer line set applications are not permitted.
3
SAFETY CONSIDERATIONS
Installation, service, and repair of these units should be attempted only by trained service technicians familiar with standard service instruction and training material.
All equipment should be installed in accordance with accepted practices and unit Installation Instructions, and in compliance with all national and local codes. Power should be turned off when servicing or repairing electrical components. Extreme caution should be observed when troubleshooting electrical components with power on. Observe all warning notices posted on equipment and in instructions or manuals.
!
ELECTRICAL HAZARD -- HIGH VOLTAGE!
Failure to follow this warning could result in personal injury or death.
Electrical components may hold charge. DO NOT remove control box cover for 2 minutes after power has been removed from unit.
PRIOR TO TOUCHING ELECTRICAL COMPONENTS:
Verify zero (0) voltage at inverter connections shown on inverter cover.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
!
WARNING
WARNING
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
Refrigeration systems contain refrigerant under pressure. Extreme caution should be observed when handling refrigerants. Wear safety glasses and gloves to prevent personal injury. During normal system operations, some components are hot and can cause burns. Rotating fan blades can cause personal injury. Appropriate safety considerations are posted throughout this manual where potentially dangerous techniques are addressed.
If you do not understand any of the warnings, contact your product distributor for better interpretation of the warnings.
GENERAL INFORMATION
The 288BNV & 189BNV split system heat pump and air conditioners features a new outdoor cabinet design that uses a four--sided coil design to minimize the unit footprint and provide the best heat exchange taking full advantage of the latest variable speed technology.
The heart of the system is the variable speed rotary compressor powered through the use of the variable speed drive (VSD) inverter control. Through the use of Puron refrigerant, compact ECM outdoor fan motor, VSD and variable speed scroll compressor, along with the new outdoor cabinet, the unit achieves a Seasonal Energy Efficiency Ratio (SEER) of up to 19 and up to 11 Heating Seasonal Performance Factor (HSPF).
To ensure ultimate comfort, these units should be combined with either the FE fan coil or Variable Speed Gas furnace controlled with a two wire communication Evolutionr Connext Control SYSTXBBITC01, SYSTXBBITW01 or SYSTXBBITN01 with version 11 software or newer. Version 12 software or newer required for model size 13. This combination will ensure achievement of comfort with the convenience of fingertip trouble shooting and diagnostic capability. These units can also use a standard, 2--stage or single--stage thermostat, for limited functionality. However, 1 --ton models will require the use of an Evolution Control.
!
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
Puronr (R--410A) systems operate at higher pressures than standard R --22 systems. Do not use R--22 service equipment or components on Puronr equipment. Ensure service equipment is rated for Puronr.
WARNING
4
ELECTRICAL
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Exercise extreme caution when working on any electrical components. Shut off all power to system prior to troubleshooting. Some troubleshooting techniques require power to remain on. In these instances, exercise extreme caution to avoid danger of electrical shock. ONLY TRAINED SERVICE PERSONNEL SHOULD PERFORM ELECTRICAL TROUBLESHOOTING.
Aluminum Wire
WARNING
MAJOR COMPONENTS
Application Operational Control Board (AOC)
!
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Aluminum wire may be used in the branch circuit (such as the circuit between the main and unit disconnect), but only copper wire may be used between the unit disconnect and the unit.
Whenever aluminum wire is used in branch circuit wiring with this unit, adhere to the following recommendations.
Connections must be made in accordance with the National Electrical Code (NEC), using connectors approved for aluminum wire. The connectors must be UL approved (marked Al/Cu with the UL symbol) for the application and wire size. The wire size selected must have a current capacity not less than that of the copper wire specified, and must not create a voltage drop between service panel and unit in excess of 2 of unit rated voltage. To prepare wire before installing connector, all aluminum wire must be “brush--scratched” and coated with a corrosion inhibitor such as Pentrox A. When it is suspected that connection will be exposed to moisture, it is very important to cover entire connection completely to prevent an electrochemical action that will cause connection to fail very quickly. Do not reduce effective size of wire, such as cutting off strands so that wire will fit a connector. Proper size connectors should be used. Check all factory and field electrical connections for tightness. This should also be done after unit has reached operating temperatures, especially if aluminum conductors are used.
CAUTION
Unit Electrical Power
Power wires from the unit’s disconnect should be routed through the power wiring hole provided at the bottom of the unit’s control box.
Connect the ground wire to the ground connection in the control box and connect the power wiring to the terminal block as shown on the wiring and Installation Instructions supplied with the unit. The unit does not require a contactor or outdoor unit transformer in order to operate.
A13361
Fig. 1 – AOC (Application Operational Control) Board
The AOC board is located in the lower right hand side of inverter tray. It’s functions include:
S Compressor speed control S Outdoor fan motor control S Reversing valve operation S Defrost operation S Crankcase heater operation S Pressure switch monitoring S Time Delays S Pressure Transducer measurements S PEV control (pressure equalizer valve) S Temperature measurements S EXV (Electronic Expansion Valve) operation control S Inverter communication and control
Inverter
The inverter is located inside the control box. This is an air--cooled device that communicates with the control board and drives the compressor and fan motor to the demanded RPM. The inverter is always powered with line voltage since no contactor is used. The inverter changes the line voltage to DC volts and then recreates 3 phase sine waves that vary in frequency to drive the compressor and fan motor at the desired RPM.
NOTE: The unit may be operated with an Evolution Connex Control or a standard 2--stage HP thermostat. However, 1 --ton models will require the use of an Evolution Control. Evolution Connex Control will utilize 5 stages of heating and cooling, while 2--stage HP thermostat will only allow 2 discrete stages of heating and cooling operation.
Variable Speed Compressor
This unit contains a variable speed rotary compressor that has a wide operating range. It operates on a variable 3 phase sine wave provided by the inverter. This compressor can only be operated by the specific inverter supplied with the unit.
5
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage and/or improper operation.
Do not attempt to apply line voltage directly to the compressor. This will destroy the compressor.
Electronic Expansion Valve (EXV)
This unit uses an electronic expansion valve for refrigerant metering in the heating mode. The control board drives the EXV to its proper position based on the operating mode and conditions. The Evolution Connex Control Service mode allows for manual opening and closing of the EXV for troubleshooting and pump down.
Outdoor Fan Motor
The compact ECM outdoor fan motor is a variable--speed brushless DC (BLDC) motor that operates at speeds from 400 to 1050 RPM. The motor is a 3--phase permanent magnet--type motor. Just like the compressor, this motor speed is determined by the inverter output frequency and amplitude.
Motor speed is controlled through the inverter board in the outdoor unit and no electronic module is attached. Motor speed is slowed as the building load decreases, maintaining the proper condensing temperature for both cooling and dehumidification. As the building load increases, the motor will increase speed until it is at maximum speed at the maximum building load.
At unit start--up, there is a slight delay and thrust motion of the fan motor/blade in the reverse direction, prior to ramping--up the fan assembly.
Pressure Transducer (SPT)
A 5 VDC output low pressure transducer that provides a 0--5 VDC data for interpretation by the control board for a 0 to 200 psig range of pressure at the suction tube. This interpreted pressure data is then intelligently used by the AOC control board for low pressure cut--out, loss of charge management, compressor protection, oil circulation management, lubrication management and EXV control.
Pressure Equalizer Valve (PEV)
At the end of every compressor operation (after the 3.5 minute Time Guard period), the equalizer valve opens for 150 seconds plus an additional 15 seconds of protection before allowing the compressor to start ramping up.
The PEV is located next to the suction and discharge of the compressor. The function of this valve is to prevent the compressor from starting with a high refrigerant pressure differential, thus helping the reliability of the compressor.
NOTE: A hissing sound may be heard during the equalization process. This is normal.
Outdoor Coil Thermistor (OCT)
The outdoor coil thermistor is a 10Kohm resistor used for multiple system operations. It provides the coil/liquid line temperature to the heat pump board and user interface. Low ambient operation, defrost initiation, defrost termination and assistance with OAT temperature measurement of some of the functions (see Fig.4) . The sensor must be securely mounted to the tube connecting the EXV and distributor. See Fig. 2 and Fig. 3 for proper placement. See Table 5 for proper resistances.
A14302
Fig. 2 – HP Outdoor Coil Thermistor (OCT) Attachment
Fig. 3 – AC Outdoor Coil Thermistor (OCT) Attachment
OAT Thermistor must be locked in place with spherical nib end f acing towards the f ront of the control box
Fig. 4 – OAT Thermistor Location (Bottom of Control Box)
(On Distributor Tube)
A14328
(On Distributor Tube)
A11142
6
Suction Thermistor (OST)
Suction Thermistor is used for assisting in EXV control and must be secured on the suction tube and aligned longitudinally to the vertical surface of the tube axis (see Fig. 5).
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
In order to minimize the ambient influence, make sure the thermistor curved surface hugs the pipe surface and is secured tight using the wire tie fished through the original slot insulating polymer body.
CAUTION
Crankcase Heater Operation
This unit has an internal crankcase heater that will be energized during the off cycle and is intelligently demanded by the system to prevent the compressor from being the coldest part of the system thus enhancing the reliability. The crankcase heater will function as needed any time the outdoor unit is powered. The indoor unit and UI do not need to be installed for the crankcase heater to operate properly.
The compressor windings will occasionally be energized during the OFF cycle (depending on the length of the OFF cycle) to start the stator heat operation, thus maintaining a sump temperature that is essential for compressor reliability. The compressor will not run during this process.
Time Delays
The unit time delays include:
S 3.5 minute time delay after last cycle, initial power up, return
from brown--out condition. To bypass this feature, momentarily short and release Forced Defrost pins.
S At the end of every compressor ON cycle, there will be 150
seconds of PEV open period for pressure equalization followed by 15 seconds of PEV Off period before the next compressor ON cycle. This delay cannot be bypassed as it helps compressor reliability.
S 15 second delay at termination of defrost before the auxiliary
heat is de--energized.
S See Table 6 for other delay information. S 10 minute sump warm--up delay. This delay is at the beginning
of each high voltage power up.
A14023
Fig. 5 – Suction Thermistor (OST) Attachment
(On Suction Tube)
Discharge Thermistor (ODT)
Discharge Thermistor is used for protection against over temperature of the compressor. The ODT is located on the compressor discharge stub--out (see Fig. 6).
A14024
Fig. 6 – Discharge Thermistor (ODT)
7
COMMUNICATION AND STATUS FUNCTION LIGHTS
Evolution Connex Control, Green Communications (COMM) Light
A green LED (COMM light) on the outdoor board (see Fig. 7 and
8) indicates successful communication with the other system products. The green LED will remain OFF until communication is established. Once a valid command is received, the green LED will turn ON continuously. If no communication is received within 2 minutes, the LED will be turned OFF until the next valid communication. The green LED will be turned off when using a standard 2--stage non--communicating heat pump thermostat.
Amber Status Light
Amber colored STATUS light indicates operation and error status. See Table 6 for definitions.
S Two minute time delay to return to standby operation from last
valid communication.
Defrost
This user interface (UI) offers 4 possible defrost interval times: 30, 60 and 90 minutes, or AUTO. The default is AUTO.
Defrost interval times: 30, 60, and 90 minutes or AUTO are selected by the Evolution Connex Control User Interface if using UI. The 90 minute selection will default to 60 minutes at ambient below 37 degrees. The UI setting will supersede the dip switch settings on the control board if not the same.
If using non--communicating thermostat, defrost intervals are set using dip switches on outdoor control board (see Fig. 7 and 8). AUTO defrosts adjusts the defrost interval time based on the last defrost time as follows:
S When defrost time <5 minutes, the next defrost interval=90
minutes. (outdoor temperature above 37_F)
S When defrost time 5--7 minutes, the next defrost interval=60
minutes.
S When defrost time >7 minutes, the next defrost interval=30
minutes. The control board accumulates compressor run time. As the accumulated run time approaches the selected defrost interval time, the control board monitors the coil temperature sensor for a defrost demand. If a defrost demand exists, a defrost cycle will be initiated at the end of the selected time interval. A defrost demand exists when the coil temperature is at or below 32_F(0_C) for 4 minutes during the interval. If the coil temperature does not reach 32_F (0_C) within the interval, the interval timer will be reset and start over.
S Upon initial power up the first defrost interval is defaulted to 30
minutes. Remaining intervals are at selected times.
S Defrost is only allowed to occur below 50_F(10_C) outdoor
ambient temperature. The defrost cycle is terminated as described below.
S When O AT is > 25_F(+3.89_C), defrost terminates if outdoor
coil temperature (OCT) > 60_F (+15.6_C). And a minimum of
one (1) minute defrost length.
S When OAT 25_F(+3.89_C), defrost will terminate if OCT is
>45_F(+4.4_C) and a minimum of 2 minutes defrost length.
S Or 10 minutes has passed.
At the defrost termination, the outdoor fan will turn on 10 seconds before the reversing valve switching.
NOTE: Compressor speed during defrost will go to defrost speed.
Fig. 7 – AOC Control Board for 1 and 2 Ton
A150034
Fig. 8 – AOC Control Board for 3, 4 and 5 Ton
A14021
8
CHECK CHARGE
Charge in CHARGING mode (communicating only)
Unit is factory charged for 15ft (4.57 m) of lineset. If any refrigerant charge adjustment is required due to the user inputted line set length, the UI will calculate and display the target subcooling and the amount of additional charge to be added. Therefore, the UI is your source of information for charging the system correctly. Refrigerant charge adjustment amount for adding or removing 0.6 oz/ft (17.74 g/m) of 3/8 liquid line above or below 15ft (4.57 m) respectively. Perform a final charge check only when in cooling and OD is between 65_F(18_C) and 100_F(38_C).
The use of a commercial charge metering device (restrictor) such as Imperial liquid low side charger model 535--C or Watsco ChargeFaster model CH200 is recommended when adding refrigerant to an operating system. This prevents potential damage of liquid slugging of the compressor and allows the subcooling to stabilize quicker.
Charging using the subcooling method optimizes charge volume and is preferred if possible. If the outdoor temperature is between 65_F -- 100_F (18.3_C -- 37.8_C) and indoor temperature is 70_F
-- 8 0 _F (21.1_C -- 26.7_C), the option to further adjust charge using “service valve subcool” will be available in the “charging mode selection” screen. If temperatures are outside of range, this option will be greyed out and not selectable. Inaccurate charging may result in nuisance fault codes.
Initial start--up can be performed using calculated charge only and once conditions are within range, the ”Service Valve Subcool” option will become selectable.
Once start is selected the system will operate in a preset mode until “done” is selected. Wait for required stabilization time then check subcooling at service valve.
Adjust charge as required to meet target service valve subcooling shown on screen --3/+0 degree. If any adjustment is necessary, add or remove the charge slowly (no greater than .5 lb per minute) and allow system to operate for 25 minutes to stabilize, before declaring a properly charged system.
Fig. 11 – Stabilization Time
A14575
Charging Non--Communicating Systems
Charging Procedure: Force system to operate in high stage
cooling by creating a large differential between room temperature and set point on thermostat. Use multi-- meter to verify that 24 VAC is present between C, Y1 /Y2 terminals at outdoor unit.
Factory charge amount is shown on unit rating plate for high stage. Target subcooling chart is provided on back of control box door see Fig. 12 -- 26 for example. To properly check or adjust charge, condition must be favorable for subcooling charging. Favorable conditions exists when outdoor temperature is between 65_F (18_C) and 100_F(38_C), and the indoor temperature is between 70_F(21_C) and 80_F(27_C). Follow the procedure below:
Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge by adding or removing 0.6 oz/ft (17.7 g/m) of 3/8 liquid line above or below 15ft (4.57 m) respectively.
For standard refrigerant line lengths (80ft/24.4 m or less), allow system to operate in cooling mode at least 25 minutes. If conditions are favorable, check system charge by subcooling method. If any adjustment is necessary, adjust charge slowly and allow system to operate for 25 minutes to stabilize before declaring a properly charged system.
If the indoor temperature is below 70°F (21.11°C), or the outdoor temperature is not in the favorable range, adjust charge for line set length above or below 15ft (4.57 m) and indoor fan coil /furnace coil per Table 1 and 2. Charge level should then be appropriate for
the system to achieve rated capacity. The charge level should then be checked at another time when the both indoor and outdoor temperatures are in a more favorable range.
NOTE: If the line length is beyond 80ft (24.38 m) or greater than 20ft (6.10 m) vertical separation see Long line guideline for special charging requirement.
Fig. 9 – Adjusting Charge Using Service Valve Subcool
Fig. 10 – Service Valve Subcool Target Value
A14573
A14574
9
Table 1—Required Charge Adjustment for Indoor Coil Model -- HP
Furnace or Fan Coil Model Number
13 24B 25 36 37 48 60
CNPV*18** --- / / / / / /
CAP**18** --- / / / / / /
CNP**24 --- / / / / / /
CNPV*19** --- / / / / / /
CAP**24 --- / / / / / /
CSPH*24 --- / / / / / /
CSPH* 30** / / / / / / /
F(E,V)4(A,B,C)NF002 +0.19 --- --- --- --- / /
CAP**30 / --- / / / / /
CNP**30 / --- / / / / /
CNP**36 / --- --- --- --- / /
F(E,V)4(A,B,C)N(B,F)003 / --- --- --- --- / /
CAP**36 / --- --- --- --- / /
CNP**42 / +.50 --- --- +.75 / /
CAP**42 / +.50 --- --- +.75 / /
CSPH*36 / / --- --- +.75 / /
CSPH* 42** / / +.75 +.7 5 +.75 / /
CNP**31* * / / +.75 +.75 +.75 / /
CNP**48 / / +.75 +.75 +.75 --- /
CSPH* 48** / / +.75 +.7 5 +1.00 --- /
CNP**37 / / / / / / /
CNP**43 / / / / / / /
CAP**48 / / / +.75 +1.00 --- /
CNP**60 / / / / +1.00 --- ---
CSPH*60 / / / / +1 .00 --- ---
F(E,V)4(A,B,C)N(B,F)005 / / +.75 +.75 +1.00 --- /
F(E,V)4(A,B,C)NB006 / / / / +1.00 +2.2 +1.00
CAP**60 / / / / / +2.2 +1.00
CNP**61 / / / / / / /
/ = Comb. not allowed
--- = No charge adjust for ID
Outdoor Model Size
Table 2—Required Charge Adjustment for Indoor Coil Model -- AC
Furnace or Fan Coil Model Number
CNPV*18** ---
CAP**18** ---
13 24B 25 36 37 48 49 60
/ / / / / / /
/ / / / / / /
CNP**24 --- --- ---
CNPV*19** ---
/ / / / / / /
CAP**24 --- --- ---
CSPH*24 --- --- ---
CSPH* 30**
/
--- ---
F(E,V)4(A,B,C)NF002 +0.19 --- --- ---
CAP**30
CNP**30
CNP**36
F(E,V)4(A,B,C)N(B,F)003
CAP**36
CNP**42
CAP**42
CSPH*36
CSPH* 42**
CNP**31* *
CNP**48
CSPH* 48**
CNP**37
CNP**43
CAP**48
CNP**60
CSPH*60
F(E,V)4(A,B,C)N(B,F)005
F(E,V)4(A,B,C)NB006
CAP**60
CNP**61
/ = Comb. not allowed
--- = No charge adjust for ID
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/ / /
/ / / /
/ / / /
/
/ / /
/ / / / /
/ / / / /
--- ---
--- ---
--- --- --- ---
--- --- --- ---
--- +.50 --- ---
+.50 +.50 --- +.75
+.50 +.50 --- +.75
+.50 +.50 --- +.75
+.50 +.50 +.75 +.75
+.50 +1.25 +.75 +.75
+.50 +1.25 +.75 +.75 --- ---
+.625 +1.25 +.75 +1.00 --- ---
+.625 +1.25 +.75 +1.00 --- ---
+.625 +1.25 +.75 +1.00 --- ---
+.625 +1.25 +.75 +1.00 --- +0.125
Outdoor Model Size
/ / / / /
/ / / / /
/ / / / /
/ / / / /
/ / / /
/ / / / /
/ / / / /
/ / /
/ / /
/ / /
/ / /
/ / /
/ / /
/ / /
/ / /
+.75 +1.00 --- ---
+1.00 --- +0.125 ---
+1.00 --- +0.125 ---
+.75 +1.00 +1.5 +.625 +1.00
+1.5 +.625 +1.00
+1.5 +.625 +1.00
/
/
/
/
/
/
10
Fig. 12 – Charging in Cooling Mode 288BNV013
Fig. 16 – Charging in Cooling Mode 288BNV037
Fig. 13 – Charging in Cooling Mode 288BNV024
Fig. 14 – Charging in Cooling Mode 288BNV025
Fig. 15 – Charging in Cooling Mode 288BNV036
Fig. 17 – Charging in Cooling Mode 288BNV048
Fig. 18 – Charging in Cooling Mode 288BNV060
11
Fig. 19 – Charging in Cooling Mode 189BNV013
Fig. 23 – Charging in Cooling Mode 189BNV037
Fig. 20 – Charging in Cooling Mode 189BNV024B
Fig. 21 – Charging in Cooling Mode 189BNV025
Fig. 24 – Charging in Cooling Mode 189BNV048
Fig. 25 – Charging in Cooling Mode 189BNV049
Fig. 22 – Charging in Cooling Mode 189BNV036
Fig. 26 – Charging in Cooling Mode 189BNV060
12
Heating Check Chart Procedure (See Fig.27 -- 33) (Communicating / Non--communicating Systems)
In heating mode, the required charging method is by weigh--in. On new installations or complete recharge, refer to the unit 0 and indoor fan coil / furnace coil per Table 1 for additional charge needed. Refrigerant charge adjustment amount for adding or removing 0.6 oz/ft (17.74 g/m) of 3/8 liquid line above or below 15ft (4.57 m) respectively.
Use the Defrost CHECKOUT mode to remove ice or frost from coil, if present, prior to checking the heating pressures.
To use the Heating Check Chart, the user interface (UI) must be in Refrigerant Charging mode selected from the Installation and Service screen. The Charging Mode Selection screen will show selections for Weigh-- In Charge Method or Heating Check Charge Method. Select Heating Check Charge Method. The Heating Check Charge method will only be displayed if the conditions are right for checking the charge in heating mode. When Heating Check Charge Method is selected, the system will operate by running in stage 5 with appropriate outdoor fan speed and indoor airflow. Upon completion of a countdown period for system stabilization, check refrigerant pressures for the appropriate ambient temperatures shown in Fig. 27 through 33 based the OD unit size.
To use the Heating Check Chart in non--communicating systems, operate system at Y1+Y2–high stage. These charts indicate whether a correct relationship exists between system operating pressure and air temperature entering indoor and outdoor units. If pressure and temperature do not match on chart, system refrigerant charge may not be correct. DO NOT USE CHART TO ADJUST
REFRIGERANT CHARGE. NOTE: High pressure is at vapor service valve. Add 12 psig if
high pressure is taken from liquid service valve. NOTE: When charging is necessary during heating season, charge
must be weighed in accordance with unit rating plate, (
±17.74 g/m). of 3/8--in. liquid--line above or below 15 ft (4.57
m), respectively.
±0.6 oz./ft
Fig. 29 – Heating Pressure Check Chart 288BNV025
Fig. 30 – Heating Pressure Check Chart 288BNV036
Fig. 27 – Heating Pressure Check Chart 288BNV013
Fig. 28 – Heating Pressure Check Chart 288BNV024
Fig. 31 – Heating Pressure Check Chart 288BNV037
Fig. 32 – Heating Pressure Check Chart 288BNV048
Fig. 33 – Heating Pressure Check Chart 288BNV060
13
Service Tool
TROUBLESHOOTING
Table 3—Factory Supplied Model Plug Information
288BNV
13 HK70EZ029 11K 220K
24B HK70EZ009 5.1K 91K
25 HK70EZ001 5.1K 11K 36 HK70EZ002 5.1K 18K 37 HK70EZ026 11K 120K 48 HK70EZ003 5.1K 24K 60 HK70EZ004 5.1K 33K
MODEL PLUG
NUMBER
P i n s 1 --- 4 Pins 2 ---3
Fig. 34 – Service Tool Connection
A150062
When working on the outdoor unit of a split system, the technician would usually need to repeatedly walk between the indoor wall control and the unit outside. To save time, the communicating controls offer a service tool feature.
By wiring the service tool into the AOC board and powering it with an external adapter, the technician can have a wall control capable of running the system right at the outdoor unit.
To use a service tool, connect the A and B communication bus wires from this second communicating control to the terminals marked A and B on the terminal strip located in the bottom left corner of the AOC board (see Fig. 34). But instead of connecting the wires on the service tool to the terminals marked C and D, connect the C and D wires from the service tool to the 24V and C on ST1 as shown in Fig. 34.
When the service tool is connected and powered up, the communicating controls inside the home will ”go to sleep” and let the service tool take control of the system. In this manner, the service technician can run the diagnostic checkouts right at the outdoor unit using the service tool.
After the checkouts are completed and it is no longer necessary to use the service tool, remove it from the communicating controls and the indoor communicating controls will regain control in about two minutes.
Systems Communication Failure
If communication is lost with the User Interface (UI), the control will flash the appropriate fault code (see Table 6). Check the wiring to the User Interface and the indoor and outdoor units and power.
Model Plug
Each control board contains a model plug. The correct model plug must be installed for the system to operate properly (see Table 3).
The model plug is used to identify the type and size of unit to the control.
On new units, the model and serial numbers are inputted into the AOC board’s memory at the factory. If a model plug is lost or missing at initial installation, the unit will operate according to the information input at the factory and the appropriate error code will flash temporarily. An RCD replacement AOC board contains no model and serial information. If the factory control board fails, the model plug must be transferred from the original board to the replacement board for the unit to operate.
When installing heat pump with older fan coils, a model plug change may be required.
NOTE: The model plug takes priority over factory model information input at the factory. If the model plug is removed after initial power up, the unit will operate according to the last valid model plug installed, and flash the appropriate fault code temporarily.
189BNV
13 HK70EZ028 11K 180K
24B HK70EZ010 5.1K 120K
25 HK70EZ011 5.1K 150K 36 HK70EZ012 5.1K 180K 37 HK70EZ025 11K 91K 48 HK70EZ013 5.1K 220K 49 HK70EZ027 11K 150K 60 HK70EZ014 5.1K 270K
MODEL PLUG
NUMBER
P i n s 1 --- 4 Pins 2 ---3
Status Codes
!
ATTENTION
Unit may occasionally become unresponsive due to certain combinations of previous fault codes. There may not be anything wrong with the unit or components. The unit may require a high voltage power cycling for at least 2 minutes or longer to clear the condition. If the condition persists, conduct further troubleshooting per Service Manual.
Table 6 shows the status codes flashed by the amber status light. Most system problems can be diagnosed by reading the status code as flashed by the amber status light on the control board.
The codes are flashed by a series of short and long flashes of the status light. The short flashes indicate the first digit in the status code, followed by long flashes indicating the second digit of the error code.
The short flash is 0.25 seconds ON and the long flash is 1.0 second ON. Time between flashes is 0.25 seconds. Time between short flash and first long flash is 1.0 second. Time between code repeating is 2.5 seconds with LED OFF.
Codes are easily read from user interface (UI) EXAMPLE: 3 short flashes followed by 2 long flashes indicates a 32 code.
Table 6 shows this to be low pressure switch open.
Variable Speed Compressor Winding Resistance
This compressor operates with 3--phase variable frequency PWM variable voltage. For troubleshooting certain fault codes related to compressor resistances, follow these steps:
1. Disconnect compressor power leads from the inverter MOC terminals, U (YEL), V (RED), and W (BLK).
2. Measure the resistance between YEL to RED, YEL to BLK, and RED to BLK and compare to Table 4 values. Each resistance set should be equal.
3. Measure the resistance to ground for each lead.
4. If the resistances check out, reconnect power leads to appropriate terminal.
5. If the resistances appear to be abnormal, it will be necessary to measure the resistance at the compressor fusite terminals.
6. During the removal of the compressor fusite cap, do not re­move the RTV sealant. Remove the harness plug, measure the resistances, and compare to Table 4.
7. Special care will need to be taken with the replacement of the compressor fusite cap. Make sure the two holes in the compressor fusite terminal box are still full of RTV sealant before the cap is reinstalled. The factory RTV can be reused
14
as long as none of it has been removed during the cap removal.
8. Reinstall compressor sound blanket making sure discharge thermistor and compressor power harness are routed as they were from the factory
Table 4—Variable Speed Compressor Resistance
(winding resistance at 70_F20_F)
WINDING
Between
terminals
Between
terminal &
ground
!
MODEL 288BNV / 189BNV (OHMs)
13, 24B 25 36 37, 48 49, 60
1.13 .59 .59 .37 .24
>1 mega
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage and/or improper operation.
Do not use Meggar for measuring the winding resistance.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage and/or improper operation.
To maintain water integrity of the compressor fusite terminal box, the two holes in outer ring need to be full of RTV sealant.
Fan Motor
If verification of proper operation is required for the fan motor used in this unit, follow these steps:
1. Disconnect fan motor connector from control board.
2. Measure resistance between any 2 of the 3 leads present.
3. Compare measurement to values below
Fan Motor Resistance
Unit Size Resistance (Ohms)
13, 24B 21.2
25, 36, 37, 48, 49 (AC), 60 11.1
Control Fault
If the outdoor unit control board has failed, the control will flash the appropriate fault code (see Table 6). The control board should be replaced.
Brown--Out Protection
If the line voltage is less than 187V for at least 4 seconds, the Compressor and OD fan goes to 0 rpm. Compressor and fan operation are not allowed until voltage is a minimum of 190V. The control will flash the appropriate fault code (see Table 6).
230V Line (Power Disconnect) Detection
The control board senses the presence of absence of 230V through inverter feedback. Voltage should present at all times when system is in service regardless if system is running or standby. If there is no 230V at the inverter when the indoor unit is powered with a cooling or heating demand, the appropriate fault code is displayed on UI (communicating only – see Fig. 38). If system is configured with conventional heat pump thermostat (non--communicating), no fault code will be displayed on AOC board, nor will any status LEDs be lit. Use multimeter to check for the presence of 230V in this situation.
High Pressure Switch Protection
The outdoor unit is equipped with a high pressure switch. If the control senses the opening of a high pressure switch (open 600+/--5 psig, close 470+/--10 psig @77_F), it will respond as follows:
1. Display the appropriate fault code (see Table. 6).
2. After a 6 minute delay, if there is a call for cooling or heat­ing and HPS is reset, the PEV opens for 150 seconds to equalize system pressures. The compressor and fan will then ramp to the next lower stage of operation until demand is satisfied. The staging down and resetting to the highest stage will end after 2 hours of accumulated operation with­out further HPS trips.
3. A system malfunction will occur after repeated HPS faults and the stages have reached the lowest level. This could take five consecutive HPS trips if the first occurred in stage 5demandor1HPStripifinstage1demand.
4. In the event of a high--pressure switch trip or high--pressure lockout, check the refrigerant charge, outdoor fan operation, and outdoor coil (in cooling) for airflow restrictions, or in­door airflow in heating.
Low Pressure Protection
The outdoor unit is equipped with low pressure transducer. If the control senses a low pressure per the table below, it will respond as follows:
Cooling
Low
Pressure
3 minute
operation
<= 33 >43 <= 15 <= 33 >35
Cool
mode
resume
operation
begins
Low
Pressure
(No Op­eration)
Heating Low
Pressure
5 minute
operation
Heat
mode
resume
operation
begins
1. Display the appropriate error code on the status LED (see Tab le 6).
2. If a demand persists after the 6--minute delay and the pressure has reached the operation level, then resume operation. Reset the 6 minute timer, clear the displayed error code and communicate cleared error to the User Interface. Status LED reverts to operation code display.
3. If a demand persists after the 6--minute delay but the pressure has not recovered, turn off the ODF. If the pressure recovers any time after the 6 minute delay, then resume operation. Reset the 6 minute timer, clear the displayed error code and communicate cleared error to the User Interface. Status LED reverts to operation code display.
4. If a pressure drops below the NO-- operation level three (3) consecutive times, then lock out operation for 4 hours and flash the appropriate error code and communicate lockout status to the User Interface. The trip counter will reset to zero if 15 minutes of successful operation occurs before the
rd
3
trip is recorded. Record the low pressure lockout in the
historical data.
5. In the event of a low pressure trip or low pressure lockout, check the refrigerant charge and indoor airflow (cooling) and outdoor fan operation and outdoor coil in heating.
Suction Pressure Transducer (SPT)
If the accuracy of the transducer is questioned, the technician can check it while it is attached to the AOC board. Connect a gage manifold to the suction valve gage port fitting.
At the AOC board, with the wire harness receptacle exposing a portion of the three pins on the AOC board, a DC voltmeter can read the DC voltage between ground and supply (input) terminal. Ensure that the input voltage is 5 VDC. Next, read the DC voltage across the ground and output terminal. Record the output voltage.
The suction pressure that the pressure transducer is reading can be calculated by taking the output voltage and subtracting 0.5 from it then taking that difference and multiplying it by 50. Pressure (psig) = 50.0 x (DCV out -- 0.5). For example, if the measured voltage is 3.0 VDC: 50 X (3.0 -- 0.5) -- 50 X 2.5 = 125 psig. See Fig. 35.
15
0
1
2
3
4
5
6
0 25 50 75 100 125 150 175 200 225
Output Voltage (V)
Pressure - Sealed Gauge (psi)
Fig. 35 – Suction Pressure Transducer (SPT)
0
50
100
150
200
250
300
350
400
450
020406080100120
RESISTANCE (KOHMS)
TEMPERATURE (°°F)
50K THERMISTOR
A12035
Output Funtion Graph
Temperature Thermistors
Thermistors are electronic devices which sense temperature. As the temperature increases, the resistance decreases. 10Kohm thermistors are used to sense outdoor air temperature (OAT), coil temperature (OCT) and the suction line temperature (OST) located between the reversing valve and the accumulator. A 50Kohm thermistor is used to sense discharge temperature (ODT).
Refer to Table 5 and Fig. 36 and 37 for resistance values versus temperature.
Table 5—10K/50Kohm Resistance Values vs Temperature
10Kohm
TEMPERATURE RESISTANCE (ohms)
25.0 (77.0) 10.0 + / --- 2.3%
0.0 (32.0) 32.6 + / --- 3.2%
-28.0 (-18.4) 85.5 + / --- 3.4%
125.0 (257.0) 1.7 + / --- 1.6%
75.0 (167.0) 7.40 + / --- 2.0%
25.0 (77.0) 50.0 + / --- 2.3%
_C(_F)
50Kohm
THERMISTOR CURVE
90
80
70
60
50
40
30
20
RESISTANCE (KOHMS)
10
0
0 20 40 60 80 100 120
Fig. 36 – 10K Thermistor Resistance Versus Temperature
TEMPERATURE (DEG. F)
A91431
Check to ensure thermistors are mounted properly (See Fig. 2, 3, 4, 5 and 6).
Thermistor Sensor Comparison
The control continuously monitors and compares the outdoor air temperature sensor and outdoor coil temperature sensor to ensure proper operating conditions. The comparison is:
S In cooling if the outdoor air sensor indicates 10_F( 5.6_C)
warmer than the coil sensor (or) the outdoor air sensor indicates 25_F( 15_C) cooler than the coil sensor, the sensors are out of range.
S In heating if the outdoor air sensor indicates 35_F( 19.4_C)
warmer than the coil sensor (or) the outdoor air sensor indicates 10_F( 5.6_C) cooler than the coil sensor, the sensors are out
of range. If the sensors are out of range, the control will flash the appropriate fault code as shown in Table 6.
Failed Thermistor Default Operation
Factory defaults have been provided in the event of failure of outdoor air thermistor (OAT) and/or outdoor coil thermistor (OCT).
If the OAT sensor should fail, defrost will be initiated based on coil temperature and time.
If the OCT sensor should fail, defrost will occur at each time interval during heating operation, but will terminate after 2 minutes.
If there is a thermistor out-- of--range error, defrost will occur at each time interval during heating operation, but will terminate after 2 minutes.
Count the number of short and long flashes to determine the appropriate flash code. Fig. 38 and Table 6 gives possible causes and actions related to each error.
Maximum Power Mode -- Inverter Over
The outdoor unit is equipped with inverter temperature sensing. If the inverter senses a temperature above the high threshold limit it will respond as follows:
1. Display the local fault code only on the AOC Status LED.
2. The system will continue to run but attempt to mitigate by speed reduction.
3. When the system demand is satisfied, the unit will shut down.
4. If the fault is still active on the AOC Status LED, the ODF will continue to run at 500 RPM until the inverter temperature falls below the threshold.
5. The compressor will not restart if the fault is still active.
Temperature
Fig. 37 – 50K Thermistor Resistance Versus Temperature
If the outdoor air or coil thermistor should fail, the control will flash the appropriate fault code (see Table 6).
IMPORTANT: The outdoor air thermistor, coil thermistor and suction thermistor should be factory mounted in the final locations.
A14022
16
Fig. 38 – Fault Code Label
17
Table 6—Fault Code Actions
Flash Code
ON, no flash Standby
1, pause Variable Capacity
1 (2 sec ON), longer pause
(1 second OFF)
25
31 Local
32 Local
33 Local
46 Local BROWNOUT EVENT 6 Minutes Both low line voltages if persistent contact power provider
48
49 Local
53 Fault
54 Fault
Ty p e Amber LED Description
Variable Capacity
(Range Cutback)
System Mal-
function
System
Malfunction
INVALID MODEL
PLUG/INVERTER SIZE
HIGH PRESSURE SWITCH
(stage/speed down for each occurrence, elevates to fault
code 84 when it occurs while
running on the lowest stage)
(elevates to fault code 83 after
LOST INVERTER COMMUNI-
(Occurs aftr 2 minutes of no
communications between AOC
(Elevates to fault code 48 after
3 consecutive failures within 20
minute or 20 minutes continu-
LOST INVERTER COMMUNI-
(Elevated from fault code 33 af-
COMPRESSOR OVER CUR-
(Elevates to fault code 95 after
SUCTION TEMP SENSOR
OPEN
LOW PRESSURE TRIP
3 occurrences)
CATIONS
and MOC)
ous loss of connection)
CATIONS
ter 3 occurrences)
RENT FAULT
5 occurrences)
OUTDOOR AIR TEMP
SENSOR FAULT
FAULT
Reset
Time
NA Both
6 Minutes
(then re-
duced
stage oper-
ation)
6 Minutes Both Low Pressure Event
NA Both
NA Both
6 Minutes Both Refer to fault code 95 Refer to fault code 95
NA Both
NA Both
Mode Possible Causes Actions
Wrong Model Plug In-
stalled
Damaged Model Plug
Missing model plug on
service board
Damaged AOC control Replace AOC control
Incorrect Model Plug
with Inverter Size
Both High Pressure Event
Loose or disconnected harness (Hardness be­tween AOC (PL20) and
MOC)
Radio or Electrical noise
Possible damage to in-
verter
Loose or disconnected harness (Hardness be­tween AOC (PL20) and
MOC)
Radio or Electrical noise
Possible damage to in-
verter
Sensor Harness not
connected to AOC con-
Suction Thermistor not
properly attached or in
trol
Broken or loose har-
ness wire
Broken or Damaged
Sensor
Hardware damage to
AOC control
Sensor Harness not
connected to AOC
control
Broken or loose
harness wire
wrong location
Broken or Damaged
Sensor
Hardware damage to
AOC control
Verify correct model plug installed
Check model plug for corrosion or breakage;
Replace plug or inverter with correct size (If
model plug is for 2 Ton but Inverter is 3 Ton,
System will self-mitigate by reducing the stage,
persistent conditions will lead to lockout (refer
to Error Code 84). 2 hours of accumulated
operation without further fault will reset fault
System will self-mitigate, persistent conditions
will lead to lockout (refer to Error Code 83) 2
hours of accumulated operation without further
System will try to self-mitigate with repeated
System will try to self-mitigate with repeated
Ensure plug is connected to AOC control
Check harness for continuity; see resistance
chart to check resistance at given temperature
Check harness for continuity; see resistance
chart to check resistance at given temperature
Ensure plug is connected to AOC control
Check harness for continuity; see resistance
chart to check resistance at given temperature
Ensure Sensor is properly attached to the ac-
Check harness for continuity; see resistance
chart to check resistance at given temperature
replace if necessary
Re-install original model plug
fault code 25 will be shown)
reduced stage operation.
fault will reset fault counter
Verify good harness connection
start attempts
change out the Inverter drive
Verify good harness connection
start attempts
change out the Inverter drive
Replace AOC control
cumulator entry-tube
Replace AOC control
18
Flash Code
55 Fault COIL TEMP SENSOR FAULT NA Both
56 Local
57 Fault
59 Local
61 Local
62 Local
63 Local
65 Local
66 Local
67 Local STATOR HEATER FAULT 6 Minutes Both
68 Event
69
71 Local
System Mal-
function
Amber LED DescriptionTy p e
OAT-OCT THERMISTOR OUT
INTERNAL FAULT (elevates to
OF RANGE
SUCTION PRESSURE
SENSOR FAULT
DISCHARGE TEMP OUT OF
RANGE EVENT
(elevates to fault code 74 after
5 occurrences)
FAN INVERTER FAULT
(elevates to fault code 76 after
5 occurrences)
FAN INVERTER TEMP HIGH
(elevates to fault code 85 after
3 occurrences)
FAN INVERTER CURRENT
(elevates to fault code 86 after
DC VOLTS LOW - SPEED
OUTDOOR FAN DROPPED
10 MIN STAGE 2 WARMUP
INVERTER/COMPRESSOR
this fault code after 5 occur-
COMPRESSOR DROPPED
FAULT
5 occurrences)
LIMITING
OUT
DELAY
rences of itself)
OUT
Reset
Time
NA
NA Both
15 Minutes Both See fault 74 Same actions for 74
6 Minutes Both OFMfailedtostart
NA Both See fault 85 Same actions for 85
6 Minutes Both See fault 86 Same actions for 86
NA Both
6 Minutes Both
10 Minutes Both
15 Minutes Both
6 Minutes Both
ActionsPossible CausesMode
Sensor Harness not
connected to AOC
control
Broken or loose
harness wire
Coil Thermistor not
properly attached or in
wrong location
Broken or Damaged
Sensor
Hardware damage to
AOC control
Coil Thermistor not
properly attached or in
wrong location
Outdoor Ambient Tem-
Both
perature sensor improp-
erly installed (sensor
body may be in contact
with sheet metal)
Heating when cooling is
Cool
demanded
Sensor Harness not
connected to AOC
control
Broken or loose
harness wire
Electrical short
destroyed Transducer
electronics
Heat damage during
brazing
Fan motor misalignment System will attempt to run again
See Fault 76 Same actions for 76
Low supply line voltage
(< 197 VAC)
Loose wire in control
box area
Inverter internal
damage
MOC is reporting that
OFM isn't running
There is a demand for
stator heat but MOC
doesn't detect it
High voltage power cy-
Phase imbalance/com-
cle
pressor or inverter-
miswire
Flooded start Troubleshoot EXV & TXV
Incorrect refrigerant
charge
Inverter damage Replace inverter
Compressor damage Replace compressor
MOC is reporting that
compressor isn't
running
Ensure plug is connected to AOC control
Check harness for continuity; see resistance
chart to check resistance at given temperature
Ensure Sensor is properly clipped to the dis-
Check harness for continuity; see resistance
chart to check resistance at given temperature
Ensure Sensor is properly clipped to the dis-
Check wiring between AOC and reversing
Ensure plug is connected to AOC control
Compare transducer reading to gauge reading
at service valve (see transducer measurement
chart); Check system for electrical shorts and
Compare transducer reading to gauge reading
at service valve (see transducer measurement
Troubleshoot outdoor fan motor & blade and
Check supply voltage to ODU; if low contact
Loose wire: check for loose wire in ODU
Troubleshoot outdoor fan motor and make
Check compressor winding resistance or mis-
wire of compressor leads at terminals U,V,W
Check compressor winding resistance or mis-
wire of compressor leads at terminals U,V,W
Check compressor winding resistance or mis-
wire of compressor leads at terminals U,V,W
tributor entry-tube
Replace AOC control
tributor entry-tube
Properly install OAT sensor
Check fuse on AOC control
troubleshoot reversing valve
Inspect outdoor coil for obstructions
Check harness
correct; replace transducer
chart); replace transducer
make sure they are working
utility provider
Replace Inverter
sure it is working
No action
Check refrigerant amount
valve
19
Flash Code
72 Local
74
75 Local
76
77 Local
79 Local
82
System
Malfunction
System
Malfunction
System Mal-
function
Amber LED DescriptionTy p e
SUCTION OVER TEMPERA-
TURE EVENT
(elevates to fault code 82 after
3 occurrences)
DISCHARGE TEMP OUT OF
RANGE LOCKOUT
(Elevated from fault code 59 af-
ter 5 occurrences)
MAXIMUM POWER MODE -
(Temporary RPM reduction or
FAN INVERTER LOCKOUT (Elevated from fault code 61
MAXIMUM POWER MODE -
(Temporary RPM reduction or
COMPRESSOR/INVERTER
(Elevates to fault code 88 after
(Elevated from fault code 72 af-
TEMP
stage lowering will result.)
after 5 occurrences)
COMP CURRENT
stage lowering will result.
FAULT
5 occurrences)
SUCTION OVER TEMP
LOCKOUT
ter 3 occurrences)
Reset
Time
15 Minutes Both See fault 82 Same actions for 82
Sensor Harness not
Both
2 Hours
Cool High Load conditions Over charge: Check system charge
Heat
Heat
NA Both
2 Hours Both
NA Both
6 Minutes Both
Both
4 Hours
Cool Uninsulated vapor line Insulate the vapor line Cool Indoor TXV operation Troubleshoot TXV Heat Outdoor EXV operation Troubleshoot EXV Both Reversing valve bypass troubleshoot reversing valve
connected to AOC
control
Broken or loose
harness wire
Broken or Damaged
Sensor
Hardware damage to
AOC control
Indoor Unit Airflow too
low or off
Outdoor Unit Airflow too
low or off
Reversing Valve By-
pass or Reversing
Valve not energized
Low Charge or Loss of
Charge at low ambient
heating conditions
Expansion Device
Restriction
Outdoor Airflow too low
or off
Blocked Inverter Heat
Exchanger (fins)
Application violates
guideline
Fan blade bent/out of
balance
Fan blade restricted
Fan motor wiring
Fan motor Replace outdoor fan motor
Inverter damage Replace inverter
Compressor is operat-
ing outside the allowed
operational envelope
Incorrect refrigerant
charge
Outdoor Airflow too low
or off
Incoming power supply
voltage
Loose or incorrect wire
connections
Compressor fails to
start
Incorrect refrigerant
charge
Ensure plug is connected to AOC control
Check harness for continuity; see resistance
chart to check resistance at given temperature
Check harness for continuity; see resistance
chart to check resistance at given temperature
Troubleshoot indoor fan motor and make sure
Troubleshoot outdoor fan motor and make
Reversing Valve stuck halfway
Check harness and connectors
Undercharged or No charge: check charge
Heating: Trouble shoot EXV (coil, harnesses);
Power Cycle system, is EXV moving on power
Check ODU coil for clogging (ice or debris)
and clean if necessary; Troubleshoot ODU fan
motor and make sure it is working
Check Inverter fins for debris and clean if nec-
Consult Application Guideline for compliance
Check outdoor fan blade clearance
Check outdoor fan motor connectors and har-
Inverter will reduce speed to a lower stage
Check ODU coil for clogging (ice or debris)
and clean if necessary; Troubleshoot ODU fan
motor and make sure it is working
Check voltage versus unit rating plate for
Check incoming power leads and leads to the
System will try to self-mitigate with repeated
ActionsPossible CausesMode
Replace AOC control
it is working
sure it is working
Ensure AOC fuse is good
24 VDC in cooling mode
Trouble shoot the TXV
up (audible)
essary
Check outdoor fan blade
Check for ice build up
Check for ice build up
ness
Check refrigerant amount
allowable range
compressor plug
start attempts
Check refrigerant amount
20
Flash Code
83
Ty p e Amber LED Description
LOW PRESSURE LOCKOUT
System
Malfunction
FOR 4 HOURS
(Elevated from fault code 32 af-
ter 3 occurrences)
Reset
Time
4 Hours
Mode Possible Causes Actions
Cooling in Low Ambient
region (55 °F and be-
low) with "Low Ambient
Cool
Cool
Cool
Cool Undercharged System
Cool
Cool
Cool
Cool
Heat Troubleshoot EXV (see guide below)
Heat
Heat
Heat
Heat Undercharged System
Heat
Both
Both
Cooling Control" dis-
abled
Outside Normal Operat­ing Range (e.g. improp­er load calculation, sys-
tem match issue, out-
side cooling range etc.)
Service Valve left
closed (Liquid or Vapor)
Indoor Airflow too low or
Restriction in Filter Drier
plus Long Line Applica-
Restriction in Circuits or
Outside Normal Operat­ing Range (e.g. improp­er load calculation, sys-
side heating range etc.)
closed (Liquid Service
Outdoor Airflow too low
Restriction in Filter Drier
plus filter drier on Out-
Expansion Device Re-
off
tion and filter drier on
Indoor Unit
Restriction due to de-
bris
Tubing
tem match issue, out-
Service Valve left
Valve)
or off
Restriction due to de-
bris
door Unit
striction
Enable "Low Ambient Cooling" via user inter-
Consult Application Guidelines
Ensure Service Valves are open
Check system subcooling to determine charge
status, if low add charge using Charging Mode
(follow proper charging procedures)
Check Indoor for clogging (ice or debris) and
clean or de-ice if necessary; Troubleshoot In-
door fan motor and make sure it is working;
follow Indoor Airflow troubleshooting instruction
Clean System (refer to application guideline)
Clean System (refer to application guideline)
Check kinks and straighten or replace circuits
Consult Application Guidelines
Ensure Liquid Service Valve is open
Check Outdoor for clogging (ice or debris) and
clean or de-ice if necessary; Troubleshoot
Outdoor fan motor and make sure it is working;
follow Outdoor Airflow troubleshooting instruc-
Check charge in cooling (if in Cooling Charge
Mode Ambient Range), if low add charge using
Charging Mode (follow proper charging proce-
dures); if outside cooling charge mode range, pull out charge, weigh in using heating charge
Clean System (refer to application guideline)
Clean System (refer to application guideline)
If short lineset (less than 15 ft.) Troubleshoot
TXV (see guide below); replace if necessary
face
and replace filter drier
and replace filter drier
tion
mode
and replace filter drier
and replace filter drier
21
Flash Code
84
85
86
System Mal-
function
System
Malfunction
System
Malfunction
Amber LED DescriptionTy p e
HIGH PRESSURE LOCKOUT
FOR 4 HOURS
(Elevated from fault code 31
when the stage (speed) can no
longer be lowered)
FAN INVERTER TEMP LOCK-
(Elevated from fault code 62 af-
FAN INVERTER CURRENT
(Elevated from fault code 63 af-
OUT
ter 3 occurrences)
LOCKOUT
ter 5 occurrences)
Reset
Time
Both
Both
Both
Both
Cool
Cool Overcharged System
Heat
Both
Both
4 Hours
15 minutes
5 minutes Both
Both
Cool
Cool
Cool
Both Faulty Pressure Switch
Heat
Heat
Heat
Both
Heat Overcharged System
Heat
Both
Both Inverter damage Replace inverter
ActionsPossible CausesMode
Outside Normal Operat­ing Range (e.g. improp­er load calculation, sys-
tem match issue, out­side cooling range, out­side heating range etc.)
Service Valve left
closed (Liquid or Vapor)
Loose High Pressure
Switch harness leads
Pressure Switch dis-
connected from ODU
Control Board
Outdoor Airflow too low
or off
Indoor Airflow too low or
charge when charging
Restriction in EXV plus
leading to Overcharge
when charging in Cool-
Non-condensable lead-
Restriction in Filter Drier
plus Long Line Applica-
Restriction in EXV plus
Restriction in Circuits or
Heat pump application:
Electric Heater stuck on
pump application: Fur-
Restriction in Filter Drier
plus Long Line Applica-
Expansion Device Re-
Reversing Valve Stuck
Unusual loading of the
Improper airflow across
Sudden supply voltage
Sudden load change on
off
Restriction due to de-
bris leading to Over-
Long Line Application
ing mode
ingtohighload
tion and filter drier on
Outdoor Unit
Overcharge
Tubing
Electric Heater plus
Furnace plus Heat
nace stuck on
tion and filter drier on
Indoor Unit
striction
in Cooling
fan
inverter heat sink
change
fan/motor
Inverter damage Replace inverter
Consult Application Guidelines
Ensure Service Valves are open
Check HPS harness
Check HPS connection on ODU control
Check Outdoor Coil for clogging (ice or debris) and clean or de-ice if necessary; Troubleshoot Outdoor fan motor and make sure it is working;
follow Outdoor Airflow troubleshooting instruc-
Check system charge using Cooling Charging
Mode (follow proper charging procedures)
Check Indoor for clogging (ice or debris) and
clean or de-ice if necessary; Troubleshoot In-
door fan motor and make sure it is working;
follow Indoor Airflow troubleshooting instruction
Clean System (refer to application guideline)
Clean System (refer to application guideline)
Clean System (refer to application guideline)
Check kinks and straighten or replace circuits
Check Discharge pressure with gauge, if less than 600 +/- 20 psig and switch is open (mea­sure resistance) then replace pressure switch
If User Interface is not requesting Electric Heat
check for heater relays, if on troubleshoot
If not in Defrost and Furnace is running same
time as heat pump, troubleshoot Furnace
Clean System (refer to application guideline)
Check charge in cooling (if in Cooling Charge
Mode Ambient Range), if low add charge using
Charging Mode (follow proper charging proce-
dures); if out side cooling charge mode range,
pull out charge, weigh in using heating charge
Troubleshoot outdoor fan motor & blade and
Check for fan outlet blockage due to snow/ice
Troubleshoot outdoor fan motor & blade and make sure they are working. Check harness
and replace filter drier
If long line, troubleshoot EXV
and replace filter drier
and replace filter drier
troubleshoot EXV
Electric Heater
and replace filter drier
Troubleshoot TXV
Troubleshoot EXV
mode
troubleshoot reversing valve
make sure they are working
Inspect outdoor coil for obstructions
Investigate incoming voltage
and connectors
tion
etc.
22
Flash
)
Code
88
91 Local
92 Local
93 Local
94 Local
95
96
97
98 Local
99
System Mal-
function
System
Malfunction
System
Malfunction
System
Malfunction
System
Malfunction
Amber LED DescriptionTy p e
COMPRESSOR / INVERTER
(Elevated from fault code 79 af-
INVERTER VDC-OUT UNDER
(Elevated from fault code 49 af-
(Elevated from fault code 92 af-
VDC OVER VOLTAGE LOCK-
(Elevated from fault code 91 af-
LOCKOUT
ter 5 occurrences)
INVERTER VDC-OUT OVER
VOLTAGE EVENT
(Elevates to fault code 97
after 5 occurrences)
VOLTAGE EVENT (Elevates to fault code 96 after 5 occur-
230VAC UNDER VOLTAGE
COMPRESSOR OVER CUR-
(Event will cause stage down
and when stage is at lowest
level, will elevate to fault code
HIGH TORQUE LOCKOUT
(Elevated from fault code 98
rences)
EVENT
230VAC OVER VOLTAGE
EVENT
RENT LOCKOUT
ter 5 occurrences)
VDC UNDER VOLTAGE
LOCKOUT
ter 5 occurrences)
OUT
ter 5 occurrences)
HIGH TORQUE EVENT
99
when 98 occurs at lowest
stage)
Reset
Time
2 Hours Both
5 Minutes Both
5 Minutes Both
5 Minutes Both
5 Minutes Both
Both High superheat
Both
2 Hours
Both
2 Hours Both
2 Hours Both
NA Both
Both Refer to 99 Refer to 99
Both Miswire
Both
2 hours
Both
Both
ActionsPossible CausesMode
Blocked Inverter Heat
Exchanger (fins)
Condenser Airflow too
low or off
Evaporator Airflow too
low or off
High Load conditions at cold ambient heating or
high ambient cooling
Inverter damage Replace inverter
Occurs when bus volt­age exceeds 410 VDC
Compressor is
suddenly unloaded
Inverter damage Replace inverter
Occurs when bus volt-
age falls below 220
VDC
Occurs when incoming
voltage is less than 197
VAC
Occurs when incoming
voltage is more than
253 VAC
Compressor is operat­ing outside the allowed
operational envelope
Incoming power
supply voltage
Loose or incorrect wire
connections
Phase imbalance
Outdoor Airflow too low
or off
Refrigerant overcharge Check refrigerant amount
Inverter damage Replace inverter
Compressor internal
damage
Low supply line voltage
(< 197 VAC)
Loose wire in control
box area
Inverter internal
damage
High supply line voltage
(> 253 VAC)
Inverter internal
damage
Compressor is operat­ing outside the allowed
operational envelope
Refrigerant overcharge
Outdoor Airflow too low
or off
Expansion Device
Restriction
Check Inverter fins for debris and clean if nec-
Check Condenser (IDU in heating, ODU in cooling) for clogging (ice or debris) and clean if necessary; Troubleshoot Condenser fan motor
and make sure it is working
Check Evaporator (IDU in cooling, ODU in heating) for clogging (ice or debris) and clean if necessary; Troubleshoot Evaporator fan motor
and make sure it is working
Over charge: Check system charge
Check operation of compressor; persistent
over voltage trips will lead to fault 97
Check that the service valves are fully open
Check for interruption in main power supply;
persistent over voltage rips will lead to fault 96
System will try to ride through voltage spikes (possibly caused by weather event) and self-
System will try to ride through voltage spikes (possibly caused by weather event) and self-
Check suction pressure transducer and suc-
Inverter will reduce speed to a lower stage
Check voltage versus unit rating plate for al-
Check incoming power leads and leads to the
Check compressor winding resistance or mis-
wire of compressor leads at terminals U,V,W
Check ODU coil for clogging (ice or debris)
and clean if necessary; Troubleshoot ODU fan
motor and make sure it is working
Check supply voltage to ODU; if low contact
Loose wire: check for loose wire in ODU
Check supply voltage to ODU; if high contact
Inverter will reduce speed to a lower stage
Check miswire of compressor leads at termi-
Check ODU coil for clogging (ice or debris)
and clean if necessary; Troubleshoot ODU fan
motor and make sure it is working
essary
recover in trip condition
recover in trip condition
Troubleshoot TXV Troubleshoot EXV
tion temperature sensor
lowable range
compressor plug
Replace compressor
utility provider
Replace Inverter
utility provider
Replace Inverter
nals U,V,W
Check refrigerant amount
Troubleshoot TXV Troubleshoot EXV
23
Variable Speed Drive LED Location and Description (Sizes 13 and 24B)
COMM
STATUS LED 207
LED 200
MOC LED Description (Sizes 13 and 24B)
Reference Color Status Condition Description
LED200 Red
LED207 Amber
Steady
On Off Abnormal No power, capacitor voltage drained
Steady
On
Blinking Abnormal
Off Normal Compressor stops and no fault
Normal I ndicates MOC powered where DC bus at 40volts or higher
Normal Compressor is running
If compressor stops, it indicates some fault happening;
If compressor is running, it indicates speed is limited or reduced.
AOC LED Descriptions (Sizes 13 and 24B)
Reference Color Status Condition Description
STATUS Amber
COMM Green
Reference Color Suspect AOC board Failure De s cription
STATUS Amber
COMM Green
Fault Code Description Faul t C od e Failure De s cription
Communications Loss 179
NOTE: If any of the AOC control board header pins are damaged or are not making good contact, AOC board should be replaced.
Steady
On
Blinking Abnormal AOC function/fault status
Steady
On
LED Not Functioning Properly --- Requires AOC or Inverter Replacement
If Amber STATUS light is not on (neither steady nor blink-
In Communicating mode, if Green COMM LED is not on
when AB indoor wires are connected to AOC AB connector
ing), with power to outdoor unit
and indoor has communications
UI Fault Codes requiring AOC or Inverter Replacement
Normal AOC status ---standby mode
Normal Communication from AOC to indoor wall control
AOC STATUS is not functioning properly and AOC board should be replaced.
AOC is not capable of communicating with indoor; AOC board should be replaced.
Loss of communication with outdoor unit AOC board; AOCorInvertermayneedtobereplaced
24
Variable Speed Drive LED Location and Description (Sizes 25, 36, 37, 48, 49 and 60)
MOC LED Description (Sizes 25, 36, 37, 48, 49 AND 60)
Reference Color Status Description
LD1 Red
LED1 Red
LED3 Amber
LD5 Green
Steady On MOC powered where DC bus is 40volts or greater
Off No power, capacitor voltage drained
Steady On DCF and board DC high voltage and discharge circuit powered on
Off No power
Steady On MOC board switching power supply to power AOC board on
Off No Power
Blinking Indicates communication from MOC to AOC
Steady On Indicates 5 volt connection status OK between AOC and MOC
Off No Power
AOC LED Descriptions (Sizes 25, 36, 37, 48, 49 AND 60)
Reference Color Status Description
STATUS Amber
COMM Green Steady On Communication from AOC to indoor wall control
Reference Color Suspect AOC board Failure De s cription
STATUS Amber
COMM Green
Fault Code Description Faul t C od e Failure De s cription
Communications Loss 179
NOTE: If any of the AOC control board header pins are damaged or are not making good contact, AOC board should be replaced.
Steady On AOC status --- standby mode
Blinking AOC function/fault status
LED Not Functioning Properly --- Requires AOC or Inverter Replacement
If Amber STATUS light is not on (neither steady nor blink-
In Communicating mode, if Green COMM LED is not on
when AB indoor wires are connected to AOC AB connector
ing), with power to outdoor unit
and indoor has communications
UI Fault Codes requiring AOC or Inverter Replacement
AOC STATUS is not functioning properly and AOC board should be replaced.
AOC is not capable of communicating with indoor; AOC board should be replaced.
Loss of communication with outdoor unit AOC board; AOCorInvertermayneedtobereplaced
25
COMPRESSOR POWER HARNESS ASSEMBLY REPLACEMENT (Reference RCD Instruction # 99TA516170)
The following is a recommended procedure for compressor power harness replacement. Always refer to the unit product installation, start--up & service instructions for detailed procedures.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Turn off and lock out all power to unit before proceeding. Discharge all capacitors before proceeding
All wiring and electrical connections shall comply with all local and national electrical codes.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
failure to follow this warning could result in personal injury.
Do not operate compressor or provide any electrical power to the compressor unless the terminal box cover is in place and secured.
Measurements of amps and volts during running conditions must be taken at other points in the power supply.
Do not provide any power to the compressor unless suction and discharge service valves are open.
Replacement
1. Follow all safety warnings and notices.
2. Precautions must be taken when servicing components
3. Remove the control box cover.
4. Disconnect compressor power harness from inverter.
5. Remove service panel to gain access to unit wiring and
6. Cut the wire tires securing the compressor power harness to
Procedure
within the control box of this unit. The technician performing the service must determine that it is safe to work on or near the inverter. The electrical disconnect that provides power to the unit must be turned off, locked and tagged out. This will insure that no damage will occur to the inverter, controls or other equipment and will prevent injury if contact is made with the electrical equipment. Wait a minimum of two minutes before servicing the unit to allow inverter capacitors to discharge. Follow safety instructions located on unit control box cover.
compressor compartment.
the control box. Remove compressor power harness (from control box). Replace wire tie with supplied wire tie; do not fasten at this time. The second wire tie for the choke on the compressor is supplied with new harness on the replacement compressor (highlighted with the yellow circles below).
WARNING
WARNING
7. Remove top two screws holding control box and remove compressor harness (highlighted in yellow below).
8. Cut double loop wire tie on suction tube holding compressor harness, replace with new one provided; do not fasten at this time. Note how the compressor harness is routed to suction tube. (Highlighted in yellow below)
26
9. With using a slot screwdriver, lift up the on the side tab to pry the cover off from the RTV. Be sure not to break the tab.
10. It may be necessary to leverage the screwdriver against cover next to tab so as not to break the tab while loosening.
12. Remove cover, unplug old harness, plug in new harness, verify bushing is reinstalled and plug leads leave the terminal box through the bushing; reinstall cover pushing one side down then the other.
NOTE: DO NOT SCRAP SEALANT
13. Reinstall compressor sound blanket making sure discharge thermistor and compressor power harness are routed as they were from the factory.
14. Route compressor power harness to new double loop wire tie and then to the wire retainers in tube sheet (route as they were originally to make sure they will not contact fan blade) and then route into control box and reinstall two control box screws. (See image below)
11. Once Cover is loosened on one side, use screwdriver along freed edge to remove.
15. Reinstall service panel.
16. Route compressor harness choke to left hand side of the top of control box and push in wire tie. Pull wires tight as they enter control box and tighten second wire tie.
17. Reconnect compressor power harness to the inverter. NOTE: Reference enclosed wiring diagrams and unit wiring diagrams in Owner’s Manual to aid in reattaching electrical connections.
18. Reinstall control box cover.
27
INVERTER ASSEMBLY w SHIELD GASKET REMOVAL AND INSTALLATION (Reference RCD Instruction # 99TA512018) Also see figures 40 through 41
6. After verifying the voltage has dissipated to zero,
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Turn off the electrical supplies to the unit before performing any maintenance or service. Follow the operating instructions on the label attached to the unit
!
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in unit damage or improper operation.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
IMPORTANT: DO NOT USE POWER TOOLS TO TIGHTEN THE INVERTER INPUT SCREW TERMINALS
Removing
Inverter:
1. Remove power to the unit. Wait a minimum of two minutes before servicing the unit to allow inverter capacitors to discharge. Follow safety instructions located on unit control box cover.
2. Precautions must be taken when servicing components within the control box of this unit. The technician performing the service must determine that it is safe to work on or near the inverter. The electrical disconnect that provides power to the unit must be turned off, locked and tagged out. This will insure that no damage will occur to the inverter, controls or other equipment and will prevent injury if contact is made with the electrical equipment.
3. Remove the control box cover.
4. The inverter capacitors are covered with a protective shield. The shield should not be removed from the inverter.
5. Before servicing the inverter, verify the inverter voltage is zero. Measure the DC voltage at the DC + VOLTAGE and DC -- VOLT AGE terminals on the inverter adjacent to the capacitors to ensure that they have totally discharged. The voltage at these terminals must be 0 (zero) before servicing (see following figures).
WARNING
CAUTION
disconnect wiring from the inverter.
7. Disconnect three compressor power wires. Note wire color order – Yellow, Red, and Black.
8. Disconnect fan motor power harness plug.
9. Disconnect reversing valve / PEV plug. (See Figure Below)
10. Disconnect high pressure switch plug.
11. Disconnect EXV plug.
12. Disconnect suction pressure transducer plug.
13. Disconnect suction thermistor plug.
14. Disconnect discharge thermistor plug.
15. Disconnect OAT/OCT plug.
16. Disconnect control wiring (ABCD or thermostat connections)
17. Disconnect two input power wires. Note wire color order – Black and Yellow.
18. Disconnect inverter ground lead. Note wire color – Green w/ Yellow Stripe.
19. Remove 12 mounting screws and pull out inverter with cover intact.
Installing New
1. Install inverter into control box. Attach (12) mounting screws.
2. Re--connect inverter ground lead. Note wire color – Green w/ Yellow Stripe.
3. Re--connect two input power wires. Note wire color order-­Black and Yellow.
4. Re--connect control wiring (ABCD or thermostat connections)
5. Re--connect OAT/OCT plug.
6. Re--connect discharge thermistor plug.
7. Re--connect suction thermistor plug.
8. Re--connect suction pressure transducer plug.
9. Re--connect EXV plug.
10. Re--connect high pressure switch plug.
11. Re--connect reversing valve / PEV plug.
12. Re--connect fan motor power harness plug.
13. Re--connect three compressor power wires. Note wire color order-- Yellow, Red and Black.
14. Replace the control box cover.
15. Apply power to the unit.
Inverter:
28
Fan Motor Harness Plug
Compressor
Power Harness Wires Yel, Red,
Fig. 39 – Compressor and Fan Harness
(Unit sizes 13 and 24B)
Fig. 40 – Compressor and Fan Harness
(Unit sizes 25, 36, 37, 48, 49 and 60)
29
Inverter Ground
Wire, GRN / YEL
Stripes
Inverter Input
and YEL
OAT/OCT PLUG
ABCD PLUG
Suction
PLUG
Suction Discharge
PLUG
High
Switch PLUG EXV PLUG
Reversing Valve PLUG
S
Power Wires BLK
Thermistor
Pressure
Thermistor
Fig. 41 – Wire Harness Connections
(Unit sizes 13 and 24B)
Pressure Transducer
Fig. 42 – Wire Harness Connections (Unit sizes 25, 36, 37, 48, 49 and 60)
30
COMPRESSOR REPLACEMENT (Reference RCD Instruction # 99TA516169)
The following is a recommended procedure for compressor replacement. Always refer to the unit product installation, start--up & service instructions for detailed procedures.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Turn off and lock out all power to unit before proceeding. Discharge all capacitors before proceeding
All wiring and electrical connections shall comply with all local and national electrical codes.
!
PERSONAL INJURY HAZARD
failure to follow this warning could result in personal injury.
Follow recognized safety practices and wear safety glasses, protective clothing, and gloves. Acids formed as a result of motor burnout can cause burns.
!
PERSONAL INJURY HAZARD
failure to follow this warning could result in personal injury.
do not disassemble bolts, plugs, fittings, etc. until all pressure has been relieved from compressor.
!
PERSONAL INJURY HAZARD
failure to follow this warning could result in personal injury.
Do not operate compressor or provide any electrical power to the compressor unless the terminal box cover is in place and secured. Measurements of amps and volts during running conditions must be taken at other points in the power supply.
Do not provide any power to the compressor unless suction and discharge service valves are open.
!
UNIT DAMAGE HAZARD
failure to follow this caution may result in equipment damage or improper operation.
Only suction line filter driers should be used for refrigerant and oil clean up.
Use of non--approved products could limit system life and void unit warranty.
WARNING
WARNING
WARNING
WARNING
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not leave system open to atmosphere. compressor oil is highly susceptible to moisture absorption.
At the time of compressor change out and at regular preventative maintenance intervals the acid/moisture content of the system should be checked using an acid/moisture test kit. This can determine, in a few minutes, whether acid and moisture are present in the system. No oil sample is required. Contact your local distributor to purchase this device.
Before Changing the
Check compressor and associated controls to be sure compressor replacement is necessary.
Classification
Failure
The replacement procedure is dependent on the type of failure. The following describes the classification process:
MECHANICAL FAILURES ELECTRICAL BURNOUT
1. No damage to windings as indicated by electri­cal check
2. Oil clean and odor free 2. Oildarkwithburnodor
3. Symptoms:Excessive Noise Won’t Pump Excessively Hot
Replacement Procedure for Mechanical Failure
1. Follow all safety warnings and notices.
2. Precautions must be taken when servicing components within the control box of this unit. The technician performing the service must determine that it is safe to work on or near the inverter. The electrical disconnect that provides power to the unit must be turned off, locked and tagged out. This will insure that no damage will occur to the inverter, controls or other equipment and will prevent injury if contact is made with the electrical equipment. Wait a minimum of two minutes before servicing the unit to allow inverter capacitors to discharge. Follow safety instructions located on unit control box cover.
3. Remove and recover all refrigerant from system until pressure gauges read 0 psi. Use all service ports. Never open a system under a vacuum to atmosphere. Break vacuum with dry nitrogen holding charge first. Do not exceed 5 psig.
4. Remove the control box cover.
5. Disconnect compressor power harness from inverter.
6. Remove service panel to gain access to unit wiring and compressor compartment.
CAUTION
Compressor
1. Windings of compressor open or grounded
3. Symptoms Blows fuses or circuit breaker Draws ab­normal amount of current
31
7. Cut the wire tires securing the compressor power harness to the control box. Remove compressor power harness (from control box). Replace wire tie with one supplied; do not fasten at this time. The second wire tie for the choke on the compressor is supplied with new harness on the replacement compressor (highlighted with the yellow circles below).
8. Remove top two screws holding control box and remove compressor harness (highlighted in yellow below).
10. Remove compressor mounting hardware.
11. Cut both suction and discharge lines with tubing cutter. Do not use brazing torch for compressor removal as oil vapor may ignite when compressor is disconnected.
12. Using caution and the appropriate lifting devices, remove compressor from the unit.
13. Scratch matching marks on stubs in old compressor. Make corresponding marks on replacement compressor.
14. Use torch to remove stubs from old compressor and install them in replacement compressor. NOTE: Use appropriate protection to avoid damage to compressor terminal cover and/or terminal box sealant with torch flame. It is intended that terminal cover remain installed during compressor installation.
15. Using caution and the appropriate lifting device, place replacement compressor in unit and secure with appropriate mounting hardware. NOTE: Use of existing or new OEM mounting hardware is recommended. NOTE: Compressor grommet and sleeve supplied with the compressor should be evaluated versus OEM hardware before assembling in unit.
16. Use copper couplings to tie compressor back into system. NOTE: Use appropriate protection to avoid damage to compressor terminal cover and/or terminal box sealant with torch flame. It is intended that terminal cover remain installed during compressor installation.
17. Remove and discard liquid line strainer and filter drier. Replace with filter drier one size larger in capacity than the unit being worked on (use bi --flow) type on heat pump. See Recommended Filter/Drier Sizes table below for appropriate size.
18. Reinstall compressor sound blanket making sure discharge thermistor and compressor power harness are routed as they were from the factory.
19. Route compressor power harness to new double loop wire tie and then to the wire retainers in tube sheet (route as they were originally to make sure they will not contact fan blade) and then route into control box and reinstall two control box screws. (See image below)
9. Cut double loop wire tie on suction tube holding compressor harness, replace with new one provided; do not fasten at this time. Note how the compressor harness is routed to suction tube (highlighted in yellow below).
32
20. Reinstall service panel.
21. Route compressor harness choke to left hand side of the top of control box and push in wire tie. Pull wires tight as they enter control box and tighten second wire tie.
22. Reconnect compressor power harness to the inverter. NOTE: Reference enclosed wiring diagrams and unit wiring diagrams in Owner’s Manual to aid in reattaching electrical connections.
23. Triple evacuate the system below 1,000 microns.
24. Recharge unit, compensating for larger liquid line filter. Charge compensation for oversize filter drier is listed in the Recommended Filter/Drier Sizes table below.
25. Check system for normal operation. If unit is a heat pump, switch from heating to cooling a few times to verify component operation.
Replacement Procedure for Electrical (System
Clean--up)
Burnout
Mild Burnout
Perform steps 1 – 25 as specified in the Replacement Procedure for Mechanical Failure and then perform steps as follows:
26. Run unit a minimum of 2 hours and replace liquid line filter drier.
27. Use a test kit to determine whether acceptable acid and moisture levels have been attained. If system is still contaminated, repeat step 17. Continue this process until the test kit indicates “clean” system.
28. Check system for normal operation. If unit is a heat pump, switch from heating to cooling a few times to verify component operation.
Severe Burnout
Perform steps 1 – 22 as specified in the Replacement Procedure for Mechanical Failure and then perform steps as follows:
23. Clean or replace TXV.
24. Drain any trapped oil from the accumulator if used.
25. Add suction line filter drier for appropriate unit size as indicated in Recommended Filter/Drier Sizes table below. Mount vertical with pressure taps on both inlet and outlet. NOTE: On heat pumps, install suction line drier between compressor and accumulator.
26. Triple evacuate the system below 1,000 microns.
27. Recharge unit, compensating for larger liquid line filter. Charge compensation for oversize filter drier is listed in Recommended Filter/Drier Sizes table below.
28. Run 1 hour minimum and change liquid line drier and suction filter.
29. Run a minimum of 2 or more hours and change liquid filter drier again. Remove suction line filter from system (do not replace suction line filter).
30. Use a test kit to determine whether acceptable acid and moisture levels have been attained. If system is still contaminated, repeat Step 22. Continue this process until the test kit indicates “clean” system.
31. Check system for normal operation. If unit is a heat pump, switch from heating to cooling a few times to verify component operation.
Recommended Filter/Drier Sizes
Minimum Required
Unit
Capacity
1, 2, 3, 4,
and 5
Quantity
1 6.5 15
Effective Desiccant Volume
Liquid CU. IN.
Suction CU.
IN.
33
WIRING DIAGRAMS -- 189BNV
W
BLK
CHOKE
1
LD1
DC
+
DC FAN
F
L1 L2
FUSE 3 AMP
120 30 60
90
J2
FORCED
DEFROST
YEL
BLK
PL18
YEL
GRN
GRN
208/230 1Ø POWER SUPPLY
LVCH
TB
21
23
L2
L1
Fig. 43 – 189BNV WIRING DIAGRAM -- Sizes 13 and 24B
CONNECTION DIAGRAM
OFM
V
RED
U
YEL
4 2
MOTOR CONTROL COMM HEADER
SW2
60 30
1
EQUIP GND
YEL
YEL
U
MOTOR & COMPRESSOR
CONTROL SECTION
HP CONTROL COMM HEADER
RVS
PL10
2
AIR CONDITIONER
CONTROL SECTION
MODEL
C
R
UTIL
24V
UTILITY INTERFACE
CHOKE
COMP
(R)
U
(C)
W
V
(S)
BLK
RED
CHOKE
RED
BLK
DC
W
V
PEV
1
BLU
BLU
STATUS COMM
PEV
2
1
O
W
Y
Y
1
-
HPS
BLU
BLU/PNK BLU/PNK
BLU
PL19
BLK
SPT
1
PL17
OST
1
PL16
ODT
1
PL15
OAT
OCT
BLK
BRN
BLK
BRN
OAT
OCT
+
WHT
-
RED
BLK
BLK
BLK
BLK
This control board contains a 3.5 minute short cycle protector. A 3.5 minute delay will occur between Compressor off/on cycles. To bypass delay, short forced defrost pins for 1 second then release. However, there is an additional 2.5 minutes delay upon expiration of the 3.5 minute short cycle delay to ensure the high and low side pressures are equalized. This is important for long term rotary compressor reliability. It is a delay that cannot and must not be bypassed. The internal crankcase heater is energized during off cycle as needed.
NOTES:
1. To Be Wired In Accordance With National Electric Code (N.E.C.) And Local Codes.
HPS
2. Use Copper Conductors Only. Use Conductors Suitable For At Least 75ºC (167ºF).
3. Two Wire A and B Required For Communication. If Outdoor Unit Improperly Grounded, Connect Indoor Ground To “C” Terminal.
4. If Any Of The Original Wire, As Supplied, Must Be Replaced, Use The Same Or Equivalent Wire.
5. Check All Electrical Connections Inside Control Box For Tightness.
6. Do Not Attempt To Operate Unit Until Service Valves Have Been Opened.
7. If Communicating, Must Use With Infinity or Evolution User Interface Listed In
Pre-sale Literature Only.
8. For Non-Communicating Thermostats, 24VAC To Be Provided To R Connection.
9. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS.
-LEGEND-
SPT
OST
ODT
FACTORY POWER WIRING FIELD POWER WIRING FACTORY CONTROL WIRING FIELD CONTROL WIRING COMPONENT CONNECTION JUNCTION FIELD SPLICE PLUG CONNECTION
SYSTEM COMMUNICATION
COMM
COMPRESSOR
COMP
HIGH VOLTAGE INDICATOR LED
LD1
HIGH PRESSURE SWITCH
HPS
LOW VOLTAGE CHOKE HARNESS
LVCH
MODEL PLUG CHART
MODEL
MODEL
PLUG
SIZE
HK70EZ
011
25
012
36
025
37
013
48
027
49
014
60
UNIT OPERATION
* MAY BE FACTORY OR FIELD INSTALLED
PIN RESISTANCE (K )
2 - 3 (R2)
1 - 4 (R1)
5.1K
150K
5.1K
180K
11K
091K
5.1K
220K
11K
150K
5.1K
270K
MODEL PLUG
MODEL
OUTDOOR AIR THERMISTOR
OAT
OUTDOOR COIL THERMISTOR
OCT
OUTDOOR DISCHARGE THERMISTOR
ODT
OUTDOOR FAN MOTOR
OFM
OUTDOOR SUCTION THERMISTOR
OST
PRESSURE EQUALIZER VALVE
PEV
SUCTION PRESSURE
SPT
TRANSDUCER SYSTEM FUNCTION LIGHT
STATUS
DEFROST TIME SELECT
SW2
TERMINAL BLOCK
TB
UTILITY CURTAILMENT
UTIL
24 VOLTS DC
24V
340613-101 REV. C
Fig. 44 – 189BNV WIRING DIAGRAM -- Sizes 25, 36, 37, 48, 49, 60
34
WIRING DIAGRAMS -- 288BNV
Fig. 45 – 288BNV WIRING DIAGRAM -- Sizes 13 and 24B
Fig. 46 – 288BNV WIRING DIAGRAM -- Sizes 25, 36, 37, 48, and 60
35
REFRIGERATION SYSTEM
Refrigerant
!
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
Puronr refrigerant which has higher pressures than R --22 and other refrigerants. No other refrigerant may be used in this system. Gauge set, hoses, and recovery system must be designed to handle Puronr. If you are unsure consult the equipment manufacturer.
In an air conditioning and heat pump system, refrigerant transfers heat from one replace to another. The condenser is the outdoor coil in the cooling mode and the evaporator is the indoor coil.
In a heat pump, the condenser is the indoor coil in the heating mode and the evaporator is the outdoor coil.
In the typical air conditioning mode, compressed hot gas leaves the compressor and enters the condensing coil. As gas passes through the condenser coil, it rejects heat and condenses into liquid. The liquid leaves condensing unit through liquid line and enters metering device at evaporator coil. As it passes through metering device, it becomes a gas--liquid mixture. As it passes through indoor coil, it absorbs heat and the refrigerant moves to the compressor and is again compressed to hot gas, and cycle repeats.
Compressor Oil
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
The compressor in a Puronr system uses a Polyol Ester (POE) oil. This oil is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Take all necessary precautions to avoid exposure of the oil to the atmosphere.
WARNING
!
CAUTION
4. Perform required service.
5. Remove and dispose of any oil contaminated material per local codes.
Brazing
This section on brazing is not intended to teach a technician how to braze. There are books and classes which teach and refine brazing techniques. The basic points below are listed only as a reminder.
Definition: The joining and sealing of metals using a nonferrous metal having a melting point over 800_F/426.6_C.
Flux: A cleaning solution applied to tubing or wire before it is brazed. Flux improves the strength of the brazed connection.
When brazing is required in the refrigeration system, certain basics should be remembered. The following are a few of the basic rules.
1. Clean joints make the best joints. To clean:
Remove all oxidation from surfaces to a shiny
finish before brazing.
Remove all flux residue with brush and water while
material is still hot.
2. Silver brazing alloy is used on copper--to--brass, copper--to--steel, or copper--to --copper. Flux is required when using silver brazing alloy. Do not use low temperature solder.
3. Fluxes should be used carefully. Avoid excessive application and do not allow fluxes to enter into the system.
4. Brazing temperature of copper is proper when it is heated to a minimum temperature of 800_F and it is a dull red color in appearance.
Service Valves and Pumpdown
!
PERSONAL INJURY AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
Never attempt to make repairs to existing service valves. Unit operates under high pressure. Damaged seats and o--rings should not be replaced. Replacement of entire service valve is required. Service valve must be replaced by properly trained service technician.
WARNING
Servicing Systems on Roofs With Synthetic Materials
POE (Polyol Ester) compressor lubricants are known to cause long term damage to some synthetic roofing materials. Exposure, even if immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more. When performing any service which may risk exposure of compressor oil to the roof, take appropriate precautions to protect roofing. Procedures which risk oil leakage include but are not limited to compressor replacement, repairing refrigerants leaks, replacing refrigerant components such as filter drier, pressure switch, metering device, coil, accumulator, or reversing valve.
Synthetic Roof Precautionary
1. Cover extended roof working area with an impermeable polyethylene (plastic) drop cloth or tarp. Cover an approximate 10 x 10 ft area.
2. Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills and prevent run--offs, and protect drop cloth from tears caused by tools or components.
3. Place terry cloth shop towel inside unit immediately under component(s) to be serviced and prevent lubricant run--offs through the louvered openings in the base pan.
Procedure
Service valves provide a means for holding original factory charge in outdoor unit prior to hookup to indoor coil. They also contain gauge ports for measuring system pressures and provide shutoff convenience for certain types of repairs.
The service valve is a front--seating valve, which has a service port that contains a Schrader fitting. The service port is always pressurized after the valve is moved off the front--seat position.
The service valves in the outdoor unit come from the factory front--seated. This means that the refrigerant charge is isolated from the line--set connection ports. The interconnecting tubing (line set) can be brazed to the service valves using industry accepted methods and materials. Consult local codes.
Before brazing the line set to the valve, the belled ends of the sweat connections on the service valves must be cleaned so that no brass plating remains on either the inside or outside of the bell joint. To prevent damage to the valve and/or cap “O” ring, use a wet cloth or other acceptable heat--sinking material on the valve before brazing. To prevent damage to the unit, use a metal barrier between brazing area and unit.
After the brazing operation and the refrigerant tubing and evaporator coil have been evacuated, the valve stem can be turned counterclockwise until back--seats, which releases refrigerant into tubing and evaporator coil. The system can now be operated.
36
The service valve--stem cap is tightened to 20 2 ft/lb torque and the service--port caps to 9 2 ft/lb torque. The seating surface of the valve stem has a knife--set edge against which the caps are tightened to attain a metal--to--metal seal.
The service valve cannot be field repaired; therefore, only a complete valve or valve stem and service--port caps are available for replacement.
If the service valve is to be replaced, a metal barrier must be inserted between the valve and the unit to prevent damaging the unit exterior from the heat of the brazing operations.
!
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when handling refrigerant.
CAUTION
Pumpdown & Evacuation
!
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental damage.
Federal regulations require that you do not vent refrigerant to the atmosphere. Recover during system repair or final unit disposal.
If this system requires either a Pump Down or Evacuation for any reason, the procedures below must be followed:
Pump Down -- Evolution Communicating -- 288BNV
Because this system is inverter controlled, compressor, suction pressure transducer and EXV, conventional procedure cannot be used to “pump down” and isolate the refrigerant into the outdoor unit. The UI (User Interface) has provisions to assist in performing this function.
1. Connect gauges to 288BNV liquid and vapor service valve ports to monitor operating pressures during and at comple­tion of the procedure.
2. In the advanced menu of the UI, go to Checkout > Heat Pump> Pumpdown
3. Select mode to pump down in (COOL or HEAT), COOL mode allows refrigerant to be isolated in outdoor unit. HEAT mode allows the refrigerant to be isolated in indoor coil and lineset. Set desired time period. Default time peri­od for the procedure is 120 minutes.
4. Select Start on UI to begin the pump--down process. Unit will begin running in selected mode after a brief delay.
5. Close the liquid service valve.
6. The unit will run in selected mode with the low pressure protection set to indicate pump-- down is complete when the suction pressure drops below 10 psig. Compressor protec­tions are still active to prevent damage to the compressor or inverter (high pressure, high current, high torque, etc.) .
7. Once system indicates pump --down complete or failure to complete shutdown, close vapor service valve.
8. A small quantity of charge will remain in isolated section of system dependent on ambient temperature and overall sys­tem charge. This charge must be manually recovered. A recovery system will be required to remove final quantity of refrigerant from indoor coil and line set.
9. Remove power from indoor and heat pump unit prior to ser­vicing unit.
CAUTION
Pump Down -- Evolution Communicating -- 189BNV
Because this system is inverter controlled, compressor, suction pressure transducer, conventional procedure cannot be used to “pump down” and isolate the refrigerant into the outdoor unit. The UI (User Interface) has provisions to assist in performing this function.
1. Connect gauges to 189BNV liquid and vapor service valve ports to monitor operating pressures during and at comple­tion of the procedure.
2. In the advanced menu of the UI, go to Checkout > Pump­down
3. Select mode to pump down in (COOL). Set desired time period. Default time period for the procedure is 120 min­utes.
4. Select Start on UI to begin the pump--down process. Unit will begin running in selected mode after a brief delay.
5. Close the liquid service valve.
6. The unit will run in selected mode with the low pressure protection set to indicate pump-- down is complete when the suction pressure drops below 10 psig. Compressor protec­tions are still active to prevent damage to the compressor or inverter (high pressure, high current, high torque, etc.) .
7. Once system indicates pump --down complete or failure to complete shutdown, close vapor service valve.
8. A small quantity of charge will remain in isolated section of system dependent on ambient temperature and overall sys­tem charge. This charge must be manually recovered. A recovery system will be required to remove final quantity of refrigerant from indoor coil and line set.
9. Remove power from indoor and outdoor unit prior to ser­vicing unit.
Pump Down – Using 2--stg HP Tstat -- 288BNV (Non--Communicating)
Because this system has an inverter controlled compressor, suction pressure transducer and EXV, conventional procedure cannot be used to “pump down” and isolate the refrigerant into the outdoor unit.
1. Connect gauges to 288BNV liquid and vapor service valve ports to monitor operating pressures during and at completion of the procedure.
2. Force system to operate in high stage by creating a large differential between room temperature and set point on thermostat. Use multi--meter to verify that 24 VAC is present between C and Y1 and Y2 terminals at outdoor unit.
3. Close the liquid service valve.
4. The unit will continue to run until high or low pressure switches open. Close vapor service valve once compressor shuts down.
5. Remove power from indoor and heat pump unit prior to servicing unit.
6. A quantity of charge will remain in isolated section of system dependent on ambient temperature and overall system charge. This charge must be manually recovered. A recovery system will be required to remove final quantity of refrigerant from indoor coil and line set.
Pump Down – Using 2--stg Tstat -- 189BNV (Non--Communicating)
Because this system has an inverter controlled compressor, suction pressure transducer, conventional procedure cannot be used to “pump down” and isolate the refrigerant into the outdoor unit.
1. Connect gauges to 189BNV liquid and vapor service valve ports to monitor operating pressures during and at completion of the procedure.
2. Force system to operate in high stage by creating a large differential between room temperature and set point on thermostat. Use multi--meter to verify that 24 VAC is present between C and Y1 and Y2 terminals at outdoor unit.
37
3. Close the liquid service valve.
4. The unit will continue to run until high or low pressure switches open. Close vapor service valve once compressor shuts down.
5. Remove power from indoor and outdoor unit prior to servicing unit.
6. A quantity of charge will remain in isolated section of system dependent on ambient temperature and overall system charge. This charge must be manually recovered. A recovery system will be required to remove final quantity of refrigerant from indoor coil and line set.
Evacuation and recovery of refrigerant from 288BNV
Because this system has an EXV for the heating expansion device, additional steps may be taken to open the EXV for fastest refrigerant recovery and evacuation. If the EXV is not open when pulling a vacuum or recovering refrigerant from the heat pump unit, extended evacuation time may be required and/or inadequate vacuum obtained. The UI (User Interface) has provisions to open the EXV for refrigerant recovery and/or evacuation.
1. Connect gauges to 288BNV liquid and vapor service valve ports to monitor operating pressures during and at comple­tion of the procedure. Attach recovery system or vacuum pump to gauge set as needed for the service procedure. The service valves must be open to evacuate the unit through the line set service ports. The suction capillary service port is a direct connection to the suction port of the compressor and mayalsobeused.
2. In the advanced menu of the UI, go to Checkout > Heat Pump > Evacuation.
3. Set desired time period. Default time period for the proced­ure is 120 minutes.
4. Select START on UI to open the valve.
5. Begin evacuation or refrigerant recovery as required for the procedure after UI indicates the EXV is open. Power may be removed from heat pump after the UI indicates “READY TO EVACUATE.”
6. Remove power from indoor and heat pump unit prior to ser­vicing unit. The EXV will retain the open position.
NOTE: See service training materials for troubleshooting the EXV using EXV CHECK mode.
Evacuation and recovery of refrigerant from 288BNV when using non--communicating thermostat
Refrigerant recovery and evacuation can be performed without a UI (User Interface) but will take more time. If EXV is not forced open the recovery and evacuation must rely on check valve as a bypass.
1. Connect gauges to 288BNV liquid and vapor service valve ports to monitor operating pressures during and at completion of the procedure. Attach recovery system or vacuum pump to gauge set as needed for the service procedure. The service valves must be open to evacuate the unit through the line set service ports. The suction capillary service port is a direct connection to the suction port of the compressor and may also be used.
2. Begin evacuation or refrigerant. Allow extra time for refrigerant recovery and establishing a thorough evacuation.
Evacuation and recovery of refrigerant from 189BNV
1. Connect gauges to 189BNV liquid and vapor service valve ports to monitor operating pressures during and at comple­tion of the procedure. Attach recovery system or vacuum pump to gauge set as needed for the service procedure. The service valves must be open to evacuate the unit through the line set service ports.
Evacuation and recovery of refrigerant from 189BNV when using non--communicating thermostat
1. Connect gauges to 189BNV liquid and vapor service valve ports to monitor operating pressures during and at completion of the procedure. Attach recovery system or vacuum pump to gauge set as needed for the service procedure. The service valves must be open to evacuate the unit through the line set service ports.
Reversing
In heat pumps, changeover between heating and cooling modes is accomplished with a valve that reverses flow of refrigerant in system. This reversing valve device is easy to troubleshoot and replace. The reversing valve solenoid can be checked with power off with an ohmmeter. Check for continuity and shorting to ground. With control circuit (24v) power on, check for correct voltage at solenoid coil. Check for overheated solenoid.
With unit operating, other items can be checked, such as frost or condensate water on refrigerant lines.
The sound made by a reversing valve as it begins or ends defrost is a “whooshing” sound, as the valve reverses and pressures in system equalize. An experienced service technician detects this sound and uses it as a valuable troubleshooting tool.
Using a remote measuring device, check inlet and outlet line temperatures. DO NOT touch lines. If reversing valve is operating normally, inlet and outlet temperatures on appropriate lines should be close to each other. Any difference would be due to heat loss or gain across valve body. Temperatures are best checked with a remote reading electronic-- type thermometer with multiple probes. Route thermocouple leads to inside of coil area through service valve mounting plate area underneath coil. Fig. 47 and Fig. 48 show test points (TP) on reversing valve for recording temperatures. Insulate points for more accurate reading.
If valve is defective:
Valve
1. Shut off all power to unit and remove charge from system.
2. Remove solenoid coil from valve body. Remove valve by cutting it from system with tubing cutter. Repair person should cut in such a way that stubs can be easily re--brazed back into system. Do not use hacksaw. This introduces chips into system that cause failure. After defective valve is removed, wrap it in wet rag and carefully unbraze stubs. Save stubs for future use. Because defective valve is not overheated, it can be analyzed for cause of failure when it is returned.
3. Braze new valve onto used stubs. Keep stubs oriented correctly. Scratch corresponding matching marks on old valve and stubs and on new valve body to aid in lining up new valve properly. When brazing stubs into valve, protect valve body with wet rag to prevent overheating.
4. Use slip couplings to install new valve with stubs back into system. Even if stubs are long, wrap valve with a wet rag to prevent overheating.
5. After valve is brazed in, check for leaks. Evacuate and charge system. Operate system in both modes several times to be sure valve functions properly.
38
A
TO OUTDOOR COIL
TO ACCUMULATOR
TP-- 4 TP- -3
FROM IN DOOR COILVI SERVICE VALVE ON OUTDOOR COIL
TP-- 2
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
To avoid filter drier damage while brazing, filter drier must be wrapped in a heat--sinking material such as a wet cloth.
TP-- 1
FROM COMPRESSOR DISCHARGE LINE
A88342
Fig. 47 – Reversing Valve
(Cooling Mode or Defrost Mode, Solenoid Energized)
FROM OUTDOOR COIL
TP--4 TP--3
INSULATE FOR
ACCURATE
READING
FROM COMPRESSOR
DISCHARGE LINE
TO
ACCUMULATOR
INSULATE
ACCURATE
READING
TP--1
ELECTRONIC
THERMOMETER
TO INDOOR COIL
VIA SERVICE VALVE
ON OUTDOOR COIL
FOR
TP--2
A88341
Fig. 48 – Reversing Valve
(Heating Mode, Solenoid De--Energized)
Liquid Line Filter Drier
Filter driers are specifically designed for R--22 or Puronr refrigerant. Only operate with the appropriate drier using factory authorized components.
It is recommended that the liquid line drier be installed at the indoor unit. Placing the drier near the TXV allows additional protection to the TXV as the liquid line drier also acts as a strainer.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
To avoid performance loss and compressor failure, installation of filter drier in liquid line is required.
CAUTION
Install Liquid --line Filter Drier
Indoor
Install filter drier as follows:
1. Braze 5 in. liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to 5 in. long liquid tube from step 1.
4. Connect and braze liquid refrigerant tube to the filter drier.
Suction Line Filter Drier
The suction line drier is specifically designed to operate with Puronr, use only factory authorized components. Suction line filter drier is used in cases where acid might occur, such as burnout. Heat pump units must have the drier installed between the compressor and accumulator only. Remove after 10 hours of operation. Never leave suction line filter drier in a system longer than 72 hours (actual time).
Thermostatic Expansion Valve (TXV)
All fan coils and furnace coils will have a factory installed thermostatic expansion valve (TXV). The TXV will be a bi--flow, hard--shutoff with an external equalizer and a balance port pin. A hard shut--off TXV does not have a bleed port. Therefore, minimal equalization takes place after shutdown. TXVs are specifically designed to operate with Puronr or R--22 refrigerant, use only factory authorized TXV’s. Do not interchange Puron
and R--22 TXVs.
Operation
TXV
The TXV is a metering device that is used in air conditioning and heat pump systems to adjust to changing load conditions by maintaining a preset superheat temperature at the outlet of the evaporator coil. The volume of refrigerant metered through the valve seat is dependent upon the following:
1. Superheat temperature is sensed by cap tube sensing bulb on suction tube at outlet of evaporator coil. This temperature is converted into pressure by refrigerant in the bulb pushing downward on the diaphragm which opens the valve via the push rods.
2. The suction pressure at the outlet of the evaporator coil is transferred via the external equalizer tube to the underside of the diaphragm. This is needed to account for the indoor coil pressure drop. Residential coils typically have a high pressure drop, which requires this valve feature.
3. The pin is spring loaded, which exerts pressure on the underside of the diaphragm. Therefore, the bulb pressure works against the spring pressure and evaporator suction pressure to open the valve. If the load increases, the temperature increases at the bulb, which increases the pressure on the top side of the diaphragm. This opens the valve and increases the flow of refrigerant. The increased refrigerant flow causes the leaving evaporator temperature to decrease. This lowers the pressure on the diaphragm and closes the pin. The refrigerant flow is effectively stabilized to the load demand with negligible change in superheat.
39
Accumulator
B
The accumulator is specifically designed to operate with Puronr or R22 respectfully; use only factory--authorized components. Under some light load conditions on indoor coils, liquid refrigerant is present in suction gas returning to compressor. The accumulator stores liquid and allows it to boil off into a vapor so it can be safely returned to compressor. Since a compressor is designed to pump refrigerant in its gaseous state, introduction of liquid into it could cause severe damage or total failure of compressor.
The accumulator is a passive device which seldom needs replacing. Occasionally its internal oil return orifice or bleed hole may become plugged. Some oil is contained in refrigerant returning to compressor. It cannot boil off in accumulator with liquid refrigerant. The bleed hole allows a small amount of oil and refrigerant to enter the return line where velocity of refrigerant returns it to compressor. If bleed hole plugs, oil is trapped in accumulator, and compressor will eventually fail from lack of lubrication. If bleed hole is plugged, accumulator must be changed. The accumulator has a fusible element located in the bottom end bell. (See Fig. 49.) This fusible element will melt at 430_F//221_C and vent the refrigerant if this temperature is reached either internal or external to the system. If fuse melts, the accumulator must be replaced.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
WARNING
REFRIGERATION SYSTEM REPAIR
Leak Detection
New installations should be checked for leaks prior to complete charging. If a system has lost all or most of its charge, system must be pressurized again to approximately 150 psi minimum and 375 psi maximum. This can be done by adding refrigerant using normal charging procedures or by pressurizing system with nitrogen (less expensive than refrigerant). Nitrogen also leaks faster than refrigerants. Nitrogen cannot, however, be detected by an electronic leak detector. (See Fig. 50.)
BEEP EEP
430° FUSE ELEMENT
Fig. 49 – Accumulator
To change accumulator:
1. Shut off all power to unit.
2. Recover all refrigerant from system.
3. Break vacuum with dry nitrogen. Do not exceed 5 psig. NOTE: Coil may be removed for access to accumulator. Refer to appropriate sections of Service Manual for instructions.
!
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when handling refrigerant.
4. Remove accumulator from system with tubing cutter.
5. Tape ends of open tubing.
6. Scratch matching marks on tubing studs and old
accumulator. Scratch matching marks on new accumulator. Unbraze stubs from old accumulator and braze into new accumulator.
7. Thoroughly rinse any flux residue from joints and paint
with corrosion--resistant coating such as zinc--rich paint.
8. Install factory authorized accumulator into system with
copper slip couplings.
9. Evacuate and charge system. Pour and measure oil quantity (if any) from old accumulator. If more than 20 percent of oil charge is trapped in accumulator, add new POE oil to compressor to make up for this loss.
CAUTION
A88410
PERSONAL INJURY AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death.
Due to the high pressure of nitrogen, it should never be used without a pressure regulator on the tank.
Assuming that a system is pressurized with either all refrigerant or a mixture of nitrogen and refrigerant, leaks in the system can be found with an electronic leak detector that is capable of detecting specific refrigerants.
If system has been operating for some time, first check for a leak visually. Since refrigerant carries a small quantity of oil, traces of oil at any joint or connection is an indication that refrigerant is leaking at that point.
A simple and inexpensive method of testing for leaks is to use soap bubbles. (See Fig. 51.) Any solution of water and soap may be used. Soap solution is applied to all joints and connections in system. A small pinhole leak is located by tracing bubbles in soap solution around leak. If the leak is very small, several minutes may pass before a bubble will form. Popular commercial leak detection solutions give better, longer--lasting bubbles and more accurate results than plain soapy water. The bubble solution must be removed from the tubing and fittings after checking for leaks as some solutions may corrode the metal.
Fig. 50 – Electronic Leak Detection
!
WARNING
A95422
40
LEAK DETECTOR SOLUTION
Fig. 51 – Bubble Leak Detection
You may use an electronic leak detector designed for specific refrigerant to check for leaks. (See Fig. 50.) This unquestionably is the most efficient and easiest method for checking leaks. There are various types of electronic leak detectors. Check with manufacturer of equipment for suitability. Generally speaking, they are portable, lightweight, and consist of a box with several switches and a probe or sniffer. Detector is turned on and probe is passed around all fittings and connections in system. Leak is detected by either the movement of a pointer on detector dial, a buzzing sound, or a light.
In all instances when a leak is found, system charge must be recovered and leak repaired before final charging and operation. After leak testing or leak is repaired, replace liquid line filter drier, evacuate system, and recharge with correct refrigerant quantity.
!
WARNING
A95423
Coil Removal
Coils are easy to remove if required for compressor removal, or to replace coil.
1. Shut off all power to unit.
2. Recover refrigerant from system through service valves.
3. Break vacuum with nitrogen.
4. Remove top cover.
5. Remove screws in base pan to coil grille.
6. Remove coil grille from unit.
7. Remove screws on corner post holding coil tube sheet.
!
FIRE HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
Cut tubing to reduce possibility of personal injury and fire.
8. Use midget tubing cutter to cut liquid and vapor lines at both sides of coil. Cut in convenient location for easy reassembly with copper slip couplings.
9. Lift coil vertically from basepan and carefully place aside.
10. Reverse procedure to reinstall coil.
11. Replace filter drier, evacuate system, recharge, and check for normal systems operation.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
41
E 2016 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Edition Date: 03/16
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. SM288BNV--- 189BNV--- 0 3
Replaces: SM288BNV---189BNV --- 02
42
Loading...