Bryant 180CNV024, 180CNV036, 180CNV060, 180CNV048 Installation Instructions Manual

Page 1
180CNV EVOLUTIONREXTREME SERIES VARIABLE SPEED HEAT PUMP WITH PURONr REFRIGERANT (2 -- 5 Ton)
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
PAGE N O .
SAFETY CONSIDERATIONS 1....................
INSTALLATION RECOMMENDATIONS 2..........
INSTALLATION 3--9..............................
Step 1 — Check Equipment and Jobsite 3...........
Step 2 — Install on Solid Pad 3...................
Step 3 — Clearance Requirements 3................
Step 4 — Operating Ambient 4...................
Step 5 — Elevate Unit 4.........................
Step 6 — Making Piping Connections 4............
Step 7 — Make Electrical Connections 5............
Step 8 — Compressor Crankcase Heater 6...........
Step 9 — Install Accessories 6....................
Step 10 — Start--Up 6...........................
Step 11 — System Functions and Seq. Of Operation. 7.
Step 12 — Check Charge 8.......................
Step 13 — Pumpdown 9.........................
MAJOR COMPONENTS 9.........................
TROUBLESHOOTING 9...........................
FINAL CHECKS 15...............................
CARE AND MAINTENANCE 15....................
PURONr REFRIGERANT QUICK REF. GUIDE 15....
Information in these installation instructions pertains only to 180CNV series units.
Indoor Thermostat Control Options
Model
180CNV Yes *
* Requires model SYSTXBBIT W01 ---A, SYSTXBBITC01---A, SYS­TXBBTC01---B or newer. Ensure the wall control software has been updat­ed to the latest version available from HVAC Partners.
Evolution
Control
SAFETY CONSIDERAT IONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and current editions of the National Electrical Code ( NEC ) NFPA 70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
!
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
Page 2
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
ELECTRICAL HAZARD -- HIGH VOLTAGE!
Failure to follow this warning could result in personal injury or death.
Electrical components may hold charge. DO NOT remove control box cover for 2 minutes after power has been removed from unit.
PRIOR TO TOUCHING ELECTRICAL COMPONENTS:
Verify zero (0)voltage at inverter connections shown on inverter cover.
WARNING
!
WARNING
Inverter Cover
IMPORTANT: The inverter cover should NEVER be removed.
The inverter is not field serviceable. A replacement cover is provided with a replacement inverter.
!
WARNING
INSTALLATION RECOMMENDATIONS
In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer.
2. In noise sensitive applications (such as bedrooms), when a lineset is mounted to ceiling joists or floor joists, the out­door unit must be located at least 10 ft (3.05 m) away. If this is not possible, create a line set configuration with enough bends to provide 10 ft (3.05 m) of total line set length outside the dwelling
3. Ensure that vapor and liquid tube diameters are appropriate for unit capacity.
4. Run refrigerant tubes as directly as possible by avoiding un­necessary turns and bends.
5. Leave some slack between structure and unit to absorb vi­bration.
6. When passing refrigerant tubes through the wall, seal open­ing with RTV or other pliable silicon--based caulk (see Fig.
1).
7. Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
8. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tub­ing (see Fig. 1).
9. Ensure that tubing insulation is pliable and completely sur­rounds vapor tube.
10. When necessary, use hanger straps which are 1 in. wide and conform to shape of tubing insulation. (See Fig. 1.)
11. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.
OUTDOOR WALL INDOOR WALL
CAULK
INSULATION
HANGER STRAP
(AROUND SUCTION
TUBE ONLY)
THROUGH THE WALL
LIQUID TUBE
SUCTION TUBE
JOIST
INSULATION
SUCTION TUBE
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
PuronR refrigerant systems operate at higher pressures than standard R--22 systems. Do not use R--22 service equipment or components on PuronR refrigerant equipment.
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
If proper lineset routing techniques are not followed, variable speed systems can be susceptible to lineset transmitted noise inside the dwelling and, in extreme cases, tubing breakage.
1” (25.4 mm)
MIN
SUSPENSION
Fig. 1 -- Connecting Tubing Installation
2
LIQUID TUBE
A07588
Page 3
The outdoor unit contains the correct amount of refrigerant charge for operation with AHRI rated and factory--approved smallest indoor unit when connected by 15 ft (4.57 m) of field--supplied or factory accessory tubing.
Adjust refrigerant charge by adding or removing the charge to/from the unit depending on lineset length and indoor unit as calculated and displayed on the wall control. The wall control calculates required charge adjustment and total system charge required. For proper unit operation, check refrigerant charge using charging information in the Check Charge section of this instruction.
IMPORTANT: Liquid-- line size is 3/8--in. OD for all 180CNV applications including long line applications.
IMPORTANT: Always install the factory--supplied liquid--line filter drier. Obtain replacement filter driers from your distributor or branch.
INSTALLATION
IMPORTANT: Effective January 1, 2015, all split system and
packaged air conditioners must be installed pursuant to applicable regional efficiency standards issued by the Department of Energy.
Specifications for this unit in residential new construction market require the outdoor unit, indoor unit (including metering device), refrigerant tubing sets, and filter drier listed in pre-- sale literature. There can be no deviation. Consult the Service Manual – Air Conditioners and Air Conditioners Using PuronRefrigerant to obtain required unit changes for specific applications and for R--22 retrofit.
Step 1 — Check Equipment and Job Site
Unpack Unit
Move to final location. Remove carton taking care not to damage unit.
This unit employs one louver spacer on each of the four sides to prevent louver movement during operation. The louver spacers are trapped between the coil surface and louver at the approximate center of each side (See Fig. 2). This louver spacer should be present and, if dislodged during shipment, must be reinstalled before unit is placed into operation.
Step 2 — Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 3 to determine base pan size and knockout hole location.
For hurricane tie downs, contact distributor for details and PE (Professional Engineer) Certification, if required.
On rooftop applications, mount on level platform or frame. Place unit above a load--bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.
Roof mounted units exposed to winds above 5 mph may require wind baffles. Consult the Service Manual -- Residential Split System Air Conditioners and Air Conditioners Using Puron Refrigerant for wind baffle construction.
NOTE: Unit must be level to within 2(3/8 in./ft,9.5 mm/m.) per compressor manufacturer specifications.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Locate the unit in such a way that it is stable in all circumstances including adverse weather conditions.
Step 3 — Clearance Requirements
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm) clearance to service end of unit and 48 in. (1219.2 mm) (above unit. For proper airflow, a 6 --in. (152.4 mm) clearance on 1 side of unit and 12--in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
On rooftop applications, locate unit at least 6 in. (152.4 mm) above roof surface.
3/8---in. (9.53 mm) Dia. Tiedown Knockouts in Basepan(2) Places
Fig. 2 -- Louver Spacer Location
Inspect Equipment
File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit corner panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.
A11380a
UNIT BASE PAN
Dimension in. (mm)
35 X 35
(889 X 889)
Fig. 3 -- Tiedown Knockout Locations
3
View From Top
A05177
TIEDOWN KNOCKOUT LOCATIONS in. (mm)
A B C
9–1/8 (231.8) 6–9/16 (166.7) 28–7/16 (722.3)
Page 4
Step 4 — Operating Ambient
The minimum outdoor operating ambient in cooling mode is 55_F (13_C) without low ambient cooling enabled, and the maximum outdoor operating ambient in cooling mode is 125_F(52_C). With Low Ambient Cooling enabled, the minimum outdoor operating ambient in cooling mode is 0_F(--18_C).
Step 5 — Elevate Unit
Elevate unit per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of unit for units installed for low ambient cooling operation..
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not allow water and/or ice to build up in base pan.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
If ANY refrigerant tubing is buried, provide a 6 in. (152.4
CAUTION
mm) vertical rise at service valve. Refrigerant tubing lengths up to 36 in. (914.4 mm) may be buried without further
Step 6 — Make Piping Connections
special consideration. Do not bury lines longer than 36 in. (914.4 mm).
!
PERSONAL INJURY AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all flow--control devices, including solenoid valves.
WARNING
Outdoor units may be connected to indoor section using accessory tubing package or field--supplied refrigerant grade tubing of correct size and condition. For tubing requirements beyond 80 ft. (24.38 m), substantial capacity and performance losses can occur. Follow the pipe sizing recommendations in the 180CNV Product data to manage these losses.
Refer to Table 1 for field tubing diameters. Refer to Table 2 for accessory requirements.
Ta ble 1 – Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (in.)
LIQUID VAPOR*
UNIT SIZE
180CNV024
180CNV036
180CNV048
180CNV060
* Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance data when using different size and length line sets. Notes:
1. Do not apply capillary tube indoor coils to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal and / or greater than 20 ft. ( 6.1 m) vertical differential, an accessory Liquid Line Solenoid must be installed.
Connection
Diameter
3/8 3/8 7/8 7/8 5/8
3/8 3/8 7/8 7/8 5/8
3/8 3/8 7/8 1 --- 1 / 8 3/4
3/8 3/8 7/8 1 --- 1 / 8 3/4
Tube
Diameter
Connection
Diameter
Max (Rated)
Diameter
Minimum Tube
Diameter
REQUIRED FOR
ACCESSORY
Crankcase Heater Standard
Evaporator Freeze Protection Standard with Evolution Con trol No No No
Low--- Ambient Control Standard with Evolution Control No No No
Puron Refrigerant Balance Port
H a r d --- S h u t O f f T X V
Support Feet Recommended No Recommended No
Winter Start Control Standard with Evolution Control Standard with Evolution Control
EMI Kit No No No Ye s
* For tubing set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 20 ft. (6.10 m) vertical differential (total equivalent length), an accessory Liquid Line Solenoid must be installed.
{ Required on all indoor units. Standard on all new Puron refrigerant fan coils and furnace coils. Standard = Standard for all new Puron refrigerant fan coils and furnace coils.
L O W --- A M B I E N T C O O L I N G
APPLICATIONS
(Below 55F/12.8_C)
Ye s {
Table 2 – Accessory Usage
REQUIRED FOR LONG LINE
APPLICATIONS*
(Over 80 ft/24.38 m)
Standard
Ye s {
4
REQUIRED FOR SEA COAST APPLICATIONS (Within 2 miles/3.22 km)
Standard Standard
Ye s { Ye s {
Standard with Evolution
Control
Installations with Radio Frequency Interfe rence
Concerns in the Range
of2to30MHZ
Standard with Evolution
Control
Page 5
Outdoor Unit Connected to Factory--Approved Indoor Unit
Outdoor unit contains correct system refrigerant charge for operation with factory--approved, AHRI--rated smallest indoor unit
when connected by 15 ft. (4.57 m) of field--supplied or factory--accessory tubing, and factory --supplied filter drier. Check refrigerant charge for maximum efficiency.
NOTE: If the indoor furnace coil width is more than the furnace casing width, refer to the indoor coil Installation Instructions for transition requirements.
Install Liquid--Line Filter Drier Indoor
Refer to Fig. 4 and install filter drier as follows:
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage or improper operation.
Installation of filter drier in liquid line is required.
1. Braze 5--in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5--in. (127 mm) liquid tube.
4. Connect and braze liquid refrigerant tube to the filter drier.
CAUTION
Evacuate Refrigerant Tubing and Indoor Coil
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used. See Service Manual for triple evacuation method. Always break a vacuum with dry nitrogen prior to opening the refrigerant system for servicing.
CAUTION
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gauge capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. (See Fig. 5)
5000
4500
4000
3500
3000
2500
2000
MICRONS
1500
1000
500
LEAK IN SYSTEM
VACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
A05227
Fig. 4 -- Liquid-- Line Filter Drier
Refrigerant Tubing connection Outdoor
Connect vapor tube to fitting on outdoor unit vapor service valves and connect the liquid tube to fitting on outdoor unit liquid service valve. See T able 1 for allowable sizes.
Sweat Connections
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Use a brazing shield S Wrap service valves with wet cloth or heat sink material.
Use refrigerant grade tubing. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, braze sweat connections using industry accepted methods and materials. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.
CAUTION
01234567
MINUTES
Fig. 5 -- Deep V acuum Graph
A95424
A95424
Final Tubing Check
IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
Step 7 — Make Electrical Connections
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not supply power to unit with compressor terminal box cover removed.
Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.
NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not
WARNING
5
Page 6
install unit in system where voltage may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch circuit disconnect of adequate size per NEC
to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440--14 of NEC.
Route Ground and Power Wires
Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.
WARNING
Connect Ground and Power Wires
Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 6.
DISCONNECT PER N. E. C. AND/OR LOCAL CODES
CONTACTOR
FIELD POWER
WIRING
FIELD GROUND
WIRING
Fig. 6 -- Line Power Connections
GROUND LUG
A91056
Connect Control Wiring
Connect to Evolution connections. Only two wires (AB) to Evolution capable indoor unit (furnace or fan coil) is required. Typical 4 wire (ABCD) may be connected (see Fig. 14).
IMPORTANT: This system requires the power supply to the outdoor unit, and the indoor unit, for the wall control to communicate with the outdoor unit.
General Information
Use No. 18 AWG or larger color--coded, insulated (35C minimum) wire for low voltage control wires.
All wiring must be NEC Class 2 and must be separated from incoming power leads.
Use furnace transformer, fan coil transformer, or accessory transformer for control power requirement of system accessories external to the OD unit. The outdoor unit has its own transformer power.
Final Wiring Check
IMPORTANT: Check factory wiring and field wire connections to
ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.
Step 8 — Compressor Crankcase Heater
This compressor has an internal crankcase heater. Furnish power to the unit a minimum of 24 hr before starting the unit for the first time.
To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit.
Power is not required to the indoor unit or wall control for proper operation of heater. Crankcase heater will however be intelligently energized as needed between operations, and otherwise even when the wall control and indoor unit is not installed, as long as there is power to the outdoor unit even if the indoor unit and wall control are not yet installed.
Airflow Setup for Evolution Control Furnace or FE Fan Coil (communicating)
This system can only be installed with Evolution--capable indoor and Evolution wall control with the latest version software. When using an Evolution wall control, airflow is automatically selected based on equipment size. The user has the option of selecting Comfort, Efficiency and Max airflow for Heating and/or Cooling modes. These should be selected based on balance between the homeowner’s comfort and energy consumption expectations. See wall control Installation Instructions for additional available adjustments.
Due to using a communicating control with the fan coil or the furnace, dip switch adjustments are not necessary. The outdoor unit configuration and the indoor airflows are determined by communicating control setup.
Step 9 — Install Accessories
There are no refrigeration circuit or electrical accessories required or available for installation within the unit. External to the unit, the same accessories such as support feet, snow rack, wind baffle etc., are available on other Bryant units can also be used on this line of product. Refer to the individual Installation Instructions packaged with kits or accessories when installing.
Step 10 — Start--Up
!
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this caution may result in minor personal injury, equipment damage or improper operation.
Observe the following:
1. Do not overcharge system with refrigerant.
2. Do not operate unit in a vacuum or at negative pressure.
3. Do not disable low pressure switch
4. Dome temperatures may be hot.
!
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when handling refrigerant.
CAUTION
CAUTION
6
Page 7
!
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental damage.
Federal regulations require that you do not vent refrigerant to the atmosphere. Recover during system repair or final unit disposal.
CAUTION
Follow these steps to properly start up the system:
1. After system is evacuated, close the disconnects to energize the ID and OD units to assess the user interface (UI), Keep system in off mode. Under the Advanced function menu, assess the REQUIRED CHARGE CALCULATION screen. Enter the lineset length and vapor tube diameter. The wall control will now display the required charge adjustment (see Fig. 7) for the lineset and an adjustment for a large in­door coil if recognized as such by the wall control.
2. Add or remove the required charge adjustment for lineset length to liquid service valve. Note: If lineset is less than 15 feet (--9.4_C), charge re- moval may be necessary.
3. Fully open liquid and vapor service valves.
Fig. 7 -- Required Charge Adjustment
A170295
Calculated in wall control
4. Set wall control to operate cooling in CHARGING mode (see Fig.7). Charging mode operates system compressor speed and fan speeds to proper conditions to check the re­frigerant charge.
NOTE: Do not check charge in a mode other than CHARGING.
5. Select service valve subcool.
6. Wait for the specified stabilization time, depending on line­set length. Then Compare measured subcooling at liquid line service valve to target service valve subcool as shown on CHARGING screens (see Fig. 8).
Fig. 8 -- Liquid Line Subcooling Target
A170296
Step 11 — System Functions And Sequence Of Operation
The 180CNV models utilize an Evolution communicating wall control. With a call for cooling, the outdoor fan and compressor are energized to run at lowest cooling demand. If this does not satisfy cooling demand, the system will ramp up in stages until it satisfies the demand. After coping with the higher demand, the unit returns to lower capacity operation until the demand is satisfied or until an increase in demand.
When all demand is satisfied, the compressor will shut off. As the unit operates at lower capacity, system vapor (suction) pressure will be higher than it is during a standard single--stage system operation or during a higher capacity operation.
When the outdoor ambient is more the 100_F (37.8_C), the outdoor fan will continue to run for one minute after compressor shuts off. This reduces pressure differential for easier starting in the next cycle.
The conventional thermostat input is designed to work for emergency operation only. Connections are Y, and C. The system will only operate at maximum capacity.
The wall control displays the operation mode and fault codes as specified in the troubleshooting section. See Table 7 for codes and definitions.
NOTE: Only one code will be displayed on the outdoor unit control board (the most recent, with the highest priority). The latest codes are stored and can be access via the wall control.
Crankcase Heater Operation
This unit has an internal crankcase heater that will be energized during the off cycle and is intelligently demanded by the system to prevent the compressor from being the coldest part of the system thus enhancing the reliability. The crankcase heater will function as needed any time the outdoor unit is powered. The indoor unit and UI do not need to be installed for the crankcase heater to operate properly.
NOTE: Contactor may close intermittently without the unit starting. This is done to determine whether the control needs to energize the crankcase heater. Closing the contactor powers the inverter and allows the system to check compressor temperature.
7
Page 8
Outdoor Fan Motor Operation
The outdoor unit control (Fig. 9) energizes outdoor fan anytime compressor is operating as needed during low--ambient cooling operation. The outdoor fan remains energized if a pressure switch opens or compressor scroll over temperature should occur. This OD fan is an ECM motor which operates at varying speeds depending on the ambient and the demand.
Time Delays
The unit time delays include:
S Five minute time delay to start cooling operation when there is a
call from the wall control. To bypass this feature, momentarily short and release Forced Defrost pins.
S Five minute compressor re--cycle delay on return from a
brown--out condition.
S See Tab le 7 for other delay information.
General Information
Evolution Controlled low ambient
This unit is capable of low ambient cooling down to 0_F (--17.8_C) with Low Ambient enabled on the Evolution wall control. A low ambient kit is not required.
The Evolution Control provides an automatic evaporator coil freeze protection algorithm that eliminates the need for an evaporator freeze thermostat. The only accessory that may be required is wind baffles in locations which are likely to experience cross winds in excess of 5 miles an hour. This generally occurs only on roof and open area applications.
Low ambient cooling must be enabled in the wall control setup. The outdoor unit fan will cycle on and off based on outdoor coil temperature, outdoor air temperature, and suction pressure measurements to keep the compressor running at the proper conditions.
Utility Interface With Evolution Wall Control
The utility curtailment relay should be wired between the two UTIL connections on the control board for this Evolution Communicating System (see Fig. 16). This input allows a power utility device to interrupt compressor operation during peak load periods. When the utility sends a signal to shut the system down, the User Interface will display, ”Curtailment Active”. See wall control installation instructions for setup details.
cooling:
Communication and Status Function Lights
Evolution Control, Green Communications (COMM)Light
A green LED (COMM light) on the outdoor board (see Fig. 9) indicates successful communication with the other system products. The green LED will remain OFF until communication is established. Once a valid command is received, the green LED will turn ON continuously. If no communication is received within 2 minutes, the LED will be turned OFF until the next valid communication.
Amber Status
Amber colored STATUS light indicates operation and error status. See Table 7 for definitions.
S Two minute time delay to return to standby operation from last
valid communication.
S One minute time delay of outdoor fan at termination of cooling
mode when outdoor ambient is greater than or equal to 100_F (37.8_C).
Light
STATUS LED
COMM LED
A11139
Fig. 9 -- Variable Speed Control Board
Step 12 — Check Charge Charge in CHARGING
Factory charge amount and desired subcooling are shown in the user interface (UI). To properly check or adjust charge, conditions must be favorable for subcooling charging in cooling mode. Favorable conditions exist when the outdoor temperature is between 65_F and 100_F(18_C and 38_C), and the indoor temperature is between 70_F and 80_F(21_C and 27_C). If the temperatures are outside of these ranges, weigh--in charge only. If confirmation is needed return and check subcooling when the temperatures are within the desired range.
Charging Procedure: Unit is factory charged for 15ft (4.57 m) of lineset and for smallest rated indoor coil combinations. If any refrigerant charge adjustment is required based on the indoor coil combination and the line set length input, the wall control will calculate and display the target subcooling and the amount of additional charge to be added. Therefore wall control is the source of information for charging the system correctly. Refrigerant charge adjustment amount for adding or removing 0.6 oz/ft (17.74 g/m) of 3/8 liquid line above or below 15ft (4.57 m) respectively, and an additional amount of refrigerant charge adjustment (2 lbs) for a large ID coil if required, is calculated and displayed by the wall control.
Perform a final charge check when OD is between 65F(18C) and 100F(38C).
If the range is acceptable, go to the CHARGING screen on the wall control. Set the wall control to check the charge in cooling mode. Allow system to operate in cooling mode for the stabilization period as indicated on the wall control. Once conditions are indicated as favorable and stable by the wall control, check the system charge by subcooling method. Compare the subcooling taken at the liquid service valve to the subcooling target (target service valve subcool) listed on the charging screen. Add refrigerant if the subcooling is low and remove charge if subcooling is high. Tolerance should be 2F.
If any adjustment is necessary, add or remove the charge slowly (no greater than 0.5 lb per minute) and allow system to operate for 15 minutes to stabilize before declaring a properly charged system.
The use of a commercial charge metering device (restrictor) such as Imperial liquid low side charger model 535--C or Watsco ChargeFaster model CH200 is recommended when adding refrigerant to an operating system. This prevents potential damage of liquid slugging of the compressor and allows the subcooling to stabilize quicker.
mode
8
Page 9
If the indoor temperature is above 80_F (26.67 _C), and the outdoor temperature is in the favorable range, adjust system charge by weight based on line length and allow the indoor temperature to drop to 80_F (26.67_C) before attempting to check system charge by subcooling method as described above.
If the indoor temperature is below 70_F (21.11_C), or the outdoor temperature is not in the favorable range, adjust charge for line set length above or below 15ft (4.57 m) only. Charge level should then be appropriate for the system to achieve rated capacity. The charge level could then be checked at another time when the both indoor and outdoor temperatures are in a more favorable range. This ensures maximum efficiency and reliability.
Step 13 — Pumpdown
If this system requires a Pumpdown for any reason, the procedures below must be followed:
Because this system has an inverter controlled, compressor, and a suction pressure transducer conventional procedure cannot be used to “pump down” and isolate the refrigerant into the outdoor unit. The wall control has provisions to assist in performing this function.
1. Connect gages to 180CNV liquid and vapor or suction cap­illary service ports to monitor operating pressures during and at completion of the procedure.
2. In the advanced menu of the wall control, go to Refrigerant Charge > Pumpdown
3. Select mode to pump down in COOL. COOL mode allows refrigerant to be isolated in outdoor unit. Set desired time period. Default time period for the procedure is 120 min­utes.
4. Select Start on wall control to begin the pumpdown process. Unit will begin running in selected mode after a brief delay.
5. Close the liquid service valve.
6. The unit will run in selected mode with the low pressure protection set to indicate pumpdown is complete when the suction pressure drops below 0 psig. Compressor protec­tions are still active to prevent damage to the compressor or inverter (high pressure, high current, high torque, scroll temperature, etc.) .
7. Once system indicates pumpdown complete or failure to complete shutdown, close vapor service valve.
8. If pumpdown does not complete due to compressor safety shutdown, a recovery system will be required to remove fi­nal quantity of refrigerant from indoor coil and line set.
9. Remove power from indoor and AC unit prior to servicing unit.
MAJOR COMPONENTS
Variable speed Control Board
The AC control board controls the following functions:
S Compressor speed S Contactor operation S Outdoor fan motor operation S Low ambient cooling S Crankcase heater operation S Pressure switch monitoring S Time Delays S Pressure Transducer S Inverter communication and control
Inverter
The inverter is located inside the control box. This is an air--cooled device that communicates with the control board and drives the compressor to the demanded RPM. When the contactor closes, it powers the inverter with line voltage. The inverter changes the line voltage to 410 volts DC 3--phase, and varies the frequency to drive the compressor at the desired RPM.
NOTE: Manually closing the contactor will not cause the unit to operate. The unit must be operated with an Evolution Control. A standard thermostat will allow operation only in the emergency mode (high speed heating or cooling).
Variable Speed Compressor
This unit contains a variable speed compressor that has a wide operating range. It operates on 410vdc provided by the inverter. This compressor can only be operated by the specific inverter supplied with the unit.
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage and/or improper operation.
Do not attempt to apply line voltage directly to the compressor. This will destroy the compressor.
Field control Connections
For normal operation use the ABCD Evolution connections only. Only two wires, AB are required. See Fig. 14. Discrete inputs (Y,C, O) are available for emergency operation if the Evolution Bus is not in operation.
Pressure Transducer (SPT)
A 5 VDC output low pressure transducer that provides a 0 --5 VDC data for interpretation by the control board for a 0 to 200 psig range of pressure at the suction tube. This interpreted pressure data is then intelligently used by the control board for low pressure cut--out, loss of charge management, compressor overall envelope management, oil circulation management and lubrication management. (See Fig. 13.)
Compressor Control Contactor
The contactor has a 24 volt coil. The electronic control board controls the operation of the contactor.
TROUBLESHOOTING
Systems Communication Failure
If communication with the Evolution control is lost with the User Interface (UI), the control will flash the appropriate fault code (see Table 7). Check the wiring to the User Interface and the indoor and outdoor units and power.
Model Plug
Each control board contains a model plug. The correct model plug must be installed for the system to operate properly (see Table 3).
Table 3 – Model Plug Information
MODEL
NUMBER
180CNV024 HK70EZ011 5.1K 150K
180CNV036 HK70EZ012 5.1K 180K
180CNV048 HK70EZ013 5.1K 220K
180CNV060 HK70EZ014 5.1K 270K
The model plug is used to identify the type and size of unit to the control.
On new units, the model and serial numbers are input into the board’s memory at the factory. If a model plug is lost or missing at initial installation, the unit will operate according to the information input at the factory and the appropriate error code will flash temporarily. An RCD replacement board contains no model and serial information. If the factory control board fails, the model plug must be transferred from the original board to the replacement board for the unit to operate.
MODEL PLUG
NUMBER
PIN RESISTANCE
( K --- o h m s )
P i n s 1 --- 4 Pins 2--- 3
9
Page 10
NOTE: The model plug takes priority over factory model information input at the factory. If the model plug is removed after initial power up, the unit will operate according to the last valid model plug installed, and flash the appropriate fault code temporarily.
High Pressure Switch Protection
The outdoor unit is equipped with high pressure switch. If the control senses the opening of a high pressure switch, it will respond as follows:
1. De--energize the contactor.
2. Keep the outdoor fan operating for 15 minutes.
3. Display the appropriate fault code (see Table 7).
4. After a 15 minute delay, if there is a call for cooling or heat­ing and HPS is reset, the contactor is energized.
5. If HPS has not closed after a 15 minute delay, the outdoor fan is turned off. If the open switch closes anytime after the 15 minute delay, then resume operation with a call for cool­ing or heating at a temporary reduced capacity.
6. After each HPS trip fault, the compressor will operate at a reduced RPM/Capacity. When the HPS trips at the mini­mum RPM, the unit will be locked out on system malfunc­tion code 84 for 4 hours.
7. In the event of a high--pressure switch trip or high--pressure lockout, check the refrigerant charge, outdoor fan operation, and outdoor coil (in cooling) for airflow restrictions, or in­door airflow in heating.
Low Pressure Protection
The outdoor unit is equipped with low pressure transducer. If the control senses a low pressure per the table below, it wil respond as follows:
Cooling Low Prssure (3 minute operation) Cool Mode <= 55 psig
Low Pressure (instantaneous) <13 psig
1. Display fault code 32 on Status LED and wall control.
2. If a demand persists after the 15--minute delay and the pressure has reached the operation level, then resume opera­tion. Reset the 15 minute timer, clear the displayed fault code and communicate cleared error to the wall control. Status LED reverts to operation code display.
3. If a demand persists after the 15 minute delay but the pres­sure has not recovered, turn off the ODF. If the pressure recovers any time after the 15 minute delay, resume opera­tion. Reset the 15 minute timer, clear the displayed error code and communicate cleared error to the wall control. Status LED reverts to operation code display.
4. If a pressure drops below the instantaneous level three (3) consecutive times, lock out operation for 4 hours and dis­play the system malfunction code 83 and communicate lockout status to the wall control. The trip counter will reset to zero if 15 minutes of successful operation occurs before
rd
trip is recorded.
the 3
5. In the event of a low pressure trip or low pressure lockout, check the refrigerant charge and indoor airflow.
Brown--Out Protection
If the line voltage is less than 187v for at least 4 seconds, the contactor and fan relay are de-- energized. Compressor and fan operation are not allowed until voltage is a minimum of 190v. The control will flash the appropriate fault code (see Table 7).
230V Line (Power Disconnect) Detection
If there is no 230v at the contactor when the indoor unit is powered with a cooling or heating demand, the appropriate fault code is displayed. Verify the disconnect is closed and 230v wiring is connected to the unit.
Inverter Voltage Sensing
The control board senses the presence or absence of 230 V through the feedback from inverter. The control monitors the high voltage to the inverter. Voltage should be present anytime the contactor is energized and voltage should not be present when the contactor is de--energized.
Temperature Thermistors
Thermistors are electronic devices which sense temperature. As the temperature increases, the resistance decreases. Thermistors are used to sense outdoor air (OAT), coil temperature (OCT) and the suction line thermistor (OST) located between the reversing valve and the accumulator.
Refer to Table 4 and Fig. 10 for resistance values versus temperature.
Ta ble 4 – Resistance Values versus Temperature
TEMPERATURE RESISTANCE (ohms)
25.0° C (77.0° F) 10.0 + / - 2.3%
0.0° C (32.0° F) 32.6 + / - 3.2%
-28.0° C (-18.4° F) 85.5 + / - 3.4%
THERMISTOR CURVE
90
80
70
60
50
40
30
20
RESISTANCE (KOHMS)
10
0
0 20 40 60 80 100 120
TEMPERATURE (DEG. F)
A91431
Fig. 10 -- Thermistor Resistance Versus Temperature
If the outdoor air or coil thermistor should fail, the control will flash the appropriate fault code (see Table 7.)
IMPORTANT: The outdoor air thermistor, coil thermistor and suction thermistor should be factory mounted in the final locations. Check to ensure thermistors are mounted properly
(See Fig. 11, 12 and 13).
Thermistor Sensor Comparison
The control continuously monitors and compares the outdoor air temperature sensor and outdoor coil temperature sensor to ensure proper operating conditions. The comparison is:
S In cooling if the outdoor air sensor indicates 10_F( 5.6_C)
warmer than the coil sensor (or) the outdoor air sensor indicates 20_F( 11_C) cooler than the coil sensor, the sensors are out
of range. If the sensors are out of range, the control will flash the appropriate fault code as shown in Table 7.
The thermistor comparisons are not performed during low ambient cooling or defrost operation.
Failed Thermistor Default Operation
Factory defaults have been provided in the event of failure of outdoor air thermistor (OAT) and/or outdoor coil thermistor (OCT).
If the OAT sensor should fail, low ambient cooling will not be allowed and the one--minute outdoor fan off delay will not occur. Defrost will be initiated based on coil temperature and time.
If the OCT sensor should fail, low ambient cooling will not be allowed.
Count the number of short and long flashes to determine the appropriate flash code. Table 7 gives possible causes and actions related to each error.
10
Page 11
Outdoor Coil Thermistor
The outdoor coil thermistor is a 10Kohm resistor used for multiple system operations. It provides the coil/liquid line temperature to the control board and wall control. Low ambient operation and assistance with OAT temperature measurement of some of the functions. The sensor must be securely mounted to the tube connecting OD coil distributor. See Fig. 11 for proper placement. See Table 4 for proper resistances.
OAT Thermistor must be locked in place with spherical n ib end facing towards the front of the control box
A170294
Fig. 13 - Suction Thermistor (OST) Attachment
(On Suction Tube)
A11142
Fig. 11 -- OAT Thermistor Location (Bottom of Control Box)
A170293
Fig. 12 -- Outdoor Coil Thermistor (OCT) Attachment
(On Distributor Tube)
Suction Ther mistor (OST)
Suction Thermistor is used for compressor protection and must be secured on the suction tube and aligned longitudinally to the vertical surface of the tube axis (see Fig. 13).
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
In order to minimize the ambient influence, make sure the thermistor curved surface hugs the pipe surface and is secured tight using the wire tie fished through the original slot insulating polymer body.
Variable Speed Compressor Sensor Output Terminals
This compressor has a motor thermistor and a scroll thermistor. Correct resistance between scroll thermistor terminal and common is 10k at 77_F(25_C). Correct resistance between motor thermistor terminal and common is 5k at 77_F(25_C).
Variable Speed Compressor Power Input Terminals
This compressor operates with a 3--phase variable frequency PWM variable voltage to the three fusite terminals.
Table 5 – Variable Speed Compressor Resistances
(winding resistance at 70_F20_F)
WINDING
Between terminals
T1, T2, and T3
Between terminal &
ground
!
180CNV024 180CNV036
.681 .203
>1 mega OHM >1 mega OHM
CAUTION
180CNV048 180CNV060
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage and/or improper operation.
Do not use Meggar for measuring the winding resistance.
11
Page 12
ECM Fan Motor
If verification of proper operation is required for the ECM motor used in this unit, follow these steps:
1. Verify that the 230v input to the transformer is present.
2. Verify that the control board is powered 18 volts to 30 volts from the transformer.
3. With the UI in charging mode in cooling, measure the DC voltage between the PWM 1 and PWM 2 terminals on the outdoor control board. The DC voltage and PWM (option­al) measured must be as shown in Table 6.
Table 6 – DC Voltage and PWM Measurement
Unit Size Volt age PWM
24, 36 8.9 VDC 52
48, 60 11.1 VDC 84
Status Codes
Table 7 shows the status codes flashed by the amber status light. Most system problems can be diagnosed by reading the status code as flashed by the amber status light on the control board.
The codes are flashed by a series of short and long flashes of the status light. The short flashes indicate the first digit in the status code, followed by long flashes indicating the second digit of the error code.
The short flash is 0.25 seconds ON and the long flash is 1.0 second ON. Time between flashes is 0.25 seconds. Time between short flash and first long flash is 1.0 second. Time between code repeating is 2.5 seconds with LED OFF.
Codes are easily read from wall control. EXAMPLE:
3 short flashes followed by 2 long flashes indicates a 32 code. Table 7 shows this to be low pressure switch open.
Emergency Mode Connections with a Conventional Thermostat
In an emergency, it is possible to replace the wall control with a conventional thermostat. The unit will operate in maximum cooling speed only.
User Interface (UI)
D
C
B
A
Humidifier
C
24vac
Furnace or Fan Coil
D
C
B
A
OAT
RYOWCHUM
C and D
not required on
VS air conditioner
A12055
VS AC
No
Use
C
B
A
Fig. 14 -- Evolution Furnace or Fan Coil Wiring with Com-
municating Variable Speed AC
Conventional
Dual-Fuel
Thermostat
GYOWC R
Furnace or Fan Coil
A
B
C
D
OAT
R
GYOWCHUM
VS AC
A
B
C
NO
USE
UT
IL
C
LS
Y
O
A11382
Fig. 15 -- Variable Speed Unit Connected to a Conventional
Dual Fuel Thermostat in an Emergency Mode
12
Page 13
1
RED
SEC1
BRN
SEC2
EXV
PL5
BLU
YEL
PL3
PL2
PL1
CC
HPS
RVS
INVERTER
COMM
B
A
C
NO
USE
STATUS
UTIL
PWM2
PWM1
PL4
SPT
CB
PL11
OST
PL6
OCT
OAT
C
LS
O
Y
PL8
MODEL
J2
FORCED
DEFROST
Utility Interface*
Fig. 16 -- Variable Speed Control Board
with optional Utility Relay
A11544
13
Page 14
Table 7 – Troubleshooting
14
Page 15
FINAL CHECKS
IMPORTANT: IMPORTANT: Before leaving job, be
sure to do the following:
1. Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub--through or wire pinching.
2. Ensure that all wiring and tubing is secure in unit before adding panels and covers. Securely fasten all panels and covers.
3. Tighten service valve stem caps to 1/12-- turn past finger tight.
4. Leave Users Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual.
5. Fill out Dealer Installation Checklist and place in customer file.
For continuing high performance and to minimize possible equipment failure, periodic maintenance must be performed on this equipment.
Frequency of maintenance may vary depending upon geographic areas, such as coastal applications. See Owner’s Manual for information.
CARE AND MAINTENANCE
PURONR (R--410A) REFRIGERANT QUICK REFERENCE GUIDE
S Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement
components are designed to operate with Puron refrigerant.
S Puron refrigerant cylinders are rose colored. S Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400. S Puron refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose
when charging into suction line with compressor operating.
S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low--side retard. S Use hoses with 700 psig service pressure rating. S Leak detectors should be designed to detect HFC refrigerant. S Puron refrigerant, as with other HFCs, is only compatible with POE oils. S Vacuum pumps will not remove moisture from oil. S Do not use liquid--line filter driers with rated working pressures less than 600 psig. S Do not leave Puron refrigerant suction line filter driers in line longer than 72 hours. S Do not install a suction--line filter drier in liquid--line. S POE oils absorb moisture rapidly. Do not expose oil to atmosphere. S POE oils may cause damage to certain plastics and roofing materials. S Wrap all filter driers and service valves with wet cloth when brazing. S A factory-- approved liquid--line filter drier is required on every unit. S Do NOT use an R --22 TXV. S If indoor unit is equipped with an R--22 TXV or piston metering device, it must be changed to a hard--shutoff Puron refrigerant
TXV.
S Never open system to atmosphere while it is under a vacuum. S When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter
driers. Evacuate to 500 microns prior to recharging.
S Do not vent Puron refrigerant into the atmosphere. S Do not use capillary tube coils. S Observe all warnings, cautions,andbold text. S All indoor coils must be installed with a hard--shutoff Puron refrigerant TXV metering device.
15
Page 16
E2017 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Edition Date: 12/17
Manufacturer reserves the right to discontinue, or change at any ti me, specifications or designs without notice and without incurring obligations.
Catalog No. II180CNV--- 0 1
Replaces: New
16
Loading...