180B (2 -- 5 Ton)
EVOLUTIONr 20 AIR CONDITIONER
WITH PURONr REFRIGERANT
Product Data
TM
the environmentally sound refrigerant
Bryant’s air conditioners with Puronr refrigerant provide a
collection of features unmatched by any other family of
equipment. The 180B has been designed utilizing Bryant’s
Puronr refrigerant. The environmentally sound refrigerant allows
consumers to make a responsible decision in the protection of the
earth’s ozone layer.
This product has been designed and manufactured to meet
Energy Starr criteria for energy efficiency when matched with
appropriate coil components. Refer to the combination ratings in
the Product Data for system combinations that meet Energy Starr
guidelines.
NOTE: Ratings contained in this document are subject to
change at any time. Always refer to the AHRI directory
(www.ahridirectory.org) for the most up--to--date ratings
information.
INDUSTRY LEADING
FEATURES / BENEFITS
Efficiency
14 -- 20 SEER / 11.6 -- 14.5 EER
S
SMicrotube Technologyt refrigeration system
SIndoor air quality accessories available
Sound
Sound level as low as 66 dBA
S
SElectronic ECM ball bearing outdoor condenser fan
motor
SCompressor sound hood
SForward--swept condenser fan blade
SQuiet mount split post compressor grommets
deplete the ozone layer and low lifetime service cost.
SFront--seating service valves
S2--stage scroll compressor
SInternal pressure relief valve
SInternal thermal overload
SLow pressure switch
SHigh pressure switch
SFilter drier
SCrank case heater standard
SBalanced refrigeration system for maximum reliability
Durability
DuraGuard Plust protection package:
SSolid, Durable sheet metal construction
SSteel louver coil guard
SBaked--on, complete outer coverage, powder paint
Applications
SLong--line -- up to 250 feet (76.2 m) total equivalent
length, up to 200 feet (60.96 m) condenser above
evaporator, or up to 80 ft. (24.38 m) evaporator above
condenser (See Longline Guide for more information.)
MODEL NUMBER NOMENCLATURE
1234 5 678910111214
NNNAA/NNNNNA/NA/NNA
180B N A036000A
Product
Famil y
1=AC8=
the environmentally sound refrigerant
180B
TierSEERMajor
0=21
Evolution
Series
SEER
Nominal
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
Series
VoltageVariation sCoolin g CapacityOpenOpenOpenMinor
B=PuronN=
208--- 230--- 1
A=
Standard
0=Not
Defined0=Not
Defined
This product has been designed and manuf actured t o
meet En ergy St ar® criteria for energy efficiency when
matched with appropriate coil components. However,
proper refrigerant charge and proper air flow are critical
to achieve rated capacity and efficiency. Installation of
this product should f ollow all manufacturing refrigerant
charging and air flow instructions. Failure to confirm
proper charge an d air flow may reduce energy
efficiency and shorten equ ipment life.
Liquid Line Sizing and Maximum Total Equivalent Lengths
The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between indoor and
outdoor units.
See Table below for liquid line sizing and maximum lengths :
Maximum Total Equivalent Length
Outdoor Unit BELOW Indoor Unit
Liquid
Size
024
AC with
Puron
036
AC with
Puron
048
AC with
Puron
060
AC with
Puron
* Maximum actual length not to exceed 200 ft (61 m)
{ Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
--- --- = o u t s i d e a c c e p t ab l e r an g e
Size
024
AC with
Puron
036
AC with
Puron
048
AC with
Puron
060
AC with
Puron
* Maximum actual length not to exceed 200 ft (61 m)
{ Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
Liquid Line
Connection
3/8
3/8
3/83/8250*250*250*250*250*250*230160--- ---
3/83/8250*250*250*225*190150110--- ------ ---
Liquid Line
Connection
3/8
3/8
3/83/8250*250*250*250*250*250*250*250*
3/83/8250*250*250*250*250*250*250*250*
Line
Diam.
w/TXV
1/47575755050--- ------ ------ ------ ---
5/16250*250*250*250*250*225*175125100
3/8250*250*250*250*250*250*250*250*250*
5/1617515015010010010075--- ------ ---
3/8250*250*250*250*250*250*250*250*250*
Liquid
Diam.
w/TXV
(0--- 1.5)
Line
1/4100125175200225*250*250*250*
5/16250*250*250*250*250*250*250*250*
3/8250*250*250*250*250*250*250*250*
5/16225*250*250*250*250*250*250*250*
3/8250*250*250*250*250*250*250*250*
AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit BELOW Indoor
0 --- 5
6 --- 1 0
(1.8--- 3.0)
11--- 20
(3.4--- 6.1)
Maximum Total Equivalent Length
Outdoor Unit ABOVE IndoorUnit
AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit ABOVE Indoor
25
(7.6)
26--- 50
(7.9--- 15.2)
{
for Cooling Only Systems with Puronr Refrigerant:
Vertical Separation ft (m)
21--- 30
(6.4--- 9.1)
51--- 75
(15.5--- 22.9)
31--- 40
(9.4--- 12.2)
Vertical Separation ft (m)
76--- 100
(23.2--- 30.5)
41--- 50
(12.5--- 15.2)
101--- 125
(30.8--- 38.1)
51--- 60
(15.5--- 18.3)
126--- 150
(38.4--- 45.7)
61--- 70
(18.6--- 21.3)
151--- 175
(46.0--- 53.3)
71--- 80
(21.6--- 24.4)
176--- 200
(53.6--- 61.0)
180B
Liquid Line SizePuron Charge oz/ft (g/m)
3/8
5/160.40 (11.83)
1/40.27 (7.98)
Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line. The factory charge for 3/8” lineset 9 oz.(266.16 g). When using other length
or diameter liquid lines, charge adjustments are required per the chart above.
Charging
Formula:
[(Lineset oz/ft x total length) – (factory charge for lineset)] = charge adjustment
Example 1: System has 15 ft of line set using existing 1/4“ liquid line. What charge adjustment is required?
Formula:(.27 oz/ft x 15ft) – (9 oz) = (-4.95) oz.
Net result is to remove 4.95 oz of refrigerant from the system
Example 2: System has 45 ft of existing 5/16” liquid line. What is the charge adjustment?
Formula:(.40 oz/ft. x 45ft) – (9 oz.) = 9 oz.
Net result is to add 9 oz of refrigerant to the system
REFRIGERANT CHARGE ADJUSTMENTS
0.60 (17.74)
(Factory charge for lineset = 9 oz / 266.16 g)
3
LONG LINE APPLICATIONS
An application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintain acceptable
refrigerant management for systems reliability. See Accessory Usage Guideline table for required accessories. Defining a system as long line
depends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units.
For Air Conditioner systems, the chart below shows when an application is considered Long Line.
AC WITH PURONr REFRIGERANT LONG LINE DESCRIPTION ft (m)
Beyond these lengths, long line accessories are required
Liquid Line SizeUnits On Same LevelOutdoor Below IndoorOutdoor Above Indoor
1/4
5/16120 (36.6)50 (15.2) vertical or 120 (36.6) total120 (36.6)
3/880 (24.4)35 (10.7) vertical or 80 24.4) total80 (24.4)
Note: SeeLongLineGuidelinefordetails
No accessories needed within allowed
lengths
No accessories needed within allowed
lengths
175 (53.3)
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line
diameters shown in the chart below are acceptable for AC systems with Puron refrigerant:
180B
Nominal
Size (Btuh)
2 --- St a g e
Puron
2 --- St a g e
Puron
2 --- St a g e
Puron
2 --- St a g e
Puron
Applications in this area may be long line and may have height restrictions. See the Residential Piping and Long Line Guideline.
— Applications in this area are not recommended due to insufficient oil return
Vapor Line Sizing and Cooling Capacity Losses — Puronr Refrigerant 2--Stage Air Conditioner Applications
Unit
024
AC
036
AC
048
AC
060
AC
Maximum
Liquid
Line
Diameters
(In. OD)
3/8
3/8
3/8
3/8
Vapo r Line
Diameters
(In.) OD
5/8011233445
3/4000011111
7/8000011111
5/812456791011
3/4001122334
7/8000011112
3/4122345677
7/8011222333
1 --- 1/800———————
3/412456791011
7/8012234455
1 --- 1/8000111111
26---50
(7.9--- 15.2)
51---80
(15.5--- 24.4)
81---100
(24.7--- 30.5)
Cooling Capacity Loss (%)
Total Equivalent Line Length ft. (m)
101---125
(30.8--- 38.1)
126---150
(38.4--- 45.7)
151---175
(46.0--- 50.3)
176---200
(53.6--- 60.0)
201---225
(61.3--- 68.6)
PHYSICAL DATA
Model180BNA
Unit Size -- - Series024---A036--- B048---A060--- A
Operating Weight lb (kg)323 (147)324 (147)325 ( 147)350 (159)
Shipping Weight lb (kg)368 (167)368 (167)370 ( 168)394 (179)
Compressor Ty pe2 --- Stage S c r o l l
REFRIGERANTPuronr (R --- 410A)
Air DischargeVertical
Air Qty (CFM)3000 / 36373124 / 37003703 / 43044209 / 4668
Motor HP1/51/51/51/5
Motor RPM628 / 752582 / 669659 / 765742 / 828
COND COIL
Face Area (Sq ft)30.1830.1830.1830.18
Fins per In.20202020
Rows2222
Circuits9999
VALVECONNECT.(In.ID)
Vapor7/87/87/87/ 8
Liquid3/8
REFRIGERANT TUBES (In. OD)
Rated Vapor*7/87/81 --- 1/81 --- 1/8
Liquid3/8
*Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
226---250
(68.9--- 76.2)
4
ELECTRICAL DATA
UNIT
MODEL
180BNA
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30_C, consult table 310 --- 16 of the NEC (NFPA 70) . The ampacity of non---metallic--- sheathed cable (NM), trade
name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 336--- 26. If other th a n u ncoated ( no---plated), 60 or 75_C insulation, copper
wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is u sed, consult applicable tables of the NEC (NFPA 70).
}Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%.
* * T i m e --- D e l a y f u s e .
FLA --- Ful l L o a d A m ps
LRA --- L o c k e d R o t or A mps
MCA --- Minimum Circuit Amps
RLA ---RatedLoadAmps
NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
Complies with 2010 requirements of ASHRAE Standards 90.1
All motors/compressors contain internal overload protection.
V --- P H --- H z
OPER
VOLTS*
MAXMINLRARLAFLA60°C75°C60°C75°C
253197
COMPRFA N
MCA
52.010.301.414.314.0014.0055 (16.8)52 (15.9)20
MIN
WIRE
SIZE{
MIN
WIRE
SIZE{
MAX
LENGTH
ft (m)}
MAX
LENGTH
ft (m)}
MAX
FUSE*
*or
CKT
BRK
AMPS
A--WEIGHTED SOUND POWER (dBA)
UNIT SIZE
180BNA024 ---A
180BNA036 ---B
180BNA048 ---A
180BNA060 ---A
NOTE: Tested in accordance with AHRI Standard 270---08. (Not listed with AHRI).
STANDARD
RATING (dBA)
* 6 9 --- l ow s t a g e46.552.559.065.054.553.047.5
7 1 --- hig h s t a g e48.554.563.059.558.058.554.5
* 6 9 --- l ow s t a g e49.053.561.563.056.553.549.5
7 2 --- hig h s t a g e49.555.567.063.557.553.056.0
* 6 6 --- l ow s t a g e47.556.061.559.056.052.550.0
7 1 --- hig h s t a g e48.559.066.064.558.557.054.5
* 6 9 --- l ow s t a g e50.559.063.062.558.558.055.0
7 2 --- hig h s t a g e53.560.565.067.060.058.554.5
1252505001000200040008000
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
180B
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE --- SERIES
180BNA024 ---A
180BNA036 ---B
180BNA048 ---A
180BNA060 ---A
REQUIRED SUBCOOLING _F(_C)
9 (5.0) HIGH STAGE
12 (6.7) HIGH STAGE
14 (7.8) HIGH STAGE
16 (8.9) HIGH STAGE
5
ACCESSORIES
KIT NUMBERKIT NAME024---A036 --- B048---A060- -- A
KSAHS2301AAAHARD START KITX
KSAHS2401AAAHARD START KITX
KSAHS2501AAAHARD START KITX
KSAHS2601AAAHARD START KITX
KSASF0101AAASUPPORT FEETXXXX
KSATX0201PURTXVX
KSATX0301PURTXVX
KSATX0401PURTXVX
KSATX0501PURTXVX
x = Accessory
CONTROLS
CONTROLDESCRIPTION
SYSTXBBUID01 --- DEvolution Control Deluxe 7 ---Day Programmable (Wall --- mounted system control.)
SYSTXBBUIZ01 ---DEvolution Control Deluxe Zoning 7 ---Day Programmable (Wall--- mounted control for a multi--- zone system.)
SYSTXBB4ZC01Evolution 4--- Zone Damper Control Module (Wall---mounted control for a four---zone system.)
SYSTXBBSMS01Evolution Smart Sensor (Optional wall control used to monitor temperature and/or fan control in an individual zone.)
SYSTXBBRRS01E volution Remote Room Sensor (Monitors temperature in an individual zone.)
SYSTXBBRWF01Evolution System Access Module (Hardware for wireless access an d control via phone or internet.)
180B
SYSTXBBNIM01Evolution Network Interface Module (Connects Heat Recovery and Energy Recovery Ventilators on non--- zoning applications.)
SYSTXBBLBPU01 --- CDecorative Back Plate for Evolution Control (Decorative wall plate.)
THERMOSTATS
THERMOSTAT / SUBBASE
PKG.
T 6 --- P R H 01 --- AProgrammable Thermidistat
T 6 --- N R H 01 --- ANon --- programmable Thermidistat
T 6 --- PA C 0 1Preferred Series Programmable AC Stat
T 6 --- N A C 01Preferred Series Non---programmable AC Stat
TSTATXXSEN01--- BOutdoor Air Temperature Sensor
DESCRIPTION
6
ACCESSORY USAGE GUIDELINE
REQUIRED FOR
ACCESSORY
Compressor Start Assist KitNoYe sNo
Crankcase Heater
Evaporator Freeze ProtectionStandard with Evolution ControlNoNo
Liquid--- Line Solenoid ValveNoNoNo
Low--- Ambient ControlStandard with Evolution ControlNoNo
Puron Refrigerant Balance Port Hard---
* For tubing set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential (total equivalent len gth), refer to the Long
Line Guideline—Air Conditioners and Heat Pumps using Puron® Refrigerant.
{ Required on all indoor units. Standard on all new Puron refrigerant fan coils and furnace coils.
ShutOff TXV
Support FeetRecommendedNoRecommended
Winter Start ControlStandard with Evolution ControlNoNo
L O W --- A M B I E N T C O O L I N G
APPLICATIONS
(Below 55°F/12.8_C)
Ye s
(standard on some units)
Ye s{
REQUIRED FOR LONG LINE
APPLICATIONS*
Ye s
(standard on some units)
Ye s{
REQUIRED FOR SEA COAST
APPLICATIONS
(Within 2 miles/3.22 km)
No
Ye s{
Accessory Description and Usage (Listed Alphabetically)
1. Compressor Start Assist -- Capacitor and Relay
Start capacitor and relay gives a ”hard” boost to compressor
motor at each start up.
Usage Guideline:
Required for reciprocating compressors in the
following applications:
Long line
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil
Required for single--phase scroll compressors in the
following applications:
Long line
Suggested for all compressors in areas with a history of
low voltage problems.
2. Crankcase Heater
An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles.
Improves compressor lubrication on restart and minimizes the
chance of liquid slugging.
Usage Guideline:
Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.
3. Outdoor Air Temperature Sensor
Designed for use with Bryant Thermostats listed in this
publication. This device enables the thermostat to display the
outdoor temperature. This device also
is required to enable special thermostat features such as auxiliary
heat lock out.
Usage Guideline:
Suggested for all Bryant thermostats listed in this
publication.
4. Support Feet
Four stick--on plastic feet that raise the unit 4 in. (101.6 mm)
above the mounting pad. This allows sand, dirt, and other debris
to be flushed from the unit base, minimizing corrosion.
Usage Guideline:
Suggested in the following applications:
Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.
For improved sound ratings.
5. Thermostatic Expansion Valve (TXV)
A modulating flow--control valve which meters refrigerant liquid
flow rate into the evaporator in response to the superheat of the
refrigerant gas leaving the evaporator.
Kit includes valve, adapter tubes, and external equalizer tube.
Hard shut off types are available.
NOTE: When using a hard shut off TXV with single phase
reciprocating compressors, a Compressor Start Assist Capacitor
and Relay is required.
Usage Guideline:
Required to achieve AHRI ratings in certain equipment
combinations. Refer to combination ratings.
Hard shut off TXV or LLS required in air conditioner
long line applications.
Required for use on all zoning systems.
180B
7
180B
DIMENSIONS -- 180BNA 2--5 TON (ENGLISH)
8
180B
DIMENSIONS -- 180BNA 2--5 TON (SI)
9
Wall
6”
A07833
(152.4)
180B
24”
Wall
Clearances (various examples)
Service
12”
(304.8)
6”
Wall
(152.4 mm)
12”
(304.8)
12”
(304.8)
12”
(304.8)
Wall
24”
(609.6)
24”
(609.6)
24”
(609.6)
Service
24”
(609.6)
Service
24”
(609.6)
Service
24”
CLEARANCES
(609.6)
Service
10
24”
(609.6)
Note: Numbers in ( ) = mm
IMPORTANT: When installing multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent re--circulation of discharge air.
TESTED AHRI COMBINATION RATINGS
NOTE: Ratings contained in this document are subject to change at any time.
For AHRI ratings certificates, please refer to the AHRI directory www.ahridirectory.org
Additional ratings and system combinations can be accessed via the Bryant database at:
* AHRI = Air Conditioning, Heating & Refrigeration Institute
EER — Energy Efficiency Ratio
SEER — Seasonal Energy Efficiency Ratio
TDR — Time---Delay Relay. In most cases, only 1 method should be used to achieve TDR function. Using more than 1 method in a system may cause
UI— User Interface
NOTES:
1. Ratings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included.
2. Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for central air conditioners. Ratings for other combinations
3. Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature.
4. Do not apply with capillary tube coils as performance and reliability are affected.
degradation in performance. Use either the accessory Time--- Delay Relay KAATD0101TDR or a furnace equipped with T DR. Most Bryant furnaces are
equipped with TDR.
are determined under DOE computer simulation procedures.
Indoor Coil Model
Number
Furnace Model Number
Cooling
Capacity
AHRI Standard Ratings --- Cooling
EERSEER
HighLow
ID CFM
180B
11
Sys.
Tot a l
KW**
Sys.
Tot a l
KW**
180B
Capacity MBtuh
Sys.
Tot a l
KW**
Capacity MBtuh
Sys.
Tot a l
KW**
Capacity MBtuh
Sys.
Tot a l
KW**
Capacity MBtuh
Sys.
Tot a l
KW**
Capacity MBtuh
Sys.
Tot a l
KW**
Capacity MBtuh
Sys.
Tot a l
KW**
CONDENSER ENTERING AIR T EMPERATURES ° F (° C)
Capacity MBtuh
180BNA024****A Outdoor Section With FE5ANB004 Indoor Section HI
(245 kW) per 1000 C FM (480 L/S) of indoor coil air for each degree below 80_F(27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F(27_C).
may occur.
{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
} Sensible capacities shown are based on 80_F(27_C) entering air at the indoor coil. For sensible capacities at other than 80_F(27_C), deduct 835 Btuh
# Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210/240---2008. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity
** System kw is total of indoor and outdoor unit kilowatts.
EWB — Entering Wet Bulb
DETAILED COOLING CAPACITIES# (CONTINUED)
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
Outdoor--mounted, air--cooled, split--system air conditioner unit
suitableforground or rooftop installation.Unitconsistsof a hermetic
compressor, an air--cooled coil, propeller--type condenser fan, and a
control box. Unit will discharge supply air upward as shown on
contract drawings. Unit willbe used ina refrigeration circuit to match
up to a packaged fan coil or coil unit.
Quality Assurance
— Unit will be rated in accordance with the latest edition of
AHRI Standard 210.
— Unit will be certified for capacity and efficiency, and
listed in the latest AHRI directory.
— Unit construction will comply with latest edition of
ANSI/ ASHRAE and with NEC.
— Unit will be constructed in accordance with UL
180B
standards and will carry the UL label of approval. Unit
will have c--UL approval.
— Unit cabinet will be capable of withstanding Federal Test
Method Standard No. 141 (Method 6061) 500--hr salt
spray test.
— Air--cooled condenser coils will be leak tested and
pressure tested.
— Unit constructed in ISO9001 approved facility.
Delivery, Storage, and Handling
— Unit will be shipped as single package only and is stored
and handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
— U.S. and Canada only.
PRODUCTS
Equipment
— Factoryassembled,singlepiece,air--cooled air
conditioner unit. Contained within the unit enclosure is
all factory wiring, piping, controls, compressor,
refrigerant charge Puronr (R--410A), and special features
required prior to field start--up.
Unit Cabinet
— Unit cabinet, including louvered coil guard, will be
constructed of galvanized steel, bonderized, and coated
with a powder coat paint.
Fans
— Condenser fan will be direct--drive propeller type,
discharging air upward.
AIR--COOLED, SPLIT--SYSTEM AIR CONDITIONER
180B
2 TO 5 NOMINAL TONS
— Condenser fan motors will be totally enclosed, 1--phase
type with class B insulation and permanently lubricated
bearings. Shafts will be corrosion resistant.
— Fan blades will be statically and dynamically balanced.
— Condenser fan openings will be equipped with coated
steel wire safety guards.
Compressor
— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration
isolators.
Condenser Coil
— Condenser coil will be air cooled.
— Coil will be constructed of aluminum fins mechanically
bonded to copper tubes which are then cleaned,
dehydrated, and sealed.
Refrigeration Components
— Refrigeration circuit components will include liquid--line
shutoff valve with sweat connections, vapor--line shutoff
valve with sweat connections, system charge of Puronr
(R--410A) refrigerant, and compressor oil.
— Unit will be equipped with high--pressure switch, low
pressure switch and filter drier for Puron refrigerant.
Operating Characteristics
— The capacity of the unit will meet or exceed _____ Btuh
at a suction temperature of _____ _F/_C. The power
consumption at full load will not exceed _____ kW.
— Combination of the unit and the evaporator or fan coil
unit will have a total net cooling capacity of _____ Btuh
or greater at conditions of _____ CFM entering air
temperature at the evaporator at _____ _F/_C wet bulb
and _____ _F/_C dry bulb, and air entering the unit at
_____ _F/_C.
— The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
Electrical Requirements
— Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v to
_____ v.
— Unit electrical power will be single point connection.
— Control circuit will be 24v.
Special Features
— Refer to section of this literature identifying accessories
and descriptions for specific features and available
enhancements.
20
SYSTEM DESIGN SUMMARY
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01--in. wc.
2. This product is qualified for low ambient cooling operation (below 55_F/12.8_C) when used with an Infinity User Interface ONLY.
3. The maximum outdoor operating ambient in cooling mode is 125_F (51.67_C).
4. For reliable operation, unit should be level in all horizontal planes.
5. For interconnecting refrigerant tube lengths greater than 80 ft (23.4 m) and/or 35 ft (10.7 m) vertical differential, consult Residential
Piping and Longline Guideline and Service Manual available from equipment distributor.
6. If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubing
lengths up to 36 in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4
mm).
7. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector
provided.
8. Do not apply capillary tube indoor coils to these units.
9. Factory--supplied filter drier must be installed.
180B
21
180B
EBryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231Edition Date: 09/12
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. PDS180B---05