Bryan Boilers HE-CLM300-W-FDG, HE-CLM150, HE-CLM180, HE-CLM210, HE-CLM240 Brochure & Specs

...
Form No. 6700
Bryan “Flexible Water Tube”
HE-CLM Series Water Boilers
900,000 to 3,000,000 BTUH
Forced draft gas fi red
Quality Construction Features
A. Heavy steel boiler frame, built and stamped in accordance
with the ASME Boiler Code, Section IV.
B. Large volume water leg down comers promote rapid internal circulation, temperature equalization and effi cient heat transfer.
C. Bryan bent water tubes are fl exible, individually replaceable with­out welding or rolling. Never more than two tube confi gurations.
D. Boiler tube and furnace area access panel: heavy gauge steel casing with 2" high temperature ceramic fi ber and insulation, bolted and tightly sealed to boiler frame.
E. Jacket access panels make the interior of the boiler easily accessible for service and inspection.
F. Steel boiler jacket with 16 gauge rust-resistant zinc coating and attractive enamel fi nish, insulated with 1½" fi berglass to insure exceptionally cool outer surface.
G. Minimum sized fl ue vent.
H. Forced draft, fl ame retention head type burner. Effi cient
combustion and quiet operation.
I. All controls, gauges, relief valve(s) are factory installed and wired and easily accessible for servicing.
J. Electrical box: all controls installed and connected to terminal strip.
Model HE-CLM300-W-FDG
Guaranteed 85% effi ciency
• With HE-CLM Series Boilers, you get a guaranteed 85% combustion effi ciency result­ ing from a uniquely designed integrated extended surface heat extractor.
• What's more, HE-CLM Boilers offer high operating effi ciency—at all normal operation temperatures— without the complications of condensation concerns.
Bryan HE-CLM Series Boiler Specifi cations
BOILER INPUT OUTPUT @ 85% EFFICIENCY MODEL MBH (KW) MBH (KW) HP (KW) SQ.FT.(M2) LBS. (KG)
HE-CLM90 900 (264) 765 (224) 23 (224) 171 (15.9) 2,110 (957) HE-CLM120 1,200 (352) 1,020 (299) 30 (299) 227 (21.1) 2,400 (1,089) HE-CLM150 1,500 (440) 1,275 (374) 38 (374) 282 (26.2) 2,860 (1,297) HE-CLM180 1,800 (527) 1,530 (448) 46 (448) 338 (31.4) 3,200 (1,452) HE-CLM210 2,100 (615) 1,785 (523) 53 (523) 394 (36.6) 3,740 (1,697) HE-CLM240 2,400 (703) 2,040 (598) 61 (598) 451 (41.9) 4,200 (1,905) HE-CLM270 2,700 (791) 2,295 (672) 69 (672) 506 (47.0) 4,740 (2,150) HE-CLM300 3,000 (879) 2,550 (747) 76 (747) 564 (52.4) 5,175 (2,348)
NOTES : (1) Output and horsepower based on an average natural gas combustion effi ciency of 85%.
K. Water side interior accessible for cleanout and inspection, front and rear openings, upper and lower drums.
L. Steel plate boiler base with lightweight, high temperature insulating fi rebrick combustion chamber, designed for maximum combustion effi ciency.
(1)
HTG.SURFACE APPROX. SHIP
(Rev. 5/07)
BRYAN® BOILERS
Originators of the “Flexible Water Tube” design
Bryan HE-CLM Series Gas Fired Flexible Tube Boilers
Effi cient Water Tube Design
The Bryan Flexible Water Tube provides for extremely fast internal circulation for maximum heat transfer and operating effi ciency.
No “Thermal Shock”
The fl exibility of the bent water tube design eliminates all possible damage from “Thermal Shock” and from stresses caused by poor or unequal internal circulation. This is particu­larly important with forced hot water heating systems designed for higher temperatures and greater temperature drops.
Natural Internal Circulation
The water tube design and the large water leg downcomers provide adequate internal circulation without concern over ex­terior pumping conditions. Low pressure drop through boiler.
Compact — Minimum Floor Space
Requires less fl oor space than most boilers — minimum boiler room size.
Shipped completely assembled and wired. Tubes are easily removable and replaceable, requiring little
service space.
BOILER DIMENSIONS in inches (cm)
A B C D E* F G H I J K L BOILER Length Width Height
MODEL Of Outside Over NUMBER Jacket Jacket Jacket Clearance Burner Nozzle
HE-CLM90-W
HE-CLM120-W
HE-CLM150-W
(151.60) (87.94) (180.03) (212.72) (3.81) (7.62) (7.62) (30.48) (75.72) (76.2) (91.44) (193.51)
HE-CLM180-W
HE-CLM210-W
HE-CLM240-W
HE-CLM270-W
HE-CLM300-W
NOTE: * Gas train and control location dimensions will vary depending on job specifi cations and conditions.
Dimensions and specifi cations are subject to change without notice. Consult factory for certifi ed dimensions.
41 7/16 34 5/8 72 1/16 69 7/16 1 NPT 3 NPT 3 NPT 10 20 11/16 30 36 76 3/16
(105.24) (87.94) (180.03) (176.98) (2.54) (7.62) (7.62) (25.40) (52.54) (76.2) (91.44) (193.51)
50 11/16 34 5/8 72 1/16 78 11/16 11/4 NPT 3 NPT 3 NPT 10 25 5/16 30 36 76 3/16
(128.74) (87.94) (180.03) (199.86) (3.18) (7.62) (7.62) (25.40) (64.29) (76.2) (91.44) (193.51)
59 11/16 34 5/8 72 1/16 87 11/16 11/2 NPT 3 NPT 3 NPT 12 29 13/16 30 36 76 3/16
69 1/8 34 5/8 72 1/16 97
(175.57) (87.94) (180.03) (246.69) (5.08) (7.62) (7.62) (35.56) (87.78) (76.2) (91.44) (193.51)
78 3/8 34 5/8 72 1/16 106
(199.07) (87.94) (180.03) (270.19) (5.08) (7.62) (7.62) (35.56) (99.53) (76.2) (91.44) (193.51)
88 34 5/8 72 1/16 116 2 NPT 3 NPT 3 NPT 16 44 30 36 76 3/16
(223.52) (87.94) (180.03) (294.64) (5.08) (7.62) (7.62) (40.64) (111.76) (76.2) (91.44) (193.51)
97 34 5/8 72 1/16 125 2 NPT 3 NPT 3 NPT 16 481/2 30 36 76 3/16
(246.38) (87.94) (180.03) (317.50) (5.08) (7.62) (7.62) (40.64) (123.19) (76.2) (91.44) (193.51)
106 5/8 34 5/8 72 1/16 134 5/8 2
(270.82) (87.94) (180.03) (341.91) (6.35) (7.62) (7.62) (40.64) (40.64) (76.2) (91.44) (193.51)
Overall Gas Train Supply Return Flue Flue Length Connection Nozzle Nozzle Size Location
1
/8 2 NPT 3 NPT 3 NPT 14 34 9/16 30 36 76 3/16
3
/8 2 NPT 3 NPT 3 NPT 14 39 3/16 30 36 76 3/16
1
/2 NPT 3 NPT 3 NPT 16 53 3/16 30 36 76 3/16
Min. Tube Clearance for Floor to
Removal Servicing Flow
Bryan HE-CLM Series Boilers Standard and Optional Equipment
STANDARD EQUIPMENT:
Combination thermometer and pres­sure gauge, ASME-rated boiler relief valve, water temperature control (240°F max. std.), high limit control, probe LWCO. Electronic combustion safety control, automatic operating gas valve, safety gas valve, pilot solenoid valve, pilot ignition assembly, main manual gas shut-off valve, pilot cock, pilot and main gas pressure regulators, air safety switch, control panel, all controls installed and wired.
Form No. 6700 ©2007 Bryan Steam LLC Printed in USA
57-8782
OPTIONAL EQUIPMENT:
1. Manual reset high limit control
2. Manual reset low water cutoff
3. Auxiliary low water cutoff
4. Combination low water cutoff and feeder
5. Alarm bells or horns
6.
UL, CUL, CSD-1, FM, IRI
surance approved control systems
7. Control panel mounted on boiler
8. Indicating lights, as desired
9. Lead-lag systems for two or more boilers with or without outdoor
reset control
10. Draft control system
11. Special construction and knocked down
OPTIONAL CONSTRUCTION:
Optional construction to ASME Power Boiler Code requirements for tempera-
or other in-
tures exceeding 240°F and/or pres­sure exceeding 160 psi to maximum of 285°F operating and 300°F design temperature and 250 psi.
Bryan Steam LLC Leaders Since 1916
783 N. Chili Ave., Peru, Indiana 46970 U.S.A. Phone: 765-473-6651 • Internet:www.bryanboilers.com
Fax: 765-473-3074
E-mail: bryanboilers@iquest.net
When ordering, please specify:
1. Boiler size
2. Supply and return temperatures required
3. Boiler relief valve setting
4. Type of fuel: natural, LP, or other gas
5. Gas BTU content, specifi c gravity and pressure
available
6. Electric power voltage,
phase and frequency
7. Optional extra equipment
or construction
8. Special approvals required (UL, CUL, CSD-1, FM, or IRI)
9. Altitude
Loading...