1.1Important Information ......................................................................................................................................... 6
1.2Disclaimers and Local Codes .............................................................................................................................. 6
1.3Test and Inspections .............................................................................................................................................. 7
2.2Boiler Foundation ................................................................................................................................................ 10
2.3Clearances and Serviceability ......................................................................................................................... 10
3.1Receiving The Boiler ........................................................................................................................................... 12
3.2.7.1Drip Leg .................................................................................................................................................. 14
3.2.7.2Gas Piping Leak Test ......................................................................................................................... 14
3.2.7.3Venting of Gas Train Components ............................................................................................... 14
3.3Combustion Air Supply System ...................................................................................................................... 14
3.3.1Combustion Air Openings: ....................................................................................................................... 15
3.3.1.3Mechanical Air Supply Systems .................................................................................................... 15
3.3.2Louvers, Grilles, and Screens .................................................................................................................. 16
3.3.2.1Louvers and Grilles: ........................................................................................................................... 16
3.3.2.4Combustion Air Ducts ....................................................................................................................... 16
3.3.3Ducted Combustion Air ............................................................................................................................. 17
3.4.1Category II Venting ..................................................................................................................................... 19
3.5.4.4Water Flow Rates for Glycol .......................................................................................................... 27
3.6Before Placing Boiler In Operation ............................................................................................................... 27
3.6.1Pre-Boil Out Flushing Of System ........................................................................................................... 27
3.6.2Boil Out Procedure ..................................................................................................................................... 27
3.7Draining and refilling the boiler & system ................................................................................................ 28
3.7.1Filling The System ....................................................................................................................................... 28
3.7.2Hydrostatic Test Of Boilers And System ............................................................................................ 28
3.8Boiler Water Treatment .................................................................................................................................... 29
3.8.1Purpose of water treatment .................................................................................................................... 29
4.3Power the Boiler: ................................................................................................................................................. 31
4.4Power the Circulators: ....................................................................................................................................... 31
4.5Pressurize the Fuel System: ............................................................................................................................. 31
Appendix A Sizing Gas Piping ........................................................................................................................................... 48
Appendix B Vent and Combustion Air Pressure Drop Data ................................................................................. 50
Appendix C Installation & Startup Report ................................................................................................................... 51
Appendix D Venting Diagrams ......................................................................................................................................... 52
Appendix E Combustion Air Diagrams ......................................................................................................................... 54
Appendix E.1 Typical Horizontal Air Intake Piping ............................................................................................ 54
Appendix E.2 Typical Vertical Air Intake Piping .................................................................................................. 55
Appendix F Boiler Piping Diagrams ............................................................................................................................... 56
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web:www.bryanboilers.com
Appendix F.5 Multiple Boilers, Primary / Secondary Piping, Heating with Domestic Hot Water ... 60
Appendix F.6 Multiple Boilers, Primary / Secondary Piping, Heating with Domestic Hot Water
Appendix G Water Flow Pressure Drops ..................................................................................................................... 62
Appendix H Wiring Diagrams ........................................................................................................................................... 63
Appendix H.2 FF1500 To FF3000 115 VAC Single Phase Wiring Diagram ............................................... 65
Appendix H.3 FF1500 To FF3000 208 – 230 VAC Single Phase Wiring Diagram .................................. 66
Appendix H.4 FF2000 To FF3000 208-460 VAC Three Phase Wiring Diagram...................................... 68
Appendix I Repair Parts ...................................................................................................................................................... 70
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
1 Introduction
1.1 Important Information
The following terms are used throughout this
manual to bring attention to the presence of
hazards of various risk levels, or to important
information concerning product life. It is
critical that all personnel read and follow all
the information provided in the boxes marked
DANGER, WARNING, CAUTION, and
NOTICE.
DANGER
Indicates an imminently hazardous
situation, which, if not avoided, will result
in death, serious injury or substantial
property damage
.
WARNING
Indicates a potentially hazardous
situation, which, if not avoided, could
result in death, serious injury or
substantial property damage.
CAUTION
Indicates a potentially hazardous
situation, which, if not avoided, may result
in moderate or minor injury or property
damage.
1.2 Disclaimers and Local Codes
Installation must conform to the requirements
of the authority having jurisdiction. In the
absence of such requirements, installation
must conform to the National Fuel Gas Code, NFPA 54/ANSI Z223.1, and/ or
CAN/CGA B149 Installation Codes. Where
required by the authority having jurisdiction,
the installation must conform to the Standard
for Controls and Safety Devices for Automatically
Fired Boilers, ANSI/ ASME CSD-1.
Installation, start-up, and maintenance of this
equipment can be hazardous and requires
trained, qualified installers and service
personnel. Do not install, operate, service or
repair any components of this equipment
unless you are qualified and fully understand
all requirements and procedures. Trained
personnel refer to those who have completed
Bryan Steam Service School training specific
to this product.
The boiler heat exchanger is manufactured
and stamped in accordance with ASME Boiler
and Pressure Vessel Code, Section IV for a
maximum allowable working pressure and
operating temperature of 160 psig (1103 kPa)
and 210 F(99 C) respectively. Aqua-stat is
factory set at 200 F (93 C).
NOTICE
Post these instructions and maintain in
legible condition.
NOTICE
Indicates specific instructions on
installation, operation, or maintenance,
which are important but not related to
personal injury hazards.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
1.3 Test and Inspections
Upon the completion of boiler installation,
final air-fuel adjustments are to be made by
factory trained service personnel. The
emissions data and the O2 levels at minimum
and maximum input rate can be found on the
back side of the front-boiler’s door, which can
be referenced in the future by the boiler
operator(s) when troubleshooting and
servicing the boiler. In addition, the following
tests and inspections are made on each boiler
at the factory to ensure it meets our highest
safety and functionality standards.
ASME hydrostatic test inspection
Electrical components inspection
Operating & efficiency test
Final engineering inspection
Crating inspection
Danger
DO NOT store or use gasoline or other
flammable vapors or liquids in the vicinity
of this or any other appliance.
If you smell gas vapors, DO NOT try to
operate any appliance—DO NOT touch
any electrical switch or use any phone in
the building. Immediately, call the gas
supplier from a remotely located phone.
Follow the gas supplier’s instructions or if
the supplier is unavailable, contact the fire
department.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
1.4 Component Description
1. Touchscreen display. The display
provides easy access for viewing and
adjusting boiler operational parameters,
monitoring historical performance
characteristics and annunciating boiler
alarm/lockout conditions.
2. Boiler On/Off switch.
3. Manual gas shutoff valve. The boiler is
equipped with two manual gas shut off
valves, one located on the incoming gas
supply line outside of the boiler, and the
other downstream of the main gas valve.
4. Main gas supply connection.
5. Pressure relief valve. The pressure relief
protects the heat exchanger from an overpressure condition.
6. Ducted combustion air flange.
7. Flue gas vent outlet. The boiler comes
with a standard AL 29-4C® stainless steel
vent connection.
11. Supply water connection. A 3” diameter
Victaulic grooved connection is provided
on the FF1000. A 3”, 150# class, flange
is provide on the FF1500 – 3000.
12. Air vent. The boiler is provided with an
internal dip tube that traps liberated air
from the boiler water. The air vent allows
the trapped air to escape from the boiler.
13. Boiler reset push button.
14. Boiler water temperature gauge.
15. Boiler water pressure gauge.
8. Boiler water flow switch. The boiler
water flow switch is adjustable within the
parameters listed in Table 1.
Settings
Switch
Closed
Open
Minimum 18
Maximum 50
Table 1Water Flow Switch Settings
9. Return water connection. A 3” diameter
Victaulic grooved connection is provided
on the FF1000. A 3”, 150# class, flange
is provide on the FF1500 – 3000.
10. Cleanout and inspection. A 3” diameter
Victaulic grooved connection is provided
for inspecting and cleaning sediment from
the heat exchanger.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
2 Pre-Installation
The customer should examine the equipment
for any damage. It is the responsibility of the
installer to ensure all parts supplied with the
equipment are fitted in a correct and safe
manner.
WARNING
This boiler requires regular maintenance
and service to operate safely. Follow the
instructions contained in this manual.
WARNING
Improper installation, adjustment,
alteration, service, or maintenance can
cause property damage, personal injury or
loss of life. Read and understand the
entire manual before attempting
installation, start-up operation, or service.
Only an experienced, skilled installer or
service agency must perform installation
and service.
WARNING
This boiler must be properly vented.
WARNING
This boiler needs fresh air for safe
operation and must be installed so there
are provisions for adequate combustion
and ventilation air.
B149 Installation Codes. Where required by
the authority having jurisdiction, the
installation must conform to the Standard for
Controls and Safety Devices for Automatically
Fired Boilers, ANSI/ ASME CSD-1.
2.2 Boiler Foundation
Before uncrating, the boiler location should
be prepared. The boiler should set upon a
good level concrete floor. If the boiler is not
level or the floor is not in good condition, a
concrete foundation should be built, the
dimensions being larger than the outside
dimensions of the boiler base. A 4” high
housekeeping pad is suggested.
WARNING
Do not install boiler on combustible
flooring.
2.3 Clearances and Serviceability
See Figure 3 and Table 2 for minimum
clearances to walls, ceilings, or obstructions.
These clearances are intended as a general
recommendation only. Local codes must be
applied to specific installations and the
minimum clearances established accordingly.
Provisions must also be made for service,
accessibility and clearance for piping and
electrical connections. Do not obstruct
combustion air and ventilation openings with
piping or any other construction. All boilers
must be installed in a space that is large
compared to the boiler.
2.1 Installation Conformance
Installation must conform to the requirements
of the authority having jurisdiction. In the
absence of such requirements, installation
must conform to the National Fuel Gas Code,
NFPA 54/ANSI Z223.1, and/ or CAN/CGA
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
3 Installation
3.1 Receiving The Boiler
The boiler is shipped from the factory with
(4) shipping feet/legs bolted to the skids.
These are provided to facilitate unloading
/moving with a forklift. Lifting points are
also provided to enable over-head lifting with
spreader bars to prevent damage to the boiler.
The shipping feet/legs MUST BE
REMOVED after the boiler is set in-place on
its concrete foundation before any
piping/electrical connections are made. It is
recommended that the plastic protective
cover be left on as long as possible to reduce
finish damage from the installation.
3.2 Boiler Connections
Do not run any pipes along the tube access
panel side of the boiler. Maintain clearances
as shown on the dimensional drawing for
servicing of the boiler tubes. All piping
should be designed and installed to avoid any
loadings on the boiler connections or piping.
3.2.1 Flow Connection
The system supply and return flow
connections are shown on Figure 1. A gate
valve should be installed on the boiler outlet
and inlet lines. This allows the boiler to be
isolated from the heating system for draining
and servicing.
3.2.2 Safety Relief Valves
Safety relief valve(s) are shipped loose.
Connections are provided in the top of the
boiler for the safety relief valve(s). The safety
relief valve discharge piping must be the same
size as the safety relief valve discharge
opening and run to a point of safe discharge.
No shutoff valves are to be placed between
the relief valve and the appliance or in the
discharge piping. Avoid over-tightening as
this can distort valve seats. All piping from
the safety relief valve(s) must be
independently supported with no weight
carried by the valve.
NOTICE
If the relief valve discharges periodically,
this may be due to thermal expansion in a
closed water supply system. Contact the
water supplier or local plumbing inspector
on how to correct this situation. DO NOT
PLUG THIS RELIEF VALVE.
3.2.3 Minimum Relief Valve Settings
The minimum relief valve setting for standard
systems shall be 30 psig. The system shall
operate with no less than 26 psig at all times.
For systems designed to operate at delta T’s
greater than 40°F, the boiler shall be equipped
with a minimum relief valve setting of 60 psig.
The system shall operate with no less than 50
psig at all times. This will prevent boiler
water hammer.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Connection(s) to an expansion tank are to be
provided by others in the system piping
separate from the boiler.
3.2.5 Drain Connection
A drain valve must be installed on the boiler
drain connection, the same pipe size as this
connection, to allow draining of the boiler.
Form: 2435
13
Table 3: Typical Condensate Flow Rate
Model
Max Condensate Flow (gph)
FF1000
7
FF1500
10.5
FF2000
16
FF2500
21.5
FF3000
27
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
3.2.6 Condensate Drain Connection
A condensate drain trap is shipped with the
boiler and is provided with a 1” nps
connection to drain the condensed products
of combustion from the boiler. Pipe with
continuous Teflon, high temperature silicone
tubing, or other tubing material compatible
with flue gas condensate. The condensate
temperature should never exceed 212o F and
the pH of the condensate should never have a
value lower than 3.5. NO VALVE is to be
installed in this line from the boiler to point
of discharge.
The condensate drain trap should be flushed
with water as part of your boiler maintenance
schedule to remove any debris that might
have accumulated over time.
A common condensate pump/sump may be
used. Run separate piping from each
condensate drain to the sump. A common
drain may be used to discharge condensate
from the sump. Consult pump/sump
materials of construction. If a common sump
is used, individual drain lines should be
connected such that one drain cannot back
feed into another drain. Use Table 3 for
sizing the pump / sump.
CAUTION
Failure to properly pipe the condensate
system will greatly reduce boiler life. Do
not install plugs, caps, or valves on
condensate piping.
Do not manifold boiler condensate and
vent drains together.
Do not crimp condensate lines or reduce
drain line inner diameter size.
3.2.6.1 FF1000 Condensate Drain Trap
Ensure that the condensate drain trap is filled
with water prior to running the boiler to
prevent flue gas emission to the boiler room.
It is recommended that the personnel
responsible for running and maintaining the
boiler periodically check the water level in the
condensate drain trap bend, especially, when
the boiler is operating in a non-condensing
condition for an extended period of time.
Consult local authorities regarding disposal of
flue gas condensate into public waste water
system. Some jurisdictions require that
condensate be buffered before discharge. This
buffering is commonly achieved by draining
the condensate through a limestone bed.
Consult Bryan Steam or a chemical treatment
company for buffering system.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
1. Union Connection to the boiler
condensate drain line
2. Removable cleaning plug
3. Condensate drain outlet connection
3.2.6.2 FF1500 – 3000 Condensate Drain
Trap
Form: 2435
14
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
After completion of the gas-piping hookup,
the installation must be checked for leaks.
Leaks shall be checked using a soap and water
solution. All joints up to the main motorized
gas valve shall be checked. A pressure gauge
shall be installed down stream of the main
motorized gas valve and up stream of the
manual gas shutoff valve in the closed
position to ensure the main motorized valves
are not leaking by. During commissioning,
Figure 5: FF1500 - 3000 Condensate Drain
Trap
the remainder of the gas train joints down
stream of the main motorized gas valve shall
be tested for leaks.
1. 1” npt outlet connection
2. Trap vent connection (tubing not shown
for clarity)
3. 2” threaded cleanout
4. Float ball
3.2.7 Gas Supply Connection
The installation must conform completely to
the requirements of the authority having
jurisdiction, or in the absence of such,
requirements shall conform in the U.S. to the
current National Fuel Gas Code, ANSI
Z223.1-1984, or in Canada to the current
Natural gas and propane installation code
(CAN/CSA B149.1-05), and applicable
regional regulations for the class; which
should be followed carefully in all cases.
Authorities having jurisdiction should be
consulted before installations are made. Refer
to paragraph 3.5.2 for gas supply
requirements.
3.2.7.1 Drip Leg
A drip leg, or sediment trap, is supplied with
the gas train. The gas line must be connected
to a supply main at least as large as the gas
train connection at the boiler. This
connection should be made with a union so
that the boiler gas train components and
burner may be easily removed for service.
3.2.7.3 Venting of Gas Train Components
The MBC (gas valve) has an internal, factory
installed vent limiter re ANSI Z21.18/ CSA
6.3. Venting required unless otherwise
accepted by the authority having jurisdiction.
The high and low gas pressure switches
incorporate a vent limiter as per UL 353 and
limits the escape of gas less than 1.0 CFH of
natural gas at 7 PSI if internal switch
diaphragm ruptures.
3.3 Combustion Air Supply System
For proper combustion it is necessary to
provide the boiler room with appropriate
openings for fresh air supply. Temporary air
intakes such as windows and doors should be
avoided since they may be closed. In addition
to air needed for combustion, sufficient air
must be supplied for ventilation as well as
other air consuming equipment that may be
present in the boiler room. Often when
personnel are working in the boiler room,
combustion air openings are closed due to the
temperature of the outside air. THIS MUST
BE AVOIDED AT ALL COSTS! Provisions
should be made to heat the outside
combustion air, if necessary, for personnel
comfort.
3.2.7.2 Gas Piping Leak Test
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
Positive means for supplying an ample
amount of outside air, allowing for the
complete combustion of the gas, must be
provided.
Movable combustion air dampers, automatic
or manually adjustable, must be electrically
interlocked with the boiler to prevent boiler
operation if the dampers are closed.
Combustion air openings must never be
blocked or obstructed in any manner.
The boiler room must be at a positive or
neutral pressure relative to the outdoors. A
negative in the boiler room will result in
downdraft problems and incomplete
combustion due to the lack of air.
WARNING!
Failure to provide an adequate air supply
will result in boiler damage and hazardous
conditions in the building (fire and
asphyxiation hazard as well as equipment
damage).
3.3.1 Combustion Air Openings:
The design of combustion air openings
MUST comply with local and/or State codes
or the authority having jurisdiction. As a
minimum, combustion air openings to the
boiler room shall be provided as follows:
One opening starting within 12” of the top of
the boiler room and one starting within 12” of
the bottom of the boiler room shall be
provided. The openings shall be open directly
to the outside or ducted directly to the
outside.
When directly open to the outside or ducted
to the outside by vertical ducts, each opening
or duct shall have a minimum fee open area
of 1 in2 per 4000 BTU total input rating of the
boiler(s) in the room.
If ducted to the outside through horizontal
ducts, each opening or duct shall have a
minimum free area of 1 in2 per 2000 BTU
total input rating of the boiler(s) in the room.
3.3.1.2 One Permanent Opening Method
One opening commencing within 12” of the
top of the room shall be provided. The
opening shall be directly to the outside or
shall be ducted to the outside with a
horizontal or vertical duct.
The opening or duct shall have a minimum
free area of:
1 in2 / 3000 BTU /hour of the total input
ratting of all appliances (boilers) in the room.
NOTICE
Combustion air provided solely from an
indoor source is discouraged. No
dimension for a round or rectangular
opening shall be less than 3”.
3.3.1.1 Two Permanent Opening Method
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Additional area must be provided for other air
consuming equipment in the room.
3.3.1.3 Mechanical Air Supply Systems
The combustion air supply may be provided
by a mechanical air supply system. If utilized,
the combustion air must be provided from
the outside at a minimum rate of 0.35 ft3/min.
for every 1000 Btu/hr. input for all appliances
located in the space.
Form: 2435
16
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
If exhaust fans are utilized, additional air shall
be provided to replace the exhausted air.
Each boiler and other appliance must be
interlocked to prevent operation when the
mechanical air supply system is not in
operation.
If the combustion air is provided by a
buildings mechanical ventilation system, the
system shall be sized to provide the specified
combustion air in addition to the ventilation
air requirements.
3.3.2 Louvers, Grilles, and Screens
3.3.2.1 Louvers and Grilles:
The required size of openings for
combustion, ventilation, and dilution air shall
e based on the net free area of each opening.
Where the free area through a design of
louver, grille, or screen is know, it shall be
used in calculating the size opening required
to provide the free area specified. Where the
louver and grille design and free area are not
know, it shall be assumed that wood louvers
have a 25 percent free area, and met louvers
and grilles have 75 percent free area. Nonmotorized louvers and grilles shall be fixed in
the open position.
3.3.2.3 Motorized Louvers:
Motorized louvers shall be interlocked with
the appliance so they are proven in the full
open position prior to main burner ignition
and during main burner operation. Means
shall be provided to prevent the main burner
from igniting should the louver fail to opening
during burner startup and to shut down the
main burner if the louver close during burner
operation.
3.3.2.4 Combustion Air Ducts
Combustion air ducts shall comply with the
following:
Ducts shall be constructed of galvanized steel
or a material having equivalent corrosion
resistance, strength and rigidity.
Ducts shall terminate in an unobstructed
space, allowing free movement of combustion
air to the appliances.
Ducts shall serve a single space.
Ducts shall not serve both upper and lower
combustion air openings where both such
openings are used. The separation between
ducts serving the upper and lower combustion
air openings shall be maintained to the source
of combustion air.
Ducts shall not be screened where terminating
in an attic space.
3.3.2.2 Screens
Minimum Screen Mesh Size:
Screens shall not be smaller than 1/4 “ mesh.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Horizontal upper combustion air ducts shall
not slope downward toward the source of
combustion air.
For informational purposes, there are several
codes that address the amount of air and/or
size of the opening(s) in walls for combustion
air.
Form: 2435
17
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
NFPA 54, National Fuel Gas Code (ANSI
Z223.1)
ASME CSD-1, Controls and Safety Devices
for Automatically Fired Boilers
ASME Section VI, Recommended Rules for
Care and Operation of Heating Boilers
BOCA, National Mechanical Code
WARNING:
Do not locate air intakes where petroleum
distillates, CFC’s, detergents, volatile
vapors or any other chemicals are present.
Severe boiler corrosion and failure will
result.
3.3.3 Ducted Combustion Air
Ducted combustion air can be connected to
the boiler air intake flange. Ducts shall be
constructed of galvanized steel or a material
having equivalent corrosion resistance,
strength and rigidity.
Appendix B shall be used to determine the
ducted combustion air system equivalent
length. For typical ducted combustion air
arrangements see Appendix E.
2. If this boiler is being installed in
Massachusetts, follow the Massachusetts
Code Instructions printed later in this
section.
3. Consult the vent pipe manufacturer’s
instructions for vent system assembly and
system specific installation requirements.
4. Vent pipe system shall be acceptable for
use with boiler fuel type.
5. Vent pipe system shall be compatible
either by directly connecting, or by using
an adaptor, to the boiler vent connection.
a. This boiler is shipped with an AL 29-
4C® Heat-Fab Saf-T-Vent connection.
b. Alteration of the boiler vent
connection is prohibited.
6. Recommended flue system material is
AL29-4C. Other materials may be used
that meet the following requirements:
a. Flue system material shall be capable
of continuous operation at 230°F or
higher.
b. Flue system material shall have the
same corrosion resistance to flue gas
condensation as AL29-4C.
3.4 Venting Requirements
In order to properly vent this boiler, the
installer must select and install a venting
system that meets all requirements specified in
this section, as well as following the
instructions provided by the venting system
manufacturer.
1. The venting system shall be designed and
constructed in accordance with the
National Fuel Gas Code, NFPA 54 /
ANSI Z223.1 and applicable local building
codes to develop a positive flow adequate
to convey flue or vent gasses to the
outdoors.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
certified to UL1738 - Venting Systems
For Gas-Burning Appliances
Categories II, III, and IV.
7. Do not reduce the diameter of the vent
pipe. The vent pipe must not be smaller
than the vent connector on the boiler.
8. Vent pipe system must be adequately
supported at intervals no less than five (5)
feet apart. The completed vent system
must be rigid and able to withstand
impacts without collapse.
Form: 2435
18
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
9. The boiler’s venting is Category IV
(positive vent pressure, flue condensing),
with regards to the National Fuel Gas
Code, NFPA 54 / ANSI Z223.1.
10. Vent pipe system must be fully sealed.
11. Atmospheric venting is prohibited.
12. Appendix B shall be used to determine
the vent system equivalent length.
13. It is permissible to run vent pipe through
a vertical or horizontal chase provided
minimum clearances to combustible
materials are maintained.
14. The minimum clearance to combustible
material is six (6) inches unless otherwise
specified by the manufacturer.
15. The vent termination location is restricted
as follows:
a. Minimum twelve (12) inches above
grade plus normally expected snow
accumulation or seven (7) feet above
grade if located adjacent to public
walkways. DO NOT INSTALL over
public walkway where local experience
indicates condensation or vapor from
the boiler creates a nuisance or hazard.
b. Minimum three (3) feet above any
forced air inlet located within ten (10)
feet of the vent termination.
16. Use appropriately designed thimbles when
passing through combustible walls or
roofs.
17. Install fire-stops where vent passes
through floors, ceilings or framed walls.
The fire-stop must close the opening
between the vent pipe and the structure.
18. Enclose vent passing through occupied or
unoccupied spaces above the boiler with
materials having a fire resistance rating at
least equal to the rating of the adjoining
floor or ceiling. Maintain minimum
clearance to combustible materials.
19. Locate vent terminal above combustion
air intake terminal (if used) and no closer
than (1) foot horizontally.
20. Vertical venting requires flashing and a
storm collar to prevent moisture from
entering the structure.
21. Vertical vent termination must be at least
two (2) feet plus the expected snow
accumulation above roof penetration
height.
22. This boiler has been certified with AL29-
4C® venting. Select a vent material that is
approved for use with condensing flue
gasses.
23. Install vent system before installing air
intake, water, gas or electrical connections.
c. Minimum four (4) feet below, four (4)
feet horizontally or one (1) foot above
any door, window or gravity air inlet.
d. Minimum four (4) feet horizontally
from electric meters, gas meters,
regulators and relief valves. This
distance may be reduced if equipment
is protected from damage due to
condensate or vapor by enclosure,
overhangs, etc.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
manufacturer’s instructions do not make a
specification, refer to the below points.
a. Make sure pipe and fittings are clean
by swabbing with alcohol. Use Dow
Corning 736 or 732 RTV, Polybar #
500 RTV or Sil-Bond 4500 or 6500 or
seal vent pipe.
Form: 2435
19
Boiler
Model
Flue Gas
Flow,
@40%XSA
200oF
Comb Air
Req. SCFM
0oF
Flue
Size
FF
1000
301
220
6”
FF
1500
452
330
8”
FF
2000
603
441
8”
FF
2500
753
550
10”
FF
3000
904
661
10”
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
b. Refer to the appropriate drawings in
Appendix D of this manual to
determine common acceptable
configurations of the vent system.
WARNING
Improper venting may result in property
damage and the release of flue gasses that
contain deadly carbon monoxide (CO)
into the building, which can cause severe
personal injury and/ or death.
WARNING
Do not use a barometric damper with this
boiler. This is a positive pressure system.
The use of a barometric damper may
cause flue gases to leak into the boiler
room.
3.4.1 Category II Venting
5. Vertical venting is recommended. Other
horizontal and vertical arrangements may
be acceptable if proven by the vent
manufacturers design calculations.
6. It is recommended that combustion air be
taken from the boiler room. Follow the
guidelines in section 3.3 Other
arrangements may be acceptable if
proven by the vent manufacturers design
calculations.
7. It is recommended that a Carbon
Monoxide detector be installed and
interlocked to the boiler. Consult your
local jurisdiction for additional
requirements.
ACFM
@40%XSA6
Category II venting is an engineered system
and shall be designed by a qualified vent
manufacturer and “APPROVED” by the local
authority. The boiler manufacturer takes no
responsibility for vent systems that create
issues and or affect the performance of the
boiler. All jurisdictional codes shall apply in
addition to the following.
1. Common vents serving multiple boilers
shall be designed for negative pressure so
that flue gasses will not expel to the room
through a boiler on standby.
2. Common venting with other appliances is
prohibited.
3. Vent systems shall be designed to
maintain a negative 0.001 iwc to negative
0.1 iwc draft at all times from the
minimum firing rate to the maximum
firing rate measured at the outlet of the
boiler.
4. A mechanical draft fan may be required to
maintain the required negative draft.
Table 4: Combustion Air and Flue Gas
Requirements
WARNING
A poorly designed Category II negative
vent system can produce positive
pressures in the vent that can spill into the
room and adjoining spaces that can cause
severe personal injury and / or death.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
3.4.2 Massachusetts
The commonwealth of Massachusetts requires
compliance with regulation 248 CMR 4.00 to
5.00 for installation of sidewall venting gas
appliance as follow.
For all side wall horizontally vented gas fueled
equipment installed in every dwelling, building
or structure used in whole or in part for
residential purpose, including those owned or
operated by Commonwealth and where the
side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area
of the venting, including but not limited to
decks and porches, the following
requirements shall be satisfied.
1. INSTALLATION OF CARBON MONOXIDE
DETECTORS: At the time of installation of
the side wall venting gas fueled
equipment, the installing plumber or
gasfitter shall observe that a hard wired
carbon monoxide detector with an alarm
and battery back-up is installed on the
floor level where the gas equipment is to
be installed. In addition, the installing
plumber or gasfitter shall observe that a
battery operated or hard wire carbon
monoxide detector with an alarm is
installed on each additional level of
dwelling, building or structure served by
the side wall horizontal vented gas fueled
equipment. It shall be the responsibility of
the property owner to secure the service
of a qualified licensed professional for the
installation of hard wired carbon
monoxide detectors.
a. In the event that the side wall
horizontally vented gas fueled
equipment is installed in a crawl
space or an attic, the hard wired
carbon monoxide detectors with
alarm and battery back-up may be
installed on the next adjacent floor
level.
b. In the event that the requirements of
this subdivision cannot be met at the
time of completion of installation, the
owner shall have a period of (30)
days to comply with the above
requirements; provided, however,
that during said (30) day period, a
battery operated carbon monoxide
detector with an alarm shall be
installed.
2. APPROVED CARBON MONOXIDE
DETECTORS. Each carbon monoxide
detector, as required in accordance with
the above provisions, shall comply with
NFPA 720 and be ANSI/UL 2034 listed
and IAS certified.
3. SIGNAGE. A metal or plastic identification
plate shall be permanently mounted to
the exterior of the building at a minimum
height of eight (8) feet above grade
directly in line with the exhaust vent
terminal for the horizontally vented gas
fueled heating appliance or equipment.
The sign shall read, in print size no less
than one-half (1/2) inch in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF
ALL OBSTRUCIONS.”
4. INSPECTION. The state or local gas
inspector of the side wall horizontally
vented gas fueled equipment shall not
approve the installation unless, upon
inspections, the inspector observes
carbon monoxide detectors and signage
installed in accordance with the
provisions of 248 CMR 5.08(2)(a)1
through 4.
a. EXEMPTIONS: The following
equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
i. The equipment listed in chapter
10 entitled “Equipment Not
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web:www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
Required To Be Vented” in the
most current edition of NFPA 54
as adopted by the Board; and
ii. Product Approved side wall
horizontally vented fueled
equipment installed in a room or
structure separate from the
dwelling, building or structure
used in whole or in part for
residential purposes.
b. MANUFACTURER REQUIREMENTS-
GAS EQUIPMENT VENTING SYSTEM
PROVIDED. When the manufacturer of
Product Approved side wall
horizontally vented gas equipment
provides a venting system design or
venting system components with the
equipment, the instructions provided
by manufacturer for installation of the
equipment and the venting system
shall include:
i. Detailed instructions for the
installation of the venting system
design or the venting system
components; and
ii. A complete parts list for the vent
system design or venting system.
c. MANUFACTURER REQUIREMENTS-
GAS EQUIPMENT VENTING SYSTEM
NOT PROVIDED. When the
manufacturer of a Product Approved
side wall horizontally vented gas
fueled equipment does not provide
the parts for venting the flue gases,
but identifies “special venting
systems”, the following requirements
shall be satisfied by the manufacturer:
i. The referenced “special venting
system” instructions shall be
included with the appliance or
equipment installation
instructions; and
ii. The “special venting systems”
shall be Product Approved by the
Board, and the instructions for the
system shall include a parts list
and detailed installation
instructions.
d. A copy of all installation instructions
for all Product Approved side wall
horizontally vented gas fueled
equipment, all venting instructions, all
parts lists for venting instructions,
and/or all venting design instructions
shall remain with appliance or
equipment at the completion of the
installation instructions.
3.4.3 Combustion Air and Venting
Requirements for Canada
Canadian Standard CAN/CSA-B149.1-05,
Natural gas and propane installation code
specifies venting systems and air supply for
appliances in Section 8. Paragraph 8.1.4 states
“Air supply shall be provided in accordance
with Clause 8.4 when either an appliance or a
combination of appliances has a total input
exceeding 400,000 Btuh. Air supply is defined
as combustion air, excess air, flue gas dilution
air, primary air, secondary air, and ventilation
air. The air supply requirements below are a
summation of Clause 8.4 specific to this
boiler.
3.4.3.1 Air Supply Requirements per
CAN/CSA-B149.1-05 for
Appliances having an input
exceeding 400 MBH.
Ventilation Air: an opening for ventilation air
at the highest point that opens to the
outdoors shall provide Ventilation of the
space. The cross sectional area of this
opening shall be at least 10% of the area
required for combustion air, but in no case
shall the cross-sectional area be less that 10 in2
(6500mm2).
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
Combustion Air: For combustion air where
the air supply is provided by natural airflow
from outdoors, in addition to the opening for
ventilation air, there shall be permanent
opening having a total cross-sectional free
area of not less than 1 in2 for each 30,000
BTU/hr. (70 mm2 for each kW) of the total
rated input of the boiler(s). The location of
the opening(s) shall not interfere with the
openings for ventilation air. Please refer to
CAN/CSA-B149.1-05, Para. 8.4.4, for
combustion air openings if there are natural
draft, fan assisted or power draft assisted
equipment in the space.
When an air supply duct is used to supply
combustion air, it’s discharge opening shall be
located where there is no possibility of cold
air affecting steam or water lines or other
temperature sensitive equipment.
3.4.3.2 Combustion Air Supply Dampers,
Louvers, and Grilles
The free area of the combustion air supply
opening shall be calculated by subtracting the
blockage area of all fixed louvers, grilles or
screens from the gross area of the opening.
When combustion air is supplied by
mechanical means, an airflow sensing device
shall be installed and wired into the safety
limit circuit of the primary safety control to
shut off the gas in the even a an air supply
failure.
3.4.3.4 Appliance Venting per CAN/CSA-
B149.1-05
Paragraph 8.9 of CAN/CSA-B149.1-05
addresses “Appliance Venting”. Paragraphs
8.9 through 8.31 address many facets of flue
gas vents, many of which do not apply to the
this boiler, which is a Category IV listed
appliance requiring the use of special venting
systems as previously described.
NOTICE
Please note that the information provided
in this manual relative to the Canadian
Standard is not meant to be all-inclusive.
Reading the entire Standard is strongly
suggested. The final approval of all
system designs must be acceptable to the
authority having jurisdiction.
Openings in a fixed louver, grille, or screen
shall have no dimension smaller than ¼” (6
mm).
No manually operated damper or manually
operated adjustable louvers are permitted.
A motorized damper or louvers shall be
interlocked so the burner(s) cannot operate
unless the damper or louver is in the fully
open position.
3.4.3.3 Mechanical Combustion Air
Supply
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
shall be as specified or furnished by
the manufacturer of the listed
appliance. This boiler is a Category
IV appliance requiring the use of
special vent that is certified.
• A special venting system shall be
installed in accordance with the terms
of it’s listing and the vent
manufacturers certified installation
manual.
• A flue gas vent or a vent connector
shall not be installed in either a duct
or a shaft used for return air, hot air,
ventilating air, or combustion air.
• An appliance that operates at a
positive vent pressure shall not be
connected to a venting system serving
Form: 2435
23
Table 5: Electrical Requirements
FF1000
Voltage
FLA
CCA
MHP
MA
120/1/60
6.6
2.6
.46
4
FF1500
Voltage
FLA
CCA
MHP
MA
208-
FF2000 to FF3000
Voltage
FLA
CCA
MHP
MA
208-
208-
480/3/60
6.6
2.6
3.2
4
FLA = Full Load Amps : CCA = Control
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
any other appliance. This boiler
operates at a positive vent pressure.
• A factory-built chimney used for
venting an appliance shall be certified.
3.5 Requirements
3.5.1 Electrical
WARNING
All electrical connections must conform to
the National Electrical Code, ANSI /
NFPA 70 and / or CSA C22.1 Electrical
Code and all other State and Local codes.
A separate electrical circuit must be run from
the main electrical service with an overcurrent device/disconnect in the circuit. A
service switch is recommended and may be
required by some local jurisdictions. Locate
the service switch such that the appliance can
be shut off without exposing personnel to
danger in the event of an emergency. See
Table 5 for available voltages.
240/1/60
240/1/60
240/3/60
6.9 2.6 1.1 4.3
8.3 2.6 1.5 5.7
9.5 2.6 3 6.9
Circuit Amps : MHP = Motor Horse Power :
MA = Motor Amps
Connect field supplied safety limits or devices
using proper terminals provided in boiler
electrical cabinet. Refer to wiring diagram
supplied with boiler for wiring information.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web:www.bryanboilers.com
See Appendix H for sample-wiring diagrams.
An as-built wiring diagram is included with
every boiler when it ships. Contact a Bryan
Steam Representative or visit the website
(www. thermalsolutions.com) for current
wiring options.
Form: 2435
24
Capacity
(SCFH)
Inlet
(nps)
Min.
(iwc)
Max.
(iwc)
FF1000
1000
1 4 14
FF1500
1500
2 4 14
FF2000
2000
2 4 14
FF2500
2500
2 4 14
FF3000
3000
2 4 14
Table 7 Sound Pressure Levels
Decibel Levels
Tube
FF1000
FF1500
67
60
61
63
Table 7 Sound Pressure Levels
Decibel Levels
Tube
FF2000
67
60
61
63
FF2500
62
62
66
61
FF3000
62
62
66
61
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
3.5.2 Gas Supply Requirements
Refer to Table 6 for minimum and maximum
gas supply pressure. When the gas supply
pressure exceeds the maximum, an additional
field supplied step down regulator will be
Model Front Rear
Side
required to reduce the supply pressure. For
proper gas supply sizing refer to Appendix A.
NOTICE
The step down regulator shall be installed
at least 60 pipe diameters from the boiler
gas inlet manual shutoff valve. This will
ensure proper gas regulation for
establishing main flame reliably.
Model
3.5.4 Pump and Piping Requirements
Pump piping and system piping must meet
the requirements of local codes and
jurisdictions. Good engineering practices
should be followed and considered for each
piping system used.
It is advised that the circulating pump for
each boiler be installed as close to the boiler
as possible in the line to the return connection
such that system water is pumped towards the
boiler.
Right
Side
Table 6: Gas Supply Requirements
3.5.3 Sound Pressure Levels
Sound pressure levels were measured at 41/2’ above the floor and 3’ from the boiler at
the front, rear and two sides. See Table 7 for
decibel readings.
Model Front Rear
Side
Right
Side
Installing circulating pumps so that the water
is pumped away from the boiler is rarely
recommended.
Means to eliminate air from the boiler/piping
systems is a must. It is advised that an air
separator be installed as close as practical to
each boiler in the outlet pipe. Further, an air
vent should be installed at all high points
throughout the piping system.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web:www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
It is recommended that a water meter be
installed in the make-up water system to the
boiler system. Scheduled recording of the
Model
gpm
water meter register will show an indication of
a potential slow system leak in addition to
providing insight into any system problems.
Also, make-up water as well as water for the
initial system fill should be provided through
a water softener. Additionally, chemical
treatment of the system water is advisable.
Contact a qualified boiler water chemical
Table 8 Minimum Water Flow Rates for
Variable Primary Pumping
treatment company for their
recommendations. See section 3.8 for more
information.
Model
gpm
See Appendix G for boiler water flow
pressure drop data and Appendix F for typical
boiler piping arrangements.
3.5.4.1 Water Flow Rates (Variable Primary
Pumping Systems)
Variable primary pumping systems shall be
capable of delivering no less than the
minimum and no more than the maximum
specified in Table 8 and Table 9 for each
boiler connected in the system.
Table 9 Maximum Water Flow Rates for
Variable Primary Pumping
WARNING
Do not use Table 8 or Table 9 to size a
constant volume pump.
3.5.4.2 Water Flow Rates (Primary /
Secondary Systems)
Each boiler connected to a secondary loop of
a primary / secondary pumping system shall
have a constant volume pump sized in
accordance with Table 10 or Table 11.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
3.5.4.3 Water Flow Rates (Constant
Volume Primary Pumping Systems)
A constant volume primary pumping system
shall be sized so that the flow rate specified in
Table 10 or Table 11 can be maintained
through each boiler connected to the system.
3.5.4.4 Water Flow Rates for Glycol
For glycol systems the gpm in Table 8, Table
9, Table 10, and Table 11 will increase as
specified in Table 12.
GPM Percent Increase
Table 12 GPM Increase for Glycol Systems
3.6 Before Placing Boiler In Operation
3.6.1 Pre-Boil Out Flushing Of System
Much of the dirt and contamination in a new
hot water system can be flushed out before
the boil out of the system. First, flush the
system of waste with clear water. The boiler
and circulating pumps must be isolated
through the successive zones of the system to
waste, carrying metal shavings, dirt, pipe joint
compound, etc. with it. Follow with a
chemical flush.
WARNING
Be CERTAIN that the chemicals used to
flush and boil-out the boiler and system
contain NO CHLORIDES. The boiler is
fabricated with austenitic stainless steels
that can be severely damaged when
exposed to chlorides.
The removal of pipe chips and other debris
from the system before opening the isolation
valves to the boiler and pumps will help to
protect this equipment from damage by such
debris.
In combination with system contamination,
bacteria from ground water boiler water may
produce objectionable odors, sometimes
resembling the odorant used in natural gas. It
is important to keep these fumes from air
intakes that would distribute them throughout
the building.
3.6.2 Boil Out Procedure
WARNING
The boil out procedure outlined must be
performed by, or under the direct
supervision of, a qualified technician.
The chemicals used present a hazard of
burns and physical injury if mishandled.
Always use a suitable facemask, goggles,
protective gloves, and garments when
handling caustic chemicals. Do not
permit the chemical to come into contact
with skin or clothing. Always follow the
safety precautions on the container's
label. Add chemicals slowly and in small
amounts to prevent excessive heat and
agitation.
The boil out of the boiler and system is
neither difficult nor expensive. The chemicals
needed for cleaning are readily available. Trisodium phosphate, and sodium hydroxide
(lye) are the most commonly used chemicals.
Be certain the chemicals used contain NO
CHLORIDES. Use only one type of solution
in the system. The amount of chemical
required will vary according to conditions, but
one pound per fifty gallons of water is
suggested.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
Fill the system with this solution, venting all
air. Then, with the circulating pump running,
bring the system to design or operating
temperature. After circulating water for two
to three hours, the system should be drained
completely, and refilled with fresh, softened
water see section 3.8. Usually enough of the
cleaning solution will adhere to the piping to
result in an alkaline solution satisfactory for
operation. A pH reading between, 8.3 – 10.5
is preferred. If necessary, to increase the pH,
a small amount of cleaner may be added.
3.6.3 Replacement Boiler Installations
Clean or replace all system piping and heating
units.
Arrange for chemical or mechanical cleaning
of the entire system. A chemical treatment
company should be consulted for the proper
means of any chemical cleaning. Replace any
piping that is deteriorated beyond safe or
cleanable condition.
Flush the system clean, being certain to isolate
the boiler.
WARNING
Do not flush the system through the
boiler.
For some old systems, there is a reluctance to
clean the piping because of possible leaks
occurring in badly corroded lines. Should the
customer refuse cleaning, it is necessary to
install filtration equipment. Install either a
fibrous filter or a centrifugal filter in the boiler
return piping. This will collect and remove
sediment from the system. A booster pump
may be required to overcome the additional
pressure drop introduced in the line by the
filter. When filling the system, provide
chemical treatment as outlined in Section 3.8.
Failure to properly clean the system or to
install mechanical sediment removal
equipment can result in tube blockage and
severe corrosion plus damage to pumps,
controls, and air removal devices.
Inspect, repair as necessary, or replace system
air control devices.
Install gauge glasses on air expansion tanks
and install a tank fitting in the system
connection to the tank.
Install a strainer in the boiler return piping.
3.7 Draining and refilling the boiler &
system
If the system is drained and then refilled,
chemical treatment is essential to treat the raw
water. Use only clean, softened water.
3.7.1 Filling The System
WARNING
Use only clean, softened, and treated
water. Chemical treatment of the raw
water is essential when filling or refilling
the system see section 3.8.
3.7.2 Hydrostatic Test Of Boilers And
System
After completing the boiler and burner
installation, the boiler connections, fittings,
attachments and adjacent piping must be
inspected for leaks by filling the unit with
water. The pressure should be gradually
increased to a pressure just below the setting
of boiler safety relief valve(s).
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
Remove the boiler tube access panels (see
dimensional drawing in the boiler manual).
Inspect the tube to header joints to be certain
that all tube fittings are sealed. This is
necessary because, although the boiler is
hydrostatically tested at the factory, minor
leaks in fittings and at attachments can
develop from shipping vibration or from
installation procedures. Replace tube access
panels before proceeding to start boiler.
3.8 Boiler Water Treatment
3.8.1 Purpose of water treatment
Water treatment is required for satisfactory
operation of the boiler. It must be devised to
prevent depositing of scale and corrosion
from acids, oxygen and other such harmful
elements that may be in the water supply. A
qualified water treatment chemist should be
consulted and the water systematically treated.
“Hot water systems must operate with a pH
above 8.5. A system that has a pH below 8.5
will usually develop the following problems:
1. Gas formation (air trouble)
2. Pump seal and gland problems
3. Air vents sticking and leaking
4. Frequent relief valve operating
5. Piping leaks at joints
4. Maintain the highest possible boiler fuel
efficiency.
5. Decrease the amount of boiler down
time from cleaning.
3.8.3 Water softener
It is highly recommended that a zeolite water
softener be used for all make-up to the boiler.
It is intended that this be used in addition to
the chemical treatment of the boiler. Water
softening removes calcium and magnesium,
the primary causes of hard boiler scale.
3.8.4 Continuous Monitoring
Water treatment should be checked and
maintained according to Table 14 whenever
the boiler is operating. The boiler operator
should be sure that the boiler is not operating
for long periods without proper water
treatment.
Water treatment may vary from season to
season or over a period of time. Therefore,
the water treatment procedure should be
checked not less than four times a year, and
possibly more frequently as the local water
conditions may indicate.
See Table 13 for examples of typical chemical
agents found in untreated water along with
their potential effects.
(American Boiler Manufacturers Association
[ABMA], 2005. Boiler Water Quality
Requirements and Associated Steam Quality
for Industrial / Commercial and Institutional
Boilers)”
3.8.2 Objectives
The basic objectives of water treatment are:
1. Prevent the accumulation of scale and
deposits in the boiler.
2. Remove dissolved gases from the water.
3. Protect the boiler against corrosion.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web:www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
Corrosion
It should be noted that water boilers may well
need chemical treatment for the first filling
plus additional periodic chemical treatment,
depending on system water losses and the
makeup requirements.
All water introduced into the boiler should be
softened and should include an oxygen
scavenger like sodium sulfite. This is required
to remove dissolved oxygen from the water.
Dissolved oxygen will cause severe system
corrosion.
Total Hardness
WARNING
Chemicals used in treating boiler water
are toxic and/or harmful. Always use
protective clothing and equipment when
working with/near chemicals. Contact
local authorities to determine if treated
boiler water can be discharged into local
waste water system.
Table 14 Recommended Feed Water
Limits
CAUTION
Bryan Steam Standard Warranty does not
cover problems caused by oxygen
contamination of boiler water.
Bryan Steam Standard Warranty does not
cover problems caused by scale build-up.
When using Glycol products, all Glycol
manufacturers’ requirements, including
rust inhibitors, must be adhered. Max
50% Glycol.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
4 SYSTEM START-UP
WARNING
Completely read, understand and follow
all instructions in this manual, Concert
Boiler Control manual, and all other
component manuals supplied with this
boiler before attempting start- up.
4.1 Concert Boiler Control Display
Navigation
This boiler is equipped with a color touch
screen display, which presents information
and control options in a page manner. Pages
are arranged in a tree structure through which
the user navigates up and down to arrive at
the desired function. The page descriptions
and a complete list of the available control
parameters are provided in a separate
instruction manual for the Concert boiler
control (Also supplied with the boiler).
Most pages have a Home button in the
top-left corner of the screen. The Home
button returns the user to the Home page to
view real time operation of the boiler.
NOTICE
Refer to the Concert Boiler Control
manual for detailed instructions on the
use of the hydronic control and display.
4.2 System Check:
1. Verify that the venting, water piping, gas
piping and electrical system are installed
properly. Refer to installation instructions
contained in this manual.
2. Confirm all electrical, water and gas
supplies are turned off at the source and
the chimney/vent is clear of obstructions.
If boiler is controlled by an external
control system, this system must be
temporarily disconnected. The local
boiler controls should be allowed to
operate the boiler.
3. Confirm that all manual shut-off valves
between the boiler and gas supply are
closed.
4.3 Power the Boiler:
The back button returns the user to the
previous page.
A padlock icon will be shown on the
screens that require the user to enter a
password to change the parameter. An
unlocked padlock indicates the correct
password has been entered to change the
parameter.
The user can access the following icons from
the Home screen: Menu, Info, Status, Adjust,
and Help. It is important that the user
become familiar in accessing additional icons
that are not shown on the home screen page.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Turn on the electrical supply to the boiler and
circulation system at fused disconnect switch.
Ensure that the circuit breaker switch is in the
“ON” position.
4.4 Power the Circulators:
Turn system circulators on and purge air from
the boiler and system piping.
4.5 Pressurize the Fuel System:
1. Open the manual gas shut-off valves
located upstream of the field supplied gas
regulator. Do not open manual gas valve
directly outside the boiler jacket.
2. Purge gas line of air.
3. Open manual ball valve outside boiler
jacket. Confirm that the supply pressure
to the manual ball valve tapping outside
Form: 2435
32
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
the boiler jacket conforms to Table 6 for
maximum and minimum supply pressure.
4. Repeat steps 2 and 3 for boiler gas train
components.
4.6 Boiler Commissioning:
All of the installation instructions found in
sections 1 through 3 shall be completed
before commissioning the boiler.
DANGER
Failure to properly adjust excess air will
result in unsafe levels of carbon
monoxide. Variations in venting or
combustion air pressure and temperature
will change excess air. Adjust excess air
levels so that variation in venting or
combustion air pressures and
temperatures caused by change of
seasons, wind conditions, opening or
closing of boiler room doors or windows
do not cause the boiler to operate with
carbon monoxide concentration above 400
parts per million.
1. Identify boiler water, gas, and electrical
connections, and other safety controls.
2. Locate manometer pressure taps for
pressure measurements in the following
areas:
a. Supply gas pressure (ball valve
tapping outside of boiler top jacket
panel)
b. Stack or flue outlet pressure
3. Install a gas analyzer probe within 6”
above the boiler flue gas outlet.
4. Verify the high temperature limit (auto
0
reset) is set to 200
5. Verify the high and low gas pressure
switch limits.
a. High gas pressure switch at 1.0” w.c.
b. Low gas pressure switch at 3.0” w.c.
F. (1000 only)
6. Menu > Operation > Auto / Manual
Rate Control > Manual (76 password
required)
7. Switch boiler circuit breaker in the
control panel to the ON Position (1000
only).
8. Close the manual gas valve between the
automatic gas valve and the blower
inlet.
9. Cycle the boiler. The boiler should
lockout on gas pressure failure. In this
case it should be the low gas pressure
switch.
10. Reset the low gas pressure switch and
gas pressure lockout.
11. Increase the high gas pressure switch
setting to 14” w.c.
12. Cycle the boiler. The boiler should
lockout on flame failure or ignition
failure. (Boiler may recycle once if there
was an ignition failure. Repeat step 12.)
13. Reset the flame failure lockout and
decrease the high gas pressure setting to
1” w.c.
14. Cycle the boiler. The boiler should
lockout on gas pressure. In this case it
will be the high gas pressure switch.
15. Open the manual gas valve between the
automatic gas valve and the blower
inlet.
16. Reset the high gas pressure switch and
gas pressure lockout.
17. Cycle the boiler. The boiler should
establish main flame.
18. If flame is not established reset the
flame failure lockout and repeat step 17.
(Consult with the factory for assistance
if flame cannot be established after 3
attempts.)
19. Check that O2 levels are within a safe
operating range. (4.5% to 7.0%)
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
20. Menu > Operation > High/Low > High
> Back Arrow (76 password required)
21. Once boiler has reached high fire rate,
check that O2 levels are within a safe
operating range. (4.5% to 7.0%)
22. Adjust supply gas pressure between 4”
w.c. and 14” w.c. as measured at the ball
valve tapping outside of the boiler top
jacket panel.
23. Adjust the O
level so that it is within
2
4.5 to 7.0 % at high fire with all jacket
doors installed and front cabinet door
closed.
a. For best efficiency, standard O2
should be set to 4.5% to 4.6%.
b. For boilers specified to be less than
20ppm NOx adjust the O
level
2
within 6.5% to 7.0%.
c. For boilers specified to be less than
9ppm NOx adjust the O2 level within
7.0% to 9.0%.
Note: High Fire O
levels are adjusted with
2
the gas shutter valve located on the
outlet of the gas valve.
i. Turn adjustment screw toward the
‘Plus (+)’ side to increase gas flow
(decrease O
level).
2
ii. Turn adjustment screw toward the
‘Minus (-)’ side to decease gas flow
(increase O
level)
2
24. Menu > Operation > High/Low > Low
> Back Arrow (76 password required)
25. Verify the O
level is within +/- 0.3% of
2
the O2 level set at high fire with all
jacket doors installed and front cabinet
door closed. (Consult the factory for
assistance if the O2 levels are not within
+/- 0.3% from high fire to low fire.)
Warning
Improper adjustments to the low fire
offset adjustment can lead to rough lightoffs and nuisance flame failures.
26. Verify O2 repeatability by
commanding the boiler to high fire
and low fire as many times as
required, repeating steps 20 to 26 as
necessary.
Figure 6: High Fire Adjustment on the
Main Gas Valve Regulator
27. Once the boiler is operating within
the specified high and low fire
ranges, record emissions, flue draft,
and other important data on the
installation and startup report, see
Appendix C.
28. Perform tests on each of the components
listed in Table 15.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
4.7 Finish Commissioning the Boiler:
Reconnect any wires from the external control
system, if applicable.
1. Perform an operation test of the external
control system.
2. Place system control back in normal
operation, if necessary.
3. Place the boiler into automatic mode.
Menu > Operation > Auto / Manual Rate
Control > Automatic (76 password
required)
4.8 Re-Starting After Prolonged
Shutdown
Use the following recommendations prior to
re-starting the heating system after prolonged
shutdown.
1. Perform Pre-Start-Up Inspection by
checking all gas, water, air intake and
venting connections to ensure proper,
leak-free connections and that the water
and gas lines has been cleaned
completely.
2. Ensure that combustion air piping, vent
piping, and terminations are free of
obstructions.
3. Inspect the boiler for damage and loose
wire connections.
4. Remove all flammable material present in
the vicinity of the boiler.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web:www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
4.9 Testing of Controls and Safety Devices
Prior to placing the boiler in operation, the installing contractor or other responsible personnel must
perform safety and control device limit tests to ensure proper operation of the appliance. Refer to
Table 15 for recommended method(s) of carrying out these safety limit devices tests.
Switch
Switch
Switch
Fuse (1000 Only)
valve between the gas
valve and air inlet.
Cycle boiler.
the switch until the
switch trips.
the burner thermal
fuse. Cycle the boiler.
the blocked condensate
switch. Cycle the
boiler.
the vestibule thermal
fuse. Cycle the boiler.
Concert Boiler Control
and switch. Adjust the
switch to its normal
Concert Boiler Control
and switch. Adjust the
switch to its normal
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
4.10 Ignition Failure
After the first ignition failure, the boiler goes into a hard lockout and a manual reset of the Concert
Boiler Control is required to restart the boiler. The boiler will then attempt to light off after it has
completed its post-purge process.
DANGER
Contact the boiler manufacturer or a qualified heating service technician if the boiler has
failed to light consecutively three times after initially resetting the Concert boiler control.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
5 Service, Maintenance, and Inspection
5.1 General Maintenance:
1. Follow any checks and/or inspections that
may be required as specified in the
component manufacturers’ instruction
manuals.
2. Repair or replace any defective
components immediately.
3. The following service procedures are
required for proper and safe boiler
operation.
DANGER
This boiler uses flammable gas, high
voltage electricity, moving parts, and very
hot water under high pressure. Assure that
all gas and electric power supplies are off
and that the water temperature is cool
before attempting any disassembly or
service.
More than one gas shut-off valve and
electrical disconnect switch are used on
the boiler. Assure that all gas valves and
electrical disconnect switches are off
before attempting any disassembly or
service.
Do not attempt any service work if gas is
present in the air in the vicinity of the
boiler. Never modify, removed or tamper
with any control device.
Do not use matches, candles, open flames
or other ignition source to check for leaks.
Read, understand and follow all the
instructions and warnings contained in all
the sections of this manual. The
instructions and warnings contained in all
of the component instruction manuals.
If any electrical wires are disconnected
during service, clearly label the wire and
ensure that the wires are reconnected
properly.
Never jump out or bypass any safety or
operating control or components of this
boiler.
Assure that all safety and operating
controls and components are operating
properly before placing boiler back in
service.
WARNING
The service instructions contained in this
manual are in addition to the instructions
provided by the manufacturer of the boiler
components. Follow component
manufacturer’s instructions. Component
manufacturer’s instructions were provided
with the boiler. Contact component
manufacturer or Bryan Steam for
replacement if instructions are missing.
Do not install, start up, operate, maintain
or service this boiler without reading and
understanding all of the component
instructions. Do not allow the boiler to
operate with altered, disconnected or
jumpered components. Only use
replacement components identical to
those originally supplied by Bryan Steam.
WARNING
This boiler must be serviced and repaired
by skilled and experienced service
technicians only.
If any controls are replaced, they must be
replaced with identical models supplied
by Bryan Steam.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
All cover plates, enclosures, and guards
must be in place at all times, except
during maintenance and servicing.
5.1.1 DAILY:
1. Make visual inspection of gauges,
monitors, and indicators and record
readings in boiler log.
Form: 2435
38
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
2. Make visual check of instrument and
equipment settings against factory
recommended specifications.
2. If inspection of the boiler tube surfaces
reveals a build-up of soot (carbon), the
tube surfaces should be thoroughly
brushed. Failure to do so may result in
3. Check operation of probe type low water
cutoff(s) to ensure control is functioning.
4. Check gas train for gas leaks and water
piping for any leaks.
5. Confirm boiler area is free of combustible
materials and that there is nothing
reduced efficiency, fire and asphyxiation
hazards.
3. The boiler pressure vessel and piping
should be checked annually.
4. Inspect the ignition rod for carbon build
up.
obstructing air intake and vent.
5. Inspect lens of the ultra-violet (uv)
scanner and remove any debris with soft
5.1.2 WEEKLY:
cloth and make sure that hole is clear
from scanner to burner.
1. Check combustion safety controls for
flame failure (or other alarm messages).
2. Check all limit controls and low water
cutoff as described above.
3. Check condensate drains for any
obstructions.
4. Check carbon monoxide level in flue
products.
6. Replace air filter.
5.2 Ignition Assembly Cleaning
1. Disconnect power and shut off the
external manual gas valve to the boiler
prior to removing the ignition assembly.
2. When removing the igniter, extra
caution must be taken to prevent
5.1.3 MONTHLY:
damaging the ceramic insulator.
1. Check high and low gas pressure
interlocks. Refer to manufacturer's
instructions for correct procedure.
2. Check proper operation of safety relief
valve.
3. Check water quality and correct if needed.
4. Inspect boiler air filter.
5.1.4 ANNUALLY:
1. The flue gas passages and the exterior
surfaces of the boiler tubes should be
inspected at least once annually. Any
accumulation of soot or debris should be
thoroughly cleaned out.
3. Remove any excess oxide deposits from
the surface of the igniter with steel wool
or emery cloth. Do not use sandpaper.
4. Inspect the ceramic insulator for cracks,
and if necessary, replace the igniter.
After each inspection of the igniter,
replace gasket and apply anti-seize
compound to mounting screws prior to
reinstalling them.
5. Ensure that igniter electrode spacing is
within 1/8 inch.
6. When reinstalling the igniter after
inspecting it, make sure there is a ⅜inch
gap between the igniter and the burner
surface.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
3. Be careful not to damage or disturb the
insulation inside of the heat exchanger.
Figure 7: Ignition Assembly
• 1. Igniter
• 2. Ultra-Violet (UV) Scanner
• 3. ½” Heat Insulator
• Igniter Gasket
5.3 Burner Assembly Cleaning
1. After disconnecting power to the boiler,
remove the boiler’s furnace door. For
part identification, refer to the “Repair
Parts” section of this manual.
2. Clean around the burner assembly by
blowing compressed air over the surface
of the burner to remove lint and debris
accumulation. Be careful when cleaning
the burner assembly, to avoid damaging
the metal mesh burner surface.
3. If the burner or the burner gasket shows
any visual deterioration or corrosion
signs, replace it immediately.
4. After replacing the burner or burner
gaskets, check for proper operation by
performing combustion analysis, as well
as checking for gas leakage around the
burner mounting and blower transition
pieces.
5.4 Heat Exchanger Cleaning
1. Perform visual inspection of both boiler
flue passes, and remove any debris from
the surfaces of the heat exchanger.
2. If necessary, brush the tubes of the heat
exchanger using non-abrasive, nonmetallic bristle brush.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
5.5 Tube Replacement Procedure
NOTICE
Performing a regular boiler inspection will prolong the life of the heat exchanger, and
ensure optimal function and energy efficiency. For best practices, adhere to the general
guidelines outlined in the service and maintenance section of this manual.
1. Inspect the boiler. Use the following steps to identify a potential tube leak and to minimize
possible damage to the boiler and other equipment as a result of tube failures.
a. Shut off power to the boiler immediately from the external, dedicated electrical disconnect.
b. Confirm that any water leakage is not the result of a blocked condensate drain line.
c. Confirm that any water leakage is not the result of a blocked condensate drain line.
d. Remove the boiler’s left side jacket panels and flue collector access panels as shown in
Figure 8.
e. Visually inspect the burner and furnace pass insulation for water damage. If significant water
damage to the insulation or burner is observed, contact the manufacturer.
f. Identify any leaking tubes.
g. Isolate and drain the boiler completely.
2. Use the proper tools. Use the following tools to remove and replace leaking boiler tubes:
a. Tube Puller (P/N 106019-02)
b. Tube Driver (P/N 106019-01)
c. Sledgehammer (steel head, approximately 3 lb)
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
1. Loosen tube-ends. Insert tube puller between the tube-end and header. Apply pressure to the
puller and strike the side of the tube two or three times with a hammer to help loosen the tubeend in the upper and lower header.
2. Pull lower tube end. Wedge the tube puller under the flange of the tube. Drive the tube puller
with several blows with a hammer on the end of the handle. Alternate with downward blows to
lift tube-end.
3. Clear tube-end from the header. Continue driving wedge under and leveraging flange up until it
pops the end of the tube free from the hole in the header.
4. Pull upper tube-end. Repeat the procedure to the pull the tube-end of the same tube from the
upper header.
5. Prepare the headers and replacement tubes. Before placing a new tube into the header, clean
the holes by wiping gently with emery cloth to be sure that there are no burrs. Clean the
replacement tube-ends of any rust or debris. With a small brush, apply a thin coating of gray
pipe dope around the inside of the hole. Pipe dope may also be applied to the tube-end. Cutting
oil may be mixed with the pipe dope for easier application.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web:www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
6. Insert both ends of the tubes into the headers. Insert the lower tube-end into the bottom
header first. Then insert the top tube-end into the top header. Insert all replacement tubes
before driving them.
7. Drive the upper and lower tube-ends. DO NOT drive the tube-ends down to the flange. With
the driver tool positioned on the flange, strike the end of the driver with hammer. After a few
hits, the feel of the strike will become solid. The tone will also change from a “ting” sound to
more of a “tong” sound. This indicates the tube has seated.
CAUTION
Do Not Overdrive Tubes! Overdriving tubes can cause damage to the tubes and boiler
header holes. Use only approved Bryan Steam tube driver and specified hammer. The endformed tube fitting is designed to deform if overdriven to minimize damage to the vessel
tube holes.
8. Reinstall the tube clamps. Replace the nuts and flat washers if damaged in any way. Use brass
nuts only! Tighten the nuts until snug. Do not try to compress the tube-ends into the holes with
the clamps, because the clamps might break or the stud might shear.
9. Refill the boiler. Fill the unit with water and ensure that there is no leakage at the replacement
tube-ends before reinstalling the flue collector panels.
WARNING
If a leak is detected after a replacement tube has been installed, pressure in the boiler must
be reduced to zero before adjusting tube(s). Adjusting tubes under pressure could result in
serious personal injury.
10. Reinstall all flue access doors, door clamps, and jacket panels.
11. Perform startup check prior to putting boiler back into operation.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web:www.bryanboilers.com
If this switch is in the off position, power is interrupted to the control circuit of the boiler,
supplied to the control circuit.
Automatic
Aquastat
If the boiler water temperature exceeds the adjustable set point, power is interrupted to the
supplied to the control circuit.
If the boiler water temperature exceeds the adjustable set point, power is interrupted to the
temperature has dropped below the setpoint minus the differential setting.
If the water flow through the boiler drops below the fixed flow rate required to move the
paddle closes the control’s contacts and power is supplied to the control circuit.
Pressure /
Valve
If the pressure inside the boiler exceeds the fixed set point, the valve opens mechanically and
If the gas pressure reaches a point above or below the adjustable set point, the contacts of
switches will not reset until the gas pressure is within the set point parameters.
Minimum
Switch
If the differential air pressure drops below the fixed set point, the contacts of the switch open
Maximum
Switch
If the differential air pressure exceeds the fixed set point, the contacts of the switch open and
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
5.6 Safety and Operating Controls
All of the safety control devices listed in Table 16 are logically linked to the Concert Boiler Control
that supervises the sequence of operation of the boiler for safe and efficient operation. It does so by
ensuring proper light off and firing of the main burner and if need be, will immediately cut-off gas
supply to the main burner when gas pressure, water temperature, water flow or another critical
attribute is outside of the operational settings. It also varies the combustion rate in real time to meet
the desired load of the system.
WARNING
Do not install, operate, service or repair any components of this equipment unless you are
qualified and fully understand all requirements and procedures. Trained personnel should
refer to those who have completed Bryan Steam Service School training specific to this
product.
Power
Switch
Reset
Operating
Manual
Reset High
Limit
Aquastat
Water Flow
Switch
Safety Relief
High and
Low Gas
Pressure
Switches
which prevents the boiler from operating. If the switch is in the on position, power is
control circuit of the boiler, which prevents the boiler from operating. When the boiler water
temperature drops below the set point minus the adjustable differential setting, power is again
control circuit of the boiler, which prevents the boiler from operating. Power is interrupted
until the control is manually reset pressing the control’s reset button. When the button is
pressed, power will again be supplied to the control circuit, assuming that the boiler water
control’s paddle enough to close the control’s contacts, power is interrupted to the control
circuit, which prevents the boiler from operating. When the water flow rate increased, the
discharges water. The valve remains open until the pressure inside the boiler drops below the
set point.
the switch open and power is interrupted to the control circuit that prevents the boiler from
operating. Power is interrupted until gas pressure is between the high and low gas pressure
set points and the control is manually reset moving the switch to the reset position. The
Air Pressure
Air Pressure
and power is interrupted to the control circuit, which prevents the boiler from operating.
Power is interrupted until air flow/pressure increases so that contacts close.
power is interrupted to the control circuit, which prevents the boiler from operating. Power
is interrupted until air flow/pressure decreases below the setting so that the contacts close.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Boiler is not seeing
Enable/Disable of
Domestic Demand
Input.
Check wiring for loose connections or wiring
errors. If Domestic Demand is expected check
the DHW Demand/Modulation is selected
properly.
Boiler is not
responding to call for
Central Heat or
Domestic Hot Water.
Check wiring for loose connections or wiring
errors.
Request the system and boiler pumps will be
free to run.
Display Completely
Dark Fun off, LWCO
power light on
Control.
No 120 Vac Power at
Boiler due to blown
high voltage fuse or
circuit breaker trip.
Check breaker and wiring between breaker and
boiler.
Replace blown high voltage fuse.
Reset tripped breaker.
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
5.7 Troubleshooting
Refer to the troubleshooting section in the Concert Boiler Control manual on how to navigate the
Limit String Status screen that shows an active safety limit status and for an in-depth guide to all the
possible lockouts as well as recommended corrective actions for restore boiler operation.
for heat, “Status” and
heat, “Status” shows
“Standby” and
“Priority” shows
Boiler is Running but
System or Boiler
Circulator is not
running.
Boiler is not firing, or
temperature is greater
than setpoint.
Pump Not Running.
Select display Help icon and review Limit
String Status.
When there is a Domestic Hot Water Heat
Request the System or Boiler Pump will be
forced “off” when their “Run Pump for”
parameter is set to “Central heat, off DHW
demand” or “Central Heat, Optional Priority”.
This has been set to allow all of the heat to be
provided for fast indirect water heater
recovery. After “Priority protection” time or
the end of the Domestic Hot Water Heat
lights off, no green
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Check loose 120 Vac connection wiring
between boiler J-Box and transformer or 24
Check for bad transformer or bad 24 Vdc
power supply: Replace if necessary.
The green light is connected to internal power
supply. The power supply is repeatedly
light. When the faulty wiring reconnected,
green light will begin to flash.
Blank Screen with
“Reading” shown.
Display lost
communication with
Control.
Failure to establish Communication upon bootup once you establish communication, reboot
display to read controller and setup display
properly.
Communication Error
2
Un-configured control,
or control has a
memory failure.
The display-write attempt has failed. The
controller is un-configured or has a memory
failure. Lockout 20 Safety Data Verification will
also be displayed. Replace Control.
Display has lost communication with
controller.
Refer to Concert Boiler Control manual for
more details.
Short Cycling
Oversized Boiler
Examine system and boiler operational settings
to determine what adjustments may be made
to reduce boiler cycling.
Contact Manufacturer.
Incorrect Gas Valve
Settings
If combustion is too lean or rich as a result of
improper gas valve settings, adjust air-fuel
ratio to match factory O2 settings.
Inspect heat exchanger tubes for damage and
carbon build-up. Inspect and clean the burner
and Inspection section of the manual for
guidance.
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
Vdc power supply.
Display Completely
Dar, Fun running.
Blinking Green power
light on Control.
No 120 Vac Power at
Control; No 24 Vdc to
Display.
Control Fault.
Check for loose 24 Vac connection wiring
between transformer and Control.
Check blown low voltage fuse: Replace in
necessary.
starting and stopping (not normal) making the
light flash. The microprocessors are not
running. Try disconnecting all terminals
except 24 Vac to power the control. The green
light should be steady. If it is not, then the
control is defective. If steady, start plugging in
all the connectors while watching the green
Communication Error
3
Communication Fault.
Poor Combustion Dirty Heat Exchanger
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web:www.bryanboilers.com
Form: 2435
48
Table 18: Maximum Gas Capacity Of Schedule 40 Pipe
Pipe
Length in
Equivalent
Feet
Pipe Size (nps)
¾ 1 1-1/4
1-1/2
2 2-1/2
3
4
10
273
514
1060
1580
3050
4860
8580
17500
20
188
353
726
1090
2090
3340
5900
12000
30
151
284
583
873
1680
2680
4740
9660
40
129
243
499
747
1440
2290
4050
8270
50
114
215
442
662
1280
2030
3590
7330
60
104
195
400
600
1160
1840
3260
6640
70
95
179
368
552
1060
1690
3000
6110
80
89
167
343
514
989
1580
2790
5680
90
83
157
322
482
928
1480
2610
5330
100
79
148
304
455
877
1400
2470
5040
125
70
131
269
403
777
1240
2190
4460
150
63
119
244
366
704
1120
1980
4050
175
58
109
224
336
648
1030
1820
3720
200
54
102
209
313
602
960
1700
3460
Based on gas pressures less than 2 psig and a pressure drop of 3.0 iwc and 0.6 specific gravity.
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
Appendix A Sizing Gas Piping
Design the gas piping system to provide an adequate gas supply to the boiler. Refer to Table 6 for
minimum and maximum gas supply pressures and boiler capacities. Also consider existing and
expected future gas utilizing equipment (i.e., water heater, cooling equipment). Refer to Table 18 for
maximum capacity of schedule 40 pipe. Table 19 lists equivalent pipe length for standard fittings.
Given the specific gravity of gas at the boiler’s location, a correction factor can be found on Table
20 and multiplied by the “Capacity in Cubic Feet of Gas Per Hour” on Table 18. For gas piping
material other than schedule 40 pipes, refer to the National Fuel Gas Code, NFPA 54/ANZI
Z223.1 and/or CAN/CGA B149 Installation codes. Use methods and materials in accordance with
Local Codes and requirements of gas supplier. In the absence of such requirement follow National
Fuel Gas Codes, NFPA /ANSI Z 223.1 and/or CAN/CGA B149 Installation Codes.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web:www.bryanboilers.com
FF1000 Pressure Drop in Equivalent Feet (Flue Vent)
Flue Vent
Diameter (in.)
Straight Length
(eq ft/ft)
90° Elbow
(eq ft)
45° Elbow
(eq ft)
Velocity
(fpm)
6 1 10
5
1534
8
.22
2.22
1.11
863
FF1500 Pressure Drop in Equivalent Feet (Flue Vent)
8
.56
5.88
2.86
1296
10
.174
1.75
.87
829
FF2000 Pressure Drop in Equivalent Feet (Flue Vent)
8 1 10
5
1728
10
.31
3.125
1.56
1106
12
.12
1.19
.59
768
FF2500 Pressure Drop in Equivalent Feet (Flue Vent)
8
1.563
16.67
8.33
2158
10
.478
5
2.44
1381
12
.183
1.852
.92
959
FF3000 Pressure Drop in Equivalent Feet (Flue Vent)
8
2.22
25
11.11
2591
10
.68
7.14
3.57
1650
12
.267
2.7
1.35
1152
FF1000 Pressure Drop in Equivalent Feet (Combustion Air Duct)
Air Duct
Diameter (in.)
Straight Length
(eq ft/ft)
90° Elbow
(eq ft)
45° Elbow
(eq ft)
Velocity
(fpm)
6
.6
6.25
3.13
1121
8
.13
1.32
.658
631
FF1500 Pressure Drop in Equivalent Feet (Combustion Air Duct)
8
.3
3.03
1.49
946
10
.09
.92
.46
605
FF2000 Pressure Drop in Equivalent Feet (Combustion Air Duct)
8
.53
5.26
2.63
1264
10
.164
1.64
.82
809
12
.063
.63
.314
562
FF2500 Pressure Drop in Equivalent Feet (Combustion Air Duct)
8
.83
8.3
4.17
1576
10
.26
2.56
1.28
1009
12
.1
.98
.49
701
FF3000 Pressure Drop in Equivalent Feet (Combustion Air Duct)
8
1.19
12.5
5.9
1895
10
.37
3.7
1.85
1213
12
.14
1.41
.7
842
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
Appendix B Vent and Combustion Air Pressure Drop Data
The combined pressure drop through the vent and combustion air duct shall not exceed 100
equivalent feet. Use the tab l es below to calculate the pressure drop in the vent / combustion
air system.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Wiring diagrams are for reference only, please refer to the wiring shipped with the boiler for accuracy.
Form: 2435
70
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
Appendix I Repair Parts
All boiler Repair Parts may be obtained through your local authorized Bryan Steam Representative.
Should you require assistance in locating a Bryan Steam representative in your area, or have
questions regarding the availability of Bryan Steam products or repair parts, please contact Bryan
Steam Customer Service at (717)-239-7642 or Fax (877)-501-5212.
Appendix I.1 FF1000 Heat Exchanger
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
Bryan Steam
(“seller”)
LIMITED WARRANTY
LIFETIME THERMAL SHOCK WARRANTY
Subject to the terms and conditions herein, Seller
warrants to the original owner at the original
installation site that the boiler pressure vessel is
covered against failure due to “Thermal Shock” for the
lifetime of the boiler as described below:
• This warranty is only valid if the boiler is installed
and operated in accordance with our Installation
and Operation Manual.
• This warranty shall cover leaks in pressure vessel
(boiler tubes, upper and lower drums) when upon
inspection by seller, such damage is attributed to
unequal expansion, often described as “thermal
shock.”
• This warranty does not cover damages or failures
that can be attributed to corrosion, scale, dirt or
sludge accumulation in the boiler, low water
conditions, failure of any safety devices or any
other improper service, operation or neglect.
LIFETIME PRESSURE VESSEL WARRANTY
Subject to the terms and conditions herein, Seller
warrants to the original owner at the original
installation site that the boiler pressure vessel is
covered against leaks (boiler tubes, upper and lower
drums) for the lifetime of the boiler as described below:
• This warranty is only valid if the boiler is installed
and operated in accordance with our Installation
and Operation Manual.
• This warranty shall cover leaks in pressure vessel
(as described above) when upon inspection by
seller, such damage is attributed to unequal
expansion, often described as “thermal shock.”
• This warranty does not cover damages or failures
that can be attributed to corrosion, scale, dirt or
sludge accumulation in the boiler, low water
conditions, failure of any safety devices or any
other improper service, operation or neglect.
FLUE GAS CORROSION WARRANTY
Subject to the terms and conditions herein, Seller
warrants to the original owner at the original
installation site that the pressure vessel and flue
collector are covered against failure due to fireside flue
gas corrosion per the schedule as follows:
A. Upper and Lower Pressure Vessel Headers -
10 years from date of shipment.
B. Flexible Boiler Tubes -
5 years from date of shipment.
C. Flue Collector Sides, Top and Bottom -
5 years from date of shipment.
BURNER HEAD WARRANTY
Subject to the terms and conditions herein, Seller
warrants to the original owner at the original
installation site that the burner head will be free from
defects in materials and workmanship for a period of
one year after the date of shipment.
LIMITED WARRANTY
Subject to the terms and conditions herein, Seller
warrants to the original owner at the original
installation site those products manufactured by Seller
(“Products”) comply, at the time of manufacture, with
recognized hydronics industry regulatory agency
standards and requirements then in effect and will be
free from defects in materials and workmanship for a
period of one year after the date of shipment.
REMEDY
A. The sole remedy for breach of this warranty is
expressly limited to the repair or replacement of
any part found to be defective under conditions of
normal use within the Warranty Period. Labor for
removal and /or installation is not included.
B. Warranty – The owner must notify the original
installer of the Product and Seller (Attention:
Bryan Steam, P.O. Box 3244, Lancaster, PA
17604-3244), in writing, within the Warranty
Period, providing a detailed description of all
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
claimed defects. Transportation to a factory or
other designated facility for repairs of any products
or items alleged defective shall, in all events, be the
responsibility and at the cost of the owner.
Exclusions
Seller shall have no liability for and this warranty does
not cover:
A. Incidental, special or consequential damages, such
as loss of the use of products, facilities or production,
inconvenience, loss of time or labor expense involved
in repairing or replacing the alleged defective Product.
B. The performance of any Product under
conditions varying materially from those under which
such Product is usually tested under industry standards
as of the time of shipment
C. Any damage to the Product due to abrasion,
erosion, corrosion, deterioration, abnormal
temperatures or the influence of foreign matter or
energy.
1. Defective installations in general and
specifically, any installation, which is made:
a. In violation of applicable state or
local plumbing housing or building
codes,
b. Without a certified ASME, pressure
relief valve, or
c. Contrary to the written instructions
furnished with the unit.
2. Adverse local conditions in general and,
specifically, sediment or lime precipitation in
the tubes and/or headers or corrosive
elements in the atmosphere.
3. Misuse in general and, specifically, operation
and maintenance contrary to the written
instructions furnished with the unit,
disconnection, alteration or addition of
components or apparatus, not approved by
Seller, operation with fuels or settings other
than those set forth on the rating plate or
accidental or exterior damage.
D. The design or operation of owner’s plant or
equipment or of any facility or system of which any
Product may be made a part.
E. The suitability of any Product for any particular
application.
F. Any failure resulting from misuse, modification
not authorized by Seller in writing, improper
installation or lack of or improper maintenance.
G. Equipment furnished by the owner, either
mounted or un-mounted, or when contracted for by
the owner to be installed or handled.
H. Leakage or other malfunction caused by:
I. Production of noise, orders, discoloration or rusty
water.
J. Damage to surrounding area or property caused by
leakage or malfunction.
K. Costs associated with the replacement and/or
repair of the unit including: any freight, shipping or
delivery charges, and removal, installation or
reinstallation charges, any material and/or permits
required for installation, reinstallation or repair, charges
to return the boiler and or components.
Seller’s liability under this warranty shall not in any case
exceed the amount paid for the Product found to be
defective.
Third-Party Warranties
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com
For goods or components not manufactured by Seller,
the warranty obligations of Seller shall, in all respects,
Form: 2435
85
Revision: 9
Free Flex Installation and Operation Manual Date: 9-1-2017
conform and be limited to one year from the date of
shipment.
Severability
To the extent that any provisions shall of this warranty
would be void or prohibited under applicable law, such
provisions shall be limited in effect to the minimum
extent necessary to render the remaining provisions
hereof enforceable.
Bryan Steam LLC, 783 N Chili Ave, Peru IN 46970 Web: www.bryanboilers.com