Bryan Boilers EB-200-W-FDGO, EB-75-S150-FDG User Manual

Bryan “Flexible Water Tube”
EB Series
Steam & Water Boilers
3,200,000 to 10,000,000 BTUH
Form No. 8100
(1/06 )
Water Boiler
EB-200-W-FDGO
Steam Boiler
EB-75-S150-FDG
BRYAN® BOILERS
Originators of the “Flexible Water Tube” design
Low initial cost, reliable operating effi ciency deliver substantial return on investment
• True “fl exible water tube” design
• High quality steam for heat or process
• Pressurized fi ring for maximum performance
J
Quality Construction Features:
A. Water side or steam side interior ac cessible
for clean out and inspection, front and rear open ings, upper and lower drums.
B. Large volume water leg down comers pro­mote rapid internal circulation, temperature equalization and effi cient heat transfer.
C. Boiler tube and furnace area access panels: heavy gauge steel casing with 2high tem­perature ceramic fi ber and insulation, bolted and tightly sealed to boiler frame.
D. Flame observation port at rear of boiler. E. Single side access; combustion chamber, tubes and
burner head are completely accessible from one side simplifying maintenance and minimizing fl oor space.
F. Minimum sized fl ue vent. G. Control panel: all controls installed with connections
to terminal strip. H. Forced draft, fl ame retention head type burner. Effi -
cient combustion of oil or gas, plus quiet operation. I. Heavy steel boiler frame, built and stamped in accor-
dance with the appropriate ASME Boiler Code. J. Heavy gauge steel boiler jacket with rust-resistant
zinc coating and enamel fi nish, insulated with 1½ fi berglass to ensure exceptionally cool outer surface.
K. Bryan bent water tubes are flexible, individually replaceable without welding or rolling. Never more than two tube configurations.
F
N
A
B
D
I
L. Internal water-cooled furnace with low heat release rate.
M. Steam boilers with extra large drum with high steam release area ensure stable water level and dry steam.
N. Pressurized design: inner fi reside casing con­structed of heavy gauge steel, completely seal­welded, lined with high temperature insulation and refractory.
K
L
M
D
C
E
G
H
Bryan EB Series Boiler Specifi cations
NOMINAL OUTPUT STEAM APPROX.
BOILER INPUT MODEL MBH (KW)
EB-75 3,200 (938) 2,560 (750) 75 2,639 (1,197) 5,810 (2,635)
EB-100 4,200 (1,230) 3,360 (984) 100 3,463 (1,570) 7,110 (3,225)
EB-125 5,250 (1,538) 4,200 (1,230) 125 4,329 (1,963) 8,300 (3,765)
EB-150 6,300 (1,845) 5,040 (1,476) 150 5,195 (2,356) 8,420 (3,819)
EB-175 7,325 (2,146) 5,860 (1,717) 175 6,041 (2,740) 11,175 (5,069)
EB-200 8,500 (2,490) 6,800 (1,992) 200 7,010 (3,179) 11,305 (5,128)
EB-240 10,000 (2,930) 8,000 (2,344) 240 8,247 (3,740) 14,455 (6,557)
NOTES: * * Nominal output based on boiler industry standard of 80% of input. Actual combustion effi ciencies will be fuel dependent. ** Lbs. steam per hour from and at 212° F.
OUTPUT SHIP WT.
MBH (KW)*
BHP*
LBS./HR** (KG) LBS. (KG)