Bryan “Flexible Water Tube”
EB Series
Steam & Water Boilers
3,200,000 to 10,000,000 BTUH
Forced draft gas, oil or dual fuel fi red
Form No. 8100
(1/06 )
Water Boiler
EB-200-W-FDGO
Steam Boiler
EB-75-S150-FDG
BRYAN® BOILERS
Originators of the “Flexible Water Tube” design
Low initial cost, reliable operating effi ciency
deliver substantial return on investment
• True “fl exible water tube” design
• High quality steam for heat
or process
• Pressurized fi ring for maximum
performance
J
Quality Construction Features:
A. Water side or steam side interior ac cessible
for clean out and inspection, front and rear
open ings, upper and lower drums.
B. Large volume water leg down comers promote rapid internal circulation, temperature
equalization and effi cient heat transfer.
C. Boiler tube and furnace area access panels:
heavy gauge steel casing with 2 high temperature ceramic fi ber and insulation, bolted
and tightly sealed to boiler frame.
D. Flame observation port at rear of boiler.
E. Single side access; combustion chamber, tubes and
burner head are completely accessible from one side
simplifying maintenance and minimizing fl oor space.
F. Minimum sized fl ue vent.
G. Control panel: all controls installed with connections
to terminal strip.
H. Forced draft, fl ame retention head type burner. Effi -
cient combustion of oil or gas, plus quiet operation.
I. Heavy steel boiler frame, built and stamped in accor-
dance with the appropriate ASME Boiler Code.
J. Heavy gauge steel boiler jacket with rust-resistant
zinc coating and enamel fi nish, insulated with 1½
fi berglass to ensure exceptionally cool outer surface.
K. Bryan bent water tubes are flexible, individually
replaceable without welding or rolling. Never more
than two tube configurations.
F
N
A
B
D
I
L. Internal water-cooled
furnace with low heat
release rate.
M. Steam boilers with
extra large drum with high
steam release area ensure
stable water level and dry
steam.
N. Pressurized design:
inner fi reside casing constructed of heavy gauge
steel, completely sealwelded, lined with high
temperature insulation
and refractory.
K
L
M
D
C
E
G
H
Bryan EB Series Boiler Specifi cations
NOMINAL OUTPUT STEAM APPROX.
BOILER INPUT
MODEL MBH (KW)
EB-75 3,200 (938) 2,560 (750) 75 2,639 (1,197) 5,810 (2,635)
EB-100 4,200 (1,230) 3,360 (984) 100 3,463 (1,570) 7,110 (3,225)
EB-125 5,250 (1,538) 4,200 (1,230) 125 4,329 (1,963) 8,300 (3,765)
EB-150 6,300 (1,845) 5,040 (1,476) 150 5,195 (2,356) 8,420 (3,819)
EB-175 7,325 (2,146) 5,860 (1,717) 175 6,041 (2,740) 11,175 (5,069)
EB-200 8,500 (2,490) 6,800 (1,992) 200 7,010 (3,179) 11,305 (5,128)
EB-240 10,000 (2,930) 8,000 (2,344) 240 8,247 (3,740) 14,455 (6,557)
NOTES: * * Nominal output based on boiler industry standard of 80% of input. Actual combustion effi ciencies will be fuel dependent.
** Lbs. steam per hour from and at 212° F.
OUTPUT SHIP WT.
MBH (KW)*
BHP*
LBS./HR** (KG) LBS. (KG)