Warnings and Cautions 2
Typical Installation 2
New Construction Installation 3
Retrofit Installation 7
Operation 12
Cleaning and Maintenance 12
Troubleshooting 12
Service Parts 13
Warranty 14
Page 2
ZB80M n ZB110M Installation Guide
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR
INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer.
If you have questions, contact the manufacturer at the address
or telephone number listed in the warranty.
2. Before servicing or cleaning unit, switch power off at service
panel and lock the service disconnecting means to prevent
power from being switched on accidentally. When the service
disconnecting means cannot be locked, securely fasten a
prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by a
qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction codes and
standards.
4. Sufficient air is needed for proper combustion and exhausting
of gases through the flue (chimney) of fuel burning equipment
to prevent backdrafting. Follow the heating equipment
manufacturer’s guideline and safety standards such as those
published by the National Fire Protection Association (NFPA),
and the American Society for Heating, Refrigeration and
Air Conditioning Engineers (ASHRAE), and the local code
authorities.
5. When cutting or drilling into wall or ceiling, do not damage
electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. Use only ON/OFF switch, mechanical timer or relay-switched
control.
8. Acceptable for use over a tub or shower when connected to
a GFCI (Ground Fault Circuit Interrupter) - protected branch
circuit.
9. This unit must be grounded.
CAUTION
1. For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors.
2. This product is designed for installation in flat ceilings. Sensor
will not function reliably if product is not installed in flat ceiling.
DO NOT MOUNT THIS PRODUCT IN A WALL.
3. To avoid motor bearing damage and noisy and/or unbalanced
impellers, keep drywall spray, construction dust, etc. off power
unit.
4. Please read specification label on product for further
information and requirements.
NOT FOR USE IN A COOKING AREA
Do not install above or inside this area
45°45°
Cooking
Equipment
Floor
Typical Installation
• Installation is the same for:
Joists I-Joists Trusses
• Fits in 2" x 8" ceiling construction.
• Infinitely adjust the fan position
between joists from 14" to 24"
on center.
The ducting from this fan to the outside of the building has a strong effect on the air flow, noise and energy use of the fan. Use the shortest, straighest duct routing possible for best performance, and avoid
installing the fan with smaller ducts than recommended. Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed with existing ducts may not achieve their rated airflow.
6-inch round rigid metal duct is recommended for best performance.
HOUSING
POWER
CABLE*
Seal gaps
around
Housing.
*Purchase
separately.
INSULATION*
(Place around and
over Fan Housing.)
FAN
ROUND
DUCT*
Seal duct
joints with
tape.
OR
ROUND
ELBOWS*
ROOF CAP*
(with built-in
damper)
Keep duct
runs short.
WALL CAP*
(with built-in
damper)
Page 3
New Construction Installation
ZB80M n ZB110M Installation Guide
Tools needed
• Power screwdriver with a Phillips bit
• Phillips screwdriver
• Flathead screwdriver
• Pliers
• Wire insulation stripper
• Wire cutter
Remove Packaging
1
Parts Bag holds
Knockout Plate
and six (6)
screws
Materials needed
• 6" round metal ducting recommended for best performance.
Use of other ducting is acceptable but may impact performance.
• Roof cap or wall cap (built-in damper recommended)
• Tape to seal duct connections
• Electrical wiring and supplies per local code requirements
Punch out Mask from
packaging. See Step 6.
Remove
Instruction
Sheet
Install
2
Mounting
Frame
2
1
4
3
Page 4
New Construction Installation
Snap-in and
3
Secure Housing
2
snap!
ZB80M n ZB110M Installation Guide
1
4
Attach Duct Connector and Ducting
4
Top and bottom flanges
go outside Housing
Insert tab into slot
inside Housing
1
6" Ducting
Tape
Screws from Parts Bag
3
3
4" Ducting
Tape
Position Housing
between joists and
crimp channel on both
sides of Mounting Frame
to lock Housing in place.
Do not crimp Housing.
Screw from
2
Parts Bag
Tape
6" to 4" Reducer (for Model ZB80M only)
Page 5
New Construction Installation
Connect Wires and Install Knockout Plate
5
• Run 120VAC electrical wiring to the installation location.
• Use proper UL-approved connectors to secure wiring to the Knockout Plate provided in Parts Bag.
• Connect wires as shown in wiring diagram.
Attach cable clamp to Knockout
1
Plate. Knockout Plate mounts to
outside of Housing and may be
oriented as desired.
Connect wires
2
ZB80M n ZB110M Installation Guide
3
4
Screw from
Parts Bag
GRD
120 VAC
LINE IN
MASTER
ON/OFF
SWITCH*
WHT
BLK
SENSOR
CONTROL
SWITCH*
purchase separately
*
MASTERMANUAL-ON
FUNCTION WALL SWITCHES
BLACK
WHITE
SENSOR/
CONTROL
STANDARD OR MULTI-
RED
BLUE
MANUAL
ON
SWITCH*
SWITCH BOX
120 VAC
LINE IN
GRD
WHT
BLK
BLU
RED
(IF ALL
WALL SWITCH
OPTIONS
ARE USED)
ORANGE
BROWN
GROUND
(green or bare)
KNOCKOUT
14/4
PLATE
BLK
RED
BLK
BRN
SENSOR/
CONTROL
ORG
RECEPTACLES
WHT
FAN
• See OPERATION section on page 12
for details.
• MASTER switch turns fan system
on and shuts it off for fan cleaning and
maintenance purposes.
• SENSOR/CONTROL switch turns
motion control automatic operation on/off.
• MANUAL-ON switch directly increases
fan operation to certified airflow rate.
• MASTER and SENSOR/CONTROL
switches can be combined (see page 10).
• MASTER switch along with or separate
from SENSOR/CONTROL switch may be
located where it is not easily accessed
for everyday usage; they may need to
be labeled and located where it can’t be
turned on without being seen from fan to
comply with local and national codes.
Page 6
New Construction Installation
Insert Mask and
6
Finish Ceiling
• Install ceiling material.
• Cut out around Housing.
CAUTION
IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE:
If the blower was unplugged, power must be
disconnected (see page 2, WARNING item 2)
before inserting motor plugs into control assembly.
ZB80M n ZB110M Installation Guide
Mask protects unit
during construction.
Remove before
installing Grille.
Install Grille
7
Plug in
Sensor
See Page 12 for Operations, Cleaning and Maintenance, and Troubleshooting.
1
2
3
Page 7
Retrofit Installation
ZB80M n ZB110M Installation Guide
Tools needed
• Power screwdriver with a Phillips bit
• Phillips screwdriver
• Flathead screwdriver
• Pliers
• Wire insulation stripper
• Wire cutter
• Ruler
• Pencil
• Drywall saw
• Claw hammer or pry bar
• Utility knife
Materials needed
• Tape to seal duct connections
• Existing rigid duct will require the
addition of a short length of flexible duct
• Electrical wiring and supplies per
local code requirements
Remove Packaging
1
Parts Bag holds
Knockout Plate
and six (6)
screws
Remove
Instruction
Sheet
Punch out Mask from
packaging. See Step 12.
Switch Off Power
2
WARNING
Before removing existing fan, switch power off at service panel and lock the service disconnecting
means to prevent power from being switched on accidentally. When the service disconnecting means
cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
Enlarge Ceiling Opening and Remove Existing Fan
3
12" (30.5 cm)
1
11" (27.9 cm)
parallel with joists
Existing ductwork and
wiring left in place
Examine Wiring
4
Examine the existing wiring to make sure it is not damaged. If any damage is found,
DO NOT CONTINUE INSTALLATION of this product. Contact a qualified person(s) for repair.
2
Page 8
Retrofit Installation
Remove Blower Assembly
5
2
ZB80M n ZB110M Installation Guide
1
Set aside
Blower
Assembly
Both sides
Remove Wiring Panel
6
Set aside
screw
1
3
Set aside
Wiring Panel
2
3
Insert
7
Mounting
Frame
4
3
1
Remove screws from
Mounting Frame
and set aside
5
2
Bend up
four tabs
Page 9
Retrofit Installation
Secure
8
Mounting
Frame
Snap-in Housing
9
ZB80M n ZB110M Installation Guide
Screws set
aside
in Step 7
2
10
Pull existing
ductwork
into Housing
1
Pull existing wiring into
Housing as it is inserted
into Mounting Frame
snap!
Attach Ducting and Duct Connector
1
4
Screw from
Parts Bag
3
Insert tab into
slot inside
Housing
6" Ducting
Tape
2
4" Ducting
6" to 4" Reducer (for Model ZB80M only)
Tape
Tape
Page 10
Retrofit Installation
Install Knockout Plate, Connect Wires and Reinstall Wiring Panel
11
Screw from
Parts Bag
• Use proper UL-approved connectors to secure wiring to the Knockout Plate provided in Parts Bag.
• Connect wires as shown in wiring diagram.
Attach cable clamp to Knockout
1
Plate. Knockout Plate mounts to
inside of Housing and may be
oriented as
2
ZB80M n ZB110M Installation Guide
desired.
Screw set
aside in
Step 6
5
6
4
Connect
3
wires
• See OPERATION section on page
12 for details.
• MASTER switch turns fan system
on along with motion control and shuts
them off for cleaning and maintenance
purposes.
• MASTER switch may be located where
it is not easily accessed for everyday
usage; it may need to be labeled and
located where it can’t be turned on without
being seen from fan to comply with local
and national codes.
120 VAC
LINE IN
BLK
WHT
GRD
BLACK
WHITE
MASTER
WALL
SWITCH
MASTER
WALL
SWITCH*
BLK
WHT
GRD
ORANGE
BROWN
SWITCH BOX
14/2
GROUND
(green or bare)
BLK
RED
BRN
KNOCKOUT
PLATE
FAN
BLK
SENSOR/
CONTROL
ORG
WHT
RECEPTACLES
purchase separately
*
120 VAC
LINE IN
Pa g e 11
Retrofit Installation
Reinsert and Secure Blower Assembly
12
CAUTION
Power must be disconnected (see page 2, WARNING item 2) before inserting motor plugs into control assembly.
ZB80M n ZB110M Installation Guide
IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE:
13
Plug in
Sensor
Install Grille
1
1
2
23
Screws from Parts Bag
If ceiling repairs are needed, place Mask in
Housing after Blower Assembly is secured.
See New Construction Installation Step 6.
Remove Mask before installing Grille.
3
Page 12
ZB80M n ZB110M Installation Guide
WARNING Before servicing or cleaning unit, switch
power off at service panel and lock the service disconnecting
means to prevent power from being switched on accidentally. When
the service disconnecting means cannot be locked, securely fasten
a prominent warning device, such as a tag, to the service panel.
Operation
It is normal for this ventilation fan to take approximately 5 seconds to
start running after it is turned on.
Modes
(For reference, wiring diagrams are on pages 5 and 10.)
Continuous ventilation:
1. Turn master wall switch on.
2. Fan operates at user-adjustable airflow rate.
Motion sensing:
1. If master wall switch is not already on, turn it on.
2. Turn sensor/control wall switch on. Some installations may not have a
separate sensor/control wall switch; where it is combined with master
wall switch.
3. Fan operates at certified airflow rate and sensor detects motion.
4. When no more motion is detected, fan enters time delay mode. (See
below.)
Manual-on (optional manual-on wall switch must be installed):
1. Turn master and manual-on wall switches on (sensor/control wall
switch can be on or off).
2. Fan operates at certified airflow rate.
3. When manual-on wall switch is turned off, fan enters timed-off mode.
(See below.)
Time Delay:
Fan continues to run at cerified airflow rate until user-adjustable TIME
delay has passed, then fan reverts to user-adjustable airflow rate.
Cleaning and Maintenance
CAUTION
IN ORDER TO PREVENT MOTOR/
CONTROL DAMAGE:
DO NOT remove motor plug to stop spinning
motor.
Power must be disconnected (see
WARNING at top left of this page) before
motor plug is removed or inserted into
control assembly.
To Clean
For quiet and efficient operation, long life and
attractive appearance, remove Grille and
vacuum interior of unit with a dusting brush
attachment.
Do not use cleaning sprays, solvents or water
on, or near, the sensor.
Motor is permanently lubricated and never
needs oiling. If motor is making excessive or
unusual noises, replace Control Assembly
and Motor.
To Set the User-Adjustable Airflow Rate*
Using a small, flat-blade screwdriver, carefully rotate the CFM
adjustment until the arrow points to the desired airflow rate.
To Set the User-Adjustable Time Delay*
Using a small, flat-blade screwdriver, carefully rotate TIME adjustment
until the arrow points to the desired minutes of time delay.
* The user-adjustable controls are located in one corner of the Fan
Housing, behind the Grille.
ZB80M User-adjustable controls
ZB110M User-adjustable controls
To Turn Fan OFF
Turn the master switch OFF.
Page 13
ZB80M n ZB110M Installation Guide
Troubleshooting
Before continuing, turn off power as previously noted
in WARNING and CAUTION sections at the top of the
previous page.
Symptom: Fan does not run.
• Check for an open fuse or circuit breaker in building’s
service panel.
• Check two (2) plug-in connections for Motor and its
Control are seated firmly in place.
• Check two (2) plug-in connections for Sensor and its
Control are seated firmly in place.
• Check that Blower Wheel spins freely.
Symptom: Motion mode does not operate fan at certi-
fied air flow rate.
• Check two (2) plug-in connections for Sensor and its
Control are seated firmly in place.
Symptom: Fan runs erratically.
• Check that Blower Wheel is firmly attached to Motor
shaft and both spin freely.
Service Parts
1
2
3
5
4
7
6
8
Symptom: Fan seems noisy.
• Check that back draft damper in fan’s Duct Connector
pivots freely. Screws used to attach duct to Duct Connector may prevent damper from opening.
• Check that back draft damper in wall or roof cap pivots
freely. Dampers are sometimes mistakenly painted shut
or obstructed by bird or insect debris.
Symptom: Fan does not properly ventilate room.
• For spot ventilation, turn both master switch and sensor/
control wall switch ON, so sensor/control operates fan at
certified airflow rate.
• For spot ventilation followed by continuous ventilation,
increase the “TIME” setting of user-adjustable time delay.
• For continuous ventilation, increase “CFM” setting of
user-adjustable airflow rate.
9
Order replacement
parts by Part No.,
not by Key No.
WARRANTY PERIOD: Broan warrants to the original consumer purchaser
of its Broan Ventilation Fan/Light (the “Fan”) that your Fan (excluding lamps/
bulbs) will be materially free from defects in materials or workmanship for a
period of three (3) years from the date of original purchase. The warranty on
the lamps/bulbs provided with the Fan is one (1) year and does not cover
lamp/bulb breakage. This warranty does not cover accessories, such as
speed controls, that may be purchased separately and installed with the Fan.
The limited warranty period for replacement parts, and for Fans repaired or
replaced under this limited warranty, shall continue for the remainder of the
original warranty period.
NO OTHER WARRANTIES: THE FOREGOING WARRANTIES ARE
EXCLUSIVE AND IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR
IMPLIED. BROAN DISCLAIMS AND EXCLUDES ALL OTHER EXPRESS
WARRANTIES, AND DISCLAIMS AND EXCLUDES ALL WARRANTIES
IMPLIED BY LAW, INCLUDING WITHOUT LIMITATION THOSE OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. TO
THE EXTENT THAT APPLICABLE LAW PROHIBITS THE EXCLUSION
OF IMPLIED WARRANTIES, THE DURATION OF ANY APPLICABLE
IMPLIED WARRANTY IS LIMITED TO THE PERIOD SPECIFIED FOR THE
EXPRESS WARRANTY. Some states do not allow limitations on how long an
implied warranty lasts, so the above limitation may not apply to you. Any oral
or written description of the Fan is for the sole purpose of identifying it and
shall not be construed as an express warranty.
REMEDY: During the applicable limited warranty period, Broan will, at its
option, provide replacement parts for, or repair or replace, without charge,
any Fan or part thereof, to the extent Broan finds it to be covered by and in
breach of this limited warranty. Broan will ship the repaired or replaced Fan
or replacement parts to you at no charge. You are responsible for all costs
for removal, reinstallation and shipping, insurance or other freight charges
incurred in the shipment of the Fan or part to Broan. This warranty does not
cover (a) normal maintenance and service, (b) normal wear and tear, (c) any
Fans or parts which have been subject to misuse, abuse, abnormal usage,
negligence, accident, improper or insufficient maintenance, storage or repair
(other than repair by Broan), (d) damage caused by faulty installation, or
installation or use contrary to recommendations or instructions, (e) any Fan
that has been moved from its original point of installation, (f) damage caused
by environmental or natural elements, (g) damage in transit, (h) natural wear
of finish, (i) Fans in commercial or nonresidential use, or (j) damage caused
by fire, flood or other act of God. This warranty covers only Fans sold in the
United States or through U.S. distributors authorized by Broan.
EXCLUSION OF DAMAGES: BROAN’S OBLIGATION TO PROVIDE
REPLACEMENT PARTS, OR REPAIR OR REPLACE, AT BROAN’S
OPTION, SHALL BE YOUR SOLE AND EXCLUSIVE REMEDY UNDER
THIS LIMITED WARRANTY AND BROAN’S SOLE AND EXCLUSIVE
OBLIGATION. BROAN SHALL NOT BE LIABLE FOR INCIDENTAL,
INDIRECT, CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT
OF OR IN CONNECTION WITH THE FAN, ITS USE OR PERFORMANCE.
Incidental damages include but are not limited to such damages as loss of
time and loss of use. Consequential damages include but are not limited to
the cost of repairing or replacing other property which was damaged if the
Fan does not work properly.
Some states do not allow the exclusion or limitation of incidental or
consequential damages, so the above limitation or exclusion may not apply
to you. This warranty gives you specific legal rights, and you may also have
other rights, which vary from state to state.
This warranty supersedes all prior warranties and is not transferable from the
original consumer purchaser.
BROAN SHALL NOT BE LIABLE TO YOU, OR TO ANYONE CLAIMING
UNDER YOU, FOR ANY OTHER OBLIGATIONS OR LIABILITIES,
INCLUDING, BUT NOT LIMITED TO, OBLIGATIONS OR LIABILITIES
ARISING OUT OF BREACH OF CONTRACT OR WARRANTY,
NEGLIGENCE OR OTHER TORT OR ANY THEORY OF STRICT LIABILITY,
WITH RESPECT TO THE FAN OR BROAN’S ACTS OR OMISSIONS OR
OTHERWISE.
This warranty covers only replacement or repair of defective Fans or parts
thereof at Broan’s main facility and does not include the cost of field service
travel and living expenses.
Any assistance Broan provides to or procures for you outside the terms,
limitations or exclusions of this limited warranty will not constitute a waiver
of such terms, limitations or exclusions, nor will such assistance extend or
revive the warranty.
Broan will not reimburse you for any expenses incurred by you in repairing
or replacing any defective Fan, except for those incurred with Broan’s prior
written permission.
HOW TO OBTAIN WARRANTY SERVICE: To qualify for warranty service,
you must (a) notify Broan at the address or telephone number stated below
within seven (7) days of discovering the covered defect, (b) give the model
number and part identification and (c) describe the nature of any defect in
the Fan or part. At the time of requesting warranty service, you must present
evidence of the original purchase date.
Broan, 926 West State Street, Hartford, WI 53027
(1-800-637-1453)
www.broan.com
If you must send the Fan or part to Broan, as instructed by Broan, you must
properly pack the Fan or part—Broan is not responsible for damage in transit.
ZB80M n ZB110M Installation Guide
99045844B
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.