Warnings and Cautions 2
Typical Installation 2
New Construction Installation 3
Retrofit Installation 7
Operation 12
Cleaning and Maintenance 12
Troubleshooting 12
Service Parts 13
Warranty 13
Page 2
XB50L1
n
XB80L1
n
XB110L1 Installation Guide
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR
INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer.
If you have questions, contact the manufacturer at the address
or telephone number listed in the warranty.
2. Before servicing or cleaning unit, switch power off at service
panel and lock the service disconnecting means to prevent
power from being switched on accidentally. When the service
disconnecting means cannot be locked, securely fasten a
prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by a
qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction codes and
standards.
4. Sufficient air is needed for proper combustion and exhausting
of gases through the flue (chimney) of fuel burning equipment
to prevent backdrafting. Follow the heating equipment
manufacturer’s guideline and safety standards such as those
published by the National Fire Protection Association (NFPA),
and the American Society for Heating, Refrigeration and
Air Conditioning Engineers (ASHRAE), and the local code
authorities.
5. When cutting or drilling into wall or ceiling, do not damage
electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. Use only ON/OFF switch, mechanical timer or relay-switched
control.
8. Acceptable for use over a tub or shower when connected to
a GFCI (Ground Fault Circuit Interrupter) - protected branch
circuit.
9. This unit must be grounded.
CAUTION
1. For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors.
2. This product is designed for installation in ceilings up to a
12/12 pitch (45 degree angle). Duct connector must point up.
DO NOT MOUNT THIS PRODUCT IN A WALL.
3. To avoid motor bearing damage and noisy and/or unbalanced
impellers, keep drywall spray, construction dust, etc. off power
unit.
4. Please read specification label on product for further
information and requirements.
NOT FOR USE IN A COOKING AREA
Do not install above or inside this area
45°45°
Cooking
Equipment
Floor
Typical Installation
• Installation is the same for:
Joists I-Joists Trusses
• Fits in 2" x 8" ceiling construction.
• Infinitely adjust the fan position
between joists from 14" to 24"
on center.
• Do not install this fan in a ceiling
thermally insulated to a value
greater than R40.
The ducting from this fan to the outside of the building has a strong effect on the air flow, noise and energy use of the fan. Use the shortest, straighest duct routing possible for best performance, and avoid
installing the fan with smaller ducts than recommended. Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed with existing ducts may not achieve their rated airflow.
6-inch round rigid metal duct is recommended for best performance.
HOUSING
POWER
CABLE*
Seal gaps
around
Housing.
*Purchase
separately.
INSULATION*
(Place around and
over Fan Housing.)
FAN
ROUND
DUCT*
Seal duct
joints with
tape.
OR
ROUND
ELBOWS*
ROOF CAP*
(with built-in
damper)
Keep duct
runs short.
WALL CAP*
(with built-in
damper)
Page 3
New Construction Installation
XB50L1
n
XB80L1
n
XB110L1 Installation Guide
Tools needed
• Power screwdriver with a Phillips bit
• Phillips screwdriver
• Flathead screwdriver
• Pliers
• Wire insulation stripper
• Wire cutter
Remove Packaging
1
Parts Bag holds
Knockout Plate
and six (6)
screws
Materials needed
• 6" round metal ducting recommended for best performance.
Use of other ducting is acceptable but may impact performance.
• Roof cap or wall cap (built-in damper recommended)
• Tape to seal duct connections
• Electrical wiring and supplies per local code requirements
Punch out Mask from
packaging. See Step 6.
Remove
Instruction
Sheet
Install
2
Mounting
Frame
2
1
4
3
Page 4
New Construction Installation
Snap-in and
3
Secure Housing
2
snap!
XB50L1
n
XB80L1
n
XB110L1 Installation Guide
1
4
Attach Duct Connector and Ducting
4
Top and bottom flanges
go outside Housing
Insert tab into slot
inside Housing
1
6" Ducting
Tape
Screws from Parts Bag
3
3
4" Ducting
Tape
Position Housing
between joists and
crimp channel on both
sides of Mounting Frame
to lock Housing in place.
Do not crimp Housing.
Screw from
2
Parts Bag
Tape
6" to 4" Reducer provided in select models
Page 5
New Construction Installation
Connect Wires and Install Knockout Plate
5
• Run 120VAC electrical wiring to the installation location.
• Use proper UL-approved connectors to secure wiring to the Knockout Plate provided in Parts Bag.
• Connect wires as shown in wiring diagram.
Attach cable clamps to
1
Knockout Plate. Knockout
Plate mounts to outside of
Housing and may be
oriented as desired.
XB50L1
n
XB80L1
3
n
XB110L1 Installation Guide
LINE
IN
LIGHT
SWITCH
FAN
SWITCH
BLK
WHT
GRD
Connect wires
2
LIGHT WITH ON/OFF SWITCH
REDBLU
BLK
WHT
GRD
BLK
LIGHT
FAN
UNITSWITCH BOX
4
Screw from
Parts Bag
WHT
RED
WHT
LINE
IN
BLK
WHT
GRD
DIMMER
SWITCH
LIGHT WITH DIMMER SWITCH
REDBLU
FAN
SWITCH
BLK
WHT
GRD
BLK
LIGHT
FAN
UNITSWITCH BOX
WHT
RED
WHT
Page 6
New Construction Installation
Insert Mask and
6
Finish Ceiling
• Install ceiling material.
• Cut out around Housing.
CAUTION
IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE:
If the blower was unplugged, power must be
disconnected (see page 2, WARNING item 2)
before inserting motor plugs into control assembly.
XB50L1
n
XB80L1
n
XB110L1 Installation Guide
Mask protects unit
during construction.
Remove before
installing Grille.
Install Grille
7
1
1
2
3
See Page 12 for Operations, Cleaning and Maintenance, and Troubleshooting.
Page 7
Retrofit Installation
XB50L1
n
XB80L1
n
XB110L1 Installation Guide
Tools needed
• Power screwdriver with a Phillips bit
• Phillips screwdriver
• Flathead screwdriver
• Pliers
• Wire insulation stripper
• Wire cutter
• Ruler
• Pencil
• Drywall saw
• Claw hammer or pry bar
• Utility knife
Materials needed
• Tape to seal duct connections
• Existing rigid duct will require the
addition of a short length of flexible duct
• Electrical wiring and supplies per
local code requirements
Remove Packaging
1
Remove
Instruction
Sheet
Parts Bag holds
Knockout Plate
and six (6)
screws
Punch out Mask from
packaging. See Step 12.
Switch Off Power
2
WARNING
Before removing existing fan, switch power off at service panel and lock the service disconnecting
means to prevent power from being switched on accidentally. When the service disconnecting means
cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
Enlarge Ceiling Opening and Remove Existing Fan
3
12" (30.5 cm)
11" (27.9 cm)
parallel with joists
Existing ductwork and
1
Examine Wiring
4
Examine the existing wiring to make sure it is not damaged. If any damage is found,
DO NOT CONTINUE INSTALLATION of this product. Contact a qualified person(s) for repair.
wiring left in place
2
Page 8
Retrofit Installation
Remove Blower Assembly
5
2
XB50L1
1
n
XB80L1
n
XB110L1 Installation Guide
Set aside
Blower
Assembly
Both sides
Remove Wiring Panel
6
1
3
Set aside
Wiring Panel
Set aside
screw
2
3
Insert
7
Mounting
Frame
4
3
1
Remove screws from
Mounting Frame
and set aside
5
2
Bend up
four tabs
Page 9
Retrofit Installation
Secure
8
Mounting
Frame
Snap-in Housing
9
Screws set
aside
in Step 7
2
XB50L1
n
XB80L1
n
XB110L1 Installation Guide
10
Pull existing
ductwork
into Housing
1
Pull existing wiring into
Housing as it is inserted
into Mounting Frame
snap!
Attach Ducting and Duct Connector
1
2
6" Ducting
Tape
4" Ducting
Tape
Tape
4
Screw from
Parts Bag
3
Insert tab into
slot inside
Housing
6" to 4" Reducer provided in select models
Page 10
Retrofit Installation
Install Knockout Plate, Connect Wires and Reinstall Wiring Panel
11
• Use proper UL-approved connectors to secure wiring to the Knockout Plate provided in Parts Bag.
• Connect wires as shown in wiring diagram.
mounts to inside of
2
Screw from
Parts Bag
1
Attach cable
clamps to
Knockout Plate.
Knockout Plate
Housing and may
be oriented
as desired.
Screw set
aside in
Step 6
5
XB50L1
4
n
XB80L1
n
XB110L1 Installation Guide
6
Connect wires
3
LINE
IN
LINE
IN
BLK
WHT
GRD
LIGHT
SWITCH
FAN
SWITCH
BLK
WHT
GRD
DIMMER
SWITCH
LIGHT WITH ON/OFF SWITCH
REDBLU
BLK
WHT
GRD
BLK
LIGHT
LIGHT WITH DIMMER SWITCH
REDBLU
FAN
SWITCH
BLK
WHT
GRD
BLK
FAN
UNITSWITCH BOX
RED
LIGHT
WHT
WHT
FAN
UNITSWITCH BOX
WHT
RED
WHT
Pa g e 11
1
23
Retrofit Installation
Reinsert and Secure Blower Assembly
12
CAUTION
Power must be disconnected (see page 2, WARNING item 2) before inserting motor plugs into control assembly.
XB50L1
IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE:
n
XB80L1
n
XB110L1 Installation Guide
13
Install Grille
1
2
23
If ceiling repairs are needed, place Mask in Housing
after Blower Assembly is secured. See New Construction
Installation Step 6. Remove Mask before installing Grille.
1
1
Screws from Parts Bag
3
Page 12
XB50L1
n
XB80L1
n
XB110L1 Installation Guide
WARNING Before servicing or cleaning unit,
switch power off at service panel and lock the service
disconnecting means to prevent power from being
switched on accidentally. When the service disconnecting
means cannot be locked, securely fasten a prominent
warning device, such as a tag, to the service panel.
Operation
To Operate Fan
Use an ON/OFF switch to operate this ventilator.
It is normal for this ventilation fan to take approximately 5
seconds to start running after it is turned on.
To Operate Lights
The fan and light can be operated independently, using
separate switches. The light may be operated with a
dimmer switch. See wiring diagrams.
Cleaning and Maintenance
CAUTION
IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE:
DO NOT remove motor plug to stop spinning motor.
Power must be disconnected (see WARNING above) before
motor plug is removed or inserted into control assembly.
Troubleshooting
Symptom: The fan does not run.
• Check for an open fuse or circuit breaker in the building’s
service panel.
• Check that the two (2) plug-in connections for the Motor
and the Control are seated firmly in place.
• Check that the Blower Wheel spins freely.
Symptom: The fan runs erratically.
• Check that the Blower Wheel is firmly attached to the
Motor shaft and both spin freely.
Symptom: The fan seems noisy.
• Check that the back draft damper in the fan’s Duct
Connector pivots freely. Screws used to attach the duct to
the Duct Connector may be preventing the damper from
opening.
• Check that the back draft damper in the wall or roof cap
pivots freely. These dampers are sometimes mistakenly
painted shut or obstructed by bird and insect debris..
To Clean
For quiet and efficient operation, long life and attractive
appearance, remove Grille and vacuum interior of unit
with a dusting brush attachment.
The Motor is permanently lubricated and never needs
oiling. If the motor bearings are making excessive or
unusual noises, replace the Control Assembly and Motor.
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.