Broan XB110H Installation Manual

READ AND SAVE THESE INSTRUCTIONS
Installer: leave this guide with homeowner.
Register your product online at www.broan.com/register.
XB110H
X1 | Single-Speed Ventilation Fan with Humidity Sensor
INSTALLATION GUIDE
© 2017 Broan
Table of Contents
Warnings and Cautions 2 Typical Installation 2 New Construction Installation 3 Retrofit Installation 7 Operation 12 Cleaning and Maintenance 12 Troubleshooting 12 Service Parts 13 Warranty 13
Page 2
XB110H Installation Guide
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed in the warranty.
2. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.
4. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. Use only ON/OFF switch, mechanical timer or relay-switched control.
8. Acceptable for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch circuit.
9. This unit must be grounded.
CAUTION
1. For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors.
2. This product is designed for installation in flat ceilings. Sensor will not function reliably if product is not installed in flat ceiling. DO NOT MOUNT THIS PRODUCT IN A WALL.
3. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
4. Please read specification label on product for further information and requirements.
NOT FOR USE IN A COOKING AREA
Do not install above or inside this area
45° 45°
Cooking Equipment
Floor
Typical Installation
• Installation is the same for:
Joists I-Joists Trusses
• Fits in 2" x 8" ceiling construction.
• Infinitely adjust the fan position between joists from 14" to 24" on center.
The ducting from this fan to the outside of the building has a strong effect on the air flow, noise and en­ergy use of the fan. Use the shortest, straighest duct routing possible for best performance, and avoid installing the fan with smaller ducts than recommended. Insulation around the ducts can reduce en­ergy loss and inhibit mold growth. Fans installed with existing ducts may not achieve their rated airflow.
6-inch round rigid metal duct is recommended for best performance.
HOUSING
POWER CABLE*
Seal gaps
around
Housing.
*Purchase separately.
INSULATION*
(Place around and
over Fan Housing.)
FAN
ROUND
DUCT*
Seal duct
joints with
tape.
OR
ROUND
ELBOWS*
ROOF CAP*
(with built-in
damper)
Keep duct
runs short.
WALL CAP*
(with built-in
damper)
Page 3
New Construction Installation
XB110H Installation Guide
Tools needed
• Power screwdriver with a Phillips bit
• Phillips screwdriver
• Flathead screwdriver
• Pliers
• Wire insulation stripper
• Wire cutter
Remove Packaging
1
Parts Bag holds Knockout Plate and six (6) screws
Materials needed
• 6" round metal ducting recommended for best performance. Use of other ducting is acceptable but may impact performance.
• Roof cap or wall cap (built-in damper recommended)
• Tape to seal duct connections
• Electrical wiring and supplies per local code requirements
Punch out Mask from
packaging. See Step 6.
Remove Instruction Sheet
Install
2
Mounting Frame
2
1
4
3
Page 4
New Construction Installation
Snap-in and
3
Secure Housing
2
snap!
XB110H Installation Guide
1
4
Attach Duct Connector and Ducting
4
Top and bottom flanges go outside Housing
Insert tab into slot inside Housing
1
Screws from Parts Bag
3
Position Housing between joists and crimp channel on both sides of Mounting Frame to lock Housing in place.
Do not crimp Housing.
Screw from
2
Parts Bag
6" Ducting
3
Tape
Page 5
New Construction Installation
Connect Wires and Install Knockout Plate
5
• Run 120VAC electrical wiring to the installation location.
• Use proper UL-approved connectors to secure wiring to the Knockout Plate provided in Parts Bag.
• Connect wires as shown in wiring diagram.
Attach cable clamp to Knockout
1
Plate. Knockout Plate mounts to
outside of Housing and may be
oriented as desired.
Connect wires
2
XB110H Installation Guide
3
4
Screw from
Parts Bag
BLK
120 VAC
LINE IN
WHT GRD
BLACK WHITE
SENSOR
CONTROL
SWITCH*
purchase separately
*
STANDARD OR MULTI-
FUNCTION WALL SWITCHES
SENSOR/ CONTROL
MANUAL
ON
SWITCH*
MANUAL-ON
RED BROWN
SWITCH BOX
120 VAC
LINE IN
14/3
(IF ALL
WALL SWITCH
OPTIONS
ARE USED)
RED BLK WHT GRD
ORANGE GROUND
(green or bare)
KNOCKOUT
PLATE
BLK
ORG
BRN
RECEPTACLES
RED
FAN
BLK
SENSOR/ CONTROL
WHT
• See OPERATION section on page 12 for details.
• SENSOR/CONTROL switch turns humidity control on for automatic operation and off for fan cleaning and maintenance purposes.
• MANUAL-ON switch directly turns fan on/off.
• MANUAL-ON switch is not required to manually turn fan on (see page 10).
• SENSOR/CONTROL switch may be located where it is not easily accessed for everyday usage; it may need to be labeled and located where it can’t be turned on without being seen from fan to comply with local and national codes.
Page 6
New Construction Installation
Insert Mask and
6
Finish Ceiling
• Install ceiling material.
• Cut out around Housing.
CAUTION
IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE:
If the blower was unplugged, power must be disconnected (see page 2, WARNING item 2) before inserting motor plugs into control assembly.
XB110H Installation Guide
Mask protects unit
during construction.
Remove before installing Grille.
Install Grille
7
Plug in Sensor
See Page 12 for Operations, Cleaning and Maintenance, and Troubleshooting.
1
2
3
Page 7
Retrofit Installation
XB110H Installation Guide
Tools needed
• Power screwdriver with a Phillips bit
• Phillips screwdriver
• Flathead screwdriver
• Pliers
• Wire insulation stripper
• Wire cutter
• Ruler
• Pencil
• Drywall saw
• Claw hammer or pry bar
• Utility knife
Materials needed
• Tape to seal duct connections
• Existing rigid duct will require the addition of a short length of flexible duct
• Electrical wiring and supplies per local code requirements
Remove Packaging
1
Parts Bag holds Knockout Plate and six (6) screws
Remove Instruction Sheet
Punch out Mask from
packaging. See Step 12.
Switch Off Power
2
WARNING
Before removing existing fan, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
Enlarge Ceiling Opening and Remove Existing Fan
3
12" (30.5 cm)
1
11" (27.9 cm) parallel with joists
Existing ductwork and wiring left in place
Examine Wiring
4
Examine the existing wiring to make sure it is not damaged. If any damage is found, DO NOT CONTINUE INSTALLATION of this product. Contact a qualified person(s) for repair.
2
Page 8
Retrofit Installation
Remove Blower Assembly
5
XB110H Installation Guide
2
Both sides
Remove Wiring Panel
6
Set aside screw
1
1
3
Set aside Wiring Panel
2
3
Set aside Blower Assembly
Insert
7
Mounting Frame
4
3
1
Remove screws from Mounting Frame and set aside
5
2
Bend up four tabs
Page 9
Retrofit Installation
Secure
8
Mounting Frame
Snap-in Housing
9
XB110H Installation Guide
Screws set
aside
in Step 7
2
10
Pull existing ductwork into Housing
1
Pull existing wiring into Housing as it is inserted into Mounting Frame
snap!
Attach Ducting and Duct Connector
1
4
Screw from
Parts Bag
3
Insert tab into slot inside Housing
6" Ducting
2
Tape
Page 10
Retrofit Installation
Install Knockout Plate, Connect Wires and Reinstall Wiring Panel
11
Screw from
Parts Bag
• Use proper UL-approved connectors to secure wiring to the Knockout Plate provided in Parts Bag.
• Connect wires as shown in wiring diagram.
Attach cable clamp to Knockout
1
Plate. Knockout Plate mounts to
inside of Housing and may be
oriented as
2
XB110H Installation Guide
desired.
Screw set
aside in
Step 6
5
6
4
Connect
3
wires
• See OPERATION section on page 12 for details.
• SENSOR/CONTROL switch allows humidity control to be turned on for automatic operation and off for fan cleaning and maintenance purposes.
• Toggle mode can be used to manually turn fan on.
• SENSOR/CONTROL switch may be located where it is not easily accessed for everyday usage; it may need to be labeled and located where it can’t be turned on without being seen from fan to comply with local and national codes.
120 VAC
LINE IN
SENSOR/ CONTROL
BLK WHT GRD
BLACK WHITE
SENSOR
CONTROL*
purchase separately
*
BLK WHT GRD
BROWN
SWITCH BOX
120 VAC
LINE IN
14/2
ORANGERED GROUND
(green or bare)
BLK
ORG
BRN
KNOCKOUT
PLATE
RED
FAN
BLK
SENSOR/ CONTROL
WHT
RECEPTACLES
Pa g e 11
Retrofit Installation
Reinsert and Secure Blower Assembly
12
CAUTION
Power must be disconnected (see page 2, WARNING item 2) before inserting motor plugs into control assembly.
XB110H Installation Guide
IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE:
13
Plug in Sensor
Install Grille
1
1
2
2 3
Screws from Parts Bag
If ceiling repairs are needed, place Mask in
Housing after Blower Assembly is secured.
See New Construction Installation Step 6.
Remove Mask before installing Grille.
3
Page 12
XB110H Installation Guide
WARNING Before servicing or cleaning unit,
switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent
warning device, such as a tag, to the service panel.
Operation
It is normal for this ventilation fan to take approximately 5 seconds to start running after it is turned on.
Modes
(For reference, wiring diagrams are on pages 5 and 10.)
Humidity sensing:
1. Turn sensor/control wall switch on (make sure manual-
on wall switch is off if it is installed).
2. Sensor monitors humidity level for (a) moderate to rapid
rise or (b) above set-point.
3. Fan operates at certified airflow rate to reduce humidity.
4. When humidity decreases, fan enters time delay mode.
(See below.)
Manual-on (optional manual-on wall switch must be
installed):
1. Turn manual-on wall switch on (sensor/control wall
switch can be on or off).
2. Fan operates at certified airflow rate.
3. Fan turns off when manual-on wall switch is turned off.
Toggle (for manual operation when optional manual-on
wall switch is not installed or manually activated timed­off is desired):
1. Turn sensor/control wall switch on (make sure manual-
on wall switch is off if it is installed).
2. Wait at least one-second.
3. Turn switch off for less than one-second.
4. Turn switch back on.
5. Fan will operate at certified airflow rate and enter time
delay mode. (See next.)
Time Delay:
Fan continues to run until user-adjustable TIME delay has passed, then fan turns off.
To Set User-Adjustable Humidity Sensitivity**
Using a small, flat-blade screwdriver, carefully rotate HU­MIDITY adjustment until arrow points to desired humidity level shown in percent relative humidity (%RH).
To Set User-Adjustable Time Delay**
Using a small, flat-blade screwdriver, carefully rotate TIME adjustment until the arrow points to the desired minutes of time delay. ** User-adjustable controls are located in corner of Fan
Housing behind Grille.
Cleaning and Maintenance
CAUTION
IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE:
DO NOT remove motor plug to stop spinning motor. Power must be disconnected (see WARNING at top left of
this page) before motor plug is removed or inserted into control assembly.
To Clean
For quiet and efficient operation, long life and attractive appearance, remove Grille and vacuum interior of unit with a dusting brush attachment.
Do not use cleaning sprays, solvents or water on, or near, the sensor.
Motor is permanently lubricated and never needs oiling. If motor is making excessive or unusual noises, replace Control Assembly and Motor.
Troubleshooting
Before continuing, turn off power as previously noted in WARNING and CAUTION sections at the top of this page.
Symptom: Fan does not run.
• Check for an open fuse or circuit breaker in the build­ing’s service panel.
• Check that the two (2) plug-in connections for the Mo­tor and the Control are seated firmly in place.
• Check two (2) plug-in connections for Sensor and its Control are seated firmly in place.
• Check that the Blower Wheel spins freely.
Symptom: Humidity mode does not operate fan.
• Check two (2) plug-in connections for Sensor and its Control are seated firmly in place.
Symptom: The fan runs erratically.
• Check that the Blower Wheel is firmly attached to the Motor shaft and both spin freely.
Symptom: The fan seems noisy.
• Check that the back draft damper in the fan’s Duct Connector pivots freely. Screws used to attach the duct to the Duct Connector may be preventing the damper from opening.
• Check that the back draft damper in the wall or roof cap pivots freely. These dampers are sometimes mistakenly painted shut or obstructed by bird and insect debris.
Loading...
+ 28 hidden pages