Warnings and Cautions 2
Typical Installation 2
New Construction Installation 3
Retrofit Installation 7
Operation 12
Cleaning and Maintenance 12
Troubleshooting 12
Service Parts 13
Warranty 13
Page 2
XB110H Installation Guide
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR
INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer.
If you have questions, contact the manufacturer at the address
or telephone number listed in the warranty.
2. Before servicing or cleaning unit, switch power off at service
panel and lock the service disconnecting means to prevent
power from being switched on accidentally. When the service
disconnecting means cannot be locked, securely fasten a
prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by a
qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction codes and
standards.
4. Sufficient air is needed for proper combustion and exhausting
of gases through the flue (chimney) of fuel burning equipment
to prevent backdrafting. Follow the heating equipment
manufacturer’s guideline and safety standards such as those
published by the National Fire Protection Association (NFPA),
and the American Society for Heating, Refrigeration and
Air Conditioning Engineers (ASHRAE), and the local code
authorities.
5. When cutting or drilling into wall or ceiling, do not damage
electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. Use only ON/OFF switch, mechanical timer or relay-switched
control.
8. Acceptable for use over a tub or shower when connected to
a GFCI (Ground Fault Circuit Interrupter) - protected branch
circuit.
9. This unit must be grounded.
CAUTION
1. For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors.
2. This product is designed for installation in flat ceilings. Sensor
will not function reliably if product is not installed in flat ceiling.
DO NOT MOUNT THIS PRODUCT IN A WALL.
3. To avoid motor bearing damage and noisy and/or unbalanced
impellers, keep drywall spray, construction dust, etc. off power
unit.
4. Please read specification label on product for further
information and requirements.
NOT FOR USE IN A COOKING AREA
Do not install above or inside this area
45°45°
Cooking
Equipment
Floor
Typical Installation
• Installation is the same for:
Joists I-Joists Trusses
• Fits in 2" x 8" ceiling construction.
• Infinitely adjust the fan position
between joists from 14" to 24"
on center.
The ducting from this fan to the outside of the building has a strong effect on the air flow, noise and energy use of the fan. Use the shortest, straighest duct routing possible for best performance, and avoid
installing the fan with smaller ducts than recommended. Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed with existing ducts may not achieve their rated airflow.
6-inch round rigid metal duct is recommended for best performance.
HOUSING
POWER
CABLE*
Seal gaps
around
Housing.
*Purchase
separately.
INSULATION*
(Place around and
over Fan Housing.)
FAN
ROUND
DUCT*
Seal duct
joints with
tape.
OR
ROUND
ELBOWS*
ROOF CAP*
(with built-in
damper)
Keep duct
runs short.
WALL CAP*
(with built-in
damper)
Page 3
New Construction Installation
XB110H Installation Guide
Tools needed
• Power screwdriver with a Phillips bit
• Phillips screwdriver
• Flathead screwdriver
• Pliers
• Wire insulation stripper
• Wire cutter
Remove Packaging
1
Parts Bag holds
Knockout Plate
and six (6)
screws
Materials needed
• 6" round metal ducting recommended for best performance.
Use of other ducting is acceptable but may impact performance.
• Roof cap or wall cap (built-in damper recommended)
• Tape to seal duct connections
• Electrical wiring and supplies per local code requirements
Punch out Mask from
packaging. See Step 6.
Remove
Instruction
Sheet
Install
2
Mounting
Frame
2
1
4
3
Page 4
New Construction Installation
Snap-in and
3
Secure Housing
2
snap!
XB110H Installation Guide
1
4
Attach Duct Connector and Ducting
4
Top and bottom flanges
go outside Housing
Insert tab into slot
inside Housing
1
Screws from Parts Bag
3
Position Housing
between joists and
crimp channel on both
sides of Mounting Frame
to lock Housing in place.
Do not crimp Housing.
Screw from
2
Parts Bag
6" Ducting
3
Tape
Page 5
New Construction Installation
Connect Wires and Install Knockout Plate
5
• Run 120VAC electrical wiring to the installation location.
• Use proper UL-approved connectors to secure wiring to the Knockout Plate provided in Parts Bag.
• Connect wires as shown in wiring diagram.
Attach cable clamp to Knockout
1
Plate. Knockout Plate mounts to
outside of Housing and may be
oriented as desired.
Connect wires
2
XB110H Installation Guide
3
4
Screw from
Parts Bag
BLK
120 VAC
LINE IN
WHT
GRD
BLACK
WHITE
SENSOR
CONTROL
SWITCH*
purchase separately
*
STANDARD OR MULTI-
FUNCTION WALL SWITCHES
SENSOR/
CONTROL
MANUAL
ON
SWITCH*
MANUAL-ON
RED
BROWN
SWITCH BOX
120 VAC
LINE IN
14/3
(IF ALL
WALL SWITCH
OPTIONS
ARE USED)
RED
BLK
WHT
GRD
ORANGE
GROUND
(green or bare)
KNOCKOUT
PLATE
BLK
ORG
BRN
RECEPTACLES
RED
FAN
BLK
SENSOR/
CONTROL
WHT
• See OPERATION section on page 12
for details.
• SENSOR/CONTROL switch turns
humidity control on for automatic
operation and off for fan cleaning and
maintenance purposes.
• MANUAL-ON switch directly turns fan
on/off.
• MANUAL-ON switch is not required to
manually turn fan on (see page 10).
• SENSOR/CONTROL switch may be
located where it is not easily accessed
for everyday usage; it may need to
be labeled and located where it can’t
be turned on without being seen from
fan to comply with local and national
codes.
Page 6
New Construction Installation
Insert Mask and
6
Finish Ceiling
• Install ceiling material.
• Cut out around Housing.
CAUTION
IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE:
If the blower was unplugged, power must be
disconnected (see page 2, WARNING item 2)
before inserting motor plugs into control assembly.
XB110H Installation Guide
Mask protects unit
during construction.
Remove before
installing Grille.
Install Grille
7
Plug in
Sensor
See Page 12 for Operations, Cleaning and Maintenance, and Troubleshooting.
1
2
3
Page 7
Retrofit Installation
XB110H Installation Guide
Tools needed
• Power screwdriver with a Phillips bit
• Phillips screwdriver
• Flathead screwdriver
• Pliers
• Wire insulation stripper
• Wire cutter
• Ruler
• Pencil
• Drywall saw
• Claw hammer or pry bar
• Utility knife
Materials needed
• Tape to seal duct connections
• Existing rigid duct will require the
addition of a short length of flexible duct
• Electrical wiring and supplies per
local code requirements
Remove Packaging
1
Parts Bag holds
Knockout Plate
and six (6)
screws
Remove
Instruction
Sheet
Punch out Mask from
packaging. See Step 12.
Switch Off Power
2
WARNING
Before removing existing fan, switch power off at service panel and lock the service disconnecting
means to prevent power from being switched on accidentally. When the service disconnecting means
cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
Enlarge Ceiling Opening and Remove Existing Fan
3
12" (30.5 cm)
1
11" (27.9 cm)
parallel with joists
Existing ductwork and
wiring left in place
Examine Wiring
4
Examine the existing wiring to make sure it is not damaged. If any damage is found,
DO NOT CONTINUE INSTALLATION of this product. Contact a qualified person(s) for repair.
2
Page 8
Retrofit Installation
Remove Blower Assembly
5
XB110H Installation Guide
2
Both sides
Remove Wiring Panel
6
Set aside
screw
1
1
3
Set aside
Wiring Panel
2
3
Set aside
Blower
Assembly
Insert
7
Mounting
Frame
4
3
1
Remove screws from
Mounting Frame
and set aside
5
2
Bend up
four tabs
Page 9
Retrofit Installation
Secure
8
Mounting
Frame
Snap-in Housing
9
XB110H Installation Guide
Screws set
aside
in Step 7
2
10
Pull existing
ductwork
into Housing
1
Pull existing wiring into
Housing as it is inserted
into Mounting Frame
snap!
Attach Ducting and Duct Connector
1
4
Screw from
Parts Bag
3
Insert tab into
slot inside
Housing
6" Ducting
2
Tape
Page 10
Retrofit Installation
Install Knockout Plate, Connect Wires and Reinstall Wiring Panel
11
Screw from
Parts Bag
• Use proper UL-approved connectors to secure wiring to the Knockout Plate provided in Parts Bag.
• Connect wires as shown in wiring diagram.
Attach cable clamp to Knockout
1
Plate. Knockout Plate mounts to
inside of Housing and may be
oriented as
2
XB110H Installation Guide
desired.
Screw set
aside in
Step 6
5
6
4
Connect
3
wires
• See OPERATION section on page
12 for details.
• SENSOR/CONTROL switch allows
humidity control to be turned on for
automatic operation and off for fan
cleaning and maintenance purposes.
• Toggle mode can be used to manually
turn fan on.
• SENSOR/CONTROL switch may be
located where it is not easily accessed
for everyday usage; it may need to be
labeled and located where it can’t be
turned on without being seen from
fan to comply with local and national
codes.
120 VAC
LINE IN
SENSOR/
CONTROL
BLK
WHT
GRD
BLACK
WHITE
SENSOR
CONTROL*
purchase separately
*
BLK
WHT
GRD
BROWN
SWITCH BOX
120 VAC
LINE IN
14/2
ORANGERED
GROUND
(green or bare)
BLK
ORG
BRN
KNOCKOUT
PLATE
RED
FAN
BLK
SENSOR/
CONTROL
WHT
RECEPTACLES
Pa g e 11
Retrofit Installation
Reinsert and Secure Blower Assembly
12
CAUTION
Power must be disconnected (see page 2, WARNING item 2) before inserting motor plugs into control assembly.
XB110H Installation Guide
IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE:
13
Plug in
Sensor
Install Grille
1
1
2
23
Screws from Parts Bag
If ceiling repairs are needed, place Mask in
Housing after Blower Assembly is secured.
See New Construction Installation Step 6.
Remove Mask before installing Grille.
3
Page 12
XB110H Installation Guide
WARNING Before servicing or cleaning unit,
switch power off at service panel and lock the service
disconnecting means to prevent power from being
switched on accidentally. When the service disconnecting
means cannot be locked, securely fasten a prominent
warning device, such as a tag, to the service panel.
Operation
It is normal for this ventilation fan to take approximately 5
seconds to start running after it is turned on.
Modes
(For reference, wiring diagrams are on pages 5 and 10.)
Humidity sensing:
1. Turn sensor/control wall switch on (make sure manual-
on wall switch is off if it is installed).
2. Sensor monitors humidity level for (a) moderate to rapid
rise or (b) above set-point.
3. Fan operates at certified airflow rate to reduce humidity.
4. When humidity decreases, fan enters time delay mode.
(See below.)
Manual-on (optional manual-on wall switch must be
installed):
1. Turn manual-on wall switch on (sensor/control wall
switch can be on or off).
2. Fan operates at certified airflow rate.
3. Fan turns off when manual-on wall switch is turned off.
Toggle (for manual operation when optional manual-on
wall switch is not installed or manually activated timedoff is desired):
1. Turn sensor/control wall switch on (make sure manual-
on wall switch is off if it is installed).
2. Wait at least one-second.
3. Turn switch off for less than one-second.
4. Turn switch back on.
5. Fan will operate at certified airflow rate and enter time
delay mode. (See next.)
Time Delay:
Fan continues to run until user-adjustable TIME delay has
passed, then fan turns off.
To Set User-Adjustable Humidity Sensitivity**
Using a small, flat-blade screwdriver, carefully rotate HUMIDITY adjustment until arrow points to desired humidity
level shown in percent relative humidity (%RH).
To Set User-Adjustable Time Delay**
Using a small, flat-blade screwdriver, carefully rotate TIME
adjustment until the arrow points to the desired minutes of
time delay.
** User-adjustable controls are located in corner of Fan
Housing behind Grille.
Cleaning and Maintenance
CAUTION
IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE:
DO NOT remove motor plug to stop spinning motor.
Power must be disconnected (see WARNING at top left of
this page) before motor plug is removed or inserted into
control assembly.
To Clean
For quiet and efficient operation, long life and attractive
appearance, remove Grille and vacuum interior of unit with a
dusting brush attachment.
Do not use cleaning sprays, solvents or water on, or near, the
sensor.
Motor is permanently lubricated and never needs oiling. If
motor is making excessive or unusual noises, replace Control
Assembly and Motor.
Troubleshooting
Before continuing, turn off power as previously noted in
WARNING and CAUTION sections at the top of this page.
Symptom: Fan does not run.
• Check for an open fuse or circuit breaker in the building’s service panel.
• Check that the two (2) plug-in connections for the Motor and the Control are seated firmly in place.
• Check two (2) plug-in connections for Sensor and its
Control are seated firmly in place.
• Check that the Blower Wheel spins freely.
Symptom: Humidity mode does not operate fan.
• Check two (2) plug-in connections for Sensor and its
Control are seated firmly in place.
Symptom: The fan runs erratically.
• Check that the Blower Wheel is firmly attached to the
Motor shaft and both spin freely.
Symptom: The fan seems noisy.
• Check that the back draft damper in the fan’s Duct
Connector pivots freely. Screws used to attach the duct
to the Duct Connector may be preventing the damper
from opening.
• Check that the back draft damper in the wall or roof cap
pivots freely. These dampers are sometimes mistakenly
painted shut or obstructed by bird and insect debris.
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.