r e l aY
cat.
rm4
Smart Interconnect
Works with all First Alert and BRK
“Smart Interconnect” CO Alarms.
meetS ul StandardS
UL217, UL2034 and UL539
for accessories.
meetS ulc StandardS
ULC S-531, CSA6.19 and
ULC S-530 for accessories.
120V AC/DC, 60Hz Wire-in
Description:
Designed to activate an auxilliary device when an alarm is initiated. The RM4 Relay is
intended for use with BRK and First Alert Smoke, Heat and Carbon Monoxide Alarms.
The relay contacts will activate whenever any interconnected alarm sounds. The relay
contacts will automatically deactivate a few seconds after the alarm stops sounding.
The RM4 may be wired next to an AC alarm or from a remote location. This relay must
be installed in a junction box.
Interconnects smoke alarms, carbon monoxide alarms and
heat alarms with:
• Lights
• Bells
• Door Closers
• Sirens
• Exit Signals
• Escape Lights
• Exhaust Fans
• Other Auxiliary Devices
Fits in most standard electrical boxes.
cat.
Alarm
AC
Power
BRK
Relay
Module
BRK
Alarm
Auxiliary
Device
Auxiliary Device
AC Power
BLUE
(N.O.)
ORANGE
(N.C.)
WHITE
NEUTRAL
WHITE
ORANGE
BLACK
INTERCONNECT
UNSWITCHED 120V AC
60 Hz SOURCE
{
TO ADDITIONAL ALARMS
{
HOT
GRAY BLACK
BROWN
(COM.)
rm4
120V AC/DC, 60Hz Wire-in
This accessory relay is designed to activate auxiliary devices such as bells, lights
and door closers. The RM4 Relay is intended for use with BRK Electronics® and
First Alert® Smoke, Heat, and Carbon Monoxide Alarms.
I NST AL LATI O N OF AL A R M
To install this relay to an alarm, connect the power wires as listed below.
(If wiring the relay remote from the alarm, use a maximum of 1000 feet
[300 meters] of #18AWG or larger wire rated at least 300V.)
ALARM RELAY
BLACK WIRE (HOT) BLACK WIRE
WHITE WIRE (NEUTRAL) WHITE WIRE
ORANGE WIRE (INTERCONNECT) ORANGE WIRE
Now connect the accessory to be activated by the relay to the relay’s switch
contact wires as listed below. (Use wiring appropriate to the auxiliary device
being controlled.) NOTE: Since voltage is present on all relay contact wires at
some time during operation, the installer must properly insulate any unused
relay contact wire.
BROWN WIRE: HOT CONTACT TO AUXILIARY DEVICE
GRAY WIRE: NORMALLY CLOSED CONTACT
BLUE WIRE: NORMALLY OPEN CONTACT
T E C H N I C A L S P E C S :
Relay Dimensions 3.5” x 1.5”
Weight: 2.4 oz.
Operating Voltage: 120V AC 60 Hz
Operating Current: .02 amps
Temperature Range: 40˚F (4˚C) to 100˚F (38˚C)
Humidity Range: 10% to 90% relative humidity (RH)
Interconnections Up to 18 units of First Alert or BRK Smoke, CO and
Listing Meets UL217, UL2034, UL539,ULC S-531,
Heat Alarms (see users manual).
CSA6.19 and ULCS-530 for accessories.
S HIP P I NG S P EC S :
Individual Carton Dimensions: 5.13”L x 2.38”W x 5.13”H
Weight: 3 lbs.
Cube: .20ft
UPC: 0 29054 00057 6
Master Carton Dimensions: 10.13”L x 4.63”W x 6.06”H
Master Pack: 12
Weight: 3 lbs.
Cube: .20ft3
I2of5: 100 29054 00057 3
Pallet Information:
Cases per Layer: 35
Number of Layers: 6
Cases per Pallet: 210
Cube: 54.69 ft
Weight: 695 lbs.
3
3
CONTACT RATINGS (MAXIMUM):
VOLTAGE RESISTIVE MOTOR
120V AC 15 AMP 1/3 H.P.
30V DC 15 AMP
After installation, test the interaction of the auxiliary device with the alarm
by pressing the alarm test button.
brkelectronics.com
©2008 BRK Brands, Inc.
a Jarden Corporation company (NYSE:JAH)
3901 Liberty Street Rd., Aurora IL 60504-8122
All rights reserved.
BRK® is a registered trademark of BRK Brands, Inc.
CM2866