EKLY TESTING
DINING ROOM
KITCHEN
BEDROOM
BEDROOM
BEDROOM
LIVING ROOM
WE
NEVER use an open flame of any kind to test this unit. You might
•
ccidentally damage or set fire to the unit or to your home. The
a
built-in test switch accurately tests the unit’s operation as required
y Underwriters Laboratories, Inc. (UL). NEVER use vehicle exhaust!
b
t may cause permanent damage and voids your warranty.
Exhaus
• DO NOT stand close to the Alarm when the horn is sounding.
posure at close range may be harmful to your hearing. When
Ex
ting, step away when horn starts sounding.
tes
t is important to test this unit every week to make sure it is working
I
properly.
1. Manually: Press the Test/Silence button on the Alarm
2. Remote Control: Aim your remote control at the Alarm
D
1 beep every second, while the Red LED flashes and the
d
horn p
LED flashes and the display shows “CO” with an increasing
C
If the Alarm does not test properly:
1. Make sure the AC power is applied and battery is fresh and installed
2. Test the unit again.
I
“Limited Warranty” at the end of this manual.
If there is still a problem, do not try to fix the Alarm yourself.This will
void your warranty!
You can test this Gas/CO Alarm two ways:
ver until alarm sounds.
co
nd press the CHANNEL or VOLUME button.
a
uring testing, you will hear a loud, repeating horn pattern:
isplay shows “GAS”. Then you will hear a loud, repeating
attern: 4 beeps, pause, 4 beeps, pause, while the Red
O ppm number.
ectly.
corr
f the Alarm is still not working properly, replace it immediately. Refer to the
REGULAR MAINTENANCE
se only the replacement batteries listed below. The unit may not operate
U
properly with other batteries. Never use rechargeable batteries since they
may not provide a constant charge.
his unit has been designed to be as maintenance-free as possible, but there
T
are a few simple things you must do to keep it working properly:
Test it at least once a week.
•
• Clean the Alarm at least once a month; gently vacuum the outside of the
• Relocate the unit if it sounds frequent unwanted alarms. See “Where This
• When the battery back-up becomes weak, the Alarm will “chirp” about
O N
D
arm. DO NOT paint over the Alarm. Doing so may permanently damage the
Al
arm.
Al
OOSING A REPLACEMENT BATTERY:
H
C
our Alarm requires one standard 9V alkaline battery. The following batteries
Y
e acce
ar
veready (Energizer) #522. You may also use a Lithium battery like the Ultralife
E
U9VL-J f
ai
v
a
Actual battery service life depends on the Alarm and the environment in which
it is i
atteries for this unit. Regardless of the manufacturer’s suggested battery life,
b
ou MUST replace the battery immediately once the unit starts “chirping” (the
y
low battery warning”).
“
WH
WH
O is an invisible, odorless, tasteless gas produced when fossil fuels do not
C
burn completely, or are exposed to heat (usually fire). Electrical appliances
ica
p
ty
hes
T
nd propane.
a
Common appliances are often sources of CO. If they are not properly main-
ained, are improperly ventilated, or malfunction, CO levels can rise quickly. CO
t
is a r
h ad
it
w
O inside.
C
YMPT
S
he
T
ALL household members.
Mild Exposure: Slight headache, nausea, vomiting, fatigue (“flu-like” symptoms).
edium Exposure:Throbbing headache, drowsiness, confusion, fast heart rate.
M
Extreme Exposure: Convulsions, unconsciousness, heart and lung failure.
xposure to Carbon Monoxide can cause brain damage, death.
E
Some i
ith cardiac or respiratory problems, infants, unborn babies, pregnant
w
others, or elderly people can be more quickly and severely affected by
m
.
O
C
adv
N
I
F
arbon monoxide is an odorless, invisible gas, which often makes it difficult to
C
ocate the source of CO after an alarm.These are a few of the factors that can
l
k
ma
ca
Be
to locate the source of CO.
or any carbon monoxide investigation or service call.
f
PO
uel-burni
F
ike:
l
wood burning fireplace, gas
kitchen range or cooktop,
gas cl
Damaged or insufficient
venting:
nected water heater vent
pipe, leaking chimney pipe
or flue, or cracked heat
changer, blocked or
x
e
clogged chimney opening.
Improper use of appliance/
device:
l or v
l
i
gr
area (like a garage or
screened porch).
Transient CO Problems: “transient” or on-again-off-again CO problems can
be caused by outdoor conditions and other special circumstances.
he f
T
.
1
2. Extended operation of unvented fuel burning devices (range, oven, fireplace).
3. Temperature inversions, which can trap exhaust close to the ground.
4. Car idling in an open or closed attached garage, or near a home.
These conditions are dangerous because they can trap exhaust in your home.
Since these conditions can come and go, they are also hard to recreate during
O investigation.
a C
ng your household vacuum’s soft brush attachment.Test the
Alarm usi
Alarm. Never use water, cleaners or solvents since they may damage the
unit.
Alarm Should Not Be Installed” for details.
once a minute (the low battery warning). You should replace the battery
mmediately to continue your protection.
i
attery power to operate. If AC power fails, and the battery is dead
b
issing, the Alarm cannot operate.
or m
OT spray cleaning chemicals or insect sprays directly on or near the
ptable as replacements: Duracell #MN1604, (Ultra) #MX1604;
onger service life between battery changes.
or l
able at many local retail stores.
l
alled.All the batteries specified above are acceptable replacement
t
ns
his Alarm must have AC or
T
T
e batteries are
hes
AT YOU NEED TO KNOW ABOUT CO
AT IS CO?
t produce CO.
o no
y d
l
l
e f
eal danger now that homes are more energy efficient. “Air-tight” homes
se s
ember
M
ice on taking additional precautions.
I
D
e it d
• H
• Problem caused by “backdrafting.”
• Transient CO problem caused by special circumstances.
use C
E
T
por
othes dryer.
ol
ce
x
E
conditions such as:
• Wind direction and/or velocity, including high, gusty winds. Heavy air in
he v
t
• Negative pressure differential resulting from the use of exhaust fans.
• Several appliances running at the same time competing for limited fresh
air.
Vent pipe connections vibrating loose from clothes dryers, furnaces, or
•
w
• Obstructions in or unconventional vent pipe designs which can amplify
the above situations.
ude:
cl
n
uels i
ed insulation, sealed windows, and other weatherproofing can “trap”
d
W
, charcoal, oil, natural gas, gasoline, kerosene,
l
a
co
,
ood
OMS OF CO POISONING
ptoms are related to CO POISONING and should be discussed with
m
y
iduals are more sensitive to CO than others, including people
v
ndi
itive populations should consult their doctors for
ens
f s
s o
NG THE SOURCE OF CO AFTER AN ALARM
te sources of CO:
oca
o l
lt t
ficu
if
ouse well ventilated before the investigator arrives.
O may dissipate by the time an investigator arrives, it may be difficult
IAL SOURCES OF CO IN THE HOME
T
N
g appl
n
table heater, gas or
corroded or discon-
operating a barbecue
icle in an enclosed
h
e
ng conditions can result in transient CO situations:
i
w
o
l
e spillage or reverse venting of fuel appliances caused by outdoor
v
ssi
ipes (cold/humid air with extended periods between cycles).
t p
n
e
er heaters.
t
a
BRK Brands, Inc. shall not be obligated to pay
iances
5 6 7
EGULATORY INFORMATION FOR CO ALARMS, Continued
HOW CAN I PROTECT MY FAMILY FROM CO
POISONING?
A Gas/CO Alarm is an excellent means of protection. It monitors the air and
nds a loud alarm before Carbon Monoxide levels become threatening for
sou
verage, healthy adults.
a
A Gas/CO Alarm is not a substitute for proper maintenance of home
iances.
appl
o help prevent CO problems and reduce the risk of CO poisoning:
T
• Clean chimneys and flues yearly. Keep them free of debris, leaves, and
sts for proper air flow. Also, have a professional check for rust and
ne
corrosion, cracks, or separations. These conditions can prevent proper
air movement and cause backdrafting. Never “cap” or cover a chimney
n any way that would block air flow.
i
• Test and maintain all fuel-burning equipment annually. Many local gas or
il companies and HVAC companies offer appliance inspections for a
o
inal fee.
nom
• Make regular visual inspections of all fuel-burning appliances. Check
ppliances for excessive rust and scaling. Also check the flame on the
a
urner and pilot lights. The flame should be blue.A yellow flame means
b
fuel is not being burned completely and CO may be present. Keep the
lower door on the furnace closed. Use vents or fans when they are
b
vailable on all fuel-burning appliances. Make sure appliances are
a
vented to the outside. Do not grill or barbecue indoors, or in garages
een porches.
or on scr
Check for exhaust backflow from CO sources. Check the draft hood on
•
an operating furnace for a backdraft. Look for cracks on furnace heat
xchangers.
e
• Check the house or garage on the other side of shared wall.
• Keep windows and doors open slightly. If you suspect that CO is
scaping into your home, open a window or a door. Opening windows
e
and doors can significantly decrease CO levels.
n addition, familiarize yourself with all enclosed materials. Read this
I
l in its entirety, and make sure you understand what to do if your
manua
Gas/CO Alarm sounds.
REGULATORY INFORMATION FOR EXPLOSIVE
GAS/CO ALARMS
RE
GULATORY INFORMATION FOR CO ALARMS
U
NDERWRITERS LABORATORIES INC. UL2034
WHAT LEVELS OF CO CAUSE AN ALARM?
nderwriters Laboratories Inc. Standard UL2034 requires residential CO
U
Alarms to sound when exposed to levels of CO and exposure times as
escribed below. They are measured in parts per million (ppm) of CO over
d
ime (in minutes).
t
UL2034 Required Alarm Points*:
If the alarm is exposed to 400 ppm of CO, IT MUST ALARM BETWEEN
•
4 and 15 MINUTES.
If the alarm is exposed to 150 ppm of CO, IT MUST ALARM BETWEEN
•
0 and 50 MINUTES.
1
• If the alarm is exposed to 70 ppm if CO, IT MUST ALARM BETWEEN
60 and 240 MINUTES.
proximately 10% COHb exposure at levels of 10% to 95% Relative
* Ap
umidity (RH).
H
he unit is designed not to alarm when exposed to a constant level of 30 ppm
T
for 30 days.
Alarms are designed to alarm before there is an immediate life threat.
O
C
Since you cannot see or smell CO, never assume it’s not present.
• An exposure to 100 ppm of CO for 20 minutes may not affect average,
lthy adults, but after 4 hours the same level may cause headaches.
hea
An exposure to 400 ppm of CO may cause headaches in average, healthy
•
adults after 35 minutes, but can cause death after 2 hours.
his CO Alarm measures exposure to CO over time. It alarms if CO levels
T
e extremely high in a short period of time, or if CO levels reach a certain
ar
nimum over a long period of time.The CO Alarm generally sounds an alarm
i
m
fore the onset of symptoms in average, healthy adults.
be
hy is this important? Because you need to be warned of a potential CO
W
oblem while you can still react in time. In many reported cases of CO
pr
xposure, victims may be aware that they are not feeling well, but become
e
d and can no longer react well enough to exit the building or get help.
e
t
n
ie
isor
d
, young children and pets may be the first affected. The average healthy
Also
ht not feel any symptoms when the CO Alarm sounds. However,
ig
lt m
u
ad
ople with cardiac or respiratory problems, infants, unborn babies, pregnant
pe
thers, or elderly people can be more quickly and severely affected by CO.
mo
pe
x
ou e
f y
I
mmediately!
i
ven mild symptoms of CO poisoning, consult your doctor
nce e
ie
r
ue
in
t
on
C
d...
R
tandards:Underwriters Laboratories Inc. Single and Multiple Station carbon
S
monoxide alarms UL2034.
According to Underwriters Laboratories Inc. UL2034, Section 1-1.2: “Carbon
xide alarms covered by these requirements are intended to respond to
mono
he presence of carbon monoxide from sources such as, but not limited to,
t
exhaust from internal-combustion engines, abnormal operation of fuel-fired
ppliances, and fireplaces. CO Alarms are intended to alarm at carbon
a
xide levels below those that could cause a loss of ability to react to the
mono
dangers of Carbon Monoxide exposure.” This CO Alarm monitors the air at
he Alarm, and is designed to alarm before CO levels become life threatening.
t
his allows you precious time to leave the house and correct the problem.
T
This is only possible if Alarms are located, installed, and maintained as
escribed in this manual.
d
Gas Detection at Typical Temperature and Humidity Ranges: The CO Alarm
is not formulated to detect CO levels below 30 ppm typically. UL tested for false
larm resistance to Methane (500 ppm), Butane (300 ppm), Heptane (500 ppm),
a
Ethyl Acetate (200 ppm), Isopropyl Alcohol (200 ppm) and Carbon Dioxide (5000
ppm).Values measure gas and vapor concentrations in parts per million.
udible Alarm:
A
inimum at 10 feet (3 meters).
85dB m
REGULATORY INFORMATION FOR EXPLOSIVE GAS
ALARMS
Standards: Underwriters Laboratories Inc. UL1484.
According to Underwriters Laboratories Inc. UL1484, this unit meets the alarm
esponse time for gas as follows: This unit shall alarm before 25% of the LEL
r
of either natural gas or propane is detected. In all cases, the unit will detect
gas as a priority over carbon monoxide. If the device is detecting CO, then
etects an amount of gas to cause an alarm, the device will stop alarming for
d
CO and begin to alarm for gas.
ENERAL LIMITATIONS OF EXPLOSIVE GAS/CO
G
ALARMS
This Gas/CO Alarm is intended for residential use. It is not intended for use in
ndustrial applications where Occupational Safety and Health Administration
i
(OSHA) requirements for Carbon Monoxide Alarms must be met.This device is
not intended to alert hearing impaired residents.
Gas/CO Alarms may not waken all individuals. If children or others do
t readily waken to the sound of the Gas/CO Alarm, or if there are infants or
no
amily members with mobility limitations, make sure that someone is assigned
f
o assist them in the event of an emergency.
t
This Gas/CO Alarm will not sense gas or CO that does not reach the
s
i
gas reaches the sensors.
Gas/CO Alarms may not be heard. The alarm horn loudness meets or
e
Gas/CO Alarm is installed outside the bedroom, it may not wake up a sound
sleeper or one who has recently used drugs or has been drinking alcoholic
be
E
blocked by distance or closed doors. Noise from traffic, stereo, radio, television,
a
t
impaired.
T
Gas/C
B
ives. Homeowners and renters must still insure their lives.
l
This Gas/CO Alarm is not foolproof. Like all other electronic devices, this
Gas/C
se
r
T
it
as possi
this device weekly. The unit should be replaced immediately if it is not operating
pr
t will only sense gas or CO at the sensor. Gas or CO may be present
ensors.
I
n other areas. Doors or other obstructions may affect the rate at which CO or
xceeds current UL standards of 85 dB at 10 feet (3 meters). However, if the
verages. This is especially true if the door is closed or only partly open.
ven persons who are awake may not hear the alarm horn if the sound is
ir conditioner, or other appliances may also prevent alert persons from hearing
he alarm horn.This Gas/CO Alarm is not intended for people who are hearing
his Gas/CO Alarm is not a substitute for life insurance.Though this
O Alarm warns against increasing CO levels or the presence of gas,
RK Brands, Inc. does not warrant or imply in any way that they will protect
O Alarm has limitations. It can only detect gas or CO that reaches the
t ma
I
.
s
nsor
emote part of the home, away from the alarm device.
his Gas/C
s parts have passed many stringent tests and are designed to be as reliable
ble, any of these parts could fail at any time. Therefore, you must test
operly.
ive early warning of the source of gas or CO is in a
t g
y no
arm has a limited life.
Al
O
Alt
houg
h t
h
is Gas/CO Alarm and all of
TROUBLESHOOTING GUIDE
If your Alarm does this... It means... You should...
een light is OFF. Unit will not alarm when you press
Gr
he Test/Silence button.
t
een light flashes ON, once a minute (horn is silent).
Gr
once a minute. Low battery warning. Battery is low or missing. Replace the battery. Avoid interrupting AC power.
”
s
irp
ch
“
he horn
T
nce a minute, the alarm sounds 3 quick “chirps”,
O
nd the green light flashes quickly three times.
a
The horn sounds constantly with no pattern and
cannot be silenced.
o alarm after you pressed the
t
n
ack i
f gas or C
is
or a l
s b
ly even though no high levels
t
n
ue
q
e
r
nds f
O are revealed in an investigation.
ptable replacement batteries, see “Regular Maintenance.”
f acce
t o
Alarm goe
Test/Silence button to silence an alarm.
Alarm sou
o
*F
If you have any questions that cannot be answered by reading this manual, call Consumer Affairs: 1-800-323-9005.
nit may not be receiving any power. Check the AC power supply. Make sure a fresh 9V
U
Alarm is no
battery back-up.
U
on self-d
or the Alarm has reached its end-of-life, 5 years.
Unit malfunction. Unit needs to be replaced. Units under warranty should be returned to
Gas a
he
T
“W
t receiving AC power.Unit is operating on
nit malfunction. Unit needs to be replaced. Based
iagnostic tests, the unit has detected a fault
e still potentially dangerous. Refer to “If Your Gas/CO Alarm Sounds” for details
els ar
v
O le
nd/or C
ly located. Refer to
r
ope
pr
m
y be i
Alarm ma
re to Install This Alarm.”
he
attery is installed to power the battery back-up
b
heck the AC power supply.
C
nits under warranty should be returned to
U
nufacturer for replacement. See “Limited
ma
Warranty” for details.
manufacturer for replacement. See “Limited
arranty” for details.
W
on how to respond to an alarm. If anyone is feeling ill,
UATE your home immediately and call 911.
C
A
V
E
f frequent alarms continue, have
I
.
larm
our a
e y
t
oca
Rel
checked for potential problems. You may be
e
home r
experiencing an intermittent gas or CO problem.
LIMITED WARRANTY
BRK Brands, Inc., ("BRK") the maker of First Alert®brand products warrants that for a period of five years from the date of purchase, this product will be free from
defects in material and workmanship. BRK, at its option, will repair or replace this product or any component of the product found to be defective during the warranty
period. Replacement will be made with a new or remanufactured product or component. If the product is no longer available, replacement may be made with a similar
product of equal or greater value.This is your exclusive warranty.
This warranty is valid for the original retail purchaser from the date of initial retail purchase and is not transferable. Keep the original sales receipt. Proof of purchase is
equired to obtain warranty performance. BRK dealers, service centers, or retail stores selling BRK products do not have the right to alter, modify or any way change
r
the terms and conditions of this warranty.
anty does not cover normal wear of parts or damage resulting from any of the following: negligent use or misuse of the product, use on improper voltage or
arr
is w
h
T
current, use contrary to the operating instructions, disassembly, repair or alteration by anyone other than BRK or an authorized service center. Further, the warranty
does not cover Acts of God, such as fire, flood, hurricanes and tornadoes or any batteries that are included with this unit.
BRK shall not be liable for any incidental or consequential damages caused by the breach of any express or implied warranty. Except to the extent prohibited by
pplicable law, any implied warranty of merchantability or fitness for a particular purpose is limited in duration to the duration of the above warranty. Some states,
a
inces or jurisdictions do not allow the exclusion or limitation of incidental or consequential damages or limitations on how long an implied warranty lasts, so the
v
o
pr
above limitations or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights that vary from state to state or
province to province.
H
o
w to Obtain Warranty Service
Service:
7:3
calling. 25 Spur Drive, El Paso TX 79906
B
to battery.
If service is required, do not return the product to your retailer. In order to obtain warranty service, contact the Consumer Affairs Division at 1-800-323-9005,
AM - 5:00 PM Central Standard Time, Monday through Friday. To assist us in serving you, please have the model number and date of purchase available when
0
y:
ter
t
a
R
B
F
or your records, please record:
Date Purchased: _______________________________
Where Purchased: ____________________________________________
Date Installed: ____________/____________Month/Year
Replacement date is five years after installation:__________/__________
nd o
E: E
T
O
N
lifecycle, the malfunction signal will sound once a minute to indicate
the need t
o immediately replace the Alarm.
, Inc. make no warranty, express or implied, written or oral, including that of merchantability or fitness for any particular purpose with respect
nds
a
K Br
Month/Year
e Signal — Once the unit reaches the end of its
if
f L
F
is a r
®
t
r
Ale
t
s
ir
ed trademark of the First Alert Trust.
r
e
t
is
g
e
ted in Mexico M08-0123-001
n
i
r
P
Q 1
STALLATION, Continued
IN
e “Avoiding Dead Air Spaces” for more information.
USER’S MANUAL
PLUG-IN EXPLOSIVE GAS AND CARBON MONOXIDE
ALARM WITH BATTERY BACK-UP AND SILENCE
FEATURE
Se
OTE:For any location, make sure no door or other obstruction could keep
N
carbon monoxide or gas from reaching the Alarm.
his unit should receive continuous electrical power. (The battery is
T
meant for emergency back-up only). Choose an outlet where it can’t be
ccidentally unplugged or switched off by children. Keep small children
a
way from the unit.Teach them not to play with it or unplug it. Explain
a
what the alarms mean.
WHERE THIS ALARM SHOULD NOT BE INSTALLED
To avoid causing damage to the unit, to provide optimum protection, and
o prevent unnecessary alarms, Do NOT locate this Alarm:
t
• In garages, kitchens, crawl spaces and unfinished attics. Avoid extremely
usty, dirty or greasy areas. Installation in these areas could lead to
d
nuisance alarms, may expose the sensor to substances that could damage
or contaminate it, or the Alarm may not be heard by persons in other areas
f the home, especially if they are sleeping.
120VAC ~ 60Hz, 0.25 A
MPORTANT! PLEASE READ CAREFULLY AND SAVE.
I
This unit was shipped with a user’s manual that contains important
information about its operation. If you are installing this unit for use by others,
ou must leave this manual—or a copy of it—with the end user.
y
rinted in Mexico
P
M08-0123-001
Q 10/06
Model GCO1
TABLE OF CONTENTS
Basic Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
Where To Install This Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Where This Alarm Should Not Be Installed . . . . . . . . . . . . . . . . . . . . . . . . .2
Before You Begin Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
How To Install This Gas/CO Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
ow Your Alarm Works . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
H
If Your Gas/CO Alarm Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
hat To Do if CO is Detected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
W
What To Do if Explosive Gas is Detected . . . . . . . . . . . . . . . . . . . . . . . . . .3
sing the Silence Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
U
Using the Remote Control Test/Silence Feature . . . . . . . . . . . . . . . . . . . . .4
Using the Peak CO Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Understanding the Light, Horn, and Display Patterns . . . . . . . . . . . . . . .3-4
eekly Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
W
Regular Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
What You Need To Know About CO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-6
What is CO? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
ymptoms of CO Poisoning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
S
Finding the Source of CO After an Alarm . . . . . . . . . . . . . . . . . . . . . . . . . .5
otential Sources of CO in the Home . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
P
ow Can I Protect My Family From CO Poisoning? . . . . . . . . . . . . . . . . . .6
H
egulatory Information For Explosive Gas/CO Alarms . . . . . . . . . . . . . . .6-7
R
gulatory Information for CO Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
Re
gulatory Information for Explosive Gas Alarms . . . . . . . . . . . . . . . . . . . .7
Re
l Limitations Of Explosive Gas/CO Alarms . . . . . . . . . . . . . . . . . . . .7
Genera
roubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
T
imited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
L
© 2
006 BRK Brands, Inc., a Subsidiary of Jarden Corporation. All rights reserved.
RK Brands, Inc., 3901 Liberty Street Road, Aurora, IL 60504-8122
B
mer Affairs: (800) 323-9005
Consu
.brkelectronics.com • www.firstalert.com
www
TY INFORMATION
IC SAF
S
A
B
Dangers, Warnings, and Cautions alert you to important operating
•
nstructions or to potentially hazardous situations. Pay special
i
attention to these items.
This combination Explosive Gas/Carbon Monoxide Alarm has two
•
eparate alarms. The CO Alarm is not designed to detect fire or any
s
ther gas.
o
t the sensor. Carbon monoxide gas may be present in other areas.
a
The Explosive Gas Alarm will only indicate the presence of explosive
gas tha
o sense smoke, heat or flames.
t
Do not stand too close to the unit when the alarm is sounding. It is
•
oud to wake you in an emergency. Exposure to the horn at close
l
ge ma
ran
Do not paint over the unit. Paint may clog the openings to the sensing
•
chamber
This unit must be powered by a 24-hour circuit. Be sure the circuit
•
cannot be turned off by a switch, dimmer, or ground fault circuit
terrupter. Failure to connect this unit to a 24-hour circuit may
n
i
vent it from providing constant protection.
pre
his
T
•
ls and the b
ai
f
The Alarm will check for the presence of explosive gas at the sensor
•
less f
could be pres
nto alarm, especially during a condition that results in a rapid
i
ldup of explosive gas.
*.
bui
• Test the Alarm once a week. If the Alarm ever fails to test correctly,
ve it replaced immediately! If the Alarm is not working properly, it
ha
cannot alert you to a problem.
This combination Carbon Monoxide and Explosive Gas Alarm is
•
ntended for residential use and is not suitable for use in hazardous
i
ca
o
l
• This product is intended for use in ordinary indoor locations of family
iving units. It is not designed to measure CO levels in compliance with
l
ccup
O
ndus
i
ke them more sensitive to carbon monoxide may consider using
ma
arning devices which provide audible and visual signals for carbon
w
on
m
carb
E
It will only indicate the presence of carbon monoxide gas
t reaches the sensor. The Explosive Gas Alarm is not designed
y harm your hearing.
g properly.
n
om opera
t the unit f
en
s and pre
arm mus
Al
requently when powered by the back-up battery. Explosive gas
ons as de
ti
ona
ti
a
trial standards. Individuals with medical conditions that may
ide con
x
o
on monoxide and your medical condition contact your physician.
v
A
e
v
t ha
ttery is dead or missing, the alarm cannot operate.
a
g the peri
n
t duri
en
n the National Electrical Code.
ned i
fi
y and Health Administration (OSHA) commercial or
t
e
l Saf
trations under 30 ppm. For additional information on
cen
r
ttery power to operate. If AC power
a
C or b
od be
ti
tween checks without going
INSTALLATION
O INSTALL THIS ALARM
T
RE
0/0
WHE
or Gas
F
to detect.
For CO Alarms,
that a CO Alarm should be centrally located outside of each separate sleeping
area in the immediate vicinity of the bedrooms. For added protection, install
additional CO Alarms in each separate bedroom, and on every level of your
home.
In general, install combination Explosive Gas and Carbon Monoxide
Alarms:
• WHERE YOU CAN HEAR THE ALARM FROM ALL SLEEPING AREAS
• In or near bedrooms and living areas or wherever you suspect a gas or
• On each level of a multi-level home.
Improper location can affect the sensitive electronic components in this Alarm.
Please see “Where this Alarm Should Not Be Installed”.
Recommended Placement
6
arms,
Al
Natural Gas (methane) is typically supplied through a main utility line
nected to your home. If you do not live in a rural area you are likely to
con
be a user of natural gas. Natural gas is a fossil fuel consisting mainly of
Methane. Methane is much lighter than air and will rise rapidly in air. If you
e a user of natural gas, the Alarm should be mounted between 6 and 12
ar
nches (152mm and 305 mm) away from the ceiling (using cord feature) to
i
ensure the earliest opportunity to detect a leak.
Propane is typically supplied to homes by delivery truck in liquid form and
stored near the home in propane tanks. Propane is used by homes in rural
areas that do not have natural gas service. Since propane is the most
y used Liquefied Petroleum Gas (LPG),
l
mon
com
often used synonymously. Unlike natural gas, propane is heavier than air
and will collect at lower levels. If you are a user of propane, the Alarm
ld be mou
shou
ensure the earliest opportunity to detect a leak.
Both propane and natural gas are colorless and odorless. For safety
easons, an ordorant (Mercaptan) is added so that any leak can be detect-
r
y smel
d b
e
around 20% of the
depending on the individuals sense of smell and how long they have been
exposed to it.The LEL of each of these gases defines the bottom range of
flammability for the gas. Your Alarm is calibrated to sound before 25% of
the LEL of either gas detected.
Therefore, it is possible that you may smell gas before the Alarm is
activated. If you are not sure which gas your home uses, contact your
utility company.
CO exposure is likely.
ing depends on the type of explosive gas you intend
t
n
mou
paneand
pro
nted near the floor (using the direct plug-in feature) to
l. The common detection threshold for smelling the gases is
Lower Explosion Limit (LEL). This can vary greatly
the National Fire Protection Association (NFPA) recommends
1 2
LP-Gasar
Continued...
e
o
In the garage, vehicle exhaust can contain some carbon monoxide. These
•
vels are higher when the engine is first started. Within hours of starting a
le
vehicle and backing it out of the garage, the levels present over time can
ivate the Alarm and become a nuisance.
act
• In the kitchen, some gas appliances can emit a short burst of CO or gas
pon start-up. This is normal. If your Explosive Gas/CO Alarm is installed
u
oo close to these appliances, it may alarm often and become a nuisance.
t
Keep units at least 20 feet (6 meters) from the sources of combustion
•
particles (stove, furnace, water heater, space heater) if possible. In areas
here a 20-foot (6m) distance is not possible – in modular, mobile, or
w
ller homes, for example – it is recommended the Alarm be placed as
sma
far from these fuel-burning sources as possible. The placement recom-
ndations are intended to keep these Alarms at a reasonable distance
me
rom a fuel-burning source, and thus reduce “unwanted” alarms. Unwanted
f
alarms can occur if an Alarm is placed directly next to a fuel-burning
source. Ventilate these areas as much as possible.
arm near a cooking or heating appliance, install at least 5 feet (1.5
Al
meters) from appliance.
• In extremely humid areas.This Alarm should be at least 10 feet (3 meters)
from a shower, sauna, humidifier, vaporizer, dishwasher, laundry room,
ility room, or other source of high humidity.
ut
In direct sunlight.
•
• In turbulent air, like near ceiling fans or open windows. Blowing air may
event CO or gas from reaching the sensors.
pr
• In areas where temperature is colder than 40˚ F (4˚ C) or hotter than
00˚ F (38˚ C).These areas include non-airconditioned crawl spaces,
1
nfinished attics, uninsulated or poorly insulated ceilings, porches, and
u
garages.
• Less than 12 inches (305 mm) away from fluorescent lights. Electrical
noise” can interfere with the sensor.
“
In “dead air” spaces. See “Avoiding Dead Air Spaces”.
•
If you must install the
AVOIDING DEAD AIR SPACES
Dead air” spaces may prevent gas from reaching the Alarm. To avoid dead
“
air spaces, follow installation recommendations below.
On ceilings, install Alarms as close to the center of the ceiling as possible.
f this is not possible, install the Alarm at least 4 inches (102 mm) from the wall
I
r.
or corne
or wall mounting,the top edge of Alarms should be placed between
F
nches (152 mm) and 12 inches (305 mm) from the wall/ceiling line.
6 i
On a peaked, gabled, or cathedral ceiling, install Alarm within 3 feet (0.9
ters) of the peak of the ceiling, measured horizontally.
me
N INSTALLATION
I
G
OU BE
Y
ORE
F
BE
O g
nce C
Si
pe of explosive gas you intend to detect. If you are not certain which type of
ty
gas you are using in your home, please read about natural gas and propane in
here to Install this Alarm”.
“W
a
M
•
Examples of noisy power could be major appliances on the same
rcuit, power from a generator or solar power, light dimmer on the
ci
ame circuit or mounted near fluorescent lighting. Excessively noisy
s
po
he p
nd t
i
F
n each la
O
•
ike 911) and a qualified appliance technician.
(l
Place one label near the Gas/CO Alarm, and the other label in the “fresh
•
air” location you plan to go if the alarm sounds.
ly mixes well with air, mounting the Alarm will depend on the
l
a
r
ne
e
e sure the a
k
er may cause damage to your Alarm.
w
ir of self-adhesive labels included with this Gas/CO Alarm.
a
larm is not receiving excessively noisy power.
n the phone number of your emergency responder
e i
it
r
bel w
HOW TO INSTALL THIS GAS/CO ALARM
IMPORTANT! Read all instructions before using this product.
ools you will need:
T
. Determine the best location for your Gas/CO Alarm.
1
our Alarm is equipped to be mounted as a corded unit (recommended
Y
.
2
for natural gas detection), a direct plug unit (recommended for propane
etection). The unit can be plugged directly into a wall outlet. If your
gas d
lets are mounted horizontally, refer to “If Outlet is Mounted Horizontally
out
(Sideways)”.
f the adapter is taken out of the unit, the Alarm can be installed high on
I
l, while the adapter is plugged into a wall outlet.The explosive gas
l
a
he w
t
you use will determine if the Alarm should be installed high on the wall
C cord option) or low on the wall (direct plug option).
(A
TING THE BATTERY BACK-UP
A
V
I
T
C
A
vate the battery back-up by installing the battery.
i
Act
up only and is not intended to power the Alarm for an extended period of
me in the absence of AC.
ti
he Alarm will light-up the display briefly to indicate the unit is receiving power.
T
RECT PLUG ALARM INTO AN OUTLET (for Propane Detection)
I
D
n be p
Alarm ca
is
h
T
is is the recommended configuration for detecting propane.
h
T
1. Choose a standard UNSWITCHED 120VAC outlet.
2. Plug Alarm in.
ewdriver, drill.
Scr
attery is for back-
he b
T
ed directly into a wall outlet located close to the floor.
ugg
l
IF OUTLET IS MOUNTED HORIZONTALLY (SIDEWAYS)
If you are going to use your Alarm as a direct plug into an outlet that is
e
t
n
mou
as follows:
1. With back of unit facing you (AC blades on your left), place your left thumb
on adapter release and grab AC blades with your right hand to release the
left side.
2. Repeat for the other side adapter thumb release. This will allow adapter to
ide out.
sl
. Remove adapter.
3
. Rotate the adapter 90º and snap firmly back into place.
4
5. Plug Alarm into AC outlet.
tally (sideways), you may want
on
iz
d hor
o r
t
te the adap
ta
o
ter 9
0º,
WALL MOUNTED ALARM (for Natural Gas Detection)
llation tips for power cord models:
ta
ns
I
more flexibility in mounting locations and allows the Alarm to be easily
installed at or above eye level.
NOTE: If you mount the Alarm high on a wall, make sure it is between 6 to 12
inches (152-305 mm) down from the ceiling.
“dead air” space and carbon monoxide or natural gas may not reach the
n
i
sensors.
NOTE: Do not cover the Alarm with a curtain.
To install for a wall-mount, you will need to pull out the removable adapter and
power cord, as follows:
1. Repeat steps 1 to 3 as described above in
2. With adapter out, pull out power cord and unwrap it.
3. Insert the screws provided until head is approx. 1/8 inch (3 mm) from wall
4. Hook the Alarm over the screw onto the keyhole in back of unit.
.
5
nting in plaster board or drywall, drill 3/16 inch (5 mm) hole and use
(if mou
plastic anchor provided). Use mounting guide template to locate holes as
shown in diagram below.
wer cord into AC outlet.
ug po
l
P
er cord option provides
w
he po
T
Any higher than this, it will be
“to rotate the adapter”.
SECURING THE POWER CORD TO AN OUTLET
NECT POWER TO THE OUTLET TO AVOID ELECTRICAL SHOCK.
N
O
C
IS
D
1.
Remove the wallplate screw from the outlet and hold the wallplate in position.
Plug the power cord into the wall outlet so that the screw hole lines up with
.
2
the wallplate screw hole.
. Insert the screw through the power cord screw hole and into the wallplate
3
screw hole.
4. Tighten screw in place and restore power to the outlet.
Mounting Guide Template
3 7/8 inches (98mm)
TEST THE ALARM
ake sure the Alarm is receiving AC power. Under normal operation, the Green
1.M
indicator light will shine continuously.
t light, recheck connections. If connections are correct and the Green
no
wer indicator still does not light, the unit should be replaced immediately.
po
. Press and hold the test button until the alarm sounds.You will hear the
2
nal that indicates the presence of explosive gas followed by the signal
sig
for carbon monoxide.
When testing the Alarm, have someone else check that the Alarm can be
d easily from the sleeping areas. The unit should be located where it
hear
n wake you if it alarms at night.
ca
If the Green power indicator light does
HOW YOUR ALARM WORKS
THE COVER OF YOUR ALARM
. Test/Silence Button:
1
ress and hold to activate
P
test, or to silence the
larm.
a
3
2
4
2. POWER Light (GREEN)
. Display
3
. (Behind the Cover) Alarm
4
orn: 85dB audible alarm
H
for test, alarm, and unit
lfunction warning.
ma
5. Display Button: Press to
recall highest CO level
1
ecorded
r
6. Battery Compartment
5
6
IF YOUR GAS/CO ALARM SOUNDS
WHAT TO DO IF CARBON MONOXIDE IS DETECTED
ctuation of your CO Alarm indicates the presence of carbon monoxide
A
(CO) which can kill you. In other words, when your CO Alarm sounds, you
t not ignore it!
mus
IF THE CO ALARM SOUNDS:
. Operate the Test/Silence button.
1
. Call your emergency services, fire department or 911.Write down the
2
number of your local emergency service here:
_______________________________________________________________
. Immediately move to fresh air—outdoors or by an open door or window.
3
o a head count to check that all persons are accounted for. Do not re-
D
enter the premises, or move away from the open door or window until the
mergency services responder has arrived, the premises have been aired
e
, and your CO Alarm remains in its normal condition.
out
. After following steps 1-3, if your CO Alarm reactivates within a 24-hour
4
period, repeat steps 1-3 and call a qualified appliance technician to
vestigate for sources of CO from fuel-burning equipment and appliances,
n
i
nd inspect for proper operation of this equipment. If problems are identi-
a
fied during this inspection have the equipment serviced immediately. Note
ny combustion equipment not inspected by the technician, and consult
a
he manufacturers’ instructions, or contact the manufacturers directly, for
t
more information about CO safety and this equipment. Make sure that
tor vehicles are not, and have not, been operating in an attached
mo
age or adjacent to the residence. Write down the number of a qualified
gar
appliance technician here:
_______________________________________________________________
WHAT TO DO IF EXPLOSIVE GAS IS DETECTED
ou hear the alarm horn sound one beep per second, gas has
If y
been de
from the building.
1. Leave the house immediately, opening doors and windows as you leave.
2. Do not use your telephone or appliances. Do not turn any light switches off
. Any spark or flame could ignite the gas.
or on
. Call 911 and your gas company from a phone that is away from your home.
3
. Do not re-enter the area until the source of the leak is found and corrected.
4
• If the unit alarms and you are not testing the unit, it is warning you
of a potentially dangerous situation that requires your immediate
ten
t
a
injury or death.
Never disconnect the power to quiet an unwanted alarm.
•
isconnecting the power disables the Alarm. This will remove
D
your protection.
arms have various limitations. See "General Limitations of Gas/CO
Al
Alarms" for details.
Condition LED
L
A
M
R
O
N
TTERY BACK-UP POWER LED is Off, flashing Green once every
BA
DURING TESTING LED flashes Red in sync with the
W OR MISSING BATTERY Normal
O
L
ALARM CONDITION LED flashes Red in sync with horn
S
GA
CARBON MONOXIDE ALARM LED flashes Red in sync with horn
PRE-ALARM CONDITION
C
O IS P
R
MALFUNCTION LED flashing Green 3 times in sync
LOW BATTERY SILENCE LED is Green.
. The word GAS will be displayed. Evacuate everyone
tected
. NEVER ignore any alarm. Ignoring the alarm may result in
on
ti
ANDING THE LIGHT, HORN, AND DISPLAY PATTERNS
T
S
R
E
D
N
U
C POWER LED is Green.
A
conds
45 se
ting an Alarm condition:
la
u
m
si
,
horn
first gas then CO
ESENT
Normal
with 3 rapid chirps
3 4
USING THE SILENCE FEATURE
N
EVER disconnect the power to your Alarm to silence the horn—use the
Silence Feature. Disconnecting the Alarm removes your protection!
• The Silence Feature is intended to temporarily silence the horn while
ou identify and correct the problem.
y
• To use the Silence Feature, press the Test/Silence button until the horn
is silent.
If the Test/Silence button is pressed while the Alarm is in the silence
•
mode, the alarm will start sounding again.
HEN THE GAS ALARM IS SILENCED...
W
The Alarm will remain silent for approximately 2 minutes and then return to
normal operation. If the gas has not cleared within the silence period, the unit
ill go back into alarm.
w
WHEN THE CO ALARM IS SILENCED...
he CO Alarm will remain silent for up to 4 minutes.While the Alarm is
T
lenced, it will continue to monitor the air for CO.After 4 minutes, if CO levels
si
remain potentially dangerous the horn will start sounding again.
The Silence Feature is intended to temporarily silence the Alarm horn. It will
t correct a CO or gas problem.
no
USING THE REMOTE CONTROL TEST/SILENCE FEATURE
sing the VOLUME or CHANNEL buttons on most remote controls, you can
U
est or silence this gas/CO Alarm from up to 12 feet (3.6 meters) away.
t
To Test or Silence the Alarm:
1. Make sure you have a clear path between you and
he Alarm, free of any obstructions.
t
2. Point the remote at the front of the Alarm.
. Press the VOLUME or CHANNEL button for at least
3
5 seconds.
If the Alarm does not respond to your remote control:
• You may be standing too far away.
Your remote may not be compatible.
•
You did not hold the button on your remote for at
•
t 5 seconds.
leas
• AC power must be present to Silence the low battery chirp.
S
ILENCING THE LOW BATTERY WARNING
This Silence Feature can temporarily quiet the low battery warning “chirp” for
p to 8 hours if AC power is present.You can silence the low battery warning
u
chirp” two ways:
“
1.
Manually: Press the Test/Silence button on the Alarm cover until you see
the Green LED flicker, acknowledging the button-press.
Using Your Remote Control: Standing no further than 12 feet (3.6 meters)
2.
away from the Gas/CO Alarm, aim your IR remote at the Alarm and press
he CHANNEL or VOLUME button for at least 3-5 seconds.
t
The display will flash “SILENCE” for 8 hours while the low battery warning
chirp” silence feature is activated. After 8 hours, the low battery “chirp” will
“
esume. The Alarm will continue to operate as long as AC power is supplied.
r
However,
replace the battery as soon as possible, to maintain protection in
ent of a power outage.
v
e
USING THE PEAK CO MEMORY
he CO Memory Feature lets you check the highest level of CO recorded.
T
To check CO Memory:
. Press the Display button until the peak CO level is displayed.
1
To clear CO Memory:
1. While checking CO memory, press or hold the Display
utt
b
2
.Press or hold the Display button until the CO Memory is
clear
E:
T
O
N
ntil you clear it. DO NOT clear the CO Memory reading if you plan to call
u
one to investigate a CO problem! Clear the CO Memory reading only
some
after the investigator has checked your home.
Horn Display
t All segments
n
le
Si
t
n
le
Si
the horn pattern for gas alarm
,
t
s
ir
F
(1 beep every second) is issued, and
he CO alarm horn pattern (4
n t
he
t
beeps, pause, 4 beeps) is issued.
A chirp is issued about every
minute.
Re
pea
pea
Re
Normal
3 rapid chirps every minute “ERROR” is displayed.
Silent “SILENCE” is displayed.
CLEAR” is displayed.
“
l
i
t
n
on u
.
d
e
vel will be saved, even after a power interruption,
O le
t C
s
he
ig
he h
T
ting 1 beep every second
4 be
pause
,
s
p
e
ng
i
t
of display are
urned on for
t
me
i
t t
a shor
upon initial
.Then
r
e
w
po
the battery level icon is displayed.
l segments of display are turned
Al
On for a short time upon initial
r. Then the battery level icon is
e
w
po
displayed flashing.
mulated
he si
ng t
i
ur
D
gas alarm,“GAS” is
yed along with
la
isp
d
a full alarm level.
During the simulated
O alarm,“CO” is
C
isplayed along with
d
a full alarm level.
veral ppm CO
Se
levels are also
displayed and
the alarm level is
ncreasing.
n i
w
sho
Battery icon will show
an empty icon.
“
GA
S”, a full level, and “EVACUATE”.
lternating
a
”
O
C
“
with the ppm
number, a full level,
nd “EVACUATE”.
a
“CO” alternating with the ppm number.
The level will indicate relative CO
exposure level.