BRK electronic First Alert SC9120BA, First Alert SC9120A User Manual

Page 1
IF THE CO ALARM SOUNDS
Actuation of this device indicates the presence of carbon monoxide (
CO) which can kill you. If the CO Alarm sounds 4 beeps:
1. Immediately move to fresh air — outdoors or by an open door or w
indow. Check that all persons are accounted for. Do not re-enter the premises or move away from the open door/window until the e
mergency services responders have arrived, the premises have
been
aired out, and your alarm remains in its normal condition.
2. Call your local emergency services, fire department, or 911.
_____________________________________________
1
2 3
INTRODUCTION
Thank you for choosing BRK Brands, Inc. for your Smoke and Carbon Monoxide Alarm needs. You have purchased a state-of-the-art Smoke & CO Alarm designed to provide you with early warning of a fire or Carbon Monoxide. Key features include: Smoke & Carbon Monoxide Combination Alarm. One alarm protects against two deadly household threats.
M
ost Accurate Carbon Monoxide Sensor* Advanced electrochemical
CO sensor technology.
I
ntelligent Sensing Technology designed to help reduce unwanted or
n
uisance alarms.
S
mart Interconnect can be interconnected to BRK Smoke Alarms.
O
ne interconnect wire carries both smoke and CO alarm signals.
S
ingle Button Test/Silence eliminates confusion. Depending on what
m
ode the alarm is in, pushing the button provides different functions
s
uch as testing the alarm, silencing the alarm, re-testing the alarm when
i
n silence and clearing the Latching feature.
T
wo Silence Features. Temporarily silence low battery chirp for up to
e
ight hours before replacing low battery or silence an unwanted alarm
f
or several minutes.
Two Latching Features. Alarm Latch: Easily identifies initiating alarm even after alarm condition has subsided. Low Battery Latch: Identifies which unit is in low battery condition.
P
erfect Mount System includes a gasketless base for easy installation
a
nd a new mounting bracket that keeps the alarm secure over a wide
r
otation range to allow for perfect alignment.
End of Life Signal. Provides audible and visual confirmation alarm needs to be replaced.
*
As compared to other sensing technologies
©
2015 BRK Brands, Inc. All rights reserved. Distributed by
B
RK Brands, Inc., 3901 Liberty Street Road, Aurora, IL 60504-8122 U.S.A.
C
onsumer Affairs: (800) 323-9005
w
ww.brkelectronics.com • www.firstalert.ca
FIRE SAFETY TIPS
F
ollow safety rules and prevent hazardous situations: 1) Use smoking
m
aterials properly. Never smoke in bed. 2) Keep matches or lighters
a
way from children; 3) Store flammable materials in proper containers;
4
) Keep electrical appliances in good condition and don’t overload electri-
c
al circuits; 5) Keep stoves, barbecue grills, fireplaces and chimneys
g
rease- and debris-free; 6) Never leave anything cooking on the stove
u
nattended; 7) Keep portable heaters and open flames, like candles,
a
way from flammable materials; 8) Don’t let rubbish accumulate.
K
eep alarms clean, and test them weekly. Replace alarms immediately
i
f they are not working properly. Smoke Alarms that do not work cannot a
lert you to a fire. Keep at least one working fire extinguisher on every
f
loor, and an additional one in the kitchen. Have fire escape ladders or
o
ther reliable means of escape from an upper floor in case stairs are
b
locked.
BASIC SAFETY INFORMATION
• Dangers, Warnings, and Cautions alert you to important operating instructions or to potentially hazardous situations. Pay special attention to these items.
• This Smoke/CO Alarm is approved for use in single-family residences. It is NOT designed for marine or RV use.
This combination Smoke/Carbon Monoxide Alarm has two sep­arate alarms. The CO Alarm is not designed to detect fire or any other gas. It will only indicate the presence of carbon monoxide gas at the sensor. Carbon monoxide gas may be present in other areas. The Smoke Alarm will only indicate the presence of smoke that reaches the sensor. The Smoke Alarm is not designed to sense gas, heat or flames.
A
ll BRK
®
a
nd First Alert
®
S
moke Alarms conform to regulatory
r
equirements,
i
ncluding ULC S531 and are designed to detect
p
articles of combustion. Smoke particles of varying number and
s
ize are produced in all fires.
I
onization technology is generally more sensitive than photelectric t
echnology at detecting small particles, which tend to be pro­d
uced in greater amounts by flaming fires, which consume com-
b
ustible materials rapidly and spread quickly. Sources of these fires
m
ay include paper burning in a wastebasket, or a grease fire in the
k
itchen. Photoelectric technology is generally more sensitive than ionization technology at detecting large particles, which tend to be produced in greater amounts by smoldering fires, which may smolder for
hours before bursting into flame. Sources of these fires may include cigarettes burning in couches or bedding.
F
or maximum protection, use both types of Smoke Alarms on each
l
evel and in every bedroom of your home.
4 5 6
INSTALLATION
WHERE TO INSTALL THIS ALARM
M
inimum coverage for Smoke Alarms, as recommended by the
N
ational Fire Protection Association (NFPA), is one Smoke Alarm on
e
very floor, in every sleeping area, and in every bedroom (See
Regulatory Information For Smoke Alarms” for details on the NFPA
r
ecommendations).
For CO Alarms, the National Fire Protection Association (NFPA) recommends that a CO Alarm should be centrally located outside of each separate sleeping area in the immediate vicinity of the bedrooms. For added protection, install additional CO Alarms in each separate bedroom, and on every level of your home.
In general, install combination Smoke and Carbon Monoxide Alarms:
On every level of your home, including finished attics and basements.
Inside every bedroom, especially if people sleep with the door partly
o
r completely closed.
• In the hall near every sleeping area. If your home has multiple sleeping areas, install a unit in each. If a hall is more than 12 meters (40 feet) long, install a unit at each end.
At the top of first-to-second floor stairs.
• At the bottom of the basement stairs.
• For additional coverage, install Alarms in all rooms, halls, and storage areas, where temperatures normally remain between 4.4 C and
37.8
o
C (40oF and 100oF).
Recommended Placement
When installing on the wall, the top edge of Smoke Alarms should
b
e placed between 102 mm (4 inches) and 305 mm (12 inches)
f
rom the wall/ceiling line.
When installing on the ceiling, place the alarm as close to the
c
enter as possible.
In either case, install at least 102 mm (4 inches) from where the
w
all and ceiling meet. See “Avoiding Dead Air Spaces” for more
i
nformation.
N
OTE: For any location, make sure no door or other obstruction could
k
eep carbon monoxide or smoke from reaching the Alarm.
I
nstalling Smoke/CO Alarms in Mobile Homes
F
or minimum security install one Smoke/CO Alarm as close to each
s
leeping area as possible. For more security, put one unit in each room.
M
any older mobile homes (especially those built before 1978) have little
o
r no insulation. If your mobile home is not well insulated, or if you are
u
nsure of the amount of insulation, it is important to install units on
i
nside walls only.
This equipment should be installed in accordance with CAN/ULC S553 or NFPA (National Fire Protection Association) 72 and
101. National Fire Protection Association, One Batterymarch Park, Quincy, MA 02269-9101 U.S.A. Additional local building and regulatory codes may apply in your area. Always check compliance requirements before beginning any instal­lation.
WHERE THIS ALARM SHOULD NOT BE INSTALLED
Do NOT locate this Smoke/CO Alarm:
• In garages, kitchens, furnace rooms, crawl spaces and unfinished
attics. Avoid extremely dusty, dirty or greasy areas.
Where combustion particles are produced. Combustion particles
f
orm when something burns. Areas to avoid include poorly ventilated
k
itchens, garages, and furnace rooms. Keep units at least 6 meters (20 feet) from the sources of combustion particles (stove, furnace, water heater, space heater) if possible. In areas where a 6 meter (20-foot) distance is not possible – in modular, mobile, or smaller homes, for example – it is recommended the Smoke/CO Alarm be placed as far from these fuel-burning sources as possible. The placement recommendations are intended to keep these Alarms at a reasonable distance from a fuel-burning source, and thus reduce “unwanted” alarms. Unwanted alarms can occur if a Smoke/CO Alarm is placed directly next to a fuel-burning source. Ventilate these areas as much as possible.
• Within 1.5 meters (5 feet) of any cooking appliance. In air streams near kitchens. Air currents can draw cooking smoke into the smoke sensor and cause unwanted alarms.
• In extremely humid areas. This Alarm should be at least 3 meters (10 feet) from a shower, sauna, humidifier, vaporizer, dishwasher, laundry room, utility room, or other source of high humidity.
• In direct sunlight.
• In turbulent air, like near ceiling fans or open windows. Blowing air may prevent CO or smoke from reaching the sensors.
• In areas where temperature is colder than 4.4
o
C (40oF) or hotter than 37.8oC (100oF). These areas include non-airconditioned crawl spaces, unfinished attics, uninsulated or poorly insulated ceilings, porches, and garages.
• In insect infested areas. Insects can clog the openings to the sensing chamber.
• Less than 305 mm (12 inches) away from fluorescent lights. Electrical “noise” can interfere with the sensor.
• In “dead air” spaces. See “Avoiding Dead Air Spaces”.
AVOIDING DEAD AIR SPACES
“Dead air” spaces may prevent smoke from reaching the Smoke/CO Alarm. To avoid dead air spaces, follow installation recommendations below. On ceilings, install Smoke/CO Alarms as close to the center of the ceiling as possible. If this is not possible, install the Smoke/CO Alarm at least 102 mm (4 inches) from the wall or corner.
For wall mounting (if allowed by building codes), the top edge of Smoke/CO Alarms should be placed between 102 mm (4 inches) and 305 mm (12 inches) from the wall/ceiling line.
On a peaked, gabled, or cathedral ceiling, install the first Smoke/CO Alarm within 0.9 meters (3 feet) of the peak of the ceiling, measured horizontally. Additional Smoke/CO Alarms may be required depending on the length, angle, etc. of the ceiling's slope. Refer to NFPA 72 for details on requirements for sloped or peaked ceilings.
Continued...
BEFORE YOU BEGIN INSTALLATION
This unit is designed to be mounted on any standard wiring junction box up to a 10 cm (4-inch) size, on either the ceiling or wall. Read “Where to Install This Alarm” and “Where This Alarm Should Not Be Installed ” before you begin installation.
• Make sure the alarm is not receiving excessively noisy power. E
xamples of noisy power could be major appliances on the
s
ame circuit, power from a generator or solar power, light dim-
m
er on the same circuit or mounted near fluorescent lighting.
E
xcessively noisy power may cause damage to your Alarm.
NOTE:A qualified appliance technician is defined as “a person, firm,
corporation, or company that either in person or through a representative, is engaged in and responsible for the installation, testing, servicing, or replacement of heating, ventilation, air conditioning (HVAC) equipment, combustion appliances and equipment, and/or gas fireplaces or other decorative combustion equipment.”
1
Mounting Bracket
2
Mounting Slot and Screw*
3 Locking Pins (break out of
bracket)
4 Hot (Black) AC Wire
5 Neutral (White) AC Wire
6 Interconnect Wire (Orange)
7
Lever to Open Battery
C
ompartment
8
Swing-Out Battery
C
ompartment
9
Quick-Connect Power
*Not Included
PARTS OF THIS SMOKE/CO ALARM
T
ools you will need: Standard Flathead screwdriver, wire strippers.
E
LECTRICAL SHOCK HAZARD. Turn off power to the area where you
w
ill install this unit at the circuit breaker or fuse box before beginning
i
nstallation. Failure to turn off the power before installation may
r
esult in serious electrical shock, injury or death.
To install this unit:
1. Remove the mounting bracket from the base. Position the screw slots on the mounting bracket over the screws in the junction box. Tighten the screws.
I
mproper wiring of the power connector or the wiring leading to the
p
ower connector will cause damage to the Alarm and may lead to a
n
on-functioning Alarm.
2. Using wire nuts, connect the power connector to the AC power.
3. Plug the power connector into the back of the Smoke/CO Alarm.
4
.
P
osition the base of the Smoke/CO Alarm over the mounting bracket
a
nd turn. The Alarm will remain secure over a wide rotation range to
a
llow for perfect alignment. When wall mounting, this will allow fine-
t
uning on the positioning to compensate for out of aligned wall studs
a
nd to keep the wording level. The Alarm can be positioned over the
b
racket every 120°. Rotate the Alarm until aligned properly.
5. Check all connections.
S
TAND ALONE ALARM ONLY:
• Connect the white wire on the power connector to the neutral wire in the junction box.
Connect the black wire on the power connector to the hot wire
i
n the junction box.
Tuck the orange wire inside the junction box. It is used for
i
nterconnect only.
I
NTERCONNECTED ALARMS ONLY:
S
trip off about 1/2” of the plastic coating on the orange
i
nterconnect wire on the power connector.
• Connect the white wire on the power connector to the neutral wire (usually white) in the junction box.
• Connect the black wire on the power connector to the hot wire (usually black) in the junction box.
Connect the orange wire on the power connector to the inter-
c
onnect wire in the junction box. Repeat for each unit you are
i
nterconnecting. Never connect the hot or neutral wires in the j
unction box to the orange interconnect wire. Never cross hot a
nd neutral wires between interconnected Alarms.
S
PECIAL REQUIREMENTS FOR INTERCONNECTED ALARMS
Failure to meet any of the above requirements could damage
t
he units and cause them to malfunction, removing your
p
rotection.
• AC and AC/DC Smoke/CO Alarms can be interconnected. Under AC power, all units will alarm when one senses smoke o
r CO. When power is interrupted, only the AC/DC units in
t
he series will continue to send and receive signals.
A
C powered Smoke/CO Alarms will not operate. See “Smart
I
nterconnect” Feature.
Interconnected units can provide earlier warning of a Smoke/CO problem than stand-alone units, especially if the problem starts in a remote area of the dwelling. If any unit in the series senses Smoke/CO, all units will alarm. To determine which Smoke/CO Alarm initiated an alarm, refer to the table.
D
uring an Alarm:
O
n Initiating Alarm(s) – Red LED(s) flashes (flash) rapidly
On All Other Alarms – Red LED is Off
A
fter an Alarm (Latching):
On Initiating Alarm(s) – Red LED(s) On for 2 seconds/Off for 2 seconds
O
n All Other Alarms – Green LED(s) On, Red LED(s) is Off
Compatible Interconnected Units
I
nterconnect units within a single family residence only. Otherwise all
h
ouseholds will experience unwanted alarms when you test any unit
i
n the series. Interconnected units will only work if they are wired to c
ompatible units and all requirements are met. This unit is designed
t
o be compatible with:
F
irst Alert
®
/
BRK
®
M
odels SC9120BA, SC9120A, CO5120BNA,
S
A520CNA, SC7010BA; BRK
®
A
uxiliary Device Model RM4 (Relay
M
odule).
Interconnected units must meet ALL of the following requirements:
A maximum of 18 compatible BRK Electronics
®
S
moke, Heat or
C
O Alarms may be interconnected. No more than 12 of the 18 can
b
e Smoke Alarms per NFPA 72.
• The same fuse or circuit breaker must power all interconnected units.
The total length of wire interconnecting the units should be
l
ess than 300 meters (1000 feet). This type of wire is commonly a
vailable at Hardware and Electrical Supply stores.
All wiring must conform to all local codes and the Canadian
E
lectrical Code, CSA 22.1.
6
. Make sure the Smoke/CO Alarm is receiving AC power. Under normal
o
peration, the green indicator light will shine continuously.
I
f the green
p
ower indicator light does not light, TURN OFF POWER TO THE
J
UNCTION BOX and recheck all connections. If all connections are
c
orrect and the green power indicator still does not light when you
r
estore the power, the unit should be replaced immediately.
7
. ACTIVATING THE BATTERY BACK-UP
Activate the battery back-up by removing the “Pull to Activate Battery Back-Up” tab. You do not need to open the battery compartment and reposition the battery during installation.
DO NOT remove the battery activation tab until AC power is turned on to conserve battery power.
8
. Single Station Alarms: Test each Alarm. Press and hold the
T
est/Silence button until you hear the acknowledge “chirp” or the
u
nit alarms.
I
nterconnected Alarms: Press and hold the Test/Silence button
u
ntil the unit alarms. All interconnected Alarms should sound. The
o
ther Alarms sounding only tests the interconnect signal between
A
larms. It does not test each Alarm’s operation. You must test each
A
larm individually to check if the Alarm is functioning properly.
If any unit in the series does not alarm during testing, TURN OFF POWER, REMOVE BATTERIES, and recheck connections. If it does not alarm when you restore power, replace it immediately.
A
. Unswitched 120VAC B. To Additional Alarms,
6
0 Hz source Maximum = 18 Alarms
1
. Smoke/CO Alarm
2
. Ceiling or Wall
3
. Power Connector
4
. Wire Nut
5
. Junction Box
6
. Neutral Wire
(White)
7
. Interconnect Wire
(Orange)
8. Hot Wire (Black)
STAND ALONE ALARM ONLY:
• If you are only installing one unit, restore power to the junction box.
INTERCONNECTED ALARMS ONLY:
• If you are interconnecting multiple Smoke/CO Alarms, repeat Step 1-5 for each Smoke/CO Alarm in the series. When you are finished, restore power to the junction box.
E
LECTRICAL SHOCK HAZARD. Do not restore power until all
A
larms are completely installed. Restoring power before installa-
t
ion is complete may result in serious electrical shock, injury or
d
eath.
HOW TO INSTALL THIS SMOKE/CO ALARM
INSTALLATION, Continued
1. Test/Silence Button: Press and hold to activate test, or to silence the alarm.
2
. POWER Light (GREEN)/
S
MOKE ALARM Light (RED)
3
. CO ALARM Light (RED)
4
. Battery Drawer
5. (Behind the Cover) Alarm Horn: 85dB audible alarm for test, alarm, and unit malfunction warning.
HOW YOUR SMOKE/CO ALARM WORKS
The optional locking features are designed to discourage unauthorized removal of the battery or alarm. It is not necessary to activate the locks in single-family households where unauthorized battery or alarm removal is not a concern.
These Smoke/CO Alarms have two separate locking features: one locks the battery compartment, and the other locks the Smoke/CO Alarm to the mounting bracket. You can choose to use either feature independently, or use them both.
Tools you will need: • Needle-nose pliers or utility knife
• Standard/Flathead screwdriver.
USING THE OPTIONAL LOCKING FEATURES
THE BATTERY COMPARTMENT LOCK
TO LOCK THE BATTERY COMPARTMENT:
Do not lock the battery compartment until you have activated the battery and tested the battery back-up.
1. Activate the battery back-up by removing the “Pull to Activate Battery Back-Up” tab. Push and hold the test button on the Smoke/CO Alarm’s cover until the alarm sounds: continuous beeping; then 4 beeps, pause, 4 beeps.
If the unit does not alarm during testing, DO NOT lock the battery compartment! Install a new battery and test again. If it still does not alarm, replace the Smoke/CO Alarm immediately.
2. Using needle-nose pliers or a utility knife, detach one locking pin from the mounting bracket.
3. Push the locking pin through the black dot on the label on the back of the Smoke/CO Alarm.
THE MOUNTING BRACKET LOCK
TO ACTIVATE THE BRACKET LOCK:
1. Using needle-nose pliers, detach one locking pin from the mounting bracket.
2. Insert the locking pin into the lock located on the base as shown in the diagram.
3. When you attach the Smoke/CO Alarm to the mounting bracket, the locking pin’s head will fit into a notch on the bracket.
TO DEACTIVATE THE BRACKET LOCK:
ELECTRICAL SHOCK HAZARD. Turn off the power to the area where the Smoke/CO Alarm is installed before removing it from the mounting bracket. Failure to turn off the power first may result in serious electrical shock, injury or death.
Always discharge the branch circuit before servicing an AC or AC/DC Smoke/CO Alarm. First, turn off the AC power at the circuit breaker or fuse box. Next, remove the battery from Smoke/CO Alarms with battery back-up. Finally, press and hold the test button.
1.
Insert a flathead screwdriver between the mounting bracket pin and the mounting bracket.
2. Pry the Smoke/CO Alarm away from the bracket by turning both the screwdriver and the Smoke/CO Alarm counterclockwise (left) at the same time.
TO PERMANENTLY REMOVE THE BRACKET LOCK:
Insert the flathead screwdriver between the locking pin and the lock, and pry the pin out of the lock.
TO UNLOCK THE BATTERY COMPARTMENT:
Once the Smoke/CO Alarm is installed, you must disconnect it from the AC power before unlocking the battery compartment.
ELECTRICAL SHOCK HAZARD. Turn off the power to the area where the Smoke/CO Alarm is installed before removing it from the mounting bracket. Failure to turn off the power first may result in serious electrical shock, injury or death.
1. Remove the Smoke/CO Alarm from the mounting bracket. If the unit is locked to the bracket, see the section “To Deactivate the Locking Feature.”
2. Disconnect the power connector by gently prying it away from the back of the Smoke/CO Alarm.
3. Insert a flathead screwdriver under the head of the locking pin, and gently pry it out of the battery compartment lock. (If you plan to relock the battery compartment, save the locking pin.)
4. To relock the battery compartment, close the battery door and reinsert the locking pin in the lock.
5. Reconnect the power connector to the back of the Smoke/CO Alarm, reattach the Smoke/CO Alarm to the mounting bracket, and restore the power.
When replacing the battery, always test the Smoke/CO Alarm before relocking the battery compartment.
M
ounting Bracket Lock
Battery Drawer Lock
Locking Pin
IF YOUR SMOKE/CO ALARM SOUNDS
WHAT TO DO IF SMOKE IS DETECTED
• If the unit alarms and you are not testing the unit, it is warning you of a potentially dangerous situation that requires your immediate attention. NEVER ignore any alarm. Ignoring the alarm may result in injury or death.
• Never disconnect the AC power to quiet an unwanted alarm. D
isconnecting the power disables the Alarm so it cannot
s
ense smoke. This will remove your protection. Instead, open
a
window or fan the smoke away from the unit. The Alarm will
r
eset automatically.
• If the unit alarms get everyone out of the house immediately.
E
LECTRICAL SHOCK HAZARD: Attempting to disconnect the
p
ower connector from the unit when the power is on may result
i
n electrical shock, serious injury or death.
W
hen an interconnected system of AC powered units is in alarm,
t
he alarm indicator light on the unit(s) that initiated the alarm will blink
r
apidly. It will remain OFF on any remaining units. If the unit alarms, get everyone out of the dwelling immediately. I
f the unit alarms and you are certain that the source of smoke is not a f
ire—cooking smoke or an extremely dusty furnace, for example—open a n
earby window or
d
oor and fan the smoke away from the unit. Use the
S
ilence Feature to silence the Alarm. This will silence the alarm, and
o
nce the smoke clears the unit will reset itself automatically.
WHAT TO DO IN CASE OF FIRE
Don’t panic; stay calm. Follow your family escape plan.
• Get out of the house as quickly as possible. Don’t stop to get
dressed or collect anything.
Feel doors with the back of your hand before opening them.
I
f a door is cool, open it slowly. Don’t open a hot door. Keep doors
a
nd windows closed, unless you must escape through them.
Cover your nose and mouth with a cloth (preferably damp).
T
ake short, shallow breaths.
• Meet at your planned meeting place outside your home,
and do a head count to make sure everybody got out safely.
Call the Fire Department as soon as possible from outside.
G
ive your address, then your name.
• Never go back inside a burning building for any reason.
Contact your Fire Department for ideas on making your home safer.
A
larms have various limitations. See "General Limitations of
S
moke/CO Alarms" for details.
“SMART INTERCONNECT” FEATURE
This Alarm includes "Smart Interconnect" which enables the Alarm to be interconnected with other BRK Smoke, Heat, and "Smart Interconnect" CO Alarms. When smoke is detected, all Alarms will sound the smoke horn pattern. When CO is detected, "Smart Interconnect" Alarms will sound the CO horn pattern. Alarms that do not have the "Smart Interconnect" Feature will remain silent during a CO alarm.
If you hear the alarm horn sound 3 beeps, pause, 3 beeps and the RED SMOKE light is flashing, smoke has been detected. Evacuate everyone from the building.
Using the Optional Locking Features (Continued)
• Connect this unit ONLY to other compatible units. See “How To Install This Smoke/CO Alarm” for details. Do not connect it to any other type of alarm or auxiliary device. Connecting anything else to this unit may damage it or prevent it from operating properly.
• The battery compartment resists closing unless a battery is installed. This warns you the unit will not operate under DC power without a battery.
• Do not stand too close to the unit when the alarm is sounding. It is loud to wake you in an emergency. Exposure to the horn at close range may harm your hearing.
• Do not paint over the unit. Paint may clog the openings to the sensing chambers and prevent the unit from operating proper­ly.
Both locking features use locking pins, molded into the mounting bracket. Using needle nose pliers or a utility knife, remove one or both pins, depending on which locking features you use.
WHAT YOU WILL SEE AND HEAR WITH THIS ALARM
Under Normal Operations
H
orn: Silent Power/Smoke LED:AC Power (LED Green); Battery Power (LED off) C
O LED: Off
When You Test the Alarm
H
orn: continuous beeping Power/Smoke LED: Flashes Red in sync with the horn pattern CO LED: Off, followed by H
orn: 4 beeps, pause, 4 beeps Power/Smoke LED:AC Power (LED Green); Battery Power (LED off) CO LED: Flashes Red in sync with the horn pattern
I
f Battery Becomes Low or is Missing
Horn: chirps once a minute P
ower/ Smoke LED: Low Battery latch is now engaged. (See
L
atching Features note below.) Green LED On for 2
s
econds/Off for two seconds.
C
O LED: Off
I
f Alarm is Not Operating Properly (MALFUNCTION SIGNAL)
H
orn: 3 chirps every minute Power/Smoke LED: Green LED 3 Flashes approx. once a minute C
O LED: Off
Alarm has reached its End of Life
H
orn: 5 chirps every minute P
ower/Smoke LED: Green LED 5 Flashes approx. once a minute C
O LED: Off
A
larm Levels of CO are Detected
H
orn: 4 beeps, pause, 4 beeps P
ower/Smoke LED:AC Power (LED Green); Battery Power (LED off) CO LED: During Alarm: Flashes Red in sync with the horn pattern.
After Alarm: Flashes Red On for 2 seconds/Off for 2 seconds. CO Alarm Latch is now engaged. (See LATCHING FEATURES section for details).
S
moke is Detected
H
orn: 3 beeps, pause, 3 beeps P
ower/Smoke LED: During Alarm: Flashes Red in sync with the horn
p
attern. After Alarm: Flashes Red On for 2 seconds/Off for 2
s
econds. Smoke Alarm Latch is now engaged. (See LATCH-
I
NG FEATURES section for details).
CO LED: Off
Smoke Alarm is Silenced
H
orn: Off P
ower/Smoke LED: Flashes Red CO LED: Off
C
O Alarm is Silenced
H
orn: Off P
ower/Smoke LED:AC Power (LED Green); Battery Power (LED
o
ff)
CO LED: Flashes Red
Latching Features Note: Without AC Power and running on battery only, Low Battery Latch or Alarm Latch are only engaged for about 15 minutes to conserve power. Low Battery Latch and Alarm Latch do not operate with a missing battery and no AC Power.
USING THE SILENCE FEATURES
N
ever remove the batteries to quiet an unwanted alarm. Removing
t
he batteries disables the alarm and removes your protection.
The Silence Feature is intended to temporarily silence the horn while you identify and correct the problem. Do not use the Silence Feature in emergency situations. It will not correct a CO problem or extinguish a fire.
The Silence Feature can temporarily quiet an unwanted alarm for several minutes. You can silence this Smoke/CO Alarm by pressing the Test/ Silence button on the alarm cover until you hear an acknowledge chirp.
After the Test/Silence button is released, the Red LED blinks during the silence mode.
SILENCING THE LOW BATTERY WARNING
This Silence Feature can temporarily quiet the low battery warning “chirp” for up to 8 hours if AC power is present. Press the Test/Silence button on the Alarm cover until you hear the acknowledge “chirp”.
Once the low battery warning “chirp” silence feature is activated, the unit continues to flash the green light once a minute for 8 hours. After 8 hours, the low battery “chirp” will resume. The Alarm will continue to operate as long as AC power is supplied. Note, if battery is missing or dead, Low Battery Silence cannot be activated and alarm with continue to chirp approximately once per minute. However, replace the batteries
as soon as possible, to maintain protection in event of a power outage. To deactivate this feature: Press the Test/Silence button again.
The unit will go into Test Mode and the low battery warning will resume (LED flashes and unit sounds “chirp” once a minute).
To silence Alarms in an interconnected series:
To silence an interconnected series of Smoke/CO Alarms, you must press the Test/Silence button on the initiating alarm (The unit with the flashing red light; the red light will be off on all other Alarms.). If you press the Test/Silence on any other Alarm, it will only silence that unit, not the whole interconnected series.
When the Smoke Alarm is Silenced
When the CO Alarm is Silenced
The Smoke Alarm will remain silent for up to 10 minutes, then return to normal operation.
If the smoke has not cleared–or continues to increase–the device will go back into alarm.
The CO alarm will remain silent for up to 4 minutes.
After 4 minutes, if CO levels remain potentially dangerous the horn will start sounding again.
SILENCING THE END OF LIFE SIGNAL
This silence feature can temporarily quiet the End of Life warning “chirp” for up to 2 days. You can silence the End of Life warning “chirp” by pressing the Test/Silence button. The horn will chirp, acknowledging that the End of Life silence feature has been activated. After approximately 2 days, the End of Life “chirp” will resume. After approximately 2-3 weeks the End of Life warning cannot be silenced.
U
SER’S MANUAL
Smoke & Carbon Monoxide Alarm
AC Powered Smoke & Carbon Monoxide Alarm with Battery Back-up, Silence Feature and Latching Alarm
M
odel SC9120BA &
SC9120A
Input: 120V AC ~ , 60Hz, 0.09A
I
MPORTANT! PLEASE READ CAREFULLY AND SAVE.
T
his user’s manual contains important information about your Alarm’s
o
peration. If you are installing the Alarm for use by others, you must
l
eave this manual—or a copy of it—with the end user.
M08-0121-014 K1 10/15 Printed in Mexico
LISTED to
CSA 6.19-01
and ULC S531
STANDARDS
ELECTRICAL SHOCK HAZARD. Turn off the power to the area where the Smoke/CO Alarm is installed before removing it from the mounting bracket. Failure to turn off the power first may result in serious electrical shock, injury or death.
• This unit will not alert hearing impaired residents. It is recommended that you install special units which use devices like flashing strobe lights to alert hearing impaired residents.
• Installation of this unit must conform to the electrical codes in your area; CSA 22.1 Canadian Electrical Code or NFPA 70, and any other local or building codes that may apply. Wiring and installation must be performed by a licensed electrician. Failure to follow these guidelines may result in injury or property damage.
• This unit must be powered by a 24-hour, 120V AC pure sine wave 60 Hz circuit. Be sure the circuit cannot be turned off by a switch, dimmer, or ground fault circuit interrupter. Failure to connect this unit to a 24-hour circuit may prevent it from providing constant protection.
Unit may be connected to
an arc fault circuit interrupter.
This Smoke/CO Alarm must have AC or battery power to operate. If AC power fails and the battery is dead or missing, the alarm cannot operate.
• Never disconnect the power from an AC powered unit to stop an unwanted alarm. Doing so will disable the unit and remove your protection. In the case of a true unwanted alarm, use the Silence Feature (if equipped), open a window or fan the smoke away from the unit. The alarm will reset automatically when it returns to normal operation. Never remove the batteries from a battery operated unit to stop an unwanted alarm (caused by cooking smoke, etc.). Instead open a window or fan the smoke away from the unit. The alarm will reset automatically.
“ALARM-MOVE TO FRESH AIR”
I
f you hear the CO alarm horn and the CO red light is flashing,
move everyone to a source of fresh air.
DO NOT remove the batteries!
M08-0121-014_M08-0121-006.E_SC9120A_BA_V5.0 15-10-16 11:24 AM Page 1
Page 2
7 8
Printed in Mexico M08-0121-014 K1 10/15
BRK Electronics®is a registered trademark of BRK Brands, Inc. First Alert
®
is a registered trademark of the First Alert Trust.
9 10 11 12
WEEKLY TESTING
• NEVER use an open flame of any kind to test this unit. You might accidentally damage or set fire to the unit or to your home. The built-in test switch accurately tests the unit’s operation as required by Underwriters Laboratories of Canada
(ULC).
NEVER use vehicle exhaust! Exhaust may
cause permanent damage and voids your warranty.
• DO NOT stand close to the Alarm when the horn is sounding. E
xposure at close range may be harmful to your hearing.
W
hen testing, step away when horn starts sounding.
I
t is important to test this unit every week to make sure it is working
p
roperly. Using the test button is the recommended way to test this
S
moke/CO Alarm.
1
. Push and hold the Test/Silence button on the cover until you hear a
chirp.” The “chirp” marks the start of the self-test sequence.
2. During testing, you will hear a loud, repeating horn pattern: 3 beeps, pause, 3 beeps while the red smoke LED flashes. Then you will hear a loud, repeating horn pattern: 4 beeps, pause, 4 beeps, pause, while the red CO LED flashes.
3
. When testing a series of interconnected units you must test each
u
nit individually. Make sure all units alarm when each one is tested.
I
f the Smoke/CO Alarm does not test properly:
1
. Make sure the AC power is applied and battery is fresh and installed
correctly.
2
. Be sure the alarm is clean and dust-free.
3
. Test the unit again.
4
. If a Latch is set, the first TEST switch activation may be interpreted
a
s a "Clear Latch" signal.
If the Smoke/CO Alarm is still not working properly, replace it immediately. Refer to the “Limited Warranty” at the end of this manual.
I
f there is still a problem, do not try to fix the Alarm yourself.
T
his will void your warranty!
REGULAR MAINTENANCE
U
se only the replacement batteries listed below. The unit may not
o
perate properly with other batteries. Never use rechargeable
b
atteries since they may not provide a constant charge.
This unit has been designed to be as maintenance-free as possible, but there are a few simple things you must do to keep it working properly:
Test it at least once a week.
• Clean the Smoke/CO Alarm at least once a month; gently vacuum the outside of the Smoke/CO Alarm using your household vacuum’s soft brush attachment. Test the Smoke/CO Alarm. Never use water, cleaners or solvents since they may damage the unit.
If the Smoke/CO Alarm becomes contaminated by excessive dirt,
d
ust and/or grime, and cannot be cleaned to avoid unwanted
a
larms, replace the unit immediately.
• Relocate the unit if it sounds frequent unwanted alarms. See “Where This Alarm Should Not Be Installed” for details.
• When the battery back-up becomes weak, the Alarm will “chirp” about once a minute (the low battery warning). This warning should last 7 days, but you should replace the battery immediately to continue your protection. This Alarm must have AC or battery
power to operate. If AC power fails, and the battery is dead or missing, the Alarm cannot operate.
D
O NOT spray cleaning chemicals or insect sprays directly on or near
t
he Alarm. DO NOT paint over the Alarm. Doing so may permanently
d
amage the Alarm.
CHOOSING A REPLACEMENT BATTERY:
This Smoke/CO Alarm requires one standard 9V alkaline battery. The following alkaline batteries are acceptable as replacements: Duracell #MN1604 or MX1604; Eveready “Energizer” 522. You can also use an Ultralife 9V lithium battery #U9VL for longer service life between battery changes. These batteries are available at many local retail stores.
All the batteries specified above are acceptable replacement batteries for this unit. Regardless of the manufacturer’s suggested battery life, you MUST replace the battery immediately once the unit starts “chirp­ing” (the “low battery warning”). For any device employing a battery, constant exposure to high or low humidity may reduce battery life. Actual battery service life depends on the Alarm and the environment in which it is installed. All the batteries specified above are acceptable replacement batteries for this unit. Regardless of the manufacturer ’s suggested battery life, you MUST replace the battery immediately once the unit starts “chirping” (the “low battery warning”).
Always use the exact batteries specified by this User ’s Manual. DO NOT use rechargeable batteries. Clean the battery contacts and also those of the device prior to battery installation. Install batteries correctly with regard to polarity (+ and -). Please dispose of or recycle used batteries properly, following any local regulations. Consult your local waste management authority or recy­cling organization to find an electronics recycling facility in your area. DO NOT DISPOSE OF BATTERIES IN FIRE. BATTERIES MAY EXPLODE OR LEAK.
Keep battery out of reach of children. In the event a battery is swal­lowed, immediately contact your poison control center, your physician, or the Canadian Battery Ingestion hotline at 1-416-813-5900 as seriou s injury may occur.
POTENTIAL SOURCES OF CO IN THE HOME
F
uel-burning appli-
a
nces like: portable
h
eater, gas or wood burn-
i
ng fireplace, gas kitchen r
ange or cooktop, gas
c
lothes dryer.
D
amaged or insufficient
v
enting: corroded or
d
isconnected water
h
eater vent pipe, leaking
c
himney pipe or flue, or
c
racked heat exchanger, blocked or clogged chimney opening.
I
mproper use of appliance/device: operating a barbecue grill or
v
ehicle in an enclosed area (like a garage or screened porch).
Transient CO Problems:“transient” or on-again-off-again CO problems can be caused by outdoor conditions and other special circumstances.
The following conditions can result in transient CO situations:
1. Excessive spillage or reverse venting of fuel appliances caused by outdoor conditions such as:
• Wind direction and/or velocity, including high, gusty winds. Heavy
air in the vent pipes (cold/humid air with extended periods between cycles).
• Negative pressure differential resulting from the use of exhaust f
ans.
• Several appliances running at the same time competing for limited f
resh air.
• Vent pipe connections vibrating loose from clothes dryers, furnaces, or water heaters.
• Obstructions in or unconventional vent pipe designs which can amplify the above situations.
2. Extended operation of unvented fuel burning devices (range, oven,
fireplace).
3. Temperature inversions, which can trap exhaust close to the ground.
4. Car idling in an open or closed attached garage, or near a home.
These conditions are dangerous because they can trap exhaust in your home. Since these conditions can come and go, they are also hard to recreate during a CO investigation.
HOW CAN I PROTECT MY FAMILY FROM CO POISONING?
A CO Alarm is an excellent means of protection. It monitors the air and sounds a loud alarm before Carbon Monoxide levels become threatening for average, healthy adults.
A CO Alarm is not a substitute for proper maintenance of home appliances.
To help prevent CO problems and reduce the risk of CO poisoning:
• Clean chimneys and flues yearly. Keep them free of debris, leaves, and nests for proper air flow. Also, have a professional check for rust and corrosion, cracks, or separations. These conditions can prevent proper air movement and cause backdrafting. Never “cap” or cover a chimney in any way that would block air flow.
• Test and maintain all fuel-burning equipment annually. Many local gas or oil companies and HVAC companies offer appliance inspections for a nominal fee.
• Make regular visual inspections of all fuel-burning appliances. Check appliances for excessive rust and scaling. Also check the flame on the burner and pilot lights. The flame should be blue. A yellow flame means fuel is not being burned completely and CO may be present. Keep the blower door on the furnace closed. Use vents or fans when they are available on all fuel-burning appliances. Make sure appliances are vented to the outside. Do not grill or barbecue indoors, or in garages or on screen porches.
• Check for exhaust backflow from CO sources. Check the draft hood on an operating furnace for a backdraft. Look for cracks on furnace heat exchangers.
• Check the house or garage on the other side of shared wall.
• Keep windows and doors open slightly. If you suspect that CO is escaping into your home, open a window or a door. Opening windows and doors can significantly decrease CO levels.
In addition, familiarize yourself with all enclosed materials. Read this manual in its entirety, and make sure you understand what to do if your CO Alarm sounds.
ABOUT SMOKE ALARMS
Battery (DC) operated Smoke Alarms: Provide protection even when
electricity fails, provided the batteries are fresh and correctly installed. Units are easy to install, and do not require professional installation. However, they do not provide interconnected functionality.
AC powered Smoke Alarms: Can be interconnected so if one unit senses smoke, all units alarm. They do not operate if electricity fails. AC with battery (DC) back-up: will operate if electricity fails, provided the batteries are fresh and correctly installed. AC and AC/DC units must be installed by a qualified electrician.
Wireless Interconnected Alarms: Offer the same interconnected functionality as with hardwired alarms, without wires. Units are easy to install and do not require professional installation. They provide protection even when electricity fails, provided the batteries are fresh and correctly installed.
Smoke Alarms for Solar or Wind Energy users and battery backup power systems: AC powered Smoke Alarms should only be operated
with true or pure sine wave inverters. Operating this Smoke Alarm with most battery-powered UPS (uninterruptible power supply) products or square wave or “quasi sine wave” inverters will damage the Alarm. If you are not sure about your inverter or UPS type, please consult with the manufacturer to verify.
Smoke Alarms for the hearing impaired: Special purpose Smoke Alarms should be installed for the hearing impaired. They include a visual alarm and an audible alarm horn, and meet the requirements of the Americans With Disabilities Act. These units can be interconnected so if one unit senses smoke, all units alarm.
Smoke alarms are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
All these Smoke Alarms are designed to provide early warning of fires if located, installed and cared for as described in the user’s manual, and if smoke reaches the Alarm. If you are unsure which type of unit to install, refer to NFPA (National Fire Protection Association) 72 (National Fire Alarm Code) and NFPA 101 (Life Safety Code). National Fire Protection Association, One Batterymarch Park, Quincy, MA 02269-9101 U.S.A. Local building codes may also require specific units in new construction or in different areas of the home.
SPECIAL COMPLIANCE CONSIDERATIONS
This unit alone is not a suitable substitute for complete fire detection systems in places housing many people—like apartment buildings, condominiums, hotels, motels, dormitories, hospitals, long-term health care facilities, nursing homes, day care facilities, or group homes of any kind—even if they were once single-family homes. It is not a suitable substitute for complete fire detection systems in warehouses, industrial facilities, commercial buildings, and special-purpose non-residential buildings which require special fire detection and alarm systems. Depending on the building codes in your area, this unit may be used to provide additional protection in these facilities.
The following information applies to all four types of buildings listed below:
I
n new construction, most building codes require the use of AC or
A
C/DC powered Smoke Alarms only. AC, AC/DC, or DC powered
S
moke Alarms can be used in existing construction as specified by local
b
uilding codes. Refer to NFPA 72 (National Fire Alarm Code) and NFPA
1
01 (Life Safety Code), local building codes, or consult your Fire
D
epartment for detailed fire protection requirements in buildings not
d
efined as “households.”
1. Single-Family Residence:
Single family home, townhouse. It is recommended this unit be installed on every level of the home, in every bedroom, and in each bedroom hallway.
2. Multi-Family or Mixed Occupant Residence:
Apartment building, condominium. This unit is suitable for use in individual apartments or condos, provided a primary fire detection system already exists to meet fire detection requirements in common areas like lobbies, hallways, or porches. Using this unit in common areas may not provide sufficient warning to all residents or meet local fire protection ordinances/ regulations.
3. Institutions:
H
ospitals, day care facilities, long-term health care facilities. This unit is
s
uitable for use in individual patient sleeping/resident rooms, provided a
p
rimary fire detection system already exists to meet fire detection
r
equirements in common areas like lobbies, hallways, or porches.
U
sing this unit in common areas may not provide sufficient warning
t
o all residents or meet local fire protection ordinances/regulations.
4
. Hotels and Motels:
A
lso boarding houses and dormitories. This unit is suitable for use inside
i
ndividual sleeping/resident rooms, provided a primary fire detection sys-
t
em already exists to meet fire detection requirements in common areas
l
ike lobbies, hallways, or porches. Using this unit in common areas may
n
ot provide sufficient warning to all residents or meet local fire protec-
t
ion ordinances/regulations.
GENERAL LIMITATIONS OF SMOKE/CO ALARMS
L
IMITED WARRANTY
B
RK Brands, Inc., ("BRK") the maker of BRK
®
b
rand and First Alert
®
b
rand products, warrants that for a period of ten years from the date of purchase,
t
his product will be free from defects in material and workmanship. BRK, at its option, will repair or replace this product or any component of the product f
ound to be defective during the warranty period. Replacement will be made with a new or remanufactured product or comp onent. If the product is no l
onger available, replacement may be made with a similar product of equal or greater value. This is your exclusive warranty.
T
his warranty is valid for the original retail purchaser from the date of initial retail purchase and is not transferable. Keep the original sales receipt.
P
roof of purchase is required to obtain warranty performance. BRK dealers, service centers, or retail stores selling BRK products do not have the right to
a
lter, modify or any way change the terms and conditions of this warranty.
This warranty does not cover normal wear of parts or damage resulting from any of the following: negligent use or misuse of the product, use on improper voltage or current, use contrary to the operating instructions, disassembly, repair or alteration by anyone other than BRK or an authorized service center. Further, the warranty does not cover Acts of God, such as fire, flood, hurricanes and tornadoes or any batteries that are included with this unit.
B
RK shall not be liable for any incidental or consequential damages caused by the breach of any express or impl ied warranty. Except to the extent
p
rohibited by applicable law, any implied warranty of merchantability or fitness for a particular purpose is limited in duration to the duration of the above
w
arranty. Some states, provinces or jurisdictions do not allow the exclusion or limitation of incidental or consequential damages or limitations on how long an
i
mplied warranty lasts, so the above limitations or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights that vary from state to state or province to province.
How to Obtain Warranty Service
Service: If service is required, do not return the product to your retailer. In order to obtain warranty service, contact the Consumer Affairs Division at
1-800-323-9005, 7:30 AM - 5:00 PM Central Standard Time, Monday through Friday. To assist us in serving you, please have the model number and date of purchase available when calling.
For Warranty Service return to: BRK Brands, Inc., 1301 Joe Battle, El Paso, TX 79936 U.S.A.
B
attery: BRK Brands, Inc. make no warranty, express or implied, written or oral, including that of merchantability or fitness for any particular purpose
w
ith respect to battery.
O
nce a minute, the alarm sounds 3 “chirps”, and
t
he green light flashes quickly three times.
M
ALFUNCTION SIGNAL. Unit needs to be
r
eplaced. Based on self-diagnostic tests, the unit
h
as detected a fault.
U
nits under warranty should be returned to
m
anufacturer for replacement. See “Limited
W
arranty” for details.
The light flashes (GREEN) and the horn sounds 3
“chirps” every minute.
END OF LIFE SIGNAL.
C
O Alarm needs to be replaced.
Immediately replace the CO Alarm.
Horn "chirps" about once per minute; Green "Power/Smoke" LED flashes Green On for 2 seconds/Off for 2 seconds. (Low Battery Latch is engaged.)
Low battery warning. Battery is low or missing. Replace the battery, avoid interrupting AC
power.
I
f your Alarm does this... It means... You should...
Green Power/Smoke LED is OFF. Unit will not alarm when you press the Test/Silence button.
Unit may not be receiving any power.
Check the AC power supply. Make sure the power connector is securely attached to the alarm. Make sure a fresh 9V battery is installed to power the battery back-up*.
Green light flashes ON, once a minute (horn is silent).
Alarm is not receiving AC power.
Unit is operating on battery back-up. Check the AC power supply.
TROUBLESHOOTING GUIDE
Alarm goes back into alarm after you pressed the Test/Silence button to silence an alarm.
Smoke and/or CO levels are still potentially dangerous.
Refer to “If Your Smoke/CO Alarm Sounds” for details on how to respond to an alarm. If anyone is feeling ill, EVACUATE your home immediately and call 911.
If you have any questions that cannot be answered by reading this manual, call Consumer Affairs: 1-800-323-9005.
*For a list of acceptable replacement batteries, see “Regular Maintenance.”
A
larm sounds frequently even though no high
l
evels of smoke or CO are revealed in an i
nvestigation.
T
he Alarm may be improperly located. Refer to
Where to Install This Alarm.”
R
elocate your alarm. If frequent alarms continue,
h
ave home rechecked for potential problems.
Y
ou may be experiencing an intermittent smoke
o
r CO problem.
E
LECTRICAL SHOCK HAZARD. Turn off the power to the area where the Alarm is installed BEFORE removing it from the mounting bracket or
c
hecking any electrical connections! Failure to turn off the power first may result in serious electrical shock, injury or death.
F
or your records, please record:
D
ate Purchased: _______________________________
Where Purchased: __________________________________________
D
ate Installed: ____________/____________Month/Year
R
eplace alarm 10 years after installation since the alarm may no longer accurately detect carbon monoxide. Please write the date in the space provided:
_
____________/____________Month/Year
The alarm will also provide an audible End-of-Life Signal approximately 10 years after installation to remind you to replace the unit.
The End-of-Life Signal can be silenced for up to 2 days. Do not unplug the alarm or remove the batteries until you get replacement.
T
his Smoke/CO Alarm is intended for residential use. It is not intended
f
or use in industrial applications where Occupational Safety and Health
A
dministration (OSHA) requirements for Carbon Monoxide Alarms must
b
e met. The Smoke Alarm portion of this device is not intended to alert
h
earing impaired residents. Special purpose Smoke Alarms should be
i
nstalled for hearing impaired residents (CO Alarms are not yet available
f
or the hearing impaired).
S
moke/CO Alarms may not waken all individuals. Practice the
e
scape plan at least twice a year, making sure that everyone is involved
from kids to grandparents. Allow children to master fire escape
p
lanning and practice before holding a fire drill at night when they are
s
leeping. If children or others do not readily waken to the sound of the
S
moke/CO Alarm, or if there are infants or family members with mobility
l
imitations, make sure that someone is assigned to assist them in fire
d
rill and in the event of an emergency. It is recommended that you hold
a
fire drill while family members are sleeping in order to determine their
r
esponse to the sound of the Smoke/CO Alarm while sleeping and
t
o determine whether they may need assistance in the event of an
e
mergency.
S
moke/COAlarms cannot work without power.Battery operated units
c
annot work if the batteries are missing, disconnected or dead, if the wrong
t
ype of batteries are used, or if the batteries are not installed correctly.
A
C units cannot work if the AC power is cut off for any reason (open fuse
o
r circuit breaker, failure along a power line or at a power station, electrical
f
ire that burns the electrical wires, etc.). If you are concerned about the
l
imitations of battery or AC power, install both types of units.
This Smoke/CO Alarm will not sense smoke or CO that does not reach the sensors. It will only sense smoke or CO at the sensor. Smoke
or CO may be present in other areas. Doors or other obstructions may affect the rate at which CO or smoke reaches the sensors. If bedroom doors are usually closed at night, we recommend you install an alarm device (Combination CO and Smoke Alarm, or separate CO Alarms and Smoke Alarms) in each bedroom and in the hallway between them.
This Smoke/CO Alarm may not sense smoke or CO on another level of the home. Example: This alarm device, installed on the second
floor, may not sense smoke or CO in the basement. For this reason, one alarm device may not give adequate early warning. Recommended minimum protection is one alarm device in every sleeping area, every bedroom, and on every level of your home. Some experts recommend battery powered Smoke and CO Alarms be used in conjunction with interconnected AC powered Smoke Alarms. For details, see “About Smoke Alarms” for details.
This carbon monoxide alarming device is designed to detect car­bon monoxide gas from ANY source of combustion. It is NOT designed
to detect smoke, fire, or any other gases.
S
moke/CO Alarms may not be heard. The alarm horn loudness
m
eets or exceeds current standards of 85 dB at 3 meters (10 feet).
H
owever, if the Smoke/CO Alarm is installed outside the bedroom, it
m
ay not wake up a sound sleeper or one who has recently used drugs or has been drinking alcoholic beverages. This is especially true if the door is closed or only partly open. Even persons who are awake may not hear the alarm horn if the sound is blocked by distance or closed doors. Noise from traffic, stereo, radio, television, air conditioner, or other appliances may also prevent alert persons from hearing the alarm horn. This Smoke/CO Alarm is not intended for people who are hearing impaired.
The Alarm may not have time to alarm before the fire itself causes damage, injury, or death, since smoke from some fires may not reach the unit immediately. Examples of this include persons smoking in bed, children playing with matches, or fires caused by violent explosions resulting from escaping gas.
This Smoke/CO Alarm is not a substitute for life insurance.
Though this Smoke/CO Alarm warns against increasing CO levels or the presence of smoke, BRK Brands, Inc. does not warrant or imply in any way that they will protect lives. Homeowners and renters must still insure their lives.
This Smoke/CO Alarm has a limited life. Although this Smoke/CO Alarm and all of its parts have passed many stringent tests and are designed to be as reliable as possible, any of these parts could fail at any time. Therefore, you must test this device weekly. The unit should be replaced immediately if it is not operating properly.
This Smoke/CO Alarm is not foolproof. Like all other electronic devices, this Smoke/CO Alarm has limitations. It can only detect smoke or CO that reaches the sensors. It may not give early warning of the source of smoke or CO is in a remote part of the home, away from the alarm device.
LATCHING FEATURES
A
larm Latch is activated after an Alarm is exposed to alarm levels of
s
moke or carbon monoxide. After smoke or CO levels drop below alarm
l
evels, the “Smoke/Power” or “CO” Red LED will begin to flash On 2 s
econds/Off 2 seconds. It will continue to flash or “latch” until you clear
i
t by testing the alarm. T
his feature helps emergency responders, investigators, or service
t
echnicians identify which unit(s) in your home were exposed to alarm
l
evels of smoke or carbon monoxide. This can help investigators p
inpoint the source of smoke or CO.
I
nterconnected Alarms. Latching Alarm Indicator shows which Alarm(s)
i
n the series were exposed to alarm levels of smoke or carbon monoxide. T
he Latching Alarm Indicator stays ON until you clear it, so it can alert
y
ou to an alarm that occurred while you were away from home, even
t
hough smoke or CO present in the air has dropped below alarm levels.
Low Battery Latch is activated when the Alarm is in the "low battery condition". When this occurs, the Smoke/Power LED flashes Green On for 2 seconds/Off for 2 seconds. This feature is designed to help you identify which Alarm needs to have the battery replaced. Although, the Alarm will sound the low battery chirp approximately once every minute, sometimes during the initial stages of "low battery", the Alarm will chirp in greater intervals than one minute, sometimes up to several hours, until the battery reaches a steady low battery level. This innovative feature eliminates the frustration of waiting for and/or identifying which unit is chirping.
Latching Features Note: Without AC Power and running on battery only, Low Battery Latch or Alarm Latch are only engaged for about 15 minutes to conserve power. Low Battery Latch and Alarm Latch do not operate with a missing battery and no AC Power.
I
F YOUR SMOKE/CO ALARM SOUNDS, Continued
WHAT YOU NEED TO KNOW ABOUT CO
WHAT IS CO?
CO is an invisible, odorless, tasteless gas produced when fossil fuels do not burn completely, or are exposed to heat (usually fire). Electrical appliances typically do not produce CO.
These fuels include: Wood, coal, charcoal, oil, natural gas, gasoline, kerosene, and propane.
C
ommon appliances are often sources of CO. If they are not properly
m
aintained, are improperly ventilated, or malfunction, CO levels can rise
q
uickly. CO is a real danger now that homes are more energy efficient.
Air-tight” homes with added insulation, sealed windows, and other
w
eatherproofing can “trap” CO inside.
SYMPTOMS OF CO POISONING
The following symptoms may be related to CARBON MONOXIDE POISONING and should be discussed with ALL members of the household:
Mild Exposure: Headaches, running nose, sore eyes, often described as “flu”-like symptoms.
Medium Exposure: Dizziness, drowsiness, vomiting. Extreme Exposure: Unconsciousness, brain damage, death.
Many cases of reported CARBON MONOXIDE POISONING indicate that while victims are aware they are not well, they become so disoriented they are unable to save themselves by either exiting the building or calling for assistance.
T
his CO Alarm measures exposure to CO over time. It alarms if CO
l
evels are extremely high in a short period of time, or if CO levels reach a
certain minimum over a long period of time. The CO Alarm generally
s
ounds an alarm before the onset of symptoms in average, healthy
a
dults.
W
hy is this important? Because you need to be warned of a potential
C
O problem while you can still react in time. In many reported cases of
C
O exposure, victims may be aware that they are not feeling well, but
b
ecome disoriented and can no longer react well enough to exit the
b
uilding or get help. Also, young children and pets may be the first
a
ffected. The average healthy adult might not feel any symptoms when
t
he CO Alarm sounds. However, people with cardiac or respiratory
p
roblems, infants, unborn babies, pregnant mothers, or elderly people
c
an be more quickly and severely affected by CO. If you experience
e
ven mild symptoms of CO poisoning, consult your doctor immediately!
This device is designed to protect individuals from the acute effects of carbon monoxide exposure. It will not fully safeguard individuals with specific medical conditions. If in doubt consult a medical practitioner.
FINDING THE SOURCE OF CO AFTER AN ALARM
C
arbon monoxide is an odorless, invisible gas, which often makes it
d
ifficult to locate the source of CO after an alarm. These are a few of
t
he factors that can make it difficult to locate sources of CO:
• House well ventilated before the investigator arrives.
• Problem caused by “backdrafting.”
• Transient CO problem caused by special circumstances.
B
ecause CO may dissipate by the time an investigator arrives, it may
b
e difficult to locate the source of CO. BRK Brands, Inc. shall not be
o
bligated to pay for any carbon monoxide investigation or service
c
all.
REGULATORY INFORMATION FOR SMOKE/CO A
LARMS
R
EGULATORYINFORMATION FOR CO ALARMS
CANADIAN STANDARDS ASSOCIATION What Levels of CO Cause an Alarm?
CSA 6.19 requires residential CO Alarms to sound when exposed to levels of CO and exposure times as described below. They are measured in parts per million (ppm) of CO over time (in minutes).
C
SA 6.19 Required Alarm Points*:
• If the alarm is exposed to 400 ppm of CO, IT MUST ALARM BETWEEN 4 and 15 MINUTES.
• If the alarm is exposed to 150 ppm of CO, IT MUST ALARM B
ETWEEN 10 and 50 MINUTES.
• If the alarm is exposed to 70 ppm if CO, IT MUST ALARM BETWEEN 60 and 240 MINUTES.
*Approximately 10% COHb exposure at levels of 10% to 95% Relative Humidity (RH).
T
he unit is designed not to alarm when exposed to a constant level
o
f 30 ppm for 30 days.
C
O Alarms are designed to alarm before there is an immediate life threat.
S
ince you cannot see or smell CO, never assume it’s not present.
• An exposure to 100 ppm of CO for 20 minutes may not affect
average, healthy adults, but after 4 hours the same level may cause headaches.
• An exposure to 400 ppm of CO may cause headaches in average,
healthy adults after 35 minutes, but can cause death after 2 hours.
Standards: CSA 6.19
Audible Alarm: 85 dB minimum at 3 meters (10 feet).
R
ECOMMENDED LOCATIONS FOR SMOKE ALARMS
I
nstalling Smoke Alarms in Single-Family Residences
The National Fire Protection Association (NFPA), recommends one Smoke Alarm on every floor, in every sleeping area, and in every bed­room. In new construction, the Smoke Alarms must be AC powered and interconnected. See “Agency Placement Recommendations” for details. F
or additional coverage, it is recommended that you install a Smoke
A
larm in all rooms, halls, storage areas, finished attics, and basements,
w
here temperatures normally remain between 4
o
C
(40
o
F
) and 38
o
C
(
100
o
F
). Make sure no door or other obstruction could keep smoke from
r
eaching the Smoke Alarms.
M
ore specifically, install Smoke Alarms:
On every level of your home, including finished attics and basements.
Inside every bedroom, especially if people sleep with the door partly
o
r completely closed.
In the hall near every sleeping area. If your home has multiple
s
leeping areas, install a unit in each. If a hall is more than 12 meters
(
40 feet long), install a unit at each end.
• At the top of the first-to-second floor stairway, and at the bottom of
the basement stairway.
Specific requirements for Smoke Alarm installation vary from state to state and from region to region. Check with your local Fire Department for current requirements in your area. It is recommended AC or AC/DC
units be interconnected for added protection.
AGENCY PLACEMENT RECOMMENDATIONS
NFPA 72 (National Fire Code) Chapter 11
For your information, the National Fire Protection Association's
S
tandard 72, reads as follows:”
11.5.1 One- and Two-Family Dwelling Units.”
“11.5.1.1 Smoke Detection. Where required by applicable laws, codes,
or standards for the specified occupancy, approved single- and multiple­station Smoke Alarms shall be installed as follows: (1) In all sleeping rooms. Exception: Smoke Alarms shall not be required in sleeping rooms in existing one- and two-family dwelling units. (2) Outside of each separate sleeping area, in immediate vicinity of the sleeping rooms. (3) On each level of the dwelling unit, including basements. Exception: In existing one- and two family dwelling units, approved Smoke Alarms powered by batteries are permitted.”
“A.11.8.3 Are More Smoke Alarms Desirable?
The required number of Smoke Alarms might not provide reliable early warning protection for those areas separated by a door from the areas protected by the required Smoke Alarms. For this reason, it is recom­mended that the householder consider the use of additional Smoke Alarms for those areas for increased protection. The additional areas include the basement, bedrooms, dining room, furnace room, utility room, and hallways not protected by the required Smoke Alarms. The installation of Smoke Alarms in kitchens, attics (finished or unfinished), or garages is not normally recommended, as these locations occasionally experience conditions that can result in improper operation.”
M08-0121-014_M08-0121-006.E_SC9120A_BA_V5.0 15-10-16 11:24 AM Page 2
Loading...