Smoke
Listed to
Standard
UL 217
AlArm
CAT.
FG225B/FG250B
DUAl IoNIZATIoN
Dual Ionization sensing chamber.
Generally more effective at
detecting small particles produced
by flaming fires. Sources may
include paper or kitchen grease.
SIleNCe FeATUre
(FG250 only) Silences nuisance alarms.
HINGeD CoVer
DeSIGN
Fast and easy installation
and battery replacement
9V Battery Powered
Description:
BRK Models FG225 and FG250 are single station smoke alarms specifically designed
for residential and institutional applications including sleeping rooms of hospitals,
hotels, motels, dormitories, and other multifamily dwellings as defined in standard NFPA
101. Models FG225 and FG250 have been fully tested and comply with, UL217, CSFM,
NFPA 72, and NFPA 101 and other agencies that model their codes after the above
agencies. They meet building codes where DC (FG225) and DC with Silence (FG250) smoke
alarms are required and with model building codes published by the ICC.
BRK Models FG225 and FG250 are state of the art smoke alarms designed to provide
early warning of a fire. They feature a fully insect screened dual ionization smoke
sensing chamber, an 85dB horn, a supervised 9V battery power supply, a full function
test switch, a silence feature (FG250 only) to silence unwanted nuisance alarms, a
red LED light that indicates DC power or alarm. Each also feature a tamper resistant
locking pin that locks alarm cover to prevent removal of battery. Perfect for apartment,
dormitory or hotel applications. The compact, low profile design complements any
décor. Battery installation and removal can occur while the unit is mounted to the
ceiling or wall via the hinged cover. When voltage drops to a pre-set warning level, the
horn will “chirp” approximately once per minute to indicate a fresh battery is needed.
To insure the battery is always replaced properly, the cover is designed to resist closing
when the battery is missing. Designed for wall or ceiling mounting. Includes mounting
anchors and screws. Both models are approved for use in recreational vehicles.
TAmPer reSISTANT
loCkING PIN
Locks alarm cover to prevent
removal of battery. Perfect for
apartment, dormitory or hotel
applications.
9V BATTerY
INClUDeD
APProVeD For
rV USe
Available in the following versions:
FG225B Carbon Zinc Battery
FG250B Silence with Carbon Zinc Battery
FG250AB Silence with Alkaline Battery
FG250LB Silence with Lithium Battery
CAT.
4.25”
FRONT
VIEW
SIDE
VIEW
Back
View
1.6”
FG225B/FG250B
ARCHITECTURAL AND ENGINEERING SPEC
1. A dual ionization sensing chamber.
2. The unit shall be capable of self restoring.
3. A fully screened sensing chamber to resist entry of small insects
thereby reducing the probability of unwanted alarms.
4. Powered by a supervised 9V battery and a solid state piezo horn
rated at 85dB at 10 ft.
5. A visual LED power-on indicator to confirm unit is receiving power or
is in alarm.
6. A full function test button. The test button should check all alarm
functions by stimulating the chamber to simulate a smoke condition,
causing the unit to alarm. Model FG250 also has a silence feature to silence
unwanted nuisance alarms.
7. A tamper resistant locking pin that locks alarm cover to prevent removal
of battery.
8. The unit shall be capable of operating between 40°F (4°C) and
100°F (38°C) and relative humidity between 10% and 90%.
9. The unit shall contain mounting hardware and shall be listed for wall
or ceiling mounting.
10. The unit shall at a minimum meet the requirements of UL217, CSFM,
NFPA 72, NFPA 101, ICC.
11. The unit shall be suitable for use in Recreational Vehicles.
INSTALLATION OF ALARM
Installation of this smoke alarm must conform to NFPA 72. Always check
your local building codes. Follow all instructions for placement as outlined
in the user’s manual in sections titled “Recommended Locations for
Smoke Alarms” and “Locations to Avoid for Smoke Alarms”.
1
TECHNICAL SPECS:
Alarm Dimensions: 4.25” dia x 1.6”H
Weight: 4.8 oz.
Operating Voltage: 9V Battery Powered
Temperature Range: 40˚F (4˚C) to 100˚F (38˚C)
Humidity Range: 10% to 95% relative humidity (RH)
Audio Alarm: 85dB at 10 feet
Test/Silence:
(FG250)
Alarm Reset: Automatic when smoke clears
Smoke Sensor: Dual Ionization
Indicator Lights:
DC Power: Intermittent Red Light
Listing ETL to UL217 Standard
Electronically simulates smoke condition, causing
the unit to alarm
SHIPPING SPECS:
Individual Carton Dimensions
Weight
Cube .02 ft3
UPC FG225B: 0 29054 00303 4
Master Carton Dimensions 9.2 ”L x 5.5”W x 5.1”H
Master Pack 6
Weight
Cube .15 ft3
I2 of 5 FG225B: 600 29054 00303 6
Pallet Information
Cases per Layer 36
Number of Layers 9
Cases per Pallet 324
Units per Pallet 1,944
Cube 55.0 ft3
Weight 1,107lbs.
4.38 ”L x 1.75”W x 4.38”H
.67lbs.
FG250B: 0 29054 00300 3
FG250AB: 0 29054 00311 9
FG250LB: 0 29054 00310 2
3.2 lbs.
FG250B: 600 29054 00300 5
FG250AB: 600 29054 00311 1
FG250LB: 600 29054 00310 4
2
The parts of this smoke alarm
1. “Open Here”
3
4
6
5
7
2. “No Battery” tab
3. Test button or
Test/Silence button (FG250 only)
4. Smoke alarm base
5. Mounting slots
6. Install 9V battery here
7. Locking pin slot
8. Locking pin: Remove and insert in 7
brkelectronics.com
8
©2008 BRK Brands, Inc. a Jarden Corporation
company (NYSE: JAH)
3901 Liberty Street Road
Aurora IL 60504-8122
All rights reserved
BRK is a registered trademark of BRK
Brands,Inc.
CM2885
7