INSTALLATION OF THE
ADF ADAPTER PLUG
ELECTRICAL SHOCK HAZARD. T
will install this unit at the cir
installation. Failure to turn off the power before installation may result in
serious electrical shock, injury or death. Do not restore power until all
Smoke Alar
For all other Smoke Alarm information, instructions and warnings, refer
to the Smoke Alarm User’s Manual.
ms are completely installed.
•
Installation of this unit must conform to the electrical codes in your
ea; Article 760 of NFPA 70 (NEC), NFPA 72, NFPA 101; SBC (SBCCI);
ar
UBC (ICBO); NBC (BOCA); OTFDC (CABO), and any other local or
building codes that may apply. Wiring and installation must be performed by a licensed electrician. Failure to follow these guidelines
esult in injury or property damage.
may r
•
This unit must be powered by a 24-hour, 120VAC
cuit. Be sure the circuit cannot be turned off by a switch, dimmer,
cir
ound fault circuit interrupter. Failure to connect this unit to a
or gr
24-hour circuit may prevent it from providing constant protection.
urn off power to the area where you
cuit breaker or fuse box before beginning
pure sine wave
60Hz
COMPATIBLE BRK®MODELS
®
All of the listed BRK®and First Aler
FIREX®Alarms and will work with the enclosed Adapter Plugs.
t
e compatible with the listed
Alarms ar
BRK®Alarms
4120, 9120 Series – AC, AC/DC Ion, Silence
5919 – AC Photo
2002RAC – AC/DC Photo
7010 Series – AC, AC/DC Photo, Silence
SC6120B, SC9120B – AC/DC Smoke/CO Combo
HD6135FB – Heat Alarm
RM3 – Auxiliary Relay
®
FIREX
406 (Model #G-6) – AC Ion
4518 (Model #ADC) – AC/DC Ion, Battery in Rear
4618 (Model #FADC) – AC/DC Ion
5000 (Model #FADC) – AC/DC Ion, Latching LED
484 (Model #PG-40) – AC Photo
4480 (Model #PAD) – AC/DC Photo
5700 (Model #ADH) – Heat Alarm
499 – Auxiliary Relay
Maximum of only 12 units (except model G-6) may be interconnected.
•
Check for model numbers above.
Adapter Plug (ADF) Diagram for FIREX®Models:
Plug Pin
iew
V
NOTE: T
Side View
wist tie should not be r
emoved.
White
Orange
Black
INSTALLATION INSTRUCTIONS
erify which
1. V
compatible with the ADF Adapter Plug (see part C below).
urn off AC power.
2. T
MODELS ar
3. Remove unit. Remove old mounting bracket.
4. Install new mounting bracket (see part A below).
5. Connect the black end of the ADF Adapter Plug to the existing power
connector (connect part C to part D as shown below).
NOTE: There may not be enough room for the Adapter Plug and additional
wiring to fit in the junction box. If not, the old power connector must be
emoved and r
r
6.
Connect the other end of the Adapter Plug to the appr
(connect part C to part B as shown below).
7. Check all connections. Make sure all plugs are completely connected and
snapped together
existing Power Connector
eplaced with a First Alert
8. Install the base of the Smoke Alarm to the mounting bracket.
9. Restore power to the junction box.
10. Test each Smoke Alarm. Press and hold the test button until the unit alarms.
When testing a series of interconnected units you must test each unit
individually. Make sure all units alarm when each one is tested.
e installed in your system to determine if they are
®
Power Connector
.
opriate Smoke Alarm
. Ensure the Adapter Plug is securely connected to the
.
The Parts of This Installation
A Mounting Bracket
B
BRK® 4120, 9120 Series
Smoke Alarm
C ADF Adapter
D Existing compatible
power connector
Electrical Rating:
120V AC, 100mA Maximum
Not for Current Interruption
NOTE: ADAPTER PLUG CANNOT BE USED TO CONNECT
MONOXIDE ALARMS.
THE ABOVE MODELS OF FIREX
INTERCONNECTED USING ONE OF THE ADAPTER PLUGS INCLUDED.
IF THE MODEL IS NOT LISTED, IT MUST BE REMOVED FROM THE SYSTEM.
®
ARE THE ONLY MODELS THAT MAY BE
FIREX® CARBON
NOTE:
TIBLE POWER CONNECTORS:
A
INCOMP
DO NOT A
TTEMPT
INSTALLATION
FIREX
NOTE: Adapter Plug can be used on FIREX® Models manufactured on or
before January 1, 2004.
Independent evaluation of the
Adapter Plug and inter
compatibility was performed by
Intertek, a division of ETL SEMKO.
connect
RECOGNIZED
COMPONENT
CONFORMS TO
ANDARD 1977
UL ST
3055574
®
© 2007 BRK Brands, Inc., a Jarden Corporation company (NYSE: JAH)
3901 Liberty Street Road, Aurora, IL 60504-8122
All rights reserved.
Consumer Af
US Patent No.: 6,641,433 B2
BRK
First Alert
Firex
fairs: (800) 323-9005 • www
®
is a registered trademark of BRK Brands, Inc.
®
is a registered trademark of the First Alert Trust.
®
is a registered trademark of Maple Chase Company.
.firstalert.com • www
.brkelectronics.com
Printed in Mexico M08-0125-001 H 06/07