BRK electronic CO511 User Manual

GARAGE
SUGGESTED AREAS FOR INSTALLING ADDITIONAL CO ALARMS
B
EDROOM
BEDROOM
HALL
L
IVING ROOM
KITCHEN
BASEMENT
BEDROOM
REQUIRED TO MEET NFPA RECOMMENDATIONS
GULAR MAINTENANCE
A
B
RE
This unit has been designed to be as maintenance-free as possible, but there
e a few simple things you must do to keep it working properly.
ar
se only the replacement batteries listed below. The unit may not
U operate properly with other batteries. Never use rechargeable batteries since they may not provide a constant charge.
Test it at least once a week.
• Clean the CO Alarm at least once a month; gently vacuum the outside f the CO Alarm using your household vacuum’s soft brush attachment.
o
can of clean compressed air (sold at computer or office supply stores)
A may also be used. Follow manufacturer instructions for use. Test the CO
. Never use water, cleaners or solvents since they may damage the
Alarm
nit.
u If the CO Alarm becomes contaminated by excessive dirt, dust and/or
ime, and cannot be cleaned to avoid unwanted alarms, replace the unit
gr immediately.
Relocate the unit if it sounds frequent unwanted alarms. See “Where CO
Alarms Shou
oosing a replacement battery:
Ch
our CO Alarm requires two standard AA batteries. The following batteries are
Y acceptable as replacements: Energizer E91.
y local retail stores.
man
ual battery service life depends on the CO Alarm and the environment in
Act which it is installed. All the batteries specified above are acceptable replace-
nt batteries for this unit. Regardless of the manufacturer’s suggested
me
attery life, you MUST replace the battery immediately once the unit starts
b “chirping” (the “low battery warning”).
To replace the batteries (without removing Alarm from the ceiling or wall):
. Open the battery compartment.
1
2. Press tabs A and B as shown in the
diagram and remove each battery.
. Insert the new batteries, making sure
3
hey snap completely into the battery
t compartment. Match the terminals on
he ends of the batteries with the
t
erminals on the unit.
t
4. Close the battery compartment, and
hen test the unit by pressing the
t
st/Silence button.
e
T
ld Not Be Installed” for details.
These batteries are available at
WHAT YOU NEED TO KNOW ABOUT CO
WHAT IS CO?
O is an invisible, odorless, tasteless gas produced when fossil fuels do not
C burn completely, or are exposed to heat (usually fire). Electrical appliances typically do not produce CO.
These fuels include: Wood, coal, charcoal, oil, natural gas, gasoline, kerosene,
nd propane.
a
mon appliances are often sources of CO. If they are not properly main-
Com
ained, are improperly ventilated, or malfunction, CO levels can rise quickly. CO
t
eal danger now that homes are more energy efficient. “Air-tight” homes
is a r
ith added insulation, sealed windows, and other weatherproofing can “trap”
w
O inside.
C
SYMPTOMS OF CO POISONING
These symptoms are related to CO POISONING and should be discussed
ith ALL household members.
w
ild Exposure:Slight headache, nausea, vomiting, fatigue (“flu-like”
M
ptoms).
m
y
s
edium Exposure:Throbbing headache, drowsiness, confusion, fast heart
M
ate.
r
posure:
treme Ex
Ex
Exposure to Carbon Monoxide can cause brain damage, death.
ndividuals are more sensitive to CO than others, including people
Some i
ith cardiac or respiratory problems, infants, unborn babies, pregnant
w m C adv
or elderly people can be m
s,
ther
o
Members of sensitive populations should consult their doctors for
.
O
ice on taking additional precautions.
FINDING THE SOURCE OF CO AFTER AN ALARM
Carbon monoxide is an odorless, invisible gas, which often makes it difficult to
he source of CO after an alarm. These are a few of the factors that can
e t
t
oca
l make it difficult to locate sources of CO:
• House well ventilated before the investigator arrives. m ca
le
ob
r
• P
t CO problem caused by special circumstances.
n
nsie
a
r
T
cause CO may dissipate by the time an investigator arrives, it may be
Be
ifficult to locate the source of CO.
d
or any carbon monoxide investigation or service call.
y f
a
o p
t
POTENTIAL SOURCES OF CO IN THE HOME
g appl
uel-burni
F
gas kitchen range or cooktop, gas clothes dryer.
D
ent pipe, leaking chimney pipe or flue, or cracked heat exchanger, blocked
v or clogged chimney opening.
Improper use of appliance/ device: operating a barbecue grill or vehicle in
n e
a Transient CO Problems: “transient” or on-again-off-again CO problems can
be caused by outdoor conditions and other special circumstances.
The following conditions can result in transient CO situations:
1. Excessive spillage or reverse venting of fuel appliances caused by outdoor
2. Extended operation of unvented fuel burning devices (range, oven,
3. Temperature inversions, which can trap exhaust close to the ground. .
4 These conditions are dangerous because they can trap exhaust in your home.
Si a CO investigation.
n
nsu
ged or i
ama
ea (l
d ar
ose
ncl
itions such as:
cond
Wind direction and/or velocity, including high, gusty winds. Heavy air in
• the vent pipes (cold/humid air with extended periods between cycles).
• Negative pressure differential resulting from the use of exhaust fans. Several appliances running at the same time competing for limited
• fresh air.
ent pipe connections vibrating loose from clothes dryers, furnaces,
V
• Obstructions in or unconventional vent pipe designs which can amplify
fireplace).
Car idling in an open or closed attached garage, or near a home.
nce t
r heaters.
e
t
a
or w
bove situations.
he a
t
se cond
he
ulsions, unconsciousness, heart and lung failure.
v
Con
ly and s
ck
ui
ore q
“backdrafting.”
y
d b
use
RK Brands, Inc. shall not be obligated
B
iances like:
t venting:
cien
fi
f
e a gar
k
i
ions ca
it
age or screened porch).
n come a
le heater, gas or wood burning fireplace,
b
a
t
por
ne
iscon
d or d
e
od
corr
nd go, they are also hard to recreate during
5 6 7
verely affected by
e
ed water heater
ct
EGULATORY INFORMATION FOR CO ALARMS, Continued
W CAN I PROTECT MY FAMILY FROM
HO
O POISONING?
C
CO Alarm is an excellent means of protection. It monitors the air and sounds
A
oud alarm before Carbon Monoxide levels become threatening for average,
a l healthy adults.
CO Alarm is not a substitute for proper maintenance of home
A
iances.
appl
To help prevent CO problems and reduce the risk of CO poisoning:
• Clean chimneys and flues yearly. Keep them free of debris, leaves, and sts for proper air flow.Also, have a professional check for rust and
ne
osion, cracks, or separations. These conditions can prevent proper
corr air movement and cause backdrafting. Never “cap” or cover a chimney
n any way that would block air flow.
i Test and maintain all fuel-burning equipment annually. Many local gas
or oil companies and HVAC companies offer appliance inspections for
inal fee.
a nom Make regular visual inspections of all fuel-burning appliances. Check
appliances for excessive rust and scaling. Also check the flame on the
urner and pilot lights. The flame should be blue. A yellow flame means
b
uel is not being burned completely and CO may be present. Keep the
f blower door on the furnace closed. Use vents or fans when they are
vailable on all fuel-burning appliances. Make sure appliances are
a
ented to the outside. Do not grill or barbecue indoors, or in garages
v or on screen porches.
Check for exhaust backflow from CO sources. Check the draft hood on
an operating furnace for a backdraft. Look for cracks on furnace heat exchangers.
Check the house or garage on the other side of shared wall.
• Keep windows and doors open slightly. If you suspect that CO is
scaping into your home, open a window or a door. Opening windows
e
nd doors can significantly decrease CO levels.
a
In addition, familiarize yourself with all enclosed materials. Read this
l in its entirety, and make sure you understand what to do if your
manua CO Alarm sounds.
GULATORY INFORMATION FOR CO ALARMS
RE
UNDERWRITERS LABORATORIES INC. UL2034
HAT LEVELS OF CO CAUSE AN ALARM?
W
Underwriters Laboratories Inc. Standard UL2034 requires residential CO
o sound when exposed to levels of CO and exposure times as
Alarms t described below. They are measured in parts per million (ppm) of CO over
ime (in minutes).
t
L2034 Required Alarm Points*:
U
• If the alarm is exposed to 400 ppm of CO, IT MUSTALARM BETWEEN 4 and 15 MINUTES.
• If the alarm is exposed to 150 ppm of CO, IT MUST ALARM BETWEEN 10 and 50 MINUTES.
If the alarm is exposed to 70 ppm of CO, IT MUST ALARM BETWEEN
• 60 and 240 MINUTES.
proximately 10% COHb exposure at levels of 10% to 95% Relative
* Ap
umidity (RH).
H
he unit is designed not to alarm when exposed to a constant level of
T 30 ppm for 30 days.
CO Alarms are designed to alarm before there is an immediate life threat.
ou cannot see or smell CO, never assume it’s not present.
nce y
Si
An exposure to 100 ppm of CO for 20 minutes may not affect average,
lt
hea
An exposure to 400 ppm of CO may cause headaches in average, healthy
ults after 35 minutes, but can cause death after 2 hours.
ad
This CO Alarm measures exposure to CO over time. It alarms if CO levels
e extremely high in a short period of time, or if CO levels reach a certain
ar
inimum over a long period of time.The CO Alarm generally sounds an alarm
m before the onset of symptoms in average, healthy adults.
y is t
h
W
oblem while you can still react in time. In many reported cases of CO
pr
posur
x
e oriented and can no longer react well enough to exit the building or get help.
, young children and pets may be the first affected. The average healthy
Also
ig
lt m
u
ad people with cardiac or respiratory problems, infants, unborn babies, pregnant
thers, or elderly people can be more quickly and severely affected by CO.
mo
f you experience even mild symptoms of CO poisoning, consult your doctor
I
iately!
d
me
m
i
, but after 4 hours the same level may cause headaches.
s
lt
u
y ad
h
is important? Because you need to be warned of a potential CO
h
e, victims may be aware that they are not feeling well, but become dis-
t feel any symptoms when the CO Alarm sounds. However,
t no
h
R
Standards: Underwriters Laboratories Inc. Single and Multiple Station carbon
xide alarms UL2034.
mono According to Underwriters Laboratories Inc. UL2034, Section 1-1.2: “Carbon
xide alarms covered by these requirements are intended to respond to
mono
he presence of carbon monoxide from sources such as, but not limited to,
t exhaust from internal-combustion engines, abnormal operation of fuel-fired
ppliances, and fireplaces. CO Alarms are intended to alarm at carbon
a
xide levels below those that could cause a loss of ability to react to the
mono dangers of Carbon Monoxide exposure.” This CO Alarm monitors the air at the
, and is designed to alarm before CO levels become life threatening. This
Alarm
llows you precious time to leave the house and correct the problem.This is
a only possible if Alarms are located, installed, and maintained as described in
his manual.
t Gas Detection at Typical Temperature and Humidity Ranges: The CO
Alarm is no
or false alarm resistance to Methane (500 ppm), Butane (300 ppm), Heptane
f (500 ppm), Ethyl Acetate (200 ppm), Isopropyl Alcohol (200 ppm) and Carbon Dioxide (5000 ppm). Values measure gas and vapor concentrations in parts pe
udible Alarm:
A
t formulated to detect CO levels below 30 ppm typically. UL tested
r million.
inimum at 10 feet (3 meters).
85 dB m
GENERAL LIMITATIONS OF CO ALARMS
his CO Alarm is intended for residential use. It is not intended for use
T in industrial applications where Occupational Safety and Health Administration (OSHA) requirements for carbon monoxide detectors
t be met.
mus CO alarms may not waken all individuals.
aken to the sound of the CO alarm, or if there are infants or family members
w
ith mobility limitations, make sure that someone is assigned to assist them in
w the event of an emergency.
O Alarms will not work without power.This alarm requires a two (2) AA
C
batteries to operate.
O Alarms for Solar or Wind Energy users and battery backup power
C
ystems:
s
sine wave inverters. Operating this Alarm with most battery-powered UPS (u
nverters
i UPS type, please consult with the manufacturer to verify.
his CO Alarm will not sense carbon monoxide that does not reach the
T sensor.
in other areas. Doors or other obstructions may affect the rate at which CO
eaches the CO Alarm. For this reason, if bedroom doors are usually closed
r at night, we recommend you install a CO Alarm in each bedroom and in the hallway between them.
CO Alarms may not sense CO on another level of the home. For example, a C
asement. For this reason, one CO Alarm may not give adequate warning.
b Complete coverage is recommended. Place CO Alarms on each level of the home
C
curr is i w
specially true if the door is closed or only partly open. Even persons who are
e
wake may not hear the alarm horn if the sound is blocked by distance or
a cl
t
o
his CO Alarm is not intended for people who are hearing impaired.
T
C
sour
O Alarm senses CO that may be escaping unnoticed from malfunctioning
C
urnaces, appliances, or other sources. Early warning of fire requires the
f installation of smoke alarms.
C
arn against increasing CO levels, BRK Brands, Inc. does not warrant or imply
w
n any way that they will protect lives from CO poisoning. Homeowners and
i
e
r CO Alarms have a limited life. Although the CO Alarm and all of its parts
ha possi your CO Alarm weekly.
C
have limitations. They can only detect CO that reaches their sensors. They ma
emote part of the home, away from the CO Alarm.
r
C powered CO Alarms should only be operated with true or pure
A
ninterruptible power supply) products or square wave or “quasi sine wave”
ill damage the Alarm.If you are not sure about your inverter or
w
This CO Alarm will only sense CO at the sensor. CO may be present
O Alarm on the second level, near the bedrooms, may not sense CO in the
.
O Alarms may not be heard.The alarm horn loudness meets or exceeds
ent UL standards of 85 dB at 10 feet (3 meters). However, if the CO Alarm
nstalled outside the bedroom, it may not wake up a sound sleeper or one
ho has recently used drugs or has been drinking alcoholic beverages.This is
osed doors. Noise from traffic, stereo, radio, television, air conditioner, or
r appliances may also prevent alert persons from hearing the alarm horn.
he
arms are not a substitute for a smoke alarm.
Al
O
f carbon monoxide, this CO Alarm does not sense smoke or fire. This
ce o
O Alarms are not a substitute for life insurance.Though these CO Alarms
nters must still insure their lives.
ve passed many stringent tests and are designed to be as reliable as
ble, any of these parts could fail at any time.Therefore, you must test
O Alarms are not foolproof.Like all other electronic devices, CO Alarms
ve early warning to rising CO levels if the CO is coming from a
i
t g
y no
If children or others do not readily
TROUBLESHOOTING GUIDE
Alarm... Problem... You should...
If the
ute. Low battery warning. Install two new AA batteries
n
i
bout once pe
s" a
irp
orn "ch
H
orn does three rapid "chirps" every minute;
H LED has 3 rapid flashes with "chirps".
nked but do not communicate with
i
e l
Alarms ar
he
T each other.
O Alarm goes back into alarm 4 minutes after you
C Silence it.
e
r
Alarm sou
O
C
vels of CO are revealed in an investigation.
le
or a list of acceptable replacement batteries, see “Regular Maintenance.”
*F If you have questions that cannot be answered by reading this manual, call Consumer Affairs at 1-800-323-9005, M-F 7:30 a.m. to 5:00 p.m. (CST)
K Br
R
B that for a period of five years from the date of purchase, this product will be
e from defects in material and workmanship. BRK, at its option, will repair
e
r
f or replace this product or any component of the product found to be
efective during the warranty period. Replacement will be made with a new or
d
ma
e
r replacement may be made with a similar product of equal or greater value. This is your exclusive warranty.
This warranty is valid for the original retail purchaser from the date of initial retail purchase and is not transferable. Keep the original sales receipt. Proof of purchase is required to obtain warranty performance. BRK dealers, service centers, or retail stores selling BRK products do not have the right to alter, mod
his warranty does not cover normal wear of parts or damage resulting from
T any of the following: negligent use or misuse of the product, use on improper voltage or current, use contrary to the operating instructions, disassembly, repair or alteration by anyone other than BRK or an authorized service center.
urther, the warranty does not cover Acts of God, such as fire, flood,
F
ica
urr
h
ate Purchased: _______________Where Purchased: __________________
D
Date Installed: ____________/____________Month/Year
Replacement date is five years after installation:
T
O
N lifecycle, the MALFUNCTION SIGNAL will sound once a minute to indicate the need to immediately replace the Alarm.
First Alert®is a registered trademark of the First Alert Trust used under license. ONELINK
nds f
nds, Inc., ("BRK") the maker of First Alert
a
ed product or component. If the product is no longer available,
ur
act
uf
n
y way change the terms and conditions of this warranty.
n
ify or a
s and tornadoes or any batteries that are included with this unit.
ne
_____________/____________Month/Year
E: End of Life Signal — Once the unit reaches the end of its
®
is a trademark of BRK Brands, Inc.
r m
uently even though no high
q
®
br
For your records, please record:
ALFUNCTION SIGNAL.Device is not working
M
properly, and needs to be replaced.
terference. Reference the Wireless
n
le i
b
ossi
P Operation section of this manual.
O levels indicate a potentially dangerous
C situation.
operly located. Refer to
pr
m
y be i
Alarm ma
O
he C
T
here to Install CO Alarms” for details.
“W
TED WARRANTY
IMI
L
ucts warrants
od
nd pr
a
nits under warranty should be returned to
U manufacturer for replacement. See “Limited
arranty” for details.
W
o different locations. Add an additional
Alarms t
e
v
o
M Alarm between the unresponsive Alarms to route the
ound obstructions.
l ar
na
sig
F YOU ARE FEELING SYMPTOMS OF CO
I POISONING, EVACUATE your home and call 911
ir
he F
or t
nds" for details.
Sou
e y
t
oca
Rel
ve home rechecked for potential CO problems.
ha
y be e
ou ma
Y
l not be liable for any incidental or consequential damages caused
l
K sha
R
B by the breach of any express or implied warranty. Except to the extent
bited by applicable law, any implied warranty of merchantability or fitness
i
oh
pr for a particular purpose is limited in duration to the duration of the above
arranty. Some states, provinces or jurisdictions do not allow the exclusion or
w
m
i
l an implied warranty lasts, so the above limitations or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights that vary from state to state or province to province.
How to Obtain Warranty Service S
In order to obtain warranty service, contact the Consumer Affairs Division at
-800-323-9005, 7:30 AM - 5:00 PM Central Standard Time, Monday through
1
riday. To assist us in serving you, please have the model number and date of
F purchase available when calling. BRK Brands, Inc., 25 Spur Drive, El Paso, TX 79906
Battery: BRK Brands, Inc. make no warranty, express or implied, written or oral, including that of merchantability or fitness for any particular purpose with respect to battery.
f incidental or consequential damages or limitations on how long
ion o
t
a
it
rvice is required, do not return the product to your retailer.
f se
vice:
er
I
For Warranty Service return to:
ment. Refer to "If The CO Alarm
t
ar
p
e
e D
If frequent alarms continue,
.
Alarm
our
riencing an intermittent CO problem.
pe
x
TABLE OF CONTENTS
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Basic Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Wireless Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
ti
a
l
l
ta
ns
I
Where to Install This Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Where CO Alarms Should NOT Be Installed . . . . . . . . . . . . . . . . . . . . . .2
How to Install This Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Step By Step Guide to Programming This Alarm . . . . . . . . . . . . . . . . . .2-3
d
Ad
ha
W
onal Locking Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
ti
p
O
If Your CO Alarm Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
ng the Silence Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
si
U
Silencing the Low Battery Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Latching Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
es
T
ly
k
ee
W
Regular Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
What You Need To Know About CO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
What is CO? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
m
y
S F
inding the Source of CO after an Alarm . . . . . . . . . . . . . . . . . . . . . . . .5
Potential Sources of CO in the Home . . . . . . . . . . . . . . . . . . . . . . . . . . .5
How Can I Protect My Family From CO Poisoning? . . . . . . . . . . . . . . . . . .6
Regulatory Information For CO Alarms . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
Underwriters Laboratories Inc. UL 2034 . . . . . . . . . . . . . . . . . . . . . . .6-7
General Limitations Of CO Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
inking Additional ONELINK
nd L
ng a
i
t You Will See and Hear With This Alarm . . . . . . . . . . . . . . . . . . . . .3
g . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
n
ti
ptoms of CO Poisoning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Printed in Mexico M08-0195-000 Q 03/07
®
Alarms
e is a
h fir
houg
Alt
*.
. . . . . . . . . . . . . . . . . .
NSTALLATION
I
USER’S MANUAL
ONELINK®BATTERY OPERATED
CARBON MONOXIDE ALARM
Features:
UL STANDARD
M0
IMPORTANT! PLEASE READ CAREFULLY AND SAVE.
This user’s manual contains important information about your Carbon
onoxide Alarm’s operation. If you are installing this Alarm for use by others,
M
ou must leave this manual—or a copy of it—with the end user.
y
NTRODUCTION
I
hank you for choosing First Alert
T
ou have purchased a state-of-the-art Alarm designed to provide you with
Y early warning of a carbon monoxide danger.
ONELINK
enabled alarms when installed.
clusive Voice Warning with Locationwill tell you the preprogrammed
Ex
location of the initiating unit and danger detected. Programmable up to 11 locations (ex. "basement"). When alarms sounds, if programmed for basement
ill say "Warning, evacuate, carbon monoxide in basement" along with all
it w other installed ONELINK
pread Spectrum Horn Tone.Lower and varying horn frequency makes it
S
easie
hrough the 2200 – 3400 Hz range.
t
F Interconnect.
R
tween alarms. 915MHz frequency with 65,000 security codes and 3 channel
be frequency hopping.
ingle Button Test/Silenceeliminates confusion. Depending on what mode
S
he alarm is in, pushing the button provides different functions such as testing
t
he alarm, silencing the alarm, re-testing the alarm when in silence and clearing
t
he La
t
wo Silence Features.Temporarily silence low battery chirp for up to eight
T
s before replacing low battery or silence an unwanted alarm for several
hour
inutes.
m Two Latching Features. Alarm Latch: Easily identifies initiating alarm even
fter alarm condition has subsided. Low Battery Latch: Identifies which unit is
a
w battery condition.
o
n l
i
e
f
r
Pe
mounting bracket that keeps the alarm secure over a wide rotation range to
low for perfect alignment.
l
a
Year End of Life Timer.Every 24 hours of operation a counter stored in
6
mory is updated.When the count equals 6 years of true operation meaning
me
ua
act
t the time of the 45 second Power-LED flash.
a
007 BRK Brands, Inc., a subsidiary of Jarden Corporation
© 2 3901 Liberty Street Road, Aurora, IL 60504-8122
ig
l r
Al Consu
®
NELINK
O Voice with Programmable Location
wo Latching Features
T
wo Silence Features
T
2034
8-0195-000
r for elderly with normal age related hearing loss to hear horn. Sweeps
ch
t
ct M
y powered-up, a malfunction chirp (triple chirp) will sound once a minute
l
l
s r
t
h
mer Affairs: (800) 323-9005 • www.firstalert.com
nabled
E
odel CO511
M
rinted in Mexico
P
®
Enabled. Alarm automatically communicates with other ONELINK
Rel
ing features.
ount System
served.
e
7
Q 03/0
®
or your Carbon Monoxide Alarm needs.
f
Key features include:
®
Voice alarms.
iable and secure radio frequency communication
etless base for easy installation and a
s a gask
e
ud
ncl
i
®
BASIC SAFETY INFORMATION
• Dangers, Warnings, and Cautions alert you to important operating nstructions or to potentially hazardous situations. Pay special
i
on t
ti
ten
t
a
O
his C
T
O
he C
T
ndicate the presence of carbon monoxide gas at the sensor.
only i Carbon monoxide gas may be present in other areas.
• This CO Alarm cannot operate without working batteries.
emoving the batteries for any reason, or failing to replace the
R
teries a
t
a
b
VER ignore any alarm. See “If Your CO Alarm Sounds” for more
E
N
• nformation on how to respond to an alarm. Failure to respond can
i result in injury or death.
The Silence Features are for your convenience only and will not
correct a pr Always check your home for a potential problem after any alarm.
ure t
l
ai
F
t this CO Alarm once a week. If the Alarm ever fails to test
es
T
correctly, have it replaced immediately! If the Alarm is not working
operly, it cannot alert you to a problem.
pr
• This product is intended for use in ordinary indoor locations of
ving units. It is not designed to measure CO levels in com-
i
ly l
i
am
f
iance with Occupational Safety and Health Administration (OSHA)
pl commercial or industrial standards. Individuals with medical condi-
ons tha
ti
ider us
cons signals for carbon monoxide concentrations under 30 ppm. For additional information on carbon monoxide and your medical
on con
conditi
e items.
o thes
arm is appr
Al
arm is n
Al
t the end o
oblem. See "Using the Silence Features" for details.
o do so can result in injury or death.
t ma
ing warning devices which provide audible and visual
oved for use in single-family residences.
gned to detect fire or any other gas. It will
i
t des
o
f their service life, removes your protection.
itive to carbon monoxide may
ens
y ma
ct y
ta
e them m
k
our ph
ore s
ysician.
WIRELESS OPERATION
First Alert®ONELINK®Technology is the easy, cost-effective way to provide
our family with whole-home safety.All ONELINK
y
ther without wires or connectors. When one Alarm sounds, they all
each o sound.This provides your family with an earlier warning of potential danger,
ves you more time to react.
i
nd g
a
munication distance (range) between any two ONELINK
he com
T typically 50 feet (15 meters) inside of a home. Some features of a home, such as the number of floors, number/size of rooms, furniture and types of building materials used may reduce the range of the Alarms. Examples include: sus­pended ceilings, ductwork, large metallic appliances (refrigerators) and metal studs. A feature of ONELINK®Alarms is that they operate as a mesh network.
Alarms w
l
Al Alarms. Interference from structural conditions can be overcome by adding
itional Alarms to route the wireless signal around obstructions.
d
ad
• The range and proper operation of any wireless device will vary depending on its surroundings. It is very important that each Alarm is tested individually before and after installation to make sure that all Alarms respond properly.
• The ONELINK
w
t
be
3
under thes
etal objects and metallic wallpaper may interfere with signals
M
om w
r
f your home such as remodeling, moving furniture, and with metal doors opened and closed.
Your First Alert®ONELINK®CO Alarm will automatically communicate both potential fires and carbon monoxide presence with all other First Alert ONELINK®Smoke/CO Alarms.
FCC NOTICE: This device complies with Part 15 of the FCC Rules.
peration is subject to the following two conditions: (1) This device may not
O cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. FCC ID: M7U5001L
Changes or modifications not expressly approved by BRK Brands, Inc. could void the user’s authority to operate the equipment.
t any alarm signal that is received to all other ONELINK
pea
e
l r
l
i
®
Alarms are not to be used outdoors or to transmit
ldings. The Alarms will not communicate properly
een bui
reless Alarms. Alarms should be tested after changes to
i
e conditi
ons.
1 2 3
®
Alarms com
municate with
®
Alarms is
®
®
WHERE TO INSTALL CO ALARMS
he National Fire Protection Association (NFPA) recommends that a CO Alarm
T
ld be centrally located outside of each separate sleeping area in the
shou immediate vicinity of the bedrooms. For added protection, install additional
O Alarms in each separate bedroom, and on every level of your home.
C
f your bedroom hallway is longer than 40 feet (12 meters), install a CO Alarm
I at BOTH ends of the hallway.
fer to state and local building codes for additional requirements.
Re
n a Single-level Home:
I
• Install at least one CO Alarm near or within each separate sleeping area.
• For added protection, install an additional CO Alarm at least 20 feet ters) away from the furnace or fuel burning heat source.
(6 me
n a Multi-level Home:
I
• Install at least one CO Alarm near or within each separate sleeping area.
For added protection, install at least one CO Alarm on each level of the
home. If you have a basement, install that CO Alarm at the top of the basement stairs.
• For added protection, install an additional CO Alarm at least 20 feet
(6 meters) away from the furnace or fuel burning heat source.
n Mobile Homes:
I
• Install CO Alarms on inside walls ONLY. Uninsulated outside walls and
roofs of mobile homes often transfer heat and cold from outdoors.
WHERE CO ALARMS SHOULD NOT BE INSTALLED
Do NOT locate this CO Alarm:
• In garages, kitchens, furnace rooms, or in any extremely dusty, dirty or
easy areas.
gr
• Closer than 15 feet (4.6 meters) from a furnace or other fuel burning heat
source, or fuel burning appliances like a water heater.
• Within 5 feet (1.5 meters) of any cooking appliance.
In areas where temperature is colder than 40˚ F (4˚ C) or hotter than 100˚ F
(38˚ C).These areas include unconditioned crawl spaces, unfinished attics,
ninsulated or poorly insulated ceilings, porches, and garages.
u In turbulent air, like near ceiling fans, heat vents, air conditioners, fresh air
eturns, or open windows. Blowing air may prevent CO from reaching the
r sensors.
In direct sunlight.
• This CO Alarm is designed for use inside a single-family home artment. It is not meant to be used in common lobbies, hall-
or ap
or b
s,
y
a
w
arms are a
Al
on areas may not be heard from inside individual family
comm
iving units.
l
O Alarm alone is not a suitable substitute for complete
his C
T
tection systems in places which house many people, like hotels
de
itories, unless a CO Alarm is also placed in each unit.
or dorm
• DO NOT use this CO Alarm in warehouses, industrial or commercial
ldings, special-purpose non-residential buildings, RVs, boats, or
bui
rplanes. This CO Alarm is specifically designed for residential
ai use, and may not provide adequate protection in non-residential
tions.
ca
i
appl
HO
W TO INSTALL THIS ALARM
ick installation instructions see the “Quick Installation Instructions”
u
or q
F included.
This CO Alarm was designed to be mounted on the ceiling or wall. It is not
top device.You must install this device on the ceiling or wall as outlined
a table
.
w
o
bel
ols y
o
T
Phillips screwdriver, hammer.
. Hold the mounting bracket against the ceiling (or wall) so the vertical
1
mou
nsid
i
ut t
P
.
2
mou
sing a 3/16” (5 mm) drill bit, drill a hole through the center of the oval
U
.
3
outlines you traced.
4. Insert the plastic screw anchors (in the plastic bag with screws) into the holes. Tap the screw anchors gently with a hammer, if necessary, until they
e fl
ar
ne t
i
L
.
5
6. Screw the mounting bracket to the ceiling or wall through the mounting
o
sl
7. Attach the CO Alarm to the mounting
acket. Line up the guides on the alarm’s
br base with the guides on the mounting bracket.When guides are lined up, turn
he base clockwise (right) until it snaps
t
nto place.
i
NOTE: Once the Alarm is snapped onto the m the Alarm to adjust the alignment.
8. Test the CO Alarm. See “Weekly Testing” for details.
E
T
S
HIS ALARM
T
he
“W
Read
ill need:
ou w
ting slot is aligned in the 12 o’clock position and trace around the
n
he mou
f t
e o
it w
n
he u
nting holes.
h t
it
ush w
n
he mou
he two screws provided.
ng t
s usi
t
ng bracket, you can rotate
ti
oun
P BY STEP GUIDE TO PROGRAMMING
s of multi-family buildings unless working CO
t
emen
as
lso installed in each family living unit. CO Alarms in
e To Install CO Alarms” before starting.
r
PARTS OF THIS CO ALARM
1 Test/Silence Button 2 Battery Compartment 3 Power LED
CO Alarm LED
4
drill with 3/16” (5mm) drill bit,
,
l
nci
pe
ing slots (vertical and horizontal mounting).
t
n
here it won’t get covered with dust when you drill the
ing or wall.
l
i
he ce
acket up over the plastic screw anchors.
ng br
i
t
FOR FIRST TIME AND WHEN CHANGING BATTERIES
ction:
A
1. Insert batteries (2, AA batteries).
. Press & Hold Test Button if you
2
would like to program the location or change the location of the Alarm. Release button after Alarm responds.
3. After you hear the location of where
our
Y Available locations:
lacing the Alarm, Press &
e p
ou ar
y Hold the Test Button.
Alarm has no
Basement Kitchen Child’s Bedroom Living Room Dining Room Master Bedroom Family Room No Location Guest Bedroom Office Hallway Utility Room
w been programmed for the location of your choice.
arm Will Say:
Al
“Welcome, First Alert Carbon Monoxide Alarm.”
No location programmed” if
time
or “[Location, example: “Basement”] location programmed” when changing batteries.
“To select location, press and hold
est button now.”
t
To save location, press and hold test
“ button after location is heard.” Alarm will speak list of locations (see below).
“[Location, example: “Basement”]
ion saved.”
t
oca
l If no location is chosen:
“No location saved.”
st
fir
he optional locking features are designed to prevent unauthorized removal of the battery or alarm. It is not necessary to activate the locks in
T
ingle-family households where unauthorized battery or alarm removal is not a concern.
s
These CO Alarms have two separate locking features: one to lock the battery compartment, and the other to lock the CO Alarm
o the mounting bracket. You can choose to use either feature independently, or use them both.
t
Tools you will need: • Needle-nose pliers • Standard flathead screwdriver.
th locking features use locking pins, which are molded into the mounting bracket. Depending on which locking features you
Bo use, remove one or both pins from the mounting bracket using needle-nose pliers.
To permanently remove either locking pin, insert a flathead screwdriver between the locking pin and the lock, and pry
n out of the lock.
the pi
T
O LOCK THE BATTERY COMPARTMENT
Do not lock the battery compartment until you install the batteries and
t the CO Alarm.
tes
If the unit does not alarm during testing, DO NOT lock the battery compartment!
nstall new batteries and test again.
I If the CO Alarm still does not alarm, replace it immediately.
1. Using needle-nose pliers, detach one ocking pin from the mounting bracket.
l
. After batteries are inserted, then push
2
he locking pin through the hole near the
t battery door latch on the back of the CO
.
Alarm
TO LOCK THE MOUNTING BRACKET
. Using needle-nose pliers, detach one
1
locking pin from the mounting bracket.
. Insert the locking pin through the hole on
2
he back of the CO Alarm as shown in the
t
iagram.
d
. When you attach the CO Alarm to the
3
nting bracket, the locking pin’s head
mou will fit into a notch on the bracket.
AD
DING AND LINKING ADDITIONAL ONELINK
OTE: Steps 1 through 3 need to be completed within two minutes. If
N
ore than t
m Simply open the battery drawer of the second Alarm and repeat
teps 1 through 3.
s
. Insert the batteries into the battery
1
drawer of the next Alarm.
O N
D
. Press and hold the test button and
2
hen close the battery drawer.
t
. Once you hear the unit chirp,
3
release the test button.
he Green power LED will start
T
o blink indicating the ONELINK
t Alarm is waiting for program data
om one o
r
f
4. Press and hold the test button on the first Alarm, until the second Alarm irps and its Green power LED stops blinking.Then release the test button.
ch
f y
I
.
5
you can now connect the hardwired Alarm by installing the three-wire con
Repeat steps 1-5 for additional ONELINK
.
6
ou have now successfully linked your new ONELINK
Y additional Alarms at a later time, follow steps 1 through 5.
wo minutes pass, the Green power LED will stop blinking.
OT CLOSE THE DRAWER.
®
f the other setup ONELINK
e purchased the hardwired battery back-up ONELINK
v
ou ha
nector on the ceiling to the Alarm.
®
Alarms
®
Alarms
.
WHAT YOU WILL SEE AND HEAR WITH THIS ALARM
perations
l O
orma
nder N
U
oice:
V
lent
Si
orn:Silent
H
ower LED:Flashes Green once/minute
P
hen You Test the Alarm
W
oice:
esting.”Horn:
V
T
,
ce:
oi
V
CO LED: Flashes Red in sync with the horn pattern
If Battery Becomes Low or is Missing
oice:
V
orn:chirps once a minute
H Power LED: Flashes Green On for 2 seconds/Off for 2 seconds.
Alarm is Not Operating Properly (MALFUNCTION SIGNAL)
If
Voice:
orn:Three rapid chirps every minute
H CO LED: Flashes approximately once a minute
Alarm Levels of CO are Detected
Horn: 4 fast beeps, pause, 4 fast beeps, pause*
oice:“Warning, evacuate carbon monoxide in [Location, example:
V
Horn: 4 beeps, pause, 4 beeps, pause repeating 2 times followed by Voice
O L
C
E:
T
O
*N
epeat for fifteen minutes. After fifteen minutes, the pause will increase to one
r minute.
CO Alarm is Silenced
Horn: CO LED: Flashes Red
ng
i
arn
“W
“Basement”]. Evacuate.” Pause.“Highest carbon monoxide level
as [CO level example: _0_
w
Replace battery in [Location, example “Basement”].”
Repeated every 5 hours
tt
w Ba
o
L
“Detector error in [Location, example “Basement”], please see
Re
.
l
ua
n
ma
n
me
Base
“ was [CO level example: ___ ppm]”.
ng a
i
arn
W
ED:
ing Alarm: Flashes Red in sync with the horn pattern. After
ur
D Alarm: Flashes Red On for 2 seconds/Off for 2 seconds. CO Alarm Latch is now engaged.
s i
it goe
n
f u
I
Off
ast beeps, pause, 4 fast beeps;
4 f
acuate carbon monoxide in [Location, example:
v
e
pm]”.
p
ngaged.
w e
ch is no
t
y La
r
e
ted every 5 hours
pea
vacuate.” Pause.“Highest carbon monoxide level
E
”].
t
.
e
v
bo
nto CO alarm, the regular 4 beeps-brief pause cycle will
IF YOUR CO ALARM SOUNDS
What You See and Hear
er to section “What You Will See and Hear With This Alarm”.
f
e
R
Actuation of your CO Alarm indicates the presence of carbon monoxide
ch can kill you. In other words, when your CO Alarm sounds,
hi
O) w
(C
ou mus
y
IF THE ALARM SIGNAL SOUNDS
1. Operate the Test/Silence button.
2. Call your emergency services, fire department or 911. Write down the number of your local emergency service here:
________________________________________________________________
3. Immediately move to fresh air—outdoors or by an open door or window. Do a head count to check that all persons are accounted for. Do not re-
nter the premises, or move away from the open door or window until the
e
me
e out, and your CO Alarm remains in its normal condition.
Af
.
4
period, repeat steps 1-3 and call a qualified appliance technician to investi­gate for sources of CO from fuel-burning equipment and appliances, and inspect for proper operation of this equipment. If problems are identified during this inspection have the equipment serviced immediately. Note any combustion equipment not inspected by the technician, and consult the manufacturers’ instructions, or contact the manufacturers directly, for more information about CO safety and this equipment. Make sure that motor vehicles are not, and have not, been operating in an attached garage or ad technician here:
________________________________________________________________
Alarms have various limitations. See "General Limitations of CO Alarms"
or de
f
gnore it!
t i
o
t n
ency services responder has arrived, the premises have been aired
g
r
ter following steps 1-3, if your CO Alarm reactivates within a 24-hour
t to the residence.Write down the number of a qualified appliance
n
jace
tails.
OPTIONAL LOCKING FEATURES
T
O UNLOCK THE BATTERY COMPARTMENT
. Remove the CO Alarm from the
1
2. Insert a flathead screwdriver under the
. To relock the battery compartment,
3
. Reattach the CO Alarm to the mounting
4
hen replacing the batteries, always test
W the Alarm before relocking the battery compartment.
TO UNLOCK THE MOUNTING BRACKET
. Insert a flathead screwdriver into the
1
2. Pry the CO Alarm away from the
®
.
®
ALARM
arms. To add
Al
®
Alarm
S
ING THE SILENCE FEATURES
US
ever remove the batteries to quiet an unwanted alarm. Removing the
N
atteries disables the alarm and removes your protection.
b
he Silence Feature is intended to temporarily silence the horn while you
T identify and correct the problem. Do not use the Silence Feature in emergency
ua
sit
he Silence Feature can temporarily quiet an unwanted alarm for several
T
ut
n
i
m the alarm cover for at least 3-5 seconds.
r t
e
t
Af
,
mod
hen the C
W
inutes. After 4 minutes, if CO levels remain potentially dangerous the horn
4 m will start sounding again.
IL
S
is si
h
T up to 8 hours. You can silence the low battery warning “chirp” by pressing the
est/Silence button on the alarm cover.
T Once the low battery warning “chirp” silence feature is activated, the unit
tinues to flash the Green light twice a minute for 8 hours. After 8 hours, the
con
w b
o
l
this unit will not operate without battery power! To deactivate this feature:
nto Test Mode and the low battery warning will resume (LED flashes and
go i
nit sounds “chirp” once a minute).
u
T
LA
Alarm Latch is activated after an Alarm is exposed to alarm levels of mono
i
g
be “latch” for about 15 minutes, to give you time to determine which unit initiated
he a
t Low Battery Latch is activated when the Alarm is in the "low battery condition".
he
W
conds f
se which Alarm needs to have the battery replaced. Although, the Alarm will sound the low battery chirp approximately once every minute, sometimes
uring the initial stages of "low battery", the Alarm will chirp in greater intervals
d than one minute, sometimes up to several hours, until the battery reaches a
ead
t
s
aiting for and/or identifying which unit is chirping.
w
WE
• Test the CO Alarm once a week. If the CO Alarm ever fails to test
• DO NOT stand close to the Alarm when the horn is sounding.
It is important to test this unit every week to make sure it is working properly. Using the test button is the recommended way to test this CO Alarm.
ou can test this CO Alarm by
Y
he Alarm cover (typically 3-5 seconds).
on t During testing, you will see and hear the following sequence:
• The
If the unit does not alarm, make sure the batteries are correctly installed, and test again. If the unit still does not alarm, replace it immediately.
mounting bracket. If the unit is locked
o the bracket, see the section
t
To Unlock the Mounting Bracket.”
head of the locking pin, and gently pry
f the battery compartment lock.
it out o (If you plan to relock the battery compartment, save the locking pin.)
ose the battery door and reinsert
cl locking pin in lock.
acket.
br
rectangular cut-out on the mounting bracket nearest to the locking pin.
acket by pushing up on the screw-
br driver and turning the CO Alarm counterclockwise (left) at the same
ime.
t
ou hear the CO alarm horn and the CO red light is flashing,
If y
ions. It will not correct a CO problem.
t
es. You can silence this Alarm by pressing the Test/Silence button on
he Test/Silence button is released, the Red LED blinks during the silence
e.
N
CI
N
E
nce f
le
attery “chirp” will resume.
NG FEATURES
CHI
xide
After CO levels drop below alarm levels, the “CO”Red LED will
.
o flash O
n t
.
larm
is occur
h
n t
or about 15 minutes. This feature is designed to help you identify
y low battery level. This innovative feature eliminates the frustration of
Y
KL
E
operly
pr working properly, it cannot alert you to a problem.
posure at close range may be harmful to your hearing.
Ex
hen tes
W
Horn will sound 4 beeps, pause, 4 beeps.The Power LED will be
nd the
f a
f
O
“ALARM—MOVE TO FRESH AIR”
ove everyone to a source of fresh air.
m
DO NOT remove the batteries!
Alarm is Silenced
O
THE LOW BATTERY WARNING
G
ure can temporarily quiet the low battery warning “chirp” for
t
ea
R
Press the Test/Silence button again. The unit will
or 2 seconds/Off for 2 seconds. It will continue to flash or
n f
he
t
,
s
ESTING
T
ha
,
ti
er
w
o
E
P
L
ve it replaced immediately! If the CO Alarm is not
tep away when horn starts sounding.
s
,
g
n
D
E
O L
C
flashe
Alarm will remain silent for up to
O
he C
t
ce the batteries as soon as possible;
a
epl
or 2 seconds/Off for 2
n f
n O
e
e
s Gr
D flashe
essing and holding the Test/Silence button
pr
.
d
s Re
4
carbon
Loading...