BRK Model CO250 is a single station carbon monoxide alarm specifically
designed for residential and institutional applications including sleeping rooms of
hospitals, hotels, motels, dormitories, and other multifamily dwellings as defined
in standard NFPA 101. Model CO250 has been fully tested and complies with,
UL2034, NFPA 720, and NFPA 101 and other agencies that model their codes
after the above agencies. It meets building codes where battery operated
carbon monoxide alarms with silence are required and with model building
codes published by the ICC.
BRK Model CO250 is a state of the art carbon monoxide alarm designed to
provide early warning of the presence of carbon monoxide. It features an
electrochemical carbon monoxide sensor, an 85dB horn, a supervised 9V battery
power supply, a full function test switch, a silence feature to silence unwanted
nuisance alarms, a red LED light that indicates DC power or alarm. It also
features a tamper resistant locking pin that locks alarm cover to prevent removal
of battery. Perfect for apartment, dormitory or hotel applications. The compact,
low profile design complements any décor. Battery installation and removal can
occur while the unit is mounted to the ceiling or wall via the hinged cover. When
voltage drops to a pre-set warning level, the horn will “chirp” approximately
once per minute to indicate a fresh battery is needed. To insure the battery is
always replaced properly, the cover is designed to resist closing when the
battery is missing. Designed for wall or
ceiling mounting. Includes
mounting anchors and
screws.
9V BATTERY
INCLUDED
CAT.
CO250B
CO
FRONT
VIEW
4.25”
SIDE
VIEW
1.6”
BACK
VIEW
ARCHITECTURAL AND ENGINEERING SPEC
The carbon monoxide alarm shall be a BRK Model CO250 and shall provide at a
minimum the following features and functions:
1. An electrochemical CO sensor.
2. The unit shall be capable of self restoring.
3. The unit shall have an "End of Life" signal. This signal should be capable of
temporarily being silenced for up to 2 days. After about 2 days, the signal will
resume. After about 2-3 weeks the signal cannot be silenced.
4. Powered by a supervised 9V battery and a solid state piezo horn
rated at 85dB at 10 ft.
5. A visual LED power-on indicator to confirm unit is receiving power or
is in alarm.
6. A full function test button. The test button should check all alarm
functions by stimulating the chamber to simulate a CO condition,
causing the unit to alarm. Model CO250 also has a silence feature to
silence unwanted nuisance alarms.
7. A tamper resistant locking pin that locks alarm cover to prevent removal
of battery.
8. The CO sensor is adjusted not to detect CO levels below 30 PPM and will not
alarm when exposed to constant levels of 30 PPM for 30 days. It will alarm
at the following levels: 400 PPM CO between 4 and 15 minutes, 150 PPM CO
between 10 and 50 minutes and 70 PPM CO between 60 and 240 minutes.
9. The unit shall be capable of operating between 40°F (4°C) and
100°F (38°C) and relative humidity between 10% and 95%.
10. The unit shall contain mounting hardware and shall be listed for wall
or ceiling mounting.
11. The unit shall at a minimum meet the requirements of UL2034, NFPA 720,
NFPA 101, ICC.
.
INSTALLATION OF ALARM
Installation of this CO alarm must conform to NFPA 720. Always check
your local building codes. Follow all instructions for placement as outlined
in the user’s manual in sections titled “Recommended Locations for
CO Alarms” and “Locations to Avoid for CO Alarms”.
1
TECHNICAL SPECS
Alarm Dimensions: 4.25” dia x 1.6”H
Weight: 5.1 oz.
Operating Volatage: 9V Battery Powered
Temperature Range: 40F (4C) to 100F (38C)
Humidity Range: 10% to 95% relative humidity (RH)
Audio Audio Alarm: 85dB at 10 feet
Test/Silence: Electronically simulates smoke condition,
causing the unit to alarm and silences unit.
Alarm Reset: Automatic when carbon monoxide clears
CO Sensor: Electrochemical
Indicator Lights:
DC Power: Intermittent Red Light
Listing: Listed to UL2034 Standard
SHIPPING SPECS:
Individual Carton Dimensions 4.38 ”L x 1.75”W x 4.38”H
Weight 0.39 lbs.
Cube 0.02 ft3
UPC 0 29054 00392 8
Master Carton Dimensions 9.2 ”L x 5.55”W x 5.1”H
Master Pack 6
Weight 3.2lbs.
Cube 0.15 ft3
I2 of 5 600 29054 00392 0
Pallet Information
Cases per Layer 36
Number of Layers 9
Cases per Pallet 324
Units per Pallet 1,944
Cube 55.0 ft3
Weight 1,107 lbs.
The parts of this CO alarm
1. "Open Here"
2
3
4
6
5
7
2. "No Battery" tab
3. Test/Silence button
4. CO alarm base
5. Mounting slots
6. Install 9V battery here
7. Locking pin slot
8. Locking pin: Remove and insert in 7
brkelectronics.com
7
8
©2009 BRK Brands, Inc. a Jarden Corporation
Company (NYSE: JAH)
3901 Liberty Street Road
Aurora, IL 60504-8122
All rights reserved
First Alert is a registered trademark of the First Alert Trust
BRK is a registered trademark of BRK Brands, Inc.
CM2925