BRK electronic 5919, 5919 TH User Manual

®
Cat. No.
5919/5919TH
PHOTOELECTRONIC
SMOKE ALARM
120V AC 60HZ
Photoelectronic sensing chamber Generally more effective at detecting slow smoldering fires Fully insect screened sensing chamber Prevents insects from entering sensing chamber, reducing unwanted alarms Interconnectable up to 18 multiple station BRK alarms Unit detects smoke, identifies itself and sends alarm signal to other units
connected in series “Quick-Connect” wiring harness Allows faster and easier connection to AC power Oversized mounting bracket Mounts to any standard electrical junction box up to 4” octagonal without
screw removal, Covers drywall cut-outs better Red LED/Light indicates unit is receiving AC power During an alarm, the red light on the unit that initiates the alarms goes out
while the others stay on 5919TH also has a 135˚ fixed heat detector Often spec’ed in Military housing and hospitals
(See wiring diagram on reverse) 85dB piezo alarm horn Provides audible notification of fire Manual test button Tests all detector functions Listed to UL 217
•Recommended for areas prone to “false” alarms; near kitchens, bathrooms, heating ducts; or in any smaller apartment or hotel rooms.
Benefits
Cat. No.
5919
Cat. No.
5919TH
S
T
A
T
E
O
F
C
A
L
I
F
O
R
N
I
A
S
T
A
T
E
F
I
R
E
M
A
R
S
H
A
L
Cat. No.
5919/5919TH
AC Powered
Photoelectronic
Interconnectable
Smoke Alarm
DESCRIPTION:
The BRK Electronics Cat. No. 5919 is a 120V AC powered photoelectronic unit designed for both single and multiple station use, up to 18 units. Its sensor operated on the scattered light principle, and electronically compensates for ambient light conditions. The unit has its on 85dB electronic alarm horn, powered-on LED and test button. It is interconnectable and comes with a plastic bracket that mounts easily to 3" and 4" octagon, 4" square or single gang boxes. The 5919 comes with a plug-in connector.
This detector is designed so that, when interconnected, if any one of the units senses smoke, its LED will turn off and its alarm will sound. All other interconnected units will sound an alarm but their LEDs will remain on. NOTE: All interconnected units must receive power from the same fuse or breaker.
Cat. No. 5919TH is identical to the 5919 but has a thermal sensor which is not connected to the unit. The thermal can be separately connected to a central control panel—ideal for hotels and hospitals. This sensor has its own plug-in connector and has a N.O. contact (Form A) rated 3A at 125V AC, a! at 30V DC.
SPECIFICATION
The smoke alarm shall be powered by a 120V AC, 650Hz. power source and shall be listed at .025A in standby condition. The alarm shall have a solid state photoelectronic sensor that operated on the scattered light principle. It shall be protected by an insect-resistant screen. The sensor shall sample the air at the alarm every 5 seconds and shall be designed to trigger an alarm if prescribed levels of smoke enter its chamber. The alarm shall electronically compensate for ambient light conditions and shall be cable of operating properly between 40° and 100°F (4°-38°C) and relative humidity between 10% and 90%. A built-in test button shall mechanically simulate the presence of smoke. A built-in light-emitting diode shall glow when AC power is being received. The alarm shall have an electronic alarm horn. It shall have a plug-in connector and be capable of interconnection with eleven other identical units. It shall be listed to UL 217.
MANUFACTURED BY: DISTRIBUTED BY :
FOR TECHNICAL HELP OR REPRESENTA TIVE NEAREST YOU PHONE 1-800-392-1395 8AM-5PM (CENTRAL TIME)
CM2154
BRK®Electronics 3901 Liberty Street Road Aurora, IL 60504-8122
©1998 BRK Brands, Inc.
Made in USA
TECHNICAL SPECIFICA TIONS
Alarm Circuit 100% solid state Alarm Dimensions 5.5" diameter, 2.5" height Operating 40°F(4.4°C) to 100°F(38°C)
T emperature Range
Operating Humidity 50%RH to 90%RH
Range
Audio Alarm 85dB at 10ft. Power Indicator Lamp Solid State LED T est Button Mechanically simulated the presence of smoke in
photoelectronic sensing chamber, causing unit to alarm Alarm Reset Automatic when smoke clears Interconnections Up to 18 units Weight 8 ounces Power Consumption .025 Amps typical in standby
.025 Amps in alarm Thermal 135°F, 50 foot space rating (cannot be used where
ambient temperature exceeds 95°F). CONT ACTS - Form
A, Ratings: 3A @ 125V AC @ 30V DC
MAXIMUM INTERCONNECT BUS LENGTH 1000 FEET FOR #12-#14 GAUGE WIRE.
ALL INTERCONNECTED SMOKE ALARMS MUST BE POWERED FROM THE SAME FUSE OR BREAKER.
INSTALL PER LOCAL ELECTRICAL CODES AND ARTICLE 780 OF THE NATIONAL ELECTRICAL CODE.
{
A
1 3
}
B
1 2 3
4
5
6
8
7
{
{
4
5
6
8
7
{
{
4
5
6
8
7
{
{
MAXIMUM INTERCONNECT BUS LENGTH 1000 FEET FOR #12-#14 GAUGE WIRE.
ALL INTERCONNECTED SMOKE ALARMS MUST BE POWERED FROM THE SAME FUSE OR BREAKER.
INSTALL PER LOCAL ELECTRICAL CODES AND ARTICLE 780 OF THE NATIONAL ELECTRICAL CODE.
Model 5919
Model 5919TH
Model 5919 Model 5919TH