
Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
1

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
2
Index
Pages
INTRODUCTION: 2
SERVICING INSTRUCTIONS: 5 - 9
TECHNICAL INFORMATION SHEETS:
Contour L 13 10
Contour L 23 11
Contour L 33 12
Contour L 43 13
Contour L 53 14
Contour L 63 15
Profiler P 23 16
Profiler P 33 17
Profiler P 43 18
Profiler P 53 19
Profiler P 63 20
Advance F 13 21
Advance F 23 22
Advance F 33 23
Advance F 43 24
Advance F 53 25
MOTOR CIRCUIT DIAGRAMS 26 - 27
COOLER CIRCUIT DIAGRAM 28
INSTALLATION
Wiring the cooler to Networker 29 - 30
Installing Multiple coolers on a Network 31
Installing dual Networkers 32 - 34
Networker Installer Parameters 35
COOLER SERVICE PARAMETERS 36 - 39
COOLER OPERATION
General Operation 40 - 43
Wash Service 44
Flush Service 46
Aquasave Operation 47
N-E5 Electronic Control Operation 48 - 50
Fan Operation 51 - 59
Pump Operation 60 - 65
Water Inlet Solenoid Operation 66 - 70
Servo Seal & Drain Valve Operation 71 - 76
Trident Water Management 77 - 90
DEALING WITH PROBLEM INSTALLATIONS 91 - 95
SERVICE MAINTENANCE 96 - 100

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
3
Introduction
In August 2003 Brivis introduced the new 3 series Contour cooler and also a lesser featured contour
was also introduced called the Brivis Profiler.
The Brivis Profiler cooler was introduced to offer a budget model Contour to meet market demand.
The Brivis Profiler looks very similar to the Contour with its sloping base, but slight changes have
been made to the decorative panels. The Brivis Profiler cooler is also slightly smaller in height than
the Contour.
Brivis Contour Brivis Profiler
Both models, Brivis Profiler and Contour, now use the N-E5 control box instead of the older N-E4.
The main difference in the N-E5 control is the removal of the isolating switch from the top of the
control box. This isolating switch has been relocated to the underside of the cooler so that the
power can be isolated without removing the front pad. There has also been some software changes
to the N-E5.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
4
Brivis Advance
The Brivis Advance was introduced in 2005 and is designed to take the place of the AD range of
units up to Model AD56. However, the AD76 and AD86 will remain in production.
In essence the Advance is a square shaped Contour/Profile, which sits upon the same base frame
as the Contour/Profiler. So for the purpose of servicing, all the electrical and operational
components are the same and therefore all the information contained in these manuals is relevant.
The BASE is square and sits on a vertical dropper box similar to the AD units, except that the
dropper box should come with outwards turned flange so that the locking brackets on the unit attach
to the dropper box. Like the AD unit, the cooler should be located high enough on the roof to
prevent the back from touching the roof.
The PAD FRAMES are attached in a similar fashion to the Contour and Profile unit. The front and
rear pads can be removed by first lifting the roof assembly, and then lifting the pad assembly out;
the same way the Contour and Profiler work.
The SIDE PAD FRAMES are slightly different and involve the pad frame being rolled into the centre
of the unit and then being raised out. It is important that the pad frame is not forced, as this could
damage the alloy brackets.
The ROOF ASSEMBLY also remains the same as the Profiler/Contour units.
Some standard features differ between the Brivis Profiler, Contour and Advance.
Advance
Motorised winter seal (Servoseal) Yes No No
Counter balanced weather-seal N/A Optional Optional
Motorised dump valve Yes Yes Optional
Aquasave Yes No No
Speed Sensor Yes Yes Yes
Networker compatible Yes Yes Yes
Water sensor Yes Yes Yes

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
5
BRIVIS
SERVICING
INSTRUCTIONS
Retrofitting the Service N-E5 to 0, 1 & 2 Series Contours.
The service N-E5 control can be used as a replacement control for all previous model coolers,
however some parameters need to be adjusted in order for the control to operate correctly. The
table below details all of the parameter adjustments that need to be made for each model cooler
when fitting an N-E5 into an older model Contour. These parameters are located in the cooler
service parameter section, and can only be accessed by using a Networker.
N-E5 parameter adjustments.
Parameter
Parameter description
Default
setting
0 Series
Contour
1 Series
Contour
2 Series
Contour
3 Series
Contour or
Profiler
3 Series
Advance
05
Model selection number -
Determines min & max
fan speeds.
1
Check
specification
sheet
Check
specification
sheet
Check
specification
sheet
Check
specification
sheet
Check
specification
sheet
15
Flush count -
Number of refills before
flushing occurs.
20 20 20
20
20
22
Aquasave - Allows
N-E5 to power Aquasave
module.
1 = Enabled
0 = Disabled
0 0 0
0
Aquasave
powered by
pump power
supply.
1 – Contour
0 - Profiler
Advance - 0
43
Flush time -
Time
solenoid is open during flush.
200
sec
100
sec
60
sec
200
sec
200
sec
200
sec

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
6
BRIVIS
SERVICING
INSTRUCTIONS
N-E5 Cooler Control Dump Delay Parameter.
Units affected:
All Version 3 Contours and Profiler coolers using N-E5 electronic controller.
Reason for change:
R&D have informed us of a change within the N-E5 service parameters. which has the potential to
cause a problem. This change has happened mid production and has affected the first 2020 units.
The problem has occurred to service parameter 01, which relates to the Dump Delay time. The
change is with the way the parameter is read. Usually the parameter unit was in single minutes, but
on the newer N-E5 controllers it has been changed to units of 10 minutes.
For example
- Normal setting was 60, meaning 60 minutes before the cooler would dump.
- New setting is 6, meaning 6 lots of 10 minutes which equals 60 minutes.
If service parameter 01 on the newer N-E5 is changed to 60 when we service these units, it
will then dump after 10 hours (60 x 10 minutes = 600 minutes). Vice Versa if Parameter 01 on
the first version N-E5 is set to 6, it will then dump after 6 minutes.
In both cases this will cause a fairly major upset with the units normal operation. We can trace the
individual controllers by their serial number. The first 2020 controllers have the dump delay setting
units in minutes, and the rest of the production controllers will all have the dump delay setting units
in lots of 10 minutes.
N-E5 Serial Numbers - 18764 020 0000 to 18764 020 2020 have the dump delay in single minutes.
N-E5 Serial Numbers - 18764 020 2021 and Beyond will have the dump delay setting in lots of 10
minutes.
N-E5 - Version 9, 9a & 10 will have the dump delay setting in lots of 10 minutes.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
7
BRIVIS
SERVICING
INSTRUCTIONS
N-E5 Cooler Control Upgrade
(This issue (2) replaces previous versions of servicing instruction #23 (issue 1))
Units affected: 3 Series Contours and Profilers.
Background: The version 7 N-E5 (original control) has proven to be unreliable, with the majority of
failures occurring with the Servo-seal action. The Version 8 N-E5 was introduced to fix this problem.
A tracking problem then started occurring on the trident water sensor. This coupled with lengthy fill
problems (software related) caused the units to operate OK for 2/3 hours before blowing hot air.
R&D have introduced the version 9 N-E5 control, which has had modifications done to the software.
This has improved the failure rate on the Servo-seal (further enhancement from the version 8), and
water level control problems, including refill times, have been rectified. Unfortunately the version 9
also suffered from Servo-seal failures, albeit few in number.
Root cause analysis has since proven that the cause of Servo-seal failures is due to power spikes
degrading PCB components. The version 9A is the latest N-E5 control, which has been upgraded to
protect components from power spikes. Field tests have already proven that the version 9A N-E5 is
very reliable.
The Version 9A controllers can be identified by the marking "9A" on the box.
Action: Technicians, when attending any 3 series cooler (Brivis Profiler or Contour), need to
complete these steps:
Identify the version of controller in the cooler and replace all N-E5 controls (version 7, 8 or 9) with
the new version "9A" controller. Version 8 controllers will be marked with an "8" on the box, and
version 9 controllers with a "9", while any version 7 and before will have no marking on the box.
Correctly label the control box with a defect sticker marked "TO BE REWORKED".
Test cooler for correct operation.
Complete your job sheet with the information below.
Documentation: These notes should be included on your POD invoice.
If the part failed before you attended the job-
Fault Part Fault Description
18764 2 Short description of the fault
If the part did not fail and was upgraded as per the Servicing instruction-
Fault Part Fault Description
18764 111 N-E5 Upgraded

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
8
BRIVIS
SERVICING
INSTRUCTIONS
Trident Water Sensor Tracking Problems
Units affected: All Contours 1,2 & 3 Series, and Profiler 3 Series.
Background: It has been found in the field that the trident water sensor can be subject to false
sensing. This is caused by mineral build up behind the water sensor probes. The cooler may run for
a period of time before the fault occurs, but the fault will eventually result in the pump cavitating
because the unit has failed to fill. The build up on the probes forces the electronic controller to think
the water level is OK, when in actual fact it doesn't really know at what level the water is at.
Action: Service technicians are required to perform this action when attending any 3 series Contour
or Profiler. This action should only be performed on 1 or 2 series Contour coolers if they exhibit the
above symptoms. The installation of a modified water sensor should be carried according to the
installation instructions.
Plastic Housing Modified Sensor
Installation: Modifications have been made to Trident water sensor to help prevent this electrical
tracking on the water sensor. The plastic legs on the trident probe housing have been removed,
preventing any build up of minerals at the low point of the probes (see pictures).
Remove the old water sensor from the cooler trough and attach a defective label to part. This part
should be sent to warranty returns. if the unit is under warranty. If the unit is not under warranty this
part is to be charged to the customer.
Replace the water sensor with Part - 18066 - WATER SENSOR ASSY CONTOUR L1, ensuring
that the plastic housing has been modified (see picture above).
Test cooler for correct operation.
Documentation: These notes should be included on your POD invoice.
Fault Part Fault Description
18066 111 Modified water sensor.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
9
BRIVIS
SERVICING
INSTRUCTIONS
Introduction of 5.5 litre ELBI solenoid
Background: On the 23/11/2004, the 5.5 litre ELBI solenoid was introduced into production for all 3
series Contours and Profilers. it was originally brought into production to try and prevent units from
failing to fill during a water limp error. it was found that the cause was not the limited flow (4 litre
ELBI) of the original solenoid but a water sensing issue. However the supplier of these solenoids
had already delivered 10,000 5.5 - litre solenoids, thus they were used in production.
Action: The introduction of the 5.5 litre solenoid is not expected to make any dramatic change to
the coolers operation. However there is a slight increase of water hammer occurring on the
premises. Tests conducted by our R&D department have proved that the hammer spike generated
by the 5.5 litre ELBI is no greater than our previous 12 litre soft close solenoid. Technicians can
identify the new 5.5 litre solenoid by a blue label that has been placed on the side of the solenoid
valve body.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 13/01/2004
Category: Specification Sheet - Cooler
Subject: Contour L 13
Sizing Guide Reference Figure 1000 - 1450
Cabinet detail
Width 1100 mm
Height front 720 mm
Height back 400 mm
Length 1100 mm
Dry Weight 48.5 kg
Wet Weight 65.2 kg
Filter Pad Details Water Treatment Unit
Quantity 4 Type WE-1
Thickness 60 mm Rating 240 V / 50 Hz 10 Watt
Type CELDEK 5090 Amps 0.12
Air/Gas Flow Rate 1 L/minute minimum flow
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
855BNVA-A12 Winding Resistance 206 Ohms (+/- 8% @ 20oC)
Watts 315 Overflow size 40 mm
Amps 2.4 Waste Outlet Size 40 mm
R.P.M. 1400 Tank Capacity 12 Litres
Capacitor Size 8 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1250 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 2 Inlet Valve Capacity 4 L or 5.5L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor ServoSeal Motor
Size 538 mm Dia. Type S.A.I.A
Type BRIVIS 538-6-23 Rating 240 V 50 Hz 0.23 Watt
Blades 6 RPM 500
Blade Angle 23 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 Networker NC-3
BWC-1 (Electronic)
BWC-2 (Manual)
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 13/01/2004
Category: Specification Sheet - Cooler
Subject: Contour L 23
Sizing Guide Reference Figure 1250 - 1800
Cabinet detail
Width 1100 mm
Height front 720 mm
Height back 400 mm
Length 1100 mm
Dry Weight 49.5 kg
Wet Weight 67.3 kg
Filter Pad Details Water Treatment Unit
Quantity 4 Type WE-1
Thickness 75 mm Rating 240 V / 50 Hz 10 Watt
Type CELDEK 5090 Amps 0.12
Air/Gas Flow Rate 1 L/minute minimum flow
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
855BNVA-A12 Winding Resistance 206 Ohm (+/- 8% @ 20oC)
Watts 315 Overflow size 40 mm
Amps 2.4 Waste Outlet Size 40 mm
R.P.M. 1400 Tank Capacity 12 Litres
Capacitor Size 8 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1350 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 1 Inlet Valve Capacity 4 L or 5.5L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor ServoSeal Motor
Size 538 mm Dia. Type S.A.I.A
Type BRIVIS 538-6-23 Rating 240 V 50 Hz 0.23 Watt t
Blades 6 RPM 500
Blade Angle 23 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 Networker N-C3
BWC-2 (Manual)
BWC-1 (Electronic)
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 13/01/2004
Category: Specification Sheet - Cooler
Subject: Contour L 33
Sizing Guide Reference Figure 1500 - 2250
Cabinet detail
Width 1100 mm
Height front 720 mm
Height back 400 mm
Length 1100 mm
Dry Weight 51.5 kg
Wet Weight 70.4 kg
Filter Pad Details Water Treatment Unit
Quantity 4 Type WE-1
Thickness 90 mm Rating 240 V / 50 Hz 10 Watt
Type CELDEK 5090 Amps 0.12
Air/Gas Flow Rate 1 L/minute minimum flow
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
80855BQVA-A22V Winding Resistance 206 Ohms (+/- 8% @ 20oC)
Watts 750 Overflow size 40 mm
Amps 4.9 Waste Outlet Size 40 mm
R.P.M. 1350 Tank Capacity 12 Litres
Capacitor Size 25 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1250 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 2 Inlet Valve Capacity 4 L or 5.5L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor ServoSeal Motor
Size 538 mm Dia. Type S.A.I.A
Type BRIVIS 538-11-30 Rating 240 V 50 Hz 0.23 Watt
Blades 11 RPM 500
Blade Angle 30 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 Networker N-C3
BWC-2 (Manual)
BWC-1 (Electronic)
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 15/01/2004
Category: Specification Sheet - Cooler
Subject: Contour L 43
Sizing Guide Reference Figure 2000 - 2750
Cabinet detail
Width 1100 mm
Height front 800 mm
Height back 480 mm
Length 1100 mm
Dry Weight 54.5 kg
Wet Weight 75.0 kg
Filter Pad Details Water Treatment Unit
Quantity 4 Type WE-1
Thickness 90 mm Rating 240 V / 50 Hz 10Watt
Type CELDEK 5090 Amps 0.12
Air/Gas Flow Rate 1 L/minute minimum flow
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
80855BQVA-A22V Winding Resistance 206 Ohm (+/- 8% @ 20oC)
Watts 750 Overflow size 40 mm
Amps 4.9 Waste Outlet Size 40 mm
R.P.M. 1350 Tank Capacity 12 Litres
Capacitor Size 25 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1250 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 2 Inlet Valve Capacity 4 L or 5.5L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor ServoSeal Motor
Size 538 mm Dia. Type S.A.I.A
Type BRIVIS 538-11-30 Rating 240 V 50 Hz 0.23 Watt
Blades 11 RPM 500
Blade Angle 30 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 Networker N-C3
BWC-2 (Manual)
BWC-1 (Electronic)
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 15/01/2004
Category: Specification Sheet - Cooler
Subject: Contour L 53
Sizing Guide Reference Figure 2400 - 3200
Cabinet detail
Width 1100 mm
Height front 800 mm
Height back 480 mm
Length 1100 mm
Dry Weight 55.6 kg
Wet Weight 77.8 kg
Filter Pad Details Water Treatment Unit
Quantity 4 Type WE-1
Thickness 110 mm Rating 240 V / 50 Hz 10 Watt
Type CELDEK 5090 Amps 0.12
Air/Gas Flow Rate 1 L/minute minimum flow
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
80855BQVA-A22V Winding Resistance 206 Ohm (+/- 8% @ 20oC)
Watts 750 Overflow size 40 mm
Amps 4.9 Waste Outlet Size 40 mm
R.P.M. 1350 Tank Capacity 12 Litres
Capacitor Size 25 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1350 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 1 Inlet Valve Capacity 4 L or 5.5L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor ServoSeal Motor
Size 538 mm Dia. Type S.A.I.A
Type BRIVIS 538-11-30 Rating 240 V 50 Hz 0.23 Watt
Blades 11 RPM 500
Blade Angle 30 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 Networker N-C3
BWC-2 (Manual)
BWC-1 (Electronic)
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 15/01/2004
Category: Specification Sheet - Cooler
Subject: Contour L 63
Sizing Guide Reference Figure 2900 - 3600
Cabinet detail
Width 1100 mm
Height front 800 mm
Height back 480 mm
Length 1100 mm
Dry Weight 56.6 kg
Wet Weight 80.3 kg
Filter Pad Details Water Treatment Unit
Quantity 4 Type WE-1
Thickness 130 mm Rating 240 V / 50 Hz 10 Watt
Type CELDEK 5090 Amps 0.12
Air/Gas Flow Rate 1 L/minute minimum flow
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
80855BQVA-A22V Winding Resistance 206 Ohm (+/- 8% @ 20oC)
Watts 750 Overflow size 40 mm
Amps 4.9 Waste Outlet Size 40 mm
R.P.M. 1350 Tank Capacity 12 Litres
Capacitor Size 25 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1350 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 1 Inlet Valve Capacity 4 L or 5.5L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor ServoSeal Motor
Size 538 mm Dia. Type S.A.I.A
Type BRIVIS 538-11-30 Rating 240 V 50 Hz 0.23 Watt
Blades 11 RPM 500
Blade Angle 30 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 Networker N-C3
BWC-2 (Manual)
BWC-1 (Electronic)
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 15/01/2004
Category: Specification Sheet - Cooler
Subject: Profiler P 23
Sizing Guide Reference Figure 1250 - 1800
Cabinet detail
Width 1100 mm
Height front 720 mm
Height back 400 mm
Length 1100 mm
Dry Weight 47.0 kg
Wet Weight 64.8 kg
Filter Pad Details
Quantity 4
Thickness 75 mm
Type CELDEK 5090
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
855BNVA-A12 Winding Resistance 206 Ohm (+/- 8% @ 20oC)
Watts 315 Overflow size 40 mm
Amps 2.4 Waste Outlet Size 40 mm
R.P.M. 1400 Tank Capacity 12 Litres
Capacitor Size 8 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1350 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 1 Inlet Valve Capacity 4 L or 5.5L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor Auto Refresh Tube
Size 538 mm Dia.. Type S.A.I.A
Type BRIVIS 538-6-23 Rating 240 V 50 Hz 0.23 Watt
Blades 6 RPM 500
Blade Angle 23 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 BWC-1 (Electronic)
BWC-2 (Manual)
Networker N-C3
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 15/01/2004
Category: Specification Sheet - Cooler
Subject: Profiler P 33
Sizing Guide Reference Figure 1500 - 2250
Cabinet detail
Width 1100 mm
Height front 720 mm
Height back 400 mm
Length 1100 mm
Dry Weight 48.2 kg
Wet Weight 66.0 kg
Filter Pad Details
Quantity 4
Thickness 75 mm
Type CELDEK 5090
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
80855BQVA-A22V Winding Resistance 206 Ohm (+/- 8% @ 20oC)
Watts 750 Overflow size 40 mm
Amps 4.9 Waste Outlet Size 40 mm
R.P.M. 1350 Tank Capacity 12 Litres
Capacitor Size 25 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1250 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 2 Inlet Valve Capacity 4 L or 5.5L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor Auto Refresh Tube
Size 538 mm Dia.. Type S.A.I.A
Type BRIVIS 538-11-30 Rating 240 V 50 Hz 0.23 Watt
Blades 11 RPM 500
Blade Angle 30 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 BWC-2 (Electronic)
BWC-1 (Manual)
Networker N-C3
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 15/01/2004
Category: Specification Sheet - Cooler
Subject: Profiler P 43
Sizing Guide Reference Figure 2000 - 2750
Cabinet detail
Width 1100 mm
Height front 720 mm
Height back 400 mm
Length 1100 mm
Dry Weight 49.0 kg
Wet Weight 67.9 kg
Filter Pad Details
Quantity 4
Thickness 90 mm
Type CELDEK 5090
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
80855BQVA-A22V Winding Resistance 206 Ohm (+/- 8% @ 20oC)
Watts 750 Overflow size 40 mm
Amps 4.9 Waste Outlet Size 40 mm
R.P.M. 1350 Tank Capacity 12 Litres
Capacitor Size 25 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1250 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 1 Inlet Valve Capacity 4 L or 5.5L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor Auto Refresh Tube
Size 538 mm Dia. Type S.A.I.A
Type BRIVIS 538-11-30 Rating 240 V 50 Hz 0.23 Watt
Blades 11 RPM 500
Blade Angle 30 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 BWC-1 (Electronic)
BWC-2 (Manual)
Networker N-C3
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 15/01/2004
Category: Specification Sheet - Cooler
Subject: Profiler P 53
Sizing Guide Reference Figure 2400 - 3200
Cabinet detail
Width 1100 mm
Height front 720 mm
Height back 400 mm
Length 1100 mm
Dry Weight 49.9 kg
Wet Weight 70.2 kg
Filter Pad Details
Quantity 4
Thickness 110 mm
Type CELDEK 5090
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
80855BQVA-A22V Winding Resistance 206 Ohm (+/- 8% @ 20oC)
Watts 750 Overflow size 40 mm
Amps 4.9 Waste Outlet Size 40 mm
R.P.M. 1350 Tank Capacity 12 Litres
Capacitor Size 25 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1350 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 1 Inlet Valve Capacity 4 L or 5.5L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor Auto Refresh Tube
Size 538 mm Dia.. Type S.A.I.A
Type BRIVIS 538-11-30 Rating 240 V 50 Hz 0.23 Watt
Blades 11 RPM 500
Blade Angle 30 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 BWC-1 (Electronic)
BWC-2 (Manual)
Networker N-C3
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 15/01/2004
Category: Specification Sheet - Cooler
Subject: Profiler P 63
Sizing Guide Reference Figure 2900 - 3600
Cabinet detail
Width 1100 mm
Height front 720 mm
Height back 400 mm
Length 1100 mm
Dry Weight 50.7 kg
Wet Weight 72.3 kg
Filter Pad Details
Quantity 4
Thickness 130 mm
Type CELDEK 5090
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
80855BQVA-A22V Winding Resistance 206 Ohm (+/- 8% @ 20oC)
Watts 750 Overflow size 40 mm
Amps 4.9 Waste Outlet Size 40 mm
R.P.M. 1350 Tank Capacity 12 Litres
Capacitor Size 25 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1350 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 1 Inlet Valve Capacity 4 L or 5.5L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor Auto Refresh Tube
Size 538 mm Dia. Type S.A.I.A
Type BRIVIS 538-11-30 Rating 240 V 50 Hz 0.23 Watt
Blades 11 RPM 500
Blade Angle 30 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 BWC-1 (Electronic)
BWC-2 (Manual)
Networker N-C3
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 06/06/2005
Category: Specification Sheet - Cooler
Subject: Brivis Advance F 13
Sizing Guide Reference Figure 1000 - 1450
Cabinet detail
Width 1100 mm
Height front 590 mm
Height back 590mm
Length 1100 mm
Dry Weight 47 kg
Wet Weight 65 kg
Filter Pad Details
Quantity 4
Thickness 60 mm
Type CELDEK 5090
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
855BNVA-A12 Winding Resistance 206 Ohm (+/- 8% @ 20oC)
Watts 315 Overflow size 40 mm
Amps 2.4 Waste Outlet Size 40 mm
R.P.M. 1400 Tank Capacity 15 Litres
Capacitor Size 8 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1250 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 2 Inlet Valve Capacity 4 L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor Auto Refresh Tube
Size 538 mm Dia.. Type S.A.I.A
Type BRIVIS 538-23-6 Rating 240 V 50 Hz 0.23 Watt
Blades 6 RPM 500
Blade Angle 23 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 BWC-1 (Electronic)
BWC-2 (Manual)
Networker N-C3
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 06/06/2005
Category: Specification Sheet - Cooler
Subject: Brivis Advance F 23
Sizing Guide Reference Figure 1250 - 1800
Cabinet detail
Width 1100 mm
Height front 590 mm
Height back 590mm
Length 1100 mm
Dry Weight 47.5 kg
Wet Weight 65.5 kg
Filter Pad Details
Quantity 4
Thickness 75 mm
Type CELDEK 5090
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
855BNVA-A12 Winding Resistance 206 Ohm (+/- 8% @ 20oC)
Watts 315 Overflow size 40 mm
Amps 2.4 Waste Outlet Size 40 mm
R.P.M. 1400 Tank Capacity 15 Litres
Capacitor Size 8 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1350 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 1 Inlet Valve Capacity 4 L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor Auto Refresh Tube
Size 538 mm Dia. Type S.A.I.A
Type BRIVIS 538-6-23 Rating 240 V 50 Hz 0.23 Watt
Blades 6 RPM 500
Blade Angle 23 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 BWC-1 (Electronic)
BWC-2 (Manual)
Networker N-C3
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 06/06/2005
Category: Specification Sheet - Cooler
Subject: Brivis Advance F 33
Sizing Guide Reference Figure 1500 - 2250
Cabinet detail
Width 1100 mm
Height front 590 mm
Height back 590mm
Length 1100 mm
Dry Weight 49 kg
Wet Weight 67 kg
Filter Pad Details
Quantity 4
Thickness 75 mm
Type CELDEK 5090
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
80855BQVA-A22V Winding Resistance 206 Ohm (+/- 8% @ 20oC)
Watts 750 Overflow size 40 mm
Amps 4.9 Waste Outlet Size 40 mm
R.P.M. 1350 Tank Capacity 15 Litres
Capacitor Size 25 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1150 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 3 Inlet Valve Capacity 4 L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor Auto Refresh Tube
Size 538 mm Dia. Type S.A.I.A
Type BRIVIS 538-11-30 Rating 240 V 50 Hz 0.23 Watt
Blades 11 RPM 500
Blade Angle 30 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 BWC-1 (Electronic)
BWC-2 (Manual)
Networker N-C3
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 06/08/2005
Category: Specification Sheet - Cooler
Subject: Brivis Advance F 43
Sizing Guide Reference Figure 1750 - 2500
Cabinet detail
Width 1100 mm
Height front 680 mm
Height back 680mm
Length 1100 mm
Dry Weight 50.5 kg
Wet Weight 69 kg
Filter Pad Details
Quantity 4
Thickness 75 mm
Type CELDEK 5090
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
80855BQVA-A22V Winding Resistance 206 Ohm (+/- 8% @ 20oC)
Watts 750 Overflow size 40 mm
Amps 4.9 Waste Outlet Size 40 mm
R.P.M. 1350 Tank Capacity 15 Litres
Capacitor Size 25 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1250 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 2 Inlet Valve Capacity 4 L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor Auto Refresh Tube
Size 538 mm Dia. Type S.A.I.A
Type BRIVIS 538-11-30 Rating 240 V 50 Hz 0.23 Watt
Blades 11 RPM 500
Blade Angle 30 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 BWC-1 (Electronic)
BWC-2 (Manual)
Networker N-C3
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Brivis Technical Data
Type: Technical Data Base Date Updated: 06/08/2005
Category: Specification Sheet - Cooler
Subject: Brivis Advance F 53
Sizing Guide Reference Figure 2250 - 3000
Cabinet detail
Width 1100 mm
Height front 680 mm
Height back 680mm
Length 1100 mm
Dry Weight 51 kg
Wet Weight 69.5 kg
Filter Pad Details
Quantity 4
Thickness 90 mm
Type CELDEK 5090
Duct Outlet Size
Width 550 mm
Length 550 mm
Pump / Water Distribution
Motor Pump Type ASKOLL M115
Type 240 V - 1 ph Pump Rating 240 V / 0.2 Amps
Model FASCO Pump Capacity 20 L/minute
80855BQVA-A22V Winding Resistance 206 Ohm (+/- 8% @ 20oC)
Watts 750 Overflow size 40 mm
Amps 4.9 Waste Outlet Size 40 mm
R.P.M. 1350 Tank Capacity 15 Litres
Capacitor Size 25 uF Distribution Hose Size 20 mm CLEAR HOSE
R.P.M Min Setting 500 Inlet Valve Type ELBI E.V Type 329
R.P.M Max Setting 1350 Inlet Valve Rating 240 V - 0.03 Amps
N-E5 Model Selection Model 1 Inlet Valve Capacity 4 L/minute
Coil Resistance 4.1 kOhm approx. @ 20oC
Inlet Valve Size 3/4" BSP (Male) Thread
Fan Impellor Auto Refresh Tube
Size 538 mm Dia. Type S.A.I.A
Type BRIVIS 538-11-30 Rating 240 V 50 Hz 0.23 Watt
Blades 11 RPM 500
Blade Angle 30 deg TIP Resistor 470 Ohm
Collet BRIVIS Capacitor 100 nF
Cooler Control Module Wall Controller
N-E5 BWC-1 (Electronic)
BWC-2 (Manual)
Networker N-C3
Water Connection
Flexible Hose Connection with 1/2" BSP (Male) Thread
Drain Connection
40 mm PVC

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Motor Circuit Diagram
MOTOR WIRING CIRCUIT DIAGRAM
BETTS 855 BNVA - A12
MOTOR - 315 WATT
DIRECT WIRED
GREEN /YELLOW
BROWN
BLUE(COMMON)
START 38.8
MAIN 10.6
EARTH
BLACK (START)
OVERLOAD
CAPACITOR 8 u/F

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Motor Circuit Diagram
MOTOR - 750 WATT
DIRECT WIRED
BETTS MODEL - 808855BQVA - A22V
GREEN /YELLOW
BROWN (RUN)
BLUE(COMMON)
START 9.6
MAIN 4.4
EARTH
BLACK (START)
OVERLOAD
CAPACITOR 25 u/F

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
INSTALLER COMMISSIONING INSTRUCTIONS
Wiring the Cooler to the Networker
The first step is to run a twin wire cable (i.e. figure 8 cable - 0.75mm2) from the
Cooler to the Networker.
Next, mount the Networker backing plate. Remove the backing plate from the
Networker by un-clipping.
Be sure to draw the wires from the wall cavity, and feed them through the centre
opening of the wall plate. Then mount the wall plate on the wall.
Connect the cable to the Networker connection lead terminal block at the Cooler, and
to either the top two terminals or the bottom two terminals on the Networker Backing
plate. If these two pairs of terminals are mixed around the Networker will not function.
Networker
If the Cooler is integrated with a Brivis MPS or Auto EMS heater(s), then simply
connect the wiring in parallel with the heater's circuit to the Networker.
Networker
Control
TW 1
TW 2
NET
WORKER

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
INSTALLER COMMISSIONING
INSTRUCTIONS;
(cont.)
Wiring the Cooler to the Networker;
(cont.)
If more than one Cooler is connected on the system to one Networker, then all the
coolers will be wired in parallel to the Networker as shown. Ensure each Cooler is
then configured correctly to the Networker, using the instructions on page 24.
Networker
Cooler No. 1
Cooler No. 2
Cooler No. 3

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Installing Multiple Coolers on the Network
The Networker is capable of controlling multiple evaporative coolers on the one
system.
When more than one Cooler is installed on a Networker, each Cooler must be given a
different specific identification number, starting at No. 1, and each Cooler must
also be designated to a zone (refer to the Networker - Advanced Programming
Manual).
First, complete the installation and wiring of all the units, as described on page 23.
Each Cooler must be powered and configured individually, whenever any Cooler
identification number is to be changed.
Isolate the power from all other coolers and Network appliances, other than the unit
which the identification number is being changed, and proceed to make the change at
the Networker wall control through the Installer Set-Up program as follows:
•
Turn the Networker OFF (ON/OFF button).
•
Press the Clock key to enter "Clock Set-Up" program.
Now simultaneously press and hold the 2nd & 4th keys for 3 - 5 seconds, until the
screen changes to display:
E01 ID07 :1
Unit Number Parameter Number Parameter Value
Eg- Evap cooler number 1 Eg- Number seven Eg- Setting of 1
Note: This is the view on the N-C3 Networker.
•
Rotate the circular dial to change the parameter value displayed at the top left of
screen, to the unit number required for this Cooler.
E01 ID07 :2
Unit Number Parameter Number Parameter Value
Eg- Evap cooler number 1 Eg- Number seven Eg- Setting of 1
Note: This is the view on the N-C3 Networker.
•
Press the Networker ON/OFF button and exit the program.
•
Turn the power supply at the Cooler OFF, to save the new identification
number.
•
Repeat the sequence for each Cooler, then follow the Networker Advanced
Programming instructions to allocate the Coolers to their respective Networker
zones.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Installing dual Networkers on a system
The new Networker N-C3 now allows two Networkers to be installed onto the one
system.
When installing two Networkers on a system, they must be wired in parallel to the
system; they cannot be wired in series as they will not function correctly. The
Networkers are not polarity sensitive.
Both Networkers must be identified individually so that they can communicate
together. One of the Networkers must be the master and the other must be the slave.
On a dual Networker installation the Master Networker always stores all of the
installer and service parameters, and all of the customers settings eg. Programming
and clock settings; The Master Networker can be identified by the CLOCK key, when
the Networker is in the OFF position.
Note: Only the Master Networker can access the installer or service
parameters.
There is only one room temperature set point, which can be adjusted on either
Networker. An Adjustment that is made on one Networker is immediately reflected on
the other Networker.
Once each Networker is given its specific Networker ID number or address (Master=1
or Slave=2), they can be assigned to operate the zones according to difference
between the sensed temperature and the set temperature. Every Zone must be
assigned a Networker for temperature control, The Master Networker is the default
Networker for every zone. However this can be altered to the most appropriate
Networker (e.g. Networker: 2 = Slave).
A new parameter has been added to the Networker zoning parameters to allow for
this Networker Zone assigning.
n01 ID29:1
Evap Common Zone, Unit Number
Evap
ID
No.
n01 ID30:0
Evap Common Zone, Networker Temp Sense
Networker
ID No
.
n01 ID31:0
Evap Zone A, Unit Number
Evap
ID
No.
n01 ID32:0
Not Used
Not Used
n01 ID30:0
Evap Zone A, Networker Temp Sense
Networker
ID No.
n01 ID34:0
Evap Zone B, Unit Number
Evap
ID
No.
n01 ID35:0
Not Used
n01 ID30:0
Evap Zone B, Networker Temp Sense
Networker
ID No
.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Installing dual Networkers on a system
Follow these procedures when configuring the two Networkers. The two Networkers
must be configured as master or slave. The Networkers should never be configured
as both masters or both slaves as the system will malfunction. Because all
Networkers come set as masters by default, only the Slave needs to be addressed.
Method 1 can only be used if both Networkers are masters. Refer to method 2 if the
Master and Slave Networkers are to be reversed, or if both Networkers have been set
to Slave by mistake.
Method 1 (new installation).
•
Connect both Networkers to the appliance and power the system up. At this stage
both Networkers will be set as Masters, so both Networkers should have the word
"clock" next to key 5 (while in the off position). The system should not be operated
in this state as there will be communication errors.
•
Determine which Networker you wish to be the Slave.
•
On the Networker you wish to be slave, push the clock key. The message “Clock
setting mode.” should be displayed.
•
After the message has finished, ensure the time on the display is flashing. Press
keys 2 & 4 for 5 seconds until the message "Installer parameter access." is
displayed.
•
By pushing the Mode key, this will move through the different appliances attached
to the system (e.g. Cooler/Heater/Networker). Push the Mode key until the screen
display looks like this.
Unit Number Parameter ID Number Parameter Value Setting.
n01 ID00 :1
Networker ID Networker Address parameter Address setting 1=Master 2=Slave
•
Using the rotary dial, change the parameter value to 2 (2=Slave).
•
Push the On/Off key to exit.
•
The unit should then be ready for zone configuration.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Installer Set-Up Programming.
Dual Networker Configuration: (cont.).
Method 2.
•
Remove the Slave Networker off the backing plate so that the controller is
powered down.
•
Press and hold keys 3 & 5, then place the Networker on the backing plate
ensuring keys 3 & 5 are still depressed. Continue holding keys 3 & 5 for five
seconds after the control is placed on the backing plate.
•
After holding keys 3 & 5 for five seconds, release the two keys. The screen should
now scroll this message “Set this Networker’s address!” If the message does
not appear please repeat the resetting procedure.
•
After the message has finished, the screen should look like this. Now the
parameter value for setting Master and Slave addresses can be set.
Networker ID
•
Rotate the circular dial to change the parameter value (displayed at the top right of
screen) to the number required for Slave. Refer to the table for settings e.g. Slave
= 2. The Master Networker address can also be set if necessary.
Networker Address or Number
Parameter ID
Number and
Value
Parameter Description Parameter Value Settings
•
Once this parameter value has been set, push the ON/OFF button to exit this
Installer set-up program.
Note: All networkers come configured as masters by default. Two masters cannot be
connected to one system otherwise the system will not function properly. Similarly if
both networkers are set as slaves, the networkers will lock out and will not be
accessible. If this has been done, the resetting procedure needs to be performed
again to rectify this problem.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Networker Installer Parameters
N-C3 Zoning Parameters
Parameter ID Number
and Value
Settings
n01 ID00:1
Networker Address or ID Number Master = 1 or Slave = 2
n01 ID01:1
Refrig Common Zone, Unit Number
Refrig/Heater
ID No.
n01 ID02:0
Refrig Common Zone - Networker Temp Sense
Networker
ID No.
n01 ID03:0
Refrig Zone A, Unit Number
Refrig/Heater
ID No.
n01 ID04:0
Refrig Zone A, Relay Number
Relay
No. 1 to 4
n01 ID05:0
Refrig Zone A - Networker Temp Sense
Networker
ID No.
n01 ID06:0
Refrig Zone B, Unit Number
Refrig/Heater
ID No.
n01 ID07:0
Refrig Zone B, Relay Number
Relay
No. 1 to 4
n01 ID08:0
Networker
ID No.
n01 ID09:0
Refrig Zone C, Unit Number
Refrig/Heater
ID No.
n01 ID10:0
Refrig Zone C, Relay Number
Relay
No. 1 to 4
n01 ID11:0
Refrig Zone C - Networker Temp Sense
Networker
ID No.
n01 ID12:0
Refrig Zone D, Unit Number
Refrig/Heater
ID No.
n01 ID13:0
Refrig Zone D, Relay Number
Relay
No. 1 to 4
n01 ID14:0
Refrig Zone D - Networker Temp Sense
Networker
ID No.
n01 ID15:1
Heater Common Zone, Unit Number
Heater
ID
No.
n01 ID16:0
Networker
ID No.
n01 ID17:0
Heater Zone A, Unit Number
Heater
ID
No.
n01 ID18:0
Heater Zone A, Relay Number
Relay
No. 1 to 4
n01 ID19:0
Heater Zone A - Networker Temp Sense
Networker
ID No.
n01 ID20:0
Heater Zone B, Unit Number
Heater
ID
No.
n01 ID21:0
Heater Zone B, Relay Number
Relay
No. 1 to 4
n01 ID22:0
Heater Zone B - Networker Temp Sense
Networker
ID No.
n01 ID23:0
Heater Zone C, Unit Number
Heater
ID
No.
n01 ID24:0
Relay
No. 1 to 4
n01 ID25:0
Networker
ID No.
n01 ID26:0
Heater Zone D, Unit Number
Heater
ID
No.
n01 ID27:0
Heater Zone D, Relay Number
Relay
No. 1 to 4
n01 ID28:0
Heater Zone D - Networker Temp Sense
Networker
ID No.
n01 ID29:1
Evap Common Zone, Unit Number
Evap
ID
No.
n01 ID30:0
Evap Common Zone - Networker Temp Sense
Networker
ID No.
n01 ID31:0
Evap Zone A, Unit Number
Evap
ID
No.
n01 ID32:0
Networker
ID No.
n01 ID34:0
Evap Zone B, Unit Number
Evap
ID
No.
n01 ID35:0
Not Used
Not Used
n01 ID36:0
Evap Zone B - Networker Temp Sense
Networker
ID No.
n01 ID37:0
Evap Zone C, Unit Number
Evap
ID
No.
n01 ID38:0
Not Used
n01 ID39:0
Evap Zone C - Networker Temp Sense
Networker
ID No.
n01 ID40:0
Evap Zone D, Unit Number
Evap
ID
No.
n01 ID41:0
Networker
ID No.
n01 ID43:0
Heating OFF cycle Circulation Fan Operation

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Service Parameters
•
To access the Cooler's service parameters, you must first enter the installer
parameters.
•
Turn the Networker OFF.
•
Press Clock key to enter "Clock Set-Up" program.
•
Now simultaneously press and hold the 2nd & 4th keys for 3 - 5 seconds, until the
screen changes to display:
E01 ID07 :1
Unit Number Parameter Number Parameter Value
Eg- Evap cooler number 1 Eg- Number seven Eg- Setting of 1
Display shown is N-C3 Networker
•
Next enter the special service access code on the Networker, and the screen will
move into the service parameter section.
•
Press the mode key to select the appropriate appliance, i.e. Networker or Heater
or Cooler.
•
To change to the parameter number requiring adjustment, press the top button to
select the next parameter number, and the second button to select the previous
parameter number.
•
Rotate the dial when the appropriate parameter number is selected, to vary the
value as displayed.
Typical display when entering adjustment mode:
E01 ID01 :60
Unit Number Parameter Number Parameter Value
Display shown is N-C3 Networker
The values may be presented in the following units:
•
Time increment of either; seconds, minutes or hours.
•
RPM.
•
Numerical number where 0 = OFF & 1 or above = ON.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Parameters
N-E5 Parameter Table:
Parameter Name
Number
Range Units Default Parameter Description
Installer Parameters
Unit ID Number
7 1 - 15. number 1 Changes the unit identification
number for multiple unit
installations.
Installer Flush Count
14 1 - 20. cycles 20 Number of tank refills before a
Dump Check
16 0 - 1 number 0 Used to check the dump
operation. If set to 1.
Must be
set back to 0 after dumping
occurs.
Service Parameters
Dump delay
1 1 - 255 10
minutes
6 Time delay after use before
dumping occurs. See servicing
instruction 21 on page 3.
6 x 10 minutes = 60 minutes
Fill time
2 1 - 255 minutes 15 Time allowed for the trough
water level to reach high level
Min Fan Speed
3 0 -125 10 x
RPM
Minimum fan speed
Max Fan Speed
4 60 -135 10 x
Maximum fan speed
Model Selection
Number
5 1 - 7. 1 Cooler model selection
number. Sets the default fan
speed by selecting the unit
number as per the
Specification sheets.
Short Dry Pad Time
13 1 - 255 minutes 2 Time the pump can be off
before a normal Pre-Wet is
necessary.
Service Flush Count
15 1 - 255 cycles See
notes
Number of tank refills before a
flush will occur.
Profiler (no Aquasave) = 20
Contour (no Aquasave) = 20
Contour (with Aquasave) = 250
Long Pre-wet Time
19 1 - 255 seconds
120 Extended Pre-wet time.
Long Dry Pad Time
20 1 - 255 minutes 10 Time the pump can be off
before an extended Pre-Wet is
required
Status Mode
21 0 - 2 2 Do not alter/ not used.
Aquasave
22 0 - 1 number 0 or 1 Is used when an Aquasave
present on the cooler.
Brivis Contour = 1
Brivis Profiler = 0
Flush time
43 1-255 seconds
200 Time solenoid is open during a
flush service.
Contour 0 series = 100 sec
Contour 1 series = 60 sec
Contour 2 series = 200 sec
Contour 3 series = 200 sec

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Parameters
N-E5 Installer Parameter Descriptions:
Unit ID Number - Installer Parameter 07 - This is where the unit can be assigned a
different unit ID number for multiple cooler installations. See section on Installing
Multiple Coolers on the Network.
Installer Flush Count - Installer Parameter 14 - This is the number of filling
operations, between the high and low water sensors, due to the evaporation of water
during operation, before the tank will be flushed to dilute the salt build up. This
parameter allows the installer to increase occurrence of the flush operation if
necessary. The installer cannot decrease the units flush operation above every 20
refills.
Dump Check - Installer Parameter 16 - This parameter was provided so that the
cooler Dump-valve and Winter-seal operation could be checked instantly upon
installation. By setting this parameter to 1, the cooler will instantly perform a dump
and close the Servoseal, and after the normal delay times it will then resume normal
operation. This dump function will only occur once, upon power up of the unit. This
means if the parameter is left on 1 the cooler will perform its dump check then
resume normal operation, but if a power interruption occurs the unit will immediately
perform another dump check. The results of leaving this setting on 1 is the possible
chance for extra long start up time, because the cooler will initially open the
Servoseal, then close the Servoseal and wait for the usual dump time to elapse
before opening the Servoseal again and performing the normal start up procedure.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Parameters
N-E5 Service Parameter Descriptions:
Riser Close Delay - This is the time delay in minutes from when both the fan and the
pump stop operating until the Servoseal closes and the drain tube lowers to drain the
tank water. See servicing instruction 21 in the front of this manual.
Fill Time - This is the time in minutes, from when the water inlet solenoid opens and
water must be sensed on either of the water level probes, before a lockout will occur.
Min Speed / Max Speed - These are the adjustment parameters, to vary the
minimum and maximum fan RPM from the default settings as per the N-E5 model
selection. It is not possible to set the minimum speed higher than the maximum
speed, and vice versa.
Model Selection Number - Model selection number should be set as per spec
sheets information.
Short Dry Pad Time - This is the time in minutes, the pump can be OFF and the filter
pads not wetted, before a Pre-wet will be required.
Service Flush Count - This is the number of filling operations, between the high and
low water sensors, due to the evaporation of water during operation, before the tank
will be flushed to dilute the salt build up. Service technicians can adjust the
occurrence of the flush operation if necessary.
Short Pre-wet Time - This is the Pre-wet time in seconds, that occurs if the pump
has been OFF longer than the Short Dry Pad Time, and less than the Long Dry Pad
Time.
Long Pre-wet Time - This is the Pre-wet time in seconds, that occurs if the pump has
been OFF longer than the Long Dry Pad Time.
Long Dry Pad Time - This is the time in minutes, the pump can be OFF and the filter
pads not wetted, before a Long Pre-wet will be required.
Aquasave - The Aquasave is a standard feature on the 3 series Contours. The
Aquasave is wired directly into the N-E5 base connector. The parameter settings are
1=Aquasave present, 0=No Aquasave.
Flush Time - The time the solenoid is open during a flush service operation.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
General Operation
When the Networker is turned OFF, or is in a mode other than "Cooler", then the
Contour Cooler will have the ServoSeal closed (Contours only), and the tank drained,
provided the unit has been in the OFF condition for longer than 60 minutes.
When the Networker is turned ON in Cooler mode, no function will occur until the
Networker signals the Cooler to operate, i.e. the ServoSeal (Contours only) will
remain closed and the tank empty.
If either the fan or the pump is required to operate, then the ServoSeal (Contours
only) will be driven open, before any other activity can run. The ServoSeal has a
direct linkage to the drain valve, and the drain valve closes as the ServoSeal opens,
and vice versa. Profiler Models do not have the Servoseal installed, but the drain
valve will operate off the same mechanism.
The ServoSeal opening delay time is 20 seconds.
On completion of the ServoSeal opening and drain valve closing action, if the
Networker calls for the pump to operate, the water inlet solenoid will be energised to
open, and the tank will begin to fill with water.
The N-E5 module will not permit the pump to be energised, until the water has
reached the high water level, on the Trident water management system.
After pump commencement the water level will possibly drop below the High level on
the Trident water sensor, so the inlet solenoid will remain open for another 10
seconds.
If the Cooler pump has been OFF longer than 2 minutes the Cooler is programmed to
automatically Pre-wet the filter pads when the pump is turned ON, before the fan
can start operating for both Networker Auto and Manual modes.
This is to ensure in all circumstances the filter pads reach full saturation and optimum
cooling potential when the fan starts.
The automatic Pre-wetting time of the dried filter pads, will depend on how long the
Cooler's pump has been OFF, as follows:

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
General Operation:
(cont.)
•
If the pump has been OFF for less than 2 minutes (ShortDryPadTime), then no
Pre-Wet will occur.
•
If the pump has been OFF for less than 10 minutes (LongDryPadTime), but
longer than 2 minutes (ShortDryPadTime), a 1 minute (ShortPrewetTime) will
apply.
•
If the pump has been OFF for longer than 10 minutes (Long DryPad Time) then
a 2 minute (LongPrewetTime) will occur.
•
If the power supply to the N-E5 has been interrupted, the first Pre-wet will be 2
minutes (LongPrewetTime).
Pump On
Pump Off
Pump On Pump On Pump On
Power
Interuption
Time interval from
prior pump
operation more than
2 mins but less than
prior pump
operation less
than 2 mins
Pump On
1 Minute Pre-wet
(Short Pre-wet time)
No Pre-Wet
2 minute Pre-wet
(Long Pre-wet time)
2 minute Pre-wet
(Long Pre-wet time)
Fan On
Time interval from
prior pump
operation more than
10 mins
If the unit is turned OFF (i.e. pump and fan OFF) for longer than 60 minutes
(ServoCloseDelay), the N-E5 module will automatically isolate the water inlet
solenoid, and drive ServoSeal motor, which will drain the trough and close the
dropper duct damper seal (Note: damper not present on Profiler coolers).

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation:
(cont.)
Networker Control in Auto Mode
The following sequences are normal operation in Auto mode, with the Networker at a
set comfort level, and the room temperature varying according to the Cooler's
operation and load conditions.
When the Networker is turned ON in Cooler Auto mode, an immediate signal is sent
to the cooler to indicate if the unit is required to operate or not.
If the comfort level setting is adjusted on the Networker when operating in Cooler
Auto mode, an immediate signal is also sent to the cooler.
Whenever the Networker sends an OFF or ON signal to the N-E5 module, both the
pump and the fan will be turned OFF or ON, however, their operation may be
delayed by the fill and Pre-wet functions.
The Cooler will be turned ON, if the room temperature is 0.50C. higher than the set
comfort level, and OFF if the room temperature is lower.
The ON fan signal from the Networker accompanies a fan speed signal, to determine
the speed required according to the temperature differential between the room
temperature and set comfort level.
The fan will operate at minimum speed, when the room temperature is up to 10C.
above the set comfort level, and is incremented to be at maximum fan speed, when
the room temperature is 50C. or more above the set comfort level.
During normal operation, at 5 minute intervals, the Networker updates the N-E5
module on the temperature differential between room temperature and the set
comfort level, and if the temperature has varied by 0.50C. or more then the cooler is
adjusted.
However, if the temperature changed rapidly by 2.50C. or more within the 5 minute
update interval, then the Networker will signal the N-E5 module to adjust
immediately.
If the room temperature is higher than the set point when the Networker is turned ON,
then the fan will immediately operate at the speed according to the set point, following
the normal ServoSeal, water fill and Pre-wet operations.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation:
(cont.)
Networker Control in Manual Mode
When operating the Cooler in manual mode, the Networker screen changes to
display a pump and fan button for manual selection.
The rotary dial is used to select the constant fan speed.
The Pre-wet times apply to manual mode, in the same way described for Auto mode.
However in manual mode, the Pre-wet period can be extended by simply operating
the pump longer without the fan.
Fan only operation is available for air movement in high humidity climate conditions,
or for ventilation and air circulation.
NOTE: Should the pump be turned ON whilst the fan is operating, then the fan will be
forced OFF for the Pre-wet period, then come back ON again automatically.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation:
(cont.)
Wash Service
When the Networker is turned OFF, at the end of use, or the pump and fan have
been OFF for more than 60 minutes, the ServoSeal closes (Contours) and the drain
valve lowers to drain the tank water.
Following the ServoSeal closing, the Cooler will automatically perform a tank washing
action, after the time delay allowed for closing the ServoSeal ServoTime (20
seconds).
A further 45 second delay (WashWaitTime) allows time for the tank to be drained
completely, and initially wash out any sediment from the tank.
With the drain valve still in the lowered position, the water inlet solenoid is opened for
30 seconds (WashTime), allowing clean water to further flush sediments from the
tank base.
On completion of the wash, an additional 45 second delay applies, before any other
(new) operation can be performed i.e. Networker turned back ON again.
The Cooler then remains idle until the Networker is turned ON again, and calls for
cooling.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Wash Service
(cont.)
Networker ON - No
call for Operation
Call for Fan
Operation
Call for Pump
Operation with
or without Fan
ServoSeal
opens
Delay = 20
seconds
(ServoTime)
Fan turns ON
ServoSeal
opens
Delay = 15
seconds
(ServoTime)
Inlet Valve
opens and
Tank fills
Water at low
level
Pump turns
ON
Pre-Wet time
starts
Pre-Wet
complete
Fan turns ON
if required
Networker turned
OFF or call for
pump and fan to
OFF
Delay = 60 minutes
(ServoCloseDelay)
ServoSeal
Closes 15
seconds
Delay = 45
seconds
(WashWaitTime)
Water Inlet Valve
opens 30 seconds
(WashTime)
Delay = 45
seconds

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Flush Service Operation.
Since the introduction of the Aquasave water treatment module on Contours, the
flushing frequency is different between Contour and a Profiler models. The Contour
flush service parameter is set to 250 while the Profiler flush cycle is set to 20. This
means the Profiler will flush more often than the Contour cooler.
The N-E5 module program performs a tank flush at regular intervals, to dilute any
salt and sediment build up as the unit is operating.
The flush service will not affect the normal pump, or fan functions of the Cooler.
The flush service timing is determined by the number of times the water has filled to
the Trident High Water Level Sensor, and then evaporated down to the Trident Low
Water Level Sensor.
After 20 tank refills, the Flush Service commences.
Each sequence of 20 or 250 refills of the tank, will force another the flush service
operation, although the time between each Flush Service can vary, according to the
conditions and Cooler settings.
When the water level evaporates down to the Low Water Level Sensor for the 20th
tank re fill, the water inlet solenoid will open and fill the tank to the high water
level, then remain open for a further 200 second period.
The water level will continue to rise above the High Water Level Sensor, and over
flow out the drain valve / overflow pipe.
The action of the fresh water entering, mixing and overflowing out from the tank,
dilutes the salt and sediment ratio back to the original supply water condition.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation:
(cont.)
Aquasave Operation:
(Contours Only).
The Aquasave water treatment module was designed to reduce the requirement for
flushing, thus saving water. The module introduces oxidants into to the trough water
through a diffuser ball. These oxidants then prevent the growth of bacteria and microorganisms in the water.
The Aquasave module will only operate when the pump is operating, and has an
internal timer that will cycle the Aquasave on and off. The timer is set to cycle the unit
7 minutes on and 7 minutes off.
The module has an internal air pump which draws the air though a filter located under
the front of the cooler trough. This air then passes through a high intensity spark
where the air is filled with oxidants. There air then passes through a tube to the
diffuser ball which should be submerged beneath the water.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation:
(cont.)
N-E5 Electronic Control Module Operation
The N-E5 module controls all the Cooler's working operations, using the signals from
the Networker sent on a 2 wire bus network. The N-E5 will communicate with the
Networker about the status of the Cooler's operation, including malfunction errors.
The N-E5 can be fitted to any 3 series Contour and Profiler Cooler models, but will
require configuring to the model type, using the service parameters accessed through
the Networker.
The power supply input and output terminals to the N-E5 module, are via the base
terminal connection mounting bracket. The module is correctly located into the
mounting bracket via side slide rails.
The N-E5 module no longer has a isolating switch on the control box itself.
There is a new isolating switch that is located under the front of the cooler
allowing the power to be cut to the unit without removing the front filter pad.
This isolates the output power supply to all components within the Cooler.
There is a new service N-E5 control box which has a switch located on the top
of the box - this is for retrofitting the control into previous model contours.
WARNING: The incoming 240 Volt power supply is not isolated using this switch,
and therefore some terminals within the Cooler will remain energised, until the main
power supply on the unit's 3 pin plug and lead, has been disconnected.
Wiring connections direct to the N-E5 module are, the Networker connection loom,
the motor speed sensor and the water level control looms. All installer and service
parameter access is done through the Networker wall control.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation:
(cont.)
N-E5 Electronic Control Module Operation:
(cont.)
The N-E5 controller is fitted with an internal 8 Amp fuse to protect the PCB circuitry.
The 8 Amp fuse will protect the N-E5 controller from short circuit and/or high current
draw, on the following circuits:
•
Pump
•
Water inlet solenoid
•
Fan motor
•
PCB relays
Important Note:
The N-E5 internal 8 Amp fuse does not protect the control against short circuit on the
ServoSeal / drain valve motor circuit.
The N-E5 controller will maintain a minimum voltage on the output to the water inlet
solenoid in the OFF cycle.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
N-E5 Electronic Control Module Operation
(cont.)
Service Checks
N-E5 not operating:
•
Check for power supply to into the unit at the power point and Active - Neutral
incoming supply terminals.
•
Check if the N-E5 power indicator LED is illuminated.
•
Check the N-E5 is correctly located in the base terminal connector and mounting
bracket.
•
Check the N-E5 is set to the correct Network ID number.
•
Check if the N-E5 internal 8 Amp fuse is in circuit or is open circuit.
If fuse NOT open circuit:
•
Check the Servoseal / Drain valve wiring loom, motor and switch
mechanisms for short circuit.
If fuse IS open circuit (blown):
•
Check the pump motor and wiring loom for short circuit.
•
Check the water inlet solenoid and wiring loom for short circuit.
•
Check the fan motor and wiring loom for short circuit.
•
Replace 8 Amp fuse and re test.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Fan Operation
N-E5 Module Cooler Model Configuration
The N-E5 module is capable of being set for up to 7 different Cooler models.
This setting relates to the Cooler's motor capacity and the appropriate RPM range for
correct operation.
The minimum RPM setting is 500 RPM for all models, and the maximum RPM varies
by the model setting selected (see table below).
L40, L50,L21, L23, L22,
L52, L51, L53, L62, L63,
P23, P43,
P53, P63, F23, F53
Model 2
500 1250
L11,L13, L31, L33, L41,
L22, L32, L42,
L43, P33, F13, F43
L10, L20,
Fan Operation
The N-E5 controls the level of voltage output to the fan and this is determined within
parameters of the Model Selection settings.
The fan speed will vary on a linear scale between the minimum and maximum
settings, even if the differential is minimal.
Other service adjustments can be made within the Model No. range, and are
discussed in the section regarding special adjustments using the Networker.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Fan Operation
(cont.)
Speed Feedback
The fan motor is fitted with a speed sensor which signals the motor RPM back to the
N-E5 Cooler control.
The N-E5 must have a speed sensor fitted and operating or the unit will operate in a
FAN LIMP mode.
The sensor is fitted to the special stub shaft provided on the motor and uses a light
beam across the shaft flat section to register the revolutions of the motor's shaft.
The purpose of the sensor is to:
•
Detect if the fan motor (impellor) is rotating when the power is first applied to the
fan motor.
•
Detect if the fan motor is locked.
•
Detect if the fan motor is not rotating within the correct operating range.
If the N-E5 doesn't receive any signal from the speed sensor, or looses the signal, the
N-E5 will adopt a FAN LIMP mode operation.
Initially, when the motor is required to run and the speed signal is lost, the fan will
immediately increase its fan speed and may be driven to the maximum power for a
short time prior to commencing the Fan Limp Mode.
Then the FAN_LIMP mode will commence, however, there will be a 4 minute delay
before the error is displayed on the Networker (where available).
If the condition rectifies itself, and the speed sensor signal is restored, then the
Cooler will resume normal fan operation.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation:
(cont.)
Fan Operation:
(cont.)
FAN_LIMP Mode - Networker Error 30
FAN_LIMP mode is displayed at the
Networker as Error 30 whilst this condition is
FAN_LIMP mode the fan speed is
controlled to a phase angle, associated with
the fan output level of the Networker,
according to its mode and/or comfort setting.
Therefore the fan can still vary in speed, whilst
operating in LIMP mode, and the user may not
even notice any difference in the unit's
operation.
Service
Service Check List
•
Check the speed sensor wire loom for damage, and plug connection into the N-E5.
•
Check the speed sensor is correctly located in the hub of the motor end plate.
•
Remove speed sensor from motor end plate and check;
•
That no foreign matter has entered the sensor cap
•
The sensor PCB is firmly secured within the sensor cap.
•
The 2 sensor probes on the PCB are vertically aligned.
•
The wiring circuit within the speed sensor and the PC not damaged.
•
Check the motor start winding is not open circuit.
•
Check the motor capacitor - replace and retest.
•
Check the N-E5 is not faulty - replace and re test.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation:
(cont.)
Fan Operation:
(cont.)
DC Brake
Whenever the fan motor is required to operate, the N-E5 uses the motor speed
sensor to checks if the motor is rotating.
This rotation of the fan and motor, may be due to air up draught in the dropper duct,
whilst the unit was not running.
The N-E5 will apply a brake to stop the rotation by energising the motor with DC
Voltage. This is to ensure the fan motor will not be energised and driven in the
reverse direction.
DC power will only be applied to the motor, if at the time the fan motor is powered,
the motor has not been previously powered for at least 10 seconds, and that
rotation is detected above the minimum RPM requiring the brake.
The DC brake will then remain ON until the motor speed sensor registers the fan
motor has slowed to a RPM not requiring the brake, before powering the motor for a
normal start.
The rate that the DC brake is applied, is a factory setting, and cannot be field
modified.
If the fan is operating in FAN_LIMP mode, then the DC brake will not be applied.
Allow for the 4 minute delay period to register the error on the Networker, before the
DC brake is disabled.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Fan Operation
(cont.)
Motor Failure - Networker Error 60
Should the motor circuit and or the Coolers motor
winding be open circuit, the N-E5 module will lockout and
display the error at the Networker
This error condition requires a power up reset to restore the
Coolers operation.
Refer to motor diagnostics for check list.
Service
Fan Motor will not Operate
•
Turn the fan ON in manual mode and make sure the motor is not in an operation
delay period i.e. Servoseal open time.
•
Check the impellor is free to turn.
•
Check the motor shaft is free to rotate and is not jammed.
•
Remove the N-E5 and check the motor wiring terminals are correctly positioned on
the circuit board and that the connections are good.
•
Check the motor winding resistance (refer Motor Circuit Diagram and Technical
Information Sheet).
OFF
10 A
V
COM
1000V- - -
750V
V
OHMS
Multimeter
FUSED
MOTOR/COMMON-BLUE
MOTOR/START-BLACK
MOTOR/RUN-BROWN
•
Check the motor is not HOT and the thermal over load switch is not open circuit.
•
Check the incoming power supply is ON and is the correct polarity.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Fan Motor will not operate (cont.)
•
Check for 240 Volts at terminals MOTOR/RUN-BROWN and MOTOR/COMMON-
BLUE on the motor supply loom terminals, located on the service compartment
back wall (max fan speed selected).
OFF
10 A
V
COM
FUSED
1000V- - -
750V
V
VOLTS
Multimeter
240
MOTOR/RUN-BROWN
MOTOR/COMMON-BLUE
If 240 Volts present:
•
Check for Volts at terminals MOTOR/COMMON-BLUE and MOTOR/START-
BLACK on the motor supply loom terminals located on the service compartment
back wall (max fan speed selected).
•
Replace capacitor and test again.
•
Replace fan motor.
OFF
10 A
V
COM
FUSED
1000V- - -
750V
V
VOLTS
Multimeter
240
MOTOR/COMMON-BLUE
MOTOR/START-BLACK

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation:
(cont.)
Fan Operation
(cont.)
Fan Motor will not operate (cont.)
If no Volts present:
•
Bridge terminals MOTOR/RUN-BROWN and MAINS/ACTIVE-IN using a
multimeter set on Amps (check current for motor - refer motor specs).
Caution: This procedure is placing full 240 volt current onto the motor, only a
qualified electrician should perform this procedure.
NOTE: Because the start winding is not in circuit, the motor may need to be manually
turned to start.
OFF
10 A
V
COM
FUSED
1000V- - -
750V
V
Amps
Multimeter
4.7
A
MOTOR/RUN-BROWN
MAINS ACTIVE-IN
If motor runs:
•
Check the motor wiring loom and all terminals.
•
Check minimum RPM setting (see section - Service Adjustments using the
Networker.
•
Check the N-E5 internal 8 Amp fuse is not open circuit.
•
Replace N-E5 and test again.
•
Check that the ServoSeal has been driven open, indicating Networker signal
operating correctly.
If ServoSeal not open
•
Replace Networker and test again.
If motor doesn't run:
•
Replace motor.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Fan Operation
(cont.)
Fan Motor will not operate - Flowchart

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation.
(cont.)
Fan Operation
(cont.)
Dismantling - Fan and Fan Motor Removal
•
Remove thumb screws from roof panel.
•
Remove the 4 filter pad frames and support tube brackets.
•
Isolate power supply on the switch under front left hand side of the cooler.
•
Close the Servoseal / Drain valve and drain tank of water.
•
Remove the 2 screws from the service access panel and open cover.
•
Unplug the Trident loom plug from the N-E5 control.
•
Remove the pump inlet lock nut from the tank base.
•
Remove the 4 screws that secure the tank to the coolers sub frame, then lift up
and remove the tank assembly.
•
Remove motor wire loom terminals on the motor supply loom terminal block
located on the service compartment back wall.
•
Feed back the wiring into the fan motor assembly area and disconnect the cable
ties from the motor bracket
•
Disconnect the speed sensor loom from the N-E5 circuit board, and feed back the
wiring loom to the motor assembly.
•
Loosen and remove the nuts on the fan impellor retaining bracket bolts.
•
Place a 50mm or larger socket fitting or similar, over the motor shaft and fan
impellor retaining bracket, so that it seats on the fan impellor hub body. Use a
mallet to hit the 50mm socket fitting, to release the tapered bracket cone from the
hub, loosening the impellor on the motor shaft.
•
Remove impellor.
•
Support the motor's weight, then loosen and remove the 2 nuts and washers on
the bolts that secure the fan motor mounting bracket around the motor's case.
•
Lower fan motor down and out of the mounting bracket.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Pump Operation
The Contour Cooler's pump has a synchronous motor with thermal protection, and a
magnetic coupling drive to the pump impellor.
The pump impellor may be driven in either rotation direction, which lessens the
likelihood of the pump blocking.
The pump base is integrated into the tank base and should not require removal.
The pump will be turned OFF for 15 seconds at 15 minute intervals, to allow the
water head in the feed tube to the distribution spreader to back flush the pump, and
keep it clear of blockages. Additionally, if the pump had an air lock, this pump
stoppage will allow water into the pump, to resume normal operation again.
All servicing and maintenance can be done through the service access compartment.
Dismantling
•
Isolate the 240 Volt power supply to the pump (N-E5).
•
Open service access compartment cover.
•
Drain the tank of water.
•
Disconnect the wiring terminals on top of the pump motor.
•
Remove 3 screws on the perimeter of the pump upper housing.
•
Separate the upper pump housing from the base, which remains plumbed in the
tank.
•
Unclip the motor winding cover.
•
Slide the winding and lamination plate assembly up and off the pump housing
centre.
•
Slide the winding coil out from the lamination plates.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Pump Operation
(cont.)
Pump will not operate
•
Check that the pump is switched ON and that the pump is not in an operation
delay period i.e. water contact across Trident probes or Servoseal open time.
•
Check for 240 Volt output to the pump, at the PUMP-NEUTRAL and PUMP-
ACTIVE terminals on the pump.
OFF
10 A
V
COM
FUSED
1000V- - 750V
V
VOLTS
Multimeter
240
PUMP - NEUTRAL
PUMP - ACTIVE

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Pump Operation
(cont.)
Electrical Checks
If power present:
•
Check the pump wire loom and connections.
•
Refer to mechanical pump checks on page 45.
•
Check the pump motor winding is not open circuit.
•
Isolate the electrical supply and use a multimeter on the Ohm's setting to check
the circuit resistance at terminals PUMP-NEUTRAL and PUMP-ACTIVE (169
Ohms +/- 5% @ 200C.)
•
Replace pump winding assembly.
OFF
10 A
V
COM
FUSED
1000V- - -
750V
V
Ohms
Multimeter
169
A
PUMP - NEUTRAL
PUMP - ACTIVE
If pump doesn't operate:
•
Refer to mechanical checks.
•
Replace pump.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Pump Operation
(cont.)
Electrical Checks (cont.)
If NO power:
Check the Cooler's operation is not in a delay period preventing the pump from
functioning.
Check the power supply is turned ON and is the correct polarity and voltage
(MAINS/ACTIVE-IN and NEUTRAL terminals).
Check the N-E5 module is turned ON and is correctly located in the mounting plug.
Empty the tank of all water and then drive the pump with your multimeter on
Amps. Caution: only a qualified electrician should perform this procedure,
because this involves full current 240 volt electricity.
Bridge terminals PUMP-ACTIVE and MAINS/ACTIVE-IN using multimeter set on
Amps.
If pump functions:
Check the pump loom and all terminals.
Check the N-E5 internal 8 Amp fuse is not open circuit.
Replace N-E5 and re-test.
Replace Networker and re-test.
OFF
10 A
V
COM
FUSED
1000V- - -
750V
V
Amps
Multimeter
.22
A
MAINS ACTIVE-IN
PUMP - ACTIVE
If pump doesn't operate:
•
Refer to mechanical checks.
•
Replace pump.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Pump Operation
(cont.)
The following checks are required if the pump has power, but will not operate, or is
not pumping sufficient water to the filter pads.
Mechanical Checks
•
Check that the tank water level is correct.
•
Check the water distribution piping is not blocked.
•
Dismantle the pump as per the instructions.
•
Check and clear the lower pump housing of any obstruction.
•
Check the pump impellor is not damaged, and can rotate within the upper pump
housing.
•
Replace upper pump housing assembly, if impellor damaged or jammed.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Pump Operation
(cont.)
Electrical & Mechanical Checks - Flowchart
Check the pump
loom and all
terminals
Pump
Electrical and
Mechanical
Checks
Check that the pump is
switched ON and that
there is 240 volt output to
the oump at the
PUMP-NEUTRAL & PUMP
ACTIVE terminals
Pump will not operate
IS POWER PRESENT?
Check if the cooler is in a
delay period prevent
pump form functioning
Check the pump wire
looms and connections
Check the pump motor
winding is not open circuit
and check ohms at
PUMP-NEUTRAL &
No
Yes
Check the power supply
is turned ON and is the
correct polarity and
voltage
Check the N-E5 module
is ON and is correctly
loctaed in the mounting
plug
Bridge terminals
PUMP-ACTIVE
& MAINS-IN
If pump doesn't
operate
Check the N-E5
internal 8 amp
fuse is not open
circuit
Replace the
N-E5 and re-test
Refer to
mechanical
checks
Replace pump
Refer to
mechanical
pump checks
Check that the
tank water level
is correct
Check the water
distribtion piping
is not blocked
Dismantle pump
as per
instruction
Check and clear
of any obstructions
Check the pump impellor
is not damaged and can
rotate within the pump
upper housing
Replace upper pump
housing assembly if
impellor is damaged
If pump
functions
Replace upper pump
housing assembly if
impellor is damaged

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation:
(cont.)
Water Inlet Solenoid Operation
The Contour Cooler has a 240 Volt water inlet solenoid on the under side of the base,
at the high side of the roof.
The water inlet solenoid has a flexible hose attached with a filter inserted in the hose
connections at each end.
A 3/4" to 1/2" BSP nipple is provide for the installer for a convenient connection to the
hose.
The water inlet solenoid is assembled in a bracket to support the pipe connection and
the outlet discharge, which is direct to a fitting moulded into the Cooler base on the
high roof side.
The wiring loom to the water inlet solenoid is concealed under the base, and feeds
back into the service access compartment.
Note: The water inlet solenoid uses the water supply pressure to it's diaphragm in the
closing action of the valve.
Ensure the solenoid closes within 5 seconds of turning the 240 Volt power OFF to the
water inlet solenoid.
Dismantling
•
Turn OFF the water.
•
Unclip the solenoid from the housing.
•
Slide the assembly out to disconnect the water supply and wire loom. Care must
be taken when disconnecting the water supply as to not break the solenoid coil of
the body of the valve.
•
To access filter, remove the water supply hose, remove filter basket with pin nose
pliers.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Water Inlet Solenoid Operation
(cont.)
Water inlet solenoid does not supply water into the tank (empty):
•
Check that the Cooler is turned ON calling for cooling (pump operation) and is not
in an operation delay period i.e. Servoseal delay.
•
Check the water supply tap is turned ON.
•
Check that the water supply pressure is within the operation range (300 kPa 1000 kPa).
•
Check that an Error 50 (both High and Low Level Water Sensors are open circuit)
is not current.
Check that the water inlet solenoid is energised (240 Volt), at the water INLET
SOLENOID-ACTIVE and INLET SOLENOID-NEUTRAL terminals, on the service
compartment back wall.
OFF
10 A
V
COM
1000V- - -
750V
V
VOLTS
Multimeter
240
FUSED
INLET VALVE - NEUTRAL
INLET VALVE - ACTIVE

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Water Inlet Solenoid Operation
(cont.)
If power present and inlet solenoid doesn't open:
•
Check the water inlet solenoid wire loom and connections.
Isolate power and check the Water Inlet Solenoid coil resistance (4.1 kOhms).
INLET VALVE - NEUTRAL
INLET VALVE - ACTIVE
OFF
10 A
V
COM
1000V- - -
750V
V
kOHMS
Multimeter
FUSED
3.9
•
Check if the water inlet solenoid is blocked.
Replace water inlet solenoid.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Water Inlet Solenoid Operation
(cont.)
If NO power:
•
Check the Cooler's operation is not in a delay period preventing the water inlet
solenoid from functioning.
•
Check the power supply is turned ON and is the correct polarity and voltage
(Mains Active In and Neutral terminals).
•
Check the N-E5 8 Amp fuse is not open circuit.
•
Check the N-E5 module is turned ON and is correctly located in the mounting plug.
Bridge power supply using a multimeter in series on Amp setting between
MAINS/ACTIVE-IN and WATER INLET SOLENOID-ACTIVE terminals. Note - Only
a Qualified electrician should perform this procedure as it involves full current
240 volt electricity.
OFF
10 A
V
COM
FUSED
1000V- - 750V
V
Amps
Multimeter
A
MAINS ACTIVE-IN
INLET VALVE - ACTIVE
If water inlet solenoid operates:
•
Replace N-E5 module, and check for output voltage to the water inlet solenoid.
If water inlet solenoid doesn't operate:
•
Check wiring terminals & loom.
•
Check water inlet solenoid is not blocked or jammed.
•
Replace water inlet solenoid.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
Water Inlet Solenoid Operation
(cont.)
Water inlet solenoid does not turn OFF
•
Check the water inlet solenoid closes within 5 seconds of turning the 240 Volt
power OFF.
•
Check the Trident wiring loom is connected to the N-E5 and the plug connection is
good.
•
Check the Trident loom circuit output and water contact sensitivity at both the
probe and the N-E5 plug terminals (see test procedure Trident Water Management
section)
If loom not connected (open circuit)
•
N-E5 Error 50 - Water inlet solenoid open for 15 minutes before lockout.
Check that the water inlet solenoid is not energised (240 Volt) at the WATER INLET
SOLENOID-ACTIVE & NEUTRAL terminals.
If power present:
•
Check if the Networker is turned ON and cooling required.
•
Check the Cooler water level is not at a level that requires the water inlet
solenoid to be energised.
•
Check the Cooler is not in a pre-program operation, requiring the water inlet
solenoid to be operating i.e. wash or flush function.
If no power:
•
Check the water inlet solenoid has not blocked or jammed open.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
ServoSeal and Drain Valve Operation
Contour and Profiler Coolers have a new and unique mechanism, to drain and empty
the Cooler's tank and simultaneously close off the duct (Contours only), at the end of
use.
The ServoSeal is a set of adjustable louvers constructed in the Contour's base, which
are driven closed and prevent heat loss from the building, when the unit is not in use.
An electric motor drives a linkage that opens and closes the louvers.
This motor has another lever that operates at the same time, to raise and lower a
flexible drain outlet tube.
When the ServoSeal closes the dropper duct, the drain outlet tube is lowered to a
position that all the tank water is naturally drained from the Cooler. The Profiler cooler
only has the Drain valve connected to the Servo motor.
The motor that drives both the ServoSeal and drain linkages, is 240 Volts controlled
through a geared cam shaft and switch.
The motor is powered to open on one switch circuit, and powered to close on
another.
The cam shaft causes the switch contacts to open, stopping the motor and
mechanism at the correct position, whether the motor is to be driven forward or
reverse.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
ServoSeal and Drain Valve Operation
(cont.)
Dismantling
ServoSeal / Drain Valve Motor (only) removal:
•
Isolate the 240 Volt power supply (N-E5).
•
Open service access compartment cover.
•
Disconnect the ServoSeal / drain valve motor wiring loom.
•
Remove the motor retaining clip holding the motor onto the gear linkage
mechanism.
•
Retract the motor.
With the motor removed the gear linkage mechanism action can be manually
operated and checked.
Motor and gear linkage mechanism removal:
•
Remove the drain valve level set screw and release the level from the geared cam
shaft.
•
Remove the fan impeller from the fan motor shaft, to gain access to ServoSeal
louver linkages (refer to fan dismantling procedures).
•
Remove the 2 linkage retaining screws that hold the lower linkage arm onto the
ServoSeal louver coupling.
•
Remove the 3 screw retaining the gear linkage mechanism to the service
compartment back wall.
•
Manoeuvre the linkage arms through the service compartment back wall opening,
and remove assembly.
•
Disconnect motor cam lever switch.
•
Disconnect linkage arm and cam shaft.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
ServoSeal and Drain Valve Operation
(cont.)
ServoSeal will not open / drain close
•
Check the power supply is turned ON, and is the correct polarity and voltage
(MAINS/ACTIVE-IN and NEUTRAL terminals).
•
Check the N-E5 module is turned ON, and is correctly located in the mounting
plug.
•
Check that the Networker is turned ON, and calling for a pump or fan operation
(allow 45 seconds following a wash operation).
•
Check if 240 Volt power present on the ServoSeal / drain valve MOTOR-SWITCH
(a) and MOTOR (b) Active Open terminals and Neutral (see diagram).
If power is present to the switch terminal, but not to the motor terminal:
•
Check wiring loom and connections between the motor and the micro switch for
open circuit.
•
Check the MOTOR/MICRO-SWITCH cam shaft is not damaged.
•
Replace the faulty motor micro switch.
OFF
10 A
V
COM
FUSED
1000V- - -
750V
V
VOLTS
Multimeter
240
(a)
MAINS ACTIVE-IN
(b)
MOTOR/MICRO-SWITCH
MOTOR-ACTIVE

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
ServoSeal and Drain Valve Operation
(cont.)
If power is present at the motor terminal:
•
Check the ServoSeal / drain valve motor winding resistance
(12.5 kOhm @ 200C.) on both motor windings (ACTIVE to NEUTRAL). Refer to
diagram below and circuit on page 57.
Replace faulty ServoSeal / drain valve motor.
OFF
10 A
V
COM
1000V- - -
750V
V
kOHMS
Multimeter
FUSED
12.5
(a)
(b)
MOTOR-ACTIVE
MOTOR-ACTIVE
MOTOR-NEUTRAL
•
If ServoSeal / drain valve motor does not operate:
•
Remove motor from gear linkage mechanism and re test.
•
Replace motor resistor / capacitor (RC) with same at terminal block, and re-test.
If motor operates:
•
Check linkages are free moving and not jammed.
•
Check gear linkage mechanism is not jammed.
•
Replace gear linkage mechanism.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
ServoSeal and Drain Valve Operation
(cont.)
If NO power present at ServoSeal motor Active Open terminal:
•
Check the N-E5 module is turned ON, and is correctly located in the mounting plug
and re-test for power.
•
REMOVE N-E5 and bridge power supply using a multimeter in series on Amp
setting, between MAINS/ACTIVE-IN and ServoSeal / drain valve MOTOR-ACTIVE
Open terminal (Black) (see diagram).
WARNING
When powering the ServoSeal drain valve motor, ensure the ServoSeal is in a
position to open/close, depending on which direction the motor is to be driven.
If the motor is driven too far in either direction, damage will occur to the linkages and
mechanism.
OFF
10 A
V
COM
FUSED
1000V- - -
750V
V
Amps
Multimeter
A
MAINS ACTIVE-IN
MOTOR-ACTIVE
If ServoSeal / drain valve motor operates:
•
Check wiring and connections for open circuit.
•
Replace N-E5 module and re test.
If ServoSeal / drain valve motor doesn't operate:
•
Remove motor from gear linkage mechanism and re-test.
•
Replace motor.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Cooler Operation
(cont.)
ServoSeal and Drain Valve Operation
(cont.)
ServoSeal will not close / drain open:
•
Check that the ServoSeal / drain valve action is not in a delay period, from a prior
Cooler operation.
i.e. 60 minute - ServoCloseDelay.
•
Follow check procedures as above for ServoSeal will not open / drain close, with
power test to Active Close terminal on ServoSeal motor and switch.
Circuit Diagram:

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Trident Water Management System
The Contour Cooler's tank water level is regulated, by turning ON and OFF the water
inlet solenoid as required, according to the operating conditions.
After the initial filling, at which point the water inlet solenoid turns OFF, the Cooler
looses tank water volume due to evaporation, in the normal course of the unit's
operation.
The rate of water evaporation is dependant on the current climatic conditions, the
Cooler's operating fan speed and the condition of the filter pad material. All of these
of course are infinitely variable.
The water management system uses 3 stainless steel probes, to detect the water
level within the tank. The mid level probe is the common low voltage output. The
shortest probe is the high water level. The longest probe is the low water level.
The switch function of both version are the same, however, the revised version
design has the common voltage output probe, at a closer position to both low and
high level probes.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Trident Water Management System
Trident Operation
When the Networker is turned ON, and the cooler is required to start from an empty
tank, the pump is delayed until the tank has sufficient water for it to operate.
As the tank fills, the water eventually makes contact between the Common Water
Sensor probe and the Low Water Level Sensor probe, at which point the pump can
start operation (Pre Wet).
When the tank fills to the high water level, The N-E5 switches OFF the water inlet
solenoid.
During the course of normal operation, with the water inlet solenoid closed, the tank
water level is evaporated down to the low water level.
The water contact between the Common Water Sensor and the Low Water Level
Sensor probes becomes open circuit.
The N-E5 will then switch on the water inlet solenoid again to refill the tank to the high
water level.
The N-E5 module is programmed as part of the overall control, if the expected water
levels are not achieved within designated times, then the N-E5 will go to water level
limp mode operation.
As the water level control probes will be constantly subjected to water and electrical
power during normal operation, it is expected that a coating will eventuate, depending
on the water quality.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Trident Water Management System
(cont.)
Abnormal Operation
Water Limp Modes
The Trident water management system will automatically adopt a controlled
operation, if it detects the malfunction of the sensing probes, or detects water in the
tank when it's not expected.
There are 4 water management errors modes, and these operation modes are
communicated to the Networker to indicate the malfunction.
Low Water Level Sensor (failure) - Error 40
High Water Level Sensor (failure) - Error 41
Drain (operation failure) - Error 42
Water Sense Failure (both low and high level sensors) - Error 50
Water Limp mode errors 40, 41 and 42, do not require the cooler to be shut down,
but the coolers filling and flush operation is time controlled.
These errors (where available) will only be displayed during the time the water inlet
solenoid is open and will alternate between the error screen and the normal display.
The N-E5 module will delay, for 4 minutes, any Limp mode error display at the
Networker, just in case the error rectifies itself.
Should the Limp mode condition correct itself, then normal operation and function
times will be restored.
Error 50 is different and will cause a lockout, but provides the user the facility to
reset the operation at the Networker. However, if the condition is still present after
reset, the unit will lockout again.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Trident Water Management System
(cont.)
Abnormal Operation
(cont.)
Low Water Level Sensor (failure) - Networker Error 40
- Fails to sense or is short
circuit.
Fails to sense:
•
Water detected at the High Water Level Sensor, but not
seen at the Low Water Level Sensor.
Short circuit:
•
Closed circuit on Low Water Level Sensor for 120
minutes of pump operation, since water detected on the
High Water Level Sensor (i.e. low evaporation).
Temporary
Low Water Level Sensor Limp Mode Operation:
•
Pump starts operation at the High Water Level Sensor
•
Water inlet solenoid closes when water is sensed at the High Water Level Sensor.
•
Water inlet solenoid is timed OFF for 90 seconds, then refills to High Water Level
Sensor again.
To rectify this condition, refer to Service Checks on page 73.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Trident Water Management System
(cont.)
Abnormal Operation
(cont.)
High Water Level Sensor (failure) - Networker Error 41
- Fails to sense or is short
circuit.
Fails to sense:
•
Open circuit on High Water Level Sensor after 3 minutes
of detecting water on the Low Water Level Sensor.
Short circuit:
•
From start up the Low Water Level Sensor is open circuit
(normal), and the High Water Level Sensor is closed
circuit.
Temporary
High Water Level Sensor Limp Mode Operation
•
Water inlet solenoid closes after 3 minutes of the water detected at the Low Water
Level Sensor.
•
Water inlet solenoid open when open circuit occurs on Low Water Level Sensor.
•
Water inlet solenoid timed to fill for 70 seconds, then closes again.
To rectify this condition, refer to Service Checks section.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Trident Water Management System
(cont.)
Abnormal Operation
(cont.)
Drain (operation failure) - Networker Error 42
- Failure to drain tank once the
ServoSeal is closed.
Water is sensed on both high and low sensors, on
completion of a WashWaitTime (45 seconds) following a
Wash.
i.e.
•
blocked drain
•
shorted contacts - stick, leaf
Temporary
Operation sequence on shutdown cycle:
•
Pump and fan OFF for 60 minutes.
•
ServoSeal closes and drain valve opens (20 seconds).
•
WashWaitTime period starts (45 seconds).
•
Water inlet solenoid opens for 30 seconds. (WashTime).
•
WashWaitTime period starts (45 seconds).
•
N-E5 checks for closed circuit on the Low and High Water Level Sensors.
•
Closed circuit on the Low and High Water Level Sensors with ServoSeal closed
and drain valve open is registered.
•
Malfunction remains current on next operation of cooler.
•
Error 42 will display only when water inlet solenoid opens.
•
Error 42 can only reset at the end of Wash sequence with no closed circuit to the
Water Level Sensors.
•
Even if the closed circuit on the water sensors has cleared by the next start up of
the cooler, this error remains current until it completes a successful shut down
without this error condition.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Trident Water Management System
(cont.)
Abnormal Operation
(cont.)
Networker Error 42
Drain - Failure to drain tank once the ServoSeal is closed (cont.)
Operation sequence on start up cycle:
If the closed circuit on the water sensors has not cleared on the next start up of the
cooler, then the Cooler operation will commence as follows:
•
ServoSeal opens and drain valve closes (20 seconds).
•
The Water inlet solenoid will open provided the water level is not already at the
High Water Level Sensor (closed circuit).
•
The pump will start operating because the Low Water Level Sensor indicates
water is at a sufficient level for the pump.
However, if both the Low and High Water Level Sensors have failed short circuit, then
the Low Water Level Sensor failure will be forced after 120 minutes of pump
operation.
Error 40 code will be displayed, alternating with this drain error, when and if the water
inlet solenoid is open.
Because both the Low and the High Water Level Sensors are closed circuit, the water
inlet solenoid will remain closed.
As the water inlet solenoid will not open, the coolers tank will not fill, and/or any water
that was present will eventually evaporate.
This condition will not harm the pump, but will result in poor and inadequate cooling
performance.
To rectify this condition, refer to Service Checks section.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Trident Water Management System
(cont.)
Abnormal Operation
(cont.)
Water Sense Failure - Networker Error 50
Fails to sense - Both the Low and High Level Water
Sensors fail to sense (open circuit) within
15 minutes of Water Inlet Solenoid opening.
Service
Reset
Operation sequence:
•
Water inlet solenoid opens.
•
Open circuit on Low Water Level Sensor after 15 minutes.
•
Open circuit on High Water Level Sensor after 15 minutes.
•
Lockout forced (error displayed at Networker).
•
Water inlet solenoid closes.
•
20 minutes delay till ServoSeal closes and drain valve opens.
•
ServoSeal closes and drain valve opens (20 seconds).
•
WashWaitTime period starts (45 seconds).
•
Water inlet solenoid opens for 30 seconds (WashTime).
•
WashWaitTime period starts (45 seconds).
If both the Low and High Water Level Sensors have failed short circuit, then the
Low Water Level Sensor failure will be forced after 120 minutes of pump operation.
Error 40 code will be displayed, alternating with this drain error, when and if the water
inlet solenoid is open.
Because both the Low and the High Water Level Sensors are closed circuit, the water
inlet solenoid will remain closed.
As the water inlet solenoid will not open, the coolers tank will not fill, and/or any water
that was present will eventually evaporate.
This condition will not harm the pump, but will result in poor and inadequate cooling
performance.
To rectify this condition, refer to Service Checks on page 73.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Trident Water Management System
(cont.)
Trident Test Procedure & Service Checks
The N-E5 has a 14 Volt output to the Trident water sensing probes.
This voltage can be measured between the Common and the High and Low Level
Water Sensors in a dry tank.
With water contact between the probes, the voltage drop across the Common and the
Low and High Water Level Sensor probes varies, depending on the quality of the tank
water.
Dry Tank Test:
With the tank empty of water
•
Check for 14 Volt across the Common (black) Water Sensor probe and the Low
Water Level (white) probe.
•
Check again for 14 Volt (with no voltage drop) across the Common (black) Water
Sensor probe and the Low Water Level (white) probe whilst gently wiggling the
Trident loom plug and connection on the N-E5.
•
Check for 14 Volt across the Common (black) Water Sensor probe and the High
Water Level (red) probe.
•
Check again for 14 Volt (with no voltage drop) across the Common (black) Water
Sensor probe and the High Water Level (red) probe whilst gently wiggling the
Trident loom plug and connection on the N-E5.
Refer to diagrams on pages 75 and 76.
If less than 14 Volts:
•
Check the Trident wire loom and loom connections.
•
Check the Trident loom for continuity.
•
Check the N-E5 Trident connection for 14 Volt output.
•
Check the N-E5 8 Amp fuse is not open circuit.
•
Check for N-E5 PCB track fracture adjacent Trident plug connection (may be
intermittent).

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Trident Water Management System
(cont.)
Trident Test Procedure & Service Checks
(cont.)
Wet Tank Test:
•
Commence filling the tank with water then:
•
Check the pump operates when water makes closed circuit at the Common and
Low Water Level Sensor probes.
•
Check for voltage drop (must be less than 9 Volt) across the Common (black)
Water Sensor probe and the Low Water Level (white) probe.
•
Check that the water doesn't overflow out the drain tube before the water reaches
the High Water Level Sensor.
•
Check for voltage drop (must be less than 9 Volt) across the Common (black)
Water Sensor probe and the High Water Level (red) probe.
Refer to diagrams on pages 75 and 76.
If voltage doesn't drop below 9 Volts:
•
Check for coating on the Water Sensor probes preventing circuit.
•
Check for high water quality (not able to make circuit - refer to Brivis).

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Trident Water Management System
(cont.)
Trident Test Procedure & Service Checks
(cont.)
RED
WHITE
BLACK
Guard Water
Sensor
Loom Cntrl-
Water Sensor
MOTOR
SPEED
SENSOR LOOM
WATER LEVEL
CONTROL LOOM
J 5
J 6
J 1
J 2
NETWORKER
LOOM
ALTERNATIVE
NETWORKER
CONNECTION
POINT
High Water Level
Common Sensor
Low Water level
OFF
10 A
V
COM
FUSED
1000V- - -
750V
V
VOLTS
14
14 Volts - Dry
When water makes closed circuit
must be less than 9 volts - Wet
Common Sensor and High Water Level
Heatshrink Sensor
Strip (100mm)
Common
Pin
High Water
Sensor Pin
Plastic Guide

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Trident Water Management System
(cont.)
Trident Test Procedure & Service Checks
(cont.)
RED
WHITE
BLACK
Guard Water
Sensor
Loom Cntrl-
Water Sensor
MOTOR
SPEED
SENSOR LOOM
WATER LEVEL
CONTROL LOOM
J 5
J 6
J 1
J 2
NETWORKER
LOOM
ALTERNATIVE
NETWORKER
CONNECTION
POINT
High Water Level
Common Sensor
Low Water level
OFF
10 A
V
COM
FUSED
1000V- - -
750V
V
VOLTS
14
14 Volts - Dry
When water makes closed circuit
must be less than 9 volts - Wet
Common Sensor and Low Water Level
Heatshrink Sensor
Strip (100mm)
Common
Pin
Low Water
Sensor Pin
Plastic Guide

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Trident Water Management System
(cont.)
Trident Test Procedure & Service Checks
(cont.)
Service Checks
•
Check the water inlet solenoid is energised.
•
Check the water supply stop tap is turned ON.
•
Check the water inlet solenoid operates.
•
Check the water inlet solenoid and supply hose filters are not blocked.
•
Check if the pump operates when powered ON and delivers sufficient water to the
distribution system.
•
Check the water distribution system is not blocked.
•
Check the filter pads are in good condition and not damaged.
•
Check if low evaporation rate conditions have applied.
•
Check if the ServoSeal opens and the drain valve is closes fully.
•
Check if the ServoSeal closes and the drain valve opens fully.
•
Check for coating on the sensor probe which may prevent proper circuit.
•
Check if the sensor probe wiring and terminals are open circuit.
•
Check if the sensor probe wiring and terminals are short circuit.
•
Check the N-E5 internal 8 Amp fuse is not open circuit.
•
Check the N-E5 module is located correctly in the base terminal connection
mounting bracket.
•
Check the Trident loom and plug connections.
•
Check in the N-E5 is a 10 Volt output to the water inlet solenoid in the OFF cycle.
•
Check the water inlet pressure is within 300 - 1000 kPa.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
90
Trident Water Management System
(cont.)
Flush-service Guide Table
The higher the quality of the water supply to the cooler, the more tank refills Cooler
can operate before a Flush-service will be required.
As the water quality also varies the Wet Test voltage readings, the appropriate Flushservice cycle may be individually set to that water quality.
The following table is a guide to the Flush-service cycle rates based on the entering
water supply quality.
The voltage reading should be based on the initial fill of the tank, when using this
guide.
The voltage may vary between the Low and High Level Water Sensors, so average
the 2 voltage readings.
Dismantling:
•
Isolate the 240 Volt power supply to the pump (N-E5).
•
Open service access compartment cover.
•
Disconnect the water level sensor loom from the N-E5.
•
Remove the 2 retaining nuts at the top of the probe assembly and remove.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Dealing with Problem Installations
Excessive External Noise from Unit
Check the ducting system for any restriction or sizing error, that would contribute to
higher than recommended back pressure on the fan.
Note the dropper duct take off sizes and details of the main, branch ducts and outlet
diffusers.
Assess the installation requirements in regard to the maximum airflow, to determine if
the fan maximum speed can be reduced, without compromising the effectiveness of
the system.
Use the Networker service access to adjust fan as required.
Excessive Internal Noise from Unit
Outlet Air Noise:
Check to see if the correct unit size has been selected for the application.
Use the sizing guide factor for the locality, and the type of
Cooled area to determine the unit size, as per table below.
Cooler Model Maximum Output
Selection Guide
L 13
1000 - 1450
L 23 & P23
1250 - 1800
L 33 & P 33
1500 - 2250
L 43 & P 43
2000 - 2750
L 53 & P 53
2400 - 3200
L 63 & P 63 2900 - 3600

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Dealing with Problem Installations
(cont.)
Calculate the volume of the individual areas the Cooler's outlets are serving.
The locality factor is used to multiply by the room volume, to determine the correct
minimum duct and register sizes.
Check that the duct and outlet sizes selected, are capable of delivering the total
output of the Cooler selected, as per the minimum recommended size tables.
Duct Size Cooling
Airflow
Size (mm) Airflow
Capacity
250 mm 150 L/s 250 X 250 Up to 100 L/s
300 mm 275 L/s 300 X 300 Up to 250 L/s
350 mm 425 L/s 350 X 350 Up to 375 L/s
400 mm 600 L/s 400 X 400 Up to 500 L/s
450 mm 990 L/s 450 X 450 Up to 600 L/s
500 mm 1080 L/s
550 mm 1230 L/s
600 mm 1420 L/s
If the room and/or the area air requirement calculation is less than 85% of the
Cooler's maximum output (midway between the minimum and maximum Output
Selection figure), then the duct and outlet sizes should be increased to meet this
level.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Dealing with Problem Installations
(cont.)
Check if the unit selection is excessively over sized, which would require the duct and
outlets to be significantly upgraded to carry the additional air quantity of the Cooler.
The Cooler Selection Chart can be used as a reference in this respect, for the
calculation of minimum sized ducting and outlets to upgrade to.
Operation Noise:
•
Check that the ducting has not been damaged or restricted.
•
Check the dropper duct has been secured to the roof timbers, or supported
sufficiently, so as not to transfer vibration through other structural members of the
building.
•
Check the water pipe and wiring (conduit) is not transferring vibration to structural
members of the building.
•
Check the duct and fittings are insulated.
•
Check the Cooler is not transferring excessive vibration onto the dropper duct of
the buildings structure.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Dealing with Problem Installations
(cont.)
Condensation:
Condensation in evaporative systems may be a result of the humidified air from the
outlets, passing over a surface that has a temperature cool enough to condense the
vapour suspended in the air, onto the cool surface.
An example of this is an outlet air stream directed onto a refrigerated cabinet in a
shop, or moist air contacting a cool tile floor surface.
In most cases, the concentration of the air from the outlet is the main contributing
factor for the condensation, therefore it is advisable to redirect the air stream.
Condensation may also result from excessive humidity, due to either the current
climate conditions, or that the conditions have changed rapidly, cooling the room air
that has a high humidity or water vapour content.
Excessive humidity may also be a result of an inadequate exhaust area.
Make sure enough window and/or door area is open, for the unit to work correctly.
The table below shows a guide to the amount of opening required, for effective
cooling for each model.
MODEL Highest Fan
Setting
Lowest Fan
Setting
L13, L23 & P23
1.5 m
2
0.9 m
2
L33 & P33
1.9 m
2
1.1 m
2
L 43 & L53
P 43 & P53
2.3 m
2
1.4 m
2
L63 & P63
2.8 m
2
1.7m
2

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Dealing with Problem Installations
(cont.)
Water Entering Building
When dealing with the problem of water entry in a building, it is often difficult to
ascertain the water source, due to water tracking and capillary action.
The following checks relate to both Cooler faults and installation faults:
•
Check the Cooler's base and trough is not damaged.
•
Check the Cooler is installed level and the overflow pipe can function correctly.
•
Check the water distribution system is not blocked causing incorrect / excessive
water to pads or water tracking.
•
Check the operation of the filter pads and ensure there is no water lift off.
•
Check the flashing of the dropper duct, water supply pipe, electrical conduits and
drain pipes for leakage.
•
Check internal water pipe and drain pipe lines and fittings for leakage.
•
Check the roof (tiles etc.) for damage.
•
Check for any sign of water/moisture, on the inside of the ductwork and bell
housing.
•
Check the route of any water discharge from the Cooler i.e. roof guttering and
water run off area down stream of Cooler.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Service Maintenance
Pre Season Maintenance
The service to a Contour Cooler requires access to the home to check the
performance of the unit through the duct system and the function of the wall control.
Service work performed without access cannot be responsible for the system
operation, only the Coolers function.
General checks
Check and seal the dropper duct flashing and any other roof penetrations.
Check the drain discharge point is appropriate for the installation - rectify or
advised owner.
Check if the tank and internal surfaces require cleaning and clean as required
using 5 mL / 10 L (4%) chlorine as per page 83.
Check the unit is not operating in a Water or Fan Limp mode, refer to service
manual to diagnose and correct.
Water Inlet Solenoid
Check the Water Inlet Solenoid and water supply hose has filters fitted and are
clean.
Check the water supply hose and clamps are in good condition and upgrade the
hose if the hose clamps are the pressed clamp type.
Check the Water Inlet Solenoid opens in the normal operation sequence and
closes within 5 seconds of the N-E5 turning OFF the power supply.
Check the water pressure is sufficient to fill the tank within the 15 minute Fill-
Time, otherwise adjust service parameter to suit.
Check for 14 Volts on the Trident Common and Low & High Level Sensor probes
with the tank dry.
Repeat the check gently wiggling the Trident loom plug connection at the N-E5,
and check if the voltage varies (refer service manual).
Check the voltage on the Trident Common and High & Low Level Sensor Probes
with the tank full (must be less than 9 Volt).

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Service Maintenance
Pre Season Maintenance (cont.)
Check the pump operation commences at the water contact point of the Common
and Low Water Level Sensors.
Check the Water Sensor probes for coating build up and clean as required.
Set the Flush-service cycle parameter relevant to the wet voltage reading (see
service notes).
Check the water Inlet Solenoid closes at the contact of water at the High Level
Water Sensor.
Check the water doesn't overflow out the Drain tube before the water is sensed
at the High Level Water Sensor.
Check the pump water discharge is sufficient for correct pad saturation.
Aqua Duct
Check the Aqua Duct water distribution system is clean and has no blockages on
the pad distribution outlets.
Motor and Fan Checks
Check the fan motor rotates freely and that the motor bearings are not worn.
Check the motor speed sensor is clean, the beam sensors are vertically aligned,
and that the sensor is correctly located in the motor's end plate.
Check the DC brake is operating correctly.
Check the fan impellor is centred within the bell housing.
Check the motor stator bracket and mountings are not damaged.
Check the fan impellor is correctly tensioned and has the correct blade height
and angle.
Check the fan motor varies through the entire range.
Check the minimum and maximum RPM setting are appropriate for the duct
installation.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Service Maintenance
Pre Season Maintenance (cont.)
ServoSeal and Drain Valve
Check the ServoSeal louvers seal correctly in the closed position.
Check the ServoSeal louvers drive open fully in the open position.
Check the Drain Valve raises to the correct height above the High Water Level
Sensor
Check the Drain Valve lowers to the correct position allowing the tank to be
completely drained.
Check the ServoSealCloseDelay parameter is set correctly.
Filter Pads
Check the pads are not damaged or have deteriorated and require replacing.
Check the pads are correctly fitted.
Check the pads are wetted evenly.
System Operation
Check the outlet diffusers are correctly positioned and the louver blades are
configured for best room air mixing.
Check the air distribution is correctly balanced.
Check there is adequate exhaust opening available for correct operation.
Check the Networker wall control is located in a suitable position for correct
operation.
Check the Coolers Pre Wet function is operating correctly.
Check the unit operates in both Manual and Auto modes.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
Service Maintenance
Pre Season Maintenance (cont.)
The following procedure is the recommended practice set out by the Australian
Department of Health:
Add 5 mL of available 4% Chlorine (household bleach) for every 10 Litres
of tank water.
Mix the Chlorine in the water and wipe all internal surfaces.
Operate the pump only for 30 minutes to flush the pads with the water
solution.
Drain the tank and refill with clean water.
Operate the pump for 5 minutes to rinse the pads and drain again.
Refill the tank with clean water, operate the pump for 5 minutes to rinse the
pads and drain again to complete.

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
100
Service Maintenance
End of Season Maintenance
Turn OFF the water supply to the unit at the isolating stop tap.
NOTE
* Do not turn OFF the power supply to the Cooler for longer than is necessary
for carrying out maintenance.
* If the power supply is turned OFF, the Networker will lose its Time/Day
settings.
* If power must be switched OFF, first make sure the ServoSeal is completely
closed.
Dismantling the Water Distribution System
Remove the 4 plastic thumb screws from the roof.
Remove the front and back pad frames, lift the roof to release the frames from the
cabinet.
Disconnect the 19mm clear water feed tube to the roof assembly at the base
connection.
Remove the roof assembly.
Release the 4 plastic thumb screw bushes from the inner distribution tray of the roof
assembly. Push the bushes out of the distribution tray.
Separate the roof outer and the inner distribution tray.
Clean the components and reassemble.