British Gas ICC2 combi ZWBR 8-30 ICC2 Installation And Servicing Instructions

Page 1
Installation and Servicing Instructions
ICC2 combi
Wall mounted condensing boiler for central heating and mains fed domestic hot water
O
ZWBR 8-30 ICC2
GC-Number: 41 108 09
ZWBR 11-37 ICC2
GC-Number: 41 108 10
6 720 610 602 GB (03.02) OSW
Page 2
6 720 610 602 GB (03.02)
2
Contents
Contents
Safety precautions 3
Symbols 3
1 Details of the appliance 4
1.1 EC Declaration of Conformity 4
1.2 Standard package 4
1.3 Description of appliance 4
1.4 Accessories 5
1.5 Casing dimensions 5
1.6 Layout of appliance 6
1.7 Function 7
1.8 Electrical wiring diagram 8
1.9 Technical data 9
2 Installation regulations 10
3 Installation 11
3.1 Important remarks 11
3.2 Domestic hot water 11
3.3 Sealed systems 11
3.4 Siting the appliance 12
3.5 Wall mounting frame assembly 13
3.6 Pre-piping the system 13
3.7 Fitting the appliance 14
3.8 Checking the connections 15
3.9 Flue Systems 15
3.9.1 Siting the Flue Terminal 16
3.9.2 Installation of the flue 17
3.9.3 Flue duct preparation and assembly 19
4 Electrical connections 20
4.1 Connecting the appliance 20
4.2 Connecting TR2 Room thermostat 21
4.3 Mains Voltage external controls connections 21
5 Commissioning 22
5.1 Commissioning 22
5.2 Switching the appliance on/off 23
5.3 Switching on the central heating 23
5.4 System controls 23
5.5 Setting the domestic hot water temperature and flow rate 24
5.5.1 Domestic hot water temperature 24
5.5.2 Hot water flow rate 24
5.6 Summer mode (hot water only) 24
5.7 Frost protection 24
5.8 Pump anti-seize function 24
5.9 Fault Condition 25
6 Text Display 26
6.1 General Description 26
6.2 Programming 26
6.2.1 Deleting a setting 27
6.2.2 Resetting all parameters to their original settings 27
6.3 Menu structure 27
6.4 Setting the time/day 28
6.4.1 Setting the time and day 28
6.4.2 Holidays 28
6.5 Heating 28
6.5.1 Heating programme 28
6.5.2 Setting the Economy temperature (if TR2 is connected) 28
6.5.3 Manual operating mode (if TR2 is not connected) 29
6.6 Hot water 29
6.6.1 Hot water programme 29
6.6.2 Hot water immediately 29
6.7 i Info 29
6.8 Settings 30
6.8.1 Heating (if TR 2 is connected) 30
6.8.2 Hot Water (Storage Tank, ZSBR models only) 30
6.8.3 Service 30
6.9 Individual timer programmes 30
7 Individual settings 31
7.1 Mechanical settings 31
7.1.1 Checking the size of the expansion vessel 31
7.1.2 Setting the central heating flow temperature 31
7.2 Settings on the Bosch Heatronic 31
7.2.1 General description 31
7.2.2 Setting the anti-cycle time (Service Function 2.4) 32
7.2.3 Setting the maximum CH flow temperature (Service Function 2.5) 32
7.2.4 Setting the heating output (Service Function 5.0) 32
7.2.5 Constant hot water cycle time (Service Function 6.8) 32
7.2.6 Variable pump settings (Service Function 7.0) 32
7.3 Setting the gas/air ratio 32
8 Converting the appliance to different
gas types 33
8.1 Setting the gas/air ratio 33
8.2 Testing combustion air/flue gas at set heat output 35
8.2.1 Testing the O2 or CO2 level in the combustion air 35
8.2.2 Testing CO and CO2 35
9 Maintenance 36
9.1 Pre-Service Check List 37
9.2 Description of servicing operations 38
9.3 Replacement of Parts 41
9.3.1 PCB control board and transformer 41
9.3.2 Fan Assembly 42
9.3.3 Pump 42
9.3.4 3-way diverter valve 43
9.3.5 3-way diverter valve motor 43
9.3.6 Sensors 43
9.3.7 Gas Valve 44
9.3.8 Domestic Hot Water Heat Exchanger 44
9.3.9 Electrode assembly 44
9.3.10Pressure gauge 44
9.3.11Expansion vessel 44
9.3.12Pressure Relief Valve 44
9.3.13Burner 44
9.3.14Flow switch 45
9.3.15Primary Heat Exchanger 45
10 Appendix 46
10.1 Fault Codes 46
10.2 Short parts list 47
10.3 Heating/hot water output settings ZWBR 8-30 N.G. 48
10.4 Heating/hot water output settings ZWBR 11-30 L.P.G 48
10.5 Heating/hot water output settings ZWBR 11-37 N.G. 48
10.6 Heating/hot water output settings ZWBR 14-37 L.P.G 48
10.7 Operational Flow diagrams 49
10.7.1Domestic hot water function 49
10.7.2Central heating function 50
Page 3
6 720 610 602 GB (03.02)
Safety precautions
3
Safety precautions
If you smell gas
B
Turn off gas service cock at the meter.
B
Open windows and doors.
B
Do not operate any electrical switches.
B
Extinguish any naked flames.
B
Telephone your gas company.
If you smell fumes from the appliance
B
Switch off appliance (see page 23).
B
Open windows and doors.
Fitting and modifications
B
Fitting of the appliance or any controls to the appli­ance may only be carried out by a competent engi­neer in accordance wth the Gas Safety (Installation and Use) Regulations 1998.
B
Flue systems must not be modified in any ways other than as described in the fitting instructions.
B
This appliance is for use on sealed primary systems only.
Maintenance
B
The user is recommended:
to have the system regularly serviced in order to ensure that it functions reliably and safely.
B
Use only original spare parts!
Combustible materials
B
Do not store or use any combustible materials (paper, thinners, paints etc.) in the vicinity of the appliance.
Health and safety
B
This appliance contains no asbestos products.
B
There is no potential hazard due to the appliance being electrically unsafe.
B
There are no substances used in the construction that are a potential hazard in relation to the COSHH Regulations (Control of Substances Hazardous to Health Regulations 1988).
Combustion air/Ambient atmosphere
B
The combustion air/ambient atmosphere should be kept free of chemically aggressive substances (e.g. halogenated hydrocarbons which contain chlorine or fluorine compounds). This will prevent corrosion.
Instructions to the customer
B
Explain to the customer how the appliance works and how to operate it.
B
Advise the user that he/she must not make any modi­fications to the appliance or carry out any repairs on it.
B
These instructions are to be left with the user or at the Gas meter.
B
Important: These instructions apply in the UK only.
Symbols
Safety instructions
in this document are identified by a warning-triangle sym­bol and are printed on a grey back­ground.
i
Notes
containing important information are identified by the symbol shown on the left. They are bordered by horizontal lines above and below the text.
Page 4
6 720 610 602 GB (03.02)
4
Details of the appliance
1 Details of the appliance
1.1 EC Declaration of Conformity
This appliance is in accordance with the applicable requirements of the Gas Appliance Directive, Boiler Efficiency Directive, Electromagnetic Compatibility Directive and the Low Voltage Directive.
1.2 Standard package
Gas condensing combination boiler for central heat­ing and domestic hot water
Control panel cover
Wall mounting frame
Room thermostat TR2
Clamp for securing flue duct kit
Fixings (screws etc.)
Set of documentation for appliance
Pre-plumbing manifold
Condensate drain pipe
Filling loop.
1.3 Description of appliance
Wall-mounted appliance, siting not dependent on room size
Natural gas models are low-emission appliances
Multifunction display
Bosch Heatronic control system with integrated tex­tdisplay for servicefunctions and faults
3-channel - digital timer for one heating circuit
Variable pump
Automatic ignition
Modulating control
Full safety systems incorporating Bosch Heatronic with flame ionisation monitoring, solenoid valves and temperature sensors
Concentric flue/air duct with testing point for CO2/CO
Regulated speed fan
Pre-mix burner
Temperature control for central heating
Temperature sensor in domestic hot water
Safety temperature limiter in 24 V electrical circuit
Relief valve, pressure gauge, expansion vessel
Flue gas temperature limiter (105 °C)
Hot water priority circuit
Motorised 3-way valve
Plate-type heat exchange
Condensate Trap.
PIN
CE-0085 BL0507
Category UK
II
2H 3P
Appliance Type
C13, C
33
Table 1
Page 5
6 720 610 602 GB (03.02)
Details of the appliance
5
1.4 Accessories
Standard horizontal flue kit at 100 mm outside diameter for flues upto 4 m in length.
Flue duct kits for horizontal (125 mm outside diameter) for flue lengths upto 10 m (ZWBR 11-37) or 13 m (ZWBR 8-30) and vertical flue systems for flue lengths 12 m (ZWBR 11-37) or 15m (ZWBR 8-
30). Fitting instructions are sent with these kits.
Heating programmer,
Security kit.
1.5 Casing dimensions
Fig. 1
13
Manifold assembly
101
Outer case
103
Facia cover
X
Standard Concentric Horizontal Flue System: min. 310 mm Alternative Concentric Flue System: min. 250 mm
Y
Standard Concentric Horizontal Flue System: 158 mm Alternative Concentric Flue System: 121 mm
Z
Standard Concentric Horizontal Flue System: 105 mm Alternative Concentric Flue System: 130 mm
*
For servicing the appliance
min.
5
min.
5
512
850
101
103
6 720 610 602 - 01.3O
200
30
13
395
360
861
906
35
X
120
Y
Z
200
**
*
*
600
Page 6
6 720 610 602 GB (03.02)
6
Details of the appliance
1.6 Layout of appliance
Fig. 2
4 Heatronic control 6 Heat exchanger safety temperature limiter
6.1 Hot water NTC sensor 7 Testing point for gas supply pressure
8.1 Pressure gauge 9 Flue gas temperature limiter 15 Relief valve 18 Pump 20 Expansion vessel 27 Automatic air vent 29 Air gas Mixer unit
32.1 Electrode assembly 36 Temperature sensor in CH flow 43 CH flow 63 Adjustable gas flow restrictor 64 Adjusting screw for min. gas flow volume 88 3-way valve (combi) 98 DHW flow switch (combi) 102 Inspection window
120 Fixing points
221.1 Flue duct
221.2 Combustion air intake 226 Fan assembly 295 Appliance type sticker 234 Testing point for combustion products
234.1 Testing point for combustion air 271 Flue duct 349 Cover plate for twin flue duct connection 355 Plate-type domestic hot water heat exchanger 358 Condensate trap 396 Hose Condensate trap 400 Textdisplay 415 Cover plate for cleaning access 416 Condensate collector 418 Data plate 423 Siphon
29
98
102
226
234.1
271
416
221.1
221.2
20
43
9
63
358
64
7
355
6.1
4
415
6
36
32.1
234
349
295
8.1
18
27
88
15
120
418
400
396
423
6 720 610 597 - 02.1O
Page 7
6 720 610 602 GB (03.02)
Details of the appliance
7
1.7 Function
Fig. 3
4 Bosch Heatronic control 6 Temperature limiter, heat exchanger
6.1 Hot water NTC sensor 7 Testing point for gas supply pressure
8.1 Pressure gauge 9 Flue gas temperature limiter 13 Manifold 15 Safety valve 18 Central heating pump 20 Expansion vessel 26 Charging valve 27 Automatic vent 29 Mixer unit
29.1 Bi-metallic thermostat for combustion air compensation 30 Burner 32 Flame sensing electrode 33 Igniter electrode 35 Heat exchanger with cooled combustion chamber 36 Temperature sensor in CH flow 43 CH flow 44 Hot water flow 45 Gas 46 Cold water inlet 47 CH return 52 Solenoid valve 1
52.1 Solenoid valve 2 55 Filter 56 Gas valve CE 427 57 Main valve disc 61 Reset button 63 Adjustable gas flow restrictor
64 Adjusting screw for min. gas flow volume 69 Control valve 84 Motor 88 3-way valve 90 Venturi 91 Pressure relief valve 93 Water flow regulator 94 Diaphragm 95 Pushrod with switch cam 96 Microswitch 97 Valve for hot water flow volume 98 Water valve 221 Flue duct 226 Fan 229 Air box 234 Testing point for flue gas
234.1 Testing point for combustion air 317 Display 355 Plate-type heat exchanger 358 Condensate trap 400 Textdisplay 423 Siphon 443 Diaphragm
ϑ
332930
226
229
234
234.1
26
6
36
29.1
63
15
45 47
20
43
44
46
13
8.1
84
90
97
98
93
94
95
96
91
69
64
57
52.1
56
52
55
7
355
M
358
18
88
max
max
1
2
3
4
5
E
ECO
0
317
61
4
400
32
9
35
221
ϑ
27
6.1
6 720 610 597- 03.2O
423
Page 8
6 720 610 602 GB (03.02)
8
Details of the appliance
1.8 Electrical wiring diagram
Fig. 4
4.1 Ignition transformer 6 Temperature limiter, heat exchanger
6.1 Hot water NTC sensor 9 Flue gas temperature limiter 18 Pump 32 Flame sensing electrode 33 Ignition electrode 36 Temperature sensor in CH flow 52 Solenoid valve 1
52.1 Solenoid valve 2 56 Gas valve CE 427 61 Reset button 84 Motor, 3-way valve 96 Microswitch, hydraulic switch 135 Master switch 136 Temperature control for CH flow 151 Fuse, slow 2.5 A, AC 230 V 153 Transformer 161 Link 226 Fan 300 Code plug 302 Earth connection 310 Temperature control for hot water 312 Fuse, slow T 1,6 A 313 Fuse, slow T 0,5 A 317 Digital display 328 Terminal block for AC 230 V Mains supply
328.1 Link 363 Indicator lamp for burner 364 Indicator lamp for power supply
365 “Chimney sweep” button 366 Service button 367 ECO button 400 Textdisplay 422 Connecting TR2
6
9
32
33
36
52.1
52
56
61
230 V
135
25 V
230V/AC
153
136
151
1247
89
161
M
226
300
L
NLsNs
328
LR
302
310
312
313
317
363
364
365
366
ECO
367
4.1
328.1
6.1
18
84
96
M
400
43F
M
6 720 610 602 - 02.1O
mains supply
422
o - orange g - green bl - black r - red p - purple
r r
bl
bl bl bl
bl
o
o
o
o
g
g
p
p
p
Page 9
6 720 610 602 GB (03.02)
Details of the appliance
9
1.9 Technical data
Units
ZWBR 8-30
Natural gas
ZWBR 11-30
Propane
ZWBR 11-37
Natural gas
ZWBR 14-37
Propane
Max. rated heat output net 40/30˚C central heating Max. rated heat output net 50/30˚C central heating Max. rated heat output net 80/60˚C central heating
kW kW kW
32.3
31.9
30.2
32.3
31.9
30.2
39.7
39.2
37.1
39.7
39.2
37.1 Max. rated heat input net kW 30.5 30.5 37.5 37.5 Min. rated heat output net 40/30˚C Min. rated heat output net 50/30˚C Min. rated heat output net 80/60˚C
kW kW kW
9.5
9.4
8.2
12.7
12.6
11.0
12.9
12.8
11.4
16.2
16.1
14.3 Min. rated heat input net kW 8.8 11.8 11.8 14.8 Max. rated heat output net, domestic hot water kW 30.2 30.2 37.1 37.1 Max. rated heat input net, domestic hot water kW 30.5 30.5 37.5 37.5 Maximum gas flow rate – After 10 minutes from lighting
Natural gas G20 (CVnet 34.02 MJ/m
3
)
m3/h
3.2 3.9
LPG (CVnet 88 MJ/m
3
)
kg/h 2.2 2.7
Gas supply pressure
Natural gas G20 (CVnet 34.02 MJ/m
3
)
mbar 20 - 20 -
LPG (CVnet 88 MJ/m
3
)
mbar - 37 - 37
Expansion vessel
Charge pressure bar 0.75 0.75 0.75 0.75 Total capacity l 10 10 10 10 Hot water specifications Hot water flow rate (factory setting) l/min 8 8 8 8 Max. hot water flow rate l/min 14.0 14.0 14.0 14.0 Outlet temperature range ˚C 40 - 60 40 - 60 40 - 60 40 - 60 Max. permissible water supply pressure bar 10 10 10 10 Min. inlet pressure bar 0.2 0.2 0.2 0.2 Specific flow rate l/min 13.7 13.7 16.9 16.9 Flue Flue gas temp. 80/60˚C, rated/min. load ˚C 78/57 78/57 87/58 87/58 Flue gas temp. 40/30˚C, rated/min. load ˚C 58/35 58/35 65/43 65/43 Residual delivery pressure (inc. pressure drop in air intake duct)
Pa 90 90 100 100
CO2 level at max. rated heat output CO2 level at min. rated heat output
% %
9.4
9.2
11.0
11.0
9.2
9.2
11.0
11.0 NOx-class 5 5 5 5
SEDBUK figure, Band A % 90.3 90.3 90.3 90.3
Condensate
Max. condensation rate (tR = 30˚C) l/h 2.6 2.6 3.2 3.2 pH-value, approx. 4.8 4.8 4.8 4.8
General Data
Electrical power supply voltage AC ... V 230 230 230 230 Frequency Hz 50 50 50 50 Max. power consumption W 156 156 161 161 Noise output level dB(A) 39 39 41 41 Appliance protection rating IP X4D X4D X4D X4D Max. CH flow temperature ˚C nom. 90 nom. 90 nom. 90 nom. 90 Max. permissible operating pressure (CH) bar 2.5 2.5 2.5 2.5 Permissible ambient temperatures ˚C 0 - 50 0 - 50 0 - 50 0 - 50 Nominal capacity of appliance l 3.75 3.75 3.75 3.75 Weight kg 53 53 53 53
Table 2
Page 10
6 720 610 602 GB (03.02)
10
Installation regulations
Condensate analysis, mg/l
Flue system
Elbow - 90 ° Equivalent length 2 m Bend - 45 ° Equivalent length 1m
Gas supply
Domestic water performance
2 Installation regulations
Gas Safety (Installation & Use) Regulations 1998: All gas appliances must be installed by a competent per­son. Failure to install correctly could lead to prosecu­tion. The manufacturers notes must not be taken, in any way, as overriding statutory obligations. The appliance must be installed in accordance with the current IEE Wiring Regulations, local Building Regula­tions, Building Standards (Scotland) (Consolidation), bye-laws of the local Water Company, Health and Safety Document 635 (Electricity at Work Regulations
1989) and any other local requirements. Product Liability regulations indicate that, in certain cir­cumstances, the installer can be held responsible, not only for mistakes on his part but also for damage result­ing from the use of faulty materials. We advise the installer to avoid any risk by using only quality approved branded fittings. The relevant British Standards should be followed i.e.
BS 6798: Specification for the installation of gas
fired hot water boilers of rated input not exceeding 60kW
BS 5449: Central Heating for Domestic Premises
BS 5546: Installation of gas hot water supplies for
domestic purposes
BS 5440:1: Flues and ventilation for gas appliances
of rated input not exceeding 70 kW (net): Flues
BS 5440:2: Flues and ventilation for gas appliances
of rated input not exceeding 70 kW (net): Air Supply
BS 6891: Installation of low pressure gas pipework
installations up to 28mm (R1).
BS 7074:1: Code of practice for domestic heating
and hot water supply
BS 7671: Requirements for Electrical Installation. These instructions must be followed.
Ammonium 1.2 Nickel 0.15 Lead 0.01 Mercury 0.0001 Cadmium 0.001 Sulphate 1 Chromium 0.005 Zinc 0.015
Halogenated hydrocarbons 0.002
Tin 0.01
Hydrocarbons 0.015 Vanadium 0.001
Copper 0.028 pH-value 4.8
Table 3
HORIZONTAL 100 mm – Standard
Overall Diameter of Duct mm 100
Max. 4 m
Flue Terminal / Duct Assembly Length
mm 600
Extension Duct Length mm 1000
Table 4
ALTERNATIVE HORIZONTAL 125 mm FLUE SYSTEM
Overall Diameter of Duct mm 125 Max. 13 m
(ZWBR 8-30)
Max. 10 m (ZWBR 11-37)
including turret
Flue Terminal / Duct Assembly
mm 1030
Table 5
VERTICAL 125 mm FLUE SYSTEM
Overall Diameter of Duct mm 125 Max. 15 m
(ZWBR 8-30)
Max. 12 m (ZWBR 11-37)
Flue Terminal / Duct Assembly
mm 1360
Table 6
Total length of gas supply pipe (metres)
Pipe diameter (mm)
369
Gas discharge rate (m
3
/h)
8.7 5.8 4.6 22
18.0 12.0 9.4 28
Table 7
ZWBR 8-30
ZWBR 11-37
Domestic Water Flow Rate l/min
Tempera­ture Rise
30 °C 14.6 18.0
Tempera­ture Rise
35 °C 12.5 15.4
Tempera­ture Rise
40 °C 11.0 13.5
Maximum Mains pressure bar 10.0 10.0
Minimum Mains pressure bar 0.2 0.2
Table 8
Page 11
6 720 610 602 GB (03.02)
Installation
11
3 Installation
3.1 Important remarks
B Appliance should only be installed in sealed central
heating and hot water systems.
B To avoid gas formation in the system, galvanised
radiators or pipes must not be used.
B If a room thermostat is used: do not fit a thermostatic
radiator valve on the radiator in the primary room.
B This appliance uses an automatically variable pump.
An auto-bypass must not be fitted.
B Add a suitable anti-freeze fluid to the water in the
central heating system. Suitable products are available from Betz-Dearborn Tel.: 0151 4209563 and Fernox Tel.: 01799
550811.
B In our experience, the addition of sealing agents to
the water in the central heating system can cause problems (deposits in the heat exchanger). For that reason we advise against their use.
3.2 Domestic hot water
Any regulations specified by the local water company must be observed.
The final 600 mm of the mains cold water connection to the applaince should be made in copper tube only.
The appliance is suitable for a mains supply having a maximum pressure of 10 bar. A pressure reducing valve must be fitted, if necessary.
The hot water outlet temperature is set to be capable of achieving a maximum of 60˚C. The maximum tempera­ture and the frequency of the recharge of the heat store may be reset.
The water flow rate of 11.0 l/min (ZWBR 8-30) and
13.5 l/min (ZWBR 11-37) will give a temperature rise of 40˚C. If a higher rise is required then the flow must be reduced at the tap and the discharge temperature will rise up to the maximum set figure.
The temperature rise, upto the maximum set by the user, is automatically maintained by the modulation of the heat input. In winter, when the mains temperature is very low, the water flow, adjusted at the tap or shower, should be reduced to maintain the required delivery temperature.
It is suggested that long pipe runs to taps or showers be insulated to prevent the rapid cooling of the water.
All types of single lever mixer taps and thermostatic mixer units suitable for a mains pressure of up to 10 bar can be used.
The head of a loose-head shower must not be allowed to fall within 25 mm of the top the bath to prevent the risk of water being drawn back into the mains. Alterna­tively the shower must be fitted with an anti-syphonage device at the point of the flexible hose connections.
Over-rim bidets may be connected to the appliance provided that it is in accordance with the requirements of the local water company. The outlet(s) should be shrouded and unable to have any temporary hand held spray attached. No anti-syphonage arrangements are necessary.
In exceptionally hard water areas a device to prevent scale formation may be fitted or, alternatively, the maxi­mum temperature reset to about 45˚C which may reduce the risk of scale formation. The installation of a scale inhibitor assembly should be in accordance with the requirements of the local water company. Artificially softened water must not be used to fill the central heat­ing system. An isolating valve should be fitted to allow for servicing.
Devices, such as water meters or back-flow pre­vention valves, capable of preventing the flow of expansion water must not be fitted unless sepa­rate arrangements have been made.
A Zilmet Z160 expansion vessel is the preferred type. A thread sealant compatible with potable water must be used. The vessel should be connected into the cold water mains inlet pipe as close as possible to the appli­ance.
3.3 Sealed systems
The appliance must not be operated without the system being full of water, properly vented and pressurised.
The expansion vessel has a volume of 10 litres and is charged to a pressure of 0.75 bar.
The water capacity of the system is shown in table 11, page 31. If a greater capacity is required then an addi­tional expansion vessel must be fitted into the system return as close to the appliance as possible. The system pressure can be set up to a maximum of 1.5 bar with 1 bar being the normal setting.
If the system pressure is greater than 2.5 bar when the appliance is operating at maximum temperature then an additional expansion vessel must be fitted into the sys­tem return as close to the appliance as possible.
The filling point must be at low level and arranged as shown in figs. 5 and 6.
The pressure relief valve is set to operate at 3 bar. There must be no connection to the mains without the
approval of the local water company. All connections in the system must be capable of withstanding a pressure
B Always turn off the gas cock before car-
rying out any work on components which carry gas.
i
Fixing of the appliance, gas and flue con­nections, commissioning of the system and electrical connections may only be carried out by competent persons author­ised by CORGI.
Page 12
6 720 610 602 GB (03.02)
12
Installation
of up to 3 bar and the radiator valves conform to the requirements of BS2767:10.
If Thermostatic Radiator Valves are fitted then it is rec­ommended that the primary radiator is left open.
Repeated venting probably indicates a leak and this must be rectified to ensure the proper operation of the appliance.
No galvanised radiators or pipes must be used. If any system water treatment is required then
only products suitable for use with Aluminium shall be used i.e Fernox- Copal or Superconcen­trate or Sentinal X100, in accordance with the
manufacturers instructions. The use of any other substances will invalidate the guarantee. The pH value of the system water must be less than 8 or the appliance guarantee will be invalidated.
A drain cock to BS2879 must be fitted to the lowest point of the system.
IMPORTANT: Check that no dirt is left in the water pipework as this could damage the appli­ance. Thoroughly flush the heating system and the mains water supply before fitting the appli­ance to the wall in accordance with the recom­mendations of BS7593:1992.
Fig. 5 Sealed primary water system
Fig. 6
3.4 Siting the appliance
Regulations concerning the Installation Site
B Relevant national regulations must be complied with
section 3.9.1.
B Consult the installation instructions for details of min-
imum clearances required.
Combustion air
In order to prevent corrosion, the combustion air must not contain any corrosive substances.
Substances classed as corrosion-promoting include halogenated hydrocarbons which contain chlorine and fluorine compounds and are contained in some sol­vents, paints, adhesives, aerosol propellants and household cleaners, for example.
Surface temperature
The max. surface temperature of the casing and the flue is less than 85 °C. This means that, no special safety precautions are required with regard to flammable building materials and fitted furniture. The specified clearences must be maintained.
Domestic hot water
Central heating flow
Radiator
valve
Lockshield
valve
Central heating return
A drain cock should be fitted at the lowest point of the heating circuit and the appliance
Water main
BS stop valve. Fixed spindle type
APPLIANCE
Refer to Fig.1
Appliance water flow
diagram
WRAS approved
filling loop
6 720 610 576 -09.3O
Heating return
Non return
valve
Non return
valve
Hose union
Test cock
Temporary hose
Stop cock
Auto
air vent
Heating return
Stop cock
Fill point
Non return valve
Make up
vessel
1000mm (39 in) above the highest point of the system.
Sealed system filling and make up
6 720 611 137 - 29.1O
Page 13
6 720 610 602 GB (03.02)
Installation
13
Cupboard/Compartment
The appliance can be installed in a cupboard/compart­ment need for airing clothes providing that the require­ments of BS6798 and BS5440:2 are followed. The low casing losses from the appliance eliminate the need for ventilation openings in the compartment.
3.5 Wall mounting frame assembly
B Take the wall mounting frame out of the package and
screw together with 6 screws as shown in fig. 7. Use the outer lugs on the top and bottom horizontal sec­tions for the appliances that are 512 mm wide.
Fig. 7
B Hold the wall-mounting frame against the wall ensur-
ing that it is vertical.
B Mark the position of the flue duct hole if a rear flue is
to be used. Refer to fig. 1 and 16.
B Mark the holes for the wall mounting frame onto the
wall, drill and plug the holes and screw the wall mounting frame to the wall with the screws provided.
Fig. 8
B Screw the pre-plumbing manifold with two screws to
the wall mounting frame.
Fig. 9
3.6 Pre-piping the system
Fig. 10 Manifold
43 CH flow 47 CH return 112 Gas cock 171 Domestic hot water 172 Cold water relief
B A drain tap should be fitted at the lowest point of the
central heating system.
B WRAS approved filling loop must be fitted.
6 720 610 597-06.1O
6 720 610 597-07.1O
6 720 610 597-08.1O
200
260
6 720 610 576-06.1O
35
120-130
50
4743
172112
171
Page 14
6 720 610 602 GB (03.02)
14
Installation
Condensate Termination and Route
The condensate connection on the British Gas/Bosch appliances is in 22 mm plastic. The pipe should be extended and run away from the appliance with a con­stant fall of 2.5 ° or 40 mm in every metre.
The condensate pipe can terminate into any of four areas:
Fig. 11
Whilst all of the above methods are acceptable it is always the best practice to terminate the condense pipe via an internal waste system.This will eliminate the need for any external condensate pipe runs which can be susceptible to freezing in extreme weather.
Fig. 12 Position of the condensate drain
External condensate pipework
All British Gas/Bosch condensing boilers have within a syphonic condensate trap. Rather than the condensate constantly dripping into the discharge pipe, the con­densate is collected into a trap which releases it in 100 ml quantities. This will help prevent freezing occurring.
If there is no alternative and the condensate pipe has to be externally run, the following should be considered:
The pipe run should take the shortest practical route.
The pipework should be insulated with weather
resistant insulation.
The pipe should terminate as close as possible to the
ground or drain, whilst still allowing the condensate to safely disperse. This would prevent wind blowing up the pipe.
The pipework should be installed with the minimum
of horizontal runs and with a downward slope of at least 2.5 °.
3.7 Fitting the appliance
B Remove packing, taking care to observe the instruc-
tions on the packing.
B Lie the boiler on its back.
Removing the outer case
B Remove retaining screw on left hand side (1). B Press both catch levers backwards (2).
Boiler
Boiler
Sink
Ø 22 min.
Ø 22 min.
Ø 22 min.
Ø 22 min.
Siphon
Siphon
75 min. trap
Invert
No length restriction
No length restriction
No length restriction
Internal soil and vent stack
The gradient of the discharge pipe should be 2.5° (40 mm/m) minimum
The gradient of the discharge pipe should be 2.5° (40 mm/m) minimum
The gradient of the discharge pipe should be 2.5° (40 mm/m) minimum
An internal waste system
An external waste system
The rainwater system
An external purpose made soakaway
The gradient of the discharge pipe should be
2.5° (40 mm/m) minimum
Use waterproof pipe work insulation in very exposed positions
External length of pipe 2m min.
Open end of pipe direct into gully, below ground but above water level.
Open end of pipe direct into gully, below ground but above water level
Open end of pipe direct into gully, below ground but above water level
75 min. trap
450 min.
Siphon
75 min. trap
Boiler
6 720 610 596 -03.1O
Boiler
Sink
6 720 610 602 - 03.1O
Benchmark: For optimum performance after installation, this boiler and its asso­ciated central heating system must be flushed in accordance with the guide­lines given in BS5793:1992 “Treatment of water in domestic hot water central heating systems”.
i
The outer case is secured against unau­thorised removal by a retaining bracket (electrical safety) at the bottom left. Always secure the outer case with this bracket again after refitting.
Page 15
6 720 610 602 GB (03.02)
Installation
15
B Lift off the top fixing lugs and slide the case forwards
and remove (3).
Fig. 13
Fixing the appliance
B Fit the washers onto the gas and water connections. B Lift the boiler onto the wall-mounting frame. The lugs
pass through the rectangular holes in the boiler back panel.
B Take care not to disturb the washers on the connec-
tions.
Connecting the flue duct
B Fit flue duct connector onto appliance flue spigot. B Secure with the two screws supplied.
Fig. 14
B For remaining installation of flue assembly, refer to
the relevant installation instructions.
3.8 Checking the connections
Water connections
B Check that the O-rings or seals are in place before
tightening the connection.
B Turn on the service valves for central heating flow
and return and fill the heating system through a WRAS approved filling loop.
B Check all seals and unions for leaks (testing pres-
sure max. 3.0 bar as indicated by pressure gauge).
B Turn on cold water service cock and fill hot water
system (testing pressure max. 10 bar).
B Check all connections for leaks.
Gas supply pipe
B Check that the seal is in place before tightening the
connection.
B Turn off gas cock to protect gas valve against dam-
age from excessive pressure.
B Check gas supply pipe. B Release the pressure on the gas supply pipe.
3.9 Flue Systems
The only flue systems that may be used are those sup­plied with the boiler. The flue system must be installed in accordance with the requirements of BS5440:1.
Standard 100 mm flue system
The standard concentric flue system provides for a hor­izontal length of upto 4 m. Full instructions for fitting this flue are in Subsection 3.9.2 “Installation of the flue”.
Alternative 125 mm diameter flue systems
Installation instructions for the alternative flue systems are sent with the appropriate flue kit.
Systems are available to give a maximum horizontal length of 13 m (ZWBR 8-30) and 10 m (ZWBR 11-37).
A vertical flue system upto a height of 15 m (ZWBR 8-
30) and 12 m (ZWBR 11-37) is available. 45° and 90° flue bends can be used with a correspond-
ing reduction in flue length of 2 m for each 90° bend and 1 m for each 45° bend used.
IMPORTANT: Any horizontal flue system fitted to a condensing boiler must incline towards the appliance at an angle of 3 % (30 mm per metre length) to prevent condensate dripping from the flue terminal. This
means that the clearance above the appliance must be increased to match the duct length. Refer to fig. 1 on page 5.
1
.
2
6 720 610 597 -09.1O
.
2.
3.
6 7 2 0 6 1 0 3 3 2 - 0 9 . 2 R
1
3
2
4
1 .
2 .
Page 16
6 720 610 602 GB (03.02)
16
Installation
3.9.1 Siting the Flue Terminal
The flue must be installed in accordance with BS 5440:1 and the Building Regulations. Flue termi­nals in carports and under balconies are to be avoided. The terminal must be positioned so that it does not cause an obstruction nor the combustion products a nuisance. See fig. 15 and table 9. The terminal will, at times, give out a plume of water vapour and consideration must be given to this when choosing a terminal position. Keep clear of security
lighting, activated by passive infra-red sensing heads. If the terminal is less than 2 m above a surface to which people have access then a guard must be fitted. The guard must be evenly spaced about the terminal with a space of 50 mm in each direction and fixed with plated screws. A guard Type K6 for the standard horizontal flue, can be obtained from Tower Flue Components, Vale Rise, Ton­bridge TN9 1TB.
Fig. 15
Minimum dimensions of flue terminal positions (all types) (see fig. 15)
Dimension Terminal Position (kW input expressed in net) Balanced fl ues room sealed: Fanned draught
A
1)
Directly below an opening, air brick, opening windows, etc. 300 mm
B
1)
Above an opening, air brick, opening window, etc. 300 mm
C
1)
Horizontally to an opening, air brick, opening window, etc. 300 mm D Below gutters, soil pipes or drain pipes 75 mm E Below eaves 200 mm F
2)
Below balconies or car port roof (lowest point) 200 mm G From a vertical drain pipe or soil pipe 150 mm H From an internal or external corner 300 mm I Above ground roof or balcony level 300 mm J From a surface facing the terminal 600 mm K From a terminal facing the terminal 1200 mm L From an opening in the car port (e. g. door, window) into the dwelling 1200 mm M Vertically from a terminal on the same wall 1500 mm N Horizontally from a terminal on the same wall 300 mm O From the wall on which the terminal is mounted Not applicable P From a vertical structure on the roof Not applicable Q Above intersection with roof Not applicable
Table 9
1) In addition, the terminal should not be nearer than 150 mm (fanned draught) to an opening in the building fabric formed for the purpose of accommo­dating a built-in element such as a window frame.
2) Not recommended.
Page 17
6 720 610 602 GB (03.02)
Installation
17
3.9.2 Installation of the flue
The standard 100 mm diameter horizontal flue system is suitable for lengths upto 4 m. Flues upto 650 mm do not require an extension duct assembly. Flues between 1600 mm and 4000 mm require exten­sion duct assemblies. NOTE: Flue lengths between 650 mm and 730 mm cannot be accomodated. Refer to fig. 17, 18, 19.
Standard system comprise: Flue turret - Flue turret clamp - Terminal assembly - Wall sealing - plates. Extension kit comprises: Air duct - Flue duct - Duct clamp. Refer to fig. 20.
Instructions for fitting other flue systems are packed with the relevant flue kit. Check that the position chosen for the appliance is sat­isfactory. Refer to fig. 16.
Fig. 16 Marking the position of the side flue opening
Fig. 17 Standard Flue
Appliance
120
Drilling point for flue duct opening
3 %
(30 mm/metre)
Centre line of flue opening and appliance
Centre line of flue/air duct
Top of the
wall
mounting
frame
H
H Standard Horizontal Flue 158 mm Optional Horizontal Flue 121 mm
6 720 610 602-07.2O
Flue Turret
No Clamp
Maximum 650 mm
Terminal Assembly
Outer Wall
6 720 610 602 - 08.1O
Page 18
6 720 610 602 GB (03.02)
18
Installation
Fig. 18 Flue with One Extension
Fig. 19 Flue with Extensions
Fig. 20 Flue Components
Maximum 1600mm
Flue Turret
No Clamp
Terminal Assembly
Outer Wall
Extension Duct
6 720 610 602 - 09.1O
Clamp
Flue Turret
No Clamp
Clamp
Extension Duct
Clamp
Extension Duct
Terminal Assembly
Outer Wall
6 720 610 602 - 10.1O
Extension Air Duct
Extension Flue Duct
Terminal Assembly
Duct Clamp
Wall Sealing Plates
6 720 610 602 - 11.1O
Flue Turret
Page 19
6 720 610 602 GB (03.02)
Installation
19
3.9.3 Flue duct preparation and assembly
Measure the flue length L. Refer to fig. 21, 22.
Fig. 21 Flue length - rear
Fig. 22 Flue length - side
Mark off the lengths shown onto the ducts and cut to length. The cuts must be square and free from burrs. Terminal assembly outer (air) duct - L- 70 mm, inner (flue) duct - L- 50 mm.The measurement is made from the ridge at the terminal indicating the outer face of the wall. Refer to fig. 23. Extension air duct - L- 70mm, flue duct - L- 50 mm. The measurement is from the formed end.
Fig. 23 Flue terminal position
Assemble flue system completely. Push the ducts fully together and clamp in the positions. The slope of the terminal outlet must face downwards.
The assembly will be made easier if a solvent free grease is lightly applied i.e Vaseline, to the male end of the ducts.
NOTE: An inner wall sealing plate is provided which should be fitted to the ducts before assem­bly.
Push the assembly through the wall and fix the turret to the appliance with the clamp. Refer to fig. 24.
Fig. 24 Flue turret
Ensure that the turret is fully entered into the socket on the boiler. From the outside fix the outer wall plate to the terminal and, after ensuring the duct is properly i nclined towards the boiler, fix the plate to the wall.
If the terminal is within 2 m of the ground where there is access then an approved terminal guard must be fitted. The guard must give a clearance of at least 50 mm around the terminal an be fixed with corrosion resistant screws.
NOTE: THE FLUE MUST BE INCLINED T O THE
BOILER
L
120
6 720 610 602 - 12.1O
NOTE: THE FLUE MUST BE INCLINED T O THE
BOILER
L
6 720 610 602 - 13.1O
Outer Wall Face
Flue Terminal
Raised Ring locating the terminal relative to the outside wall face
6 720 610 576 - 20.1O
Air and Flue Duct Entry into silicone rubber seals
Flue Turret
Clamp
Flue Socket on Boiler
6 720 610 602 - 14.1O
Page 20
6 720 610 602 GB (03.02)
20
Electrical connections
4 Electrical connections
All control and safety systems are built into the appli­ance.
B Allow mains cable to protrude at least 50 cm from
wall.
B To make splash-water proof (IP): cut the cable grom-
met hole size to match diameter of cable, see fig. 27.
It must be possible to isolate the appliance. The appli­ance must be earthed.
The appliance must be connected to the mains through a 6 A double pole isolator with a contact separation 3 mm in all poles and supplying the appliance and con­trols only. The wiring must comply with the current requirements of the IEE Wiring Regulations and any local regulations which apply.
Supply: 230 V ~ 50 Hz, 140 Watts
Mains cable: PVC insulated 0.75 mm2
(24 x 0.20 mm) to BS6500-Table 6. Temperature rated 100˚C.
Protection IPX4D
External fuse 3 A.
4.1 Connecting the appliance
To gain access to the mains connection remove the drop down facia cover. The drop down cover is removed by lowering it to the horizontal position and pushing firmly upwards at the rear of the supports to release the cover. Lift cover from the appliance.
After installation (or in the event of an electrical fault) the electrical system shall be checked for short circuits, fuse failure, incorrect polarity of connections, earth con­tinuity and resistance to earth.
B Pull out cover panel at the bottom and remove. Refer
to fig. 25.
Fig. 25
B Remove screw and slide terminal cover forwards to
remove. Refer to fig. 26.
Fig. 26
B Always disconnect the power supply to
the appliance at the mains before carry­ing out any work on the electrical sys­tems and components.
0
1
2
3
4
5
E
6 720 610 332-10.1R
0
1
2
3
4
5
E
6 720 610 336 -18.1R
Page 21
6 720 610 602 GB (03.02)
Electrical connections
21
B Cut cable grommet to diameter of cable.
Fig. 27
B Feed cable through cable grommet and connect the
mains supply cable, see fig. 28.
B Secure cable in cable grommet by means of cable
grip.
Fig. 28
4.2 Connecting TR2 Room thermostat
The TR2 should be connected to terminals 3, 4 and F beneath the Textdisplay, page 8, fig. 4, item 422.
4.3 Mains Voltage external controls connections
Fig. 29
Note: If an external timer is used then the domestic hot water pre-heat facility can only be isolated by actuating the ECO-button.
0
1
2
3
4
5
E
6 720 610 332-12.1R
13-14
10-12
8-9
5-7
L
N
N
LL
R
S
S
4130-14.1R
230 V R
oom Thermostat Connections
Ns
Ls
L
R
ST8
Ns
Ls
L
R
ST8
Remove Link
Neutral
Liv
e
Swit
ched Liv
e
Neutr
al
Live
Swit
ched Live
Motor
230 V Pr
ogrammer Connections
230 V r
oom thermostat and
Programmer Connections
Ns
Ls
L
R
ST8
Neutral
Live
N
eutr
al
Live
Swit
ched Liv
e
Motor
S
w
it
c
h
e
d
L
iv
e
Series connection to be made
safe
NOTE: Only double insulated controls not requiring an earth can be used
6 720 610 576 - 22.1O
Page 22
6 720 610 602 GB (03.02)
22
Commissioning
5 Commissioning
Fig. 30
8.1 Pressure gauge 15 Safety valve 27 Automatic vent 61 Reset button 135 Master switch 136 Temperature control for central heating 170 Service cocks on CH flow and return 171 Hot water 172 Gas cock (shown in off position) 173 Cold water service cock 295 Appliance type sticker 310 Temperature control for hot water 317 Multifunction display 358 Condensation trap 363 Indicator lamp for burner 364 Indicator lamp for power supply 365 “Chimney sweep” button 366 Service button 367 ECO button 400 Textdisplay
5.1 Commissioning
Benchmark Water Treatment: For optimum perform­ance after installation, this boiler and its associated cen­tral heating system should be flushed in accordance with the guidelines given in BS7593:1992 - Treatment of water in domestic hot water systems. Full instruc­tions are supplied with proprietary cleansers sold for this purpose. If an inhibitor is to be used after flushing, it should be used in accordance with the inhibitor man­ufacturers instructions.
To drain the appliance shut the system valves and open the system drain point.
Suitable flushing agents and inhibitors are available from Betz/Dearborn Tel.: 0151 4209563, Fernox Tel.: 01799 550811 and Salamander Tel.: 0121 378 0952. Instructions for use are supplied with the these products.
.
nn
ECO
364
135
295
E
8.1
365
61
317 366 367
310
136
363
400
15
27
358
6 720 610 597 - 05.1O
170
171
173
170
172
Never run the appliance when empty or unpressurised.
i
The operational CO2 level is set at the fac­tory and no adjustment is necessary when installing a natural gas fired appliance.
Page 23
6 720 610 602 GB (03.02)
Commissioning
23
B Before commissioning, the gas supply pres-
sure must be checked at the gas supply pres­sure test point (see page 6, fig. 2, item 7). Natural gas appliances must not be operated if the gas supply pressure is below 18 mbar or above 24 mbar. LPG appliances must not be operated if the supply pressure is not 37 mbar at the inlet to the appliance.
B Unscrew the condensation trap (358) and pull out,
fill with approx. 1/4 l of water and refit. Refer to fig. 30.
B Adjust charge pressure of expansion vessel to static
head of the central heating system (see page 31).
B Open all system radiator valves. B Turn on service valves (170), fill central heating sys-
tem to pressure of 1 - 2 bar through the WRAS approved filling loop. Refer to fig. 30.
B Vent radiators. B Refill heating system and set the pressure to 1 bar. B Turn on cold water service cock (173). Refer to
fig. 30.
B Check that the gas type specified on the identifica-
tion plate matches that of the gas supply.
B Turn on gas cock (172). Refer to fig. 30.
5.2 Switching the appliance on/off
Switching on
B Switch on the appliance at the master switch (I).
The indicator lamp shows green and the display will show the central heating flow temperature, when the appliance is operating in the central heating mode.
Fig. 31
The trap filling programme ensures that the condensa­tion trap is filled after the appliance has been installed or after the appliance has been out of use for a long period or the mains supply has been interrupted. For that reason, the appliance remains at minimum heating output for 15 minutes.
B Open automatic vent (27) and re-close after venting
(page 22).
Switching off the appliance
B Set the master switch to (0).
The green indicator lamp goes out. The optional timer will continue running until the emergency sup­ply is exhausted.
5.3 Switching on the central heating
The central heating flow temperature is adjustable between 35˚C and 88˚C. Refer to table 12, page 31.
B Turn the temperature control to set the flow tem-
perature to a level appropriate to the type of central heating system:
– Underfloor heating: e.g. setting “3”
(approx. 50˚C)
– Low-temperature heating: setting “E
(approx. 75˚C)
– Central heating systems for flow temperatures up
to 88 °C: limited “max” setting for low-temperature operation (see page 31).
When the burner is alight, the red indicator lamp lights up.
Fig. 32
5.4 System controls
B Set room thermostat to the desired room tempera-
ture.
B Set outside- temperature driven control unit, if fitted.
Refer to the instructions with the control.
B Set the thermostatic radiator valves to the desired
settings.
i
If the display alternates between -II- and the central heating flow temperature, the trap filling programme is active.
6 720 610 333-04.1O
B Always disconnect the appliance from
the power supply (fuse, circuit breaker) before carrying out any work on the electrical systems or components.
6 720 610 333-05.1O
Page 24
6 720 610 602 GB (03.02)
24
Commissioning
5.5 Setting the domestic hot water temperature and flow rate
5.5.1 Domestic hot water temperature
The hot water temperature can be set to between approx. 40 °C and 60 °C.
This temperature is not shown on the display.
Fig. 33
“ECO” button
By pressing and holding the “ECO” button , until the display lights, you can switch between Comfort mode and Economy mode.
Comfort mode: button is not lit (factory setting)
The appliance is held constantly at the set temperature. This means that hot water is available almost instanta­neously at the tap. Consequently the appliance will switch on at intervals, even if no hot water is being drawn.
ECO mode with demand detection, button is lit
The demand detection function enables maximum gas and water economy. Briefly turning a hot water tap on and then off again sig­nals demand to the appliance which then heats up the water to the set temperature. Hot water is thus available in about 1 minute.
ECO mode, button is lit
Water is not heated up until hot water is drawn. This means that there is a longer waiting period before hot water is available.
5.5.2 Hot water flow rate
The flow rate is factory set to 8 l/min. Under standard conditions (2 bar) supply pressure, one
full turn is equivalent to approximately 2 l/min.
B To increase the flow rate (max. 14 l/min):
turn screw on flow switch anti-clockwise (+). The outlet temperature will decrease relative to the increase in the flow rate.
B To reduce the flow rate (min. 8 l/min):
turn screw on flow switch clockwise (–). The outlet temperature will increase relative to the decrease in the flow rate.
Fig. 34
5.6 Summer mode (hot water only)
With room thermostat
B Turn temperature control on the appliance anti-
clockwise as far as the stop. The central heating is now turned off. The hot water function and the mains power supply for the heating programmer and timer remain switched on.
5.7 Frost protection
B Leave master switch switched on.
If the appliance is to be left for long periods switch the central heating off:
B Add a suitable anti-freeze fluid to the water in the
central heating system. Suitable products are available from Betz-Dearborn Tel.: 0151 4209563 and Fernox Tel.: 01799
550811.
5.8 Pump anti-seize function
Every time the pump is switched off, a timer is started. If after 24 hours the pump has not run again, it is switched on for a period of 10 seconds.
Setting Hot Water temperature
Turn fully anti-clockwise approx. 40˚C
approx. 55˚C
Turn fully clockwise approx. 60˚C
Table 10
6 720 610 333-07.1O
i
Frost protection and constant frost pro­tection modes can be set on the text dis­play module.
i
This function prevents the central heating pump seizing after long periods of inactiv­ity.
6720 610 332-25.1O
Page 25
6 720 610 602 GB (03.02)
Commissioning
25
5.9 Fault Condition
In the unlikely event of a fault occuring while the appli­ance is in operation:
The display and the textdisplay then show a fault code and the button may also flash.
If the button flashes: B Press and hold the button until the display shows
“– –”. The appliance will then start up again and the display
will show the central heating flow temperature. If the button does not flash: B Switch the appliance off and then on again at the
master switch.
The appliance will start up again and the central heat-
ing flow temperature will be displayed.
i
A list of faults that may occur is given on page 46.
Page 26
6 720 610 602 GB (03.02)
26
Text Display
6 Text Display
6.1 General Description
The text display is used to display information about
the appliance and the system and to alter the set­tings displayed.
Once the appliance has been in operation for one
day, the text display module has a power buffer period of about 10 hours during which it will run with­out the mains power supply. After that period has elapsed, the clock function shuts down but all other settings are retained.
6.2 Programming
Fig. 35 Controls
a Display b “Up”/“More” button c “Down”/“Less” button d “Back” button e “Next” button f “Delete” button
The standard display shows the following information:
Time
Room temperature (if TR 2 connected)
CH flow temperature
Domestic Hot Water temperature (ZSBR if a Stor-
age Tank is accorded).
Additional indication if a special programme is active:
x holidays
Hot water immediately
Constant on (comfort, if TR2 is not connected)
Constant off (economy, if TR2 is not connected).
Other special operating modes may be displayed dur­ing commissioning, servicing, etc.
The programming procedure is described in detail below using the clock function as an example:
B To start programming, press any button, e. g. .
The display lighting switches on and the main menu is displayed:
Fig. 36 Main menu
B Use the or button to move the cursor
arrow on the left of the menu so that it points to the desired menu item. In this example, the cursor is positioned next to the menu item Time/day/holidays.
B Confirm the selection by pressing the button.
The corresponding submenu is displayed:
Fig. 37 Submenu: Time/day
In the submenus, the top line indicates what action is required. The bottom line shows the previous menu level, if appli­cable (see fig. 38).
B Use the or button to select Time/day. B Confirm the selection by pressing the button.
The corresponding submenu is displayed:
Fig. 38 Setting the hour
When settings are being entered, the setting to be altered is indicated on the top line. In addition, the set­ting being altered is displayed with a dark background.
B Use the or button to set the hour.
– Press and release to change the display by one
unit at a time
– Press and hold to change the display rapidly
B Confirm the setting by pressing the button.
B Use the or button to set the minutes. B Confirm the setting by pressing the button. B Use the or button to set the day of the
week.
c
b
a
f
e
d
C
6 720 610 337-08.1R
6 720 610 598-04.2O
T
/holidays
6 720 610 598-05.2O
T
6 720 610 598-06.2O
T
H
Page 27
6 720 610 602 GB (03.02)
Text Display
27
B Press the button to confirm the setting. The
cursor then returns to the top line.
-or-
B Press the button to confirm the setting and
return to the previous menu (fig. 37 page 26).
-or-
B Do not press any other buttons for 15 minutes.
6.2.1 Deleting a setting
Either overwrite the setting or press the button to delete it.
B Find the setting to be deleted. B Press and release the button.
The display shows --:--
6.2.2 Resetting all parameters to their original
settings
B Press and hold the button for more than 15 sec-
onds.
After about 5 seconds, the following message
appears on the display:
ATTENTION
Delete all parameters
in x seconds
Once the reset has been completed, the following
message is displayed:
Please wait... Initialising
6.3 Menu structure
i
The hours of service can not be reset to 0.
C
C
C
Submenu
Main menu 1. 2. 3.
Parameters to change/select
Page
Time/ day/holi­days
Time/day - - - Hours
- Minutes
- Day of week
28
Holidays - - Days holiday 28
Heating Heating
program
- - - Day
- 1st operating mode
- 1st switching point ...
- 6th switching point
28
Set econ­omy temp. (if TR2 is con­nected)
- - 5...30˚C 28
Manual (if TR2 is not con­nected)
- - - Automatic
- Constant on (comfort)
- Constant off (economy)
29
Hot water
Hot water program
- - - Day
- 1st operating mode
- 1st switching point
...
- 6th switching point
29
Hot water immedi­ately
- - Off/On 29
Info - - - - 29 Settings Heating - - Optimum Start Off/On 30
Hot water (ZSBR­models)
- - Only charging times/ times and tempera­tures
29
Service Display
service param.
- - 30
Further options
Lan­guage
-English/
-Français/
-Deutsch
30
-Time correction
-LCD contrast
30 30
Operat­ing times
- 30
Fault history
- 30
Page 28
6 720 610 602 GB (03.02)
28
Text Display
6.4 Setting the time/day
6.4.1 Setting the time and day
For details of how to set the time and day, refer to page 26.
6.4.2 Holidays
In the Holiday programme, the central heating runs in Economy mode and the hot water is switched off (frost protection function remains active).
B From the main menu, select Time/day/holidays,
and from the first submenu select Holidays.
B Enter the number of days holiday by pressing or
(max. 99 days holiday). After the set number of days, the text display module automatically cancels Economy mode at midnight on the last day and returns to Automatic mode.
To cancel Holiday mode early: B In the Holidays submenu:
Press the button until the display shows 0 .
6.5 Heating
6.5.1 Heating programme
Basic setting (Automatic mode)
The appliance switches automatically between nor-
mal heating, Economy mode and Frost protection mode according to the timer settings entered.
Basic setting:Heating starts at 6:00 amEconomy starts at 10:00 pm
Setting options
Maximum of six switching points per day with three different operating modes (Heating, Economy, Frost protection).
Same times for Monday to Friday.
Same times for Saturday and Sunday.
Different times for every day.
Setting switching times and operating mode
B From the main menu select Heating and then from
the first submenu, select Heating program.
B Select Monday - Friday, Saturday and Sunday or
an individual day of the week. – Monday - Friday: to have “Heating” and “Econ-
omy” or “Frost protection” switching on at the same times every weekday.
Saturday - Sunday: to have “Heating” and
“Economy” or “Frost protection” switching on at the same times Saturday and Sunday.
– Individual day of the week (e. g. Thursday): to
have the relevant program always switching on at the specified time on that day of the week, i.e. “Heating”, “Economy” or “Frost protection” at the same time every Thursday.
B Press . The display shows Set 1. operating
mode.
B Set the desired first operating mode (Heating, Econ-
omy or Frost protection).
B Press . The display shows Set 1. time period. B Set the desired first time period. B Press . Set the following operating modes and
time periods as described for the first.
B If necessary: select the next day and enter the oper-
ating modes and timer periods as described above.
Timer periods and operating modes are you do not wish to change can be skipped by pressing .
6.5.2 Setting the Economy temperature (if TR2 is connected)
This option allows you to set the room temperature for Economy mode (Off (Economy)).
This function is only active if:
Automatic mode or Economy mode is set on the TR
2 room thermostat.
B From the main menu, select Heating and then from
the first submenu, select Set Economy temp..
B Use the or button to set a temperature
between 5 and 30 ˚C.
i
Changing winter and summer time:
B Only adjust the clock! Do not alter the
switching points (for heating, econo­my, etc.).
i
The day on which you enter the days holiday counts as the first day of the holiday, i.e. the unit starts the holiday program immediately. Only include the day on which you are return­ing if you don’t want the heating to return to the normal program on that day!
C
i
If the settings for a particular day of the week are different from the settings for the other days, then if Monday - Friday or Saturday and Sunday is selected, the display shows
--:--, i.e. there are no common switching points for those options.
Page 29
6 720 610 602 GB (03.02)
Text Display
29
6.5.3 Manual operating mode (if TR2 is not con­nected)
For selecting an operating mode that is different from the one set in the heating programme (Automatic mode).
You can choose between Automatic, Constant on
(comfort) and Constant off (economy).
The manually selected operating mode starts imme-
diately.
Constant off (economy) and Constant on (comfort)
are automatically reset at 00.00 (midnight).
To cancel the manually selected operating mode:
select the relevant menu and then press the
button,
or select a different operating mode,or set Holiday.
B From the main menu select Heating and then from
the first submenu Manual select required mode.
6.6 Hot water
General description
Combi models only: The basic settings provide a
straightforward timer programme: enabled from 5:00 am, disabled from 10:00 pm. The ECO button must not be lit (Comfort mode).
ZSBR models (with Storage Tank): The basic
settings provide a timer programme: enable from 5:00 am, disable from 10:00 pm. With the menu Hot water (see page 29) you can choose a timer-/tem­perature programme with the basic settings: 60˚C from 5:00 am, 10˚C from 10:00 pm.
6.6.1 Hot water programme
Up to six switching points per day can be set.
There are two operating modes: Blocked and
Released.
B From the main menu, select Hot water and then
from the first submenu, select Hot water program.
B Set the days of the week, Blocked/Released (oper-
ating mode) in the same way as for the switching points and modes for heating as described on page 28.
6.6.2 Hot water immediately
Hot water immediately ON:
Comfort mode is active for 2 hours.
Comfort mode is active for 2 hours: normal auto-
matic program (Hot water mode according to timer programme entered).
B From the main menu, select Hot water and then
from the first submenu, select Hot water immedi- ately.
B Press or to switch Hot water immedi-
ately on or off.
6.7 i Info
B Select Info from the main menu.
You can view the following information:
C
Display text Description
Room tempera­ture
(if TR 2 connected)
Current temperature in the room where TR 2 is installed
Required room temperature
(if TR 2 connected)
Required temperature in room where TR 2 is installed
Operating mode
(if TR 2 connected)
E. g. Heating, Economy in Automatic mode or Economy, Heating, Frost protection in manual mode
Max. flow temp. Maximum CH flow tempera-
ture set on the temperature control for CH flow
Actual flow temp. Actual CH flow temperature Required flow
temp.
Required CH flow tempera­ture
Max HW temp. Maximum permissible hot
water outflow temperature
Required HW temp.
Required hot water temper­ature
Actual HW temp. Actual hot water outflow
temperature
Storage Tank charge released or blocked
Shows, if hot water is released or blocked
Storage Tank charge on or off or Storage Tank charge afterrunning
Shows, if hot water is on or off, or if the pump for the Storage Tank afterrunning is on
Boiler operat. mode winter/ summer
Indicates which mode the CH flow temperature control is set to
Burner on/off Indicates whether the
burner is alight or not
Pump on/off Indicates whether the inte-
gral pump is switched on or off
Page 30
6 720 610 602 GB (03.02)
30
Text Display
6.8 Settings
6.8.1 Heating (if TR 2 is connected)
Optimum Start
B From the main menu, select Settings and from the
first submenu, select Heating.
B Press or to switch Optimum Start on or off.
Basic setting: “ON”
6.8.2 Hot Water (Storage Tank, ZSBR models only)
The text display can control the hot water either with Times and temperatures or only times.
Times and temperatures: One can choose up to
six different times with temperatures, see page 29 “Hot water”.
Only times: During that times the Storage Tank will
be charged to the choosed temperature.
B From the main menu, select Settings and from the
first submenu select hot water.
B Press or to switch Times and temperatures
or only times.
6.8.3 Service
Displaying service functions
This option displays various current settings and sta­tuses of the electrically controlled appliance and sys­tem components for the benefit of the heating engineer.
Service parameters
Language Available languages are: English, Français (French), Deutsch (German).
B From the main menu, select Settings, from the first
submenu select Service, from the Second submenu select Further options, and from the third submenu select Language.
B Press or to select the desired language.
Two other supplementary functions can be selected from the third submenu Language:
Time correction
LCD contrast.
Time correction: B Press and hold the button (about 5 seconds)
until the display shows Time correction and LCD contrast.
B Press or to select Time correction.
B Press the button. The display shows Change
value.
B Press or to set the number of seconds in
24 hours.
Basic setting: “+ 0 s” LCD contrast:
B Press and hold the button (about 5 seconds)
until the display shows Time correction and LCD contrast.
B Press or to select LCD contrast. B Press the button. The display shows Change
value.
B Press or to adjust the LCD contrast.
Basic setting: e. g. “47
Operating times This option shows the hours of service (appliance, burner and hot water) since commissioning.
B From the main menu, select Settings, from the first
submenu select Service, from the Second submenu select Further options, and from the third submenu select Operating times.
Fault history This option displays any faults that have occurred for the information of the service engineer. The first fault displayed may still be active. Any other faults displayed are no longer active.
B From the main menu, select Settings, from the first
submenu select Service, from the Second submenu select Further options, and from the third submenu select Fault history.
6.9 Individual timer programmes
Tables for your own timer programmes you find in the User Manual.
i
Turn the hot water temperature control always higher than the temperature at the text display is choosen.
Page 31
6 720 610 602 GB (03.02)
Individual settings
31
7 Individual settings
7.1 Mechanical settings
7.1.1 Checking the size of the expansion vessel
Maximum pressure at maximum CH flow temperature is
2.5 bar. If the pressure is greater than this then fit an extra expansion vessel. Refer to table 11.
System Capacity – BS7074:1
7.1.2 Setting the central heating flow tempera­ture
The central heating flow temperature can be set to between 35˚C and 88˚C.
Limited maximum setting for low-temperature operation
The temperature control is factory limited to setting E, giving a maximum flow temperature of 75˚C.
Adjustment of the heating output to the calculated heat demand is not required by the heating systems regula­tions.
Removing the maximum setting limit
For heating systems which require higher flow temper­atures, the maximum setting limit can be removed.
B Lift off the yellow button on the temperature control
with a screwdriver.
Fig. 39
B Rotate yellow button through 180° and replace (dot
facing inwards). The CH flow temperature is no longer limited.
7.2 Settings on the Bosch Heatronic
7.2.1 General description
The text display module provides a convenient means of setting various appliance functions.
This description is limited to those functions necessary for commissioning.
Displaying service functions
All service functions are displayed.
B Press any button to activate the main menu. B Press or button until the arrow cursor is
pointing to Settings.
B Press the button. B Press or button until the arrow cursor is
pointing to Service.
B Press the button. B Press the button to select Display service
parameters. Service function 0.0, Last fault is displayed.
B Press the or button to cycle through the
current settings.
B Press the button to exit the menu.
Expansion Vessel Pressure and System Capacity
Expansion Vessel litres 10
Expansion Vessel Charge Pressure
bar 0.75
System pressure and capacity
1 bar litres 82
1.5 bar litres 46
Table 11
i
With underfloor heating systems, observe the maximum permissible flow tempera­tures.
6 720 610 332-27.1O
Control setting CH flow temperature
1 approx. 35˚C 2 approx. 43˚C 3 approx. 51˚C 4 approx. 59˚C 5 approx. 67˚C
E approx. 75˚C
max approx. 88˚C
Table 12
Service function Code no.
see page
Anti-cycle time 2.4 32 Max. CH flow temp. 2.5 32 Max. heating output 5.0 32 Constant hot water cycle-
time
6.8 32
Variable pump settings 7.0 32
Table 13
i
For a detailed description, refer to Service Booklet for the Engineer 7 181 465 347.
Page 32
6 720 610 602 GB (03.02)
32
Individual settings
Setting service functions
Only the service functions that can be set are displayed.
B Press any button to activate the main menu. B Press or button until the arrow cursor is
pointing to Settings.
B Press the button. B Press oder button until the arrow cursor
is pointing to Service.
B Press the button.
The cursor is pointing to Display service parame- ters.
B Press and hold the button (for about 5 sec-
onds) until the display shows Adjust service parameters and the first service function to be set, e.g. 2.0, Operating mode. If a fault has occurred, the display will show 0.0 and the last fault.
B Press the or button until the desired
service function is displayed.
B Press the button.
The first line of the display shows Change value.
B Use the or buttons to enter the required
setting.
B Press the button.
The text display shows ATTENTION Store set- tings?.
B Press or to select yes or no. B Press to confirm your selection.
The text display shows Please wait ... ..., and the
service function is then displayed with the new set­ting.
B Press the or button until the next func-
tion you wish to change is displayed.
-or-
B Press the button to exit the menu.
7.2.2 Setting the anti-cycle time (Service Function 2.4)
This service function is only active if Service Function
2.7, automatic anti-cycle time, is deactivated.
The anti-cycle time can be set to between 0 and 15 min­utes (is factory set to 3 minutes).
If the setting 0 is entered, the anti-cycle time is inactive. The shortest possible anti-cycle time is 1 minute (rec-
ommended for single-pipe and hot-air heating systems).
7.2.3 Setting the maximum CH flow tempera­ture (Service Function 2.5)
The maximum CH flow temperature can be set to between 35˚C and 88˚C (factory setting).
7.2.4 Setting the heating output (Service Function 5.0)
The heating output can be set to any level between min. rated heat output and max rated heat output to limit it to the specific heat requirements.
The factory setting is the max. rated heat output, 100 %. B Look up heating output in kW and corresponding
code number on the settings tables for heating out­put (see page 48).
B Enter the code number on the text display module. B Measure the gas flow rate and compare with the fig-
ures specified for the code number shown. If differ­ent, correct code number.
7.2.5 Constant hot water cycle time (Service Function 6.8)
In Comfort mode “ECO light off”, the hot water inside the appliance is held constantly at the set temperature. For that reason, the appliance switches on if the water temperature falls below a certain temperature. In order to prevent it switching on and off too frequently, the constant hot water cycle time service function allows you to set the minimum period between switching off and on again. This function has no effect on normal demand for hot water and relates only to the constant hot water function in Comfort mode.
The cycle time can be set to any period between 20 and 60 minutes (is factory set to 20 minutes).
7.2.6 Variable pump settings (Service Function 7.0)
The pump speed varies automatically to match the water flow requirement of the system determined by the position of thermostatic radiater valves. An automatic by-pass must not be used.
The Service Function 7.0 is factory set to 4 which will accommodate the majority of heating systems.
Information on the re-settings of this functions can be found in the Service Booklet for the Engineer number 7 181 465 347.
7.3 Setting the gas/air ratio
The appliance is set at the factory and adjustment is not necessary.
i
If the appliance is connected to an out­side-temperature controlled heating pro­grammer, the anti-cycle time does not need to be set on the appliance and is op­timised by the programmer instead.
i
The full rated heat output is still available for hot water or charging the hot water cyl­inder even if the heating output has been limited.
Page 33
6 720 610 602 GB (03.02)
Converting the appliance to different gas types
33
8 Converting the appliance to different gas types
The setting is factory sealed at maximum. Adjustment to the rated heat input and min. heat input is not neces­sary.
Checking the gas supply pressure
B Check the gas supply pressure at the gas supply
pressure testing point.
Natural gas
Appliances for natural gas type G20 are factory set
to Wobbe-Index 15 kWh/m3 and 20 mbar supply pressure and sealed.
Conversion kits
Instructions are sent with each conversion kit.
8.1 Setting the gas/air ratio
The gas/air ratio may only be adjusted on the basis of a CO2 measurement at max. heat output and min. heat output using an electronic tester.
B Switch off the appliance at the master switch (O). B Remove the outer case (see page 15, refer to
fig. 13).
B Switch on the appliance at the master switch (I). B Unscrew sealing plug from flue gas testing
point (234). Refer to fig. 40.
B Insert testing probe about 135 mm into the flue gas
testing point and seal testing point.
Fig. 40
B On the text display unit, select in the main menu Set-
tings, Service, Display service parameters.
B Press and hold the button (for about 5 sec-
onds) until the display shows Adjust service
parameters and the first service function to be set,
2.0 Operating mode. If a fault has occurred, the
display will show 0.0 and the last fault.
B Press or until the display shows 2.0
Operating mode normal.
B Press the button. B Press or to select Max. B Measure the CO2 level. B Prise off the seal on the gas flow restrictor.
i
Natural gas appliances must not be oper­ated if the gas supply pressure is below 18 mbar or above 24 mbar.
LPG appliances must not be operated if the supply pressure is below or above 37 mbar.
Model
For conversion from ... Order no.
ZWBR 8-30 N.G to L.P.G 7 710 149 050
ZWBR 11-30 L.P.G to N.G 7 710 239 086
ZWBR 14-37 L.P.G to N.G 7 710 239 087
ZWBR 11-37 N.G to L.P.G 7 710 149 052
Table 14
6 7 2 0 6 1 0 3 3 2 - 5 7 . 2 R
2 3 4
Page 34
6 720 610 602 GB (03.02)
34
Converting the appliance to different gas types
B Adjust the gas flow restrictor (63) to obtain the CO2
level given in Table 15. Refer to fig. 41.
Fig. 41
B Press or to select Min. B Measure the CO2 level. B Remove the seal from the gas valve adjusting
screw (64) and adjust the CO2 level to the figure given in Table 15 for min. rated heat output. Refer to fig. 42.
Fig. 42
B Recheck the levels at min. and max. rated heat output
and re-adjust if necessary.
B Press or until the display shows
normal.
B Press the button. The text display shows
Store settings.
B Press to select yes. B Press the button. B Remove testing probe from the flue gas testing
point (234) and refit sealing plug.
B Re-seal gas valve adjusting screw and gas flow
restrictor.
B Replace the outer case by locating it on the top lugs
and pushing backwards until the bottom clips are fully engaged. Check that the case is properly aligned with facia. Refer to fig. 13.
B Secure by replacing the screw at the bottom left.
Refer to fig. 13.
ZWBR 8-30
Gas Type
CO2 reading at max. rated heat output
CO2 reading at min. rated heat output
Natural gas type G20
9.4 % 9.2 %
LPG G31 (propane)
11.0 % 11.0 %
Table 15
ZWBR 11-37
Gas Type
CO2 reading at max. and min. rated heat output
Natural gas type G20
9.2 %
LPG G31 (propane)
11.0 %
Table 16
63
6 720 610 332-64.1R
64
3928-74.1R
Page 35
6 720 610 602 GB (03.02)
Converting the appliance to different gas types
35
8.2 Testing combustion air/flue gas at set heat output
8.2.1 Testing the O2 or CO2 level in the combustion air
B Press and hold the button until the display
shows – –. “Chimney sweep” mode is now active. The button will light up and the display shows the CH flow temperature.
B Remove sealing plug from combustion air testing
point (234.1, fig. 43).
B Insert testing probe about 80 mm into the testing
point and seal testing point.
Fig. 43
B Measure O2 and CO2 levels. B Refit sealing plug. B Press and hold button until the display shows – –.
The button will stop flashing and the display shows the CH flow temperature.
8.2.2 Testing CO and CO
2
B Press and hold the button until the display
shows – –. “Chimney sweep” mode is now active. The button will light up and the display shows the CH flow temperature.
B Remove sealing plug from flue gas testing point
(234, fig. 43).
B Insert testing probe about 135 mm into the testing
point and seal testing point.
B CO- and CO2 levels. B Refit sealing plug. B Press and hold button until the display shows – –.
The button will stop flashing and the display shows the CH flow temperature.
i
By testing the O2 or CO2 level in the com­bustion air the gas tightness of a type C13, C33 flue system can be checked. The O2 level must not be less than 20,6 %. The CO2 level must not exceed 0,2 %.
i
In “chimney sweep” mode, the appliance switches to max. rated heat output or the set heating output. You then have 15 min­utes in which to measure the levels. After that, the appliance switches back from “chimney sweep” mode to normal mode.
6 7 2 0 6 1 0 3 3 2 - 6 5 . 2 R
2 3 4
2 3 4 . 1
i
You have 15 minutes in which to measure the levels. After that, the appliance switch­es back from “chimney sweep” mode to normal mode.
Page 36
6 720 610 602 GB (03.02)
36
Maintenance
9 Maintenance
B The User should be recommended to have the appli-
ance serviced regularly by a competent person.
B Use only genuine spare parts B Refer to the Spare Parts List when ordering spare
parts.
B Always renew seals and O-rings removed during
servicing or repair work.
B Use only the following types of grease:
– Water valve: WRAS approved silicon based
grease
– Unions: approved sealant.
B To drain the appliance shut the system valves and
open the pressure relief valve.
B Upon completion of any electrical work check for
earth continuity, correct polarisation and resistance to earth.
Replace the text display module or the Heatronic PCB
If the text display module is replaced, the service func­tion settings are retained.
B The remaining settings have to be re-entered.
If the Heatronic PCB is replaced: B Re-enter the service function settings as recorded in
the commissioning record.
B Always disconnect the appliance from
the electrical power supply (fuse, circuit breaker) before carrying out any work on the electrical systems or components.
B Always turn off the gas cock before car-
rying out any work on components which carry gas.
i
There is a Service booklet for the Engi­neer, order no. 7 181 465 347, available to competent persons.
i
All safety and control systems are moni­tored by the Bosch Heatronic. In the event of a component fault, the textdisplay shows a fault code.
Page 37
6 720 610 602 GB (03.02)
Maintenance
37
9.1 Pre-Service Check List
Date
1 Call up the last fault stored by the text-
display , (see page 30).
2 Check ionisation current, Service
Function 3.3, (see page 38).
3 Perform visual check of air/flue duct.
Visual check of diaphragm for soiling and splits (see page 40).
4 Check gas supply pressure
(see page 33).
mbar
5 Test combustion air/flue gas
(see page 35).
6 Check CO2 setting for min./
max. (gas/air ratio) (see page 35).
min. %
max. %
7 Check gas and water systems for
leaks (see page 15).
8 Check hot water outlet temperature
(see page 38).
9 Check heat exchanger
(see page 38).
mbar
10 Check burner (see page 39).
11 Clean condensation trap
(see page 40).
12 Check charge pressure of
expansion vessel matches static head of heating system.
mbar
13 Check central heating system
pressure.
mbar
14 Check electrical wiring for damage.
15 Check heating programmer settings in
the textdisplay.
16 Check appliances that are part of
the heating system.
Table 17
Page 38
6 720 610 602 GB (03.02)
38
Maintenance
9.2 Description of servicing operations
The combustion performance must be checked before and after any servicing work on the combustion and burner components. Refer to section 8.2.
Checking the ionisation current, Service Function 3.3
B Select Service Function 3.3. (See page 31 “Display-
ing Service Functions”)
If the display shows 2 or 3, the ionisation current is OK. If the display shows 0 or 1, the electrode assembly (32.1, page 6) must be cleaned or replaced.
Domestic hot water
If the flow rate is too slow: B remove the domestic hot water heat exchanger and
replace,
-or-
B descale with a descaling agent approved for use on
stainless steel.
B Before removing the heat exchanger shut the inlet
valve and drain the hot water circuit.
B Use new seals when replacing the heat exchanger.
Fig. 44
Primary Heat exchanger
There is a special accessory kit (no. 840) for cleaning the heat exchanger, order no. 7 719 001 996.
B Check control pressure on the air - gas mixer unit at
max. rated heat output using an electronic manome­ter.
Fig. 45
B Remove cleaning access cover (415, page 6) and
the metal plate below it, if present. Refer to fig. 2.
B Unscrew condensation trap and place suitable con-
tainer underneath. Refer to fig. 46.
B Remove the fan and the burner as described in the
text headed “Burner” (see page 39).
Fig. 46
7 181 465 330-06.1R
i
The heat exchanger should only be cleaned if the control pressure is
5.0 mbar (ZWBR 8-30)
4.5 mbar (ZWBR 11-37)
(depression) or less.
6 720 610 332-69.1R
6 720 610 332-72.1R
Page 39
6 720 610 602 GB (03.02)
Maintenance
39
B Loosen any deposits in the heat exchanger from top
to bottom using the cleaning blade. Refer to fig. 47.
Fig. 47
B Clean the heat exchanger from top to bottom using
the brush. Refer to fig. 48.
Fig. 48
B Flush the heat exchanger from the top. Refer to
fig. 49.
B Clean out the condensate collector and trap connec-
tion (with other end of brush).
Fig. 49
B Refit the clean-out cover using a new seal and
tighten screws to torque of approx. 5 Nm.
Burner
B Check that the gas cock is turned off and the master
switch is in the OFF position
B Remove the clips (1) and unscrew the two bolts (2).
Refer to fig. 50.
B Unscrew and remove the two hexagon screws secur-
ing the fan (3).
B Slacken fully the rear securing bolt (4). B Remove the burner coverplate.
Fig. 50
B Remove the burner skin and clean components. Do
not use a wire brush. Refer to fig. 51.
Fig. 51
B Re-assemble burner in reverse order using a new
seal.
B Adjust gas/air ratio. Refer to section 8.2.
6 720 610 332-73.1R
6 720 610 332-74.1R
6 720 610 332-75.2R
1.
2.
4.
7 181 465 330-04.1R
3.
7 181 465 330-08.1R
Page 40
6 720 610 602 GB (03.02)
40
Maintenance
Condensation trap
In order to prevent spillage of condensate the conden­sation trap should be completely removed, (see page 38, fig. 46).
B Unscrew condensation trap and check connection
to heat exchanger is clear.
B Remove condensation trap cover and clean. B Fill condensation trap with approx. 1/4 l of water and
refit.
Electrode assembly
B Switch off the master switch. B Pull off the leads from the electrodes. Refer to fig. 2. B Unscrew the two fixing screws and carefully remove
the electrode assembly . Refer to fig. 45.
B Clean the electrodes with a non-metallic brush. (The
spark gap should be 4,5 mm ± 0,5 mm.)
B Replace and re-connect the assembly taking care
not to mislay the inspection window.
Diaphragm in mixer unit for ZWBR 8-30 ICC2
B Open mixer unit (29). B Carefully withdraw diaphragm (443) from fan intake
tube and check for soiling and splits.
Fig. 52
B Carefully refit diaphragm (443) the correct way
round into the fan intake tube.
B Seal the mixer unit (29).
Diaphragm in mixer unit for ZWBR 11-37 ICC2
B Remove fan and mixer unit assembly.
Fig. 53
B Unscrew mixer unit (29). B Remove sleeve. B Carefully remove diaphragm (443) and check for
soiling and cracks.
B Refit diaphragm (443) taking care to ensure it is the
correct way round.
B Refit mixer unit (29) and fan assembly.
B Take care not to damage diaphragm
(443) when removing and refitting it.
1.
2.
3.
443
29
6 720 610 790-07.2R
i
The flaps of the diaphragm (443) must open upwards.
i
The flaps of the diaphragm (443) must open upwards.
1.
2.
3.
4.
5.
443
6 720 610 910-63.1R
29
Page 41
6 720 610 602 GB (03.02)
Maintenance
41
Siphon
B Unscrew the clip and disconnect the pipe to the
siphon.
B Remove the yellow plug to drain the siphon. B Unscrew the securing nut from beneath the side
facia and remove the siphon. Refer to figure below.
B Refit and prime the siphon.
Fig. 54
Expansion vessel
The expansion vessel should be checked once a year.
B Depressurise appliance. B If necessary, adjust expansion vessel charge pres-
sure to static head of the heating system.
Heating system pressure
B The pointer on the pressure gauge should be 1 bar. B If the pointer is below 1 bar (when the system is
cold), water should be added until the pointer is 1 bar again.
B Max. pressure of 2.5 bar when the heating system
water is at maximum temperature must not be exceeded. If this pressure is exceeded then an extra expansion vessel must be fitted in the system return as close to the appliance as possible.
B If the system does not retain the pressure, the expan-
sion vessel and the heating system should be checked for leaks.
9.3 Replacement of Parts
Before changing any components check that the gas is turned off and that the appliance is electrically isolated. When necessary close the system valves and drain the appliance.
Refitting is a reverse of the procedure for removal using new seals or o-rings as appropriate.
9.3.1 PCB control board and transformer
B Switch off the appliance. B Disconnect appliance from the power supply. B Unplug all connectors from the control box (inc.
keyed plug). Access is gained by removing the cov­ers. Refer to fig. 25, 26.
B Remove screw holding power connector earth lead
and remove earth lead.
B Remove two top fixing screws from the control box.
Refer to fig. 55.
Fig. 55
B Lower the control box. B Unscrew earth lead. B Unscrew four fixing screws from cover plate. Refer to
fig. 56.
B Prise off cover plate. B Pull off transformer. B Remove pcb holder.
i
Fill the system using the WRAS approved filling loop.
6 720 610 602
- 16.
1O
Siphon
Condensate Drain
7 181 465 330-09.1R
1
2
3
4
5
E
1
3
2
4
1
3
2
4
1
3
2
4
Page 42
6 720 610 602 GB (03.02)
42
Maintenance
B Remove the pcb control board.
Fig. 56
Fuses
B Remove the connections covers. Refer to fig. 25,
26.
The fuses are located adjacent to the mains connector block and connector ST18. Refer to fig. 4.
Fuse, item 312, is only replaceable by removing the pcb.
Spare fuses are fixed to the connections cover. A fuse pack is available: Part number 8 744 503 010 0.
9.3.2 Fan Assembly
Fig. 57
B Switch off the appliance. B Undo lower pipe union on gas pipe (1.). Refer to
fig. 57.
B Remove fan lead and earth connector (2.). The earth
connector has a positive clip fixing.
B Remove fixing screws attaching fan to the burner
cover (3.).
B Remove fan together with gas pipe and mixer unit. B Separate the fan from the pipe and mixer unit by
twisting the mixer unit to release it (4.).
9.3.3 Pump
B Switch off the appliance. B Disconnect the appliance from the power supply. B Remove two switchbox fixing screws (1.). Refer to
fig. 58.
B Lower switchbox (2.). B Remove screw from underside of right-hand plastic
cover plate (3.).
B Pull cover plate forwards to remove (4.). B Unscrew and remove the the siphon by releasing the
jubilee clip. Refer to fig. 54.
B Unscrew the pump union nuts (5.). Refer to fig. 58. B Carefully remove the pump and disconnect the
leads.
7 181 465 330-10.1
R
1.
2.
3.
4.
7 181 465 330-05.1R
Page 43
6 720 610 602 GB (03.02)
Maintenance
43
Alternatively
B After removing the siphon release the four Allen
screws and remove and replace the pump head.
Fig. 58
9.3.4 3-way diverter valve
B Switch off the appliance. B Disconnect appliance from the power supply. B Turn off service cocks. B Unplug connector from 3-way valve motor. Refer to
fig. 59.
B Pull out retaining clip. B Remove motor. B Disconnect the relief valve drain. B Disconnect the pressure gauge by withdrawing the
clip and pulling out the capillary head.
B Undo pipe unions by withdrawing the clips.
B Remove 3-way valve.
Fig. 59
After refitting: B Fill system, bleed and re-pressurise
(see Installation Instructions).
9.3.5 3-way diverter valve motor
B Switch off the appliance. B Turn off the service cocks. B Unplug connector from 3-way valve motor. Refer to
fig. 59.
B Pull out retaining clip. B Remove motor.
9.3.6 Sensors
B Check that the appliance is electrically isolated.
Central Heating Flow Temperature Sensor – Item 36, fig. 2, 55
B Pull-off the connector. B Release the sensor clip and withdraw the sensor. B Apply heat transfer paste to the replacement sensor.
Safety Temperature Limiter – Item 6, fig. 2, 55
B Pull-off the connectors. B Unscrew the sensor.
Flue Temperature Limiter – Item 9, fig. 2, 55
B Pull-off the connectors. B Unscrew the sensor.
1.
1.
2.
3.
4.
5.
7 181 465 330-03.1R
7 181 465 330-12.1R
Page 44
6 720 610 602 GB (03.02)
44
Maintenance
Domestic Hot Water Temperature Sensor – Item 6.1, fig. 2
B Check that the inlet water valve is closed and the
domestic hot water circuit is drained.
B Release and pull-off the connector. B Unscrew the sensor.
9.3.7 Gas Valve
B Check that the gas cock is turned off. B Lower the control panel. Refer to fig. 58. B Pull off the solenoid connections at the rear of the
valve.
B Undo the union, within the inner casing, securing the
valve to the gas/air tube. Refer to fig. 57.
B Remove the white plastic cap from the gas valve. B Release the gas inlet union at the manifold assembly. B Unscrew the two screws securing the gas valve
assembly bracket to the back panel and withdraw the assembly.
B Transfer the bracket and inlet pipe assembly to the
new gas valve.
B Check for gas soundness when the new gas valve
has been fitted.
B Recheck the combustion performance as described
in section 8.1.
Fig. 60
9.3.8 Domestic Hot Water Heat Exchanger
B Refer to section 9.2. B Use new seals when fitting the new heat exchanger.
9.3.9 Electrode assembly
B Refer to section 9.2. B Use a new seal if the existing seal is damaged.
9.3.10 Pressure gauge
B Drain the appliance. B Lower the facia. Refer to fig. 58. B Twist the pressure gauge head anti-clockwise to
release it from the casing. Refer to fig. 2.
B Disconnect the capillary head from the rear of the
diverter valve by withdrawing the clip and pulling out the head. Refer to fig. 59.
9.3.11 Expansion vessel
B Drain the appliance. B Undo the union connection at the base of the vessel.
Refer to fig. 2.
B Unscrew the top and bottom fixing screws and
remove the vessel.
B Set the pressure of the new vessel to that required
by the system.
9.3.12 Pressure Relief Valve
B Drain the appliance. B Disconnect the drain pipe from the valve. Refer to
fig. 30.
B Pull-out the clip securing the valve. B Pull-out the valve. B Ensure that the replacement valve is fully entered
before fitting the clip.
9.3.13 Burner
B Refer to section 9.2.
6 720 610 602 - 04.1O
Page 45
6 720 610 602 GB (03.02)
Maintenance
45
9.3.14 Flow switch
B Shut the mains water inlet valve and drain the domes-
tic hot water circuit.
B Pull-off the connectors from the micro-switch. B Unscrew the inlet and union connection and remove
the assembly.
B Reset the domestic hot water flow rate on the new
assembly.
Fig. 61
9.3.15 Primary Heat Exchanger
B Drain the appliance. B Check that the gas supply is turned off. B Check that the appliance is electrically isolated. B Remove the fan assembly complete with the gas/air
tube and mixer assembly. Refer to section 9.3.2.
B Remove the burner. Refer to section 9.2. B Disconnect the sensors. Refer to section 9.3.6. B Undo the central heating flow union. B Undo the top connection of the pump. Refer to
fig. 57.
B Undo the grey plastic cap, next to the top pump con-
nection at the base of the heat exchanger.
B Unscrew and remove the condensate trap. Refer to
section 9.2.
B Unscrew and remove the two screws securing the
heat exchanger top bracket to the rear panel.
B Lift up the flue duct, item 271, refer to fig. 2. B Pull forward from the top and lift the heat exchanger
from the casing.
B Transfer components, as necessary, to the new heat
exchanger.
B Ensure that all the seals are in place and all of the
connections are tight before re-commissioning the appliance.
Fig. 62
6 720 610 602 - 05.10
INLET
OUTLET
6 720 610 602 - 06.10
Page 46
6 720 610 602 GB (03.02)
46
Appendix
10 Appendix
10.1 Fault Codes
More detailed fault finding procedures are described in the Service Booklet for the Engineer number 7 181 465 347.
Display code
Description Remedy
A1 pump has run dry Check system pressure, add water and bleed
system as necessary
A7 Hot water NTC sensor defective. Check hot water NTC sensor and connecting
lead for circuit breaks/short circuits.
A8 Break in communication Check connecting lead to TR2 b1 Keyed plug not detected. Insert keyed plug correctly, test and replace if
necessary.
C1 Fan speed too low. Check fan lead and connector, and fan; replace
as necessary.
d3 Jumper 8-9 not detected. Connector not connected, link missing, under-
floor heating limiter tripped.
E2 CH flow NTC sensor defective Check CH flow NTC sensor and connecting
lead.
E9 Safety temp. limiter in CH flow has tripped. Check system pressure, check safety temp. lim-
iters, check pump operation, check fuse on pcb, bleed appliance.
EA Flame not detected. Is gas cock turned on? Check gas supply pres-
sure, power supply, igniter electrode and lead, ionisation sensing electrode and lead, flue duct and CO2 level.
F0 Internal error. Check electrical connector contacts, program-
mer interface module ignition leads and bus module are not loose; replace pcb or bus mod­ule if necessary.
F7 Flame detected even though appliance
switched off.
Check electrode assembly, dry pcb. Flue clear?
FA Flame detected after gas shut off. Check gas valve and wiring to gas valve. Clean
condensation trap and check electrode assem­bly. Flue clear?
FC Textdisplay not detected. Check connecting lead between Textdsiplay
and Heatronic , replace Textdisplay if necessary
Fd Reset button pressed by mistake. Press reset button again P1, P2,
P3, P1...
Please wait, initialisation in progress. 24 V fuse blown. Replace fuse.
Table 18
Page 47
6 720 610 602 GB (03.02)
Appendix
47
10.2 Short parts list
Key Description Qty GC Spare part number
1 Sensor - Flue gas temp. 1 8 729 000 144 0 2 Sensor - CH flow temp. 1 8 714 500 087 0 3 Sensor - DHW flow temp. 1 8 714 500 054 0 4 Control board pcb 1 8 748 300 418 0 5 Gas valve ZWBR 8-30 1 8 747 003 516 0
5.1 Gas valve ZWBR 11-37 1 8 747 003 515 0 6 Fan assembly 1 8 717 204 325 0 7 Fan washer 1 8 729 000 183 0 8 Expansion vessel 1 8 715 407 246 0 9 Relief valve 1 8 717 401 012 0 10 Electrode assembly 1 8 718 107 077 0 11 Electrode lead 1 8 714 401 999 0 12 Pump 1 8 717 204 477 0 13 Pressure gauge 1 8 717 208 079 0 14 Burner skin seal 1 8 711 004 168 0 15 Transformer - facia 1 8 747 201 358 0 16 Flow switch 1 8 717 002 110 0 17 3-way diverter valve 1 8 717 010 062 0 18 Heat exchanger washer 1 8 710 103 153 0 19 Washer set Condensation
Trap
1 8 710 103 154 0
20 Fuse set 1 8 744 503 010 0 21 Service set Water Valve 1 8 710 503 031 0 22 Domestic Hot Water Heat
Exchanger
1 8 715 406 659 0
23 Text Display 1 8 747 208 103 0 24 Primary heat exchanger 1 8 715 406 615 0 25 Diaphragm 1 8 715 505 801 0
Table 19
Page 48
6 720 610 602 GB (03.02)
48
Appendix
10.3 Heating/hot water output settings ZWBR 8-30 N.G.
10.4 Heating/hot water output settings ZWBR 11-30 L.P.G
10.5 Heating/hot water output settings ZWBR 11-37 N.G.
10.6 Heating/hot water output settings ZWBR 14-37 L.P.G
Natural gas G20
Display code
Heat output, kW
Heat input, kW
Gas vol. flow rate (l/min at t
V/tR
= 80/60 C)
30 9.1 9.2 16.0
40 12.1 12.2 21.4
50 15.1 15.3 26.7
60 18.1 18.3 32.0
70 21.1 21.4 37.4
80 24.2 24.4 42.7
90 27.2 27.5 48.0
100 30.2 30.5 53.4
Table 20
Propane
Display code
Heat output kW Heat input kW
40 12.1 12.2
50 15.1 15.3
60 18.1 18.3
70 21.1 21.4
80 24.2 24.4
90 27.2 27.5
100 30.2 30.5
Table 21
Natural gas G20
Display code
Heat output, kW
Heat input, kW
Gas vol. flow rate (l/min at t
V/tR
=
80/60˚C)
30 11.1 11.3 19.7
40 14.9 15.0 26.3
50 18.6 18.8 32.8
60 22.3 22.5 39.4
70 26.0 26.3 45.9
80 29.7 30.0 52.5
90 33.4 33.8 59.1
100 37.1 37.5 65.6
Table 22
Propane
Display code
Heat output, kW Heat input, kW
40 14.9 15.0
50 18.6 18.8
60 22.3 22.5
70 26.0 26.3
80 29.7 30.0
90 33.4 33.8
100 37.1 37.5
Table 23
Page 49
6 720 610 602 GB (03.02)
Appendix
49
10.7 Operational Flow diagrams
10.7.1 Domestic hot water function
Fig. 63
Mains
switch
ON.
Green
light
ON.
Burner lights.
Red light ON.
Ignition spark for
5 seconds.
Fan runs to purge
gas from burner.
Repeats 5 times
before lock-out.
Hot
water
demand.
Pump ON
Diverter valve
operates.
Heat input
modulates to
maintain the
delivery
temperature.
Gas valve
closes.
Red light
OFF.
Fan runs for
upto 3 mins.
Pump runs
for 30secs.
Over temperature
shut-down if water
temperature is 8°C
above set value.
Burner remains OFF
until flow temperature
is below set value.
Gas valve shuts.
Pump remains ON.
Demand
ends.
Yes
No
** NOTE:
The appliance controls can be set to one of
2 modes of operation.
1.
Comfort
mode -
Full pre-heat
2.
ECO
mode -
a) Operates as an instantaneous combination
boiler.
b) Demand Detection: a short demand (less
than 5 seconds) switches the control to
Comfort mode for 5 mins. Mini pre-heat.
The Factory setting is
Comfort
mode.
Fan to
start speed.
Gas valve opens.
Pre-heat
mode.**
Ignition sequence
Pre-heat
mode.**
Burner shut-down if
primary temperature
exceeds 94 °C remains
OFF until 78 °C
Pump ON
Diverter valve
operates.
Fan to
start speed.
Gas valve opens.
Pre-heat satisfied.
Ignition sequence
Burner lights.
Red light ON.
Ignition
spark
5 secs
.
6 720 610 576 - 24.1O
Page 50
6 720 610 602 GB (03.02)
50
Appendix
10.7.2 Central heating function
Fig. 64
Mains
switch
ON.
Fan min.
speed for
90 secs.
Green
light
ON.
Burner lights.
Red light ON.
Ignition spark for
5 seconds.
Fan runs to purge
gas from burner.
Repeats 5 times
before lock-out.
Room thermostat
and/or mains
programmer or
link ON
AND
Electronic facia
programmer
(if fitted) ON
AND
CH control knob
ON.
CH
demand.
Pump ON
Fan to
start speed.
Gas valve opens.
Burner
stabilises at
start speed
for 5-10 secs
Fan speed
reduces
over 15
secs.
Gas valve
closes.
Red light
OFF.
*
Minimum
heat input
for 15min.
Boiler
operates to
match
system load
and CH
control
setting.
Boiler
unused for
long
period.*
Over temperature
shut-down if water
temperature is 5°C
above set value.
Burner remains OFF
until flow temperature
is below set value.
Gas valve shuts.
Pump remains ON.
Pump and Fan
run for upto
3 mins.
CH demand
satisfied.
Yes
No
Yes
No
* NOTE: The sequence ensures that the condensate siphon is not empty
after long
OFF
periods. (More than 24 hours without a demand).
Ignition sequence
ce
6 720 610 576 - 25.1O
Page 51
6 720 610 602 GB (03.02)
Appendix
51
Page 52
AppendixAppendix
EXCELLENCE COMES AS STANDARD
Manufactured exclusively for British Gas by The Bosch Group
Bosch Group, Worcester Heat Systems, Cotswold Way, Warndon, Worcester WR4 9SW.
Telephone: (01905) 754624 Fax: (01905) 754619
Page 53
Service Booklet for the Engineer for Gas Condensing Boilers
6 720 610 333-00.1
R
ZSBR 7-28 ICS1 GC-Number: 41 108 04 ZWBR 8-30 ICC2 GC-Number: 41 108 09 ZBR 8-35 ICS1 GC-Number: 41 108 05 ZWBR 11-37 ICC1 GC-Number: 41 108 10
ZWBR 7-28 HE plus GC-Number: 47 311 56 ZWBR 11-35 HE plus GC-Number: 47 311 57
7 181 465 347 (01.07) OSW
Page 54
7 181 465 347 (01.07)2
Contents
Contents
Safety precautions 3
Symbols 3
1 Layout of Appliance (ZSBR/ZWBR) 4
2 Operation 5
2.1 Standard display 5
2.2 Displaying service functions 5
2.3 Setting service functions 5
2.4 Resetting service functions to factory settings 5
2.4.1 Resetting service functions 0.0 to 4.9 to their factory settings (Reset 1): 5
2.4.2 Resetting service functions 0.0 to 9.9 to the factory setting (Reset 2): 5
3 Boiler service functions 6
3.1 Summary 6
3.2 Explanation of service functions 9
4 Rectifying faults 14
4.1 Boiler failure codes indication 14
4.1.1 ... on the boiler 14
4.1.2 ... on the programmer (optional accessory) 14
4.2 Summary 14
4.2.1 Appliance faults 14
4.2.2 Faults that are not indicated on any display 14
4.3 How to use the fault tables 16
4.4 Faults indicated on display 17
4.5 Faults that are not displayed 36
4.5.1 Appliance faults 36
4.5.2 Programmer faults 41
5 Appendix 45
5.1 NTC values 45
5.1.1 Outside temperature sensor 45
5.1.2 CH flow NTC sensor, heat store NTC sensor, constant hot water NTC sensor and hot water NTC sensor 45
5.2 Electronic schemes 46
5.3 List of most important replacement parts 47
5.4 Approved corrosion inhibitors and anti-freeze fluids for central heating water 48
5.5 Detecting corrosion by CFCs 49
Page 55
7 181 465 347 (01.07)
Safety precautions
3
Safety precautions
Repairs
B Repairs may only be carried out by an approved
installer!
B Before carrying out any work on the appliance,
switch it off at the master switch!
B Even when the appliance is switched off at the mas-
ter switch, some components on the PCB control board inside the control box are still live. Therefore:
B Before carrying out any work on the electrical parts
of the appliance fully disconnect it from the power supply (e. g. by means of fuse or circuit breaker)!
B Flue ducting must not be modified in any way. B Use only original spare parts!
Instructions to the customer
B Advise the customer that he/she must not make any
modifications to the appliance or carry out any repairs on it.
B Draw attention to the need for an annual service (or
maintenance contract if applicable).
Symbols
Signal words indicate the seriousness of the hazard in terms of the consequences of not following the safety instructions.
Caution indicates that minor damage to property
could result.
Warning indicates that minor personal injury or seri-
ous damage to property could result.
Danger indicates that serious personal injury could
result. In particularly serious cases, lives could be at risk.
Notes contain important information in cases where there is no risk of personal injury or damage to property.
Safety instructions in this document are identified by a warning-triangle sym­bol and are printed on a grey back­ground.
i
Notes are identified by the symbol shown on the left. They are bordered by horizon­tal lines above and below the text
Page 56
7 181 465 347 (01.07)4
Layout of Appliance (ZSBR/ZWBR)
1 Layout of Appliance (ZSBR/ZWBR)
Fan fixing screws
Burner fixing screws
Electrode assembly: Flame sensing electrode Ignition electro­des
CH flow NTC sensor
CH flow safety temperature limiter
Variable-charac­teristic pump
Automatic vent
G
as flow
restrictor: adju-
s
ting screw for
C
O2 max.
Gas valve: adjusting screw for CO
2
min.
Plate-type heat exchanger (ZWBR)
Hot water NTC sensor (ZWBR)
CH flow
Silencer
Fan
Fan connector
Mixer unit
Condensation trap
Gas supply pipe
Flue gas safety temperature limiter
Testing points: flue gas air
Inspection opening
Water switch (ZSBR)
Change-over valve motor
Change-over
valve
Heatronic
Transformer
Page 57
7 181 465 347 (01.07)
Operation
5
2 Operation
Instructions on the use of the text display module are given in the operating and installation instructions for the boiler.
Fig. 1 Controls
a Display b “Up” or “More” button c “Down”, or “Less” button d “Back” button e “Nest” button f “Delete” button
2.1 Standard display
The text display shows the time, the CH flow tempera­ture and the measured outside temperature in plain English.
In addition, the 2-digit display also shows the current CH flow temperature in Heating mode and Hot Water mode (display range 00 °C to 99 °C).
2.2 Displaying service functions
B Press any button to activate the main menu. B Press or button until the arrow cursor is
pointing to Settings.
B Press the button. B Press or button until the arrow cursor is
pointing to Service .
B Press the button. B Press button to select Display service
parameters. Service function 0.0, Last fault is displayed.
B Press or button to cycle through the
current settings.
B Press button to exit the menu.
2.3 Setting service functions
B Press any button to activate the main menu. B Taste or button until the arrow cursor is
pointing to Settings.
B Press the button. B Press or button until the arrow cursor is
pointing to Service.
B Press the button.
The cursor is pointing to Display service parameters.
B Press and hold the button (for about 5 sec-
onds) until the display shows shows Adjust service parameters and the first service function to be set, e.g. 2.0, Operating mode. If a fault has occur red, the display will show 0.0 and the last fault.
B Press or button until the desired service
function is displayed.
B Press the button.
The first line of the display shows Change value.
B Use the and buttons to enter the
required setting.
B Press the button.
The text display shows ATTENTION Store set- tings?.
B Press or to select yes or no. B Press to confirm your selection.
The text display shows Please wait ..., and the serv­ice function is then displayed with the new setting.
B Press the or button until the next func-
tion you wish to change is displayed.
-or-
B Press the button to exit the menu.
2.4 Resetting service functions to fac­tory settings
2.4.1 Resetting service functions 0.0 to 4.9 to their factory settings (Reset 1):
B Power OFF the appliance. B Press the button and keep it pressed. B Switch on the appliance, press and hold the but-
ton until the display shows r1 followed by [ ] .
2.4.2 Resetting service functions 0.0 to 9.9 to the factory setting (Reset 2):
B Power OFF the appliance. B Simultaneously press and hold buttons and . B Switch on appliance, press and hold the and
buttons until the display shows r2 followed by [ ] .
c
b
a
f
e
d
C
6 720 610 337-08.1R
i
To reset all parameters (except service settings) set on the text display module):
B Press and hold the button until the
settings are deleted.
C
Page 58
7 181 465 347 (01.07)6
Boiler service functions
3 Boiler service functions
3.1 Summary
Text display message Display
Range adjustable from - to
Reset Value
0.0 Last fault 00 - FF Clear only 0
0.1 Flow temp. sensor 0 - 99 °C - -
0.2 Hot water temp. sensor 0 - 99 °C - -
0.3 Stor. tank temp. sensor1 0 - 99 °C - -
0.4 Stor. tank temp. sensor2 0 - 99 °C - -
1.2 Code plug 8714411 XXX 0 - 255 - -
1.5 Required flow temp. 0 - 99 °C - -
1.9 Module detection no module detected
bus module
--
2.0 Operating mode - normal Min Max
normal
2.2 Pump switch mode - 1 - 3 2
2.3 Stor. tank charge output - 0 - 100% 100 %
2.4 Anti-cycle mode - 0 - 15 min 3 min
2.5 Max. flow temperature - 35 - 88 °C 88 °C
2.6 Switch.diff.flow temperature - 0 - 30 °C 0 °C
2.7 Autom. anti-cycle mode - on
off
on
2.9 Actual output 0 - 100 % - -
3.0 Fan speed 0 - 255 U/s - -
3.3 Ionisations current no
low middle high
--
3.4 Pump mode - 0 - 3 0
1)
3.5 Pump blocking time - 0 - 240 s in 15-s increments
0 s
3.6 Software version BF 11.XX - -
Table 1
Page 59
7 181 465 347 (01.07)
Boiler service functions
7
3.9 Link 8 - 9 open closed
--
Link Ls-Lr open
closed
--
4.0 Stor. tank. therm.. (7-9) blocked heat demand
--
4.1 Room therm. LSM blocked heat demand
--
LSM release blocked
heat demand
--
4.2 Timer ch. 1 (heating) blocked heat demand
--
Timer ch. 2 (hot wat.) blocked
heat demand
--
4.4 Heat demand (heating). yes no
--
Heat demand (stor. tank). yes
no
--
4.5 Heat demand (hot water). yes no
--
Keep hot period yes
no
--
4.6 Internal regulator blocked heat demand
--
5.0 Max. output (heating) - 27 - 100% 100 %
5.1 Permanent ignition - no
yes
no
5.2 GFA status / error 00h - FFh - -
5.5 Min. output - 27 - 100 % 27 %
5.8 Cyclic boiler starts - on
off
on
5.9 Fan speed (start) - low
high
low
6.7 Pump off (hot water). - off
on
off
Text display message Display
Range adjustable from - to
Reset Value
Table 1
Page 60
7 181 465 347 (01.07)8
Boiler service functions
6.8 Cycle time (hot water) - 0 - 60 min 0 min
6.9 Duration (hot water) - 0 - 30 min 1 min
7.0 Pump map (heating) - 0 Pump step adjustable
1 Const. pressure high 2 Const. pressure middle 3 Const. pressure low 4 Prop.pressure high 5 Prop.pressure low
4 Prop. pres­sure high
7.1 Map pump step (heat.). - 2 - 7 7
7.2 Antiblock. map pump. - off
on
on
7.3 Air purge mode - off on autom. deaktivat. permanent on
on autom. deaktiv at./ off
7.4 Actual map pump step 1 - 8 - -
7.5 Map pump load index 0 ... 255 - -
7.6 Map pump type 0 .. 99 - -
7.7 Output reduction - off
only in heating mode only in hot water mode in heat./hot water mode.
only in heating mode
8.5 Siphonfillprogram - on, boiler min.output, on, adjust. min output, off
on, boiler min. output
9.2 Hot water on demand - off on
on
9.3 GFA-Asic-error 00h - FFh - -
1) The reset value depends on the code plug.
Text display message Display
Range adjustable from - to
Reset Value
Table 1
Page 61
7 181 465 347 (01.07)
Boiler service functions
9
3.2 Explanation of service functions
0.0 Last fault
The last fault can also be recalled for servicing pur­poses when the appliance is functioning correctly.
To delete the stored fault:
B Delete fault (no fault displayed). B Press the button. B Use the or button to select yes. B Press the button.
If a list of the last 10 indicated faults is required for serv­icing purposes, look under Settings -> Service -> Fur- ther options -> Fault history.
0.1 Flow NTC
The temperature measured by the NTC sensor on the CH flow pipe is indicated.
0.2 Hot water NTC
The temperature measured by the NTC sensor on the plate-type heat exchanger outflow is indicated.
0.3 Storage tank NTC 1
Indirectly heated heat store (SO..., SK..., ST...): The temperature measured by NTC sensor 1 in the heat store is indicated.
Stratified-charge tank (ST...S): The temperature measured by NTC sensor 2 at the bot- tom of the heat store is indicated.
0.4 Storage tank NTC 2
Stratified-charge tank (ST...S): The temperature measured by NTC sensor 2 at the top of the heat store is indicated.
1.2 Code plug
The 10-digit part number of the code plug is indicated. The code plug determines the appliance functions. If
the appliance is converted from natural gas to LPG or vice versa (using conversion kit) the code plug also has to be changed.
1.5 Desired flow temp.
The CH flow temperature demanded by the text display module or a programmer connected to the bus module is displayed.
1.9 Module detection
The text display module shows the modules detected by the appliance.
2.0 Operating mode
There are 3 operating modes to choose from.
Normal mode: the appliance operates according to
the commands received from the programmer.
Min mode: the appliance runs constantly at minimum
output. The text display shows MIn mode. The 2-digit dis­play alternates between the CH flow temperature and
– –
.
Max mode: the appliance runs constantly at maxi-
mum output. The text display shows Max mode. The 2-digit dis­play alternates between the CH flow temperature and
– –
.
2.3 Stor. tank charge outp
The heat store charging output can be set to any level between the minimum and maximum rated heat output for hot water according to the heat transfer capacity of the heat store.
B Enter the heat store charging output setting on the
commissioning record enclosed with the appliance.
2.4 Anti-cycle mode
This function is only active if service function 2.7 Auto­matic anti-cycle mode is disabled.
The anti-cycle time is factory set to 3 minutes. The shortest possible period is 1 minute (recom-
mended for single-pipe and hot-air heating systems). The setting 0 means that the anti-cycle time is disabled.
B Enter the anti-cycle time on the commissioning
record enclosed with the appliance.
2.5 Max. flow temperature
The maximum CH flow temperature can be set to between 35 °C and 88 °C (factory setting).
2.6 Switch diff. flow NTC
The switching difference is the permissible deviation from the spec ified CH fl ow temperatur e. It can be set in increments of 1 K. The adjustment range is from 0 to 30 K (factory setting: 0 K). The minimum CH flow tem­perature is 30 °C.
B Disable anti-cycle time (setting 0). B The switching difference setting should be entered
on the commissioning record supplied with the appli­ance.
i
If an outside-temperature controlled heat­ing programmer is used, no setting is re­quired. The anti-cycle time is optimised by the programmer.
i
If an outside-temperature controlled heat­ing programmer is used, no setting is re­quired on the appliance.
Page 62
7 181 465 347 (01.07)10
Boiler service functions
2.7 Autom. anti-cycle mode
If an outside-temperature controlled programmer is con­nected to the appliance, the anti-cycle time is adjusted automatically.
Automatic adjustment of the anti-cycle time can be dis­abled. This may be necessary in the case of unfavoura­bly dimensioned heating systems.
If automatic adjustment of the anti-cycle time is disa­bled, the length of the anti -cycle time mus t be set under service function 2.4.
B If automatic adjustment of the anti-cycle time has
been disabled, this should be entered on the com­missioning record enclosed with the appliance.
2.9 Actual output
The actual output of the appliance at the time viewed is displayed.
3.0 Fan speed
The current fan speed is displayed.
3.3 Ionisation current
The burner flame is monitored by measuring the ionisa­tion current generated during combustion. If no ionisa­tion current is detected, the gas valve shuts off. This ensures that unburned gas does not escape.
3.4 Pump mode (ZBR.. models only)
The possible settings are:
Pump mode 1: if a heating pump and a 3-way valve
for charging the heat store are connected. The 3-way valve is de-energised when the heat store circuit is open.
Pump mode 2 (factory setting): if a circulation
pump and a heat store charging pump are con­nected. In ECO mode, if the circulation pump and the heat store charging pump call for heat simultane­ously, the system alternates between 12 minutes heating and 12 minutes hot water.
Pump mode 3: if a circulation pump and a heat store
charging pump are connected. In ECO mode, if the circulation pump and the heat store charging pump call for heat at the same time, both pumps run simul­taneously. The heat store charging temperature has priority (up to 85 °C). The hydraulic configuration must be matched to this pump mode (use of a mixer unit and hydraulic balancing).
B The pump mode setting should be entered on the
commissioning record enclosed with the appliance.
3.5 Pump blocking time (ZBR.. models only)
If the system incorporates a 3-way valve external to the appliance, the heating pump is disabled while the 3-way valve is being actuated. therefore, the blocking time of the heating pump should be the ac t uation time of th e 3-way valve. The blocking time has an adjustment range of 0 to 16, with each increment equivalent to 15 seconds. The adjustment range therefore equates to 0 to 240 sec­onds.
Factory setting is 30 seconds.
B Enter the pump blocking time on the commissioning
record enclosed with the appliance.
3.6 Software version
The version number of the software is displayed.
3.9 Jumper 8 - 9 /
3.9 Jumper Ls - Lr
When supplied, the appliance has a jumper fitted across terminals 8-9 (= Heat demand). If that connec­tion is opened (e.g. by a limiter for an underfloor heating system), heating mode is disabled.
When supplied, the appliance has a jumper fitted across terminals Ls-Lr (= Heat demand). If that connec­tion is opened (e.g. by an external 2-point programmer), heating mode is disabled.
4.0 Stor. tank therm. (7 - 9)
When supplied, the appliance has no jumper across ter­minals 7- 9 (= Disabled). If that connection is closed (e.g. by a heat store thermostat) heat store charging is enabled.
4.1 Room therm. LSM/ 4.1 LSM release
When supplied, a jumper is fitted across terminals LZ ­L1 on the LSM (= Heat demand). If that connection is opened (e.g. by a connected room thermostat), heating mode is disabled.
LSM release shows the total number of all possible ena­ble signals connected via the LSM. As soon as a mod­ule connected to it (e.g. mechanical limiter for underfloor heating, limit switch on flue flap, combustion air flap, etc.) shuts off, heating and hot water modes are disabled.
4.2 Timer ch. 1 (heating)/ 4.2 Timer ch. 2 (hot water)
Shows the status of channel 1 of the timer integrated in the text display module or the separate programmer. If that channel’s status is “Heat demand”, heating mode will be activated according to the programmer com­mands.
i
Only applies if service function 3.4, Pump mode, is set to Pump mode 1 (external 3­way valve for heat store charging is con­nected). Otherwise has no function.
Page 63
7 181 465 347 (01.07)
Boiler service functions
11
Shows the status of channel 2 of the timer integrated in the text display module or the separate programmer. If that channel’s status is “Heat demand”, hot water mode will be activated according to the programmer commands.
4.4 Heat demand (heating)/ Heat demand (stor. tank) (ZSBR.. only)
Heat demand (heating) shows the heat demand status for the central heating system.
If this channel’s status is “Heat demand”, heating mode will be activated according to the programmer com­mands.
Heat demand (stor. tank) shows the heat demand sta­tus for charging the heat store.
If this channel’s status is “Heat demand”, the heat store will be charged according to the commands from the heat store thermostat or NTC sensor.
4.5 Heat demand (hot water)/
Keep hot period (ZWBR... models only)
Heat demand (hot water) shows the heat demand sta­tus for the hot water function. If this channel’s status is “Heat demand”, the hot water function operates according to the commands from the hot water NTC sensor.
Keep hot period shows the constant hot water circuit status of the heat exchanger (ECO or Comfort mode). If this channel’s status is “Heat demand”, Comfort mode is active. If the status is “Disabled”, ECO mode with demand detection is active.
4.6 Internal regulator
The boiler has an internal anti-cycle function which pre­vents the burner overheating if the heat output can not be dissipated even in Min mode. The appliance will then switch off even when the system is calling for heat.
It will subsequently switch on again
• after 5 seconds in hot water mode
• after 30 seconds in heat store charging mode
• after 0 to 15 minutes in heating mode (depending on
the setting for service function 2.4 Anti-cycle mode).
The anti-cycle function is cancelled by
• switching the appliance off and on again at the mas-
ter switch,
• another demand for heat,
• activating Min or Max mode
• or briefly switching to summer mode on the tempera-
ture control for CH flow.
5.0 Max. output (heating)
Some gas suppliers demand an output-dependent basic charge.
The heating output can be limited to any level between the min. rated heat output and the max. rated heat out­put to suit the specific heat requirements.
The factory setting is maximum rated output – display shows “100 %”.
5.1 Permanent ignition
This function allows permanent ignition without gas supply to be activated for the purposes of checking the ignition mechanism.
5.2 GFA status/error
The status of the automatic ignition module integrated in the PCB control board is indicated.
5.5 Min. output
The min. heat input is factory set, see technical data. The modulation range can be extended at the top end to suit the chimney conditions.
B Refer to settings table for heating and heat store
charging output for details of the min. heat output in kW and the corresponding percentage (see installa­tion instructions for boiler).
B Enter perc entage on text dis p lay modul e and confirm . B Measure gas flow rate and compare with the figures
quoted for the percentage shown. If different, correct the percentage figure!
B Enter min. rated heat output on the commissioning
record enclosed with the appliance.
5.8 Cyclic boiler starts (ZSBR 3/5-16 A... only)
When supplied, this function is activated on the above appliances and prevents start-up problems caused by poor ignition characteristics.
A truncated start cycle is activated if the burner has not been in operation for more than 3 hours.
During a truncated start cycle, the fan runs and the gas valve is opened long enough to completely fill the gas pipe with gas (approx. 1 - 2 seconds) but the burner is not ignited.
This function is not required, and can not be activated, on any other models.
6.7 Pump off (hot water)
The appliance is supplied with this function activated, i.e. there is a delay before the pump switches on in hot water mode. This means that cold water comes out of the pipe to begin with, followed by hot water once the pump switches on.
If the pump is set to switch on immediately (Pump off function deactivated), the hot water temperature rises gradually until the set temperature is reached.
i
Even if the heating output is limited, the full rated heat output remains available for hot water or heat store charging.
Page 64
7 181 465 347 (01.07)12
Boiler service functions
If a stratified-charge tank is connected, it is useful to have the function activated.
The delayed cut-in of the pump then prevents cold water being pumped through the tank and cooling it down.
6.8 Cycle time (hot water) (ZWBR... only)
The appliance is supplied with the hot water cycle time set to 3 minutes.
The hot water cycle time specifies how long after hot water is drawn the pump continues to pump water through the internal hot water system.
6.9 Duration (hot water) (ZWBR... only)
The appliance is supplied with the hot water duration set to 3 minutes.
The hot water duration specifies how long after hot water is drawn heating mode remains disabled.
7.0 Pump map (heating) (not ZBR...)
The appliance is supplied with this function set to “4 Prop. pressure high”(see pump characteristic in boiler installation instructions).
The pump map indicates how the pump is controlled in heating mode. The pump switches between the various pump speeds so as to reproduce the characteristic curve selected. (The current setting can be viewed by means of service function 7.4.)
Changing the pump characteristic can be helpful if a lower pressure difference will guarantee the necessary circulation on the basis of the system dimensions and pump characteristic (see installation instructions).
If this parameter is set to “0 Pump step adjustable”, then the pump speed set under function 7.1 is active.
7.1 Map pump step (heat.) (not ZBR...)
The appliance is supplied with this function set to 1 (see pump characteristic in boiler installation instructions). However, th e setting is only active if function 7.0, Pump map (heating), is set to “0 Pump step adjustable”.
This service function corresponds to the pump speed switch used on conventional heating pumps.
7.2 Antiblock. map pump (not ZBR...)
The appliance is supplied with this function activated. If the pump threatens to jam, an oscillating pump action
is activated. Afterwards, the required ope rating mode is continued.
7.3 Aeration mode (not ZBR...)
The first time the appliance is switched on, a once-only venting function is activated. The heating pump then switches on and off at intervals. This sequence lasts about 8 minutes and the text display shows “Aeration mode”. The 2-digit display shows “
o
o
” in alternation with the CH flow temperature. The automatic vent must be opened and then closed again once the venting sequence is complete.
• If the venting function is set to “On, autom. deacti-
vat.”, once the sequence has been completed.
7.4 Actual map pump step (not ZBR...)
The currently active pump speed is displayed (see func­tion 7.0).
7.5 Map pump load index (not ZBR...)
The load index is displayed.
7.6 Map pump type (not ZBR...)
The pump type code of the pump fitted is displayed.
7.7 Output reduction
The appliance is supplied with this function activated. It prevents overload of the heat exchanger with high CH flow temperatures.
The output of the burner is reduced according to the CH flow temperature, i.e. up to 80 °C flow temperature, full burner output is permitted. Above 80 °C, the burner output is reduced as flow temperature increases up to 90 °C at which only minimum output is available (even with maximum heat demand).
This function can be deactivated for hot water and/or central heating mode.
i
In order to save as much energy as possi­ble and to mi n i m i se the po s s i b i l ity of wa t e r circulation noise, a low characteristic should be chosen.
i
The venting function can be activated manually after servicing.
Page 65
7 181 465 347 (01.07)
Boiler service functions
13
8.5 Siphon fill program
The trap filling programme ensures that the condensa­tion trap is filled when the appliance is first installed or after it has been shut down for a long period: The con­densation trap prevents flue gas escaping from the appliance into the room in which it is installed.
The trap filling programme is activated:
• the appliance is switched on at the master switch
• the burner has not been in operation for at least 48 hours
• the appliance is switched from summer to winter mode.
The next time the heating or hot water system calls for heat, the appliance is held at minimum output for 15 minutes. The trap filling programme remains active until the a p p l i a n c e has complet e d 15 mi n u t e s of op e r a tion at minimum output. The text display shows “Siphon fill program” and the 2-digit display alternates between „-II-“ and the CH flow temperature.
The factory setting is „1“ (activated).
9.2 Hot water on demand
The appliance is supplied with this function activated. This function relates to mode, the button lights up. The demand detection function enables maximum gas
and water economy. Briefly turning a hot water tap on and then off again sig­nals demand to the appliance which then heats up the water to the set temperature. Hot water is then available at short notice.
9.3 GFA-Asic error (automatic ignition module,
extended messages)
The status of, or an error message from the automatic ignition module integrated in the PCB control board is displayed.
Warning: if the condensation trap is not filled, flue gas can escape!
B Only deactivate the trap filling program-
me in order to carry out servicing work.
B Always re-activate trap filling program-
me once servicing is complete.
Page 66
7 181 465 347 (01.07)14
Rectifying faults
4 Rectifying faults
4.1 Boiler failure codes indication
4.1.1 ... on the boiler
In order to identify the specific boiler failure a two digit alphanumeric code is used. This allows a quick fault identification and solution.
The text display shows the message Fault EA. Please call service, for example. At the same time, the fault code appears on the 2-digit display, in this example: EA.
You can view an explanatory description of the fault indi­cated by going to Settings -> Service -> Service
parameters, in this example: EA: During operation: Flame not detected.
The failures can be divided into four basic typologies, as described:
• The appliance continues to work at a minimum func­tion level (e. g. with error codes A5, A7, A8, AC, Ad, CC, FC).
• The appliance is locked until the failure is repaired (e. g. with error codes (b1, C1, d1, d3, E2, F0)).
• The appliance is locked, until the ON/OFF switch is turned (A1).
• The boiler has shut down and locked out ( flashes) and remains so until the cause of the fault has been eliminated and the lock-out cancelled (e.g. E9, EA, F0, F7, FA,Fd).
4.1.2 ... on the programmer (optional accessory)
A TW 2 remote control unit can also be connected to the text display module.
If other/more functions are required, another program­mer must be connected. Those programmers are then controlled via the bus module BM1.
For more detailed information, refer to the installation instructions for the boiler and the installed programmer.
Faults on this programmer are indicated by text mes­sages on the programmer display.
Once the fault has been put right, the programmer reverts to its normal display.
4.2 Summary
4.2.1 Appliance faults
4.2.2 Faults that are not indicated on any dis­play
i
To unblock the appliance:
B Press the unblock button until the
digit –– appears on the display. Once the appliance starts up success­fully, the fault disappears from the text display.
Appliance faults
ZBR ... A
ZSBR ... A
ZWBR ...A
Page
A1 X X 17
A5 X 18
A7 XXX 19
A8 XXX 20
Ad XXX 21
b1 XXX 22
C1 XXX 23
d3 XXX 24
E2 XXX 25
E9 XXX 26
EA XXX 28
F0 XXX 32
F7 XXX 33
FA XXX 34
FC XXX 35
Fd XXX 35
Table 2
Appliance faults
ZBR ... A
ZSBR ... A
ZWBR ...A
Page
Excessive burner noise, rum­bling noises
XXX 36
Flue gas levels incorrect, CO level too high
XXX 37
Ignition too harsh, ignition poor
XXX 38
Boiler indicates P1, P2, P3 at start-up and then restarts with P1, ...
XXX 36
Table 3
Page 67
7 181 465 347 (01.07)
Rectifying faults
15
Loose or broken contact on heat store NTC sensor
XX 39
Specified CH flow tempera­ture from TA... programmer exceeded
XX 40
Programmer faults
TR 2
Page
Set room temperature not reached
X41
Set room temperature exceeded by large amount
X43
Set room temperature not reached
41
Temperature rises instead of falling
X43
Room temperature too high in Economy mode
X43
Incorrect or no modulation X 43
Heat store fails to heat up 44
Table 4
Appliance faults
ZBR ... A
ZSBR ... A
ZWBR ...A
Page
Table 3
Page 68
7 181 465 347 (01.07)16
Rectifying faults
4.3 How to use the fault tables
The procedure is explained using the fault code EA as an example:
The table heading shows the fault code and a general description of the fault.
In the example shown, you are instructed to note the current settings before going any further. If you can see the flame (answer to question is “yes”) you move on to Step 5. ( 5.). The question asked in Step 5 is “Is there a problem with the flue”. The flue must then be checked.
If the answer to the first question (“Is burner flame visi­ble?”) was“no””, then you go to and answer Question 2, “Is the gas cock turned on?”. If the gas cock is turned off, it must be turned on and the appliance reset. To do so, you press the button. Restart th e ap p l i a nce and run through a complete heat-demand cycle until the appliance switches off.
If the fault is now cured, the appliance will revert to nor­mal operation and the fault-finding process is complete. Now simply re-check the setting of the two temperature controls.
If the fault EA recurs during the heat-demand cycle, it will be shown on the display again. In that case continue the fault finding procedure from Step 3 (thermal cut-out in gas cock) as described above.
If a different fault code is displayed after the heat­demand cycle, find the appropriate section of the fault finding table and work through the procedure described step by step.
EA and flashing.
Flame not detected
Check Action
1. Is burner flame visible? yes: 5.
no: 2.
2. Is the gas cock turned on? yes: 3.
no: B Turn on the gas cock.
B Press , does appliance restart???
EA? 3.
3. Did the thermal security of the gas cock lock out?
yes: B ...
no: ↓ ...
4. ...
5. Is there a problem with the flue? B Check CO
2
level in combustion air. > 0,2 % CO
2
?
yes: B Check the flue.
no: ↓ ....
... ...
Page 69
7 181 465 347 (01.07)
Rectifying faults
17
4.4 Faults indicated on display
A1 flashing.
Controlled-characteristic pump has run dry
Check Action
1. System pressure below 1.2 bar? yes: B Power OFF the appliance.
B Check appliance and system for water leaks and
repair as necessary.
B Top up system. B Turn ON the appliance.
A1? 2.
no: ↓2.
2. Activate venting sequence. B Activate menu option Show service parameters.
B Select 7.3 Aeration mode select setting On,
autom. deactivat. and confirm.
B Vent appliance
1)
.
B Vent radiators.
3.
1) See installation instructions
3. Audible bearing damage on pump? yes: B Power OFF the appliance.
B Drain appliance. B Replace pump. B Top up system. B Turn ON the appliance.
Page 70
7 181 465 347 (01.07)18
Rectifying faults
A5 flashing.
Heat store NTC sensor 2 defective
Check Action
1. B Activate menu option
Show service parameters.
B Select
.4 Stor.tank temp.sensor2 . Is a temperature between 0. and 5. displayed?
yes: B Is the connector for heat store NTC sensor 2 cor-
roded
1)
, damaged or dirty? Replace affected
components.
2.
1) For notes, refer to Appendix.
no: ↓3.
2. B Disconnect connector for heat store NTC sensor 2.
B Short-circuit the 2-pin connector
on the end of the 20-pin connector lead assembly. After max. 60 sec: Display changes to temperature between 100. and 95.?
yes: B Power OFF the appliance.
B Change heat store NTC sensor 2. B Plug the connection wire. B Turn ON the appliance.
A7? 3.
no: B Change the 20-pin connector lead assembly.
3.
3. Temperature between 95. and 100. is
displayed. B Unplug the connector.
After max. 60 sec.: Does the displayed code change to a value between 0. and 5.?
yes: B Power OFF the appliance.
B Change heat store NTC sensor 2. B Plug the connection wire. B Turn ON the appliance.
A7? 4.
no: ↓4.
4. B Unplug the 20-pin connector lead assembly from the Heatronic. After max. 60 sec.: Does the displayed code change to a value between 0. and 5.?
yes: B Change the 20-pin connector lead assembly.
no: B Power OFF the appliance.
B Disconnect the boiler electrical connection. B Change PCB control board. B Reconnect the boiler electrical connection. B Turn ON the appliance.
Page 71
7 181 465 347 (01.07)
Rectifying faults
19
A7 flashing.
Hot water NTC sensor defective
Check Action
1. B Activate menu option
Show service parameters.
B Select
.2 Hot water temp.sensor . Is a temperature between 0. and 5. displayed?
yes: B Is the connector for hot water NTC sensor corro-
ded
1)
, damaged or dirty? Replace affected com-
ponents.
2.
1) For notes, refer to Appendix.
no: ↓3.
2. B Disconnect connector for hot water NTC sensor.
B Short-circuit the 2-pin connector
on the end of the 20-pin connector lead assembly. Display changes to temperature between 100. and 95.?
yes: B Power OFF the appliance.
B Change hot water NTC sensor. B Plug the connection wire. B Turn ON the appliance.
A7? 3.
no: B Change the 20-pin connector lead assembly.
3.
3. Temperature between 95. and 100. is
displayed. B Unplug the connector.
After max. 60 sec.: Does the displayed code change to a value between 0. and 5.?
yes: B Power OFF the appliance.
B Change hot water NTC sensor. B Plug the connection wire. B Turn ON the appliance.
A7? 4.
no: ↓4.
4. B Unplug the 20-pin connector lead assembly from the Heatronic. After max. 60 sec.: Does the displayed code change to a value between 0. and 5.?
yes: B Change the 20-pin connector lead assembly.
no: B Power OFF the appliance.
B Disconnect the boiler electrical connection. B Change PCB control board. B Reconnect the boiler electrical connection. B Turn ON the appliance.
Page 72
7 181 465 347 (01.07)20
Rectifying faults
A8 flashing.
No correct electrical connection
Check Action
1. Mode selector switch is between two settings
B Turn switch until it clicks into position.
A8? 2.
2. B Power OFF the appliance. Wiring between TR 2 and text-
display OK?
• Terminal 3 on TR 2 connected to
Terminal 3 on textdisplay ?
• Terminal 4 ... Terminal 4 ....
etc.
yes: B Turn ON the appliance.
3.
no: B Rewire correctly as specified in the installation
instructions.
B Turn ON the appliance.
after 90 sek.: A8? 3.
3. Lead(s) defective. B Check leads for continuity and replace as
necessary.
A8? 4.
4. TR 2 defective. B Power OFF the appliance.
B Change TR 2 . B Turn ON the appliance.
Page 73
7 181 465 347 (01.07)
Rectifying faults
21
Ad flashing.
Heat store NTC sensor 1 not detected
Check Action
1. Is lead for heat store NTC sensor
correctly routed, i.e. not through cable clamp?
yes: 2.
no: B Route connecting lead for heat store tempera-
ture sensor as specified in installation instruc­tions.
2. B Activate menu option
Show service parameters.
B Select
.3 Stor.tank temp.sensor1 . Is a temper ature between 0. and 5. displayed?
yes: Connector on end of NTC sensor lead:
B Flue gas connector corroded
1)
, damaged or
dirty? Change relative parts.
B Press button .
Ad? 3.
1)
no: ↓4.
3. Heat store -NTC 1: B Unplug connector from PCB con-
trol board.
B Short circuit the connector using
wire jumper. After max. 60 sec: Display changes to temperature between 100. and 95.
yes: B Replace heat store NTC sensor 1.
no: B Power OFF the appliance.
B Disconnect the boiler electrical connection. B Change PCB control board. B Reconnect the boiler electrical connection. B Turn ON the appliance.
4. Temperature between 95. and 100. is displayed.
B Unplug the connector.
After max. 60 sec.: Does the displayed code change to a value between 0. and 5.?
yes: B Replace heat store NTC sensor 1.
no: B Power OFF the appliance.
B Disconnect the boiler electrical connection. B Change PCB control board. B Reconnect the boiler electrical connection. B Turn ON the appliance.
Page 74
7 181 465 347 (01.07)22
Rectifying faults
b1 flashing.
Code plug not detected.
Check Action
1. No fault or fault code FC displayed
on text display?
yes: B Power OFF the appliance.
B Fit code plug (correctly), making sure code
number (see Appendix) is correct.
B Turn ON the appliance.
b1? 2.
no: ↓2.
2. B Activate menu option Show serv- ice parameters.
B Select 1.2 Code plug. B Compare number displayed with
that shown in Appendix. No number or incorrect number (last three digits) displayed.
yes: 2.
no: 4.
3. Code plug loose, incorrect or defec-
tive.
B Power OFF the appliance. B Replace code plug
1)
, making sure code number
is correct.
B Turn ON the appliance.
b1? 4.
1) For order no., refer to Appendix
4. The PCB control board is damaged. B Power OFF the appliance.
B Disconnect the boiler electrical connection. B Change PCB control board. B Reconnect the boiler electrical connection. B Turn ON the appliance.
Page 75
7 181 465 347 (01.07)
Rectifying faults
23
C1 flashing.
Fan speed too low
Check Action
1. Fan lead connector properly con­nected?
yes: 2.
no: B Power OFF the appliance.
B Plug in connector. B Turn ON the appliance.
C6? 2.
2. Fan lead defective? yes: B Power OFF the appliance.
B Replace fan lead. B Turn ON the appliance.
C6? 3.
no: ↓3.
3. Fan defective? yes: B Power OFF the appliance.
B Plug the connection wire. B Replace fan. B Plug the connection wire. B Turn ON the appliance.
C6? 4.
no: ↓4.
4. The PCB control board is damaged. B Power OFF the appliance.
B Disconnect the boiler electrical connection. B Change PCB control board. B Reconnect the boiler electrical connection. B Turn ON the appliance.
Page 76
7 181 465 347 (01.07)24
Rectifying faults
d3 flashing.
Wrong signal from pin 8-9.
Check Action
1. Jumper 8 - 9 fitted correctly? yes: 2.
no: B Power OFF the appliance.
B Fit jumper 8 - 9 correctly, tighten screw. B Turn ON the appliance.
d3? 2.
2. B Turn ON the appliance. B Measure voltage between Termi-
nal 4 and Terminal 8.
24 V DC?
yes: 3.
no: 5.
3. Heat store NTC sensor connected to terminals 7, 8 and 9?
yes: B Power OFF the appliance.
B Plug heat store NTC sensor connector into PCB
control board (303, page 46, Pos. 303). If lead has no connector: replace heat store NTC sen­sor.
B Turn ON the appliance.
d3? 4.
no: ↓4.
4. Existing heat store thermostat con­nected to Terminals 7, 8 and 9?
yes: B Power OFF the appliance.
B Fix the additional bridge 8-9 in the right position
and close the screws.
B Turn ON the appliance.
d3? 5.
no: ↓5.
5. The PCB control board is damaged. B Power OFF the appliance.
B Disconnect the boiler electrical connection. B Change PCB control board. B Reconnect the boiler electrical connection. B Turn ON the appliance.
Page 77
7 181 465 347 (01.07)
Rectifying faults
25
E2 flashing.
The heating outlet NTC sensor is damaged.
Check Action
1. B Activate menu option
Show service parameters.
B Select .1 Flow temp.sensor.
Is a temperature between 0. and 5. displayed?
yes: The heating outlet NTC sensor is in short circuit:
B Power OFF the appliance. B Replace CH flow NTC sensor; observe fitting
instructions for NTC sensor when doing so.
B Turn ON the appliance.
E2? 2.
no: ↓ 2.
2. Heating outlet NTC sensor:
Temperature between 95. and 100. is displayed.
yes: The CH flow NTC sensor is interrupted:
B Power OFF the appliance. B Replace CH flow NTC sensor; observe fitting
instructions for NTC sensor when doing so.
B Turn ON the appliance.
E2? 3.
no: ↓3.
3. Check if the 20-pin connector lead assembly is damaged.
B Power OFF the appliance. B Change the 20-pin connector lead assembly. B Turn ON the appliance.
E2? 4.
4. The PCB control board is damaged. B Power OFF the appliance.
B Disconnect the boiler electrical connection. B Change PCB control board. B Reconnect the boiler electrical connection. B Turn ON the appliance.
Page 78
7 181 465 347 (01.07)26
Rectifying faults
E9 and flashing.
Safety temperature limiter has tripped.
Check Action
1. Is the heating pressure between 1 and 2 bar?
yes: B Top up system.
B Vent appliance. B Press , does appliance restart???
E9?2.
no: ↓2.
2. Is the pump blocked? yes: B Unblock the pump.
If pump won’t start:
B Power OFF the appliance. B Disconnect the boiler electrical connection. B Change the pump. B Reconnect the boiler electrical connection. B Turn ON the appliance. B Press , does appliance restart???
E9? 3.
no: ↓3.
3. Is lead disconnected from one/both safety temperature limiters?
yes: B Power OFF the appliance.
B Connect lead. B Turn ON the appliance. B Press , does appliance restart???
E9? 4.
no: ↓4.
4. B Power OFF the appliance. B Unplug the connector from the
cut-off device.
B Measure the NTC electrical resist-
ance.
R = ∞?
yes: B Change the over heating cut-off device.
B Connect flue gas safety temperature limiter lead. B Turn ON the appliance. B Press , does appliance restart???
E9? 5.
no: B Connect flue gas safety temperature limiter lead.
B Turn ON the appliance.
E9? 5.
Page 79
7 181 465 347 (01.07)
Rectifying faults
27
5. B Power OFF the appliance. B Remove fuse SI 3 from appliance
PCB control board and test for continuity.
R = ∞?
yes: B Change the fuse.
B Turn ON the appliance. B Press , does appliance restart???
E9? 6.
no: B Remount the fuse.
B Turn ON the appliance.
6. The PCB control board is damaged. B Power OFF the appliance.
B Disconnect the boiler electrical connection. B Change PCB control board. B Reconnect the boiler electrical connection. B Turn ON the appliance.
E9 and flashing.
Safety temperature limiter has tripped.
Check Action
Page 80
7 181 465 347 (01.07)28
Rectifying faults
EA and flashing.
During operation: flame not detected
Check Action
1. Is the flame present? yes: 6.
no: 2.
2. Is the gas cock open? yes: 3.
no: B Open the gas cock
B Press , does appliance restart???
EA? 3.
3. Is there air in the supply pipe? yes: B Vent supply pipe.
B Press , does appliance restart???
EA? 4.
no: ↓4.
4. Did the thermical security of the gas cock lock out?
yes: B Reset security.
B Press , does appliance restart???
EA? 5.
no: ↓5.
5. Natural gas models: does the building have a supply pres­sure regulator?
yes: B Check that it is fitted correctly and functioning
properly and correct if necessary.
B Check supply pressure, inform gas company if
outside correct range.
B Press , does appliance restart???
EA? 6.
no: 6.
LPG models:
is the flow rate of the gas supply to the appliance correct?
yes: 6.
no: B Is there enough gas in the supply cylinder?
B Is there air in the supply pipe? B Is the solenoid valve in the “meter cabinet” open-
ing?
B Is the supply pressure OK? (if the supply pres-
sure is too high, check the pressure regulator in the “meter cabinet” and on the LPG supply cylin­der).
B Press , does appliance restart???
EA? 6.
Page 81
7 181 465 347 (01.07)
Rectifying faults
29
6. Is the ground connection correct? yes: ↓7.
no: B Rewire correctly as specified in the installation
instructions.
B Press , does appliance restart???
EA? 7.
7. Two phase net: Is there a resistor fitted between Pe and N?
yes: 8.
no: B Power OFF the appliance.
B Disconnect the boiler electrical connection. B Insert resistance (Order no. 8 900 431 516)
between the ground and the N connection.
B Reconnect the boiler electrical connection. B Turn ON the appliance. B Press , does appliance restart???
EA? 10.
8. Is condensation trap in condensing boiler blocked?
yes: B Unscrew condensation trap and clean.
B Press , does appliance restart???
EA? 12.
no: ↓9.
9. Check the gas valve?
B Power OFF the appliance. B Unplug the connectors from the
gas valve.
B Measure the gas valve coils I and
II electrical resistance.
R =164 ± 40 Ω?
yes: B Reconnect the gas valve.
B Turn ON the appliance. B Press , does appliance restart???
EA? 10.
no: B Change the gas valve.
B Reconnect the gas valve. B Turn ON the appliance. B Press , does appliance restart???
EA? 10.
10. Is flue blocked? B Check CO
2
level in combustion air. > 0,2 % CO
2
?
yes: B Check the flue.
B Press , does appliance restart???
EA? 11.
no: ↓11.
EA and flashing.
During operation: flame not detected
Check Action
Page 82
7 181 465 347 (01.07)30
Rectifying faults
11. Is flue gas CO
2
level incorrect1) ? yes: B Adjust to correct level.
B Press , does appliance restart???
EA? 12.
no: ↓12.
12. B Activate menu option Show serv- ice parameters.
B Select 5.1 Permanent ignition. Continuous ignition OK?
yes: 13.
no: 16.
13. Ignition lead connected to ignition
electrodes?
yes: 14.
no: B Connect cable to ignition electrode.
B Press , does appliance restart???
EA? 14.
14. Ignition cable connector engaged in
switchbox?
yes: 15.
no: B Power OFF the appliance.
B Engage ignition cable connector in switchbox. B Turn ON the appliance. B Press , does appliance restart???
EA? 15.
15. Ignition cable defective? yes: B Power OFF the appliance.
B Replace ignition cable. B Turn ON the appliance. B Press , does appliance restart???
EA? 16.
no: ↓16.
16. B Select 3.3 Ionisation current.
Measured ionisation current medium or high?
yes: 18.
no: 17.
EA and flashing.
During operation: flame not detected
Check Action
Page 83
7 181 465 347 (01.07)
Rectifying faults
31
17. Electrode assembly defective?
B Power OFF the appliance. B Remove electrode assembly.
Electrodes worn out?
yes: B Replace electrode assembly.
B Turn ON the appliance. B Press , does appliance restart???
EA? 18.
no: B Refit electrode assembly.
B Turn ON the appliance. B Press , does appliance restart???
EA? 18.
18. Check if the 20-pin connector lead assembly is damaged.
B Power OFF the appliance. B Change the 20-pin connector lead assembly. B Turn ON the appliance. B Press , does appliance restart???
EA? 19.
19. The PCB control board is damaged. B Power OFF the appliance.
B Disconnect the boiler electrical connection. B Change PCB control board. B Reconnect the boiler electrical connection. B Turn ON the appliance.
1) See installation instructions
EA and flashing.
During operation: flame not detected
Check Action
Page 84
7 181 465 347 (01.07)32
Rectifying faults
F0 (and possibly ) flashing.
Internal failure
Check Action
1. B Activate menu option
Show service parameters.
B Select 9.3 GFA-Asic-error.
A message is displayed.
B Record figure displayed in service report.
2.
2. B Select 5.2 GFA status / error.
A message is displayed.
B Record figure displayed in service report.
3. B Select Settings -> Service -> Further options -> Fault history.
Other faults apart from F0 dis­played?
yes: B Deal with fault(s) displayed as instructed in rele-
vant fault table(s) .
no: ↓3.
4. flashing? yes: B Press button .
B Initiate demand for heat by pressing the . but-
ton and then cancel after 30 seconds by pressing the button again.
B Initiate demand for heat twice more as described
above.
F0? 4.
no: ↓4.
5. The PCB control board is damaged. B Power OFF the appliance.
B Disconnect the boiler electrical connection. B Change PCB control board. B Reconnect the boiler electrical connection. B Turn ON the appliance.
Page 85
7 181 465 347 (01.07)
Rectifying faults
33
F7 and flashing.
Although appliance switches off, flame still detected
Check Action
1. Electrode(s) dirty or defective. B Power OFF the appliance. B Replace electrode assembly. B Turn ON the appliance. B Press , does appliance restart???
F7? 2.
2. B Power OFF the appliance.
B Disconnect the boiler electrical
connection. B Remove PCB control board. PCB control board damp?
yes: B Dry PCB control board (e.g. with hair dryer).
B Refit PCB control board. B Reconnect the boiler electrical connection. B Press , does appliance restart???
F7? 3.
no: ↓3.
3. Is there a problem with the flue? B Check CO
2
level in combustion air. > 0,2 % CO
2
?
yes: B Check flue and repair or replace if necessary.
no: 4.
4. The PCB control board is damaged. B Power OFF the appliance. B Disconnect the boiler electrical connection. B Change PCB control board. B Reconnect the boiler electrical connection. B Turn ON the appliance.
Page 86
7 181 465 347 (01.07)34
Rectifying faults
FA and flashing.
After appliance switches off flame is detected
Check Action
1. Is condensation trap in condensing boiler blocked?
yes: B Clean condensation trap discharge pipe.
B Press , does appliance restart???
FA? 2.
no: ↓2.
2. Electrodes faulty. B Replace electrode assembly.
B Turn ON the appliance. B Press , does appliance restart???
FA? B Power OFF the appliance.
3.
3. Problem with flue? B Check CO
2
level in combustion air. > 0,2 % CO
2
?
yes: B Check flue and repair or replace if necessary.
B Press , does appliance restart???
FA? B Power OFF the appliance.
4.
no: ↓4.
4. The gas valve is damaged. B Change the gas valve.
B Turn ON the appliance. B Press , does appliance restart???
FA? B Power OFF the appliance.
5.
5. Check if the 20-pin connector lead assembly is damaged.
B Change the 20-pin connector lead assembly. B Turn ON the appliance. B Press , does appliance restart???
FA? B Power OFF the appliance.
6.
6. The PCB control board is damaged. B Disconnect the boiler electrical connection.
B Change PCB control board. B Reconnect the boiler electrical connection. B Turn ON the appliance.
Page 87
7 181 465 347 (01.07)
Rectifying faults
35
FC flashing.
Text display module not detected
Check Action
1. No fault or fault code FC displayed
on text display?
B Power OFF the appliance. B Fit code plug (correctly), making sure code
number is correct (see Appendix).
B Turn ON the appliance.
FC? 2.
2. B Unplug text display module con­nector.
B Connecting lead between text dis-
play module and Heatronic OK.?
yes: B Plug in connector.
FC? 3.
no: B Replace text display module.
FC? 3.
3. Text display module defective. B Replace text display module.
Fd and flashing.
Reset button pressed inadvertently
Check Action
1. B Press button again.
2. The PCB control board is damaged. B Disconnect the boiler electrical connection.
B Change PCB control board. B Reconnect the boiler electrical connection. B Turn ON the appliance.
Page 88
7 181 465 347 (01.07)36
Rectifying faults
4.5 Faults that are not displayed
4.5.1 Appliance faults
Boiler indicates P1, P2, P3 at start-up and then restarts with P1..
Check Action
1. Fuse T 1.6 A (312) defective. yes: B Turn ON the appliance.
B Change the fuse. B Power OFF the appliance.
Start sequence not completed? 2.
no: ↓2.
2. The PCB control board is damaged. B Change PCB control board.
Excessive burner noise, rumbling noises
Check Action
1. Does the gas supply type match the specifications on the appliance iden­tification plate?
yes: 2.
no: B Convert appliance to correct gas type
1)
.
2. B Test gas supply pressure - OK?
1)
? yes: 3.
no: B Decommission appliance.
B Notify gas company.
3. Problem with flue? B Check CO
2
level in combustion air. > 0,2 % CO
2
?
yes: B Check flue and repair or replace if necessary.
no: 4.
4. B Remove silencer, flue pipe and mixer unit. Is internal flue pipe/silencer dirty or clogged or are seals defective or incorrectly fitted?
yes: B Repair or replace components.
B Grease seal before fitting, B Make sure it is fitted in correct position.
no: ↓5.
5. Flue gas CO
2
levels measured at min. and max. load do not match specified levels
1)
.
B Measure CO
2
levels.
yes: B Adjust CO
2
levels.
no: B Power OFF the appliance.
B Change the gas valve. B Turn ON the appliance.
1) See installation instructions
Page 89
7 181 465 347 (01.07)
Rectifying faults
37
Flue gas levels incorrect, CO level too high
Check Action
1. Does the gas supply type match the specifications on the appliance iden­tification plate?
yes: 2.
no: B Convert appliance to correct gas type
1)
.
2. B Test gas supply pressure
1)
, - OK? yes: 3.
no: B Decommission appliance.
B Notify gas company.
3. Problem with flue? B Check CO
2
level in combustion air. > 0,2 % CO
2
?
yes: B Check flue and repair or replace if necessary.
no: 4.
4. Flue gas CO
2
levels measured at min. and max. load do not match specified levels?
1)
.
B Measure CO
2
levels.
yes: B Adjust CO
2
levels.
no: ↓5.
5. Gas volumetric flow too high when CO
2
level correctly set1).
yes: B Reduce gas volumetric flow rate by means of
adjusting screw on gas valve and/or gas flow restrictor.
B Check CO
2
adjustment.
no: ↓6.
6. B Change the gas valve.
1) See installation instructions
Page 90
7 181 465 347 (01.07)38
Rectifying faults
Ignition too harsh, ignition poor
Check Action
1. B Activate menu option
Show service parameters.
B Select 5.1 Permanent ignition.
Continuous ignition OK?
yes: 6.
no: 2.
2. Ignition lead connected to ignition electrodes?
yes: 3.
no: B Connect cable to ignition electrode.
B Press button .
Ignition poor? ↓3.
3. Ignition cable connector engaged in switchbox?
yes: 4.
no: B Power OFF the appliance.
B Engage ignition cable connector in switchbox. B Turn ON the appliance. B Press button . B Power OFF the appliance.
Ignition poor? ↓4.
4. Ignition cable defective? yes: B Power OFF the appliance.
B Replace ignition cable. B Turn ON the appliance. B Press button . B Power OFF the appliance.
Ignition poor? ↓5.
no: ↓5.
5. Electrode assembly defective?
B Power OFF the appliance. B Remove electrode assembly.
Electrodes worn out?
yes: B Replace electrode assembly.
B Turn ON the appliance. B Press , does appliance restart???
Ignition poor? ↓6.
no: B Refit electrode assembly.
B Turn ON the appliance. B Press , does appliance restart???
Ignition poor? ↓6.
6. Does the gas supply type match the specifications on the appliance iden­tification plate?
yes: 7.
no: B Carry out gas type conversion as described in
installation instructions.
Ignition poor? ↓7.
Page 91
7 181 465 347 (01.07)
Rectifying faults
39
7. B Test gas supply pressure
1)
- OK?. yes: 8.
no: B Decommission appliance.
B Notify gas company.
8. Problem with flue? B Check CO
2
level in combustion air. > 0,2 % CO
2
?
yes: B Check flue and repair or replace if necessary.
Ignition poor? ↓8.
no: ↓9.
9. Flue gas CO
2
levels measured at min. and max. load do not match specified levels.
B Measure CO
2
levels.
yes: B Adjust CO
2
levels.
no: ↓9.
10. Burner not correctly fitted or defec­tive?
B Remove burner.
Cover fixings not tight
or
seal defective or not correctly fitted
or
burner defective.
B Replace burner and seal if necessary B Ensure seal is fitted in correct position.
1) See installation instructions
Ignition too harsh, ignition poor
Check Action
Loose or broken contact on heat store NTC sensor
Check Action
Heat store NTC sensor lead is not fit­ted as described in the installation instructions (i.e. the cable does not pass through the cable grip in the switchbox).
B Record condition of appliance as found in custo-
mer service record.
B Route cable as specified in installation instruc-
tions.
Text display fails to respond, no display or display incorrect
Check Action
Ignition lead is not fitted as specified in installation instructions (i.e. the lead should be routed through the clip on the underside of the air box).
B Route cable as specified in installation instruc-
tions.
Page 92
7 181 465 347 (01.07)40
Rectifying faults
Specified CH flow temperature from TA... programmer exceeded
Check Action
If outside-temperature controlled programmer (TA...) is connected to boiler:
• The anti-cycle time is adjusted by the programmer to the suit the system.
• The factory setting for the anti-cycle time (3 min.) and the heating mode hysteresis setting, if applicable, are deactivated.
• In cyclic mode, the switching of the boiler on or off is subject to a time delay in order to prevent diver­gence between the average CH flow temperature and the specified CH flow temperature. As a result (depending on the heat draw), the specified CH flow temperature is briefly exceeded. In extreme cases, it can happen that the burner does not switch off until the maximum CH flow tempe­rature is reached even though a lower CH flow temperature has been specified.
1. B Activate menu option
Show service parameters.
B Select 2.7 Autom. anti-cycle
mode.
Read off status of automatic anti­cycle time (0 = Disabled, 1=Enabled)
B Disable automatic anti-cycle time, i.e. change
setting to 0.
2. B Select 2.4 Anti-cycle mode.
Read off anti-cycle time setting ( 0 ... 15 min)
B Set anti-cycle time as required, e.g. factory set-
ting 3 min.
Page 93
7 181 465 347 (01.07)
Rectifying faults
41
4.5.2 Programmer faults
Set room temperature not reached (TR 2)
Check Action
1. Thermostatic valve(s) set too low? yes: B Turn up thermostatic valve(s).
2.
no: ↓2.
2. CH flow temperature control on boiler set too low?
yes: B Turn up CH flow temperature control.
no: 3.
3. Air in the heating system. B Power OFF the appliance.
B Check appliance and system for water leaks and
repair as necessary.
B Top up system. B Activate menu option Show service parame-
ters.
B Select 7.3 Aeration mode , select setting On,
autom. deactivat. and confirm.
B Vent appliance
1)
.
B Vent radiators. B Turn ON the appliance.
1) See installation instructions
Page 94
7 181 465 347 (01.07)42
Rectifying faults
Set room temperature not reached
Check Action
1. Thermostatic valve(s) set too low? yes: B Turn up thermostatic valve(s).
2.
no: ↓2.
2. Heating characteristic set too low? yes: B Correct heating characteristic.
3.
no: ↓3.
3. CH flow temperature control on boiler set too low?
yes: B Turn up CH flow temperature control.
4.
no: ↓4.
4. Heat store connected via HSM? yes: ↓5.
no: ↓6.
5. Is heat store temperature unreacha­ble (CH flow temperature control set too low)?
yes: B Turn up CH flow temperature control.
6.
no: ↓6.
6. Air in the heating system. B Power OFF the appliance.
B Check appliance and system for water leaks and
repair as necessary.
B Top up system. B Activate menu option Show service parame-
ters.
B Select 7.3 Aeration mode , select setting On,
autom. deactivat. and confirm.
B Vent appliance
1)
.
B Vent radiators. B Turn ON the appliance.
1) See installation instructions
Page 95
7 181 465 347 (01.07)
Rectifying faults
43
Set room temperature exceeded by large amount
Check Action
1. Do radiators get too hot? yes: TR 2:
B Decrease setting of “Heating” control
2.
no: ↓2.
2. Bad choice of location for program­mer, e.g. outside wall, near window, in draught, on hollow wall, etc.
yes: B Select better installation location
1)
.
3.
no: ↓3.
3. B Turn down thermostatic valve(s).n
1) See installation instructions
Temperature rises instead of falling
Check Action
Timer clock (DT 2) incorrectly set B Check setting and correct as necessary.
Room temperature too high in Economy mode
Check Action
Building retains heat well yes: B Set economy temperature lower.
-or-
B Set earlier start time for Economy mode.
Incorrect or no modulation
Check Action
Programmer incorrectly wired B Check wiring against wiring diagram and correct
as necessary.
Page 96
7 181 465 347 (01.07)44
Rectifying faults
Heat store fails to heat up
Check Action
1. with TR 2: CH flow temperature control on boiler set too low.
B Increase CH flow temperature control setting.
2. Hot water temperature control on boiler set too low
B Increase hot water temperature control setting.
Page 97
7 181 465 347 (01.07)
Appendix
45
5Appendix
5.1 NTC values
5.1.1 Outside temperature sensor
5.1.2 CH flow NTC sensor, heat store NTC sen­sor, constant hot water NTC sensor and hot water NTC sensor
Outside temperature
(°C)
Measurement
tolerance ± 10%
Resistance
( )
-20 2 392
-16 2 088
-12 1 811
-8 1 562
-4 1 342
01 149
4984
8842
10 781
15 642
20 528
25 436
Table 5
Temperature ( °C)
Measurement
tolerance ± 10%
Resistance
( )
20 14 772
25 11 981
30 9 786
35 8 047
40 6 653
45 5 523
50 4 608
55 3 856
60 3 243
65 2 744
70 2 332
75 1 990
80 1 704
85 1 464
90 1 262
95 1 093
100 950
Table 6
Page 98
7 181 465 347 (01.07)46
Appendix
5.2 Electronic schemes
Fig. 2
4.1 Ignition transformer 6 Temperature limiter, heat exchanger 9 Flue gas temperature limiter 18 Pump 32 Flame sensing electrode 33 Ignition electrode 36 Temperature sensor in CH flow 52 Solenoid valve 1
52.1 Solenoid valve 2 56 Gas valve CE 427 61 Reset button 84 Motor, 3-way valve (ZSBR) 135 Master switch 136 Temperature control for CH flow 151 Fuse, slow 2.5 A, AC 230 V 153 Transformer 161 Link
226 Fan 300 Code plug 302 Earth connection 310 Temperature control for hot water 312 Fuse, slow T 1,6 A 313 Fuse, slow T 0,5 A 317 Digital display 328 Terminal block for AC 230 V Mains supply
328.1 Link 363 Indicator lamp for burner 364 Indicator lamp for power supply 365 “Chimney sweep” button 366 Service button 367 ECO button 400 Textdisplay 422 Connecting TR2
6
9
32
33
36
52.1
52
56
61
230 V
135
25 V
230V/AC
153
136
151
1247
89
161
M
226
300
L
NLsNs
328
LR
302
310
312
313
317
363
364
365
366
ECO
367
4.1
328.1
18
84
M
400
43F
M
6 720 610 603 - 03.1O
mains supply
422
r r
bl bl bl bl
bl
o
o
p p
p
o - orange bl - black r - red p - purple
Page 99
7 181 465 347 (01.07)
Appendix
47
5.3 List of most important replacement parts
Component Order no. Remarks
Switchbox
PCB control board
8 748 300 385
Transformer 8 747 201 358
Ignition lead 8 714 401 878
20-pin connector lead assembly
8 714 401 912
Fuse 1 904 522 730 T 0,5 A
Fuse 1 904 522 740 T 1,6 A
Fuse 1 904 521 342 T 2,5 A
Code plug included in
Conversion kit G20 -> 31
7 710 149 050 ZWBR
8-30
Conversion kit G31 -> G20
7 710 239 086 ZWBR
11- 30
Conversion kit G20 -> G31
7 710 149 051 ZWBR
11 - 37
Conversion kit G31 -> G20
7 710 239 087 ZWBR
14 - 37
Conversion kit G20 -> G31
7 710 149 052 ZSBR
7-28
Conversion kit G31 -> G20
7 710 239 088 ZSBR
11-28
Conversion kit G20 -> G31
7 710 149 053 ZBR 8-35
Conversion kit G31 -> G20
7 710 239 089 ZBR 11-35
Conversion kit G20 -> G31
7 710 149 046 ZWBR
7-28
Conversion kit G31 -> G20
7 710 239 082 ZWBR
11-35
Conversion kit G20 -> G31
7 710 149 047 ZWBR
11-35
Conversion kit G31 -> G20
7 710 239 083 ZWBR
14-35
Table 7
Heat exchanger
Temperature lim­iter STB
8 729 000 144 110 °C
Flue gas temper­ature limiter
8 729 000 144
Temperature sensor, CH flow
8 714 500 054 NTC
Burner
Electrode assembly
8 718 107 064
Gas valve
Gas valve 8 747 003 516
Gas valve 8 747 003 515 ZBR 11/
14..42A
Other components
Fan 8 717 204 325
Gas supply pipe 8 714 401 885
Textdisplay 8 747 208 081
Plate-type heat exchanger
8 715 406 659 ZWBR
7/11-28 A.
Component Order no. Remarks
Table 7
Page 100
7 181 465 347 (01.07)48
Appendix
5.4 Approved corrosion inhibitors and anti-freeze fluids for central heating water
Manufacturer Description Remarks
Mixing concentra– tion % by weight
With all anti-freeze fluids and corrosion inhibitors, it is extremely important to observe the manufacturer’s recom­mended concentration levels and to check the concentration regularly. In the case of anti-freeze fluids, it should be noted that the efficiency of fluid-to-fluid heat transfer diminishes as the anti-freeze concentration increases.
Anti-freeze fluid
Hüls Ilexan E Anti-freeze fluid, equivalent to Antifrogen N.
Tyforop Chemie GmbH, Hamburg
Tyfocor L Anti-freeze fluid based on propylene glycol. 25-80
Schilling Chemie Varidos FSK Anti-freeze fluid based on ethylene glycol with
good corrosion-inhibiting properties. Also suitable for aluminium.
22-55
Hoechst Antifrogen N Anti-freeze fluid based on ethylene glycol with
good corrosion-inhibiting properties.
20-40
Fernox Alphi-11 Anti-freeze fluid with corrosion inhibitor, also suit-
able for aluminium.
BASF Glythermin NF Anti-freeze fluid based on ethylene glycol with
good corrosion-inhibiting properties, also suitable for aluminium.
20-62
Corrosion inhibitor
Schilling Chemie Varidos KK Corrosion inhibitor 0,5
Schilling Chemie Varidos 1+1 Corrosion inhibitor 1-2
Schilling Chemie Varidos AP Corrosion inhibitor, also suitable for aluminium. 1-2
Benckiser Wassertechnik
Randophos HS Universal
Corrosion inhibitor
Geminox, Frankreich
Inibal Corrosion inhibitor, suitable for aluminium. 1-2
Betz Dearborn, Belgien
Sentinel X 100 Corrosion inhibitor for hot water heating systems,
also suitable for aluminium.
1,1
Fernox Copal Corrosion inhibitor, also suitable for aluminium. 1
Cillit Wassertechnik Cillit-HS Combi Corrosion inhibitor 0,5
Other additives
Fernox Restorer Superfloc
Universal Cleanser
Cleaning agent (for sludge removal), also suitable for aluminium.
1-2
Fernox Superconcentrate
Central heating Protector
Reduces limescale precipitation, also suitable for aluminium.
Table 8
Loading...