Briggs & Stratton bsp5500l User Manual

Model No. 1774-0 (5500 Watt AC Generator) Manual No. 191242GS Revision 0 (06/06/2002)
Owner’s Manual / Manual del Propietario / Manual do Proprietário
BSP5500L
Questions?
Help is just a moment away!
Find your Briggs and Stratton
distributor in our distributor
locator map at
or contact your local Briggs and
Stratton dealer for further
information.
Preguntas?
La ayuda es justa un momento lejos!
Encuentre su Briggs y Stratton
distribuidor en nuestro mapa del
localizador de distribuidor en
o avise su Briggs y Stratton el
comerciante local para la información
adicional.
Perguntas?
O auxílio está a poucos passos!
Procure o fornecedor de serviços
authrizados mais próximo em nosso
mapa de fornecedores em
ou entre em contato com seu
representante local da Briggs &
Stratton para obter mais informações.
2
BSP5500L Generator
TABLE OF CONTENTS
Safety Rules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Know Your Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Product Specifications / Maintenance . . . . . . . . . . . . . . . . 9
Storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 & 17
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Schematic/Wiring Diagram . . . . . . . . . . . . . . . . . . . . 12-13
Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . 14-16
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Last Page
EQUIPMENT
DESCRIPTION
Read this manual carefully and become familiar with your generator. Know its applications, its limitations and any hazards involved.
This generator is an engine–driven, revolving field,alternating current (AC) generator. It was designed to supply electrical power for operating compatible electrical lighting, appliances, tools and motor loads.The generator’s revolving field is driven at about 3,600 rpm by a single-cylinder engine.
CAUTION! Do Not exceed the generator’s
wattage/amperage capacity. See “Don’t Overload the Generator” on page 8.
Every effort has been made to ensure that information in this manual is accurate and current. However,Briggs & Stratton reserves the right to change, alter or otherwise improve the product and this document at any time without prior notice.
The Emission Control System for this generator is warranted for standards set by the Environmental Protection Agency. For warranty information refer to the engine owner’s manual.
SAFETY RULES
The safety alert symbol ( ) is used with a signal word (DANGER, CAUTION,WARNING), a pictorial and/or a safety message to alert you to hazards. DANGER indicates a hazard which, if not avoided, will result in death or serious injury. WARNING indicates a hazard which, if not avoided, could result in death or serious injury. CAUTION indicates a hazard which, if not avoided, might result in minor or moderate injury. CAUTION, when used without the alert symbol, indicates a situation that could result in equipment damage. Follow safety messages to avoid or reduce the risk of injury or death.
The engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
WARNING
• Operate generator ONLY outdoors.
• Keep at least 2 feet of clearance on all sides of generator for adequate ventilation.
• Do not operate generator inside any building or enclosure, including the generator compartment of a recreational vehicle (RV).
Running generator gives off carbon monoxide, an odorless, colorless, poison gas.
Breathing carbon monoxide will cause nausea, fainting or death.
DANGER
• When using generator for backup power,notify utility company. Use approved transfer equipment to isolate generator from electric utility.
• Use a ground circuit fault interrupter (GFCI) in any damp or highly conductive area, such as metal decking or steel work.
• Do not touch bare wires or receptacles.
• Do not use generator with electrical cords which are worn, frayed, bare or otherwise damaged.
• Do not operate generator in the rain.
• Do not handle generator or electrical cords while standing in water, while barefoot, or while hands or feet are wet.
• Do not allow unqualified persons or children to operate or service generator.
Generator produces powerful voltage. Failure to isolate generator from power utility
can result in death or injury to electric utility workers due to backfeed of electrical energy.
DANGER
• National Electric Code requires generator to be properly grounded to an approved earth ground. Call an electrician for local grounding requirements.
Failure to properly ground generator can result in electrocution, especially if the generator is equipped with a wheel kit.
DANGER
3
BSP5500L Generator
WHEN ADDING FUEL
• Turn generator OFF and let it cool at least 2 minutes before removing gas cap.Loosen cap slowly to relieve pressure in tank.
• Fill fuel tank outdoors.
• Do not overfill tank. Allow space for fuel expansion.
• Keep gasoline away from sparks, open flames, pilot lights, heat, and other ignition sources.
• Do not light a cigarette or smoke.
WHEN OPERATING EQUIPMENT
• Do not tip engine or equipment at angle which causes gasoline to spill.
WHEN TRANSPORTING OR REPAIRING EQUIPMENT
• Transport/repair with fuel tank EMPTY or with fuel shutoff valve OFF.
• Disconnect spark plug wire.
WHEN STORING GASOLINE OR EQUIPMENT WITH FUEL IN TANK
• Store away from furnaces, stoves, water heaters,clothes dryers or other appliances that have pilot light or other ignition source because they can ignite gasoline vapors.
Gasoline and its vapors are extremely flammable and explosive.
Fire or explosion can cause severe burns or death.
WARNING
• Do not allow any open flame, spark, heat, or lit cigarette during and for several minutes after charging a battery.
• Wear protective goggles,rubber apron, and rubber gloves.
Storage batteries give off explosive hydrogen gas during recharging.
Hydrogen gas stays around battery for a long time after battery has been charged.
Slightest spark will ignite hydrogen and cause explosion.
You can be blinded or severely injured. Battery electrolyte fluid contains acid and is
extremely caustic. Contact with battery fluid will cause severe
chemical burns.
DANGER
• Do not touch hot surfaces.
• Allow equipment to cool before touching.
Running engines produce heat.Temperature of muffler and nearby areas can reach or exceed 150°F (65°C).
Severe burns can occur on contact.
WARNING
• Do not tamper with governed speed. Generator supplies correct rated frequency and voltage when running at governed speed.
• Do not modify generator in any way.
Excessively high operating speeds increase risk of injury and damage to generator.
Excessively low speeds impose a heavy load.
CAUTION
• See “Don’t Overload Your Generator” on page 8.
• Start generator and let engine stabilize before connecting electrical loads.
• Connect electrical loads in OFF position, then turn ON for operation.
• Turn electrical loads OFF and disconnect from generator before stopping generator.
Exceeding generators wattage/amperage capacity can damage generator and/or electrical devices connected to it.
CAUTION
• Use generator only for intended uses.
• If you have questions about intended use, ask dealer or contact Briggs & Stratton.
• Operate generator only on level surfaces.
• Do not expose generator to excessive moisture, dust, dirt, or corrosive vapors.
• Do not insert any objects through cooling slots.
• If connected devices overheat, turn them off and disconnect them from generator.
• Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
Improper treatment of generator can damage it and shorten its life.
CAUTION
BSP5500L Generator
4
120 Volt AC, 20 Amp, Duplex Receptacles — May be
used to supply electrical power for the operation of 120 Volt AC, 20 Amp, single phase, 60 Hz electrical, lighting, appliance, tool and motor loads.
120/240 Volt AC, 30 Amp Locking Receptacle — May be used to supply electrical power for the operation of 120 and/or 240 Volt AC, 30 Amp, single phase, 60 Hz electrical, lighting, appliance, tool and motor loads.
Air Cleaner — Uses a dry type filter element to limit the amount of dirt and dust sucked into the engine.
Choke Lever — Used when starting a cold engine.
Circuit Breakers (AC) — Push to reset circuit breakers
are provided to protect the generator against electrical overload.
Fuel Tank — Capacity of seven (7) U.S.gallons. Grounding Wing Nut — Used for proper grounding of
unit (see page 6).
Oil Fill — Add engine oil here. Recoil starter — Used to start the engine. Rocker Switch — Set this switch to "On" before using
recoil starter. Set switch to "Off" to switch off engine. Spark Arrester Muffler — Exhaust muffler lowers
engine noise and is equipped with a spark arrester screen.
KNOW YOUR GENERATOR
Read this owner’s manual and safety rules before operating your generator.
Compare the illustrations with your generator, to familiarize yourself with the locations of various controls and adjustments. Save this manual for future reference.
120 Volt AC, 20 Amp Duplex Receptacles
Fuel Tank
Choke Lever
Recoil Starter
Rocker Switch (on engine shroud)
Circuit Breakers (AC)
120/240 Volt AC, 30 Amp Receptacle
Spark Arrester Muffler
Air Cleaner
Grounding Wing Nut
Oil Fill
BSP5500L Generator
5
BEFORE STARTING THE
ENGINE
Add Oil
CAUTION! Any attempt to crank or start the engine
before it has been properly filled with the recommended oil may result in an engine failure.
To fill your engine with oil:
• Place generator on a level surface.
• Follow the oil grade recommendations and oil fill instructions given in the engine owner’s manual.
NOTE:The generator’s revolving field rides on a prelubricated and sealed ball bearing that requires no additional lubrication for the life of the bearing.
Add Gasoline
WARNING! Never fill fuel tank indoors. Never
fill fuel tank when engine is running or hot.Allow unit to cool for two minutes before refueling. Do Not light a cigarette or smoke when filling the fuel tank.
WARNING! Do Not overfill the fuel tank.
Always allow room for fuel expansion.
• Use regular UNLEADED gasoline with the generator engine. Do Not use premium gasoline. Do Not mix oil with gasoline.
• Clean area around fuel fill cap, remove cap.
• Slowly add unleaded regular gasoline to fuel tank. Be careful not to overfill.Allow about 1.5" of tank space for fuel expansion (Figure 1).
• Install fuel cap and wipe up any spilled gasoline.
IMPORTANT: It is important to prevent gum deposits from forming in essential fuel system parts, such as the carburetor, fuel filter,fuel hose or tank during storage.Also, experience indicates that alcohol–blended fuels (called gasohol, ethanol or methanol) can attract moisture, which leads to separation and formation of acids during storage. Acidic fuel can damage the fuel system of an engine while in storage.
Be sure to review the precautions given in “Storage” on page 9. Never use engine or carburetor cleaner products in the fuel tank or permanent damage may occur.
Figure 1 — Typical Fuel Expansion Space
Fuel
Tank
1.5” Airspace
BSP5500L Generator
6
GROUNDING THE
GENERATOR
The National Electrical Code requires that the frame and external electrically conductive parts of this generator be properly connected to an approved earth ground. Local electrical codes may also require proper grounding of the unit. For that purpose, a GROUNDING WING NUT is provided on the generator end (Figure 2).
Generally, connecting a No. 12 AWG (American Wire Gauge) stranded copper wire to the grounding wing nut and to an earth–driven copper or brass grounding rod (electrode) provides adequate protection against electrical shock. Be careful to keep the grounding wire attached after connecting the stranded copper wire. However, local codes may vary widely. Consult with a local electrician for grounding requirements in your area.
Properly grounding the generator helps prevent electrical shock if a ground fault condition exists in the generator or in connected electrical devices, especially when the unit is equipped with a wheel kit. Proper grounding also helps dissipate static electricity, which often builds up in ungrounded devices.
OPERATING THE
GENERATOR
CAUTION! Never start or stop the engine with
electrical loads connected to the receptacles AND with the connected devices turned ON.
Starting the Engine
Disconnect all electrical loads from the generator. Use the following start instruction steps by numerical order:
1. Turn the fuel valve to the “On” position (Figure 3).
2. Place the choke lever in the “Choke” position
(Figure 4).
3. Set the rocker switch to “On” position (Figure 5).
4. Grasp the recoil handle and pull slowly until slight
resistance is felt.Then pull rapidly to start engine.
5. Move choke lever to “Run” position a short distance at
a time over several seconds in warm weather or minutes in cold weather. Let engine run smoothly before each change. Operate with choke in “Run” position.
NOTE: If engine still fails to start, see engine manual.This engine may be equipped with a low oil device.
Refer to the engine owner’s manual for more detailed starting instructions.
Fuel Valve is shown in the Off position
Figure 3 — Fuel Valve
Figure 4 — Choke Lever
Figure 5 — Rocker Switch
Figure 2 — Grounding Wing Nut
Grounding Wing Nut
BSP5500L Generator
7
Connecting Electrical Loads
• Let engine stabilize and warm up for a few minutes after starting.
• Plug in and turn on the desired 120 and/or 240 Volt AC, single phase, 60 Hz electrical loads.
Do Not connect 240 Volt loads to the 120 Volt duplex receptacles.
Do Not connect 3–phase loads to the generator.
Do Not connect 50 Hz loads to the generator.
DO NOT OVERLOAD THE GENERATOR. See “Don’t Overload the Generator” on page 8.
Stopping the Engine
• Unplug all electrical loads from generator panel receptacles. Never start or stop engine with electrical devices plugged in and turned ON.
• Let engine run at no-load for several minutes to stabilize the internal temperatures of engine and generator.
• Move rocker switch to “Off” position.
• Move the fuel valve to the “Off” position.
RECEPTACLES
120/240 Volt AC, 30 Amp, Locking
Receptacle
Use a NEMA L14–30 plug with this receptacle. Connect a 4–wire cord set rated for 250 Volt AC loads at 30 Amps (or greater) (Figure 6).You can use the same 4–wire cord if you plan to run a 120 Volt load.
This receptacle powers 120/240 Volt AC, 60 Hz, single phase loads requiring up to 5,500 watts of power (5.5 kW) at 30 Amps for 120 Volts or 240 Volts.The outlet is protected by a push–to–reset circuit breaker.
CAUTION! Although this outlet states it has a
120/240 Volt 30 Amp rating (up to 7,200 watts), the generator is only rated for 5,500 watts. Powering loads that exceed the wattage/amperage capacity of the generator can damage it or cause serious injuries.
120 Volt AC, 20 Amp, Duplex
Receptacles
Each duplex receptacle (Figure 7) is protected against overload by a push–to–reset circuit breaker.
Use each receptacle to operate 120 Volt AC, single–phase, 60 Hz electrical loads requiring up to 2,400 watts (2.4 kW) at 20 Amps of current. Use cord sets that are rated for 125 Volt AC loads at 20 Amps (or greater).
CAUTION!These outlets are rated at 120 Volt
20 Amp each (up to 80 Amps).The generator is only rated for up to 45.8 Amps. Powering loads that exceed the wattage/amperage capacity of the generator can damage it or cause serious injuries.
Figure 7 — 120 Volt, 20 Amp Duplex Receptacle
Figure 6 — 120/240 Volt AC, 30 Amp Receptacle
4-Wire Cord Set
240V
120V
120V
W (Neutral)
X (Hot)
Y (Hot)
NEMA L14-30
Ground (Green)
BSP5500L Generator
8
DON'T OVERLOAD YOUR
GENERATOR
Capacity
You must make sure your generator can supply enough rated (running) and surge (starting) watts for the items you will power at the same time. Follow these simple steps:
1. Select the items you will power at the same time.
2. Total the rated (running) watts of these items. This is
the amount of power your generator must produce to keep your items running. See Figure 8.
3. Estimate how many surge (starting) watts you will
need. Surge wattage is the short burst of power needed to start electric motor-driven tools or appliances such as a circular saw or refrigerator. Because not all motors start at the same time, total surge watts can be estimated by adding only the item(s) with the highest additional surge watts to the total rated watts from step 2.
Example:
Total Rated (Running) Watts = 3075 Highest Additional Surge Watts = 1800 Total Generator Output Required = 4875
Power Management
To prolong the life of your generator and attached devices, it is important to take care when adding electrical loads to your generator.There should be nothing connected to the generator outlets before starting it's engine.The correct and safe way to manage generator power is to sequentially add loads as follows:
1. With nothing connected to the generator, start the
engine as described in this manual.
2. Plug in and turn on the first load, preferably the largest
load you have.
3. Permit the generator output to stabilize (engine runs
smoothly and attached device operates properly.
4. Plug in and turn on the next load.
5. Again, permit the generator to stabilize.
6. Repeat steps 4 and 5 for each additional load. Never add more loads than the generator capacity.Take
special care to consider surge loads in generator capacity, as described above.
*Wattages listed are approximate only. Check tool or appliance for actual wattage.
Tool or Appliance
Rated (Running)
Watts
Additional Surge
(Starting) Watts Window Air Conditioner
1200 1800
Refrigerator 800 1600 Deep Freezer 500 500 Television 500 ­Light (75 Watts) 75 -
3075 Total
Running Watts
1800 Highest
Surge Watts
Tool or Appliance
Rated*
(Running)
Watts
Additional
Surge
(Starting)
Watts
Essentials
Light Bulb - 75 watt
75
-
Deep Freezer
500
500
Sump Pump
800
1200
Refrigerator/Freezer - 18 Cu. Ft.
800
1600
Water Well Pump - 1/3 HP
1000
2000
Heating/Cooling
Window AC - 10,000 BTU
1200
1800
Window Fan
300
600
Furnace Fan Blower - 1/2 HP
800
1300
Kitchen
Microwave Oven - 1000 Watt
1000
-
Coffee Maker
1500
-
Electric Stove - Single Element
1500
-
Hot Plate
2500
-
Family Room
DVD/CD Player
100
-
VCR
100
-
Stereo Receiver
450
-
Color Television - 27”
500
-
Personal Computer w/17” monitor
800
-
Other
Security System
180
-
AM/FM Clock Radio
300
-
Garage Door Opener - 1/2 HP
480
520
Electric Water Heater - 40 Gallon
4000
-
DIY/Job Site
Quartz Halogen Work Light
1000
-
Airless Sprayer - 1/3 HP
600
1200
Reciprocating Saw
960
960
Electric Drill - 1/2 HP
1000
1000
Circular Saw - 7 1/4”
1500
1500
Miter Saw - 10”
1800
1800
Table Planer - 6”
1800
1800
Table Saw/Radial Arm Saw - 10”
2000
2000
Air Compressor - 1-1/2 HP
2500
2500
Figure 8 - Wattage Reference Chart
BSP5500L Generator
9
SPECIFICATIONS
Maximum Surge Watts . . . . . . . . . . . . . . . . .8,500 watts
Continuous Wattage Capacity . . . . . . . . . . .5,500 watts
Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.0
Rated Maximum Continuous AC Load Current:
At 120 Volts . . . . . . . . . . . . . . . . . . . . . . .45.8 Amps
At 240 Volts . . . . . . . . . . . . . . . . . . . . . . .22.9 Amps
Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1–phase
Rated Frequency . . . . . . . . . . . . . . . . . . . . . . .60 Hertz
Fuel Tank Capacity. . . . . . . . . . . . . . . . . . . 7 U.S. gallons
Shipping Weight . . . . . . . . . . . . . . . . . . . . . . . . . 152 lbs.
GENERAL MAINTENANCE
RECOMMENDATIONS
The Owner/Operator is responsible for making sure that all periodic maintenance tasks are completed on a timely basis; that all discrepancies are corrected; and that the unit is kept clean and properly stored. Never operate a
damaged or defective generator.
Engine Maintenance
See engine owner’s manual for instructions.
CAUTION! Avoid prolonged or repeated skin
contact with used motor oil. Used motor oil has been shown to cause skin cancer in certain laboratory animals.Thoroughly wash exposed areas with soap and water. KEEP OUT OF REACH OF CHILDREN. DON'T POLLUTE. CONSERVE RESOURCES. RETURN USED OIL TO COLLECTION CENTERS.
Generator Maintenance
Generator maintenance consists of keeping the unit clean and dry. Operate and store the unit in a clean dry environment where it will not be exposed to excessive dust, dirt, moisture or any corrosive vapors. Cooling air slots in the generator must not become clogged with snow, leaves or any other foreign material.
NOTE:Do Not use a garden hose to clean generator. Water can enter engine fuel system and cause problems. In addition, if water enters generator through cooling air slots, some of the water will be retained in voids and cracks of the rotor and stator winding insulation.Water and dirt buildup on the generator internal windings will eventually decrease the insulation resistance of these windings.
To Clean the Generator
CAUTION! Never insert any object or tool
through the air cooling slots, even if the engine is not running.
• Use a damp cloth to wipe exterior surfaces clean.
• A soft bristle brush may be used to loosen caked on dirt or oil.
• A vacuum cleaner may be used to pick up loose dirt and debris.
• Low pressure air (not to exceed 25 psi) may be used to blow away dirt. Inspect cooling air slots and opening on generator.These openings must be kept clean and unobstructed.
STORAGE
The generator should be started at least once every seven days and allowed to run at least 30 minutes. If this cannot be done and you must store the unit for more than 30 days, use the following guidelines to prepare it for storage.
Generator Storage
• Clean the generator as outlined in “To Clean the Generator.”
• Check that cooling air slots and openings on generator are open and unobstructed.
CAUTION! Storage covers can be flammable.
Do Not place a storage cover over a hot
generator. Let the unit cool for a sufficient time before placing the cover on the unit.
Engine Storage
See engine owner’s manual for instructions.
Other Storage Tips
• To prevent gum from forming in fuel system or on essential carburetor parts, add fuel stabilizer into fuel tank and fill with fresh gasoline. Run the unit for several minutes to circulate the additive through the carburetor. The unit and fuel can then be stored for up to 24 months. Fuel stabilizer can be purchased locally.
Do Not store gasoline from one season to another unless it has been treated as described above.
• Replace fuel container if it starts to rust. Rust and/or dirt in fuel can cause problems if it's used with this unit.
• Store in clean and dry area.
10
BSP5500L Generator
NOTES
11
BSP5500L Generator
TROUBLESHOOTING
Problem
Cause
Solution
Engine is running, but no AC output is available.
1. Circuit breaker is open.
2. Poor connection or defective cord set.
3. Connected device is bad.
4. Fault in generator.
1. Reset circuit breaker.
2. Check and repair.
3. Connect another device that is in good condition.
4. Contact Briggs and Stratton service facility.
Engine runs good but bogs down when loads are connected.
1. Short circuit in a connected load.
2. Generator is overloaded.
3. Engine speed is too slow.
4. Shorted generator circuit.
1. Disconnect shorted electrical load.
2. See “Don’t Overload the Generator” on page 8.
3. Contact Briggs and Stratton service facility.
4. Contact Briggs and Stratton service facility.
Engine will not start; or starts and runs rough.
1. Rocker switch set to “Off”.
2. Fuel valve is in the “Closed” position.
3. Low oil level.
4. Dirty air cleaner.
5. Out of gasoline.
6. Stale gasoline.
7. Spark plug wire not connected to spark plug.
8. Bad spark plug.
9. Water in gasoline.
10. Overchoking.
11. Excessively rich fuel mixture.
12. Intake valve stuck open or closed.
13. Engine has lost compression.
1. Set switch to “On”.
2. Turn fuel valve to the “Open” position.
3. Fill crankcase to proper level.
4. Clean or replace air cleaner.
5. Fill fuel tank.
6. Drain gas tank and fill with fresh fuel.
7. Connect wire to spark plug.
8. Replace spark plug.
9. Drain gas tank; fill with fresh fuel.
10. Set choke to “Off” position.
11. Contact Briggs and Stratton service facility.
12. Contact Briggs and Stratton service facility.
13. Contact Briggs and Stratton service facility.
Engine shuts down during operation.
1. Out of gasoline.
2. Fault in engine.
1. Fill fuel tank.
2. Contact Briggs and Stratton service facility.
Engine lacks power.
1. Load is too high.
2. Dirty air filter.
1. See “Don’t Overload the Generator” on page 8.
2. Replace air filter.
Engine “hunts” or falters.
1. Choke is opened too soon.
2. Carburetor is running too rich or too lean.
1. Move choke to halfway position till engine runs smoothly.
2. Contact Briggs and Stratton service facility.