This generator is rated in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) and CSA (Canadian Standards
Association) standard C22.2 No. 100-4 (motors and generators).
Thank you for purchasing this quality-built GE generator. We’re pleased that you’ve placed your confidence in the GE
NOT
for
REPRODUCTION
brand. When operated and maintained according to the instructions in the operator’s manual, your generator will
provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with residential
generator systems and how to avoid them. This generator system is designed and intended only for use as an optional
standby system that provides an alternate source of electric power and to serve loads such as heating, refrigeration
systems, and communication systems that, when stopped during any power outage, could cause discomfort or
inconvenience. Save these original instructions for future reference.
This standby generator requires professional installation before use. The installer should follow the
instructions completely.
Where to Find Us
You never have to look far to find support and service for your generator. For quick service when you need
it most fill out the information below and keep your original receipt with this manual. You may contact
Customer Service at 888‑575‑8226 between 8:00 AM and 5:00 PM CT., or click on SERVICE & SUPPORT at
www.standbygeneratorsystems.com, which provides a list of authorized dealers.
For Future Reference
Please fill out the information below and keep with your receipt to assist in unit identification for future purchase issues.
Date of Purchase: _____________________________
Generator
Model Number _____________________________
Model Revision _____________________________
Serial Number _____________________________
2
Table of Contents
NOT
for
REPRODUCTION
Important Safety Instructions .........................................4
important instructions that should be followed during
installation and maintenance of the generator and batteries.
Safety Symbols and Meanings
Fire
Toxic Fumes
Explosive Pressure
Rotating Fan Blade
Electrical ShockExplosion
Hot SurfaceRotating Parts
Chemical BurnAuto Start
Exploding BatteryRotating Belt/Pulley
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings
in this manual, and the tags and decals affixed to the unit
are, therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that it
is safe for you and others. You must also make sure that the
procedure, work method or operating technique that you
choose does not render the generator system unsafe.
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
• Operate this product ONLY outdoors in an area that will not
accumulate deadly exhaust gas.
• Keep exhaust gas away from any windows, doors, ventailation
intakes, soffit vents, crawl spaces, open garage doors or other
openings that can allow exhaust gas to enter inside or be drawn
into a potentially occupied building or structure.
• Carbon monoxide detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Smoke alarms cannot detect carbon
monoxide gas.
Lift HazardRead Manual
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a degree
or level of hazard seriousness. A safety symbol may be used
to represent the type of hazard. The signal word NOTICE is
used to address practices not related to personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
4
WARNING The engine exhaust from this product contains
chemicals known to the State of California to cause cancer, birth
defects, or other reproductive harm.
WARNING Certain components in this product and related
accessories contain chemicals known to the State of California
to cause cancer, birth defects, or other reproductive harm. Wash
hands after handling.
WARNING Storage batteries give off explosive hydrogen gas
NOT
for
REPRODUCTION
during recharging.
Slightest spark will ignite hydrogen and
cause explosion, resulting in death or
serious injury.
Battery electrolyte fluid contains acid and is extremely caustic.
Contact with battery contents could cause severe chemical burns.
A battery presents a risk of electrical shock and high short
circuit current.
• DO NOT dispose of battery in a fire. Recycle battery.
• DO NOT allow any open flame, spark, heat, or lit cigarette during
and for several minutes after charging a battery.
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death or serious injury.
• Install the fuel supply system according to NFPA 37 and other
applicable fuel-gas codes.
• Before placing the generator into service, the fuel system lines
must be properly purged and leak tested.
• After the generator is installed, you should inspect the fuel
system periodically.
• NO leakage is permitted.
• DO NOT operate engine if smell of fuel is present or other
explosive conditions exist.
• DO NOT smoke around the generator. Wipe up any oil spills
immediately. Ensure that no combustible materials are left in the
generator compartment. Keep the area near the generator clean
and free of debris.
WARNING Moving parts could crush and cut.
Starter and other rotating parts
could entangle hands, hair, clothing,
or accessories resulting in serious injury.
• NEVER operate generator without protective housings, covers, or
guards in place.
• DO NOT wear loose clothing, jewelry or anything that could be
caught in the starter or other rotating parts.
• Tie up long hair and remove jewelry.
• Before servicing, remove 15 Amp fuse from control panel and
disconnect Negative (NEG or ‑) battery cable.
WARNING Hazardous Voltage - Contact with power lines could
cause electric shock or burn, resulting in death or
serious injury.
Lifting Hazard / Heavy Object - Could result in
serious injury.
• If lifting or hoisting equipment is used, DO NOT contact any
power lines.
• DO NOT lift or move generator without assistance.
• Use lifting pipes as described in Lifting the Generator.
• DO NOT lift unit by roof as damage to generator will occur.
WARNING Generator produces hazardous voltage.
Failure to properly ground generator could result
in electrocution.
Failure to isolate generator from power utility could result
in death or serious injury to electric utility workers due to
backfeed of electrical energy.
• DO NOT touch bare wires or bare receptacles.
• DO NOT use generator with electrical cords which are worn,
frayed, bare or otherwise damaged.
• DO NOT handle generator or electrical cords while standing in
water, while barefoot, or while hands or feet are wet.
• If you must work around a unit while it is operating, stand on an
insulated dry surface to reduce the risk of a shock hazard.
• DO NOT allow unqualified persons or children to operate or
service generator.
• In case of an accident caused by electrical shock, immediately
shut down the source of electrical power and contact the local
authorities. Avoid direct contact with the victim.
• Despite the safe design of the residential generator, operating
this equipment imprudently, neglecting its maintenance or being
careless could cause possible injury or death.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• Before performing any maintenance on the generator, disconnect
the battery cable indicated by a NEGATIVE, NEG or (‑) first. When
finished, reconnect that cable last.
• After your system is installed, the generator may crank and start
without warning any time there is a power failure. To prevent
possible injury, always set the generator’s system switch to OFF,
open service disconnect switch AND remove the 15 Amp fuse
BEFORE working on the equipment.
5
WARNING Exhaust heat/gases could ignite combustibles
NOT
for
REPRODUCTION
or structures resulting in death or serious injury.
Contact with muffler area could cause burns
resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Exhaust outlet side of weatherproof enclosure must have at least
5 ft. (1.5m) minimum clearance from any structure, shrubs, trees
or any kind of vegetation.
• Standby generator weatherproof enclosure must be at least
5 ft. (1.5m) from windows, doors, any wall opening, shrubs or
vegetation over 12 inches (30.5 cm) in height.
• Standby generator weatherproof enclosure must have a minimum
of 5 ft. (1.5 m) overhead clearance from any structure, overhang,
or trees.
• DO NOT place weatherproof enclosure under a deck or other type
of structure that may confine airflow.
• Use only flexible fuel line provided. Connect provided fuel line to
generator. DO NOT use with or substitute any other flexible
fuel line.
• Smoke detector(s) MUST be installed and maintained indoors
according to the manufacturer’s instructions/recommendations.
Carbon monoxide alarms cannot detect smoke.
• Keep at least minimum distances shown in General Location Guidelines to insure for proper generator cooling and
maintenance clearances.
• Replacement parts must be the same and installed in the same
position as the original parts.
CAUTION Installing the 15A fuse could cause the engine
to start at any time without warning resulting in minor or
moderate injury.
• Observe that the 15 Amp fuse has been removed from the control
panel for shipping.
• DO NOT install this fuse until all plumbing and wiring has been
completed and inspected.
WARNING Hot pressurized coolant could cause serious injury.
• DO NOT open radiator cap when hot.
• Before servicing, allow coolant to cool.
CAUTION Excessively high operating speeds could result in
minor injury.
Excessively low speeds impose a heavy load on generator.
• DO NOT tamper with governed speed. Generator supplies correct
rated frequency and voltage when running at governed speed.
• DO NOT modify generator in any way.
NOTICE Exceeding generators wattage/amperage capacity could
damage generator and/or electrical devices connected to it.
• Start generator and let engine stabilize before connecting
electrical loads.
NOTICE Improper treatment of generator could damage it and
shorten its life.
• Use generator only for intended uses.
• If you have questions about intended use, contact your
authorized dealer.
• Operate generator only on level surfaces.
• Adequate, unobstructed flow of cooling and ventilating air is
critical to correct generator operation.
• The access panels/door must be installed whenever the unit
is running.
• DO NOT expose generator to excessive moisture, dust, dirt, or
corrosive vapors.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• DO NOT start engine with air cleaner or air cleaner cover removed.
• DO NOT insert any objects through cooling slots.
• DO NOT use the generator or any of its parts as a step. Stepping
on the unit could cause stress and break parts. This may result in
dangerous operating conditions from leaking exhaust gases, fuel
leakage, oil leakage, etc.
• If connected devices overheat, turn them off,disconnect them
from generator, and determine the cause of overheating.
• Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively;
-unit makes unusual noises.
6
Installation
NOT
for
REPRODUCTION
This product is only for use as an optional generator system
which provides an alternate source of electric power and
to serve loads such as heating, refrigeration systems, and
communication systems that, when stopped during any
power outage, could cause discomfort or inconvenience.
NOTICE This product does NOT qualify for either an
emergency standby or legally required standby system as
defined by NFPA 70 (NEC).
• Emergency generator systems are intended to
automatically supply illumination, power, or both,
to designated areas and equipment in the event of
failure of the normal supply. Emergency systems may
also provide power for such functions as ventilation
where essential to maintain life, where current
interruption of the normal supply would produce
serious life safety or health hazards.
• Legally Required standby generator systems are
intended to automatically supply power to selected
loads in the event of failure of the normal source
which could create hazards or hamper rescue or firefighting operations.
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the
right to change, alter, or otherwise improve the product and
this document at any time without prior notice.
Only current licensed electrical and plumbing professionals
should attempt generator system installations. Installations
must strictly comply with all applicable codes, industry
standards, laws and regulations.
Owner Responsibilities
• Read and follow the instructions given in the
operator’s manual.
• Follow a regular schedule in maintaining, caring
for and using your generator, as specified in the
operator’s manual.
Installing Dealer/Contractor Responsibilities
• Read and observe the safety rules.
• Install only an UL approved transfer switch that is
compatible with the generator.
• Read and follow the instructions given in this
installation and start-up manual.
• Carbon monoxide detector(s) MUST be installed and
maintained indoors according to the manufacturer’s
instructions/ recommendations. Smoke alarms
cannot detect carbon monoxide gas.
• Smoke detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Carbon monoxide alarms cannot
detect smoke.
7
Unpacking Precautions
NOT
for
REPRODUCTION
The unit is shipped ready for installation on a prepared
reinforced cement slab or engineered base. Avoid
damage from dropping, bumping, collision, etc. Store and
unpack carton with the proper side up, as noted on the
shipping carton.
Delivery Inspection
After removing the carton, carefully inspect the generator for
any damage that may have occurred during shipment.
If loss or damage is noted at time of delivery, have the
person(s) making delivery note all damage on the freight bill
and affix his signature under the consignor’s memo of loss or
damage. If loss or damage is noted after delivery, separate
the damaged materials and contact the carrier for claim
procedures. Missing or damaged parts are not warranted.
Shipment Contents
The generator system is supplied with:
• Fully-serviced coolant system
• Fully-serviced oil/lubricating system
• Flexible fuel hook-up
• Installation and start-up manual
• Operator’s manual
• Spare access door keys
• Spare 15 Amp ATO-type fuse
• Ten-pin control panel connector
• Touch up paint
• Remote wireless monitor
• Antenna
To be supplied by Installer / owner:
• Carbon monoxide detector(s)
• Smoke detector(s)
• Starting battery
• Reinforced concrete mounting pad
• Connecting wire and conduit
• Fuel supply valves/plumbing
• Various specialty tools/equipment
• Two (2) AA batteries for remote wireless monitor
8
Installation Checklist ‑ GE Home Generator Systems
NOT
for
REPRODUCTION
Proper installation of the home generator requires the completion of the following tasks:
Carbon Monoxide (CO) Detector/ Smoke Detector
Carbon Monoxide (CO) detector(s) installed and in working
order.
Smoke detector(s) installed and in working order.
Placement
Required permits have been obtained.
Generator placed in an area free from Carbon Monoxide
(CO) buildup. See Placement of Standby Generator to
Reduce the Risk of Carbon Monoxide Poisoning.
Generator placed in an area compliant to NFPA 37. See
Placement of Standby Generator to Reduce the Risk of
Fire.
Generator placed in an area free from water damage. See
Other General Location Guidelines.
Generator placed in an area free from utility and other
home systems. See Other General Location Guidelines.
Generator placed in a debris free zone. See Other General
Location Guidelines.
Generator placed on flat ground with provisions for water
drainage.See Other General Location Guidelines.
Fuel
Generator is connected to fuel source with steel flexible
fuel line, has no fuel leaks and conforms to local codes. See
The Gaseous Fuel System.
Proper fuel pressure has been measured with all gas
appliances operating. See The Gaseous Fuel System.
Fuel system has been configured for the proper fuel
supply: Natural gas (NG) or liquefied petroleum ( LP). See
Fuel pressure at fuel inlet port with generator on and at
full load and all gas appliances turned on and operating
____________________.
Electrical
Generator neutral is connected to Automatic Transfer
Switch. See Generator AC Connection System.
Generator is grounded. See Grounding the Generator and
NFPA 70,NEC.
Generator is connected to the transfer switch with the
specified wiring. See Utility Circuit Connection and
Transfer Switch Communication.
Generator is connected to the transfer switch with the
specified wiring. #18AWG twisted pair wiring from the
generator control panel to the transfer switch is installed
in a separate conduit from high voltage wires unless
the insulation rating on all wiring is rated for 600V See
Transfer Switch Communication.
Dipswitches in most transfer switches must be set to
correspond to the wattage of the generator. See Transfer
Switch Operator/Installation Manual.
Operation
Correct battery type is installed and fully charged. See
Final Installation Considerations.
Generator engine oil level is at full mark. See Final
Installation Considerations.
Circuit breaker is in the ON position.
Utility was shut off to test the operation of generator and
transfer switch. Note any fault codes and make corrections
as required.
AC Voltage Output___________________________.
Frequency Output___________________________.
Before installing the generator, consult with the owner and
convey the following requirements, which must be satisfied
before the installation is complete.
There are two equally important safety concerns in regards
to carbon monoxide poisoning and fire. There are also
several general location guidelines that must be met before
the installation is considered complete.
Exhaust Side of Generator
A
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
• Operate this product ONLY outdoors in an area that will not
accumulate deadly exhaust gas.
• Keep exhaust gas away from any windows, doors, ventailation
intakes, soffit vents, crawl spaces, open garage doors or other
openings that can allow exhaust gas to enter inside or be drawn
into a potentially occupied building or structure.
• Carbon monoxide detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Smoke alarms cannot detect carbon
monoxide gas.
B
• Exhaust outlet side of weatherproof enclosure
A
• Weatherproof enclosure opposite exhaust side
B
10
A
Placement of Standby Generator to REDUCE THE RISK OF CARBON MONOXIDE POISONING
NOT
for
REPRODUCTION
The figure below displays POTENTIAL points of entry for Carbon Monoxide Gas.
BBC
All fossil fuel burning equipment, such as standby
generators, contains carbon monoxide (CO) gas in the engine
exhaust. CO gas is odorless, colorless and tasteless and is
unlikely to be noticed until a person is overcome. CO gas can
kill you so it is required that the following is included as part
of the installation:
• Install generator outdoors in an area that will not
accumulate deadly exhaust gas.
• DO NOT install generator where exhaust gas could
accumulate and enter inside or be drawn into a
potentially occupied building or structure.
• By law it is required in many states to have a Carbon
Monoxide (CO) detector in operating condition in
homes and other structures occupied by people.
Carbon monoxide detector(s) (A) MUST be
installed and maintained indoors according to the
manufacturer’s instructions / recommendations.
A CO monitor is an electric device that detects
hazardous levels of CO. When there is a buildup of
CO, the monitor will alert the occupants by flashing
visual indicator light and alarm. Smoke alarms cannot
detect CO gas.
• Nearby structures may be exposed to the engine
exhaust from your standby generator and must be
considered when installing your standby generator.
A
• Ensure exhaust gas is kept away from:
B overhead doors
B
C doors
C
D windows (not shown)
D
E other openings that can allow exhaust gas to enter
E
inside or be drawn into a potenially occupied building
or structure.
A
11
• Direct the standby generator exhaust away from or
NOT
for
REPRODUCTION
parallel to the building or structure. DO NOT direct the
generator exhaust towards a potentially occupied
building, structure, windows, doors, ventilation
intakes, soffit vents, crawl spaces, open garage
doors or other openings where exhaust gas could
accumulate and enter inside or be drawn into a
potentially occupied building or structure.
• DO NOT place standby generator in any area where
leaves or debris normally accumulates. Position
standby generator in an area where winds will carry
the exhaust gas away from any potentially occupied
building or structure.
Other General Location Guidelines
• Place the standby generator in a prepared location
that is flat and has provisions for water drainage.
• Install the standby generator in a location where
sump pump discharge, rain gutter down spouts, roof
run-off, landscape irrigation, or water sprinklers will
not flood the unit or spray the enclosure and enter
any air inlet or outlet openings.
12
• Install the standby generator where it will not affect or
obstruct any services (including covered, concealed
and underground), such as telephone, electric, fuel
(natural gas / LPG vapor), irrigation, air conditioning,
cable, septic, sewer, well and so forth.
• Install the standby generator where leaves, grass,
snow, etc will not obstruct air inlet and outlet
openings. If prevailing winds will cause blowing or
drifting, you may need to construct a windbreak to
protect the unit.
Placement of Standby Generator to REDUCE THE RISK OF FIRE
NOT
for
REPRODUCTION
The National Fire Protection Association (NFPA) standard
NFPA 37 establishes criteria for minimizing the hazard
of fire during the installation and operation of stationary
combustion engines. NFPA 37 limits the spacing of an
enclosed generator from openings in walls, structures and
combustible materials outside the enclosure.
The placement requirements provided are based on
compliance to NFPA 37 2010 section 4.1.4.
WARNING Exhaust heat/gases could ignite combustibles or
structures resulting in death or serious injury.
• Exhaust outlet side of weatherproof enclosure must have at least
5 ft (1.5 m) minimum clearance from any structure, shrubs, trees
or any kind of vegetation.
• Standby generator weatherproof enclosure must be at least
5 ft (1.5 m) from windows, doors, any wall opening, shrubs or
vegetation over 12 inches (30.5 cm) in height.
• Standby generator weatherproof enclosure must have a minimum
of 5 feet (1.5 m) overhead clearance from any structure, overhang
or trees.
• DO NOT place weatherproof enclosure under a deck or other type
of structure that may confine airflow.
• USE ONLY flexible steel fuel line provided. Connect provided fuel
line to generator, DO NOT use with or substitute any other flexible
fuel line.
• Smoke detector(s) MUST be installed and maintained indoors
according to the manufacturer’s instructions/ recommendations.
Carbon monoxide alarms cannot detect smoke.
• DO NOT place weatherproof enclosure in manner other than
shown in illustrations.
Examples of standby generator locations to reduce the
risk of fire:
Legend for Generator Locations to reduce the risk of fire.
Standby weatherproof enclosure must be at least 5 ft
A
(1.5 m) from windows, doors, any wall opening, shrubs
or vegetation over 12 inches (30.5 cm) in height.
Exhaust outlet side of weatherproof enclosure must
B
have at least 5 ft (1.5 m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
Standby weatherproof enclosure must have a
C
minimum of 5 feet (1.5 m) overhead clearance from
any structure, overhang or trees.
NOTICE DO NOT place weatherproof enclosure under a deck
or other type of covered structure that may confine airflow.
Vertical Clearances
A
C
A
A
A
13
Typical Installations
NOT
for
REPRODUCTION
NOTICE The figures below show the minimum installation distances allowed to structures and items listed in legend.
Exhaust
5 ft (1.5 m) min.
A
5 ft (1.5 m) min.5 ft (1.5 m) min.
Standby
5 ft (1.5 m) min.
B
A
B
5 ft (1.5 m) min.
Exhaust
5 ft (1.5 m) min.
AA
Standby
A
5 ft (1.5 m) min.
Exhaust
A
Legend for Generator Locations to reduce the risk of fire.
Standby weatherproof enclosure must be at least 5 ft
A
(1.5 m) from windows, doors, any wall opening, shrubs
or vegetation over 12 inches (30.5 cm) in height.
Exhaust outlet side of weatherproof enclosure must
B
have at least 5 ft (1.5 m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
Standby
B
5 ft (1.5 m) min.
Standby
Exhaust
5 ft (1.5 m) min.
A
B
Standby weatherproof enclosure must have a
C
minimum of 5 feet (1.5 m) overhead clearance from
any structure, overhang or trees.
NOTICE DO NOT place weatherproof enclosure under a deck
or other type of covered structure that may confine airflow.
14
Concrete Slab
NOT
for
REPRODUCTION
At the appropriate location, construct a concrete slab:
• 28 day compression strength of 3000 psi (200 MPa)
• Minimum 5” (13cm) thick
• Minimum 6” (15cm) wider than enclosure on all sides
(shown as D in figure)*
• Strengthen slab with No. 6 reinforcing bars (on
12” (30.5cm) centers) or 8 ga. steel wire fabric (6”
(15cm) centers).
Avoid placing reinforcement in entrance stub-up area (shown
as (B ).
B
Attach unit to slab at four corner locations (A) with minimum
5/16” diameter (8mm) (per local requirements) masonry
anchor bolts long enough to secure the unit.
The fuel inlet location (C) ,the concrete slab, and the
exhaust outlet (E) are shown for reference.
• The standby generator enclosure F measures 96”
(234 cm) X 37” (94 cm).
D
A
C
E
D
F
129.5cm
92”
233.7cm
51”
14-3/4”
37.5cm
6”
15.2cm
7-1/2”
19cm
34-1/4”
87cm
5”
12.7cm
A
B
C
F
Electrical and Fuel Inlet Locations
A through-slab power cable stub-up is preferred (see
figure above). If stub-up’s are not used, (F) indicates the
recommended location for punching holes for attaching
power conduit. The 1 inch N.P.T. fuel inlet connector (C) is
shown for reference.
F
C
E
A
A Holes located in base to anchor to pad
B
B Stub up Area
C
C Fuel Inlet
D
D Concrete slab
D Exhaust Outlet
E
D Standby Generator Enclosure
F
F
D
C
15
Lifting the Generator
NOT
for
REPRODUCTION
The generator weighs approximately 1,500 pounds (682 kg).
Proper tools, equipment and qualified personnel should be
used in all phases of handling and moving the generator.
WARNING Hazardous Voltage - Contact with power lines could
cause electric shock or burn, resulting in death or
serious injury.
Lifting Hazard / Heavy Object - Could result in
serious injury.
• If lifting or hoisting equipment is used, DO NOT contact any
power lines.
• DO NOT lift or move generator without assistance.
• Use lifting pipes as described in Lifting the Generator.
• DO NOT lift unit by roof as damage to generator will occur.
Remove circuit breaker box bottom plate prior to positioning
generator. Two 60” lengths of 2” Schedule 40 pipe (A),
supplied by the installer, are required to lift the generator
onto cement pad. Insert pipes through the lifting holes (B)
located near the unit’s base.
Use a spreader bar to ensure that the chains, straps or
cables DO NOT touch the generator’s roof. Retouch any
chipped paint with supplied touch-up paint.
A
B
A
B
16
Access Ports
NOT
for
REPRODUCTION
The generator is equipped with an enclosure that has
several access doors, as shown. The doors are named for a
significant component located behind them, as follows:
A
A - Fuel Inlet port (shown for reference)
B
B - Control Panel door (may be two doors)
C - Exhaust opening (shown for reference)
C
D - Coolant/Oil Fill door
D
- Battery door
E
- Muffler door
F
WARNING Contact with muffler area could cause burns
resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
The Coolant Fill, Battery and Control Panel doors must be
installed whenever the unit is running to assure proper
cooling, reduce noise and for added safety. The enclosure
also includes muffler and radiator access panels, used for
cleaning those components. Those panels should remain
closed at all other times.
Each generator is shipped with a set of identical keys. These
keys fit the locks that secure the access ports.
To open access door:
1. Insert key into lock of access door handle and turn
key one quarter turn counterclockwise.
2. Grasp door’s handle and turn one quarter turn
counterclockwise to open. Remove key.
3. Coolant Fill door is unlocked in the same manner. It
can be used for adding coolant or oil.
To close access door:
1. Close door and turn door’s handle one quarter
turn clockwise.
2. Insert key into lock of door handle and turn key one
quarter turn clockwise. Remove key.
Additional force may be required to fully close and lock
the doors because they create a pressurized seal for the
generator enclosure.
C
A
B
F
D
E
17
The Gaseous Fuel System
NOT
for
REPRODUCTION
The information below is provided to assist gaseous fuel
system technicians in planning installations. In no way
should this information be interpreted to conflict with
applicable fuel gas codes. Consult with your local fuel
supplier or Fire Marshall if questions or problems arise.
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death or serious injury.
• LP gas is heavier than air and will settle in low areas.
• Natural gas is lighter than air and will collect in high areas.
• The slightest spark could ignite these fuels and cause an explosion.
• DO NOT light a cigarette or smoke.
TO THE INSTALLER: Consult with the generator owner(s) and
convey any technical considerations that might affect their
installation plans before applying these general guidelines.
NOTICE The supplied flexible gaseous pipe is not to be installed
underground or in contact with the ground.
• The entire flexible gaseous pipe must be visible for periodic
inspection and must not be concealed within nor contact nor run
through any wall, floor, or partition.
The following general rules apply to gaseous fuel
system piping:
• The piping should be of a material that conforms
to federal and local codes, rigidly mounted and
protected against vibration.
• Piping should be protected from physical damage
where it passes through flower beds, shrub beds, and
other cultivated areas where damage could occur.
• Install the flexible, gaseous hose (B) (supplied)
between the generator Fuel Inlet port (A) and rigid
piping to prevent thermal expansion or contraction
from causing excessive stress on the piping material.
• A union (C) or flanged connection shall be provided
downstream from the shut-off valve to permit
removal of fuel system components.
• A manometer port should be provided (D) . A digital
manometer, P/N 19495, is available at your Briggs &
Stratton service center. When the initial test runs are
complete, the manometer is removed and the port
is plugged. The manometer port permits temporary
installation of a manometer to ensure that the
engine receives the correct fuel pressure to operate
efficiently throughout its operating range.
• Where the formation of hydrates or ice is known to
18
occur, piping should be protected against freezing.
The termination of hard piping should include a
sediment trap (E) where condensate is not likely
to freeze.
C
E
B
A
D
• A minimum of one accessible, approved manual
shutoff valve (F) shall be installed in the fuel supply
line within 6 ft (1.8 m) of the generator.
• A minimum 10 ft. (3 m) section of gas pipe between
the primary fuel regulator and the generator fuel inlet
connection (acts as accumulator for high block loads).
• A manual fuel shut-off valve located in the interior of
the building.
• Where local conditions include earthquake,
tornado, unstable ground, or flood hazards, special
consideration shall be given to increase strength and
flexibility of piping supports and connections.
• Piping must be of the correct size to maintain the
required supply pressures and volume flow under
varying generator load conditions with all gas
appliances connected to the fuel system turned on
and operating.
• Use a pipe sealant or joint compound approved for
use with NG/LPG on all threaded fittings to reduce the
possibility of leakage.
• Installed piping must be properly purged and
leak tested, in accordance with applicable codes
and standards.
F
E
A Generator Fuel Inlet
A
B Flexible Fuel Hose
B
C Union Fitting
C
D Manometer Test Port
D
E Sediment Trap
E
F Manual Shut-off Valve
F
F
D
C
A
B
Fuel Pipe Sizing
NOT
for
REPRODUCTION
There are numerous on-line or otherwise-published
references for fuel pipe sizing. For example, NFPA 54 National Fuel Gas Code, 2006 (Item #: 320-6031-06) is a
common resource. The installer should consider the specific
gravity of gas and compensate for a nominal amount of
restriction from bends, fittings, etc. If an unusual number of
fittings, bends, or other restrictions are used, refer to federal
and local codes for guidance.
Fuel Conversion
The unit is shipped from the factory calibrated for NG
operation. To convert the engine from NG to LP vapor, follow
these steps:
1. Set generator’s circuit breaker to its OFF position.
2. Press and hold the control board OFF button.
3. Remove 15 Amp fuse from control board.
4. Locate the fuel selector switch (A) . Using a 6 mm
Allen wrench, turn the selector switch to either LP or
NG.
5. After all servicing has been completed, replace fuses
in transfer switch, replace 15 Amp fuse in control
board, set circuit breaker ON and press and hold
control board AUTO button.
A
A
Fuel Pressure
Both LP vapor and natural gas fuel supply pressure at the
generator’s fuel inlet port should be between 7 to 11 inches
of water (in. W.C.) at full load with all gas appliances turned on
and operating.
Power Loss
Air density is less at high altitudes, resulting in less available
engine power. Specifically, engine power will decrease 3.5% for
each 1,000 feet (300 meters) above sea level and 1% for each
10° F (5.6°C) above 77°F (25°C). Make sure you and your installer
consider these factors when determining total generator load.
19
Fuel Consumption
NOT
for
REPRODUCTION
Estimated fuel supply requirements at half and full load for
natural gas and LP vapor fuels are shown here.
* LHV (Low Heat Value) is the more realistic rating.
** Gross heat value does not consider heat lost in the form of water during
combustion.
*** Density is given in “Cubic Feet of Gas per Gallon of Liquid”.
† Weight is given in “Pounds per Gallon of Liquid”.
LP VaporNatural
Gas
GasGas
-44
-44
83,340
91,547
2,500
110+
97
-259
-259
63,310
1,000
110+
20
System Connectors
NOT
for
REPRODUCTION
Low Voltage connections to signal fault contacts, transfer switch communication and auxiliary 12VDC power are made via a
field connection terminal block in control board area. Compare this illustration with your generator to familiarize yourself with
the location of these connections.
F
E
[
[
[
C
B
A ‑ Fuse Block — Used to connect utility 240 VAC from
A
fuse block in ATS to the control board. Connect only
one wire per terminal.
B
B ‑ Fault Contacts — Use NO, COM and NC to hook
up a siren, light, etc. to alert you in case of a fault.
Contacts reverse state (NO goes to NC and vice
versa) upon a fault condition.
C
C ‑ Transfer Switch Communication (TxRx and TxRx
GND) — Connect to transfer switch control board for
communication interface using 18AWG twisted pair
wire. (Not applicable with all transfer switches.)
D
A
D ‑ +LED and GND Connection — Not required for
D
optional wireless monitor. Available for optional
hardwired remote system status panel accessory,
#6154.
E ‑ Eight Pin Terminal Block — Used to connect signal
E
wires to the control board. Connect only one wire per
terminal.
F
F ‑ Power Connection (Line 1 and Line 2) — Power
connection to transfer switch.
G ‑ Neutral and/or Ground Connection — Connect to
transfer switch neutral and ground
GND
F
• For power output connection, use 300 volt, 167 °F194 °F (75 °C-90 °C) wire. See chart on right for proper
wire size.
• For Utility Circuit connection use #14 AWG minimum
300 volt, 167 °F-194 °F (75 °C-90 °C) wire.
• For transfer switch communication use #18 AWG
twisted pair conductors, no greater than 200 ft (60 m)
in length, 300 volt, 167 °F-194 °F (75 °C-90 °C) wire.
• When connecting to the ten-pin connector plug,
fasten only one wire to each connector screw.
• Torque connector plug screws to 7 in-lb (7.9 Newton meter).
* SeriesVoltageRated AmpsWire Size
Single Phase120/2401462/0
*Refer to Generator Data Tag to determine series of generator.
21
Generator AC Connection System
NG
V
22
NOT
for
REPRODUCTION
A single-phase, three-wire AC connection system is used
in the generator. The stator assembly consists of a pair of
stationary windings with two leads brought out of each
winding. The junction of leads 22 and 33 forms the neutral
lead, as shown schematically and as wiring diagram. A
complete schematic and wiring diagram can be found later
in this manual.
Neutral is not bonded to ground at generator.
When making connections, obey wire type and torque
specifications shown on the circuit breaker and neutral/
ground connector.
Power Winding
Neutral
11
33
44
44
Circuit
Breaker
11
Neutral
120 V
120
240 V
Ground
Neutral
Line 1
To Transfer Switch
Control
Board
10 A
240 VAC
To Transfer Switch
Utility Fuse Connection
Line 2Ground
Optional
Water
Heater
10 A
22
Grounding the Generator
NOT
for
REPRODUCTION
Ground the generator per applicable codes, standards and
regulations. There are two generator GND lug locations.
The one inside the generator junction box next to the circuit
breaker (B) is the primary lug and should suffice for most
applications. The second generator GND lug is located
on the frame below the generator circuit breaker cover
and should ONLY be used for a ground rod located at the
generator, if required by local codes.
A
Utility Circuit Connection
A
GND
“240V Utility” leads must be routed in conduit. The
“240V Utility” leads deliver power to the generator’s circuit
board and optional water heater. This power also charges
the battery. When power on these leads is lost, the generator
will start.
Using installer-supplied #14 AWG minimum 300 volt
75°C-90°C wire, connect each ten-amp fuse terminal in the
alternator junction box to the two-amp fuse terminals in the
automatic transfer switch.
Service Code Detection System
The generator may have to run for long periods of time with
no operator present. For that reason, the system is equipped
with sensors that automatically shut down the generator
in the event of potentially damaging conditions, such as
low oil pressure, high temperature, over speed, and other
conditions. Refer to Service Code Detection System in the
operator’s manual for more detailed information.
When making connections, obey wire type and torque
specifications printed on the circuit breaker and neutral/
ground connector.
23
System Control Panel
NOT
for
REPRODUCTION
The generator control panel, located inside the generator
housing, is shown below.
A
B
C
F
E
D
Brief descriptions of the controls used during installation are:
A ‑ Menu/Programming Navigation Buttons — See
A
Menu section for details
B
B ‑ USB Port — Authorized Dealer Service Use Only
C - Generator Operation Control Buttons —
C
•“AUTO” Normal operating position. Press and hold
button to put unit into Automatic mode. If a utility
power outage is sensed, the system will start the
generator. When utility power is restored, auto lets the
engine stabilize internal temperatures, shuts o the
generator, and waits for the next utility outage.
•“OFF” Turns o running generator, prevents unit from
starting, and resets any detected faults.
OFF must be pressed and held for more than 5
seconds in order to reset service codes.
•“MANUAL” Used to manually start the generator.
“AUTO” LED — LED will light when unit is placed into
Auto mode. LED will blink if exercise cycle is not set or
set to OFF.
D – 15 Amp Fuse — Protects the home generator DC
D
control circuits. If the fuse has ‘blown’ (melted open)
or was removed, the engine cannot crank or start.
Replace the fuse using only an identical ATO 15A
fuse. One spare fuse is supplied with the unit.
E
E ‑ Cover — This protective cover must be opened to
access the fuse and the USB port.
F
F ‑ Digital Display — Displays generator mode, menu
options, service codes, and service engine indicators
More information may be found in Controls in the
operator’s manual.
24
Menu
NOT
for
REPRODUCTION
The following chart shows the icons for the buttons that control the system control panel.
MENU
ESCAPE (EXIT)
RIGHT ARROW
LEFT ARROW
MANUAL MODE
OFF
AUTOMATIC MODE
ENTER THE MENU (VIEW SETTINGS)
PRESS TO CONFIRM SELECTION WHEN PROGRAMMING.
RETURN TO LAST MENU ITEM
TOGGLE THROUGH MENU OPTIONS
SETTING SYSTEM PARAMETERS
TOGGLE THROUGH MENU OPTIONS
SETTING SYSTEM PARAMETERS
USED TO MANUALLY START THE Generator. PRESS AND HOLD BUTTON TO
START THE Generator.
TURNS OFF RUNNING Generator, PREVENTS UNIT FROM STARTING, AND
RESETS ANY DETECTED FAULTS.
NORMAL OPERATING POSITION. PRESS AND HOLD BUTTON TO PUT UNIT
INTO AUTOMATIC MODE. IF A UTILITY POWER OUTAGE IS SENSED, THE
SYSTEM WILL START THE Generator. WHEN UTILITY POWER IS RESTORED,
AUTO LETS THE ENGINE STABILIZE INTERNAL TEMPERATURES, SHUTS OFF
THE Generator, AND WAITS FOR THE NEXT UTILITY POWER OUTAGE.
The following chart describes key sequences for accessing different programming modes;
GENERAL
SET‑UP
ADVANCED
SETTINGS
WIRELESS
LINK MODE
PRESS AND HOLD [ARROW LEFT AND ARROW RIGHT]
FOR THREE SECONDS TO ENTER THE PROGRAM MODE.
PRESS AND HOLD [ARROW LEFT, ARROW RIGHT AND
ESC] FOR THREE SECONDS TO ENTER THE ADVANCED
SETTINGS MODE.
PRESS AND HOLD [MENU AND ESC] FOR THREE SECONDS TO ENTER THE WIRELESS LINKING MODE.
25
General Set Up Screen
NOT
for
REPRODUCTION
For general set up, press and hold the left arrow and right arrow for 3 seconds. Follow the prompts as outlined below.
NOTE: Date and Time were set at the factory and stored in the control panel memory. The Exercise Cycle was
also set at the factory. The default exercise cycle occurs on Tuesdays, at 2:00 P.M. Central Standard Time.
To updated or change these settings, follow the steps below.
SET DATE
or
SET TIME
or
SET EXERCISE
CYCLE
or
YEAR
FLASHING
or
HOURS
FLASHING
or
OFF
DAY OF WEEK
FLASHING
MONTH
FLASHING
or
MIN
FLASHING
or
If set to OFF, display will read: EXERCISE CYCLE OFF
HOURS
FLASHING
DAY##
FLASHING
or
AM/PM
FLASHING
or
MIN
FLASHING
AM/PM
FLASHING
or
EVENT
LOG
26
or
Display will scroll last service code event, date, time, and
temperature of when the event occured.
or
or
IF DURING PROGRAMMING NO BUTTONS ARE PRESSED FOR 30 SECONDS,
THE CONTROL PANEL WILL AUTO MATICALLY EXIT THE PROGRAM MODE.
or
or
Control Panel Prompts
AUTOMATIC MODE
GENERATOR ON
(When Generator Running - Auto Mode)
GENERATOR READY or SERVICE CODE DESCRIPTION
(When Generator NOT Running - Auto Mode)
NOT
for
REPRODUCTION
Automatic Mode
In Automatic Mode, the display screen will display via
scrolling text:
• Generator READY - if the unit is in standby and utility
power is present.
• Generator ON - if the unit is running and utility power
is not present.
• SERVICE CODE - if a system fault has been detected.
General System Parameters
To view general system parameters, press the MENU button.
The following will scroll across the digital display and then
move to the next item:
• Run time
• Date
• Time
• Exercise Cycle date and start time
The user can press the LEFT ARROW or RIGHT ARROW at any
time to move to the next item.
The user can press ESCAPE to go back to Generator READY.
If no user inputs are made for 10 seconds after all the items
have been displayed, the control board will reset to
Generator READY.
AUTOMATIC MODE
GENERATOR READY or SERVICE CODE DESCRIPTION
(When Generator NOT Running - Auto Mode)
GENERATOR ON
(When Generator Running - Auto Mode)
(MENU)
RUN TIME
or
DATE
or
TIME
or
EXERCISE CYCLE
27
Advanced Settings Screen
NOT
for
REPRODUCTION
Advanced setting parameters are preset at the factory for a typical installation. To view Advanced Settings items and/or to
change items, follow the instructions listed below.
NOTICE Advanced settings are critical to the operation of the unit. Careful consideration should be taken when working
in the Advanced Settings menu. Exercise caution when selecting and verifying parameters for the generator and region
where the generator is being operated. Confirm all settings before operating the generator for the first time.
For advanced menu items, press and hold the left arrow, right arrow, and escape key for 3 seconds. Follow the
prompts as outlined below.
NOTICE In the Advanced Setting menu, a three button access code (left arrow, right arrow, and escape key must
be pressed once to enter the menu and again to change any setting. After each confirmation of a setting, the selection will
display solid for 2 seconds before moving to the next program item.
kW
or
Hz
or
PHASE
or
kW
FLASHING
or
50/60 Hz
FLASHING
or
SINGLE
or
THREE
FLASHING
or
Not applicable
with these
models
28
VOLTS
or
E-Governor
Check
or
SOFTWARE
Version Displayed
VOLT S
FLASHING
or
Stepper Motor
will sweep through throttle
range for dealer
visual verication
or
Final Installation Considerations
NOT
for
REPRODUCTION
Engine Oil
NOTICE Any attempt to crank or start the engine before it has
been properly serviced with the recommended coolant or oil will
result in equipment failure.
• Refer to Maintenance in the operator’s manual for coolant and oil
fill information.
• Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
The engine is shipped from the factory pre-run and filled
with non-synthetic oil (API SL 10W-30). This allows for system
operation in a wide range of temperature and climate
conditions. Before starting the engine, check oil level and
ensure that engine is serviced as described in the operator’s
manual.
Coolant System
This engine is shipped from the factory filled with a 50-50 mix
of automotive (Ethylene glycol) anti-freeze and water. This
will provide optimum year round protection against freezing,
boiling and corrosion. The coolant system incorporates an
optional water heater that operates with a fixed thermostat
set at 100°F - 120°F (39°C - 49°C) AND utility power is present
at the transfer switch. Before starting the engine, check
coolant level as described in the Maintenance section.
Battery
The installer must supply and install a valve-regulated
rechargeable starting battery. The starting battery MUST
conform to the specifications shown in this chart.
Battery Specifications
Volts12 Volt DC
Amps (MIN)650 CCA (cold cranking amps)
TypeValve Regulated Lead Acid (VRLA)
Terminal Hardware Post
Dimensions (MAX):
Width7.5 inches (191mm)
Length11.25 inches (286mm)
Height10.0 inches (254mm)
Install the battery as described in Servicing the Battery in
the Maintenance section of the operator’s manual. Always
make sure the NEGATIVE cable is connected last.
WARNING Battery posts, terminals and related accessories
contain lead and lead compounds, chemicals known to the State
of California to cause cancer and reproductive harm. Wash hands
after handling.
Fuel Supply System
Ensure that all fuel pipe connections are tight, secure and
without leaks.
Ensure that all gas line shutoff valves are OPEN and that
adequate fuel pressure is available whenever automatic
operation is desired.
29
Initial Start‑up (No Load)
NOT
for
REPRODUCTION
Before operating the generator or placing it into service,
inspect the entire installation carefully. Then begin testing the
system without any electrical loads connected, as follows:
Unit has been set-up for NG or LP vapor operation at the
factory. Fuel conversion, if needed, must be completed
prior to performing these steps. See Fuel Conversion, later in
this manual.
1. Connect an accurate AC voltmeter and a frequency
meter to check generator output at load side of
circuit breaker.
2. Set generator’s circuit breaker to its ON
(closed) position.
4. Install 15 Amp fuse in control board.
5. Press and hold MANUAL button on control board for 3
seconds. Engine will start.
When the generator is started for the very first time,
it will require that air in the gaseous fuel lines be
purged. This may take a few minutes.
6. Listen for unusual noises, vibration or other
indications of abnormal operation. Check for oil or
coolant leaks while engine runs.
7. Let engine warm up for about five minutes to allow
internal temperatures to stabilize.
8. No-load voltage should be 239 - 244 Volts, frequency
should be 59.8 - 60.2 Hz.
If AC voltage is outside these ranges, perform the
generator adjustment, Steps 11 and 12 below.
9. Check generator output between one of the generator
connection lugs and the neutral lug, then between the
other generator connection lug and the neutral lug. In
both cases, voltage reading should be 117 - 123 Volts.
DO NOT proceed until you are certain that generator
AC voltage is correct and within the stated limits.
Generator frequency is fixed and not adjustable.
10. If voltage and frequency values are correct, proceed
to step 13.
11. Connect voltmeter as described in step 1 above.
12. While observing voltmeter, adjust alternator voltage
control (A) for 240 volts. See (G) on previous page. DO
NOT adjust either of the other alternator controls.
13. Push and hold OFF BUTTON on control board until
engine stops.