Briggs & Stratton 076000NG, 076000LP Service & Troubleshooting Manual

Home Generator System Manual 278382GS Rev A 6/08
SERVICE & TROUBLESHOOTING MANUAL
HOME GENERATOR SYSTEM - 30kW
BRIGGS & STRATTON
FORWARD
This manual was written to assist authorized technicians and service personnel with the repair and maintenance procedures for Briggs & Stratton home standby generator systems. It assumes that persons using this manual have been properly trained in and are familiar with the servicing procedures for these products, including the proper use of required tools and safety equipment and the application of appropriate safety practices. Persons untrained or unfamiliar with these procedures or products should not attempt to perform such work.
Proper maintenance and repair is important to safe, reliable operation of the standby system. The troubleshooting, testing, maintenance, and repair procedures described in this manual are appropriate for the models described herein. Alternative methods or procedures may pose risk to personal safety and the safety and/or reliability of the equipment and are not endorsed or recommended by Briggs & Stratton.
All information, illustrations, and specifications contained in this manual were based on the data available at the time of publication. Briggs & Stratton Corporation reserves the right to change, alter, or otherwise improve the product or the product manuals at any time without prior notice.
Copyright © 2008 Briggs & Stratton Corporation All rights reserved.
No part of this material may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying or recording by any information storage and retrieval system, without prior written permission from Briggs & Stratton Corporation.
TABLE OF CONTENTS
SECTION 1 - SAFETY, MAINTENANCE AND ADJUSTMENTS......................................1
SAFETY MESSAGES .................................................................................................................. 1
ACCESS TO THE GENERATOR................................................................................................. 5
GENERATOR COMPONENTS.................................................................................................... 6
GENERATOR CLEARANCES..................................................................................................... 9
SYSTEM CONNECTIONS........................................................................................................... 10
FUEL SUPPLY............................................................................................................................. 12
ENGINE MAINTENANCE ............................................................................................................ 13
SETTING THE EXERCISE TIMER.............................................................................................. 13
SECTION 2 - TROUBLESHOOTING.................................................................................17
SYSTEM CONTROL PANEL (SCP) ............................................................................................17
FAULT CODE INDICATIONS ...................................................................................................... 18
STOPPING THE SYSTEM FOR MAINTENANCE.......................................................................19
GENERATOR AC CONNECTION SYSTEM................................................................................ 20
(FAULT CODE_1) DEAD UNIT/LOW BATTERY VOLTAGE.......................................................21
(FAULT CODE_2) LOW OIL PRESSURE ................................................................................... 29
(FAULT CODE_3) LOW OUTPUT VOLTAGE............................................................................. 33
(FAULT CODE_4) ENGINE FAILS TO START/FAILS TO CRANK............... ................... ........... 39
(FAULT CODE_5) UNDER FREQUENCY................................................................................... 51
(FAULT CODE_6) OVER FREQUENCY ..................................................................................... 54
(FAULT CODE_7) HIGH TEMPERATURE.................................................................................. 55
(FAULT CODE_8) TRANSFER SWITCH FAILURE .................................................................... 58
Page i
SECTION 3- SPECIFICATIONS & REFERENCE.................................................. ............59
SPECIFICATIONS ............................................ ............................................ ................................ 59
SCHEMATIC ......................................... ....................................................................................... 60
WIRING DIAGRAM ...................................................................................................................... 61
Page ii
SECTION 1 - SAFETY, MAINTENANCE AND ADJUSTMENTS
In The Interest Of Safety
This repair manual contains safety information that is designed to:
• Make you aware of hazards associated with engines.
• Inform you of the risk of injury associated with those hazards.
• Tell you how to avoid or reduce the risk of injury.
WARNING
Before attempting to service this equipment, read and understand this manual and the operating instructions of the equipment
Failure to follow instructions could result in DEATH, SERIOUS INJURY (including paralysis) or property damage.
The Safety Alert Symbol
The safety alert symbol ( ) is used to identify safety information about hazards that can result in personal injury.
A signal word (DANGER, WARNING, or CAUTION) is used with the alert symbol to indicate the likelihood and the potential severity of injury. In addition, a hazard symbol may be used to represent the type of hazard.
DANGER indicates a hazard which, if
not avoided, will result in death or serious injury.
• Prior to work, read and understand the section(s) of this manual that pertain to the job. Follow all safety warnings.
• Wear suitable eye protection.
• When servicing engines or equipment, prevent accidental starting by disconnecting control panel fuse, spark plug wire from the spark plug(s), and disconnect negative battery cable.
• Disconnect all sources of supply voltage before servicing the generator.
HAZARD SYMBOLS AND MEANINGS
Fire Electrical
Explosion
Toxic
Fumes
Rotating
Shock
Hot Surface
Parts
1
WARNING indicates a hazard which, if
not avoided, could result in death or serious injury.
CAUTION indicates a hazard which, if
not avoided, might result in minor or moderate injury.
CAUTION: When this signal word is used
without the alert symbol, it indicates a situation that could result in damage to the engine.
Auto Start
Lift Hazard Read
Explosive
Pressure
Manual
Chemical
Burn
1
WARNING
WARNING
1
The engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
WARNING
Storage batteries give off explosive hydrogen gas during recharging. Slightest spark will ignite hydrogen and cause explosion. Battery electrolyte fluid contains acid and is extremely caustic. Contact with battery contents will cause severe chemical burns. A battery presents a risk of electrical shock and high short circuit current.
DO NOT dispose of a battery in a fire.
DO NOT allow any open flame, spark, heat, or lit cigarette during and for several minutes after charging a battery.
DO NOT open or mutilate the battery.
Wear protective goggles, rubber apron, and rubber gloves.
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
WARNING
Running engine gives off carbon mon­oxide, and odorless, colorless, poison gas. Breathing carbon monoxide can cause headache, fatigue, dizziness, vomiting, confusion, seizures, nausea, fainting, or death.
Operate generator ONLY outdoors.
Install a battery operated carbon monox­ide alarm near the bedrooms.
Keep exhaust gas from entering a con­fined area through windows, doors, venti­lation intakes, or other openings.
Generator produces hazardous volt­age.
Failure to properly ground generator can result in electrocution.
Failure to isolate generator from power utility can result in death or injury to electric utility workers due to backfeed of electrical energy.
When using generator for backup power, notify utility company.
DO NOT touch bare wires or receptacles.
DO NOT handle generator or electrical cords while standing in water, while bare­foot, or while hands or feet are wet.
If you must work around a unit while it is operating, stand on an insulated dry sur­face to reduce shock hazard.
DO NOT allow unqualified persons or chil­dren to operate or service generator.
In case of an accident caused by electri­cal shock, immediately shut down the source of electrical power and contact the local authorities. Avoid direct contact
with the victim.
Despite the safe design of the home gen­erator, operating this equipment impru­dently, neglecting its maintenance, or being careless can cause possible injury or death.
Remain alert at all times while working on this equipment. Never work on the equip­ment when you are physically or mentally fatigued.
Before performing any maintenance on the generator, disconnect the battery cable indicated by a NEGATIVE, NEG, or (-) first. When finished, reconnect that cable last.
After your home generator is installed, the generator may crank and start without warning any time there is a power failure. To prevent possible injury, always set the generator’s system switch to OFF AND remove the 15 Amp fuse BEFORE work­ing on the equipment.
2
WARNING
WARNING
Propane and Natural Gas are extremely flammable and explosive.
Fire or explosion can cause severe burns or death.
Install the fuel supply system according to N.F.P.A 37 and other applicable fuel-gas codes.
Before placing the home generator into service, the fuel system lines must be properly purged and leak tested.
After the generator is installed, you should inspect the fuel system periodically.
NO leakage is permitted.
DO NOT operate engine if the smell of fuel is present or other explosive condi­tions exist.
DO NOT smoke around the generator, Wipe up any oil spills immediately. Ensure that no combustible materials are left in the generator compartment. Keep the area near the generator clean and free of debris.
Starter and other rotating parts can entangle hands, hair, clothing, or accessories.
NEVER operate generator without protec­tive housing or covers.
DO NOT wear loose clothing, jewelry, or anything that may be caught up in the starter or other rotating parts.
Tie up long hair and remove jewelry.
CAUTION
Installing the control panel’s 15A fuse could cause the engine to start.
DO NOT install this fuse until all plumbing and wiring has been completed and inspected.
CAUTION
1
WARNING
Contact with muffler area can result in serious burns. Exhaust heat/gases can ignite com­bustibles or structures, causing a fire.
DO NOT touch hot parts and AVOID hot exhaust gases.
Allow equipment to cool before touching.
DO NOT install the generator closer than 5 feet (1.5m) from any combustibles or structures with combustible walls having a fire resistance rating of less than 1 hour.
Excessively high operating speeds increase risk of injury and damage to the generator.
Excessive load will cause engine shutdown.
DO NOT tamper with governed speed. Generator supplies correct rated fre­quency and voltage when running at gov­erned speed.
DO NOT modify the generator in any way.
CAUTION
Avoid prolonged or repeated skin contact with used motor oil.
Used motor oil has been shown to cause skin cancer in certain laboratory animals.
Thoroughly wash exposed areas with soap and water.
3
1
CAUTION
Exceeding generators wattage/amperage capacity can damage generator and/or electri­cal devices connected to it.
See Essential Circuits in the Operator’s manual.
Start generator and let engine stabilize before connecting electrical loads.
CAUTION
Improper treatment of generator can damage it and shorten its life, or result in personal injury.
Use generator only for intended uses.
If you have questions about intended use, ask dealer or contact Briggs and Stratton.
Operate generator only on level surface.
Adequate, unobstructed flow of cooling and ventilating air is critical to correct gen­erator operation.
The Coolant Fill, Battery, and Control Panel doors must be installed whenever the unit is running.
DO NOT expose generator to excessive moisture, dust, dirt, or corrosive vapors.
Despite the safe design of the home gen­erator, operating this equipment impru­dently, neglecting its maintenance or being careless can cause possible injury or death.
DO NOT start engine with air cleaner removed.
DO NOT insert any objects through the cooling slots.
DO NOT use the generator or any of its parts as a step. Stepping on the unit can cause stress and break parts. This may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
If connected devices overheat, turn them off and disconnect them from generator.
Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
Standby Safety Practices
• This manual contains important safety messages. Read these carefully and understand them before proceeding with maintenance and repairs.
• Become familiar with the Home Generator System. Know its applications, its limitations, and any hazards involved.
• This unit must not be modified for any application other than that for which it was designed. If you have any questions about the home generator System, ask the dealer or consult Briggs and Stratton.
• Never handle any kind of electrical cord or device while standing in the water, while barefoot, or while hands and feet are wet.
• Worn, bare, frayed, or otherwise damaged electrical cord sets should not be used with the Home Generator System. Using a defective cord may result is an electrical shock or damage to the test equipment and/or the unit.
• The Home Generator System requires an adequate supply of cooling air for continued proper operation. Never allow the free flow of cooling air into or out of the unit to be obstructed in any way.
• Home Generator Systems produce powerful voltages that can cause extremely dangerous electrical shock. Avoid contact with bare wires, terminals, etc. Never permit an untrained person to service or assist with the procedures discussed in this manual.
• Never manually start or stop this unit with electrical loads connected to the receptacles and turned ON. Start the engine and allow it to stabilize before connecting any electrical loads. Turn OFF and disconnect all electrical loads before shutting down the generator.
• The manufacturer cannot anticipate every circumstance that might involve or constitute a hazard. Warnings in manuals, warnings on hang tags, and labels affixed to the unit are NOT all­inclusive. Do not handle, operate, or service the unit using a procedure or method that is not specifically recommended by the manufacturer.
4
ACCESS TO THE GENERATOR
The home generator is equipped with an enclosure that has four access doors (Figure 1). The doors are named for a significant component located behind them, as follows:
• Control Panel Door
• Coolant Fill Door
• Battery Door
• Exhaust Door
WARNING
Removing An Access Door
1. Insert key into lock of access door handle you wish to open and turn one quarter turn counterclockwise. Remove key. Handle will remain unlocked until you relock it.
2. Grasp door’s handle and turn one quarter turn counterclockwise to open.
3. Coolant Fill door is unlocked in the same manner. It can be used for adding coolant or engine oil.
NOTE: The enclosure also includes muffler and radiator access panels, used for cleaning those components. Those panels should remain closed at all other times.
1
Contact with muffler area can result in serious burns.
DO NOT touch hot parts and AVOID hot exhaust gases.
Allow equipment to cool before touching.
Each Home Standby Generator System is equipped with two identical keys. These keys fit all the doors.
NOTE: The Coolant Fill, Battery and Control Panel doors must be installed whenever the unit is running, or the generator may overheat.
Installing An Access Door
1. Mount the door using the notches on the generator base.
2. Close door and turn handle one quarter turn clockwise.
3. Insert key into lock in handle and turn one quarter turn clockwise. Remove key.
Figure1
5
1
GENERATOR COMPONENTS
NOTE: Generator is shown with access door removed.
A - Oil Dip Stick - Used to check the engine oil
level. B - Engine Label - Identifies engine model and type. C - Oil Fill Cap - Remove to service the engine with recommended oil. D - Thermostat - Allows the engine to heat up quickly, and then to keep the engine at a con­stant temperature. It does this by regulating the amount of coolant that goes through the radiator. E - Coolant Recovery Bottle - Provides visual indicator of engine coolant level. F - Oil Filter - Filters engine oil to prolong sys­tem life. G - Oil Drain Plug - Provided to facilitate oil changing. H - Ignition Coil - Amplifies the voltage of elec­tricity supplied to the ignition system. J - Battery Negative Cable - Cable connects negative battery terminal to various electrical cir­cuit and to the engine for starting. K - Oil Pressure Switch - Monitors engine oil pressure when the engine is running. Indicates a drop to below the minimum permissible pres­sure. L - Starter Contactor/Motor - The starter con­tactor supplies the high current
needed to run the starter motor and also pro­vided the force needed to engage the starter. The starter is an electric motor used to turn over the engine to start it. M - Battery Fuse Holder - Provides over-current protection for safe operation of generator battery. Fully insulated and water proof. N - Fuel Solenoid - One inlet and one outlet, electrically controlled to permit and shut off fluid flow. P - Generator Ground - Located on the frame below the generator circuit breaker cover. If required by local codes, should ONLY be used for a ground rod. See System Control Panel for other Ground locations. R - Unit Data Decal - Identifies unit by model and serial number. S - Stub In Location - Located in bottom of cir­cuit breaker enclosure for power cable stub in location. Panel is removable to allow easy hole cutting for conduit. T - Circuit Breaker Enclosure - Equipped with removable bottom to assist with conduit connec­tion. U - Automatic Voltage Regulator - Access hole for voltage regulator adjustment. V - Control Panel - Used for various tests, oper­ation, and maintenance functions. See System Control Panel on the next page.
6
NOTE: Circuit breaker cover is removed for illustration purposes.
A - Circuit Breaker — Protects the system from shorts and other over-current conditions. Must be ON to supply power to the Automatic Transfer Switch. B - Generator Neutral Lug — Connection for neutral. Neutral is not bonded to ground or generator. C - Set Exercise Button — Used to set the exercise cycle start time and day-of-the-week . Must be reset if the fuse is removed or the battery is disconnected. D- Manual Over-Ride Button — With the system switch in AUTO position, push the manual over-ride switch to start the generator. To turn off the generator, push and hold the manual over-ride switch again until engine stops. E - 15 Amp Fuse — Protects the home generator DC control circuits. If the fuse has ‘blown’ (melted open) or was removed, the engine cannot crank or start. F - System Switch — This two-position switch is the most important control on the system and is used as follows:
• “AUTO position is the normal operating
position. If a utility power outage is sensed, the system will start the generator. When utility power is restored, AUTO lets the engine stabilize internal temperatures, shuts
1
off the generator, and waits for the next utility power outage.
• “OFF” position turns off running generator, prevents unit from starting and resets any detected faults.
G - Digital Display — Displays the total number of hours the generator has been running and fault codes. Used to schedule maintenance tasks and for troubleshooting operational problems with the home generator. All fault conditions are described in Fault Description System. H - Ten Pin Connection — Low Voltage connection to signal fault contacts, transfer switch communication, remote LED and auxiliary 12VDC power are made to a removable ten-pin connector plug. J - Generator Ground Lug — Located next to the circuit breaker and should meet most codes, standards, and regulations. K - Utility Circuit Connection — Delivers power to the generator’s circuit board (within internal battery trickle charge) and water heater. When the power on these leads is lost, the generator will start. Fuse protected. Replace the fuse(s) only with identical fuse(s). L - Generator AC Lugs — Connection for generator load(s).
7
1
NOTE: Generator is shown with access door
removed. A - Over Temperature Switch - Switch for auto­matically making or breaking an electrical circuit at predetermined temperature. Will signal the system control panel to shut down the generator when the engine coolant reaches a critical level.
B - RPM Sensor - A permanent magnet built into the sensor provides a magnetic field at the base of the sensor. As each tooth of the flywheel passes through the magnetic field, a signal (volt­age pulse) is generated. The engine control unit uses this to monitor engine speed to maintain a specific generator frequency.
D - Alternator Data Plate - Lists alternator data specific to the Marathon alternator assembly.
E - Battery - Stores and supplies electrical energy. The manufacturer does not supply the battery.
F- Engine Warmer - An electric heater that heats the engine by keeping the engine coolant warm to ease starting in cold weather. Con­nected to utility power and fully automatic.
C - Air Cleaner - Protects engine by filtering dust and debris out of intake air.
8
GENERATOR CLEARANCES
WARNING
Running engine gives off carbon mon­oxide, and odorless, colorless, poi­son gas. Breathing carbon monoxide can cause headache, fatigue, dizziness, vomiting, confusion, seizures, nau­sea, fainting, or death.
drifting you may need to construct a windbreak to protect the unit.
• Install the generator as close as possible to the transfer switch and fuel supply to reduce the length of wiring, conduit, and piping.
Operate generator ONLY outdoors.
Install a battery operated carbon monox­ide alarm near the bedrooms.
Keep exhaust gas from entering a con­fined area through windows, doors, venti­lation intakes, or other openings.
WARNING
Exhaust heat/gases can ignite com­bustibles or structures, causing a fire.
DO NOT install the generator closer to 5 feet (1.5m) from any combustibles or structures with combustible walls having a fire resistance rating of less than 1 hour.
General Location Guidelines
• Install the unit outdoors ONLY.
• Place the unit on a prepared concrete slab that is flat, level, and has provisions for water drainage.
• Install the unit in a location where sump pump discharge, rain gutter down spouts, roof run-off, landscape irrigation, or water sprinklers will not flood the unit or spray the enclosure and enter any air inlet or outlet openings.
• Install the unit where the location of any services such as phone, electrical, fuel, air conditioning, irrigation, including covered, concealed and underground services will not be affected or obstructed.
• Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, sand, etc. If prevailing winds will cause blowing or
1
IMPORTANT: Laws or local codes may regulate
the distance to the fuel supply.
The Minimum clearances from aerial view of generator (A) to combustible (C,D) materials is shown in Figure 1.
• These distances are provided to give generator location guidance relative ONLY to combustibles, generator cooling, and maintenance.
• The minimum distances in the figure are as shown. All four sides of the generator cannot be enclosed or restricted, even if the minimum distances are maintained. DO NOT connect (C) to (D).
• A roof cannot be constructed over the top of the generator.
• Exhaust (B) is directed out the top of the generator and must not be allowed to accumulate.
9
1
SYSTEM CONNECTION
Low Voltage (LV) connections to signal fault contacts, transfer switch communications, remote LED and auxiliary 12VDC power are made to a removable ten-pin connector plug. Compare this illustration with the location of these important connections:
A - 10 Pole Connector Plug B - Fault Contacts — Use NO, COM and NC for operating a siren, light, optional GenAlert, etc. to alert
you in case of a fault. Contacts reverse state (NO goes to NC and vice versa) upon a fault condition. C - Transfer Switch Communication — Connects to transfer switch control board for communication
interface. D - Remote LED Output — Used to connect to the remote LED supplied with the generator. The remote
LED will turn on and off in a series of blinks if certain faults are detected in the generator. E - +12Volt DC, .5 Amp Output — Internal auxiliary power supply.
10
GENERATOR AC CONNECTION SYSTEM
A single-phase, three-wire AC connection system is used on the home generator. The stator assembly consists of a pair of stationary windings with two leads brought out of each winding. The junction of leads T2 and T3 forms the neutral lead, as shown schematically and as wiring diagram below. A complete schematic and wiring diagram can be found later in this manual.
NOTE: Neutral is not bonded to ground at generator.
Grounding the Generator
Ground the home generator per applicable codes, standards and regulations. There are two generator Ground lug locations. The one inside the alternator junction box next to the circuit breaker is the primary lug and should meet most applications. The second Ground lug is located on the frame below the generator circuit breaker cover, and should ONLY be used for a ground rod located at the generator, if required by local codes. See Controls for location.
Utility Circuit Connection
“240V Utility” leads must be routed in conduit. The “240V Utility” leads deliver power to the generator’s circuit board and water heater. This power also charges the battery. When power on these leads is lost, the generator will start.
Fault Detection System
The generator may have to run for long periods of time with no operator present. For that reason, the system is equipped with sensors that automatically shut down the generator in the event of potentially damaging conditions, such as low oil pressure, high water temperature, over speed, and other conditions. Refer to Fault Detection System for more detailed information.
1
11
1
FUEL SUPPLY
Depending on the generator model number, the home standby generator was manufactured and shipped to run on natural gas or liquid propane vapor. No matter which type of fuel the generator was manufactured to run on, it can be field converted to operate on either type of fuel. When troubleshooting, engine performance is dependent on receiving the specific pressure and volume of fuel under varying load conditions with all gas appliances turned on and operating. For fuel consumption and pressure specifications, consult the installation manual. For proper engine function, factors that are inherent to each of these fuels, your location and the duration of possible utility interruptions are important considerations in the following fuel guidelines:
• Use clean, dry fuel, free of moisture or any particulate material. Using fuels outside the following recommended values may cause performance problems.
• For engines set up to run on propane vapor (LP), commercial grade HD5 propane with a minimum fuel energy of 2500 BTUs/ft3 with maximum propylene content of 5% and butane and heavier gas content of 2.5% and minimum propane content of 90%.
10F (5.6C) above 77F (25C). These factors must be considered when determining total generator
load.
WARNING
Propane and Natural Gas are extremely flammable and explosive.
Fire or explosion can cause severe burns or death.
Install the fuel supply system according to N.F.P.A 37 and other applicable fuel-gas codes.
Before placing the home generator into service, the fuel system lines must be properly purged and leak tested.
After the generator is installed, you should inspect the fuel system periodically.
NO leakage is permitted.
DO NOT operate engine if the smell of fuel is present or other explosive condi­tions exist.
DO NOT smoke around the generator, Wipe up any oil spills immediately. Ensure that no combustible materials are left in the generator compartment. Keep the area near the generator clean and free of debris.
WARNING
Propane and Natural Gas are extremely flammable and explosive.
Fire or explosion can cause severe burns or death.
The home generator is equipped with an automatic safety gas “fuel shut-off” valve.
DO NOT operate the equipment if the “fuel shut-off” valve is missing or inoperative.
Power Decrease at High Altitude or High Temperature
Air density is less at high altitudes, resulting in less available engine power. Specifically, engine power will decrease 3.5% for each 1,000 feet (300 meters) above sea level and 1% for each
12
SETTING THE EXERCISE TIMER
The home generator is equipped with an exercise timer that will start and exercise the system once every seven days. During this exercise period, the unit runs for approximately 20 minutes and then shuts down. Electrical load transfer DOES NOT occur during the exercise cycle (unless an utility power outage occurs).
A button on the control panel is labeled “Set Exercise” (see System Control Panel). The specific day and the specific time of day this button is pressed is programmed into the control board memory. This date and time is then used to automatically initiate the system exercise cycle. The “Set Exercise” legend on the control panel will flash until the set exercise cycle is set.
To perform the Set Exercise procedure:
1. Choose the day and time you want your home generator to exercise.
2. On that day and time, press and hold down the “Set Exercise” button for three seconds.
NOTE: “SET EXERCISE” will flash until the button is pressed for three seconds, then “SET EXERCISE” will illuminate for 5 seconds, and finally turn off.
3. The unit will then start and run it’s 20 minute exercise cycle.
For example, if you press the “Set Exercise” button on Sunday morning at 10:00 AM, the unit will run an immediate exercise cycle and an exercise cycle will occur every following Sunday at 10:100 AM (+/- 1/2 hour).
NOTE: “Set Exercise” will only work if the unit is in the Automatic mode and this exact procedure is followed. The exerciser will need to be re-set whenever the 15 Amp fuse is removed or changed, or if the 12 Volt DC battery is disconnected.
If you want to change the day and time the unit exercises, simply perform the “Set Exercise” procedure at the exact weekday and time you want it to take place.
GENERATOR MAINTENANCE
Generator maintenance consists of keeping the unit clean. Operate the unit in an environment where it will not be exposed to excessive dust, dirt, moisture or any corrosive vapors. Cooling air louvers on the enclosure must not become clogged with snow, leaves, or any other foreign material.
Check the cleanliness of the unit frequently and clean when dust, dirt, oil, moisture or other foreign substances are visible on its exterior/ interior surface.
NOTE: DO NOT use direct spray from a garden hose to clean generator. Water can enter the engine and generator and cause problems.
Engine Maintenance
An engine manual was packaged with this system. Please refer to it for all engine-related maintenance topics. However, proper engine cooling and lubrication are so important we also reference them.
Engine Oil
The system is filled with the recommended non­synthetic oil (API SL 10W-30W). This allows for proper system operation in a wide range of temperature and climate conditions.
NOTE: Refer to the engine operator’s manual for the recommended oil change intervals.
Shown here is the oil drain location (B) and the oil filter (A).
1
13
Figure2
Changing Engine Oil
CAUTION
Avoid prolonged or repeated skin contact with used motor oil.
Engine Coolant System
With the engine cold, check the coolant level in the coolant recovery bottle, seen inside the Control Panel door. Maintenance instructions for engine coolant are found in the engine operator’s manual.
1
Used motor oil has been shown to cause skin cancer in certain laboratory animals.
Thoroughly wash exposed areas with soap and water.
KEEP OUT OF THE REACH OF CHILDREN. DON’T POLLUTE. CONSERVE RESOURCES. RETURN USED OIL TO COLLECTION CENTERS.
1. Put SYSTEM switch in OFF. Remove 15 Amp fuse. Disconnect negative battery cable from negative battery terminal.
2. Change oil while the engine is still warm from running, as described in the engine operator’s manual.
NOTICE
Any attempt to crank or start the engine before it has been properly serviced with the recom­mended coolant or oil will result in equipment failure.
BATTERY
Charging the Battery
If it is necessary to charge the battery, proceed as follows:
1. Set generator’s system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Disconnect negative battery cable to negative battery terminal (indicated by NEGATIVE,
NEG, or (-)).
NOTICE
Failure to disconnect the negative battery cable will result in equipment failure.
DO NOT attempt to jump start the battery.
Damage to equipment resulting from fail­ure to follow this instruction will void war­ranty.
Refer to Maintenance in the Operator’s Manual and engine manual for coolant and oil fill information.
Damage to equipment resulting from fail­ure to follow this instruction will void engine and generator warranty.
To fill your engine with oil:
Follow the oil grade recommendation and oil fill instructions given in the engine operator’s manual.
To make the task of adding oil more convenient, we recommend the use of a funnel attached to the length of tubing long enough to reach from the Coolant Fill door to the oil fill opening on the engine valve cover. Recheck oil level,reconnect battery, install fuse, put in AUTO and reset exercise timer when complete.
14
4. Charge battery with a battery charger at 2 Amps until battery holds 12 Volts.
NOTE: With the battery installed and utility power available to the transfer switch, the battery receives a trickle charge whenever the engine is not running. It may take up to 72 hours to fully charge a discharged battery with the trickle charge. The trickle charge is not able to recharge a battery that is completely discharged.
WARNING
Storage batteries give off explosive hydrogen gas during recharging.
Slightest spark will ignite hydrogen and cause explosion.
Battery electrolyte fluid contains acid and is extremely caustic.
Contact with battery contents will cause severe chemical burns.
A battery presents a risk of electrical shock and high short circuit current.
DO NOT dispose of battery in fire.
DO NOT allow any open flame, spark, heat, or lit cigarette during and for several minutes after charging a battery.
DO NOT open or mutilate the battery.
Wear protective goggles, rubber apron, and rubber gloves.
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Servicing the Battery
If it is necessary to service the battery, proceed as follows:
1. Set control board System switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Service or replace battery as required.
4. Connect red battery cable to battery positive terminal (indicated by POSITIVE, POS, or (+)).
5. Connect negative battery cable to negative battery terminal (indicated by NEGATIVE, NEG, or (-)).
6. Ensure hardware on both positive and negative battery terminals is secure.
7. Reinstall 15 Amp fuse in control panel.
8. Set generator’s system switch to AUTO.
9. Reset exercise timer. See Setting Exercise
Timer.
To Clean the Generator
NOTICE
Improper treatment of generator can damage it and shorten its life.
1
5. Connect negative battery cable to negative battery terminal (indicated by NEGATIVE, NEG, or (-)).
6. Ensure hardware on both positive and negative battery terminals is secure.
7. Reinstall 15 Amp fuse in control panel.
CAUTION
Installing the control panel’s 15A fuse could cause the engine to start.
DO NOT install this fuse until all plumbing and wiring has been completed and inspected.
8. Set generator’s system switch to AUTO.
9. Reset exercise timer. See Setting Exercise
Timer.
DO NOT expose generator to excessive moisture, dust, dirt, or corrosive vapors.
DO NOT insert any objects through cool­ing slots.
• Use a damp cloth to wipe exterior surfaces clean.
• Use a soft bristle brush to loosen caked on dirt, oil, etc.
• Use a vacuum cleaner to pick up loose dirt and debris.
• Use low pressure air (not to exceed 25 psi) to blow away dirt. Inspect cooling air slots and openings on the generator. These openings must be kept clean and unobstructed.
15
1
16
Loading...
+ 45 hidden pages