Briggs & Stratton 040586, 040610, 040588 Specification Sheet

17 & 20kW1 Standby Generator
Briggs & Stratton®
The Smart Choice
Reliable back-up power for added peace of mind. Guard against losses due to power outages with a Briggs & Stratton Standby Generator.
4
New Upgraded Control System
New AVR optimizes generator performance with tighter voltage control
LCD display that displays multi-line text and graphics
Default exercise cycle setting of 16 seconds
Low speed exercise available to save fuel and reduce noise
Monitors cold temperatures to avoid moisture buildup in engine oil
Cleaner power with improved frequency regulation
Designed for Easy Installation & Maintenance
Approved for installation as close as 18" to a building
Hinged roof and removable side panels for better service access to the
engine and alternator
Controller, battery charger, and AVR can be replaced separately
External on/o switch located on back of enclosure
2
Commercial Vanguard® Engine
Easy conversion between natural gas (NG) and liquid propane vapor
(LPV) during installation
Advanced debris management keeping engine clean and cool for
enhanced durability and performance
Dynamically balanced crankshaft minimized engine noise and vibration
Charging System
Independent battery charger
Optimizes battery life with a 3-stage battery charger (bulk,
absorption, and float stage)
Corrosion Resistant Enclosure & Base
Made with automotive grade galvanneal steel or aluminum
to resist rust
Powder-coated paint for years of protection against chips
and abrasions
Certified to withstand hurricane-force winds up to 175mph
5
Briggs & Stratton® Full Synthetic Generator Oil
Shields the engine from low temperature sludge buildup
and high temperature deposits
Reduces engine wear, scoring and abrasion
Compatible with Symphony® II Power Management System
Customizable to your home’s needs
Automatically balances the power of your home’s electrical load
including high wattage items like air conditioning units and electric ovens
Oers whole house power with a more aordable home generator
Compatible transfer switches and modules sold separately
Generator Set Rating
Liquid Propane Vapor Natural Gas Limited Warranty
Model
17kW1040610 Steel 120/24 0 1 60 80 17 70.8 15.3 63.7 5 Year
20kW1040586 Steel 120/240 1 60 100 20 83.3 18 75.5 5 Year
20kW1040588 Aluminum 120/24 0 1 60 100 20 83.3 18 75.5 5 Year
1
This generator is certified in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) and CSA (Canadian Standards Association) standard C 22.2 No. 100-14 (motors and generators).
2
3
Single pha se units are r ated at 1. 0 power fac tor and three phase unit s are rated at 0 .8 power factor.
4
Se e operator ’s manual or BRIGGSand STRATTON.com for complete warranty details.
5
Up to 175 mph, when in stalled in accordance with the in stallati on manual.
Enclosure Type
Voltage Phase3Hz
Circuit Breaker Amps
LPV kW1LPV Amps NG kW
NG
1
Amps
Parts, Labor, Travel
4
Engine Specifications
17 & 20kW¹ Standby Generator
Engine
Engine Brand Vanguard
Engine Speed (RPM) 3600
Engine Fuel
Liquid Propane Vapor (LPV) or Natural Gas (NG)
Engine Cylinder Configuration OHV
Number of Cylinders 2
Displacement (L / Ci) 0.993 / 60.60
Compression Ratio 9:7:1
Governor Type Electronic
Frequency Regulation +/- 0.3 Hz (0.5%)
Valves OHV with Hardened Seats
Ignition System
Fixed Timing Magnetron® Electric Ignition
Starter Motor Rating Voltage 12 Volt
Battery Required
12 Volt, Group BCI 26 or 51, 540 CCA Minimum
Lubrication
Oil Capacit y (L / qt) 2.3 / 2.46
Low Pressure Switch Included
Lubrication System Full Pressure
Oil Briggs & Stratton 5W30 Full Synthetic
Alternator Specs
Manufacturer Briggs & Stratton
Type Self-Excited, 4-Lead
Voltage Regulator Automatic
Insulation Class F
Peak Motor Starting kVA 17kW - 39 / 20kW - 41
Controller Features
Generator Sensing Single phase voltage monitoring
LCD Display Displays multi-line text and graphics
High Temperature Switch Included
Dura-Bore Cast Iron Cylinder Sleeve
Included
Fault Display Provides up to 39 detailed fault codes
Exercise Cycle
Six exercise length options Default: Start and run for 16 seconds; Abort exercise below 40° F (internal temperature)
Operations
Fuel Consumption
BTU / hr
1
ft3 / hr
17kW
m3 / hr
g / hr LPV - 3.19 LPV - 2.00 LPV - 1.08
BTU / hr
1
ft3 / hr
20kW
m3 / hr
g / hr LPV - 3.65 LPV - 2.24 LPV - 1.08
1
This generator is certified in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) and CSA (Canadian Standards Association) standard C 22.2 No. 100-14 (motors and generators).
2
Fuel consumption rates are estimated based on normal operating conditions at ½ load. Generator operation may be greatly affected by elevation and the cycling
operation of multiple electrical appliances – fuel flow rates may vary depending on these factors.
3
See oper ator’s manual or BRIGGSandSTRATTON.com for complete warranty details.
4
Lowest no-load measurement per ISO 3744. Sound level measurement at other locations around generator may b e dif ferent depending upon installation configuration
2
Full Load 1/2 Load No Load
NG - 248,000 LPV - 295,000
NG - 248 LPV - 118
NG - 7.02 LPV - 3.34
NG - 170,000 LPV - 185,000
NG - 170 LPV - 74
NG - 4.81 LPV - 2.10
NG - 99,000 LPV - 72,000
NG - 99 LPV - 40
NG - 2.80 LPV - 1.13
Full Load 1/2 Load No Load
NG - 260,000 LPV - 337,500
NG - 260 LPV - 135
NG - 7.36 LPV - 3.82
NG - 187,000 LPV - 207,50 0
NG - 187 LPV - 83
NG - 5.30 LPV - 2.35
NG - 99,000 LPV - 100,000
NG - 99 LPV - 40
NG - 2.80 LPV - 1.13
Sound R ating At 7 Meters
Low Idle Mode 64 dBA
No Load 67 dBA
4
4
3
Unlike some other standby generator manufacturers, our warranty covers parts,
labor AND travel for the full length of the warranty with no start-up costs!
.
Loading...