Briggs & Stratton 030659-00 Owner’s Manual

Not for
Reproduction
Portable Generator
Operator’s Manual
(motors and generators) and rated in accordance with PGMA (Portable Generator Manufacturers’ Association)
standard PGMA G200 (Standard for Testing and Validating Performance of Portable Generators).
BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC
MILWAUKEE, WISCONSIN, U.S.A.
Manual No. 80012142 Revision -
Not for
Reproduction
Thank you for purchasing this quality-built Briggs & Stratton® generator. We are pleased that you’ve placed your confidence in the Briggs & Stratton brand. When operated and maintained according to the instructions in this manual, your Briggs & Stratton generator will provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with generator products and how to avoid them. This generator is designed and intended only for supplying electrical power for operating compatible electrical lighting, appliances, tools and motor loads, and is not intended for any other purpose. It is important that you read and understand these instructions thoroughly before attempting to start or operate this equipment. Save these original instructions for future reference.
This generator requires final assembly before use. Refer to the Assembly section of this manual for instructions on final assembly procedures. Follow the instructions completely.
Where to Find Us
You never have to look far to find Briggs & Stratton support and service for your generator. Consult your Yellow Pages. There are over 30,000 Briggs & Stratton authorized service dealers worldwide who provide quality service. You can also contact Briggs & Stratton Customer Service by phone at (800) 743-4115, or on the Internet at BRIGGSandSTRATTON.COM.
Generator Engine
Model Number ______________________ Model Number ________________________
Revision
Serial Number
Date Purchased ____________________
____________________ Type Number _________________________
_________________ Code Number _________________________
Table of Contents
Safe Operation Checklist ............... 3
Operator Safety....................... 4
Assembly............................ 9
Features and Controls ................ 14
Operation........................... 17
Maintenance ........................ 21
Troubleshooting ..................... 26
Warranty ........................... 28
Product Specifications ................ 32
Common Service Parts ............... 32
Copyright © 2014. Briggs & Stratton Power Products Group, LLC Milwaukee, WI, USA. All rights reserved. BRIGGS & STRATTON POWER PRODUCTS is a registered trademark of Briggs & Stratton Corporation Milwaukee, WI, USA
2 BRIGGSandSTRATTON.COM
Not for
Reproduction
Safe Operation Checklist
Safe operation of the portable generator requires the completion of the following tasks:
Carbon Monoxide (CO) Alarm
Carbon monoxide (CO) alarm(s) in working order.
Smoke Alarm
Smoke alarm(s) in working order.
Generator Location
Generator placed in a Carbon Monoxide (CO) safe zone. See Generator Location to reduce the Risk of
Carbon Monoxide Poisoning.
Generator placed in a fire safe zone. See Generator Location to reduce the Risk of Fire. Generator located on flat and level surface.
Oil and Fuel
Engine has proper oil level. See Verify Engine Oil Level. Fuel tank filled at or below baffle. See Add Fuel. Inspect fuel lines, tank, cap and fittings each time before using generator. DO NOT use if fuel leak or damage
is found.
Electrical
When connecting to a buildings electrical system install listed transfer equipment. See Connecting to a
Building’s Electrical System.
Electrical cords are rated for intended loads. See Cord Sets and Receptacles. Electrical cords do not run through doorways, windows, holes in ceilings, walls or floors. Inspect electrical cords thoroughly before each use. DO NOT use if damaged. All labeled electrical cord safeties are understood and being followed.
Operation
Start engine. See Starting the Engine.
3
Not for
Reproduction
Operator Safety
Safety Labels
The generator safety labels shown below and on the next page are placed on your portable generator to draw attention to potential safety hazards.
202997
4 BRIGGSandSTRATTON.COM
Not for
Reproduction
5
Not for
Reproduction
Equipment Description
Read this manual carefully and become
familiar with your generator. Know its applications, its limitations and any hazards involved.
The generator is an engine-driven, revolving field, alternating current (AC) generator equipped with a voltage regulator. The voltage regulator is designed to automatically maintain a constant output voltage level. It was designed to supply electrical power for operating compatible electrical lighting, appliances, tools and motor loads. The generator’s revolving field is driven at about 3600 rpm by a single cylinder engine.
Important Safety Information
The manufacturer cannot possibly anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and the tags and decals affixed to the unit are, therefore, not all-inclusive. If you use a procedure, work method or operating technique that the manufacturer does not specifically recommend, you must satisfy yourself that it is safe for you and others. You must also make sure that the procedure, work method or operating technique that you choose does not render the generator unsafe.
Safety Symbols and Meanings
NOTICE
capacity could damage generator and/or electrical devices connected to it.
• DO NOT exceed the generator’s wattage/amperage capacity. See Don’t Overload Generator in the Operation section.
Every effort has been made to ensure that the information in this manual is both accurate and current. However, the manufacturer reserves the right to change, alter or otherwise improve the generator and this documentation at any time without prior notice.
The Emission Control System for this generator is warranted for standards set by the Environmental Protection Agency and the California Air Resources Board.
This spark ignition system complies with the Canadian standard ICES-002.
Exceeding generators wattage/amperage
Toxic Fumes
Fire
Moving Parts
The safety alert symbol indicates a potential personal injury hazard. A signal word (DANGER, WARNING, or CAUTION) is used with the alert symbol to designate a degree or level of hazard seriousness. A safety symbol may be used to represent the type of hazard. The signal word NOTICE is used to address practices not related to personal injury.
DANGER indicates a hazard which, if not avoided, will result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could result in minor or moderate injury.
NOTICE address practices not related to personal injury.
Kickback
Explosion
Flying Objects
Electrical Shock
Operator’s Manual
Hot Surface
6 BRIGGSandSTRATTON.COM
Not for
Reproduction
WARNING POISONOUS GAS HAZARD.
Engine exhaust contains carbon monoxide, a poisonous gas that could kill you in
minutes. You CANNOT smell it, see it, or taste it. Even if you do not smell exhaust fumes, you could still be exposed to carbon monoxide gas.
• Operate this product ONLY outside far away from windows, doors and vents to reduce the risk of carbon monoxide gas from accumulating and potentially being drawn towards occupied spaces.
• Install battery-operated carbon monoxide alarms or plug-in carbon monoxide alarms with battery back-up according to the manufacturer’s instructions. Smoke alarms cannot detect carbon monoxide gas.
• DO NOT run this product inside homes, garages, basements, crawlspaces, sheds, or other partially­enclosed spaces even if using fans or opening doors and windows for ventilation. Carbon monoxide can quickly build up in these spaces and can linger for hours, even after this product has shut off.
• ALWAYS place this product downwind and point the engine exhaust away from occupied spaces.
If you start to feel sick, dizzy, or weak while using this product, get to fresh air RIGHT AWAY. See a doctor. You may have carbon monoxide poisoning.
WARNING The engine exhaust from this
product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
WARNING Certain components in this product
and related accessories contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm. Wash hands after handling.
WARNING
• This generator does not meet U. S. Coast Guard Regulation 33CFR-183 and should not be used on marine applications.
• Failure to use the appropriate U. S. Coast Guard approved generator could result in death or serious injury.
WARNING Starter cord kickback (rapid
retraction) will pull hand and arm toward engine faster than you can let go which could cause broken bones, fractures,
bruises, or sprains resulting in serious injury.
• When starting engine, pull cord slowly until resistance is felt and then pull rapidly to avoid kickback.
• NEVER start or stop engine with electrical devices plugged in and turned on.
WARNING Fuel and its vapors are extremely
flammable and explosive which could cause burns, fire or explosion resulting in death or serious injury.
WHEN ADDING OR DRAINING FUEL
• Turn generator engine OFF and let it cool at least 2 minutes before removing fuel cap. Loosen cap slowly to relieve pressure in tank.
• Fill or drain fuel tank outdoors.
• DO NOT overfill tank. Allow space for fuel expansion.
• If fuel spills, wait until it evaporates before starting engine.
• Keep fuel away from sparks, open flames, pilot lights, heat, and other ignition sources.
• Check fuel lines, tank, cap and fittings frequently for cracks or leaks. Replace if necessary.
• DO NOT light a cigarette or smoke.
WHEN STARTING EQUIPMENT
• Ensure spark plug, muffler, fuel cap, and air cleaner are in place.
• DO NOT crank engine with spark plug removed.
WHEN OPERATING EQUIPMENT
• DO NOT operate this product inside any building, carport, porch, mobile equipment, marine applications, or enclosure.
• DO NOT tip engine or equipment at angle which causes fuel to spill.
• DO NOT stop engine by moving choke control to CHOKE (
WHEN TRANSPORTING, MOVING OR REPAIRING EQUIPMENT
• Transport/move/repair with fuel tank EMPTY or with fuel shutoff valve OFF (0).
• DO NOT tip engine or equipment at angle which causes fuel to spill.
• Disconnect spark plug wire.
WHEN STORING FUEL OR EQUIPMENT WITH FUEL IN TANK
• Store away from furnaces, stoves, water heaters, clothes dryers, or other appliances that have pilot light or other ignition source because they could ignite fuel vapors.
) position.
7
Not for
Reproduction
WARNING
electrical shock or burn resulting in death or serious injury.
• Use listed transfer equipment, suitable for the intended use, to prevent backfeed by isolating generator from electric utility workers.
• When using generator for backup power, notify utility company.
• Use a ground fault circuit interrupter (GFCI) in any damp or highly conductive area, such as metal decking or steel work.
• DO NOT touch bare wires or receptacles.
• DO NOT use generator with electrical cords which are worn, frayed, bare or otherwise damaged.
• DO NOT operate generator in the rain or wet weather.
• DO NOT handle generator or electrical cords while standing in water, while barefoot, or while hands or feet are wet.
• DO NOT allow unqualified persons or children to operate or service generator.
Generator voltage could cause
WARNING Starter and other rotating parts
could entangle hands, hair, clothing, or accessories resulting in serious injury.
• NEVER operate generator without protective housing or covers.
• DO NOT wear loose clothing, jewelry or anything that could be caught in the starter or other rotating parts.
• Tie up long hair and remove jewelry.
CAUTION Excessively high operating speeds
could result in minor injury. Excessively low operating speeds impose a heavy load.
• DO NOT tamper with governor spring, links or other parts to increase engine speed. Generator supplies correct rated frequency and voltage when running at governed speed.
• DO NOT modify generator in any way.
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage fuel tank causing a fire, resulting in
death or serious injury. Contact with muffler area could cause burns resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Keep at least 5 ft. (1.5 m) of clearance on all sides of generator including overhead.
• It is a violation of California Public Resource Code, Section 4442, to use or operate the engine on any forest­covered, brush-covered, or grass-covered land unless the exhaust system is equipped with a spark arrester, as defined in Section 4442, maintained in effective working order. Other states or federal jurisdictions may have similar laws.
Contact the original equipment manufacturer, retailer,
or dealer to obtain a spark arrester designed for the exhaust system installed on this engine.
• Replacement parts must be the same and installed in the same position as the original parts.
WARNING Unintentional sparking could cause
fire or electric shock resulting in death or serious injury.
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR GENERATOR
• Disconnect the spark plug wire from the spark plug and place the wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
• Use approved spark plug tester.
• DO NOT check for spark with spark plug removed.
NOTICE
capacity could damage generator and/or electrical devices connected to it.
• DO NOT exceed the generator’s wattage/amperage capacity. See Don’t Overload Generator in the Operation section.
• Start generator and let engine stabilize before connecting electrical loads.
• Connect electrical loads in OFF position, then turn ON for operation.
• Turn electrical loads OFF and disconnect from generator before stopping generator.
NOTICE
damage it and shorten its life.
• Use generator only for intended uses.
• If you have questions about intended use, ask dealer or contact local service center.
• Operate generator only on level surfaces.
• DO NOT expose generator to excessive moisture, dust, dirt, or corrosive vapors.
• DO NOT insert any objects through cooling slots.
• If connected devices overheat, turn them off and disconnect them from generator.
• Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
Exceeding generators wattage/amperage
Improper treatment of generator could
8 BRIGGSandSTRATTON.COM
Not for
Reproduction
Assembly
Your generator requires some assembly and is ready for use after it has been properly serviced with the recommended fuel and oil level is verified.
If you have any problems with the assembly of your generator, please call the generator helpline at (800) 743-4115. If calling for assistance, please have the model, revision, and serial number from the identification label available.
Unpack Generator
1. Set the carton on a rigid, flat surface.
2. Remove everything from carton except generator.
3. Open carton completely by cutting each corner from top to bottom.
4. Leave generator on carton to install wheel kit.
The generator is supplied with:
• Operator’s manual
• Wheel kit
Install Wheel Kit
NOTICE Wheel kit is not intended for over-the-road use.
Install the wheel kit as follows:
1. Tip generator so that engine end is up.
2. Slide a washer (A) over axle stud (B).
3. Slide a wheel (C) over axle stud (B). NOTICE Be sure to install wheel with raised hub
inboard.
4. Slide axle stud (B) through mounting bracket.
5. Insert retaining pin (D) through hole on axle stud.
6. Repeat steps 2 thru 5 to secure second wheel.
7. Line up holes in support leg (E) with holes in
generator frame.
8. Attach support leg using four capscrews (F) and four flange nuts (G). Tighten with 10 and 13 mm wrenches.
9. Return generator to normal operating position (resting on wheels and support leg).
Verify Engine Oil Level
The generator engine is shipped from the factory filled with oil (API SJ or higher 10W-30). This allows for generator operation in the widest range of temperature and climate conditions. Before starting the engine, check oil level and ensure that engine is serviced as described in Maintenance.
NOTICE Any attempt to crank or start the engine before it has been properly filled with the recommended oil could result in equipment failure.
• Refer to Maintenance for oil fill information.
• Damage to equipment resulting from failure to follow this
instruction will void warranty.
A
B
C
D
F
E
G
NOTICE See Oil in the Maintenance section to review oil recomendations. Verify provided oil in engine is the correct viscosity for current ambient temperature.
9
Not for
Reproduction
Add Fuel
Fuel must meet these requirements:
• Clean, fresh, unleaded gasoline.
• A minimum of 87 octane/87 AKI (91 RON). For high altitude use, see High Altitude.
• Gasoline with up to 10% ethanol (gasohol) is acceptable.
NOTICE Use of unapproved fuels could damage generator and voids warranty.
• DO NOT use unapproved gasoline such as E15 and E85.
• DO NOT mix oil in gasoline or modify engine to run on
alternate fuels.
To protect the fuel system from gum formation, mix in a fuel stabilizer when adding fuel. See Storage. All fuel is not the same. If you experience starting or performance problems after using fuel, switch to a different fuel provider or change brands. This engine is certified to operate on gasoline. The emission control system for this engine is EM (Engine Modifications).
WARNING Fuel and its vapors are extremely
flammable and explosive which could cause burns, fire or explosion resulting in death or serious injury.
WHEN ADDING FUEL
• Turn generator engine OFF and let it cool at least 2 minutes before removing fuel cap. Loosen cap slowly to relieve pressure in tank.
• Fill fuel tank outdoors.
• DO NOT overfill tank. Allow space for fuel expansion.
• If fuel spills, wait until it evaporates before starting engine.
• Keep fuel away from sparks, open flames, pilot lights, heat, and other ignition sources.
• Check fuel lines, tank, cap and fittings frequently for cracks or leaks. Replace if necessary.
• DO NOT light a cigarette or smoke.
1. Clean area around fuel fill cap, remove cap.
2. Slowly add unleaded gasoline (A) to fuel tank (B). Be careful not to fill above the baffle (C). This allows adequate space for fuel expansion as shown.
TANK
C
3. Install fuel cap and let any spilled fuel evaporate before starting engine.
High Altitude
At altitudes over 5,000 ft. (1524 m), a minimum 85 octane / 85 AKI (89 RON) gasoline is acceptable. To remain emissions compliant, high altitude adjustment is required. Operation without this adjustment will cause decreased performance, increased fuel consumption, and increased emissions. See an authorized dealer for high altitude adjustment
B
FUEL
A
information. Operation of the engine at altitudes below 2,500 ft. (762 m) with the high altitude kit is not recommended.
System Ground
The generator has a system ground that connects the generator frame components to the ground terminals on the AC output receptacles. The system ground is connected to the AC neutral wire (the neutral is bonded to the generator frame).
Special Requirements
There may be Federal or State Occupational Safety and Health Administration (OSHA) regulations, local codes, or ordinances that apply to the intended use of the generator. Please consult a qualified electrician, electrical inspector, or the local agency having jurisdiction:
• In some areas, generators are required to be registered with local utility companies.
• If the generator is used at a construction site, there may be additional regulations which must be observed.
Connecting to a Building’s Electrical System
Connections for standby power to a building’s electrical system must use a listed transfer switch installed by a current licensed electrician. The connection must isolate the generator power from the utility power and must comply with all applicable laws and electrical codes.
WARNING
electrical shock or burn resulting in death or serious injury.
• Use listed transfer equipment, suitable for the intended use, to prevent backfeed by isolating generator from electric utility workers.
• When using generator for backup power, notify utility company.
• Use a ground fault circuit interrupter (GFCI) in any damp or highly conductive area, such as metal decking or steel work.
• DO NOT touch bare wires or receptacles.
• DO NOT use generator with electrical cords which are worn, frayed, bare or otherwise damaged.
• DO NOT operate generator in the rain or wet weather.
• DO NOT handle generator or electrical cords while standing in water, while barefoot, or while hands or feet are wet.
• DO NOT allow unqualified persons or children to operate or service generator.
Generator voltage could cause
10 BRIGGSandSTRATTON.COM
Not for
Reproduction
Portable Generator Location
Before starting the portable generator there are two equally important safety concerns regarding carbon monoxide (CO) poisoning and fire that must be addressed.
NOTICE Satisfying the RISK OF CARBON MONOXIDE POISONING location requirements may not satisfy the fire location requirements. Satisfying the RISK OF FIRE location requirements may not satisfy the CARBON MONOXIDE POISONING location requirements.
Operation Location of Portable Generator to REDUCE THE RISK OF CARBON MONOXIDE POISONING
All fossil fuel burning equipment, such as a portable generator, contains carbon monoxide (CO) gas in the engine exhaust, a poisonous gas that could kill you in minutes. You CANNOT smell it, see it, or taste it. Even if you do not smell exhaust fumes, you could still be exposed to carbon monoxide gas. The following must be completed prior to starting the portable generator engine:
• By law it is required in many states to have a
Carbon Monoxide (CO) alarm (A) in operating condition in your home. Install/maintain battery­operated carbon monoxide alarms or plug-in carbon monoxide alarms with battery back-up according to the manufacturer’s instructions. A CO alarm is an electronic device that detects hazardous levels of CO. When there is a buildup of CO, the alarm will alert the occupants by flashing visual indicator light and alarm. Smoke alarms cannot detect CO gas.
A
• Operate this product ONLY outside far away from windows, doors and vents to reduce the risk of carbon monoxide gas from accumulating and potentially being drawn towards occupied spaces.
• DO NOT run this product inside homes, garages, basements, crawlspaces, sheds, or other partially­enclosed spaces even if using fans or opening doors and windows for ventilation. Carbon monoxide can quickly build up in these spaces and can linger for hours, even after this product has shut off.
• Your neighbor(s) home may be exposed to the engine exhaust from your portable generator and must be considered when deciding on a location for the safe operation of your portable generator.
• ALWAYS place this product downwind and point the engine exhaust away from occupied spaces.
If you start to feel sick, dizzy, or weak while using this product, get to fresh air RIGHT AWAY. See a doctor. You may have carbon monoxide poisoning.
11
Not for
Reproduction
EXAMPLE OF LOCATION TO REDUCE THE RISK OF CARBON MONOXIDE
POISONING
CO Alarm
S
A
H
U
X
E
T
(
C
O
)
KEEP
FAR AWAY
in Living Areas
Direct exhaust AWAY from windows, doors, and vents.
DO NOT OPERATE IN ANY OF THE FOLLOWING LOCATIONS
Only use OUTSIDE and FAR AWAY from windows, doors and vents.
Attic
Entryway,
Porch
Garage
Living Area
Basement
Crawlspace
U
A
H
X
E
S
T
(
C
O
)
Generator too close to home and exhaust directed towards windows, doors and vents.
12 BRIGGSandSTRATTON.COM
Not for
Reproduction
Operation Location of Portable Generator to REDUCE THE RISK OF FIRE
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage fuel tank causing a fire, resulting in death or serious injury.
• Portable generator must be at least 5 ft. (1.5 m) from any structure, overhang, trees, windows, doors, any wall opening, shrubs, or vegetation over 12 inches (30.5 cm) in height.
• DO NOT place portable generator under a deck or other type of structure that may confine airflow.
• Smoke alarm(s) MUST be installed and maintained indoors according to the manufacturer’s instructions/ recommendations. Carbon monoxide alarms cannot detect smoke.
• DO NOT place portable generator in manner other than shown.
EXAMPLE OF LOCATION TO REDUCE THE RISK OF FIRE
5 ft. (1.5 m) min.
H
A
X
E
U
S
T
(
C
O
)
5 ft. (1.5 m) min.
Direct exhaust AWAY from windows, doors, and vents.
13
Not for
Reproduction
Features and Controls
Read this Operator’s Manual and safety rules before operating your generator.
Compare the illustrations with your generator, to familiarize yourself with the locations of various controls and adjustments. Save this manual for future reference.
A
B
C
D
R
Q
E
F
G
H
J
K
A - Hour Meter — Displays and records how many
hours your generator has run (up to 9,999.9).
B - Engine Switch — Set this switch to ON (I) before
starting engine. Set switch to OFF (0) to shut off engine.
C - Main Breaker — The receptacles are provided
with a rocker switch main circuit breaker to protect the generator against electrical overload.
D - 120/240 Volt AC, 30 Amp Locking Receptacle
— May be used to supply electrical power for the operation of 120 and/or 240 Volt AC, 30 Amp, single phase, 60 Hz electrical, lighting, appliance, tool and motor loads.
E - Circuit Breakers (AC) — The 120 Volt AC, 20A
GFCI duplex receptacles are provided with “push to reset” circuit breakers to protect the generator against electrical overload.
F - 120 Volt AC, 20 Amp, GFCI Duplex Receptacles
— May be used to supply electrical power for the operation of 120 Volt AC, 20 Amp, single phase, 60 Hz electrical, lighting, appliance, tool and motor loads.
G - 120 Volt AC, 20 Amp, Duplex Receptacle
May be used to supply electrical power for the operation of 120 Volt AC, 20 Amp, single phase, 60 Hz electrical, lighting, appliance, tool and motor loads.
H - Oil Fill Cap/Dipstick — Check and add engine oil
here.
J - Oil Drain Plug — Drain engine oil here. K - Grounding Fastener — Consult your local agency
having jurisdiction for grounding requirements in your area.
P
N
M
L
L - Spark Arrester Muffler — Exhaust muffler lowers
engine noise and is equipped with a spark arrester screen.
M - Air Cleaner — Protects engine by filtering dust
and debris out of intake air.
N - Choke Lever — Used when starting a cold engine. P - Recoil Starter — Used to start the engine
manually.
Q - Fuel Valve — Used to turn fuel supply on and off
to engine.
R - Fuel Tank — Capacity of 7.5 U.S. gallons (28.4 l).
Items Not Shown: Engine Identification — Provides model, type and
code of engine. Please have these readily available if calling for assistance.
Identification Label — Provides model, revision and serial number of generator. Please have these readily available when calling for assistance.
14 BRIGGSandSTRATTON.COM
Not for
Reproduction
Cord Sets and Receptacles
Use only high quality, well-insulated, grounded extension cords with the generator’s receptacles. Inspect extension cords before each use.
Check the ratings of all extension cords before you use them. Check the operator’s manuals of devices for the manufacturer’s recommendations.
A double pole rocker switch main circuit breaker is provided to protect the locking receptacle. If this circuit breaker is tripped, all receptacles are disconnected.
WARNING Damaged or overloaded electrical
cords could overheat, arc, and burn resulting in death or serious injury.
• ONLY use cords rated for your loads.
• Follow all safeties on electrical cords.
• Inspect cord sets before each use.
120/240 Volt AC, 30 Amp, Locking Receptacle
Use a NEMA L14-30 plug with this receptacle. Connect a 4-wire cord set rated for 250 Volt AC loads at 30 Amps (or greater). You can use the same 4-wire cord if you plan to run a 120 Volt load.
4-Wire Cord Set
240V
120 Volt AC, 20 Amp, Duplex Receptacle
The duplex receptacle is protected against overload by a push-to-reset circuit breaker.
Use receptacle to operate 120 Volt AC, single-phase, 60 Hz electrical loads requiring up to 2,400 watts (2.4 kW) at 20 Amps of current. Use cord sets that are rated for 125 Volt AC loads at 20 Amps (or greater).
120 Volt AC, 20 Amp, GFCI Duplex Receptacles
Each GFCI duplex receptacle is protected against overload by a push–to–reset circuit breaker.
120V
Y (Hot)
NEMA L14-30
This receptacle powers 120/240 Volt AC, 60 Hz, single phase loads requiring up to 6,500 watts of power (6.5 kW) at 27.0 Amps for 240 Volts or two independent 120 Volt loads at 27.0 Amps each. The outlet is protected by a two pole rocker switch circuit breaker.
NOTICE
value greater than generator output capacity.
• NEVER attempt to power a device requiring more amperage than generator or receptacle can supply.
• DO NOT overload the generator. See Don’t Overload Generator.
Receptacles may be marked with rating
120V
W (Neutral)
X (Hot)
Ground (Green)
Use each receptacle to operate 120 Volt AC, single­phase, 60 Hz electrical loads requiring up to 2,400 watts (2.4 kW) at 20 Amps of current. Use cord sets that are rated for 125 Volt AC loads at 20 Amps (or greater).
15
Not for
Reproduction
Ground Fault Protection
The duplex receptacles are protected with Ground Fault Circuit Interruption (GFCI). This meets applicable federal, state and local codes. The generator’s locking receptacle is not protected by Ground Fault Circuit Interruption (GFCI).
The GFCI protects against electrical shock that may be caused if your body becomes a path which electricity travels to reach ground. This could happen if you touch a “Live” appliance or wire, or are touching plumbing or other materials that connect to the ground.
When protected by a GFCI, one may still feel a shock, but the GFCI should cut current off quickly enough so that a person in normal health should not suffer any serious electrical injury.
WARNING
electrical shock or burn resulting in death or serious injury.
• Contact with the hot and neutral conductor at the same time can cause electrical shock or burn, even if the circuit is GFCI protected.
• Before using the GFCI receptacle, ALWAYS push the test button to insure it works.
Generator voltage could cause
Testing the GFCI
Test your GFCI outlet prior to each use, as follows:
• Push the “Test” button. The “Reset” button should
pop out, which should allow no power to reach the outlet. Use a test lamp in each outlet to test this.
• If the GFCI tests good, restore power by pressing
the “Reset” button firmly until it is fully in place and locks in that position. If the GFCI outlet does not
reset properly, do not use the outlet. Call or take your generator to a local service center.
• If the GFCI trips by itself at any time, reset and
test the outlet. If the reset button does not pop
out when the test button is pressed, do not use the outlet. Call or take your generator to a local service center.
16 BRIGGSandSTRATTON.COM
Not for
Reproduction
Operation
Starting the Engine
Disconnect all electrical loads from the generator. Use the following start instructions:
1. Make sure unit is on a level surface. NOTICE Failure to start and operate the unit on a
level surface will cause the unit not to start or shut down during operation.
2. Turn the fuel valve (A) to the ON (I) position.
6. Move choke lever to HALF choke position, and pull recoil handle twice.
• If engine fails to start, repeat steps 5 thru 7.
7. Slowly move choke lever to RUN ( engine falters, move choke lever to HALF choke position until engine runs smoothly, and then to RUN ( ) position.
NOTICE If engine floods, place choke lever in RUN ( ) position and crank until engine starts.
NOTICE If engine starts after 3 pulls but fails to run, or if unit shuts down during operation, make sure unit is on a level surface and check for proper oil level in crankcase. This unit may be equipped with a low oil protection device. If so, oil must be at proper level for engine to start.
) position. If
A
3. Push choke lever (B) to CHOKE ( ) position.
B
4. Set engine switch (C) to ON (I) position.
C
5. Grasp recoil handle and pull slowly until slight resistance is felt. Then pull rapidly one time only to start engine.
• If engine starts, proceed to step 7.
• If engine fails to start, proceed to step 6.
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage fuel tank causing a fire, resulting in
death or serious injury. Contact with muffler area could cause burns resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Keep at least 5 ft. (1.5 m) of clearance on all sides of generator including overhead.
• It is a violation of California Public Resource Code, Section 4442, to use or operate the engine on any forest­covered, brush-covered, or grass-covered land unless the exhaust system is equipped with a spark arrester, as defined in Section 4442, maintained in effective working order. Other states or federal jurisdictions may have similar laws.
Contact the original equipment manufacturer, retailer,
or dealer to obtain a spark arrester designed for the exhaust system installed on this engine.
• Replacement parts must be the same and installed in the same position as the original parts.
WARNING Starter cord kickback (rapid
retraction) will pull hand and arm toward engine faster than you can let go which could cause broken bones, fractures,
bruises, or sprains resulting in serious injury.
• When starting engine, pull cord slowly until resistance is felt and then pull rapidly to avoid kickback.
• NEVER start or stop engine with electrical devices plugged in and turned on.
17
Not for
Reproduction
Connecting Electrical Loads
1. Let engine stabilize and warm up for a few minutes after starting.
2. Ensure main breaker is in ON (I) position.
3. Plug in and turn on the desired 120 and/ or 240 Volt AC, single phase, 60 Hz electrical loads.
NOTICE When plugging into the 120 Volt receptacles, plug items to be powered in sequence as shown below.
1
2
5
3
4
6
NOTICE
• DO NOT connect 240 Volt loads to 120 Volt duplex receptacles.
• DO NOT connect 3-phase loads to generator.
• DO NOT connect 50 Hz loads to generator.
• DO NOT OVERLOAD THE GENERATOR. See Don’t Overload Generator.
NOTICE
capacity could damage generator and/or electrical devices connected to it.
• DO NOT exceed the generator’s wattage/amperage
capacity. See Don’t Overload Generator in the Operation section.
• Start generator and let engine stabilize before connecting
electrical loads.
• Connect electrical loads in OFF position, then turn ON for
operation.
• Turn electrical loads OFF and disconnect from generator
before stopping generator.
Exceeding generators wattage/amperage
Stopping the Engine
1. Turn OFF and unplug all electrical loads from
generator panel receptacles. NEVER start or stop engine with electrical devices plugged in and turned ON.
2. Let engine run at no-load for several minutes to stabilize internal temperatures of engine and generator.
3. Push engine switch to OFF (0) position.
WARNING Fuel and its vapors are extremely
flammable and explosive which could cause burns, fire or explosion resulting in death or serious injury.
• DO NOT stop engine by moving choke lever to CHOKE
4. Move fuel valve to OFF (0) position.
( )position.
Low Oil Shutdown
If the engine oil drops below a preset level, an oil switch will stop the engine. Check oil level with dipstick.
If oil level is between ADD and FULL mark on dipstick:
1. DO NOT try to restart the engine.
2. Contact an Authorized Briggs & Stratton Service Dealer.
3. DO NOT operate engine until oil level is corrected.
If oil level is below ADD mark on dipstick:
1. Add oil to bring level to FULL mark.
2. Restart engine and if the engine stops again a low oil condition may still exist. DO NOT try to restart the engine.
3. Contact an Authorized Briggs & Stratton Service Dealer.
4. DO NOT operate engine until oil level is corrected.
Cold Weather Operation
Under certain weather conditions (temperatures below 40°F [4°C] combined with high humidity), your generator may experience icing of the carburetor and/ or the crankcase breather system. To reduce this problem, you need to perform the following:
1. Make sure generator has clean, fresh fuel.
2. Turn the fuel valve to the ON (I) position.
3. Use SAE 5W-30 oil.
4. Check oil level daily or after every eight (8) hours of operation.
5. Maintain generator following Maintenance Schedule in Maintenance section.
6. Shelter unit from elements.
18 BRIGGSandSTRATTON.COM
Not for
Reproduction
Creating a Temporary Cold Weather Shelter
1. For temporary shelter, the original shipping carton can be used.
2. Cut off top carton flaps and one long side of carton to expose muffler side of unit. If required, tape up other sides of carton to fit over generator as shown.
Wind
NOTICE If required, remove wheel kit to fit carton over generator as shown.
3. Cut appropriate slots to access receptacles of unit.
4. Face exposed end away from wind and elements.
5. Locate generator as described in the section Generator Location. Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes or other openings.
WARNING POISONOUS GAS HAZARD.
Engine exhaust contains carbon monoxide, a poisonous gas that could kill you in
minutes. You CANNOT smell it, see it, or taste it. Even if you do not smell exhaust fumes, you could still be exposed to carbon monoxide gas.
• Operate this product ONLY outside far away from windows, doors and vents to reduce the risk of carbon monoxide gas from accumulating and potentially being drawn towards occupied spaces.
• Install battery-operated carbon monoxide alarms or plug-in carbon monoxide alarms with battery back-up according to the manufacturer’s instructions. Smoke alarms cannot detect carbon monoxide gas.
• DO NOT run this product inside homes, garages, basements, crawlspaces, sheds, or other partially­enclosed spaces even if using fans or opening doors and windows for ventilation. Carbon monoxide can quickly build up in these spaces and can linger for hours, even after this product has shut off.
• ALWAYS place this product downwind and point the engine exhaust away from occupied spaces.
If you start to feel sick, dizzy, or weak while using this product, get to fresh air RIGHT AWAY. See a doctor. You may have carbon monoxide poisoning.
6. Start generator as described in the section Starting the Engine, then place carton over generator. Keep at least 5 ft. (1.5 m) clearance on all sides of generator including overhead with shelter in place.
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage fuel tank causing a fire, resulting in
death or serious injury. Contact with muffler area could cause burns resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Keep at least 5 ft. (1.5 m) of clearance on all sides of generator including overhead.
• Remove shelter when temperatures are above 40°F [4°C].
7. Remove shelter when temperatures are above 40°F [4°C].
8. Turn engine OFF and let cool two (2) minutes before refueling. Let any spilled fuel evaporate before starting engine.
Building a Cold Weather Shelter
1. Using non combustible material with a fire rating of at least one hour, build a shelter that will enclose three sides and the top of the generator. Make sure muffler side of generator is exposed.
NOTICE Contact your local building material supplier for non combustible materials with a fire rating of at least one hour.
NOTICE Be sure shelter can easily be repositioned for change in wind direction.
2. DO NOT enclose generator any more than shown. Shelter should hold enough heat created by the generator to prevent icing problem.
NOTICE If a wheel kit is installed on the generator, enlarge shelter accordingly.
3. Follow steps 3 through 8 as described previously in Creating a Temporary Cold Weather Shelter.
19
Not for
Reproduction
Don’t Overload Generator
Capacity
You must make sure your generator can supply enough rated (running) and surge (starting) watts for the items you will power at the same time. Follow these simple steps:
1. Select the items you will power at the same time.
2. Total the rated (running) watts of these items. This is the amount of power your generator must produce to keep your items running. See the table on the right.
3. Estimate how many surge (starting) watts you will need. Surge wattage is the short burst of power needed to start electric motor-driven tools or appliances such as a circular saw or refrigerator. Because not all motors start at the same time, total surge watts can be estimated by adding only the item(s) with the highest additional surge watts to the total rated watts from step 2.
Example:
Tool or Appliance
Window Air Conditioner
Refrigerator 800 1600 Deep Freezer 500 500 Television 500 — Light (75 Watts) 75
Total Rated (Running) Watts = 3075 Highest Additional Surge (Starting) Watts = 1800 Total Generator Output Required = 4875
Power Management
To prolong the life of your generator and attached devices, it is important to take care when adding electrical loads to your generator. There should be nothing connected to the generator outlets before starting its engine. The correct and safe way to manage generator power is to sequentially add loads as follows:
1. With nothing connected to the generator, start the engine as described in this manual.
2. Plug in and turn on the first load, preferably the largest load you have.
3. Permit the generator output to stabilize (engine runs smoothly and attached device operates properly).
4. Plug in and turn on the next load.
5. Again, permit the generator to stabilize.
6. Repeat steps 4 and 5 for each additional load.
Rated
(Running)
Watts
1200 1800
3075 Total
Running Watts
Additional Surge
(Starting) Watts
1800 Highest
Additional Surge
Watts
NEVER add more loads than the generator capacity. Take special care to consider surge loads in generator capacity, as described above.
Rated*
Tool or Appliance
Essentials
Light Bulb - 75 watt 75 ­Deep Freezer 500 500 Sump Pump 800 1200 Refrigerator/Freezer - 18 Cu. Ft. 800 1600 Water Well Pump - 1/3 HP 1000 2000
Heating/Cooling
Window AC - 10,000 BTU 1200 1800 Window Fan 300 600 Furnace Fan Blower - 1/2 HP 800 1300
Kitchen
Microwave Oven - 1000 Watt 1000 ­Coffee Maker 1500 ­Electric Stove - Single Element 1500 ­Hot Plate 2500 -
Family Room
DVD/CD Player 100 ­VCR 100 ­Stereo Receiver 450 ­Color Television - 27” 500 ­Personal Computer w/17” monitor 800 -
Other
Security System 180 ­AM/FM Clock Radio 300 ­Garage Door Opener - 1/2 HP 480 520 Electric Water Heater - 40 Gallon 4000 -
DIY/Job Site
Quartz Halogen Work Light 1000 ­Airless Sprayer - 1/3 HP 600 1200 Reciprocating Saw 960 960 Electric Drill - 1/2 HP 1000 1000 Circular Saw - 7 1/4” 1500 1500 Miter Saw - 10” 1800 1800 Table Planer - 6” 1800 1800 Table Saw/Radial Arm Saw - 10” 2000 2000 Air Compressor - 1-1/2 HP 2500 2500
* Wattages listed are approximate only. Check tool or
appliance for actual wattage.
(Running)
Watts
Additional
Surge
(Starting)
Watts
20 BRIGGSandSTRATTON.COM
Not for
Reproduction
Maintenance
Maintenance Schedule
Follow the hourly or calendar intervals, whichever occurs first. More frequent service is required when operating in adverse conditions noted below.
First 5 Hours
• Change engine oil
Every 8 Hours or Daily
• Clean debris
• Check engine oil level
Every 25 Hours or Yearly
• Clean engine air filter
Every 50 Hours or Yearly
• Change engine oil
Yearly
• Replace engine air filter
• Service fuel valve
• Service spark plug
• Inspect muffler and spark arrester
• Clean cooling system
1 Service more often under dirty or dusty conditions.
General Recommendations
Regular maintenance will improve the performance and extend the life of the generator. See any authorized dealer for service.
The generator’s warranty does not cover items that have been subjected to operator abuse or negligence. To receive full value from the warranty, the operator must maintain the generator as instructed in this manual.
Some adjustments will need to be made periodically to properly maintain your generator.
All service and adjustments should be made at least once each season. A new spark plug and clean air filter assure proper fuel-air mixture and help your engine run better and last longer. Follow the requirements in the Maintenance Schedule chart above.
1
1
1
1
Generator Maintenance
Generator maintenance consists of keeping the unit clean and dry. Operate and store the unit in a clean dry environment where it will not be exposed to excessive dust, dirt, moisture, or any corrosive vapors. Cooling air slots in the generator must not become clogged with snow, leaves, or any other foreign material.
NOTICE DO NOT use water or other liquids to clean generator. Liquids can enter engine fuel system, causing poor performance and/or failure to occur. In addition, if liquid enters generator through cooling air slots, some of the liquid will be retained in voids and cracks of the rotor and stator winding insulation. Liquid and dirt buildup on the generator internal windings will eventually decrease the insulation resistance of these windings.
Cleaning
Daily or before use, look around and underneath the generator for signs of oil or fuel leaks. Clean accumulated debris from inside and outside the generator. Keep the linkage, spring and other engine controls clean. Keep the area around and behind the muffler free from any combustible debris. Inspect cooling air slots and openings on generator. These openings must be kept clean and unobstructed.
Engine parts should be kept clean to reduce the risk of overheating and ignition of accumulated debris:
• Use a damp cloth to wipe exterior surfaces clean.
NOTICE
damage it and shorten its life.
• DO NOT expose generator to excessive moisture, dust, dirt, or corrosive vapors.
• DO NOT insert any objects through cooling slots.
• Use a soft bristle brush to loosen caked on dirt or
• Use a vacuum cleaner to pick up loose dirt and
Improper treatment of generator could
oil.
debris.
Fuel Valve Maintenance
The fuel valve is equipped with a fuel sediment cup, screen, and o-ring that need to be cleaned.
1. Move fuel valve to OFF (0) position.
2. Remove sediment cup (A) from fuel valve.
Remove o-ring (B) and screen (C) from fuel valve.
Emissions Control Maintenance, replacement, or repair of the
emissions control devices and systems may be performed by any non-road engine repair establishment or individual. However, to obtain
”no charge” emissions control service, the work must be performed by a factory authorized dealer. See the Emissions Warranty.
C
B
A
21
Not for
Reproduction
3. Wash sediment cup, o-ring, and screen in a nonflammable solvent. Dry them thoroughly.
4. Place screen and o-ring into fuel valve. Install sediment cup and tighten securely.
5. Move fuel valve to ON (I) position, and check for leaks. Replace fuel valve if there is any leakage.
Engine Maintenance
WARNING Unintentional sparking could cause
fire or electric shock resulting in death or serious injury.
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR GENERATOR
• Disconnect the spark plug wire from the spark plug and place the wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
• Use approved spark plug tester.
• DO NOT check for spark with spark plug removed.
Checking Oil Level
Oil level should be checked prior to each use or at least every 8 hours of operation. Keep oil level maintained.
1. Make sure generator is on a level surface.
2. Clean area around oil fill, remove oil cap/dipstick and wipe dipstick with clean cloth. Replace dipstick. Remove and and check oil level.
NOTICE DO NOT screw in dipstick when checking oil level.
3. Verify oil is at FULL mark (A) on dipstick. Replace and tighten oil cap/dipstick.
Oil
Oil Recommendations
We recommend the use of Briggs & Stratton Warranty Certified oils for best performance. Other high-quality detergent oils are acceptable if classified for service SF, SG, SH, SJ or higher. DO NOT use special additives.
Outdoor temperatures determine the proper oil viscosity for the engine. Use the chart to select the best viscosity for the outdoor temperature range expected.
* Below 40°F (4°C) the use of SAE 30 will result in hard
starting.
** Above 80°F (27°C) the use of 10W30 may cause
increased oil consumption. Check oil level more frequently.
A
Adding Engine Oil
1. Make sure generator is on a level surface.
2. Check oil level as described in Checking Oil Level.
3. If needed, slowly pour oil into oil fill opening to the FULL mark on dipstick. DO NOT overfill.
NOTICE Overfilling with oil could cause the engine to not start, or hard starting.
• DO NOT overfill.
• If over the FULL mark on dipstick, drain oil to reduce oil
level to FULL mark on dipstick.
4. Replace and tighten oil cap/dipstick.
22 BRIGGSandSTRATTON.COM
Not for
Reproduction
Changing Engine Oil
If you are using your generator under extremely dirty or dusty conditions, or in extremely hot weather, change the oil more often.
Service Air Cleaner
Your engine will not run properly and may be damaged if you run it with a dirty air cleaner. Clean or replace more often if operating under dusty or dirty conditions.
CAUTION Avoid prolonged or repeated skin
contact with used motor oil.
• Used motor oil has been shown to cause skin cancer in certain laboratory animals.
• Thoroughly wash exposed areas with soap and water.
KEEP OUT OF REACH OF CHILDREN.
DON’T POLLUTE. CONSERVE RESOURCES. RETURN USED OIL TO COLLECTION CENTERS.
Change the oil while the engine is still warm from running, as follows:
1. Make sure unit is on a level surface.
2. Disconnect the spark plug wire from the spark plug and place the wire where it cannot contact spark plug.
3. Clean area around oil drain plug (A). The oil drain plug is located at base of engine, opposite carburetor.
A
4. Remove oil drain plug and drain oil completely into a suitable container.
5. Reinstall oil drain plug and tighten securely. Remove oil cap/dipstick.
6. Slowly pour recommended oil (about 36 oz. (1 liter)) into oil fill opening. Pause to permit oil to settle. Fill to FULL mark on dipstick.
7. Wipe dipstick clean each time oil level is checked. DO NOT overfill.
8. Reinstall oil cap/dipstick. Tighten cap securely.
9. Wipe up any spilled oil.
To service the air cleaner, follow these steps:
1. Loosen screws (B) and remove air cleaner cover (C).
E
D
C
B
2. Carefully remove cartridge (D) from base (E).
3. Install clean (or new) air cleaner assembly inside cover. Dispose of old filter properly.
4. Assemble air cleaner cover onto base and tighten screws.
Service Spark Plug
Changing the spark plug will help your engine to start easier and run better.
1. Clean area around spark plug.
2. Remove and inspect spark plug.
3. Replace spark plug if electrodes are pitted, burned or porcelain is cracked. Use the recommended replacement spark plug. See Specifications.
4. Check electrode gap with wire feeler gauge and reset spark plug gap to recommended gap if necessary (see Specifications).
5. Install spark plug and tighten firmly.
23
Not for
Reproduction
Inspect Muffler and Spark Arrester
The engine exhaust muffler has a spark arrester screen. Inspect the muffler for cracks, corrosion, or other damage. Inspect spark arrester screen for damage or carbon blockage. Clean if carbon blockage is found or replace if damaged. If replacement parts are required, make sure to use only original equipment replacement parts.
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage fuel tank causing a fire, resulting in
death or serious injury. Contact with muffler area could cause burns resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Keep at least 5 ft. (1.5 m) of clearance on all sides of generator including overhead.
• It is a violation of California Public Resource Code, Section 4442, to use or operate the engine on any forest­covered, brush-covered, or grass-covered land unless the exhaust system is equipped with a spark arrester, as defined in Section 4442, maintained in effective working order. Other states or federal jurisdictions may have similar laws.
Contact the original equipment manufacturer, retailer,
or dealer to obtain a spark arrester designed for the exhaust system installed on this engine.
• Replacement parts must be the same and installed in the same position as the original parts.
Clean or replace spark arrester as follows:
1. Remove four screws that connect heat shield (A) to muffler (B).
C
Clean Cooling System
Over time debris may accumulate in cylinder cooling fins and cannot be observed without partial engine disassembly. For this reason, we recommend you have a Briggs & Stratton authorized dealer clean the cooling system (D) per recommended intervals (see Maintenance Schedule in the Maintenance section). Equally important is to keep top of engine free from debris. Also see Cleaning.
D
Carburetor Adjustment
The carburetor on this engine is low emission. It is equipped with a non-adjustable idle mixture valve. Top speed has been set at the factory. If adjustment is required, see a Briggs & Stratton authorized dealer.
CAUTION Excessively high operating speeds
could result in minor injury. Excessively low operating speeds impose a heavy load.
• DO NOT tamper with governor spring, links or other parts to increase engine speed. Generator supplies correct rated frequency and voltage when running at governed speed.
• DO NOT modify generator in any way.
A
B
2. Remove four screws that attach spark arrester
screen (C).
3. Obtain a replacement screen if torn, perforated or otherwise damaged. DO NOT use a defective screen. If screen is not damaged, clean it with commercial solvent.
4. Reattach screen and muffler guard.
24 BRIGGSandSTRATTON.COM
Not for
Reproduction
Storage
The generator should be started at least once every seven days and allowed to run at least 30 minutes. If this cannot be done and you must store the unit for more than 30 days, use the following guidelines to prepare it for storage.
Generator Storage
• Clean the generator as outlined in Cleaning.
• Check that cooling air slots and openings on generator are open and unobstructed.
Long Term Storage Instructions
Fuel can become stale when stored over 30 days. Stale fuel causes acid and gum deposits to form in the fuel system or on essential carburetor parts. To keep fuel fresh, use Briggs & Stratton® Advanced Formula Fuel Treatment & Stabilizer, available wherever Briggs & Stratton genuine service parts are sold.
There is no need to drain gasoline from the engine if a fuel stabilizer is added according to instructions. Run the engine for 2 minutes to circulate the stabilizer throughout the fuel system before storage.
If gasoline in the engine has not been treated with a fuel stabilizer, it must be drained into an approved container. Run the engine until it stops from lack of fuel. The use of a fuel stabilizer in the storage container is recommended to maintain freshness.
Change Engine Oil
While engine is still warm, drain oil from crankcase. Refill with recommended grade. See Changing Engine Oil.
Other Storage Tips
1. DO NOT store fuel from one season to another unless it has been treated as described in Long Term Storage Instructions.
2. Replace fuel container if it starts to rust. Rust and/ or dirt in fuel can cause problems if it’s used with this unit.
3. Cover unit with a suitable protective cover that does not retain moisture.
WARNING Storage covers could cause a fire
resulting in death or serious injury.
• DO NOT place a storage cover over a hot generator.
• Let equipment cool for a sufficient time before placing the cover on the equipment.
4. Store generator in clean, dry area.
WARNING Fuel and its vapors are extremely
flammable and explosive which could cause burns, fire or explosion resulting in death or serious injury.
WHEN STORING FUEL OR EQUIPMENT WITH FUEL IN TANK
• Store away from furnaces, stoves, water heaters, clothes dryers or other appliances that have pilot light or other ignition source because they could ignite fuel vapors.
WHEN DRAINING FUEL
• Turn generator engine OFF and let it cool at least 2 minutes before removing fuel cap. Loosen cap slowly to relieve pressure in tank.
• Drain fuel tank outdoors.
• Keep fuel away from sparks, open flames, pilot lights, heat, and other ignition sources.
• Check fuel lines, tank, cap and fittings frequently for cracks or leaks. Replace if necessary.
• DO NOT light a cigarette or smoke.
25
Not for
Reproduction
Troubleshooting
Problem Cause Correction
Engine is running, but no AC output is available.
Engine runs good at no-load but “bogs down” when loads are connected.
1. One of the circuit breakers is open.
2. Fault in generator.
3. Poor connection or defective cord set.
4. Connected device is bad.
1. Short circuit in a connected load.
2. Engine speed is too slow.
3. Generator is overloaded.
4. Shorted generator circuit.
5. Clogged or dirty fuel filter.
1. Reset circuit breaker.
2. Contact authorized service facility.
3. Check and repair.
4. Connect another device that is in good condition.
1. Disconnect shorted electrical load.
2. Contact authorized service facility.
3. See Don’t Overload Generator.
4. Contact authorized service facility.
5. Clean or replace fuel filter.
Engine will not start, starts and runs rough or shuts down when running.
Engine lacks power.
1. Engine rocker switch set to OFF (0) position.
2. Fuel Valve is in OFF (0) position.
3. Low oil level.
4. Dirty air cleaner.
5. Clogged or dirty fuel filter.
6. Out of fuel.
7. Stale fuel.
8. Spark plug wire not connected to spark plug.
9. Bad spark plug.
10. Water in fuel.
11. Flooded.
12. Excessively rich fuel mixture.
13. Intake valve stuck open or closed.
14. Engine has lost compression.
1. Load is too high.
2. Dirty air filter.
3. Clogged or dirty fuel filter.
1. Set engine rocker switch to ON (I) position.
2. Turn fuel valve to ON (I) position.
3. Fill crankcase to proper level or place generator on level surface.
4. Clean or replace air cleaner.
5. Clogged or dirty fuel filter.
6. Fill fuel tank.
7. Drain fuel tank and carburetor; fill with fresh fuel.
8. Connect wire to spark plug.
9. Replace spark plug.
10. Drain gas tank and carburetor; fill with fresh fuel.
11. Wait 5 minutes and re-crank engine.
12. Contact authorized service facility.
13. Contact authorized service facility.
14. Contact authorized service facility.
1. See Don’t Overload Generator.
2. Replace air filter.
3. Clean or replace fuel filter.
Engine “hunts” or falters.
1. Carburetor is running too rich or too lean.
2. Clogged or dirty fuel filter.
1. Contact authorized service facility.
2. Clean or replace fuel filter.
26 BRIGGSandSTRATTON.COM
Not for
Reproduction
Schematic
27
Loading...
+ 61 hidden pages