This generator is certified in accordance with CSA (Canadian Standards Association) standard C22.2 No. 100-04
(motors and generators) and rated in accordance with PGMA (Portable Generator Manufacturers’ Association)
standard PGMA G200 (Standard for Testing and Validating Performance of Portable Generators).
BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC
MILWAUKEE, WISCONSIN, U.S.A.
Manual No. 80012142 Revision -
Not for
Reproduction
Thank you for purchasing this quality-built Briggs & Stratton® generator. We are pleased that you’ve placed your
confidence in the Briggs & Stratton brand. When operated and maintained according to the instructions in this
manual, your Briggs & Stratton generator will provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with generator
products and how to avoid them. This generator is designed and intended only for supplying electrical power
for operating compatible electrical lighting, appliances, tools and motor loads, and is not intended for any other
purpose. It is important that you read and understand these instructions thoroughly before attempting to start or
operate this equipment. Save these original instructions for future reference.
This generator requires final assembly before use. Refer to the Assembly section of this manual for
instructions on final assembly procedures. Follow the instructions completely.
Where to Find Us
You never have to look far to find Briggs & Stratton support and service for your generator. Consult your Yellow
Pages. There are over 30,000 Briggs & Stratton authorized service dealers worldwide who provide quality service.
You can also contact Briggs & Stratton Customer Service by phone at (800) 743-4115, or on the Internet at
BRIGGSandSTRATTON.COM.
Generator Engine
Model Number ______________________ Model Number ________________________
Revision
Serial Number
Date Purchased ____________________
____________________ Type Number _________________________
_________________Code Number _________________________
Safe operation of the portable generator requires the completion of the following tasks:
Carbon Monoxide (CO) Alarm
Carbon monoxide (CO) alarm(s) in working order.
Smoke Alarm
Smoke alarm(s) in working order.
Generator Location
Generator placed in a Carbon Monoxide (CO) safe zone. See Generator Location to reduce the Risk of
Carbon Monoxide Poisoning.
Generator placed in a fire safe zone. See Generator Location to reduce the Risk of Fire.
Generator located on flat and level surface.
Oil and Fuel
Engine has proper oil level. See Verify Engine Oil Level.
Fuel tank filled at or below baffle. See Add Fuel.
Inspect fuel lines, tank, cap and fittings each time before using generator. DO NOT use if fuel leak or damage
is found.
Electrical
When connecting to a buildings electrical system install listed transfer equipment. See Connecting to a
Building’s Electrical System.
Electrical cords are rated for intended loads. See Cord Sets and Receptacles.
Electrical cords do not run through doorways, windows, holes in ceilings, walls or floors.
Inspect electrical cords thoroughly before each use. DO NOT use if damaged.
All labeled electrical cord safeties are understood and being followed.
Operation
Start engine. See Starting the Engine.
3
Not for
Reproduction
Operator Safety
Safety Labels
The generator safety labels shown below and on the next page are placed on your portable generator to draw
attention to potential safety hazards.
202997
4 BRIGGSandSTRATTON.COM
Not for
Reproduction
5
Not for
Reproduction
Equipment Description
Read this manual carefully and become
familiar with your generator. Know its
applications, its limitations and any hazards
involved.
The generator is an engine-driven, revolving field,
alternating current (AC) generator equipped with a
voltage regulator. The voltage regulator is designed to
automatically maintain a constant output voltage level.
It was designed to supply electrical power for operating
compatible electrical lighting, appliances, tools and
motor loads. The generator’s revolving field is driven at
about 3600 rpm by a single cylinder engine.
Important Safety Information
The manufacturer cannot possibly anticipate every
possible circumstance that might involve a hazard.
The warnings in this manual, and the tags and decals
affixed to the unit are, therefore, not all-inclusive.
If you use a procedure, work method or operating
technique that the manufacturer does not specifically
recommend, you must satisfy yourself that it is safe
for you and others. You must also make sure that the
procedure, work method or operating technique that
you choose does not render the generator unsafe.
Safety Symbols and Meanings
NOTICE
capacity could damage generator and/or electrical
devices connected to it.
• DO NOT exceed the generator’s wattage/amperage
capacity. See Don’t Overload Generator in the Operation
section.
Every effort has been made to ensure that the
information in this manual is both accurate and current.
However, the manufacturer reserves the right to
change, alter or otherwise improve the generator and
this documentation at any time without prior notice.
The Emission Control System for this generator is
warranted for standards set by the Environmental
Protection Agency and the California Air Resources
Board.
This spark ignition system complies with the Canadian
standard ICES-002.
Exceeding generators wattage/amperage
Toxic Fumes
Fire
Moving Parts
The safety alert symbol indicates a potential
personal injury hazard. A signal word (DANGER,
WARNING, or CAUTION) is used with the alert symbol
to designate a degree or level of hazard seriousness.
A safety symbol may be used to represent the type of
hazard. The signal word NOTICE is used to address
practices not related to personal injury.
DANGER indicates a hazard which, if not avoided,
will result in death or serious injury.
WARNING indicates a hazard which, if not
avoided, could result in death or serious injury.
CAUTION indicates a hazard which, if not
avoided, could result in minor or moderate injury.
NOTICE address practices not related to personal
injury.
Kickback
Explosion
Flying Objects
Electrical Shock
Operator’s Manual
Hot Surface
6 BRIGGSandSTRATTON.COM
Not for
Reproduction
WARNING POISONOUS GAS HAZARD.
Engine exhaust contains carbon monoxide,
a poisonous gas that could kill you in
minutes. You CANNOT smell it, see it, or
taste it. Even if you do not smell exhaust fumes, you
could still be exposed to carbon monoxide gas.
• Operate this product ONLY outside far away from
windows, doors and vents to reduce the risk of carbon
monoxide gas from accumulating and potentially being
drawn towards occupied spaces.
• Install battery-operated carbon monoxide alarms or
plug-in carbon monoxide alarms with battery back-up
according to the manufacturer’s instructions. Smoke
alarms cannot detect carbon monoxide gas.
• DO NOT run this product inside homes, garages,
basements, crawlspaces, sheds, or other partiallyenclosed spaces even if using fans or opening doors
and windows for ventilation. Carbon monoxide can
quickly build up in these spaces and can linger for hours,
even after this product has shut off.
• ALWAYS place this product downwind and point the
engine exhaust away from occupied spaces.
If you start to feel sick, dizzy, or weak while using this
product, get to fresh air RIGHT AWAY. See a doctor. You
may have carbon monoxide poisoning.
WARNING The engine exhaust from this
product contains chemicals known to the State of
California to cause cancer, birth defects, or other
reproductive harm.
WARNING Certain components in this product
and related accessories contain chemicals known to
the State of California to cause cancer, birth defects
or other reproductive harm. Wash hands after
handling.
WARNING
• This generator does not meet U. S. Coast Guard
Regulation 33CFR-183 and should not be used on
marine applications.
• Failure to use the appropriate U. S. Coast Guard
approved generator could result in death or serious injury.
WARNING Starter cord kickback (rapid
retraction) will pull hand and arm toward
engine faster than you can let go which
could cause broken bones, fractures,
bruises, or sprains resulting in serious injury.
• When starting engine, pull cord slowly until resistance is
felt and then pull rapidly to avoid kickback.
• NEVER start or stop engine with electrical devices
plugged in and turned on.
WARNING Fuel and its vapors are extremely
flammable and explosive which
could cause burns, fire or explosion
resulting in death or serious injury.
WHEN ADDING OR DRAINING FUEL
• Turn generator engine OFF and let it cool at least 2
minutes before removing fuel cap. Loosen cap slowly to
relieve pressure in tank.
• Fill or drain fuel tank outdoors.
• DO NOT overfill tank. Allow space for fuel expansion.
• If fuel spills, wait until it evaporates before starting engine.
• Keep fuel away from sparks, open flames, pilot lights,
heat, and other ignition sources.
• Check fuel lines, tank, cap and fittings frequently for
cracks or leaks. Replace if necessary.
• DO NOT light a cigarette or smoke.
WHEN STARTING EQUIPMENT
• Ensure spark plug, muffler, fuel cap, and air cleaner are
in place.
• DO NOT crank engine with spark plug removed.
WHEN OPERATING EQUIPMENT
• DO NOT operate this product inside any building,
carport, porch, mobile equipment, marine applications, or
enclosure.
• DO NOT tip engine or equipment at angle which causes
fuel to spill.
• DO NOT stop engine by moving choke control to
CHOKE (
WHEN TRANSPORTING, MOVING OR REPAIRING
EQUIPMENT
• Transport/move/repair with fuel tank EMPTY or with fuel
shutoff valve OFF (0).
• DO NOT tip engine or equipment at angle which causes
fuel to spill.
• Disconnect spark plug wire.
WHEN STORING FUEL OR EQUIPMENT WITH FUEL IN
TANK
• Store away from furnaces, stoves, water heaters, clothes
dryers, or other appliances that have pilot light or other
ignition source because they could ignite fuel vapors.
) position.
7
Not for
Reproduction
WARNING
electrical shock or burn resulting in death or
serious injury.
• Use listed transfer equipment, suitable for the intended
use, to prevent backfeed by isolating generator from
electric utility workers.
• When using generator for backup power, notify utility
company.
• Use a ground fault circuit interrupter (GFCI) in any damp
or highly conductive area, such as metal decking or steel
work.
• DO NOT touch bare wires or receptacles.
• DO NOT use generator with electrical cords which are
worn, frayed, bare or otherwise damaged.
• DO NOT operate generator in the rain or wet weather.
• DO NOT handle generator or electrical cords while
standing in water, while barefoot, or while hands or feet
are wet.
• DO NOT allow unqualified persons or children to operate
or service generator.
Generator voltage could cause
WARNING Starter and other rotating parts
could entangle hands, hair, clothing, or
accessories resulting in serious injury.
• NEVER operate generator without protective housing or
covers.
• DO NOT wear loose clothing, jewelry or anything that
could be caught in the starter or other rotating parts.
• Tie up long hair and remove jewelry.
CAUTION Excessively high operating speeds
could result in minor injury.
Excessively low operating speeds impose a heavy
load.
• DO NOT tamper with governor spring, links or other parts
to increase engine speed. Generator supplies correct
rated frequency and voltage when running at governed
speed.
• DO NOT modify generator in any way.
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage
fuel tank causing a fire, resulting in
death or serious injury.
Contact with muffler area could cause burns
resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Keep at least 5 ft. (1.5 m) of clearance on all sides of
generator including overhead.
• It is a violation of California Public Resource Code,
Section 4442, to use or operate the engine on any forestcovered, brush-covered, or grass-covered land unless
the exhaust system is equipped with a spark arrester, as
defined in Section 4442, maintained in effective working
order. Other states or federal jurisdictions may have
similar laws.
Contact the original equipment manufacturer, retailer,
or dealer to obtain a spark arrester designed for the
exhaust system installed on this engine.
• Replacement parts must be the same and installed in the
same position as the original parts.
WARNING Unintentional sparking could cause
fire or electric shock resulting in
death or serious injury.
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR
GENERATOR
• Disconnect the spark plug wire from the spark plug and
place the wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
• Use approved spark plug tester.
• DO NOT check for spark with spark plug removed.
NOTICE
capacity could damage generator and/or electrical
devices connected to it.
• DO NOT exceed the generator’s wattage/amperage
capacity. See Don’t Overload Generator in the Operation
section.
• Start generator and let engine stabilize before connecting
electrical loads.
• Connect electrical loads in OFF position, then turn ON for
operation.
• Turn electrical loads OFF and disconnect from generator
before stopping generator.
NOTICE
damage it and shorten its life.
• Use generator only for intended uses.
• If you have questions about intended use, ask dealer or
contact local service center.
• Operate generator only on level surfaces.
• DO NOT expose generator to excessive moisture, dust,
dirt, or corrosive vapors.
• DO NOT insert any objects through cooling slots.
• If connected devices overheat, turn them off and
disconnect them from generator.
• Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
Exceeding generators wattage/amperage
Improper treatment of generator could
8 BRIGGSandSTRATTON.COM
Not for
Reproduction
Assembly
Your generator requires some assembly and is ready
for use after it has been properly serviced with the
recommended fuel and oil level is verified.
If you have any problems with the assembly of
your generator, please call the generator helpline
at (800) 743-4115. If calling for assistance, please
have the model, revision, and serial number from the
identification label available.
Unpack Generator
1. Set the carton on a rigid, flat surface.
2. Remove everything from carton except generator.
3. Open carton completely by cutting each corner
from top to bottom.
4. Leave generator on carton to install wheel kit.
The generator is supplied with:
• Operator’s manual
• Wheel kit
Install Wheel Kit
NOTICE Wheel kit is not intended for over-the-road
use.
Install the wheel kit as follows:
1. Tip generator so that engine end is up.
2. Slide a washer (A) over axle stud (B).
3. Slide a wheel (C) over axle stud (B).NOTICE Be sure to install wheel with raised hub
inboard.
4. Slide axle stud (B) through mounting bracket.
5. Insert retaining pin (D) through hole on axle stud.
6. Repeat steps 2 thru 5 to secure second wheel.
7. Line up holes in support leg (E) with holes in
generator frame.
8. Attach support leg using four capscrews (F) and
four flange nuts (G). Tighten with 10 and 13 mm
wrenches.
9. Return generator to normal operating position
(resting on wheels and support leg).
Verify Engine Oil Level
The generator engine is shipped from the factory filled
with oil (API SJ or higher 10W-30). This allows for
generator operation in the widest range of temperature
and climate conditions. Before starting the engine,
check oil level and ensure that engine is serviced as
described in Maintenance.
NOTICE Any attempt to crank or start the engine
before it has been properly filled with the recommended
oil could result in equipment failure.
• Refer to Maintenance for oil fill information.
• Damage to equipment resulting from failure to follow this
instruction will void warranty.
A
B
C
D
F
E
G
NOTICE See Oil in the Maintenance section to review
oil recomendations. Verify provided oil in engine is the
correct viscosity for current ambient temperature.
9
Not for
Reproduction
Add Fuel
Fuel must meet these requirements:
• Clean, fresh, unleaded gasoline.
• A minimum of 87 octane/87 AKI (91 RON). For
high altitude use, see High Altitude.
• Gasoline with up to 10% ethanol (gasohol) is
acceptable.
NOTICE Use of unapproved fuels could damage
generator and voids warranty.
• DO NOT use unapproved gasoline such as E15 and E85.
• DO NOT mix oil in gasoline or modify engine to run on
alternate fuels.
To protect the fuel system from gum formation, mix in a
fuel stabilizer when adding fuel. See Storage. All fuel is
not the same. If you experience starting or performance
problems after using fuel, switch to a different fuel
provider or change brands. This engine is certified to
operate on gasoline. The emission control system for this
engine is EM (Engine Modifications).
WARNING Fuel and its vapors are extremely
flammable and explosive which could
cause burns, fire or explosion
resulting in death or serious injury.
WHEN ADDING FUEL
• Turn generator engine OFF and let it cool at least 2 minutes
before removing fuel cap. Loosen cap slowly to relieve
pressure in tank.
• Fill fuel tank outdoors.
• DO NOT overfill tank. Allow space for fuel expansion.
• If fuel spills, wait until it evaporates before starting engine.
• Keep fuel away from sparks, open flames, pilot lights,
heat, and other ignition sources.
• Check fuel lines, tank, cap and fittings frequently for
cracks or leaks. Replace if necessary.
• DO NOT light a cigarette or smoke.
1. Clean area around fuel fill cap, remove cap.
2. Slowly add unleaded gasoline (A) to fuel tank
(B). Be careful not to fill above the baffle (C).
This allows adequate space for fuel expansion as
shown.
TANK
C
3. Install fuel cap and let any spilled fuel evaporate
before starting engine.
High Altitude
At altitudes over 5,000 ft. (1524 m), a minimum
85 octane / 85 AKI (89 RON) gasoline is acceptable.
To remain emissions compliant, high altitude
adjustment is required. Operation without this
adjustment will cause decreased performance,
increased fuel consumption, and increased emissions.
See an authorized dealer for high altitude adjustment
B
FUEL
A
information. Operation of the engine at altitudes
below 2,500 ft. (762 m) with the high altitude kit is not
recommended.
System Ground
The generator has a system ground that connects the
generator frame components to the ground terminals
on the AC output receptacles. The system ground is
connected to the AC neutral wire (the neutral is bonded
to the generator frame).
Special Requirements
There may be Federal or State Occupational Safety
and Health Administration (OSHA) regulations, local
codes, or ordinances that apply to the intended use of
the generator. Please consult a qualified electrician,
electrical inspector, or the local agency having
jurisdiction:
• In some areas, generators are required to be
registered with local utility companies.
• If the generator is used at a construction site,
there may be additional regulations which must be
observed.
Connecting to a Building’s Electrical
System
Connections for standby power to a building’s electrical
system must use a listed transfer switch installed by
a current licensed electrician. The connection must
isolate the generator power from the utility power and
must comply with all applicable laws and electrical
codes.
WARNING
electrical shock or burn resulting in death or
serious injury.
• Use listed transfer equipment, suitable for the intended
use, to prevent backfeed by isolating generator from
electric utility workers.
• When using generator for backup power, notify utility
company.
• Use a ground fault circuit interrupter (GFCI) in any damp
or highly conductive area, such as metal decking or steel
work.
• DO NOT touch bare wires or receptacles.
• DO NOT use generator with electrical cords which are
worn, frayed, bare or otherwise damaged.
• DO NOT operate generator in the rain or wet weather.
• DO NOT handle generator or electrical cords while
standing in water, while barefoot, or while hands or feet
are wet.
• DO NOT allow unqualified persons or children to operate
or service generator.
Generator voltage could cause
10 BRIGGSandSTRATTON.COM
Not for
Reproduction
Portable Generator Location
Before starting the portable generator there are two
equally important safety concerns regarding carbon
monoxide (CO) poisoning and fire that must be
addressed.
NOTICE Satisfying the RISK OF CARBON
MONOXIDE POISONING location requirements may
not satisfy the fire location requirements. Satisfying the
RISK OF FIRE location requirements may not satisfy
the CARBON MONOXIDE POISONING location
requirements.
Operation Location of Portable Generator to
REDUCE THE RISK OF CARBON MONOXIDE
POISONING
All fossil fuel burning equipment, such as a portable
generator, contains carbon monoxide (CO) gas in the
engine exhaust, a poisonous gas that could kill you in
minutes. You CANNOT smell it, see it, or taste it. Even
if you do not smell exhaust fumes, you could still be
exposed to carbon monoxide gas. The following must
be completed prior to starting the portable generator
engine:
• By law it is required in many states to have a
Carbon Monoxide (CO) alarm (A) in operating
condition in your home. Install/maintain batteryoperated carbon monoxide alarms or plug-in
carbon monoxide alarms with battery back-up
according to the manufacturer’s instructions. A
CO alarm is an electronic device that detects
hazardous levels of CO. When there is a buildup
of CO, the alarm will alert the occupants by
flashing visual indicator light and alarm. Smoke
alarms cannot detect CO gas.
A
• Operate this product ONLY outside far away from
windows, doors and vents to reduce the risk of
carbon monoxide gas from accumulating and
potentially being drawn towards occupied spaces.
• DO NOT run this product inside homes, garages,
basements, crawlspaces, sheds, or other partiallyenclosed spaces even if using fans or opening
doors and windows for ventilation. Carbon
monoxide can quickly build up in these spaces
and can linger for hours, even after this product
has shut off.
• Your neighbor(s) home may be exposed to the
engine exhaust from your portable generator and
must be considered when deciding on a location
for the safe operation of your portable generator.
• ALWAYS place this product downwind and point
the engine exhaust away from occupied spaces.
If you start to feel sick, dizzy, or weak while using this
product, get to fresh air RIGHT AWAY. See a doctor.
You may have carbon monoxide poisoning.
11
Not for
Reproduction
EXAMPLE OF LOCATION TO REDUCE THE RISK OF CARBON MONOXIDE
POISONING
CO Alarm
S
A
H
U
X
E
T
(
C
O
)
KEEP
FAR AWAY
in Living Areas
Direct exhaust AWAY
from windows, doors,
and vents.
DO NOT OPERATE IN ANY OF THE FOLLOWING LOCATIONS
Only use OUTSIDE
and FAR AWAY from
windows, doors and vents.
Attic
Entryway,
Porch
Garage
Living Area
Basement
Crawlspace
U
A
H
X
E
S
T
(
C
O
)
Generator too
close to home
and exhaust
directed towards
windows, doors
and vents.
12 BRIGGSandSTRATTON.COM
Not for
Reproduction
Operation Location of Portable Generator to
REDUCE THE RISK OF FIRE
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage fuel tank
causing a fire, resulting in death or serious
injury.
• Portable generator must be at least 5 ft. (1.5 m) from
any structure, overhang, trees, windows, doors, any wall
opening, shrubs, or vegetation over 12 inches (30.5 cm)
in height.
• DO NOT place portable generator under a deck or other
type of structure that may confine airflow.
• Smoke alarm(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Carbon monoxide alarms cannot
detect smoke.
• DO NOT place portable generator in manner other than
shown.
EXAMPLE OF LOCATION TO REDUCE THE RISK OF FIRE
5 ft. (1.5 m) min.
H
A
X
E
U
S
T
(
C
O
)
5 ft. (1.5 m) min.
Direct exhaust AWAY from
windows, doors, and vents.
13
Not for
Reproduction
Features and Controls
Read this Operator’s Manual and safety rules before operating your generator.
Compare the illustrations with your generator, to familiarize yourself with the locations of various controls
and adjustments. Save this manual for future reference.
A
B
C
D
R
Q
E
F
G
H
J
K
A - Hour Meter — Displays and records how many
hours your generator has run (up to 9,999.9).
B - Engine Switch — Set this switch to ON (I) before
starting engine. Set switch to OFF (0) to shut off
engine.
C - Main Breaker — The receptacles are provided
with a rocker switch main circuit breaker to protect
the generator against electrical overload.
D - 120/240 Volt AC, 30 Amp Locking Receptacle
— May be used to supply electrical power for the
operation of 120 and/or 240 Volt AC, 30 Amp,
single phase, 60 Hz electrical, lighting, appliance,
tool and motor loads.
E - Circuit Breakers (AC) — The 120 Volt AC, 20A
GFCI duplex receptacles are provided with “push
to reset” circuit breakers to protect the generator
against electrical overload.
F - 120 Volt AC, 20 Amp, GFCI Duplex Receptacles
— May be used to supply electrical power for the
operation of 120 Volt AC, 20 Amp, single phase,
60 Hz electrical, lighting, appliance, tool and motor
loads.
G - 120 Volt AC, 20 Amp, Duplex Receptacle —
May be used to supply electrical power for the
operation of 120 Volt AC, 20 Amp, single phase,
60 Hz electrical, lighting, appliance, tool and motor
loads.
H - Oil Fill Cap/Dipstick — Check and add engine oil
here.
J - Oil Drain Plug — Drain engine oil here.
K - Grounding Fastener — Consult your local agency
having jurisdiction for grounding requirements in
your area.
P
N
M
L
L - Spark Arrester Muffler — Exhaust muffler lowers
engine noise and is equipped with a spark arrester
screen.
M - Air Cleaner — Protects engine by filtering dust
and debris out of intake air.
N - Choke Lever — Used when starting a cold engine.
P - Recoil Starter — Used to start the engine
manually.
Q - Fuel Valve — Used to turn fuel supply on and off
to engine.
R - Fuel Tank — Capacity of 7.5 U.S. gallons (28.4 l).
Items Not Shown:
Engine Identification — Provides model, type and
code of engine. Please have these readily available if
calling for assistance.
Identification Label — Provides model, revision and
serial number of generator. Please have these readily
available when calling for assistance.
14 BRIGGSandSTRATTON.COM
Not for
Reproduction
Cord Sets and Receptacles
Use only high quality, well-insulated, grounded
extension cords with the generator’s receptacles.
Inspect extension cords before each use.
Check the ratings of all extension cords before you use
them. Check the operator’s manuals of devices for the
manufacturer’s recommendations.
A double pole rocker switch main circuit breaker is
provided to protect the locking receptacle. If this circuit
breaker is tripped, all receptacles are disconnected.
WARNING Damaged or overloaded electrical
cords could overheat, arc, and burn
resulting in death or serious injury.
• ONLY use cords rated for your loads.
• Follow all safeties on electrical cords.
• Inspect cord sets before each use.
120/240 Volt AC, 30 Amp, Locking Receptacle
Use a NEMA L14-30 plug with this receptacle.
Connect a 4-wire cord set rated for 250 Volt AC loads
at 30 Amps (or greater). You can use the same 4-wire
cord if you plan to run a 120 Volt load.
4-Wire Cord Set
240V
120 Volt AC, 20 Amp, Duplex Receptacle
The duplex receptacle is protected against overload by
a push-to-reset circuit breaker.
Use receptacle to operate 120 Volt AC, single-phase,
60 Hz electrical loads requiring up to 2,400 watts
(2.4 kW) at 20 Amps of current. Use cord sets that are
rated for 125 Volt AC loads at 20 Amps (or greater).
120 Volt AC, 20 Amp, GFCI Duplex Receptacles
Each GFCI duplex receptacle is protected against
overload by a push–to–reset circuit breaker.
120V
Y (Hot)
NEMA L14-30
This receptacle powers 120/240 Volt AC, 60 Hz,
single phase loads requiring up to 6,500 watts of
power (6.5 kW) at 27.0 Amps for 240 Volts or two
independent 120 Volt loads at 27.0 Amps each. The
outlet is protected by a two pole rocker switch circuit
breaker.
NOTICE
value greater than generator output capacity.
• NEVER attempt to power a device requiring more
amperage than generator or receptacle can supply.
• DO NOT overload the generator. See Don’t Overload Generator.
Receptacles may be marked with rating
120V
W (Neutral)
X (Hot)
Ground (Green)
Use each receptacle to operate 120 Volt AC, singlephase, 60 Hz electrical loads requiring up to 2,400 watts
(2.4 kW) at 20 Amps of current. Use cord sets that are
rated for 125 Volt AC loads at 20 Amps (or greater).
15
Not for
Reproduction
Ground Fault Protection
The duplex receptacles are protected with Ground
Fault Circuit Interruption (GFCI). This meets applicable
federal, state and local codes. The generator’s locking
receptacle is not protected by Ground Fault Circuit
Interruption (GFCI).
The GFCI protects against electrical shock that may be
caused if your body becomes a path which electricity
travels to reach ground. This could happen if you touch
a “Live” appliance or wire, or are touching plumbing or
other materials that connect to the ground.
When protected by a GFCI, one may still feel a shock,
but the GFCI should cut current off quickly enough so
that a person in normal health should not suffer any
serious electrical injury.
WARNING
electrical shock or burn resulting in death or
serious injury.
• Contact with the hot and neutral conductor at the same
time can cause electrical shock or burn, even if the circuit
is GFCI protected.
• Before using the GFCI receptacle, ALWAYS push the
test button to insure it works.
Generator voltage could cause
Testing the GFCI
Test your GFCI outlet prior to each use, as follows:
• Push the “Test” button. The “Reset” button should
pop out, which should allow no power to reach the
outlet. Use a test lamp in each outlet to test this.
• If the GFCI tests good, restore power by pressing
the “Reset” button firmly until it is fully in place and
locks in that position. If the GFCI outlet does not
reset properly, do not use the outlet. Call or
take your generator to a local service center.
• If the GFCI trips by itself at any time, reset and
test the outlet. If the reset button does not pop
out when the test button is pressed, do not
use the outlet. Call or take your generator to
a local service center.
16 BRIGGSandSTRATTON.COM
Not for
Reproduction
Operation
Starting the Engine
Disconnect all electrical loads from the generator. Use
the following start instructions:
1. Make sure unit is on a level surface.
NOTICE Failure to start and operate the unit on a
level surface will cause the unit not to start or shut
down during operation.
2. Turn the fuel valve (A) to the ON (I) position.
6. Move choke lever to HALF choke position, and
pull recoil handle twice.
• If engine fails to start, repeat steps 5 thru 7.
7. Slowly move choke lever to RUN (
engine falters, move choke lever to HALF choke
position until engine runs smoothly, and then to
RUN () position.
NOTICE If engine floods, place choke lever in
RUN () position and crank until engine starts.
NOTICE If engine starts after 3 pulls but fails to run,
or if unit shuts down during operation, make sure unit
is on a level surface and check for proper oil level in
crankcase. This unit may be equipped with a low oil
protection device. If so, oil must be at proper level for
engine to start.
) position. If
A
3. Push choke lever (B) to CHOKE () position.
B
4. Set engine switch (C) to ON (I) position.
C
5. Grasp recoil handle and pull slowly until slight
resistance is felt. Then pull rapidly one time only
to start engine.
• If engine starts, proceed to step 7.
• If engine fails to start, proceed to step 6.
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage
fuel tank causing a fire, resulting in
death or serious injury.
Contact with muffler area could cause burns
resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Keep at least 5 ft. (1.5 m) of clearance on all sides of
generator including overhead.
• It is a violation of California Public Resource Code,
Section 4442, to use or operate the engine on any forestcovered, brush-covered, or grass-covered land unless
the exhaust system is equipped with a spark arrester, as
defined in Section 4442, maintained in effective working
order. Other states or federal jurisdictions may have
similar laws.
Contact the original equipment manufacturer, retailer,
or dealer to obtain a spark arrester designed for the
exhaust system installed on this engine.
• Replacement parts must be the same and installed in the
same position as the original parts.
WARNING Starter cord kickback (rapid
retraction) will pull hand and arm toward
engine faster than you can let go which
could cause broken bones, fractures,
bruises, or sprains resulting in serious injury.
• When starting engine, pull cord slowly until resistance is
felt and then pull rapidly to avoid kickback.
• NEVER start or stop engine with electrical devices
plugged in and turned on.
17
Not for
Reproduction
Connecting Electrical Loads
1. Let engine stabilize and warm up for a few
minutes after starting.
2. Ensure main breaker is in ON (I) position.
3. Plug in and turn on the desired 120 and/ or
240 Volt AC, single phase, 60 Hz electrical loads.
NOTICE When plugging into the 120 Volt
receptacles, plug items to be powered in sequence as
shown below.
1
2
5
3
4
6
NOTICE
• DO NOT connect 240 Volt loads to 120 Volt
duplex receptacles.
• DO NOT connect 3-phase loads to generator.
• DO NOT connect 50 Hz loads to generator.
• DO NOT OVERLOAD THE GENERATOR. See
Don’t Overload Generator.
NOTICE
capacity could damage generator and/or electrical
devices connected to it.
• DO NOT exceed the generator’s wattage/amperage
capacity. See Don’t Overload Generator in the Operation
section.
• Start generator and let engine stabilize before connecting
electrical loads.
• Connect electrical loads in OFF position, then turn ON for
operation.
• Turn electrical loads OFF and disconnect from generator
before stopping generator.
Exceeding generators wattage/amperage
Stopping the Engine
1. Turn OFF and unplug all electrical loads from
generator panel receptacles. NEVER start or stop
engine with electrical devices plugged in and
turned ON.
2. Let engine run at no-load for several minutes
to stabilize internal temperatures of engine and
generator.
3. Push engine switch to OFF (0) position.
WARNING Fuel and its vapors are extremely
flammable and explosive which could
cause burns, fire or explosion
resulting in death or serious injury.
• DO NOT stop engine by moving choke lever to
CHOKE
4. Move fuel valve to OFF (0) position.
()position.
Low Oil Shutdown
If the engine oil drops below a preset level, an oil
switch will stop the engine. Check oil level with
dipstick.
If oil level is between ADD and FULL mark on
dipstick:
1. DO NOT try to restart the engine.
2. Contact an Authorized Briggs & Stratton Service
Dealer.
3. DO NOT operate engine until oil level is corrected.
If oil level is below ADD mark on dipstick:
1. Add oil to bring level to FULL mark.
2. Restart engine and if the engine stops again a low
oil condition may still exist. DO NOT try to restart
the engine.
3. Contact an Authorized Briggs & Stratton Service
Dealer.
4. DO NOT operate engine until oil level is corrected.
Cold Weather Operation
Under certain weather conditions (temperatures
below 40°F [4°C] combined with high humidity), your
generator may experience icing of the carburetor and/
or the crankcase breather system. To reduce this
problem, you need to perform the following:
1. Make sure generator has clean, fresh fuel.
2. Turn the fuel valve to the ON (I) position.
3. Use SAE 5W-30 oil.
4. Check oil level daily or after every eight (8) hours
of operation.
5. Maintain generator following Maintenance Schedule in Maintenance section.
6. Shelter unit from elements.
18 BRIGGSandSTRATTON.COM
Not for
Reproduction
Creating a Temporary Cold Weather Shelter
1. For temporary shelter, the original shipping carton
can be used.
2. Cut off top carton flaps and one long side of
carton to expose muffler side of unit. If required,
tape up other sides of carton to fit over generator
as shown.
Wind
NOTICE If required, remove wheel kit to fit carton
over generator as shown.
3. Cut appropriate slots to access receptacles of
unit.
4. Face exposed end away from wind and elements.
5. Locate generator as described in the section
Generator Location. Keep exhaust gas from
entering a confined area through windows, doors,
ventilation intakes or other openings.
WARNING POISONOUS GAS HAZARD.
Engine exhaust contains carbon monoxide,
a poisonous gas that could kill you in
minutes. You CANNOT smell it, see it, or
taste it. Even if you do not smell exhaust fumes, you
could still be exposed to carbon monoxide gas.
• Operate this product ONLY outside far away from
windows, doors and vents to reduce the risk of carbon
monoxide gas from accumulating and potentially being
drawn towards occupied spaces.
• Install battery-operated carbon monoxide alarms or
plug-in carbon monoxide alarms with battery back-up
according to the manufacturer’s instructions. Smoke
alarms cannot detect carbon monoxide gas.
• DO NOT run this product inside homes, garages,
basements, crawlspaces, sheds, or other partiallyenclosed spaces even if using fans or opening doors
and windows for ventilation. Carbon monoxide can
quickly build up in these spaces and can linger for hours,
even after this product has shut off.
• ALWAYS place this product downwind and point the
engine exhaust away from occupied spaces.
If you start to feel sick, dizzy, or weak while using this
product, get to fresh air RIGHT AWAY. See a doctor. You
may have carbon monoxide poisoning.
6. Start generator as described in the section
Starting the Engine, then place carton over
generator. Keep at least 5 ft. (1.5 m) clearance
on all sides of generator including overhead with
shelter in place.
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage
fuel tank causing a fire, resulting in
death or serious injury.
Contact with muffler area could cause burns
resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Keep at least 5 ft. (1.5 m) of clearance on all sides of
generator including overhead.
• Remove shelter when temperatures are above 40°F [4°C].
7. Remove shelter when temperatures are above
40°F [4°C].
8. Turn engine OFF and let cool two (2) minutes
before refueling. Let any spilled fuel evaporate
before starting engine.
Building a Cold Weather Shelter
1. Using non combustible material with a fire rating
of at least one hour, build a shelter that will
enclose three sides and the top of the generator.
Make sure muffler side of generator is exposed.
NOTICE Contact your local building material supplier
for non combustible materials with a fire rating of at
least one hour.
NOTICE Be sure shelter can easily be repositioned
for change in wind direction.
2. DO NOT enclose generator any more than shown.
Shelter should hold enough heat created by the
generator to prevent icing problem.
NOTICE If a wheel kit is installed on the generator,
enlarge shelter accordingly.
3. Follow steps 3 through 8 as described previously
in Creating a Temporary Cold Weather Shelter.
19
Not for
Reproduction
Don’t Overload Generator
Capacity
You must make sure your generator can supply
enough rated (running) and surge (starting) watts for
the items you will power at the same time. Follow these
simple steps:
1. Select the items you will power at the same time.
2. Total the rated (running) watts of these items.
This is the amount of power your generator must
produce to keep your items running. See the table
on the right.
3. Estimate how many surge (starting) watts you will
need. Surge wattage is the short burst of power
needed to start electric motor-driven tools or
appliances such as a circular saw or refrigerator.
Because not all motors start at the same time, total
surge watts can be estimated by adding only the
item(s) with the highest additional surge watts to
the total rated watts from step 2.
Example:
Tool or
Appliance
Window Air
Conditioner
Refrigerator8001600
Deep Freezer500500
Television500—
Light (75 Watts)75—
Total Rated (Running) Watts = 3075
Highest Additional Surge (Starting) Watts = 1800
Total Generator Output Required = 4875
Power Management
To prolong the life of your generator and attached
devices, it is important to take care when adding
electrical loads to your generator. There should be
nothing connected to the generator outlets before
starting its engine. The correct and safe way to
manage generator power is to sequentially add loads
as follows:
1. With nothing connected to the generator, start the
engine as described in this manual.
2. Plug in and turn on the first load, preferably the
largest load you have.
3. Permit the generator output to stabilize (engine
runs smoothly and attached device operates
properly).
4. Plug in and turn on the next load.
5. Again, permit the generator to stabilize.
6. Repeat steps 4 and 5 for each additional load.
Rated
(Running)
Watts
12001800
3075 Total
Running Watts
Additional Surge
(Starting) Watts
1800 Highest
Additional Surge
Watts
NEVER add more loads than the generator capacity.
Take special care to consider surge loads in generator
capacity, as described above.
Rated*
Tool or Appliance
Essentials
Light Bulb - 75 watt75Deep Freezer500500
Sump Pump8001200
Refrigerator/Freezer - 18 Cu. Ft.8001600
Water Well Pump - 1/3 HP10002000
Heating/Cooling
Window AC - 10,000 BTU12001800
Window Fan300600
Furnace Fan Blower - 1/2 HP8001300
DVD/CD Player100VCR100Stereo Receiver450Color Television - 27”500Personal Computer w/17” monitor800-
Other
Security System180AM/FM Clock Radio300Garage Door Opener - 1/2 HP480520
Electric Water Heater - 40 Gallon4000-
DIY/Job Site
Quartz Halogen Work Light1000Airless Sprayer - 1/3 HP6001200
Reciprocating Saw960960
Electric Drill - 1/2 HP10001000
Circular Saw - 7 1/4”15001500
Miter Saw - 10”18001800
Table Planer - 6”18001800
Table Saw/Radial Arm Saw - 10”20002000
Air Compressor - 1-1/2 HP25002500
* Wattages listed are approximate only. Check tool or
appliance for actual wattage.
(Running)
Watts
Additional
Surge
(Starting)
Watts
20 BRIGGSandSTRATTON.COM
Not for
Reproduction
Maintenance
Maintenance Schedule
Follow the hourly or calendar intervals, whichever
occurs first. More frequent service is required when
operating in adverse conditions noted below.
First 5 Hours
• Change engine oil
Every 8 Hours or Daily
• Clean debris
• Check engine oil level
Every 25 Hours or Yearly
• Clean engine air filter
Every 50 Hours or Yearly
• Change engine oil
Yearly
• Replace engine air filter
• Service fuel valve
• Service spark plug
• Inspect muffler and spark arrester
• Clean cooling system
1 Service more often under dirty or dusty conditions.
General Recommendations
Regular maintenance will improve the performance
and extend the life of the generator. See any
authorized dealer for service.
The generator’s warranty does not cover items that
have been subjected to operator abuse or negligence.
To receive full value from the warranty, the operator
must maintain the generator as instructed in this
manual.
Some adjustments will need to be made periodically to
properly maintain your generator.
All service and adjustments should be made at least
once each season. A new spark plug and clean
air filter assure proper fuel-air mixture and help
your engine run better and last longer. Follow the
requirements in the Maintenance Schedule chart
above.
1
1
1
1
Generator Maintenance
Generator maintenance consists of keeping the unit
clean and dry. Operate and store the unit in a clean dry
environment where it will not be exposed to excessive
dust, dirt, moisture, or any corrosive vapors. Cooling
air slots in the generator must not become clogged
with snow, leaves, or any other foreign material.
NOTICE DO NOT use water or other liquids to clean
generator. Liquids can enter engine fuel system,
causing poor performance and/or failure to occur. In
addition, if liquid enters generator through cooling air
slots, some of the liquid will be retained in voids and
cracks of the rotor and stator winding insulation. Liquid
and dirt buildup on the generator internal windings will
eventually decrease the insulation resistance of these
windings.
Cleaning
Daily or before use, look around and underneath
the generator for signs of oil or fuel leaks. Clean
accumulated debris from inside and outside the
generator. Keep the linkage, spring and other engine
controls clean. Keep the area around and behind
the muffler free from any combustible debris. Inspect
cooling air slots and openings on generator. These
openings must be kept clean and unobstructed.
Engine parts should be kept clean to reduce the risk of
overheating and ignition of accumulated debris:
• Use a damp cloth to wipe exterior surfaces clean.
NOTICE
damage it and shorten its life.
• DO NOT expose generator to excessive moisture, dust,
dirt, or corrosive vapors.
• DO NOT insert any objects through cooling slots.
• Use a soft bristle brush to loosen caked on dirt or
• Use a vacuum cleaner to pick up loose dirt and
Improper treatment of generator could
oil.
debris.
Fuel Valve Maintenance
The fuel valve is equipped with a fuel sediment cup,
screen, and o-ring that need to be cleaned.
1. Move fuel valve to OFF (0) position.
2. Remove sediment cup (A) from fuel valve.
Remove o-ring (B) and screen (C) from fuel valve.
Emissions Control
Maintenance, replacement, or repair of the
emissions control devices and systems may
be performed by any non-road engine repair
establishment or individual. However, to obtain
”no charge” emissions control service, the work must
be performed by a factory authorized dealer. See the
Emissions Warranty.
C
B
A
21
Not for
Reproduction
3. Wash sediment cup, o-ring, and screen in a
nonflammable solvent. Dry them thoroughly.
4. Place screen and o-ring into fuel valve. Install
sediment cup and tighten securely.
5. Move fuel valve to ON (I) position, and check for
leaks. Replace fuel valve if there is any leakage.
Engine Maintenance
WARNING Unintentional sparking could cause
fire or electric shock resulting in
death or serious injury.
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR
GENERATOR
• Disconnect the spark plug wire from the spark plug and
place the wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
• Use approved spark plug tester.
• DO NOT check for spark with spark plug removed.
Checking Oil Level
Oil level should be checked prior to each use or
at least every 8 hours of operation. Keep oil level
maintained.
1. Make sure generator is on a level surface.
2. Clean area around oil fill, remove oil cap/dipstick
and wipe dipstick with clean cloth. Replace
dipstick. Remove and and check oil level.
NOTICE DO NOT screw in dipstick when checking
oil level.
3. Verify oil is at FULL mark (A) on dipstick. Replace
and tighten oil cap/dipstick.
Oil
Oil Recommendations
We recommend the use of Briggs & Stratton Warranty
Certified oils for best performance. Other high-quality
detergent oils are acceptable if classified for service
SF, SG, SH, SJ or higher. DO NOT use special
additives.
Outdoor temperatures determine the proper oil
viscosity for the engine. Use the chart to select the
best viscosity for the outdoor temperature range
expected.
* Below 40°F (4°C) the use of SAE 30 will result in hard
starting.
** Above 80°F (27°C) the use of 10W30 may cause
increased oil consumption. Check oil level more frequently.
A
Adding Engine Oil
1. Make sure generator is on a level surface.
2. Check oil level as described in Checking Oil Level.
3. If needed, slowly pour oil into oil fill opening to the
FULL mark on dipstick. DO NOT overfill.
NOTICE Overfilling with oil could cause the engine
to not start, or hard starting.
• DO NOT overfill.
• If over the FULL mark on dipstick, drain oil to reduce oil
level to FULL mark on dipstick.
4. Replace and tighten oil cap/dipstick.
22 BRIGGSandSTRATTON.COM
Not for
Reproduction
Changing Engine Oil
If you are using your generator under extremely dirty or
dusty conditions, or in extremely hot weather, change
the oil more often.
Service Air Cleaner
Your engine will not run properly and may be damaged
if you run it with a dirty air cleaner. Clean or replace
more often if operating under dusty or dirty conditions.
CAUTION Avoid prolonged or repeated skin
contact with used motor oil.
• Used motor oil has been shown to cause skin cancer in
certain laboratory animals.
• Thoroughly wash exposed areas with soap and water.
KEEP OUT OF REACH OF CHILDREN.
DON’T POLLUTE. CONSERVE
RESOURCES. RETURN USED OIL TO
COLLECTION CENTERS.
Change the oil while the engine is still warm from
running, as follows:
1. Make sure unit is on a level surface.
2. Disconnect the spark plug wire from the spark
plug and place the wire where it cannot contact
spark plug.
3. Clean area around oil drain plug (A). The oil
drain plug is located at base of engine, opposite
carburetor.
A
4. Remove oil drain plug and drain oil completely
into a suitable container.
6. Slowly pour recommended oil (about 36 oz.
(1 liter)) into oil fill opening. Pause to permit oil to
settle. Fill to FULL mark on dipstick.
7. Wipe dipstick clean each time oil level is checked.
DO NOT overfill.
8. Reinstall oil cap/dipstick. Tighten cap securely.
9. Wipe up any spilled oil.
To service the air cleaner, follow these steps:
1. Loosen screws (B) and remove air cleaner cover (C).
E
D
C
B
2. Carefully remove cartridge (D) from base (E).
3. Install clean (or new) air cleaner assembly inside
cover. Dispose of old filter properly.
4. Assemble air cleaner cover onto base and tighten
screws.
Service Spark Plug
Changing the spark plug will help your engine to start
easier and run better.
1. Clean area around spark plug.
2. Remove and inspect spark plug.
3. Replace spark plug if electrodes are pitted,
burned or porcelain is cracked. Use the
recommended replacement spark plug. See
Specifications.
4. Check electrode gap with wire feeler gauge and
reset spark plug gap to recommended gap if
necessary (see Specifications).
5. Install spark plug and tighten firmly.
23
Not for
Reproduction
Inspect Muffler and Spark Arrester
The engine exhaust muffler has a spark arrester
screen. Inspect the muffler for cracks, corrosion,
or other damage. Inspect spark arrester screen for
damage or carbon blockage. Clean if carbon blockage
is found or replace if damaged. If replacement parts
are required, make sure to use only original equipment
replacement parts.
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage
fuel tank causing a fire, resulting in
death or serious injury.
Contact with muffler area could cause burns
resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Keep at least 5 ft. (1.5 m) of clearance on all sides of
generator including overhead.
• It is a violation of California Public Resource Code,
Section 4442, to use or operate the engine on any forestcovered, brush-covered, or grass-covered land unless
the exhaust system is equipped with a spark arrester, as
defined in Section 4442, maintained in effective working
order. Other states or federal jurisdictions may have
similar laws.
Contact the original equipment manufacturer, retailer,
or dealer to obtain a spark arrester designed for the
exhaust system installed on this engine.
• Replacement parts must be the same and installed in the
same position as the original parts.
Clean or replace spark arrester as follows:
1. Remove four screws that connect heat shield (A)
to muffler (B).
C
Clean Cooling System
Over time debris may accumulate in cylinder cooling
fins and cannot be observed without partial engine
disassembly. For this reason, we recommend you
have a Briggs & Stratton authorized dealer clean the
cooling system (D) per recommended intervals (see
Maintenance Schedule in the Maintenance section).
Equally important is to keep top of engine free from
debris. Also see Cleaning.
D
Carburetor Adjustment
The carburetor on this engine is low emission. It is
equipped with a non-adjustable idle mixture valve.
Top speed has been set at the factory. If adjustment is
required, see a Briggs & Stratton authorized dealer.
CAUTION Excessively high operating speeds
could result in minor injury.
Excessively low operating speeds impose a heavy
load.
• DO NOT tamper with governor spring, links or other parts
to increase engine speed. Generator supplies correct
rated frequency and voltage when running at governed
speed.
• DO NOT modify generator in any way.
A
B
2. Remove four screws that attach spark arrester
screen (C).
3. Obtain a replacement screen if torn, perforated
or otherwise damaged. DO NOT use a defective
screen. If screen is not damaged, clean it with
commercial solvent.
4. Reattach screen and muffler guard.
24 BRIGGSandSTRATTON.COM
Not for
Reproduction
Storage
The generator should be started at least once every
seven days and allowed to run at least 30 minutes. If
this cannot be done and you must store the unit for
more than 30 days, use the following guidelines to
prepare it for storage.
Generator Storage
• Clean the generator as outlined in Cleaning.
• Check that cooling air slots and openings on
generator are open and unobstructed.
Long Term Storage Instructions
Fuel can become stale when stored over 30 days.
Stale fuel causes acid and gum deposits to form in the
fuel system or on essential carburetor parts. To keep
fuel fresh, use Briggs & Stratton® Advanced Formula
Fuel Treatment & Stabilizer, available wherever Briggs
& Stratton genuine service parts are sold.
There is no need to drain gasoline from the engine
if a fuel stabilizer is added according to instructions.
Run the engine for 2 minutes to circulate the stabilizer
throughout the fuel system before storage.
If gasoline in the engine has not been treated with a
fuel stabilizer, it must be drained into an approved
container. Run the engine until it stops from lack
of fuel. The use of a fuel stabilizer in the storage
container is recommended to maintain freshness.
Change Engine Oil
While engine is still warm, drain oil from crankcase.
Refill with recommended grade. See Changing Engine Oil.
Other Storage Tips
1. DO NOT store fuel from one season to another
unless it has been treated as described in Long Term Storage Instructions.
2. Replace fuel container if it starts to rust. Rust and/
or dirt in fuel can cause problems if it’s used with
this unit.
3. Cover unit with a suitable protective cover that
does not retain moisture.
WARNING Storage covers could cause a fire
resulting in death or serious injury.
• DO NOT place a storage cover over a hot generator.
• Let equipment cool for a sufficient time before placing the
cover on the equipment.
4. Store generator in clean, dry area.
WARNING Fuel and its vapors are extremely
flammable and explosive which could
cause burns, fire or explosion
resulting in death or serious injury.
WHEN STORING FUEL OR EQUIPMENT WITH FUEL IN
TANK
• Store away from furnaces, stoves, water heaters, clothes
dryers or other appliances that have pilot light or other
ignition source because they could ignite fuel vapors.
WHEN DRAINING FUEL
• Turn generator engine OFF and let it cool at least 2
minutes before removing fuel cap. Loosen cap slowly to
relieve pressure in tank.
• Drain fuel tank outdoors.
• Keep fuel away from sparks, open flames, pilot lights,
heat, and other ignition sources.
• Check fuel lines, tank, cap and fittings frequently for
cracks or leaks. Replace if necessary.
• DO NOT light a cigarette or smoke.
25
Not for
Reproduction
Troubleshooting
ProblemCauseCorrection
Engine is running, but no
AC output is available.
Engine runs good at
no-load but “bogs down”
when loads are connected.
1. One of the circuit breakers is open.
2. Fault in generator.
3. Poor connection or defective cord
set.
4. Connected device is bad.
1. Short circuit in a connected load.
2. Engine speed is too slow.
3. Generator is overloaded.
4. Shorted generator circuit.
5. Clogged or dirty fuel filter.
1. Reset circuit breaker.
2. Contact authorized service facility.
3. Check and repair.
4. Connect another device that is in
good condition.
1. Disconnect shorted electrical load.
2. Contact authorized service facility.
3. See Don’t Overload Generator.
4. Contact authorized service facility.
5. Clean or replace fuel filter.
Engine will not start, starts
and runs rough or shuts
down when running.
Engine lacks power.
1. Engine rocker switch set to OFF (0)
position.
2. Fuel Valve is in OFF (0) position.
3. Low oil level.
4. Dirty air cleaner.
5. Clogged or dirty fuel filter.
6. Out of fuel.
7. Stale fuel.
8. Spark plug wire not connected to
spark plug.
9. Bad spark plug.
10. Water in fuel.
11. Flooded.
12. Excessively rich fuel mixture.
13. Intake valve stuck open or closed.
14. Engine has lost compression.
1. Load is too high.
2. Dirty air filter.
3. Clogged or dirty fuel filter.
1. Set engine rocker switch to ON (I)
position.
2. Turn fuel valve to ON (I) position.
3. Fill crankcase to proper level or
place generator on level surface.
4. Clean or replace air cleaner.
5. Clogged or dirty fuel filter.
6. Fill fuel tank.
7. Drain fuel tank and carburetor; fill
with fresh fuel.
8. Connect wire to spark plug.
9. Replace spark plug.
10. Drain gas tank and carburetor; fill
with fresh fuel.
11. Wait 5 minutes and re-crank
engine.
12. Contact authorized service facility.
13. Contact authorized service facility.
14. Contact authorized service facility.
1. See Don’t Overload Generator.
2. Replace air filter.
3. Clean or replace fuel filter.
Engine “hunts” or falters.
1. Carburetor is running too rich or too
lean.
2. Clogged or dirty fuel filter.
1. Contact authorized service facility.
2. Clean or replace fuel filter.
26 BRIGGSandSTRATTON.COM
Not for
Reproduction
Schematic
27
Loading...
+ 61 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.