This generator is rated in accordance with CSA (Canadian Standards Association) standard C22.2 No. 100-04
(motors and generators) and PGMA (Portable Generator Manufacturers’ Association) standard PGMA G200
(Standard for Testing and Validating Performance of Portable Generators).
BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC
MILWAUKEE, WISCONSIN, U.S.A.
Manual No. 80008045 Revision B
Not for
Reproduction
Thank you for purchasing this quality-built Briggs & Stratton® generator. We are pleased that you’ve placed your
confidence in the Briggs & Stratton brand. When operated and maintained according to the instructions in this
manual, your Briggs & Stratton generator will provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with generator
products and how to avoid them. This generator is designed and intended only for supplying electrical power
for operating compatible electrical lighting, appliances, tools and motor loads, and is not intended for any other
purpose. It is important that you read and understand these instructions thoroughly before attempting to start or
operate this equipment. Save this original manual for future reference.
This generator requires final assembly before use. Refer to the Assembly section of this manual for
instructions on final assembly procedures. Follow the instructions completely.
Where to Find Us
You never have to look far to find Briggs & Stratton support and service for your generator. Consult your Yellow
Pages. There are over 30,000 Briggs & Stratton authorized service dealers worldwide who provide quality service.
You can also contact Briggs & Stratton Customer Service by phone at (800) 743-4115, or on the Internet at
BRIGGSandSTRATTON.COM.
Generator Engine
Model Number _____________________ Model Number ______________________
Revision __________________________ Type Number _______________________
Serial Number ______________________ Code Number _______________________
Safe operation of the portable generator requires the completion of the following tasks:
Carbon Monoxide (CO) Alarm
Carbon monoxide (CO) alarm(s) in working order.
Smoke Alarm
Smoke alarm(s) in working order.
Generator Location
Generator placed in a Carbon Monoxide (CO) safe zone. See Generator Location to reduce the Risk of
Carbon Monoxide Poisoning.
Generator placed in a fire safe zone. See Generator Location to reduce the Risk of Fire.
Generator located on flat and level surface.
Oil and Fuel
Engine filled to proper oil level. See Add Engine Oil.
Fuel tank filled at or below baffle. See Add Fuel.
Inspect fuel lines, tank, cap and fittings each time before using generator. DO NOT use if fuel leak or
damage is found.
Electrical
When connecting to a buildings electrical system install listed transfer equipment. See Connecting to a
Building’s Electrical System.
Electrical cords are rated for intended loads. See Cord Sets and Receptacles.
Electrical cords do not run through doorways, windows, holes in ceilings, walls or floors.
Inspect electrical cords thoroughly before each use. DO NOT use if damaged.
All labeled electrical cord safeties are understood and being followed.
Operation
Start engine. See Starting the Engine.
3
Not for
Reproduction
Operator Safety
Safety Labels
The generator safety labels shown below and on the next page are placed on your portable generator to draw
attention to potential safety hazards.
202997
4 BRIGGSandSTRATTON.COM
Not for
Reproduction
312728
WARNING
AVERTISSEMENT
5
Not for
Reproduction
Equipment Description
Read this manual carefully and become
familiar with your generator. Know its
applications, its limitations and any hazards
involved.
The generator is an engine–driven, revolving field,
alternating current (AC) generator. It was designed
to supply electrical power for operating compatible
electrical lighting, appliances, tools and motor loads.
The generator’s revolving field is driven at about
3,600 rpm by a single-cylinder engine.
Safety Symbols and Meanings
Toxic Fumes
Fire
Kickback
Explosion
Electrical Shock
Operator’s Manual
NOTICE
capacity could damage generator and/or electrical
devices connected to it.
• DO NOT exceed the generator’s wattage/amperage
capacity. See Don’t Overload Generator in the Operation
section.
Every effort has been made to ensure that the
information in this manual is both accurate and current.
However, the manufacturer reserves the right to
change, alter or otherwise improve the generator and
this documentation at any time without prior notice.
The Emission Control System for this generator is
warranted for standards set by the Environmental
Protection Agency and the California Air Resources
Board.
Exceeding generators wattage/amperage
Important Safety Information
The manufacturer cannot possibly anticipate every
possible circumstance that might involve a hazard.
The warnings in this manual, and the tags and decals
affixed to the unit are, therefore, not all-inclusive.
If you use a procedure, work method or operating
technique that the manufacturer does not specifically
recommend, you must satisfy yourself that it is safe
for you and others. You must also make sure that the
procedure, work method or operating technique that
you choose does not render the generator unsafe.
Moving Parts
The safety alert symbol indicates a potential
personal injury hazard. A signal word (DANGER,
WARNING, or CAUTION) is used with the alert symbol
to designate a degree or level of hazard seriousness.
A safety symbol may be used to represent the type of
hazard. The signal word NOTICE is used to address
practices not related to personal injury.
DANGER indicates a hazard which, if not avoided,
will result in death or serious injury.
WARNING indicates a hazard which, if not
avoided, could result in death or serious injury.
CAUTION indicates a hazard which, if not avoided,
could result in minor or moderate injury.
NOTICE address practices not related to personal
injury.
WARNING The engine exhaust from this
product contains chemicals known to the State of
California to cause cancer, birth defects, or other
reproductive harm.
WARNING Certain components in this product
and related accessories contain chemicals known to
the State of California to cause cancer, birth defects
or other reproductive harm. Wash hands after
handling.
Flying Objects
Hot Surface
6 BRIGGSandSTRATTON.COM
Not for
Reproduction
WARNING POISONOUS GAS HAZARD.
Engine exhaust contains carbon monoxide,
a poisonous gas that could kill you in
minutes. You CANNOT smell it, see it, or
taste it. Even if you do not smell exhaust fumes, you
could still be exposed to carbon monoxide gas.
• Operate this product ONLY outside far away from
windows, doors and vents to reduce the risk of carbon
monoxide gas from accumulating and potentially being
drawn towards occupied spaces.
• Install battery-operated carbon monoxide alarms or
plug-in carbon monoxide alarms with battery back-up
according to the manufacturer’s instructions. Smoke
alarms cannot detect carbon monoxide gas.
• DO NOT run this product inside homes, garages,
basements, crawlspaces, sheds, or other partiallyenclosed spaces even if using fans or opening doors
and windows for ventilation. Carbon monoxide can
quickly build up in these spaces and can linger for hours,
even after this product has shut off.
• ALWAYS place this product downwind and point the
engine exhaust away from occupied spaces.
If you start to feel sick, dizzy, or weak while using this
product, get to fresh air RIGHT AWAY. See a doctor. You
may have carbon monoxide poisoning.
WARNING Starter cord kickback (rapid
retraction) will pull hand and arm toward
engine faster than you can let go which
could cause broken bones, fractures,
bruises, or sprains resulting in serious injury.
• When starting engine, pull cord slowly until resistance is
felt and then pull rapidly to avoid kickback.
• NEVER start or stop engine with electrical devices
plugged in and turned on.
WARNING Fuel and its vapors are extremely
flammable and explosive which
could cause burns, fire or explosion
resulting in death or serious injury.
WHEN ADDING OR DRAINING FUEL
• Turn generator engine OFF and let it cool at least 2
minutes before removing fuel cap. Loosen cap slowly to
relieve pressure in tank.
• Fill or drain fuel tank outdoors.
• DO NOT overfill tank. Allow space for fuel expansion.
• If fuel spills, wait until it evaporates before starting engine.
• Keep fuel away from sparks, open flames, pilot lights,
heat, and other ignition sources.
• Check fuel lines, tank, cap and fittings frequently for
cracks or leaks. Replace if necessary.
• DO NOT light a cigarette or smoke.
WHEN STARTING EQUIPMENT
• Ensure spark plug, muffler, fuel cap, and air cleaner are
in place.
• DO NOT crank engine with spark plug removed.
WHEN OPERATING EQUIPMENT
• DO NOT operate this product inside any building,
carport, porch, mobile equipment, marine applications, or
enclosure.
• DO NOT tip engine or equipment at angle which causes
fuel to spill.
• DO NOT stop engine by moving choke control to
CHOKE (
WHEN TRANSPORTING, MOVING OR REPAIRING
EQUIPMENT
• Transport/move/repair with fuel tank EMPTY or with fuel
shutoff valve OFF (0).
• DO NOT tip engine or equipment at angle which causes
fuel to spill.
• Disconnect spark plug wire.
WHEN STORING FUEL OR EQUIPMENT WITH FUEL IN
TANK
• Store away from furnaces, stoves, water heaters, clothes
dryers, or other appliances that have pilot light or other
ignition source because they could ignite fuel vapors.
WARNING
• This generator does not meet U. S. Coast Guard
Regulation 33CFR-183 and should not be used on
marine applications.
• Failure to use the appropriate U. S. Coast Guard
approved generator could result in death or serious injury.
) position.
7
Not for
Reproduction
WARNING
electrical shock or burn resulting in death or
serious injury.
• Use listed transfer equipment, suitable for the intended
use, to prevent backfeed by isolating generator from
electric utility workers.
• When using generator for backup power, notify utility
company.
• Use a ground fault circuit interrupter (GFCI) in any damp
or highly conductive area, such as metal decking or steel
work.
• DO NOT touch bare wires or receptacles.
• DO NOT use generator with electrical cords which are
worn, frayed, bare or otherwise damaged.
• DO NOT operate generator in the rain or wet weather.
• DO NOT handle generator or electrical cords while
standing in water, while barefoot, or while hands or feet
are wet.
• DO NOT allow unqualified persons or children to operate
or service generator.
Generator voltage could cause
WARNING Starter and other rotating parts
could entangle hands, hair, clothing, or
accessories resulting in serious injury.
• NEVER operate generator without protective housing or
covers.
• DO NOT wear loose clothing, jewelry or anything that
could be caught in the starter or other rotating parts.
• Tie up long hair and remove jewelry.
CAUTION Excessively high operating speeds
could result in minor injury.
Excessively low operating speeds impose a heavy
load.
• DO NOT tamper with governor spring, links or other parts
to increase engine speed. Generator supplies correct
rated frequency and voltage when running at governed
speed.
• DO NOT modify generator in any way.
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage
fuel tank causing a fire, resulting in
death or serious injury.
Contact with muffler area could cause burns
resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Keep at least 5 ft. (1.5 m) of clearance on all sides of
generator including overhead.
• It is a violation of California Public Resource Code,
Section 4442, to use or operate the engine on any forestcovered, brush-covered, or grass-covered land unless
the exhaust system is equipped with a spark arrester, as
defined in Section 4442, maintained in effective working
order. Other states or federal jurisdictions may have
similar laws.
Contact the original equipment manufacturer, retailer,
or dealer to obtain a spark arrester designed for the
exhaust system installed on this engine.
• Replacement parts must be the same and installed in the
same position as the original parts.
WARNING Unintentional sparking could cause
fire or electric shock resulting in
death or serious injury.
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR
GENERATOR
• Disconnect the spark plug wire from the spark plug and
place the wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
• Use approved spark plug tester.
• DO NOT check for spark with spark plug removed.
NOTICE
capacity could damage generator and/or electrical
devices connected to it.
• DO NOT exceed the generator’s wattage/amperage
capacity. See Don’t Overload Generator in the Operation
section.
• Start generator and let engine stabilize before connecting
electrical loads.
• Connect electrical loads in OFF position, then turn ON for
operation.
• Turn electrical loads OFF and disconnect from generator
before stopping generator.
NOTICE
damage it and shorten its life.
• Use generator only for intended uses.
• If you have questions about intended use, ask dealer or
contact local service center.
• Operate generator only on level surfaces.
• DO NOT expose generator to excessive moisture, dust,
dirt, or corrosive vapors.
• DO NOT insert any objects through cooling slots.
• If connected devices overheat, turn them off and
disconnect them from generator.
• Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
Exceeding generators wattage/amperage
Improper treatment of generator could
8 BRIGGSandSTRATTON.COM
Not for
Reproduction
Assembly
Your generator requires some assembly and is ready
for use after it has been properly serviced with the
recommended oil and fuel.
If you have any problems with the assembly of your
generator, please call the generator helpline at
1-800-743-4115. If calling for assistance, please
have the model, revision, and serial number from the
identification label available. See Features and Controls
for identification label location.
Unpack Generator
1. Set the carton on a rigid, flat surface.
2. Remove everything from carton except generator.
3. Open carton completely by cutting each corner
from top to bottom.
4. Leave generator on carton to install wheel kit.
Shipment Contents
The generator is supplied with:
• Engine oil bottle
• Operator’s manual
• Wheel kit
7. Line up holes in support leg (E) with holes in
generator frame.
G
E
F
8. Attach support leg using two 16 mm capscrews
(F) and two M8 hex nuts (G). Tighten with a
13 mm socket wrench and 13 mm wrench.
9. Return generator to normal operating position
(resting on wheels).
10. Slide handle bracket over generator frame and
attach handle (H) using two 50 mm capscrews (J)
and two M8 hex nuts (K). Tighten with a 13 mm
socket wrench and 13 mm wrench.
J
K
Install Wheel Kit
NOTICE Wheel kit is not intended for over-the-road
use.
You will need the following tools to install these
components:
• 13 mm wrench
• Socket wrench with 13 mm socket
Install the wheel kit as follows:
1. Tip generator so that engine side is down.
2. Slide axle stud (A) through wheel (B).
C
D
NOTICE Be sure to install wheel with raised hub
inboard.
3. Slide a spacer (C) over axle stud on back side of
wheel.
4. Slide axle stud through mounting bracket.
5. Insert retaining pin (D) through hole on axle stud.
6. Repeat steps 2 through 5 to secure second wheel.
B
H
Add Engine Oil
1. Place generator on a flat, level surface.
2. Clean area around oil fill and remove yellow oil fill cap.
A
3. Using oil funnel (optional), slowly pour contents of
provided oil bottle into oil fill opening.
NOTICE
damage it and shorten its life.
• DO NOT attempt to crank or start the engine before it has
been properly serviced with the recommended oil. This
could result in an engine failure.
4. Replace oil fill cap and fully tighten.
Improper treatment of generator could
Add Fuel
Fuel must meet these requirements:
• Clean, fresh, unleaded gasoline.
• A minimum of 87 octane/87 AKI (91 RON). For
high altitude use, see High Altitude.
• Gasoline with up to 10% ethanol (gasohol) is
acceptable.
9
Not for
Reproduction
NOTICE Use of unapproved fuels could damage
generator and voids warranty.
• DO NOT use unapproved gasoline such as E15 and E85.
• DO NOT mix oil in gasoline or modify engine to run on
alternate fuels.
To protect the fuel system from gum formation, mix
in a fuel stabilizer when adding fuel. See Storage.
All fuel is not the same. If you experience starting or
performance problems after using fuel, switch to a
different fuel provider or change brands. This engine is
certified to operate on gasoline. The emission control
system for this engine is EM (Engine Modifications).
WARNING Fuel and its vapors are extremely
flammable and explosive which could
cause burns, fire or explosion
resulting in death or serious injury.
WHEN ADDING FUEL
• Turn generator engine OFF and let it cool at least 2
minutes before removing fuel cap. Loosen cap slowly to
relieve pressure in tank.
• Fill fuel tank outdoors.
• DO NOT overfill tank. Allow space for fuel expansion.
• If fuel spills, wait until it evaporates before starting engine.
• Keep fuel away from sparks, open flames, pilot lights,
heat, and other ignition sources.
• Check fuel lines, tank, cap and fittings frequently for
cracks or leaks. Replace if necessary.
• DO NOT light a cigarette or smoke.
1. Clean area around fuel fill cap, remove cap.
2. Slowly add unleaded gasoline (A) to fuel tank
(B). Be careful not to fill above the baffle (C).
This allows adequate space for fuel expansion as
shown.
TANK
C
3. Install fuel cap and let any spilled fuel evaporate
before starting engine.
High Altitude
At altitudes over 5,000 ft. (1524 m), a minimum
85 octane / 85 AKI (89 RON) gasoline is acceptable.
To remain emissions compliant, high altitude
adjustment is required. Operation without this
adjustment will cause decreased performance,
increased fuel consumption, and increased emissions.
See an authorized dealer for high altitude adjustment
information. Operation of the engine at altitudes
below 2,500 ft. (762 m) with the high altitude kit is not
recommended.
B
FUEL
A
System Ground
The generator has a system ground that connects the
generator frame components to the ground terminals
on the AC output receptacles. The system ground is
connected to the AC neutral wire (the neutral is bonded
to the generator frame).
Special Requirements
There may be Federal or State Occupational Safety
and Health Administration (OSHA) regulations, local
codes, or ordinances that apply to the intended use of
the generator. Please consult a qualified electrician,
electrical inspector, or the local agency having
jurisdiction:
• In some areas, generators are required to be
registered with local utility companies.
• If the generator is used at a construction site,
there may be additional regulations which must be
observed.
Connecting to a Building’s Electrical
System
Connections for standby power to a building’s electrical
system must use a listed transfer switch installed by
a current licensed electrician. The connection must
isolate the generator power from the utility power and
must comply with all applicable laws and electrical
codes.
WARNING
electrical shock or burn resulting in death or
serious injury.
• Use listed transfer equipment, suitable for the intended
use, to prevent backfeed by isolating generator from
electric utility workers.
• When using generator for backup power, notify utility
company.
• Use a ground fault circuit interrupter (GFCI) in any damp
or highly conductive area, such as metal decking or steel
work.
• DO NOT touch bare wires or receptacles.
• DO NOT use generator with electrical cords which are
worn, frayed, bare or otherwise damaged.
• DO NOT operate generator in the rain or wet weather.
• DO NOT handle generator or electrical cords while
standing in water, while barefoot, or while hands or feet
are wet.
• DO NOT allow unqualified persons or children to operate
or service generator.
Generator voltage could cause
10 BRIGGSandSTRATTON.COM
Not for
Reproduction
Portable Generator Location
Before starting the portable generator there are two
equally important safety concerns regarding carbon
monoxide (CO) poisoning and fire that must be
addressed.
NOTICE Satisfying the RISK OF CARBON
MONOXIDE POISONING location requirements may
not satisfy the fire location requirements. Satisfying the
RISK OF FIRE location requirements may not satisfy
the CARBON MONOXIDE POISONING location
requirements.
Operation Location of Portable Generator to
REDUCE THE RISK OF CARBON MONOXIDE
POISONING
All fossil fuel burning equipment, such as a portable
generator, contains carbon monoxide (CO) gas in the
engine exhaust, a poisonous gas that could kill you in
minutes. You CANNOT smell it, see it, or taste it. Even
if you do not smell exhaust fumes, you could still be
exposed to carbon monoxide gas. The following must
be completed prior to starting the portable generator
engine:
• By law it is required in many states to have a
Carbon Monoxide (CO) alarm (A) in operating
condition in your home. Install/maintain batteryoperated carbon monoxide alarms or plug-in
carbon monoxide alarms with battery back-up
according to the manufacturer’s instructions. A
CO alarm is an electronic device that detects
hazardous levels of CO. When there is a buildup
of CO, the alarm will alert the occupants by
flashing visual indicator light and alarm. Smoke
alarms cannot detect CO gas.
A
• Operate this product ONLY outside far away from
windows, doors and vents to reduce the risk of
carbon monoxide gas from accumulating and
potentially being drawn towards occupied spaces.
• DO NOT run this product inside homes, garages,
basements, crawlspaces, sheds, or other partiallyenclosed spaces even if using fans or opening
doors and windows for ventilation. Carbon
monoxide can quickly build up in these spaces
and can linger for hours, even after this product
has shut off.
• Your neighbor(s) home may be exposed to the
engine exhaust from your portable generator and
must be considered when deciding on a location
for the safe operation of your portable generator.
• ALWAYS place this product downwind and point
the engine exhaust away from occupied spaces.
If you start to feel sick, dizzy, or weak while using this
product, get to fresh air RIGHT AWAY. See a doctor.
You may have carbon monoxide poisoning.
11
Not for
Reproduction
EXAMPLE OF LOCATION TO REDUCE THE RISK OF CARBON MONOXIDE
POISONING
CO Alarm
A
H
U
X
S
E
T
(
C
O
)
KEEP
FAR AWAY
in Living Areas
Direct exhaust AWAY
from windows, doors,
and vents.
DO NOT OPERATE IN ANY OF THE FOLLOWING LOCATIONS
Only use OUTSIDE
and FAR AWAY from
windows, doors and vents.
Attic
Entryway,
Porch
Garage
Living Area
Basement
Crawlspace
A
H
X
U
E
S
T
(
C
O
)
Generator too
close to home
and exhaust
directed towards
windows, doors
and vents.
12 BRIGGSandSTRATTON.COM
Not for
Reproduction
Operation Location of Portable Generator to
REDUCE THE RISK OF FIRE
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage fuel
tank causing a fire, resulting in death or
serious injury.
• Portable generator must be at least 5 ft. (1.5 m) from
any structure, overhang, trees, windows, doors, any wall
opening, shrubs, or vegetation over 12 inches (30.5 cm)
in height.
• DO NOT place portable generator under a deck or other
type of structure that may confine airflow.
• Smoke alarm(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Carbon monoxide alarms cannot
detect smoke.
• DO NOT place portable generator in manner other than
shown.
EXAMPLE OF LOCATION TO REDUCE THE RISK OF FIRE
5 ft. (1.5 m) min.
H
A
X
E
U
S
T
(
C
O
)
5 ft. (1.5 m) min.
Direct exhaust AWAY from
windows, doors, and vents.
13
Not for
Reproduction
Features and Controls
Read this Operator’s Manual and safety rules before operating your generator.
Compare the illustrations with your generator, to familiarize yourself with the locations of various controls
and adjustments. Save this manual for future reference.
A
B
C
D
N
M
L
K
J
E
F
G
A - Rocker Switch — Set this switch to ON (I) before
using recoil starter. Set switch to OFF (0) to shut
off engine.
B - 120 Volt AC, 30 Amp Travel Trailer Receptacle
— May be used to supply electrical power for the
operation of 120 Volt AC, 30 Amp, single phase,
60 Hz electrical, travel trailer loads.
C - Circuit Breakers — Push-to-reset circuit breakers
are provided to protect the generator against
electrical overload.
D - 120 Volt AC, 20 Amp, GFCI Duplex Receptacle
— May be used to supply electrical power for the
operation of 120 Volt AC, 20 Amp, single phase,
60 Hz electrical, lighting, appliance, tool and motor
loads.
E - Oil Fill Cap — Check and add engine oil here.
F - Oil Drain Plug — Drain engine oil here.
G - Grounding Fastener — Consult your local agency
having jurisdiction for grounding requirements in
your area.
H
H - Spark Arrester Muffler — Exhaust muffler lowers
engine noise and is equipped with a spark arrester
screen.
J - Recoil Starter — Used to start the engine
manually.
K - Air Cleaner — Protects engine by filtering dust
and debris out of intake air.
L - Choke Lever — Used when starting a cold engine.
M - Fuel Valve — Used to turn fuel supply on and off to
engine.
N - Fuel Tank — Capacity of four (4) U.S. gallons
(15.14 l).
Items Not Shown:
Engine Identification — Provides model, type and
code of engine. Please have these readily available if
calling for assistance.
Identification Label — Provides model and serial
number of generator. Please have these readily
available if calling for assistance.
14 BRIGGSandSTRATTON.COM
Not for
Reproduction
Cord Sets and Receptacles
Use only high quality, well-insulated, grounded
extension cords with the generator’s receptacles.
Inspect extension cords before each use.
Check the ratings of all extension cords before you
use them. Check operator’s manuals of devices to be
powered for the manufacturer’s recommendations.
WARNING Damaged or overloaded electrical
cords could overheat, arc, and burn
resulting in death or serious injury.
• ONLY use cords rated for your loads.
• Follow all safeties on electrical cords.
• Inspect cord sets before each use.
120 Volt AC, 30 Amp Travel Trailer Receptacle
Use a NEMA TT–30 plug with this receptacle. Connect
a 3–wire travel trailer cord set rated for 125 Volt AC
loads at 30 Amps to the plug.
NEMA TT-30
Hot
120V
Use this receptacle to operate 120 Volt AC, 60 Hz,
single phase travel trailer loads requiring up to
3,500 watts (3.5 kW) of power at 29.16 Amps. The
outlet is protected by a push-to-reset circuit breaker.
NOTICE
value greater than generator output capacity.
• NEVER attempt to power a device requiring more
amperage than generator or receptacle can supply.
• DO NOT overload the generator. See Don’t Overload Generator.
Receptacles may be marked with rating
Ground (Green)
Neutral
120 Volt AC, 20 Amp, GFCI Duplex Receptacle
The duplex receptacle is protected against overload by
a push–to–reset circuit breaker.
Use receptacle to operate 120 Volt AC, single-phase,
60 Hz electrical loads requiring up to 2,400 watts
(2.4 kW) at 20 Amps of current. Use cord sets that are
rated for 125 Volt AC loads at 20 Amps (or greater).
Ground Fault Protection
The duplex receptacle is equipped with Ground Fault
Circuit Interrupter (GFCI) protection. This device
meets applicable federal, state and local codes. The
generator’s travel trailer receptacle is not protected by
a Ground Fault Circuit Interrupter (GFCI).
The GFCI protects against electrical shock that may be
caused if your body becomes a path which electricity
travels to reach ground. This could happen if you touch
a “Live” appliance or wire, or are touching plumbing or
other materials that connect to the ground.
When protected by a GFCI, one may still feel a shock,
but the GFCI should cut current off quickly enough so
that a person in normal health should not suffer any
serious electrical injury.
WARNING
electrical shock or burn resulting in death or
serious injury.
• Contact with the hot and neutral conductor at the same
time can cause electrical shock or burn, even if the circuit
is GFCI protected.
• Before using the GFCI receptacle, ALWAYS push the
test button to insure it works.
Testing the GFCI
Test your GFCI outlet prior to each use, as follows:
• Push the “Test” button. The “Reset” button should
pop out, which should allow no power to reach the
outlet. Use a test lamp in each outlet to test this.
• If the GFCI tests good, restore power by pressing
the “Reset” button firmly until it is fully in place
and locks in that position. If the GFCI outlet
does not reset properly, do not use the outlet.
Call or take your generator to a local service
center.
• If the GFCI trips by itself at any time, reset and
test the outlet. If the reset button does not pop
out when the test button is pressed, do not
use the outlet. Call or take your generator to
a local service center.
Generator voltage could cause
15
Not for
Reproduction
Operation
Starting the Engine
Disconnect all electrical loads from the generator. Use
the following start instructions:
1. Make sure unit is on a level surface.
NOTICE Failure to start and operate the unit on a
level surface could cause the unit not to start or shut
down during operation.
2. Turn the fuel valve (A) to the ON (I) position.
A
3. Push choke lever (B) to CHOKE () position.
B
4. Push rocker switch (C) to ON (I) position.
C
5. Grasp recoil handle and pull slowly until slight
resistance is felt. Then pull rapidly one time only
to start engine.
• If engine starts, proceed to step 7.
• If engine fails to start, proceed to step 6.
6. Move choke lever to HALF choke position, and
pull recoil handle twice.
• If engine fails to start, repeat steps 5 thru 7.
7. Slowly move choke lever to RUN (
engine falters, move choke lever to HALF choke
position until engine runs smoothly, and then to
RUN () position.
NOTICE If engine floods, place choke lever in
RUN () position and crank until engine starts.
NOTICE If engine starts after 3 pulls but fails to run,
or if unit shuts down during operation, make sure unit
is on a level surface and check for proper oil level in
crankcase. This unit may be equipped with a low oil
protection device. If so, oil must be at proper level for
engine to start.
WARNING Exhaust heat/gases could ignite
combustibles, structures or damage
fuel tank causing a fire, resulting in
death or serious injury.
Contact with muffler area could cause burns
resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Keep at least 5 ft. (1.5 m) of clearance on all sides of
generator including overhead.
• It is a violation of California Public Resource Code,
Section 4442, to use or operate the engine on any forestcovered, brush-covered, or grass-covered land unless
the exhaust system is equipped with a spark arrester, as
defined in Section 4442, maintained in effective working
order. Other states or federal jurisdictions may have
similar laws.
Contact the original equipment manufacturer, retailer,
or dealer to obtain a spark arrester designed for the
exhaust system installed on this engine.
• Replacement parts must be the same and installed in the
same position as the original parts.
) position. If
WARNING Starter cord kickback (rapid
retraction) will pull hand and arm toward
engine faster than you can let go which
could cause broken bones, fractures,
bruises, or sprains resulting in serious injury.
• When starting engine, pull cord slowly until resistance is
felt and then pull rapidly to avoid kickback.
• NEVER start or stop engine with electrical devices
plugged in and turned on.
16 BRIGGSandSTRATTON.COM
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.