Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual

TABLE OF CONTENTS

TABLE OF CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SAFETY RULES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
For the Home or Business Owner: . . . . . . . . . . . . . . 4
For the Installing Dealer/Contractor: . . . . . . . . . . . . . 4
Owner Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installer Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . 4
Equipment Description. . . . . . . . . . . . . . . . . . . . . . . . . 5
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Delivery Inspection . . . . . . . . . . . . . . . . . . . . . . . . 5
Shipment Contents . . . . . . . . . . . . . . . . . . . . . . . . 5
Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . 5
Mounting Guidelines . . . . . . . . . . . . . . . . . . . . . . . 6
Power Wiring Interconnections . . . . . . . . . . . . . . . . 6-7
SYSTEM OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
TESTING THE AUTOMATIC TRANSFER SWITCH . . . . 8
Automatic Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Utility Fail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Engine Warm-Up . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Utility Pickup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Retransfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Engine Cool Down . . . . . . . . . . . . . . . . . . . . . . . . 8
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Model 01813 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Model 01814 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
When Calling The Factory . . . . . . . . . . . . . . . . . . . . . . 8
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
DIAGRAMS, EXPLODED VIEWS, PARTS LISTS . . . . . 10-13
NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual

SAFETY RULES

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
The safety alert symbol ( ) is used with a signal word (DANGER, CAUTION,WARNING), a pictorial and/or a safety message to alert you to hazards. DANGER indicates a hazard which, if not avoided, will result in death or serious injury. WARNING indicates a hazard which, if not avoided, could result in death or serious injury. CAUTION indicates a hazard which, if not avoided, might result in minor or moderate injury. CAUTION, when used without the alert symbol, indicates a situation that could result in equipment damage. Follow safety messages to avoid or reduce the risk of injury or death.
The manufacturer cannot possibly anticipate every possible circumstance that might involve a hazard.The warnings in this manual, and the tags and decals affixed to the unit are, therefore, not all-inclusive. If you use a procedure, work method or operating technique that the manufacturer does not specifically recommend, you must satisfy yourself that it is safe for you and others.You must also make sure that the procedure, work method or operating technique that you choose does not render the transfer switch unsafe.
• DO NOT touch bare wires or receptacles.
• DO NOT use transfer switch with worn, frayed, bare or otherwise damaged wiring.
• DO NOT handle electrical cords while standing in water, while barefoot, or while hands or feet are wet.
• If you must work around a unit while it is operating, stand on an insulated dry surface to reduce shock hazard.
• DO NOT allow unqualified persons or children to operate or service transfer switch.
• In case of an accident caused by electrical shock, immediately shut down the source of electrical power and contact local authorities. Avoid direct contact with the victim.
Failure to properly ground transfer switch can result in electrocution.
WARNING
Only qualified electricians should attempt installation
of this system, which must strictly comply with
applicable codes, standards and regulations.
WARNING
• Use transfer switch only for intended uses.
• If you have questions about intended use, ask dealer or contact Briggs and Stratton Power Products.
• DO NOT expose transfer switch to excessive moisture, dust, dirt, or corrosive vapors.
• Despite the safe design of the transfer switch, operating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death.
• Remain alert at all times while working on this equipment. NEVER work on the equipment when you are physically or mentally fatigued.
• If connected devices overheat, turn them off and turn off their circuit breaker/fuse.
Improper treatment of transfer switch can damage it and shorten its life.
CAUTION
4
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
INTRODUCTION
Thank you for your purchase of this Briggs & Stratton
Power Products Automatic Transfer Switch.This product is intended for use with Briggs & Stratton Home Standby Generator sets ONLY.This is an optional home standby system which provides an alternate source of electric power and to serve loads such as heating, refrigeration systems, and communication systems that, when stopped during any power outage, could cause discomfort, or the like.This product DOES NOT qualify for emergency standby as defined by NFPA 70 (NEC).
Briggs and Stratton Power Products (BSPP) has made every effort to provide for a safe, streamlined and cost-effective installation. Each installation is unique, it is impossible to know of and advise of all conceivable procedures and methods by which installation might be achieved.We could not know of possible hazards and/or the results of each method or procedure. For these reasons,
Only licensed electrical contractors should
install transfer switches. Installations must
strictly comply with all applicable federal,
state and local codes, standards and
regulations.
Your BSPP Transfer Switch is supplied with this combined “Installation and Owner’s Manual”.This is an important document and should be retained by the owner after the installation has been completed.
Every effort has been expended to make sure that the information in this manual is both accurate and current. However, the manufacturer reserves the right to change, alter or otherwise improve the system at any time without prior notice.
For the Home or Business Owner
To help you make informed choices and communicate effectively with your installation contractor(s),
Read and understand the
Owner Orientation Section of this manual
BEFORE
contracting or starting
your transfer switch installation.
To arrange for proper installation, contact the store at which you purchased your BSPP Transfer Switch, your dealer, or your utility power provider.
The Transfer Switch Warranty is VOID
unless the system is installed by a
licensed electrical professional.
For the Installing Dealer/Contractor
Check federal, state and local codes for questions on
installation.
If you need more information about the transfer switch,
call 1-800-743-4115, between 8:00 AM and 5:00 PM CT.
Owner Orientation
The illustrations are for typical circumstances and are meant to familiarize you with the installation options available with your transfer switch.
Local codes, appearance, and distances are the factors that must be considered when negotiating with an installation professional.As the distance from the existing electrical service increases, compensation in wiring materials must be allowed for.This is necessary to comply with local codes and overcome electrical voltage drops.
The factors mentioned above will have a direct effect on the overall price of your transfer switch installation.
NOTE:Your installer must check local codes AND obtain
permits before installing the system.
• Read and follow the instructions given in this manual.
• Follow a regular schedule in caring for and using your transfer switch, as specified in the manual.
Installer Responsibilities
• Read and observe the safety rules.
• Read and follow the instructions given in this manual.
• Check federal, state and local codes.
5
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
Equipment Description
These switches are a new generation of transfer switches that are intended to transfer the entire load of normal residential installations.The load is connected either to utility power (normal) or home standby power (emergency).The transfer switch monitors utility and generator voltages and will automatically connect to the appropriate source of power.
Major components of the transfer switch are a 2 pole double throw transfer switch, control circuit board, fused utility terminals and interconnecting wiring.
The transfer switch is solenoid-operated from utility or generator inputs and contain suitable mechanical and electrical interlock switches to eliminate the possibility of connecting the utility service to the generator output. It has ratings capable of switching full utility power into the residence. In addition, a manual override lever is provided for the transfer function.
The control circuit board has active circuits sensing utility and generator voltages. It creates a signal for the generator start-up, switch transfer, retransfer when utility is restored and generator cool down periods.The control board also contains red and green LED’s indicating the power sources available and two relay operated contacts that provide supervisory control of external loads.
INSTALLATION
Unpacking
Delivery Inspection
After removing the carton, carefully inspect the transfer switch components for any damage that may have occurred during shipment.
IMPORTANT: If loss or damage is noted at time of delivery, have the person(s) making delivery note all damage on the freight bill and affix his signature under the consignor's memo of loss or damage. If loss or damage is noted after delivery, contact the carrier for claim procedures. Missing or damaged parts are not warranted.
Shipment Contents
• Automatic Power Transfer Switch
• Installation and Owner’s Manual
Mounting Dimensions
Figure 1 depicts the physical size and mounting hole locations of the NEMA 3R automatic transfer switch enclosure.This enclosure is suitable for indoor/outdoor use.
The transfer switch enclosure is commonly secured through the predrilled holes, as shown.
Figure 1 — Automatic Power Transfer Switch Dimensions
Model 01813
Model 01814
Enclosure Dimensions
Mounting Dimensions
Enclosure Dimensions
Mounting Dimensions
6
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
Mounting Guidelines
The Automatic Transfer Switch is enclosed in a NEMA Type 3R enclosure suitable for indoor/outdoor use. Guidelines for mounting the Automatic Transfer Switch include:
• Install the switch on a firm, sturdy supporting structure.
• The switch must be installed with minimum NEMA 3R hardware for conduit connections.
• To prevent switch contact distortion, level and plumb the enclosure.This can be done by placing washers between the switch enclosure and the mounting surface.
• NEVER install the switch where any corrosive substance might drip onto the enclosure.
• Protect the switch at all times against excessive moisture, dust, dirt, lint, construction grit and corrosive vapors.
A typical installation of the Automatic Power Transfer Switch is depicted in Figure 2. It is best if it is mounted near the utility meter, either inside or outside. Discuss layout suggestions/changes with the owner before beginning the system installation process.
Power Wiring Interconnections
All wiring must be the proper size, properly supported and protected by conduit.
Complete the following connections between the transfer switch, main distribution panel, utility power and generator (Figure 3, on next page).
1. Ensure utility power is turned OFF. Connect utility
power supply leads to transfer switch terminals marked “UTILITY CONNECTION”.
2. Connect utility neutral to the transfer switch
“NEUTRAL” terminal.
3. Connect main distribution panel power leads to transfer switch terminals marked “LOAD CONNECTION”.
4. Connect main distribution panel neutral lead to transfer switch “NEUTRAL” terminal.
5. Connect generator power supply leads from the generator’s control panel to transfer switch terminals marked “GENERATOR CONNECTION”.
6. Connect generator Neutral from the control panel to the transfer switch “NEUTRAL” terminal.
7. Connect generator “GND” from the control panel to the transfer switch “GND” terminal.
8. Connect main distribution panel “GND” to the transfer switch “GND” terminal.
9. Connect generator utility 240 VAC terminals to transfer switch utility 240 VAC terminals.
10. Terminal strip on control module in transfer switch has four connections for customer use.There are two sets of “Normally Closed” contacts available.They will be activated when generator power is required.These can be used for supervisory control of large connected loads on generator, for example, disconnecting air conditioner, water heater, etc. or an alarm source.
11. Tighten all wire connections/fasteners to proper torque.
• Failure to follow above warning could cause damage and/or malfunction of equipment.
Low voltage wire cannot be installed in same conduit as power voltage wiring.
CAUTION
Figure 2 — A Typical Transfer Switch Mounting
Main
Breaker
Panel
Transfer Switch
Generator
Service
Disconnect
Watt-
Hourmeter
7
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
Figure 3 — A Typical Installation Diagram for Transfer Switch
MODEL 01813
MODEL 01814
Main
Main Distribution Panel
Ground Bus
Neutral
Bus
To Generator
Neutral
Terminal
To Utility Power
Normally
Closed
Contacts
Load
Connection
Ground Lug
Generator
Connection
Utility
Connection
Main
Main Distribution Panel
Ground Bus
Neutral
Bus
To Generator
Neutral
Terminal
To Utility Power
Normally
Closed
Contacts
Load
Connection
Ground Lug
Generator
Connection
Utility
Connection
8
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
SYSTEM OPERATION
To select automatic transfer operation, do the following:
1. Set service disconnect switch that sends utility power
to transfer switch to “On” position.
2. Set generator’s main circuit breaker to its “On”
position.
3. Install 15 Amp fuse in control panel on generator.
4. Set AUTO/OFF/MANUAL switch on generator to
AUTO” position.
The system will now be in automatic operation mode.
TESTING THE
AUTOMATIC TRANSFER SWITCH
Turn the service disconnect feeding the transfer switch, to the “Off” position.The automatic sequence will follow.To go back to utility power, turn the service disconnect to the “On” position.
Automatic Sequence
Utility Fail
Utility voltage sensor senses when utility voltage is below 70 percent of nominal. Engine start sequence is initiated after 6 second time delay.
Engine Warm-Up
Time delay to allow for engine warm-up before transfer fixed at 20 seconds or 50 seconds with optional cold weather package.
Transfer
Transfers from utility to standby supply occurs after standby voltage is above set levels. Minimum engine run time is 4 minutes after transfer.
Utility Pickup
Voltage pickup level is 80 percent of nominal voltage.
Retransfer
Retransfer from standby to utility supply 10 seconds after utility voltage supply is above pickup level.
Engine Cool Down
Engine will run for 60 seconds after retransfer.
Specifications
UL® 1008 Listed Transfer Switch Model 01813
Maximum Load/Circuit:
from Load Center . . . . . . . . . . 100 Amps
Rated AC Voltage. . . . . . . . . . . . . 250 Volts
Poles . . . . . . . . . . . . . . . . . . . . . . 2
Frequency . . . . . . . . . . . . . . . . . . 50/60 Hz
Fault Current Rating . . . . . . . . . . 22,000 RMS Symmetrical
Amperes Supervisory Contacts Rating . . . 5 Amp, 125 Volt AC
Weight . . . . . . . . . . . . . . . . . . . . . 21 lbs.
Model 01814
Maximum Load/Circuit:
from Load Center . . . . . . . . . . 200 Amps
Rated AC Voltage. . . . . . . . . . . . . 250 Volts
Poles . . . . . . . . . . . . . . . . . . . . . . 2
Frequency . . . . . . . . . . . . . . . . . . 50/60 Hz
Fault Current Rating . . . . . . . . . . 25,000 RMS Symmetrical
Amperes Supervisory Contacts Rating . . . 5 Amp, 125 Volt AC
Weight . . . . . . . . . . . . . . . . . . . . . 34 lbs.
When Calling the Factory
Before contacting Briggs and Stratton Power Products regarding service or repair of this transfer switch, obtain the Model Number and Serial Number from the unit data decal located on or inside the case.
To contact Briggs and Stratton Power Products call 1-800-743-4115, between 8:00 AM and 5:00 PM CT.
9
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
TROUBLESHOOTING
Problem
Automatic transfer switch does not transfer to generator
Automatic transfer switch does not transfer to utility
Generator is still running after switch transfers to utility power
Supervised loads (air conditioner, etc.) are not operating when utility is present
Cause
1. Generator breaker open.
2. Generator voltage not acceptable.
1. Service disconnect breaker open.
2. Utility voltage not acceptable.
Engine cool down period.
NC contacts not operating correctly.
Correction
1. Reset generator circuit breaker.
2. Refer to generator manual.
1. Reset service disconnect breaker.
2. Wait for utility voltage to return to normal.
Engine should stop after 1 minute.
Check NC contact for proper operation and/or check control wiring to external load.
10
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
TRANSFER SWITCH SCHEMATIC
11
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
TRANSFER SWITCH WIRING DIAGRAM