Bray GAS Series, GASRE24-450, GASEX24-450 Operating Instructions Manual

Bray Controls Commercial Division 13788 West Road, Suite 200A Houston, Texas 77041
BCDSales@Bray.com Phone: 1-888-412-2729 Fax: 1-888-412-2720 www.braycommercialdivision.com
GAS Series - ActuatorOperating Instructions
1/28/19
GAS -Spring Return Actuator - (GASRE24-450 & GASEX24-450)
24V, On/O, Floating and Modulating Automatic adaptation to valve, precision control and high energy eciency with minimal operating noise.
Features
• Actuator with spring return action and pushing force of 450 lbs. (2000 N), in 'normally retracted' or 'normally extended' versions
• DC motor with electronic control unit and electronic load- dependent cut-o
• Automatic detection of control signal applied (modulating or oating), display via 2 LEDs
• The type of characteristic curve (linear, quadratic or equal percentage) can be adjusted in the drive
• Independent adaptation to valve stroke between 0.31 in.(8 mm) and 1.57 in.(40 mm), captive even if the power is turned o
• Direction of travel can be selected via screw terminals when making electrical connection or remotely
• Hand crank for external manual adjustment with motor cut-o and as trip for re-calibration
• Easy assembly with valve, spindle connection takes place automatically after application of control voltage
• Many adaptor kits allow assembly on third-party valves
Technical Description
• Two-part housing made of self-extinguishing red plastic and sealing to IP66 (equivalent to NEMA 4) protection class
• Maintenance-free gearbox in sintered steel, gearbox base-plate in steel
• Spring assembly in Stainless Steel
• Patented drive-valve coupling
• Mounting column made of stainless steel and mounting bracket for tting valve made of cast light alloy
• Electrical connections 13 AWG (max. 2.5 mm²) with screw terminals
• Three knock-out cable entries for M20×1.5 (2×) and M16×1.5
• Fitting position: vertical to horizontal, but not upside down
Accessories
Auxillary Switches
0372333 001 Continuously adjustable, min. 100 mA and 12 V, additional load 6(2) A 0372333 002 Gold-plated contacts, from 1 mA and up to 30 V, further range 3(1) A Adaptor kits for Industrial Globe Valves GA-MTG-01 DG250-x and DG3-x GA-MTG-02 DG4-x, DG5-x and DG6-x Fittings 0386263 001 Screwed cable tting M16 X 1.5 0386263 002 Screwed cable tting M20 X 1.5
High Media Temperature Kit
0372336 240 Adaptor required for medium temperatures between 266˚F (130˚C) and 464˚F (240˚C)
Operation
After a new start, up to 45 s of waiting time will pass before the drive is available again. Depending on the type of connection (see the wiring diagram), the device can be used as a modulating drive (0...10 V and/or 4...20 mA), a On/O (2-point) drive (extend/retract) or a Floating (3-point) drive (extend/stop/retract). The run time of the drive can be set according to the specic requirements, using switches S1 and S2. Switches S3 and S4 are used to congure the characteristic curve (equal percentage, linear or quadratic). The external hand crank allows you to adjust the position manually. When the hand crank is folded out, the motor is switched o. After the hand crank is folded back, the spring function is active again and the setpoint position is adopted again (without calibration). If the hand crank is unfolded, the drive stays in this position.
Calibration and feedback signal
The drive calibrates itself automatically, whether it is used in a modulating, On/O (2-point )or Floating (3-point) mode. Voltage needs to be applied to terminal 21. As soon as voltage is applied to either terminals 2a or 2b for the rst time and the waiting period (both LEDs green) of approximately 45 seconds has elapsed, the drive moves to the lower limit stop on the valve, thus enabling automatic connection with the valve spindle. Then it moves to the upper limit stop, and the value is recorded and saved with the help of a path measurement system.
GAS Series - ActuatorsOperating Instructions Continued
Calibration and feedback signal - Continued
The control signal and the feedback signal are adjusted to this eective stroke. After an interruption to the voltage or a spring return action, no re-calibration is performed and the values are saved. Calibration must be performed in order to utilize the feedback signal when On/O (2-point) or Floating (3-point) control is required. Terminal 44 is 0-10 VDC feedback. The feedback signal always increases as the shaft extends.
Re-Calibration
To re-calibrate, voltage needs to be applied to either terminals 2a or 2b and terminal 21. Prior to re-calibration if power has been disconnected or terminal 21 has lost power there will be a waiting period (both LEDs ash green) of approximately 45 seconds. To trigger re-calibration, fold the hand crank out and back in again twice within 4 seconds. Each time the hand crank is folded out rotate it slightly in either direction until a clicking sound is heard. Both the LEDs will then ash red.
During re-calibration, the feedback signal is inactive, or it corresponds to a value of "0". Re-calibration uses the shortest run time. The re-calibration is only valid once the entire procedure has been completed. Folding the hand crank out again will interrupt the procedure. If the actuator detects a blockage, it will report this by setting the feedback signal to 0 V after approx. 90's. However, the drive will try to overcome the blockage during this time. If it is possible to overcome the blockage, the normal control function is activated again and the feedback signal is restored.
Spring Return
If the voltage supply fails or is switched o, or if a terminal 21is disconnected, the brush- less DC motor releases the gear and the drive is moved into the respective end position (depending on the design version) by the pre-tensioned spring. As this happens, the control function of the drive is disabled for approximately 45 seconds (both LEDs green) so that the end position can be reached in every case. The reset speed is controlled with the help of the motor so that there are no pressure surges in the line. The brushless DC motor has three functions: as a magnet to hold the position, as a brake (by acting as a generator) and as a motor for the control function. After a spring return function, the drive does not re- calibrate itself.
Connection as a On/O (2-point) Actuator
This activation can take place via two cables. Voltage is applied to terminals 2a and 21. Applying the voltage (24 V) to terminal 2b causes the actuator shaft to extend. After this voltage has been switched o, the drive moves to the opposite end position. The electronic motor switch-o responds in the end positions (valve limit stop, or when maximum stroke is reached) or in case of overload (no limit switches). The coding switch can be used to set the run times. The characteristic curve cannot be selected in this case (resulting in the characteristic curve for the valve). The feedback signal is active as long as the calibration was performed. Terminals 3i, 3u must not be connected.
Connection as a Floating (3-point) Actuator
Applying voltage to terminals 21, 2a or 2b makes it possible to move the valve to any desired position. If voltage is applied to 2b, the actuator shaft extends. The shaft retracts when voltage is applied terminal 2a. In the end positions (at the valve stop, or when the maximum stroke is reached) or in case of an over- load, the electronic motor switch-o responds (no limit switches). The direction of the stroke can be changed by transposing the connections. The coding switch is used to set the run times. In this case, the characteristic curve cannot be selected (resulting in the char­acteristic curve for the valve). The feedback signal is active as long as the calibration was performed. Terminals 3i, 3u must not be connected.
Modulating Actuator (0...10 V and/or 4...20 mA)
The built-in positioner controls the drive depending on the controller input signal y. The input signal used is a voltage signal (0...10 V–) at terminal 3u, or a current signal at terminal 3i. If an input signal is present at both terminals (3u (0...10 V) and 3i (4...20 mA)) simultaneously, the input with the higher value takes priority.
Apply voltage to terminal 21.
Mode of action 1 (apply voltage to internal connection 2a): As the input signal increases, the valve shaft extends.
Mode of action 2 (apply voltage to internal connection 2b): As the input signal increases, the valve shaft retracts.
The starting point and the control span are xed. After the voltage supply is applied and after calibration, the drive moves to each valve stroke between 0% and 100%, depending on the input signal. The electronics and the path measurement system ensure that no stroke is lost, and the drive does not require re-calibration at intervals. When the end positions are reached, the position is checked, corrected as necessary and stored again. This ensures parallel running of several drives of the same type. Feedback signal y0 = 0...10 V corresponds to the eective valve extention of 0 to 100%.
GAS Series - ActuatorsOperating Instructions Continued
Modulating Actuator (0...10 V and/or 4...20 mA) - Continued
The coding switch can be used to set the characteristic for the valve. Equal-percentage and square characteristics can only be produced if the device is used as a proportional-action drive. Further switches can be used to select the run-times
(can be used for the On/O (2-point), Floating (3-point) or proportional functions).
LED Display
The display consists of two dual-color LEDs (red / green). Both LEDs ashing red: Calibration procedure Upper LED lit red: Upper limit stop or "shaft fully retracted" position reached Lower LED lit red: Lower limit stop or "shaft fully extended" position reached Upper LED ashing green: Drive running, "shaft retracting" Upper LED lit green: Drive stationary, last direction of running "is shaft retracting" Lower LED ashing green: Drive running, moving towards "fully extended" position Lower LED lit green: Drive stationary, last direction of running "is shaft extending" Both LEDs lit green: Waiting time after switching on or after spring return No LED lit: No voltage supply (terminal 2a or 2b) Both LEDs are ashing red and green: Drive is in manual mode
Engineering and Installation Notes
Penetration of condensate or dripping water, etc. along the valve spindle into the drive should be avoi- ded. The valve is plugged directly onto the drive and is xed with screws (no further settings are needed). The drive is automati­cally connected to the valve spindle. When the device is delivered, the drive spindle is in the middle position. The housing contains three breakthrough-type cable lead-throughs which are broken open automatically when the cable lead-through is screwed in. The stepping motor/electronics concept guarantees parallel running of several valve drives of the same type. The cross-section of the connecting cable should be selected according to the line length and the number of drives. With ve drives connected in parallel and a line length of 50 m, we recommend using a cable cross-section of 1,5 mm2 (power consumption of the drive × 5).
Fitting Outdoors
If the devices are tted outdoors, we recommend that additional measures be taken to protect them against the eects of the weather.
Additional Technical Information
The red housing, comprising the front section, rear section and connection cover, only serves the purpose of a cover. The crank for manual adjustment is located on the front. The DC motor, the control electronics, the supporting components and the maintenance-free gear are accommodated in the housing.
Auxiliary Changeover Switch 0372333 001 Switching capacity max. 250 V~, min. current 250 mA at 12 V (or 20 mA at 20 V) Switching capacity max.
12...30 V=, max. current 100 mA 0372333 002 Switching capacity max. 250 V~, min. current 1 mA at 5 V Switching capacity max. 0.1...30 V=, current
1...100 mA. Even if used only once above 10 mA or up to 50 V, the gold coating will be destroyed. The switch can then be used only for higher switching outputs.
Warnings
• If the temperature of the medium in the valve is high, the drive columns and the shaft may also reach high temperatures.
• Drives with safety functions must be regularly checked to see that they are in working order (trial run).
• If a failure of the nal control element could cause damage, additional protective precautions must be taken.
• It is forbidden to dismantle the springs in the device due to the high risk of injuries.
CE Conformity EMC Directive 2004/108/EC Machinery Directive 98/37/EEC/I/B Low Voltage Directive 2006/95/EC EN 61000-6-1 DIN EN 150 14121 EN 60730-1 EN 61000-6-2 EN 60730-2-14 EN 61000-6-3 Over-voltage category III EN 61000-6-4 Degree of pollution III
GAS Series - ActuatorsOperating Instructions Continued
GAS - Curve Characteristic Switch Settings
Desired
Character.
Curve
Switch Coding
Characteristic Curve for Valve
v
1 2 3 4
On
Off
Equal
percentage
v
Stroke
1 2 3 4
On
Quadratic
Off
Stroke
v
1 2 3 4
On
LinearEqual
Off
Stroke
v
1 2 3 4
On
Off
percentage
v
Stroke
1 2 3 4
On
Linear
Off
Stroke
= factory setting
Characteristic Curve for Drive
Stroke
Signal
Stroke
Signal
Stroke
Signal
Stroke
Signal
Stroke
Signal
Effective on Valve
v
= %
Signal
v
2
x
Signal
v
lin
Signal
v
= %
Signal
v
lin
Signal
GAS - Run Time Switch Settings
Run Time
per
Switch coding
in.(mm)
1 2 3 4
51 (2)
Seconds
102 (4)
1 2 3 4
Seconds
1 2 3 4
153 (6)
Seconds
= factory setting
On
Off
On
Off
On
Off
On
Off
Run time for
0.55 in.(14 mm) stroke
Run time for
0.79 in.(20 mm) stroke
1.58 in.(40 mm)
28s ± 1 40s ± 1 80s ± 2
56s ± 2 80s ± 2 160s ± 4
84s ± 4
120s ± 4 240s ± 8
Run time for
stroke
GAS - Dimensions
0.73 in.
(18.5mm)
B
GAS Series - ActuatorsOperating Instructions Continued
2.24 in.
(57mm)
2.87 in.
(73mm)
Spring Return
9.06 in.(230mm)
Adaptor for media temperatures between
266˚F (130˚C) and 464˚F (240˚C)
C
GAS - Wiring
Modulating
S1
S2 S3 S4
S1; S2 = Runtime S3; S4 = Characteristic
Y = modulating signal 21= Latch voltage for the spring. Lose of power here causes the spring to drive to the fail position. 1= Neutral/Common for power and signal 2a/2b- These terminals determine forward acting/reverse acting. One should be powered with 24V. 2a = Extends. 0 volts = 0% extended. 10V = 100% extended 2b = Retracts. 0 volts = 100% extended. 10V = 0% extended 3u = 0 .. 10 V, in case of control by voltage 3i = 4 .. 20 mA, in case of control by current 44 = 0 .. 10 V Feedback, independent from the use of 3u or 3i
A
3.54 in.(90mm)
Description A B C
GAS Series
_
+
y=0…10V
121 2a 2b 3i 44
3u
2.52 in.
(64mm)
_
+
y=4…20mA
11.38 in.
(289mm)
_
+
yo=0…10V
µC
3u
3i
44
0%
0V
4mA
0V
On
Off
2a
100%
10V
20mA
0%
20mA
100%
10V
4mA
0V
GASEX
GASRE
100%
0%
2pt, 3pt, Cont.
2b
21
10V
0V
10V
M
Shaft
0%
100%
1.73 in.
(44mm)
24 V~/=
Part Number A B
0372336 240
4.31 in.
(109.4mm)
On/Off (2 Point)
24 V~/=
1 2a 2b
21 3u 3i 44
Floating (3 Point)
24 V~/=
121 2a 2b 3u 3i 44
= Extra Low Voltage
A
B
3.94 in.
(100mm)
Options
0372333 001 0372333 002 (Auxillary Switches)
4 5 6 7
8 9
GAS - Specifications
Technical Specifications
Spring Return
Power Requirements
Positioner
1
GASRE24-450
GASEX24-450
On/Off, Floating and Modulating
Control Signal 1
GAS Series - ActuatorsOperating Instructions Continued
On/Off, Floating and Modulating, Shaft Normally Retracted
On/Off, Floating and Modulating, Shaft Normally Extended
24 VAC (±20%) at 50/60 Hz or 24 VDC (±15%)
0 to 10 V, Ri> 100 kΩ
Control Signal 2
Position Feedback Signal
4 to 20 mA, Ri = 50Ω
0 to 10 V, Load >2.5 kΩ
Action Direct or Reverse Acting
Switching Range 300 mv
Power Consumption
2
Spring Return 7.5W, 20VA
Force Spring Return 450 lbs. (2,000 N) Power stroke and spring stroke
Stroke 0.31" to 1.57" (8 mm to 40 mm)
Max. Temperature of Medium
3
Ambient Conditions
Temperature 14˚F to 131˚F (-10˚ to 55˚C)
Humidity 0 to 95% RH without condensation
266˚F (130˚C)
Level of Protection Equivalent to NEMA 4 (IP 66)
Protection Class III to IEC 60730
Enclosure Self-extinguishing plastic sealing equivalent to NEMA 4
Gear Materials
Gears & Gearbox Mounting Column Mounting Bracket
Steel Stainless Steel Cast Light Alloy
Electrical Connection
Motor Run Time sec. per in. (mm)
Spring Run Time
4
Number of Spring Returns
Response Time ­3-Point
Weight Spring Return 12.3 lbs. (5.6 kg)
UL Listed Temperature-Indicating and Regulating Equipment, XAPX, XAPX7. File E366456
1
Also for On/Off (2-point) or Floating (3 point) depending on the connection for 24V
2
Design the transformers for this value, otherwise functional faults may occur.
3
An intermediate piece is required for medium temperatures between 266˚F (130˚C) and 464˚F (240˚C)
4
The return time corresponds to a stroke of 0.55 in. (14 mm) to 1.58 in. (40 mm) and does not depend on the set run time.
Disclaimer - The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Bray office. Bray, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
13 AWG (2.5 mm²) with screw terminals. Three knock-out cable entries for M20×1.5 (2×) and M16×1.5
2 (51), 4 (102), 6 (153), Dip Switch Adjustable
15… 30 seconds
> 40,000
200 ms
~
Loading...