• Three knock-out cable entries for M20×1.5 (2×) and M16×1.5
• Fitting position: vertical to horizontal, but not upside down
Accessories
Auxillary Switches
0372333 001 Continuously adjustable, min. 100 mA and 12 V, additional load 6(2) A
0372333 002 Gold-plated contacts, from 1 mA and up to 30 V, further range 3(1) A
Adaptor kits for Industrial Globe Valves
GA-MTG-01 DG250-x and DG3-x
GA-MTG-02 DG4-x, DG5-x and DG6-x
Fittings
0386263 001 Screwed cable tting M16 X 1.5
0386263 002 Screwed cable tting M20 X 1.5
High Media Temperature Kit
0372336 240 Adaptor required for medium temperatures between 266˚F (130˚C) and 464˚F (240˚C)
Operation
After a new start, up to 45 s of waiting time will pass before the drive is available again. Depending on the type of connection
(see the wiring diagram), the device can be used as a modulating drive (0...10 V and/or 4...20 mA), a On/O (2-point) drive
(extend/retract) or a Floating (3-point) drive (extend/stop/retract). The run time of the drive can be set according to the specic
requirements, using switches S1 and S2. Switches S3 and S4 are used to congure the characteristic curve (equal percentage,
linear or quadratic). The external hand crank allows you to adjust the position manually. When the hand crank is folded out, the
motor is switched o. After the hand crank is folded back, the spring function is active again and the setpoint position is adopted
again (without calibration). If the hand crank is unfolded, the drive stays in this position.
Calibration and feedback signal
The drive calibrates itself automatically, whether it is used in a modulating, On/O (2-point )or Floating (3-point) mode. Voltage
needs to be applied to terminal 21. As soon as voltage is applied to either terminals 2a or 2b for the rst time and the waiting
period (both LEDs green) of approximately 45 seconds has elapsed, the drive moves to the lower limit stop on the valve, thus
enabling automatic connection with the valve spindle. Then it moves to the upper limit stop, and the value is recorded and saved
with the help of a path measurement system.
1
GAS Series - Actuators — Operating Instructions Continued
Calibration and feedback signal - Continued
The control signal and the feedback signal are adjusted to this eective stroke. After an interruption to the voltage or a
spring return action, no re-calibration is performed and the values are saved. Calibration must be performed in order to
utilize the feedback signal when On/O (2-point) or Floating (3-point) control is required. Terminal 44 is 0-10 VDC feedback.
The feedback signal always increases as the shaft extends.
Re-Calibration
To re-calibrate, voltage needs to be applied to either terminals 2a or 2b and terminal 21. Prior to re-calibration if power has
been disconnected or terminal 21 has lost power there will be a waiting period (both LEDs ash green) of approximately
45 seconds. To trigger re-calibration, fold the hand crank out and back in again twice within 4 seconds. Each time the hand
crank is folded out rotate it slightly in either direction until a clicking sound is heard. Both the LEDs will then ash red.
During re-calibration, the feedback signal is inactive, or it corresponds to a value of "0". Re-calibration uses the shortest run
time. The re-calibration is only valid once the entire procedure has been completed. Folding the hand crank out again will
interrupt the procedure. If the actuator detects a blockage, it will report this by setting the feedback signal to 0 V after
approx. 90's. However, the drive will try to overcome the blockage during this time. If it is possible to overcome the blockage,
the normal control function is activated again and the feedback signal is restored.
Spring Return
If the voltage supply fails or is switched o, or if a terminal 21is disconnected, the brush- less DC motor releases the gear
and the drive is moved into the respective end position (depending on the design version) by the pre-tensioned spring. As
this happens, the control function of the drive is disabled for approximately 45 seconds (both LEDs green) so that the end
position can be reached in every case. The reset speed is controlled with the help of the motor so that there are no pressure
surges in the line. The brushless DC motor has three functions: as a magnet to hold the position, as a brake (by acting as a
generator) and as a motor for the control function. After a spring return function, the drive does not re- calibrate itself.
Connection as a On/O (2-point) Actuator
This activation can take place via two cables. Voltage is applied to terminals 2a and 21. Applying the voltage (24 V) to
terminal 2b causes the actuator shaft to extend. After this voltage has been switched o, the drive moves to the opposite
end position. The electronic motor switch-o responds in the end positions (valve limit stop, or when maximum stroke is
reached) or in case of overload (no limit switches).
The coding switch can be used to set the run times. The characteristic curve cannot be selected in this case (resulting in the
characteristic curve for the valve). The feedback signal is active as long as the calibration was performed. Terminals 3i, 3u
must not be connected.
Connection as a Floating (3-point) Actuator
Applying voltage to terminals 21, 2a or 2b makes it possible to move the valve to any desired position. If voltage is applied to
2b, the actuator shaft extends. The shaft retracts when voltage is applied terminal 2a.
In the end positions (at the valve stop, or when the maximum stroke is reached) or in case of an over- load, the electronic
motor switch-o responds (no limit switches). The direction of the stroke can be changed by transposing the connections.
The coding switch is used to set the run times. In this case, the characteristic curve cannot be selected (resulting in the characteristic curve for the valve). The feedback signal is active as long as the calibration was performed. Terminals 3i, 3u must
not be connected.
Modulating Actuator (0...10 V and/or 4...20 mA)
The built-in positioner controls the drive depending on the controller input signal y.
The input signal used is a voltage signal (0...10 V–) at terminal 3u, or a current signal at terminal 3i. If an input signal is
present at both terminals (3u (0...10 V) and 3i (4...20 mA)) simultaneously, the input with the higher value takes priority.
Apply voltage to terminal 21.
Mode of action 1 (apply voltage to internal connection 2a): As the input signal increases, the valve shaft extends.
Mode of action 2 (apply voltage to internal connection 2b): As the input signal increases, the valve shaft retracts.
The starting point and the control span are xed. After the voltage supply is applied and after calibration, the drive moves to
each valve stroke between 0% and 100%, depending on the input signal. The electronics and the path measurement system
ensure that no stroke is lost, and the drive does not require re-calibration at intervals. When the end positions are reached,
the position is checked, corrected as necessary and stored again. This ensures parallel running of several drives of the same
type. Feedback signal y0 = 0...10 V corresponds to the eective valve extention of 0 to 100%.
2
GAS Series - Actuators — Operating Instructions Continued
Modulating Actuator (0...10 V and/or 4...20 mA) - Continued
The coding switch can be used to set the characteristic for the valve. Equal-percentage and square characteristics can only
be produced if the device is used as a proportional-action drive. Further switches can be used to select the run-times
(can be used for the On/O (2-point), Floating (3-point) or proportional functions).
LED Display
The display consists of two dual-color LEDs (red / green).
Both LEDs ashing red: Calibration procedure
Upper LED lit red: Upper limit stop or "shaft fully retracted" position reached
Lower LED lit red: Lower limit stop or "shaft fully extended" position reached
Upper LED ashing green: Drive running, "shaft retracting"
Upper LED lit green: Drive stationary, last direction of running "is shaft retracting"
Lower LED ashing green: Drive running, moving towards "fully extended" position
Lower LED lit green: Drive stationary, last direction of running "is shaft extending"
Both LEDs lit green: Waiting time after switching on or after spring return
No LED lit: No voltage supply (terminal 2a or 2b)
Both LEDs are ashing red and green: Drive is in manual mode
Engineering and Installation Notes
Penetration of condensate or dripping water, etc. along the valve spindle into the drive should be avoi- ded.
The valve is plugged directly onto the drive and is xed with screws (no further settings are needed). The drive is automatically connected to the valve spindle. When the device is delivered, the drive spindle is in the middle position.
The housing contains three breakthrough-type cable lead-throughs which are broken open automatically when the cable
lead-through is screwed in. The stepping motor/electronics concept guarantees parallel running of several valve drives of
the same type. The cross-section of the connecting cable should be selected according to the line length and the number
of drives. With ve drives connected in parallel and a line length of 50 m, we recommend using a cable cross-section of 1,5
mm2 (power consumption of the drive × 5).
Fitting Outdoors
If the devices are tted outdoors, we recommend that additional measures be taken to protect them against the eects of
the weather.
Additional Technical Information
The red housing, comprising the front section, rear section and connection cover, only serves the purpose of a cover. The
crank for manual adjustment is located on the front. The DC motor, the control electronics, the supporting components and
the maintenance-free gear are accommodated in the housing.
Auxiliary Changeover Switch
0372333 001 Switching capacity max. 250 V~, min. current 250 mA at 12 V (or 20 mA at 20 V) Switching capacity max.
12...30 V=, max. current 100 mA
0372333 002 Switching capacity max. 250 V~, min. current 1 mA at 5 V Switching capacity max. 0.1...30 V=, current
1...100 mA. Even if used only once above 10 mA or up to 50 V, the gold coating will be destroyed.
The switch can then be used only for higher switching outputs.
Warnings
• If the temperature of the medium in the valve is high, the drive columns and the shaft may also reach high temperatures.
• Drives with safety functions must be regularly checked to see that they are in working order (trial run).
• If a failure of the nal control element could cause damage, additional protective precautions must be taken.
• It is forbidden to dismantle the springs in the device due to the high risk of injuries.
CE Conformity
EMC Directive 2004/108/EC Machinery Directive 98/37/EEC/I/B Low Voltage Directive 2006/95/EC
EN 61000-6-1 DIN EN 150 14121 EN 60730-1
EN 61000-6-2 EN 60730-2-14
EN 61000-6-3 Over-voltage category III
EN 61000-6-4 Degree of pollution III
3
GAS Series - Actuators — Operating Instructions Continued
GAS - Curve Characteristic Switch Settings
Desired
Character.
Curve
Switch Coding
Characteristic
Curve for Valve
v
1 2 3 4
On
Off
Equal
percentage
v
Stroke
1 2 3 4
On
Quadratic
Off
Stroke
v
1 2 3 4
On
LinearEqual
Off
Stroke
v
1 2 3 4
On
Off
percentage
v
Stroke
1 2 3 4
On
Linear
Off
Stroke
= factory setting
Characteristic
Curve for Drive
Stroke
Signal
Stroke
Signal
Stroke
Signal
Stroke
Signal
Stroke
Signal
Effective on Valve
v
= %
Signal
v
2
x
Signal
v
lin
Signal
v
= %
Signal
v
lin
Signal
GAS - Run Time Switch Settings
Run Time
per
Switch coding
in.(mm)
1 2 3 4
51 (2)
Seconds
102 (4)
1 2 3 4
Seconds
1 2 3 4
153 (6)
Seconds
= factory setting
On
Off
On
Off
On
Off
On
Off
Run time for
0.55 in.(14 mm)
stroke
Run time for
0.79 in.(20 mm)
stroke
1.58 in.(40 mm)
28s ± 140s ± 180s ± 2
56s ± 280s ± 2160s ± 4
84s ± 4
120s ± 4240s ± 8
4
Run time for
stroke
GAS - Dimensions
0.73 in.
(18.5mm)
B
GAS Series - Actuators — Operating Instructions Continued
2.24 in.
(57mm)
2.87 in.
(73mm)
Spring Return
9.06 in.(230mm)
Adaptor for media temperatures between
266˚F (130˚C) and 464˚F (240˚C)
C
GAS - Wiring
Modulating
S1
S2 S3 S4
S1; S2 = Runtime
S3; S4 = Characteristic
Y = modulating signal
21= Latch voltage for the spring. Lose of power here causes the spring to drive to the fail position.
1= Neutral/Common for power and signal
2a/2b- These terminals determine forward acting/reverse acting. One should be powered with 24V.
2a = Extends. 0 volts = 0% extended. 10V = 100% extended
2b = Retracts. 0 volts = 100% extended. 10V = 0% extended
3u = 0 .. 10 V, in case of control by voltage
3i = 4 .. 20 mA, in case of control by current
44 = 0 .. 10 V Feedback, independent from the use of 3u or 3i
A
3.54 in.(90mm)
Description A B C
GAS Series
_
+
y=0…10V
1212a 2b3i44
3u
2.52 in.
(64mm)
_
+
y=4…20mA
11.38 in.
(289mm)
_
+
yo=0…10V
µC
3u
3i
44
0%
0V
4mA
0V
On
Off
2a
100%
10V
20mA
0%
20mA
100%
10V
4mA
0V
GASEX
GASRE
100%
0%
2pt, 3pt, Cont.
2b
21
10V
0V
10V
M
Shaft
0%
100%
1.73 in.
(44mm)
24 V~/=
Part Number A B
0372336 240
4.31 in.
(109.4mm)
On/Off (2 Point)
24 V~/=
1 2a 2b
213u 3i 44
Floating (3 Point)
24 V~/=
121 2a 2b 3u 3i 44
= Extra Low Voltage
A
B
3.94 in.
(100mm)
Options
0372333 001
0372333 002
(Auxillary Switches)
4 5 6 7
8 9
5
GAS - Specifications
Technical Specifications
Spring Return
Power
Requirements
Positioner
1
GASRE24-450
GASEX24-450
On/Off, Floating and
Modulating
Control Signal 1
GAS Series - Actuators — Operating Instructions Continued
On/Off, Floating and Modulating, Shaft Normally Retracted
On/Off, Floating and Modulating, Shaft Normally Extended
24 VAC (±20%) at 50/60 Hz
or 24 VDC (±15%)
0 to 10 V, Ri> 100 kΩ
Control Signal 2
Position Feedback
Signal
4 to 20 mA, Ri = 50Ω
0 to 10 V, Load >2.5 kΩ
ActionDirect or Reverse Acting
Switching Range300 mv
Power
Consumption
2
Spring Return7.5W, 20VA
ForceSpring Return450 lbs. (2,000 N) Power stroke and spring stroke
Stroke0.31" to 1.57" (8 mm to 40 mm)
Max. Temperature
of Medium
3
Ambient
Conditions
Temperature14˚F to 131˚F (-10˚ to 55˚C)
Humidity0 to 95% RH without condensation
266˚F (130˚C)
Level of Protection Equivalent to NEMA 4 (IP 66)
Protection Class III to IEC 60730
EnclosureSelf-extinguishing plastic sealing equivalent to NEMA 4
Gear Materials
Gears & Gearbox
Mounting Column
Mounting Bracket
Steel
Stainless Steel
Cast Light Alloy
Electrical
Connection
Motor Run Time
sec. per in. (mm)
Spring Run Time
4
Number of Spring
Returns
Response Time 3-Point
WeightSpring Return12.3 lbs. (5.6 kg)
UL ListedTemperature-Indicating and Regulating Equipment, XAPX, XAPX7. File E366456
1
Also for On/Off (2-point) or Floating (3 point) depending on the connection for 24V
2
Design the transformers for this value, otherwise functional faults may occur.
3
An intermediate piece is required for medium temperatures between 266˚F (130˚C) and 464˚F (240˚C)
4
The return time corresponds to a stroke of 0.55 in. (14 mm) to 1.58 in. (40 mm) and does not depend on the set run time.
Disclaimer - The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond
these specifications, consult the local Bray office. Bray, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
13 AWG (2.5 mm²) with screw terminals.
Three knock-out cable entries for M20×1.5 (2×) and M16×1.5
2 (51), 4 (102), 6 (153), Dip Switch Adjustable
15… 30 seconds
> 40,000
200 ms
~
6
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.