Bray 52 User Manual

SERIES 52
2N1 ProxSensor Valve Status Monitor
OPERATION AND MAINTENANCE MANUAL
BRAY Series 52 Valve Status Monitor Operation and Maintenance Manual
Table Of COnTenTs:
page
SaFeTY INSTRUCTIONS: DeFINITION OF TeRMS .................................................1
aTeX USeR INSTRUCTIONS ..........................................................................................2
INTRODUCTION ................................................................................................................5
TaRgeT MOUNTINg
aDJUSTaBLe TaRgeT MOUNTINg ............................................................. 6
NON-aDJUSTaBLe TaRgeT MOUNTINg ...................................................8
DC pNp VeRSION ..............................................................................................................8
DC NpN VeRSION .............................................................................................................9
INTRINSICaLLY SaFe VeRSION ................................................................................10
FIeLDBUS CapaBLe VeRSIONS
aS-I (aCTUaTOR SeNSOR INTeRFaCe) ....................................................12
DeVICeNeT .......................................................................................................13
pROFIBUS Dp ............................................................................................... 14-15
appLICaTION eXaMpLe # 1 (DC pNp) ............................................................... 16-17
appLICaTION eXaMpLe # 2 (aS-I) ............................................................................18
FOR INFORMaTION ON ThIS pRODUCT aND OTheR BRaY pRODUCTS
pLeaSe VISIT US aT OUR weB page - www.bray.com
BRAY Series 52 Valve Status Monitor
!
!
!
Operation and Maintenance Manual
safeTy InsTruCTIOns - DefInITIOn Of Terms
reaD anD fOllOW THese InsTruCTIOns
saVe THese InsTruCTIOns
WARNING
CAUTION
indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
used without the safety alert symbol indicates a potential situation which, if
NOTICE
not avoided, may result in an undesirable result or state, including property damage.
1.1 HazarD-free use
This device left the factory in proper condition to be safe­ly installed and operated in a hazard-free manner. The notes and warnings in this document must be observed by the user if this safe condition is to be maintained and hazard-free operation of the device assured.
Take all necessary precautions to prevent damage to the valve status monitor due to rough handling, impact, or improper storage. Do not use abrasive compounds to clean the actuator, or scrape metal surfaces with any objects.
Is trained or authorized to energize, de-energize, ground, tag and lock electrical circuits and equipment in accordance with established safety practices
Is trained in the proper use and care of personal protective equipment (PPE) in accordance with established safety practices
• Is trained in rst aid
In cases where the device is installed in a potentially
explosive (hazardous) location – is trained in the operation, commissioning, operation and maintenance of equipment in hazardous locations
WARNING
The control systems in which the valve status monitor is installed must have proper safeguards to prevent injury to personnel, or damage to equipment, should failure of system components occur.
1.2 QualIfIeD PersOnnel
A qualied person in terms of this document is one who
is familiar with the installation, commissioning and op­eration of the device and who has appropriate qualica­tions, such as:
Is trained in the operation and maintenance of electric equipment and systems in accordance with estab­lished safety practices
The valve status monitor must only be installed,
commissioned, and operated by qualied personnel.
The device generates large mechanical force during normal operation. All installation, commissioning, operation and maintenance must be performed under strict observation of all applicable codes, standards and safety regulations.
Reference is specically made here to observe all
applicable safety regulations for actuators installed in potentially explosive (hazardous) locations.
1
BRAY Series 52 Valve Status Monitor Operation and Maintenance Manual
CAT 3, S52 2N1ProxSensor
Valve Status Monitor
User Instructions. (EHSR 1.0.6)
specic to hazardous area installations
(reference European ATEX Directive 94/9/EC,
Annex II, 1.0.6.)
The following instructions apply to the Bray International S52 2N1ProxSensor Valve Status Monitors Part nos. 52100*-71114536 (*= 1, 2, 4,
6, 7, 8, and 9) covered by certicate number Sira
11ATEX4135X. Translations into other languages are available on request.
1. The equipment may be used with ammable gases and vapours with apparatus Gas Groups IIA, IIB and IIC in Zone 2 locations, and Dust Group IIIB in zone 22 locations.
2. The equipment Temperature Class is T4 for
gases and T102°C for dusts, and is only certied
for use in ambient temperatures in the range
-20°C to +70°C and should not be used outside this range.
3. Installation shall be carried out in accordance with the applicable code of practice by suitably­trained personnel.
4. Repair of this equipment shall be carried out in accordance with the applicable code of practice.
5. The X sufx to the certicate number is to indicate that there is a special condition for safe use, which is regarding the potential build up of static electricity and the precautions to be taken, some of the sensors must be protected from impact/ mechanical damage.
6. If the equipment is likely to come into contact with aggressive substances, then it is the responsibility of the user to take suitable precautions that prevent it from being adversely affected, thus ensuring that the type of protection is not compromised.
Aggressive substances - e.g. acidic liquids or gases that may attack metals, or solvents that may affect polymeric materials.
S52 2N1ProxSensor Intrinsically
Safe Valve Status Monitor
User Instructions
specic to hazardous area installations
(reference European ATEX Directive 94/9/EC,
Annex II, 1.0.6.)
The following instructions apply to the Bray International S52 2N1ProxSensor Valve Status Monitor Part 521003-71114536 Intrinsically Safe
covered by certicate number Sira 11ATEX2134X.
Translations into other languages are available on request.
1. The equipment may be used with ammable gases and vapours with apparatus Gas Groups IIA, IIB and IIC in Zone 0, 1 or 2 locations.
2. The equipment Temperature Class is T4 and is
only certied for use in ambient temperatures
in the range -20°C to +70°C and should not be used outside this range.
3. Installation shall be carried out in accordance with the applicable code of practice by suitably­trained personnel.
4. Repair of this equipment shall be carried out in accordance with the applicable code of practice.
5. The X sufx to the certicate number is to indicate that there is a special condition for safe use, which is regarding the potential build up of static electricity and the precautions to be taken.
6. If the equipment is likely to come into contact with aggressive substances, then it is the responsibility of the user to take suitable precautions that prevent it from being adversely affected, thus ensuring that the type of protection is not compromised.
Aggressive substances - e.g. acidic liquids or gases that may attack metals, or solvents that may affect polymeric materials.
Suitable precautions - e.g. regular checks as part of routine inspections or establishing from the
material’s data sheet that it is resistant to specic
chemicals.
Suitable precautions - e.g. regular checks as part of routine inspections or establishing from the
material’s data sheet that it is resistant to specic
chemicals.
Copy of Certicate number Sira 11ATEX4135X
2
Copy of Certicate number Sira 11ATEX2134X
BRAY Series 52 Valve Status Monitor
C E R T I F I C A T ION
Operation and Maintenance Manual
1 EC TYPE-EXAMINATION CERTIFICATE
2 Equipment intended for use in Potentially Explosive Atmospheres Directive 94/9/EC
3 Certificate Number: Sira 11ATEX2134X Issue: 0
4 Equipment: Series 52 2N1ProxSensor Valve Status Monitor
5 Applicant: Bray International
6 Address: 13333 Westland East Boulevard
7 This equipment and any acceptable variation thereto is specified in the schedule
the documents therein referred to.
8 Sira Certification Service, notified body number 0518 in accordance with Article 9 of Directive 94/9/EC
of 23 March 1994, certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of equipment intended for use in potentially explosive atmospheres given in Annex II to the Directive.
The examination and test results are recorded in the confidential reports listed in Section 14.2.
9 Compliance with the Essentia
the schedule to this certificate, has been assured by compliance with the following documents:
EN 60079-0:2006 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 EN 60079-0:2009
10 If the sign ‘X’ is placed after the certificate number, it indicates that the equipment is subject to special
conditions for safe use specified in the schedule to this certificate.
11 This EC type-examination certificate relates only to the design and construction
equipment. If applicable, further requirements of this Directive apply to the manufacture and supply of this equipment.
12 The marking of the equipment shall include the following:
Houston Texas, 77041 USA
to this certificate and
l Health and Safety Requirements, with the exception of those listed in
(used for guidance in respect of marking)
of the specified
Project Number 22753 D R Stubbings BA MIET
This certificate and its schedules may only be reproduced in its entirety and without change.
Form 9400 Issue 2
II 1 G D Ex ia IIC T4 Ga Ta = -20°C to +70°C Ex iaD 20 T135°C Da
Certification Manager
Sira Certification Service
Page 1 of 2
Rake Lane, Eccleston, Chester, CH4 9JN, England
Tel: +44 (0) 1244 670900 Fax: +44 (0) 1244 681330 Email: info@siracertification.com Web: www.siracertification.com
3
BRAY Series 52 Valve Status Monitor
C E R T I F I C A T ION
Operation and Maintenance Manual
1 TYPE EXAMINATION CERTIFICATE
2 Equipment intended for use in Potentially Explosive Atmospheres Directive 94/9/EC
3 Certificate Number: Sira 11ATEX4135X Issue: 0
4 Equipment: Series 52 2N1ProxSensor Valve Status Monitors
5 Applicant: Bray International
6 Address: 13333 Westland East Boulevard
7 This equipment and any acceptable variation thereto are specified in the schedule to this certificate and
the documents therein
8 Sira Certification Service certifies that this equipment has been found to comply with the Essential
Health and Safety Requirements that relate to the design of Category 3 equipment, which is intended for use in potentially explosive atmospheres. These Essential Health and Safety Requirements are given in Annex II to European Union Directive 94/9/EC of 23 March 1994.
The examination and test results are recorded in the confidential reports listed in Section 14.2.
9 Compliance with the Essential Health and Safety Requirements, with the exception of those listed in the
schedule of this ce
EN 60079-0:2009 EN 60079-15:2010 EN 60079-31:2008
10 If the sign “X” is placed after the certificate number, it indicates that the equipment is subject to special
conditions for safe use specified in the schedule to this certificate.
11 This TYPE EXAMINATION CERTIFICATE relates only to the design of the specified equipment, and not
to specific items of equipment subsequently manufactured.
12 The marking of the equipment shall include the following:
Houston Texas, 77041
USA
referred to.
rtificate, has been assessed by reference to:
Project Number 22753 D R Stubbings BA MIET
This certificate and its schedules may only be reproduced in its entirety and without change.
Form 9402 Issue 2
4
II 3 G D Ex nA IIC T4 Gc Ta = -20°C to +70°C Ex tc IIIB T102°C Dc
Page 1 of 2
Certification Manager
Sira Certification Service
Rake Lane, Eccleston, Chester, CH4 9JN, England
Tel: +44 (0) 1244 670900 Fax: +44 (0) 1244 681330 Email: info@siracertification.com Web: www.siracertification.com
BRAY Series 52 Valve Status Monitor Operation and Maintenance Manual
Introduction
Note: The following information is intended to as­sist individuals with the use and support of the Bray S52 Valve Status Monitors.
The Series 52 Valve Status Monitor has been de­signed to provide valve position indication. The 2N1TM ProxSensor is available in several con-
gurations:
DC Version 10-30VDC PNP (Sourcing)
DC Version 10-30VDC NPN (Sinking)
DC NAMUR Intrinsically Safe Version
(to be used with IS Barrier)
AC Version 20-250VAC, 50-60Hz
Fieldbus capable Versions
1. AS-i (Actuator Sensor Interface)
2. DeviceNet
3. PROFIBUS DP (Process Fieldbus Decentralized Peripherals)
Each of these congurations will be covered in
more detail on the pages that follow. Additional­ly, examples of how to apply some of these prod­ucts will be given.
All Bray S52 Valve Status Monitors utilize solid state switches. Although the solid state switch performs the same function as a conventional me­chanical switch, there are differences in the way solid state switches operate.
NOTICE
It is very important for the user to pay close
attention to the exact specications of their
sensor in order to avoid damaging the unit.
Solid state switches have current restrictions im­posed by the semi conducting materials used to form the sensor. These current limitations have to be accounted for during setup. Unlike mechani­cal switches, which can normally handle several
amperes of current owing through them, solid
state switches are generally rated for half an am­pere or less.
NOTICE
The Parameters of the S52 must be compatible with the application
When working with the S52, several parameters
must be considered. A few of which (with signi­cant importance) are listed here: operating volt-
age, maximum switching current, output voltage drop, and residual current. Using an S52 outside of these parameter limits can cause damage to the unit and void factory warranty.
Operating voltage is the amount of voltage nec­essary for the sensor to operate. The maximum switching current is the largest amount of cur­rent that the sensor’s solid state electronics can
have owing through them in the On-State (when
the target is in proximity of the sensor). During commissioning, it is up to the user to correctly ap­ply the sensor to their control system in order to
limit the current owing through the device. This
is done through the use of a load; all the wiring diagrams associated with the S52s specify where this load needs to be placed in the circuit. Com­mon control systems utilize a digital input card to monitor devices like the S52; these cards have loads (parameter usually referred to as “input im­pedance”) – it is the responsibility of the user to
ensure that this load is sufciently sized to limit the current owing through the S52 below the
maximum switching current, yet above the On­State input current minimum of their monitoring device. We will cover an example of this on page 14-15.
Output voltage drop is dened as the amount of
voltage that will drop across the solid state switch. This voltage drop will often vary with the amount
of current owing through the sensor and the load.
5
BRAY Series 52 Valve Status Monitor Operation and Maintenance Manual
This drop in voltage becomes paramount when connecting several valve status monitors in series, each unit will have a voltage drop across it – add­ing each subsequent drop and subtracting from the supply voltage yields the resulting voltage at the end of the series connection. The user needs to ensure that the supply voltage is large enough so that the resulting voltage after all the drops is above the min. operating voltage of the last S52 in the series connection. Sensors located a great dis­tance from the load require consideration as well, as a general rule, every 1000 ft. of wire will have
a resistance of 10Ω (see electrical code references for the resistance value of specic wire sizes), it is
important for the customer to ensure that the dis­tance between the S52 and the control panel is not long enough to cause the voltage drop to fall be­low the minimum operating voltage of the sensor.
Residual current is often referred to as leak­age current. In the “Off” state (target is NOT in proximity of the sensor) the sensor draws a small
amount of current in order to power the device’s electronics. This is necessary for the device to sense the target at any point in time when the sup­ply voltage is applied. It is important that this residual current is below the maximum Off-State current rating of the control system.
Target Mounting
All congurations of the S52 are offered with two
types of targets; adjustable and non-adjustable. Standard S52 (AC, DC, and DC Intrinsically Safe units) utilize inductive proximity sensing technolo-
gy to provide valve position indication; the eldbus
capable versions utilize hall effect sensing technol­ogy to accomplish the same objective. When ap-
plying eldbus capable S52s, the same targets are
used; however, small magnets are located in the small chambers behind the metal inserts on the sides of the targets.
Adjustable Target Mounting
The adjustable versions are for customers that want the exibility to position their indication limits outside
of the standard 0 to 90°. The components that come in the adjustable target kit are displayed in Figure 1. Figure 2 shows the components of the High Visibility Indicator Kit and the adjustable target kit.
Figure 1: Adjustable Target Kit. From
Left to Right: (1) S52 Mounting Screws,
(2) Base, (3) Middle Piece, (4) Top, (5)
Yellow Pointer w/ mounting screw
Figure 2: High visibility indicator with adjustable
target. Pictured from left to right:
(1) Indicator cover w/mounting screws, (2) indica-
tor w/mounting screw, and (3) adjustable target.
6
BRAY Series 52 Valve Status Monitor Operation and Maintenance Manual
The steps required to set up the adjustable target for your S52 2N1 Valve Status Monitor:
Step 1: Place the base on top of your pneumatic actuator’s output pinion.
Step 3: Place the top piece so that the metal target will be directly in front of the top switch (labeled
1) on the S52 when the actuator rotates to it’s op­posite end of travel position. If you have a high visibility indicator kit, jump to step 5 - otherwise proceed to step 4.
Step 2: Place the middle piece on top of the base so that the metal target is in front of where the bottom switch (labeled 2) of the S52 will be located.
Step 4: Place the yellow pointer in your desired
orientation and tighten the mounting screw. Note:
Units assembled at the factory will have yellow pointers in line with valve discs.
Step 5: Mount the high visibility beacon on top of the target to display ‘Open’ and ‘Closed’ according to your actuator/valve mounting orientation.
Step 6: Tighten the mounting screw to ensure that your indicator and target are secured to the pinion of the actuator. Note: damage to the indicator can
result from over tightening the screw.
7
BRAY Series 52 Valve Status Monitor Operation and Maintenance Manual
Step 7: Place the S52 on the actuator, aligning the holes in the sensor with the mounting holes of the actuator. Insert the cover over the indicator and align the mounting holes of the cover with those of the sensor. Use the longer mounting bolts supplied with your kit and tighten the cover and sensor to the actuator.
Non-Adjustable Target Mounting
The S52 Valve Status Monitor is offered with a non-adjustable target. The non-adjustable target is a one piece puck style target with metal inserts offset by 90°. The yellow pointer however is adjustable and can be positioned however you require; when the unit is mounted at the factory the pointer will be in line with the
valve disc. All components of the non-adjustable kit are shown below in Figure 3. The procedure for mount-
ing the non-adjustable target is described on the next page. Note: when conguring this target with your
input monitoring device pay close attention to metal insert position versus sensor position as your actuator rotates from open to close.
Figure 3: Non-Adjustable Target with pointer.
Figure 4: Non-adjustable Target mounting
Mounting of the non-adjustable target:
Insert the target on the pinion of the pneumatic actuator. Based on what position your pinion/ac­tuator is in, one of the metal inserts of the target will be directly in front of switch ‘1’ or switch ‘2’ on your sensor. When your quarter turn ac­tuator rotates 90° to its opposite travel limit, the other metal insert of the target will be directly in front of switch ‘2’ or switch ‘1’, respectively. Position your actuator to yield your desired in­dication results.
8
BRAY Series 52 Valve Status Monitor Operation and Maintenance Manual
The Standard S52 (non eldbus capable versions) are offered with two types of connections; the DC ver­sions are offered with a 4-pin M12 connection, and the AC versions are offered with a 5-pin 7/8” con-
nection. Both types are pictured below:
4-pin M12 Connector 5-pin 7/8” Connector
Figure 5: Standard S52 Connectors
The following pages cover each of the congurations of the S52 in more detail.
DC Version 10-30VDC PNP (Sourcing)
Specications:
Operating Voltage 10 to 30VDC
Target Type Metallic
Electrical Conguration DC - PNP
Maximum Switching Current 200mA
Output Voltage Drop < 2VDC
Residual Current (Off State Current) 20μA
+
10 to 30 Vdc
-
LOAD 2
LOAD 1
PIN 1
PIN 2
PIN 4
PIN 3
S2
PNP
WIRING DIAGRAM
3
4
2
1
KEY
M12 X1
CONNECTOR
PINOUT
DIAGRAM
S1
PNP
9
BRAY Series 52 Valve Status Monitor
!
Operation and Maintenance Manual
DC Version 10-30VDC NPN (Sinking)
Specications:
Operating Voltage 10 to 30VDC
Target Type Metallic
Electrical Conguration DC - NPN
Maximum Switching Current 200mA
Output Voltage Drop < 2VDC
Residual Current (Off State Current) 20μA
+
10 to 30 Vdc
-
LOAD 2
LOAD 1
PIN 1
PIN 2
PIN 4
PIN 3
S2
PNP
WIRING DIAGRAM
3
4
2
1
KEY
M12 X1
CONNECTOR
PINOUT
DIAGRAM
S1
PNP
I.S. S52 must be used in conjunction with I.S. barrier. Installation and wiring should
WARNING
be carried out by trained personnel who will ensure that the work complies with local standards & NEC practices
Any approved Intrisically Safe apparatus with Entity Concept param­eters as follows: Voc or Vt 15V Isc or It 53mA Ca = Ccable + 220nF La > Lcable + 280 uH
Any approved Intrisically Safe apparatus with Entity Concept param­eters as follows: Voc or Vt  15V Isc or It  53mA Ca = Ccable + 220nF La > Lcable + 280 uH
WIRING DIAGRAM
DC Intrinsically Safe Version
+
PIN 1
_
PIN 4
+
PIN 2
_
PIN 3
Specifications:
Operating Voltage 7 to 12VDC
Target Type Metallic
Electrical Conguration NAMUR
S1
S2
10
WARNING
!
BRAY Series 52 Valve Status Monitor Operation and Maintenance Manual
AC Version 20-250VAC, 50-60Hz
I.S. S52 must be used in conjunction with I.S. barrier. Installation and wiring should be carried out by trained personnel who will ensure that the work complies with local standards & NEC practices
3
KEY
2
1
NOTE: WIRES NOT USED SHOULD BE COILED AND TAPED FOR PROTECTION
4
5
7/8’’ 16 UN CONNECTOR
PINOUT DIAGRAM
NEUTRAL
20 to 250 Vac
LIVE
NOT USED
LOAD 2
LOAD 1
PIN 5
PIN 4
PIN 2
PIN 3
PIN 1
WIRING DIAGRAM
Specications:
Operating Voltage 20-250 VAC
Target Type Metallic
Electrical Conguration AC
Maximum Switching Current 500mA
Output Voltage Drop < 5VAC
Residual Current (Off State Current) < 1mA
S2
S1
Bray P/N: 52-1004-12624-536 (Kit) includes:
- 52-1004-71114-536 (S52)
- 52-1000-14811-533 (target & std. indicator)
Drawing: ES11A-0544
S63 Solenoid, Bray P/N:
PLC with Digital
63-0250-21520-536
AC Input Module
Y Cord, Bray P/N: 60-0250-23661-536 Drawing # : ES11A-0559
11
BRAY Series 52 Valve Status Monitor Operation and Maintenance Manual
AS-i (Actuator Sensor Interface) Version with
M12 Quick Connector
S1
S2
Specications:
Operating Voltage 30.5 VDC by AS-i Network
Target Type Magnetic
Electrical Conguration AS-i Spec. 3.2 (1), (2)
Maximum Switching Current 100mA
Consumption Current < 25mA
Addressing 0 to 31A or B
Data Bits Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2: Output to Solenoid
(1) Hardware AS-i Version 3.0 - congured as AS-i Version 2.1
(2) Full backwards compatibility is maintained with earlier AS-i networks and products
2
4
1
3
SOL -
SOL +
GND GN/YE
NC
NC
YE
RD
WIRING DIAGRAM
3
4
2
1
KEY
M12 X1
CONNECTOR
PINOUT
DIAGRAM
BN
BU
+ _
AS - i
AS-i Controller and AS-i 24VDC Power Supply
12
AS-i S52, Bray P/Ns: 52-1005-12624-536 (Kit) includes:
- 52-1005-71114-536 (S52)
- 52-1000-14821-533 (target) 52-1000-14805-533 (high visibility indicator)
AS-i bus
BRAY Series 52 Valve Status Monitor Operation and Maintenance Manual
DeviceNet Version
S1
S2
Specications:
Operating Voltage 24VDC by DN Network
Target Type Magnetic
Electrical Conguration DeviceNet
Maximum Switching Current 100mA
Consumption Current < 20mA
Output Voltage Drop < 2.5VDC
Addressing 0 to 63 software congured
Data Bits Input Bit 0: Sensor 1
Input Bit 1: Sensor 2
Output Bit 0: Solenoid
2
4
5
3
1
SOL -
SOL +
GND GN/YE
BARE
YE
RD
WIRING DIAGRAM
3
4
5
KEY
PINOUT DIAGRAM
RD
WH
BU
BK
V+
CNH
CNL
V-
GND
2
1
DeviceNet S52, Bray P/Ns: 52-1007-12624-536 (kit) includes:
- 52-1007-71114-536 (S52)
- 52-1000-14821-536 (target)
High Visibility Indicator,
Bray P/N: 52-1000-14805-533
PLC with DeviceNet Scanner
13
BRAY Series 52 Valve Status Monitor
OUT
IN
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
V -
V +
A
B
TERRE
X 10
X 1
SOL -
SOL +
NC
U = 24 V CC - IL = 50 mA
SÉLECTION
D’ADRESSE
RACCORDEMENTS
SUR BORNIER
Operation and Maintenance Manual
PROFIBUS DP Version
V -
(WH)
A
(YE)
V ­A
S1
S2
GND B V +
SOL -
SOL +
NC
YE
RD
GND B V +
V ­A
GND B V +
(GN) (BR)
(WH) (YE)
(GN) (BR)
SCHÉMA ÉLECTRIQUE
Specications:
Operating Voltage 24VDC by Probus DP
Target Type Magnetic
Electrical Conguration Probus DP
Maximum Switching Current 100mA
Consumption Current < 30mA
Output Voltage Drop < 2.5VDC
Addressing 0 to 63 software
congured
Data Bits Input Bit 0: Sensor 1
Input Bit 1: Sensor 2
Output Bit 0: Solenoid
Step 1: Purchase several PROFIBUS DP S52s from your local Bray Distributor
14
Step 2: Separate the connection module from the sensor module by loosening the two fastening screws.
Step 3: Take an inventory of all com­ponents of the PROFIBUS DP S52 to ensure that you have all the necessary parts of the module. Clockwise from the top left on the image above, you should have th following: (a) connec­tion module, (b) PG connectors, (c) sensor module, (d) connection plate, (e) terminal connectors.
BRAY Series 52 Valve Status Monitor Operation and Maintenance Manual
Step 4: Use the adjustment knobs to set your device’s network address.
Step 7: Place the connection plate on the connection module and tighten the fastening screws.
Step 5: Insert your solenoid cable and your PROFIBUS DP & BUS power cable through the cable glands of the connection module. Terminate the wires into the la­beled connectors.
Step 8: Align the connection module to the sensor module and tighten the fastening screws. Your sensor is now ready to be mounted on your actuator.
Step 6: Heat shrink the termina­tions and pull the excess cable back through the cable glands, aligning the connectors with the chambers of the connection module.
PLC with Probus
DP Scanner
Probus DP S52, Bray P/Ns: 52-1008-12624-536 (kit) includes:
- 52-1008-71114-536 (S52)
- 52-1000-14821-533 (target)
15
BRAY Series 52 Valve Status Monitor Operation and Maintenance Manual
Application Example #1 (DC PNP S52)
PLC with Digital DC Input Module
DC PNP S52, Bray P/Ns: 52-1001-12624-536 (kit) includes:
- 52-1001-71114-536 (S52)
- 52-1000-14811-533 (adjustable target) 52-1000-14805-533 (high visibility indicator.)
Customer has an Allen Bradley CompactLogix 1769 PLC platform with DC Input Module Model # 1769-IQ6XOW4. In order for you to determine if the Bray S52 2N1 DC Prox Sensor is compatible with
this device, reference the specications of each device. Using the manufacturer’s website, you should be able to nd a manual for your customers DCS or PLC. In this documentation, you can do a search for the input module in question. Below are some important specications from Allen Bradley’s literature on this specic card.
Model #: 1769-IQ6XOW4
Voltage Input Type 24V dc, sinking or sourcing
Voltage, On-state Input, Min. 10V dc
Voltage, On-state Input, Max. 30V dc @ °C (86 °F)
26.4V dc @ 60 °C (140 °F)
Number of Inputs 6
Voltage, Off-State Input, Max. 5V dc
Current, Off-State Input, Max. 1.5 mA
Current, On-Stae Input, Min. 2 mA
Input Impedance, Nom. 3 KΏ
From this information, and the DC PNP S52 specications on page 7, you should be able to determine
that these two devices are compatible.
The operating voltage of the DC S52 (specied as: 10-30VDC) is within the acceptable On-State Input Voltage Min. and Max. range of the Input Module (specied as: 10VDC to 30 VDC @86°F/26.4Vdc
@140°F).
16
BRAY Series 52 Valve Status Monitor Operation and Maintenance Manual
The residual Off-state Current of the DC S52 (specied as: 20 μA) is below the Off-State Current Max. of the Input Card (specied as: 1.5mA). Note: this means that the leakage current of the S52 will not
cause false readings.
The Nominal Impedance of the Input Card (specied as: 3kΩ) is sufcient enough to limit the current owing through the proximity switch below its Max. Switching Current (specied as: 200mA).
Ohm’s Law: V = IR (V = Voltage, I = Current, R = Resistance*) 24VDC = I x 3 KΩ
24/3000 = .008 A or 8 mA
This value is the amount of current that will ow through the S52 in the On-State (when the target is
in proximity of the sensor). This value, 8 mA, is below the Max. Switching Current of the S52 (cur­rent exceeding 200mA can damage the device) and above the Min. On-State Input Current of the input
module (specied as: 2mA). *Note: Resistance in this case is referred to as Input Impedance
Once you have determined the compatibility of the two devices; you can wire the two devices together using their appropriate wiring diagrams. The diagram in Figure 5 below shows you how to do this cor­rectly.
Note: Each proximity switch in the S52 will require a separate input into the PLC card; thus, (1) S52 will utilize (2) inputs into the PLC Input Module. One input for ‘Valve Open’ indication and one for ‘Valve
Close’ indication. Because this specic input module only has 6 inputs, three S52s can be wired into this device. The number of necessary modules grows quite rapidly when you have several devices in use; this is why eldbus capable versions can be so cost effective, for more information please see the eldbus ap-
plication example.
FIELD WIRING TO PLC
AND 24 VDC SUPPLY
+
24 Vdc
DC
COM
LOAD 2
LOAD 1
IN 0
IN 1
-
S52 VALVE STATUS
MONITOR
PIN 1
S2
PNP
PIN 2
S1
PNP
PIN 4
PIN 3
WIRING DIAGRAM
Figure 5: Wiring diagram showing how to wire a DC PNP S52 to an
Allen Bradley Model # 1769-IQ6XOW4 DC Input Module.
17
BRAY Series 52 Valve Status Monitor Operation and Maintenance Manual
Application Example #2 (AS-i S52)
Customer has an AS-i (Actuator Sensor Interface) controller with an AS-i approved 24VDC power sup-
ply. Once your customer has the conguration software (usually provided with the controller) they can scan the bus and congure any AS-i device connected. Up to 62 devices can be connected to one con-
troller (V2.1 or 3), in applications requiring several valve status monitors, cost is greatly reduced when only one single module can control 62 devices versus having to purchase a PLC input module for every three to four S52s that you have.
1) Bray S52 is connected to the AS-i BUS and is located at address 12.
2) By selecting the device at address
12, a conguration window allows
you to modify the device address, check input state, and test the output.
3) Input 1 is shown in the ‘On’ State, Input 0 is ‘Off’, and the Output to the solenoid is not energized.
AS-i Controller and AS-i 24VDC Power Supply
AS-i slave (1 of 62), Bray S52 P/Ns: 52-1005-12624-536 (kit) includes:
- 52-1005-71114-536 (S52)
- 52-1000-14821-533 (target) 52-1000-14805-533 (indicator)
AS-i bus
18
CONTROLS
R
A Division of BRAY INTERNATIONAL, Inc. 13333 Westland East Blvd. Houston, Texas 77041 281/894-5454 FAX 281/894-9499 www.bray.com
Bray® is a registered trademark of BRAY INTERNATIONAL, Inc. © 2011 Bray International. All rights reserved. OM-52-001 07-2011
Loading...