Brahms B2 Technical Manual

Page 1
Burglar Alarm System
B2
10
1 2 3 4 5 6 7 8
9
12
Fri
Partial
03rd
Armed
30
March
Disarmed
09-05-2011 - 24848602
Technical Manual
1
Page 2
2
Page 3
CONTENTS
1- GENERAL SETTING INFORMATION Page 5
Introduction ................................................................................. 6
General Information on Setting
the Control Panel - B2UC0002 ......................................... 7
How to access
the setting functions ............................................................ 7
Inputs or Zones .......................................................................... 9
Areas ............................................................................................. 10
Sceneries .....................................................................................10
Arming modes ........................................................................10
Types of Inputs....................................................................... 10
Type of balancing................................................................. 12
- Rolling Shutter Sensor.................................................... 14
- Vibration Sensor ................................................................. 14
- Gong Option ........................................................................ 15
- Tamper ..................................................................................... 15
Outputs ........................................................................................... 16
Activating area ....................................................................... 16
Activating events .................................................................. 16
Output Type ............................................................................. 17
Activation Type ...................................................................... 17
Users ................................................................................................. 18
Priority Levels .......................................................................... 19
2 SETTING THE CONTROL PANEL Page 21
Main window with the system turned off ............ 22
Learning ........................................................................................ 24
Identification .............................................................................. 25
Device identification .......................................................... 25
Assigning a symbolic name
to the devices ......................................................................... 26
Check module operation ................................................ 27
State of the connected sensors .................................. 28
Erasing a device..................................................................... 28
View Devices State ................................................................. 29
Setting Menu ............................................................................. 30
Input Setting ........................................................................... 31
- Type of Input ........................................................................ 32
- Type of balancing .............................................................. 34
- IR sensor setting ................................................................. 35
- Dual-technology sensor setting ................................ 36
Output Setting ....................................................................... 37
User Setting ............................................................................. 39
Keypad Setting ...................................................................... 41
IR Receiver Setting ............................................................... 42
General Parameters ............................................................. 42
Alarm Parameters ................................................................. 44
GSM Communicator Menu ............................................ 45
- GSM Message Setting .................................................... 45
- Phone Book Setting ......................................................... 45
- Phone Parameters ............................................................. 46
- Sceneries Setting ................................................................48
- Timer Setting .........................................................................49
- Automatic Programs ........................................................49
- Weekly Timer Setting .......................................................50
- Holydays Setting .................................................................50
- Daylight Saving Time Setting .....................................51
Date and Time ........................................................................... 52
Device Test ................................................................................... 53
Input Test ................................................................................... 53
Output Test ............................................................................... 53
Siren Test .................................................................................... 54
Battery Test ............................................................................... 54
Transmission Quality Test ................................................ 54
Event Log ...................................................................................... 55
Default Restore ......................................................................... 57
Change Installer Code ......................................................... 58
Control Panel Version .......................................................... 58
Table of the default settings of all the parameters
.... 59
3
Page 4
4
Page 5
GENERAL SETTING INFORMATION
1
general setting information
5
Page 6
Introduction
This section of the Installer Manual is NOT intended to define the operating procedures for setting the system
1
parameters (covered in the next chapter), but has the purpose of providing basic information concerning the characteristics of the system. Reading this chapter is essential in order to understand the system's performance and be able to take full advan­tage of its capabilities.
DEU
POR
general setting information
Fig. 1
Choose Language
ENG
ESP
FRA
ITA
ESC
The “Select language” window will appear auto­matically when the system is powered on or after there has been a power outage. By pressing the appropriate icon it will be possible to choose the system language.
6
Page 7
General Information on Setting the Control Panel - B2UC0002
Fig. 1
1 2 3 4 5 6 7 8 9 10
12
Fri
Partial
:
03rd
Armed
Enter Code
2 1 3 4
30
March
Disarmed
HOW TO ACCESS THE SETTING FUNCTIONS.
With the system turned off, i.e., with no area armed, press the icon (fig. 1).
Enter the Installer Code, (which at the first start-up will be 5 6 7 8 fig. 2), to access the Installer Menu (fig. 3).
1
general setting information
Fig. 2
Fig. 3
6 5 7 8
Esc OK
Learn
1
2
9 0
Installer Menu
S
S
I I I
I
I I
I
Identify
TEST
S
MEM
S
S S S
View
ORY
P
P
P
Setting
P P
P
P
P P
P
P
P
Now press the icon Setting
P
to access the
Setting
Setting Menu (fig. 4).
P
1 2 3 4 5 6 7 8 9
0
If you are in the "Installer Menu", this is signalled on
ESC
the "mechanical" keypads and receivers by all four LEDs flashing intermittently.
7
Page 8
1
Fig. 4
general setting information
In
In
12V
In
In
12V
0 123456789 0 123456789 0 123456789 0 123456789
Gen. Param.
Setting Menu
Out
Out
Out
Out
Alarm
ESC
In the Setting Menu, there are a series of icons that, when pressed, allow access to the setting parameters of:
In
In
12V
In
In
12V
Out
Out
Out
Out
Inputs
Outputs
Users
These first three items of the menu require further discussion that will facilitate the setting operations, while the other menu items will be completely explained in the chapter on setting the control panel.
8
Page 9
4 IN Module 01.4 01 Area Burglar Alarm Entry Delay=000 Exit Delay =000 NC contact
OK
Fig. 5
Wall IR 01
Input Setting
Input Setting
ESC
In
In
12V
In
In
12V
Inputs or Zones
The definitions of the parameters for each burglar alarm input or zone is fundamental to the crea­tion of a safe, functional system. The following is a description of some of the parameters that can be set for each of them (fig. 5, 6, 7).
For greater immediacy in the viewing of events, each input and each area can be assigned an alpha­numeric description of 14 characters. It is strategical and highly recommended that you assign names to the inputs that identify their posi­tions. This rule also holds for the areas, for which the system provides a non-modifiable numbering and a descrip­tion that can be freely assigned to the number.
1
01 Area Burglar Alarm Entry Delay=000 Exit Delay =000 Gong Off
OK
Fig. 6
Input Setting
1 IN PW01 01 Area Burglar Alarm Entry Delay=000
general setting information
ESC
Exit Delay =000 NC contact
OK
Fig. 7
ESC
9
Page 10
A5
A7
A8 A9
A1
A10
A2
A4
A3
A6
1
Fig. 8
AREAS
It is possible to divide the space to be protected into areas. An Area of the system is nothing more than a logical grouping of inputs. The subdivision of a system into areas is achieved simply by assigning one of the ten possible areas to each input. Subdividing the system into areas is essential if you plan to:
general setting information
• Arm the system in partial mode as well
• Differentiate the access to particular environments according to the User Code (see relevant section)
• Have differentiated signals for alarms coming from different zones (through the setting of the outputs).
To meet these needs, the system can be subdivided into a maximum of 10 areas (e.g.: fig. 8).
SCENERIES
The term scenery is intended as a combination of areas that are activated according to set procedures. During setting, the installer will create the sceneries containing groupings of areas which, upon activa­tion, will be placed in a state established by the installer himself. A name can be assigned to the scenery which is suggestive of the functions associated with it (“Fence Sensors”, for example). A maximum of 10 sceneries can be set.
The default setting establishes that each input (zone) is assigned to the first Area.
– The Installer (in agreement with the User) must
decide the partial activation mode of the sys­tem:
. Through free selection by the User of the areas
to be activated
. Through activation of sceneries predefi ned by
the Installer during setting.
ARMING MODES
“Full” Arming
This arming mode activates all areas of the system provided that the user, which has entered the code, is permitted to manage all the areas.
Partial Arming
This arming mode is useful in the event it is nec­essary to activate only some areas of the burglar alarm system.
Forced Arming
This mode allows arming of the system even if one or more devices belonging to the system are already in a state of alarm. This arming mode forces the temporary exclusion of the devices in alarm.
TYPES OF INPUTS
“Burglar Alarm” input
If activated, when the system/area is armed, this input automatically activates the sound alarm sig­nals (continuous sounding of the buzzer) of the control panel and auxiliary keypads as well as the visual alarm signals on the control panel, auxiliary keypads and receivers. According to the settings, the “Burglar Alarm” event can activate the sirens and/or one or more outputs (telephone diallers, for example). For each input defined as a “Burglar Alarm”
“Entry Delay”
As the name suggests, the “Entry Delay” allows the user time to enter the protected area and deactivate the system by entering the proper code, without activating the alarm system. The “Exit Delay” allows the user time to exit the protected area after having entered the activation code. During the time interval denominated as “Entry Delay” or “Exit Delay”, the control panel and auxiliary keypads
and “Exit Delay” can be defined.
, an
10
Page 11
emit a continuous buzzer sound to advise the user of the imminent activation of the alarm system.
The “Entry Delay” and “Exit Delay” apply ONLY to inputs de ned as “Burglar Alarm”.
“Silent Alarm” or “Anti-aggression” input
If activated, under any system conditions, this input does NOT activate any visual or sound alarm signal but can be used to activate one or more outputs for the activation, for example, of a telephone call using an external dialler. This function can be useful in the event the user desires to request outside help (with a hidden button, for example) without alarming a pos­sible intruder that may be threatening the user.
An input de ned as “Rescue Alarm”
If activated, under any system conditions, this input activates the lighting of the alarm LED on the keypads and receivers. It can be used to alarm those who are inside the pro­tected area, but it can also be set to activate one or more outputs and can even be directly activated with keys and keypads (see the “User Manual” also).
“Panic Alarm” input
If activated, under any system conditions, this input activates the Sirens (which can be set in the window “Alarm Parameters”) as well as the sound and visual alarm signals (lighting of the LEDs, sounding of the buzzers and keypads) of the control panel, auxiliary keypads and receivers. According to the settings, the “Panic Alarm” event can activate the sirens and/or one or more outputs.
“Generic Alarm” input
This type of input is intended to be associated with sensors or detectors for gas leaks, flooding, fire, etc. If activated, under any system conditions, this input activates the lighting of the alarm LED on the keypads and receivers; it can also be used to activate one or more outputs.
“Auxiliary Alarm” input
This type of input can also be associated with detec­tors of the type described above, in order to better differentiate the functions. If activated, under any system conditions, this type of input activates the lighting of the alarm LED on the keypads and receivers; it can also be used to activate one or more outputs. Up to eight types of auxiliary alarms can be used.
“Passage” Burglar Alarm Input active when the control panel is armed. It behaves as a delayed input during the system arming procedure, if a delayed input belonging to any area is activated; in all the other situations it behaves as an instantaneous input.
“Pulse Arming Input”
This input is used to arm/disarm the entire system and thus is no longer available as a burglar alarm input. If unbalanced, it causes the alternating arming/ disarming of the control panel; this mode is used, for example, to control the control panel with a remote control/gate opener. Contrasting commands given from the control panel, keypads and receivers have priority over commands given from the “Key” zone.
1
general setting information
“Tamper Alarm” input
If activated, under any system conditions, this input activates the Sirens as well as the sound and visual alarm signals (lighting of the LEDs, sounding of the buzzers and keypads) of the control panel, auxiliary keypads and receivers. According to the settings, the “Tamper Alarm” event can be used to activate one or more outputs.
“Level Arming Input”
This type of input is used to arm/disarm the entire system and thus is no longer available as a burglar alarm input. If unbalanced, it arms the system; and it disarms the system when balanced. Contrasting commands given from the control panel, keypads and receivers have priority over commands given from the “Key” zone.
11
Page 12
Alarm contact
Z1
Alarm
contact
Z1
Alarm
contact
Z1
Alarm
contact
Z1
Standby condition
open input
Line cut
not detected
Alarm condition
input closed at earth
Short circuit on line
as input
closed at earth
Standby condition
input closed at earth
Line cut
as open input
Alarm condition
open input
Short circuit on line
NOT DETECTED
Alarm
contact
Z1
Alarm
contact
Z1
Alarm
contact
Z1
Alarm contact
Z1
Input/event type Activated if
Activates
Sirens
Activates Sound

Signal
Activates Visual

Signal
Burglar Alarm Armed Area YES  YES – Intermittent YES YES
1
Silent Alarm Always NO No NO YES Rescue Alarm Always NO No YES YES Panic Alarm Always YES  YES – Intermittent YES YES Tamper Alarm Always YES YES – Intermittent YES YES Generic Alarm Always NO No YES YES Auxiliary Alarm 1-8 Always NO No YES YES “Passage” Burglar Alarm Armed Area YES  YES – Intermittent YES YES
(1) The activation of the sirens in case of “Burglar Alarm” and “Panic Alarm” can be set in the window “Alarm
Parameters”.
(2) The sound alarm signals are emitted by the control panel and auxiliary keypads through the intermittent sounding
of the buzzer. For the control panel and each keypad, however, it is possible to set whether or not said signal should be emitted (see Keypad Setting and User Menu).
(3) The visual alarm signals are emitted by the control panel, through the relative icon appearing on the display, and by
the auxiliary keypads and receivers, through the lighting of the alarm LED.
(4) The activation of one or more outputs can be set by associating them to the relative events (see Output Setting).
general setting information
Activates
Outputs

TYPE OF BALANCING
The following pages describe all the types of bal­ancing that can be associated with each input com-
prising the burglary alarm system. This operation is essential in order to prevent false alarms.
Normally Open - Schematic diagram for the connection of a device with Normally Open alarm contact.
Normally Closed - Schematic diagram for the connection of a device with Normally Closed alarm contact.
12
Page 13
Alarm
contact
Z1
RFL
Alarm contact
Z1
RFL
Alarm
contact
Z1
RFL
Alarm contact
Z1
RFL
Standby condition
input closed at earth
with resistance RFL=2.2KΩ
Line cut
open input alarm
Alarm condition
open input
Short circuit on line
Input closed at earth
Tamper Alarm
One Resistance Mode - Schematic diagram for the 'one resistance mode' connection of a device with
Line cut
open input
Tamper Alarm
Standby condition
input closed at earth
with resistance RFL=2.2KΩ
Alarm condition
input closed at earth
with resistance RFL+RA = 4.4KΩ
Short circuit on line
Input closed at earth
Tamper Alarm
Alarm
contact
Z1
Tamper
contact
RFL
RA
Alarm
contact
Z1
Tamper contact
RFL
RA
Alarm contact
Z1
Tamper
contact
RFL
RA
Alarm
contact
Z1
Tamper
contact
RFL
RA
Normally Closed alarm contact.
Two Resistance Mode - Schematic diagram for the 'two resistance mode' connection of a device with Normally Closed alarm contact.
1
general setting information
The control panel has the following default settings for the balancing of sensors connected to the input mod­ules:
• input of the powered 1-input modules: one resistance mode.
• input of the 4-input modules: NC contact.
• The set type of balancing must be consistent with the type of physical connection made for the devices con­nected to the input modules, in order to prevent serious malfunctioning of the security system. Thus, if sensors are to be connected to the input modules with balancing different from the default setting, it is essential to set the “type of balancing” parameter appropriately in order avoid false alarms.
• The connection of the sensors without balancing (NO, NC), although permitted by the control panel, does not allow recognition of a short circuit or cutting of the detection line which is accidental or intended to neutralize the burglar alarm. It is therefore not advisable to use it for the connection of burglar alarm sensors, while it is
admissible for the connection of sensors connected to inputs set as “Generic Alarm
” or “
Auxiliary Alarm
”.
13
Page 14
ROLLING SHUTTER SENSOR
This type of selection allows the direct connection (without requiring an interface card) to the Brahms CFSST prewired cable contact input modules for
1
protection of the rolling shutters. The “Rolling Shutter Sensor” inputs require the set­ting of the following parameters.
Pulse Number
This determines the number of the pulses that must be reached in order to cause the alarm condition.
Time Interval
This determines the duration of the time interval in which must be recorded the set number of pulses in order to cause the alarm condition.
general setting information
VIBRATION SENSOR
This type of selection allows the direct connection (without requiring an interface card) to the Brahms SVAMB and SINZI breaking sensor input modules. The “Vibration Sensor” inputs require the setting of the following parameter.
Pulse Length
It determines the minimum amplitude that the pulse coming from the sensor must have in order to be considered as an alarm.
This parameter has no affect on the inputs defined differently from “Rolling Shutter Sensor”.
To prevent serious malfunctioning, use exclusively Brahms CFSST cable contacts (or equivalent) if con­tacts of this type are to be connected directly to the input modules. For the connection of other types of devices, contact the Brahms Technical Service Department.
14
This parameter has no affect on the inputs defined differently from “Vibration Sensor”.
To prevent serious malfunctioning, use exclusively Brahms SVAMB and SINZI breaking sensors (or equivalent) if contacts of this type are to be con­nected directly to the input modules. For the connection of other types of devices, contact the Brahms Technical Service Department.
Page 15
GONG OPTION
An attribute which can be assigned to “Burglar Alarm” inputs with a type of balancing other than
“Rolling Shutter Sensor” and “Vibration Sensor”. A “Gong” input, if activated
when the control panel is armed, behaves as a normal burglar alarm input. If activated when the control panel is disarmed, it activates the buzzer of the control panel, without reproducing the sound emission on the buzzers of the keypads. The activation of the GONG option requires that, when the item is enabled in the setting menu of the individual inputs, the buzzer of the control panel must be activated in the window “User Menu” (see
User Manual).
TAMPER
This option allows the installer to choose whether or not the B2MI0401
input modules should man­age the tamper signal separately from the alarm contact. This is useful if the tamper signal is to be managed separately using magnetic contacts with wires or terminals dedicated to this type of signal.
1
User Menu
S
S
S
S S S
Visualizza
P
P
P
Setting
MEM
P P
P
123 456 789
P
ORY
0
S
TEST
ESC
Buzzer off
Buzzer on
The setting of these parameters must be consistent with the type of physical connection made for the devices connected to the input modules, in order to prevent serious malfunctioning of the security system.
general setting information
15
Page 16
1
Output Setting
2 OUT Module
01.2
Areas Not Ready Pulse 005
Out
Out
Out
Out
8 9 10 7 1 2 3 4 5 6
For greater immediacy in the viewing of events, each output can be assigned an alphanumeric description of 14 characters.
Outputs
Normally Active
Fig. 9
2 OUT Module
general setting information
Generic Alarm Level 000 Normally Disactive
OK
Output Setting
01.2
OK
ACTIVATING AREA
For the outputs as well, it is also possible to select
ESC
8 9 10 7 1 2 3 4 5 6
ESC
the group of areas for which these will be activated (fig. 9). If, for example, the areas 1-5 are selected, then the output will be activated only if the event has been triggered by an input belonging to the areas 1-5.
ACTIVATING EVENTS
The 4 outputs on the card of the power supplier or those belonging to the 2-output expansion mod­ules can be activated by events such as faults, alarms and system states that can also be differenti­ated by the area of the system in which the event was generated (fig. 10). Not all events are affected by the area, as shown in the table provided on the following page.
Fig. 10
16
The 4 outputs located on the power supplier are provided with a standard setting that automatically associates each output with an event: PW OUT 01 Burglar Alarm PW OUT 01.2 Tamper Alarm PW OUT 01.3 Fault PW OUT 01.4 Disarmed
Page 17
The table below provides the complete list of events that can be selected from the display (fig. 10)
and their interaction with the areas.
Events Activated if
No events Always NO NO NO NO Accessories Aux PW Fault Always NO NO Intermittent YES Bus PW Fault Always NO NO Intermittent YES PW Fault Always NO NO Intermittent YES
FAU LT S
Battery Fault Always NO NO Intermittent YES Fault (any type of fault) Always NO NO Intermittent YES Burglar Alarm Armed Area YES YES  Intermittent YES Silent Alarm Always YES NO NO NO Rescue Alarm Always YES NO NO YES Panic Alarm Always YES YES  Intermittent YES
ALARMS
Tamper Alarm Always YES YES Intermittent YES Generic Alarm Always YES NO NO YES Auxiliary Alarm 1-8 Always YES NO NO YES Partial Armed Always NO NO NO YES Area Not Ready for Arming Disarmed Area YES NO NO YES Disarmed Area Disarmed Area YES NO NO YES
STATES
Area with Temp. Excluded Zones Armed Area YES NO NO NO
(1) The activation of the sirens in case of “Burglar Alarm” and “Panic Alarm” can be set in the window “Alarm Parameters”. (2) The sound alarm signals are emitted by the control panel and auxiliary keypads through the intermittent sounding of the
buzzer. For the control panel and each keypad, however, it is possible to set whether or not said signal should be emitted (see Keypad Setting and User Menu).
(3) The visual alarm signals are emitted by the control panel, through the relative icon appearing on the display, and by the
auxiliary keypads and receivers, through the lighting of the alarm LED.
Conditioned by the Areas
Siren
Activation
Activates
Sound Signal ⁽²⁾
Activates
Visual Signal ⁽³⁾
1
general setting information
OUTPUT TYPE
Level
- For outputs associated with alarms, the output remains activated for the “Alarm Time” and can be deactivated like a siren.
- For outputs associated with faults or control panel states, the output remains activated for the entire time the triggering event is present.
Pulse
The output is activated by the presence of the event, but remains active only for the set time. The output, however, will remain operative even if, during that time, the cause that triggered the acti­vation of the output is restored.
TYPE OF ACTIVATION
Normally Disactive
The output is normally inactive. It is activated when an event is present. The relay coil of the outputs is always de-energized, and it is energized when there is an activating event.
Normally Active
The output is normally active. It is deactivated when an event is present. The relay coil of the outputs is always energized, and it is de-energized when there is an activating event.
17
Page 18
1
User Setting
Marco
1 2 3 445 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
2
4
3
1
OK
ESC
Users
Each User can be assigned a group of areas and/or sceneries
that will be the only ones the User can arm and/or disarm ( g. 12). It is also possible to assign each user a
from 1 to 4
2
4
, which will allow or not the user to
3
1
priority level
perform a series of operations, as speci ed in the tables on the next page.
Fig. 12
general setting information
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z ' . ­0 1 2 3 4 5 6 7 8 9
CAP
Fig. 13
Enter User Name
Marco
BkSp
DEL
OK
Each User can be assigned a symbolic description to ensure certain identification (fig. 13), and the description will also be used in recording each access.
ESC
The default setting establishes that:
• all areas/sceneries are assigned to all User Codes;
• the highest Level of Priority (4) is assigned to all
User Codes (4)
• at the first start-up there is only one User Code,
which will be “1 2 3 4”
• at the first start-up the Installer Code, i.e., the sin-
gle code that allows access to the Installer Menu, will be “5 6 7 8”.
The setting of the assigned areas, the assigned sceneries and the level of priority for each User is carried out inside the Installer Menu; the assigning of the Keypad Codes and Key Codes for each User is carried out inside the User Menu by a User with Priority Level 4.
18
Page 19
PRIORITY LEVELS
User with priority level 4 - Can be considered the system administrator because he has access to all the functions that
can be managed by the User.
User with priority level 3 - Is the normal user of the system that can arm and disarm the system but does not require
access to particular functions.
User with priority level 2 - Is a User with restrictions that allow him only to arm the system (the cleaning personnel, for
example).
User with priority level 1 - Can only leave evidence of his passage in the event log (the security service, for example).
Action Level 4 Level 3 Level 2
Full or partial Arming/Disarming of the sceneries or associated areas
Alarms Off  YES YES NO Forced Arming  YES YES NO Alarm Memory Reset YES YES NO Access to the User Menu YES YES NO
YES YES Arming only
1
A code set with priority level 1 does not cause any action; only the valid typed data is memorized. (1) The alarms are silenced by any operation (turning on or off, turning on partially, etc.) validly carried out by a User
with Priority Level 2, 3, 4, or through the appropriate control located on the main window in the presence of one or more alarms.
(2) This occurs in the case in which the automatic arming option is not selected (in the menu “General Parameters”),
otherwise the forced arming will be automatic. The forced arming can be done with a code having Priority Level 3 or 4 using the dedicated command in the window that displays the inputs already in alarm before the arming; the forced arming of one or more areas or the entire system entails the temporary exclusion of the inputs already in a state of alarm before the arming. The forced insertion of one or more areas or the whole system entails the temporary exclusion of the inputs connected to the alarm before the insertion, with the exception of inputs configured with an “Output Time” other than 0, as described on page 32.
Functions executable inside the User Menu and accessible only to Users with Priority Level 3 and 4.
Action Level 4 Level 3
Viewing the State and Temporary Exclusion of Inputs YES YES Viewing the Event Log YES YES Setting the Date and Time YES NO Changing User Codes of others / Registering Keys of others
Changing own User Code / Registering own Key Deleting User Codes YES NO Input Test YES YES Siren Test YES YES Battery Test YES YES
YES NO YES YES
general setting information
19
Page 20
1
general setting information
.
Page 21
SETTING THE CONTROL PANEL
2
setting the control panel
21
Page 22
2
Main window with the system turned off
Installer Menu access
State of Areas display
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
All areas deactivated All areas activated Areas partially activated Areas not ready or in alarm
Fri
setting the control panel
1 2 3 4 5 6 7 8 9 10
12
Partial
:
03rd
Armed
30
March
Disarmed
User Menu access
Date and Time display
System Disarmed Indicator/Button
System Armed Indicator/Button
System Partially Armed Indicator/Button
Pen for touchscreen
Button/LED always lit. Pressing the button activates the backlighting of the screen (the back lighting is activated automati-
cally after the touch-screen is pressed)
22
1 2 3 4 5 6 7 8
12
Fri
03rd
Partial
:
Armed
10
9
30
March
Disarmed
Page 23
1 2 3 4 5 6 7 8 9 10
With the system turned o , i.e., with no area armed, press the icon ( g. 1). A keypad will appear on which to enter the Installer
Code
(which at the  rst start-up will be 5, 6, 7, 8,  g .
2) in order to access the
Installer Menu ( g. 3).
Fig. 1
12
Fri
Partial
:
03rd
Armed
30
March
Disarmed
Enter Code
2 1 3 4
6 5 7 8
Esc OK
9 0
The following pages will analyze all the items of the “Installer Menu”, which are:
Learn
Learn
I I I
I
I I
I
S
S
S S S
View
P
P P
P
P
Setting
1
Identify
S
View
P
Setting
2
Date and Time
Identify
S
P
2
setting the control panel
Fig. 2
Fig. 3
Learn
1
Installer Menu
I I I
I
I I
I
Identify
2
TEST
S
MEM
S
S S S
View
TEST
MEM
P
S
S
ORY
P
P
Setting
P P
P
P
1 2 3 4 5 6 7 8 9
0
ESC
Test
ORY
Memory
Default Restore
1 2 3 4 5 6 7 8 9
0
Change Code
Control Panel Version
23
Page 24
2
Fig. 4
Devices Detected
Start
devices detection?
OK
ESC
Learn
Learning
When the appropriate icon is pressed, the system automatically detects the connected devices (fig.
4).
At this point, a list will appear with the number of devices detected and a different icon for each type of device (fig. 5, 6). To scroll through the complete list of the devices, press the buttons
.
If a device is not recognized, it may not have been connected correctly.
POWER SUPPLIER
A
UC
CONTROL PANEL
4 IN MODULE
In
1 IN PW MODULE
Fig. 5
In
12V
2 OUT MODULE
Out
IR
WALL IR SENSOR
R
EXT. SIREN
IR RECEIVER
SUPPLEMENTARY KEYPAD
setting the control panel
Devices Detected
01 01 01 01 02 03
Devices Detected
01 03 03
ESC
Once the connection problems have been resolved, the detection of the devices can be repeated by simply pressing the icon
R
.
Pressing the icon ESC, we will now return to the “Installer Menu” ( g. 3).
R
Fig. 6
24
ESC
Before proceeding with the commissioning, it is important that all the devices are recog­nized by the system
Page 25
Devices Detection
In
4 IN Module
In
Mod 4 IN 01.1
In
Mod 4 IN 01.2
In
Mod 4 IN 01.3
In
Mod 4 IN 01.4
ID: 022228237 V:0.1
OK DEL
Devices Detection
IR Receiver IR Receiver 01.1
ID: 022228233 V:0.1
OK DEL
Devices Detection
In
1 IN PW Module
12V
In
1 IN PW Mod 01.1
12V
01
01
01
ESC
ESC
Devices Detection
A
Power Supplier
A
PW. OUT 01.1
A
PW. OUT 01.2
A
PW. OUT 01.3
A
PW. OUT 01.4
ID: 02228296 V:0.1
OK DEL
Devices Detection
Out
2 OUT Module
Out
2 OUT Module 01.1
Out
2 OUT Module 01.2
ID: 022228259 V:0.1
OK DEL
Devices Detection
IR
Sensore IR Par.
IR
Wall IR 01.1
01
01
01
ESC
ESC
I I I
I
I I
I
Identify
Identification
By pressing the appropriate icon, we now proceed to the identification of the devices. Using this function, we can identify, name and set the components of the burglar alarm system.
To facilitate the identification of each individual device and its outputs or inputs, numbered pro­gressively, these will now appear in a list divided over several pages (fig. 7).
To scroll through the pages containing the list of devices, use the icons .
2
ID: 022228382 V:0.1
OK DEL
Devices Detection
Ext. Siren
EXT Siren 01.1
ID: 022228226 V:0.1
OK DEL
Fig. 7
In
4 IN Module
In
4 IN Mod 01.1
In
4 IN Mod 01.2
In
4 IN Mod 01.3
In
4 IN Mod 01.4
ESC
01
ESC
ID: 022228632 V:0.1
OK DEL
Devices Detection
Rec. Keypad
REC Keypad 01.1
ID: 022228333 V:0.1
OK DEL
Devices Detection
01
01
ESC
ESC
In the event, once the siren has been recognized, it is necessary to perform work on the installation and on the wiring of the siren itself, (or branches upstream from the siren), it is necessary to proceed as follows in order to avoid the ’“Tamper Alarm”: 1- Erase the Siren(s) by pressing on the button
.
DEL
2- Carry out the necessary operations on the instal-
lation.
3- Perform the detection of the Siren(s) again and
recheck the setting.
DEVICES DETECTION
The icon
allows you to activate the LEDs and buzzers present on the connected devices and identify their position within the environment (fig.
8).
setting the control panel
ID: 022228776 V:0.1
OK DEL
Fig. 8
ESC
The firmware ID and version of each device is displayed at the bottom of the screen.
25
Page 26
2
Devices Detection
In
4 IN Module
In
Mod 4 IN 01.1
In
Mod 4 IN 01.2
In
Mod 4 IN 01.3
In
Mod 4 IN 01.4
ID: 022228237 V:0.1
01
Consider a 4-input module as an example; the first line (fig. 9) cannot be changed, it contains the default name assigned by the system and represents the type of device recognized.
Fig. 9
In
4 IN Module
In
Mod 4 IN 01.1
In
Mod 4 IN 01.2
setting the control panel
In
Mod 4 IN 01.3
In
Mod 4 IN 01.4
ID: 022228237 V:0.1
Fig. 10
OK DEL
Devices Detection
OK DEL
01
ESC
ESC
ASSIGNING A SYMBOLIC NAME TO THE DEVICES
The next lines on the page (fig. 10) represent each of the 4 inputs to which an external sensor can be connected; pressing on the text, an alphanumeric keypad will appear which allows us to assign them a name. We recommend that you use a symbolic name that identifies their position, for example garage 01.1, or that identifies their use, for example Gas detector (fig. 11). Press OK to con rm the selections made before exiting from the screen with ESC.
Once these operations have been carried out for all the connected devices, whether these are entry panels, outputs, sirens, IR receivers or what have you, we will have a precise picture of the location of each component and/or its function.
Enter Zone Name
Garage 01.1
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z ' . ­0 1 2 3 4 5 6 7 8 9
CAP
Fig. 11
26
OK
DEL
BkSp
ESC
It is advisable that you carry out the identi­fication operations carefully, as the names assigned to the devices will help you to recog­nize them during the subsequent operations as well.
Page 27
Devices Detection
IR
Sensore IR Par.
IR
Wall IR 01.1
ID: 022228632 V:0.1
OK DEL
01
ESC
CHECK MODULE OPERATION
We will now consider as an example another device recognized by the system during detection, and we will analyze the column indicated by the arrow (fig. 12). Clicking on this icon, we act on the state of the device as follows:
Included
Off
2
Fig. 12
Devices Detection
IR
Sensore IR Par.
IR
Wall IR 01.1
ID: 022228823 V:0.1
OK DEL
Fig. 13
In Test state
With the device in test state we can perform main­tenance on the installation while keeping it active but avoiding the e ective sounding of the alarm sirens; the activation of the devices, however, will be indicated in the “Event Log”.
01
The second column (fig. 13) cannot be changed from the display, as it shows the effective state of the connected device:
setting the control panel
in Alarm
Tamper
ESC
Fault
Press OK to con rm the selections made before exiting from the screen with ESC.
- The state of the devices set by the installer (
in Test State) become a permanent state which cannot be modified by the User.
- In order to avoid false alarms or malfunctioning, it
is recommended to turn Off nected inputs
.
all the uncon-
On, Off,
27
Page 28
2
Fig. 14
setting the control panel
Devices Detection
In
4 IN Module
In
Mod 4 IN 01.1
In
Mod 4 IN 01.2
In
Mod 4 IN 01.3
In
Mod 4 IN 01.4
ID: 022228456 V:0.1
OK DEL
Devices Detection
IR
Sensore IR Par.
IR
Wall IR 01.1
01
01
ESC
STATE OF THE CONNECTED SENSORS
If there are inputs in alarm even though there are no activating events in progress, then it is neces­sary to check the correctness of the connection and its consistency with the setting of the “type of balancing” parameter for each input this, just press on the icon of the device in alarm ( g. 14) to access all the setting functions which will be discussed later in this manual in the “Setting Menu” section.
ERASING A DEVICE
In the event you must remove a device, just press the button so that the device is no longer recognized by the system.
(fig. 15) and con rm the selection
DEL
; in order to do
ID: 022228632 V:0.1
OK DEL
Fig. 15
ESC
For more information on the meaning of these parameters, see the section entitled “General Setting Information”.
28
Page 29
Fig. 16
Learn
1
Installer Menu
I I I
I
I I
I
Identify
2
TEST
S
MEM
S
S S S
View
S
S
S
S
S S S
S
ORY
P
P
Setting
P P
P
P
1 2 3 4 5 6 7 8 9
0
P
S
View
By pressing the appropriate icon (fig. 16), it is pos­sible to check the state of the connected devices; this state is represented by icons arranged in two different columns. By clicking on the icons in the
View Devices State
2
first column (fig. 17), the state of the devices will change as follows:
ESC
Included
Off
In Test state
Fig. 17
Fig. 18
View Devices State
In
Mod 4 IN 01.1
In
Mod 4 IN 01.2
In
Mod 4 IN 01.3
In
Mod 4 IN 01.4
IR
WALL IR SENSOR.01
OKDEL
View Devices State
In
Mod 4 IN 01.1
In
Mod 4 IN 01.2
In
Mod 4 IN 01.3
In
Mod 4 IN 01.4
IR
WALL IR SENSOR.01
OKDEL
ESC
ESC
With the device in test state, maintenance can be performed on the installation while keeping it active but avoiding the e ective sounding of the alarm sirens; the activation of the devices, however, will be indicated in the “Event Log”. The second column (fig. 18) cannot be changed from the display, as it shows the effective state of the connected device:
in Alarm
Tamper
Fault
Press OK to con rm the selections made before exiting from the screen with ESC.
- The state of the devices set by the installer (
On, Off, in Test State) become a permanent state which cannot be modified by the User.
- In order to avoid false alarms or malfunctioning, it is recommended to turn Off nected inputs
.
all the uncon-
setting the control panel
29
Page 30
2
Learn
1
Installer Menu
I I I
I
I I
I
Identify
2
TEST
S
View
MEM
S
S
S S S
ORY
P
P P
P
P
P
P
P
S
P
P
Setting
P P
P
P
1 2 3 4 5 6 7 8 9
0
Setting
From the “Installer Menu”, pressing the appropriate icon ( g. 19) will take us to the “Setting Menu”. The definitions of the parameters for each burglar
Setting Menu
alarm input or zone is fundamental to the creation of a safe, functional system.
Fig. 19
In
In
12V
In
In
12V
0 123456789 0 123456789 0 123456789
setting the control panel
0 123456789
Gen. Param.
Fig. 20
Setting Menu
Out
Out
Out
Out
Alarm
ESC
ESC
The icons present in the “Setting Menu” represent the following (fig. 20):
In
In
12V
In
In
12V
Out
Out
0 123456789 0 123456789 0 123456789 0 123456789
Gen. Param.
Input Setting
Out
Out
Output Setting
User Setting
Keypad Setting
IR Receiver Setting
General Parameters
30
Alarm
Alarm Parameters
GSM Communicator
Sceneries Setting
Timer Setting
Page 31
Input Setting
4 IN Module 01.4
In
In
12V
In
12V
In
INPUT SETTING
01 Area Burglar Alarm Entry Delay=000 Exit Delay =000 NC contact
OK
Fig. 21
Enter Zone Name
Garage 01.1
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z ' . -
ESC
For greater immediacy in the viewing of events, each input and each area can be assigned a descrip­tion (14 alphanumeric characters for the inputs and 11 for the areas) (fig. 22). In order to do this, just press on the name of the input or the area in ques­tion using the pen provided (fig. 21). If the commissioning has been carried out properly, you will read the name (which in any case can be changed) already assigned during the identifica­tion of the devices. Pressing the icons
will scroll through the
various inputs and areas available ( g. 21).
It is strategical and highly recommended that you assign names to the inputs that identify their posi­tions. This rule also holds for the 10 areas available, for which the system provides a non-modifiable num­bering and a description that can be freely assigned to the number (fig. 23).
2
setting the control panel
0 1 2 3 4 5 6 7 8 9
Fig. 22
CAP
OK
DEL
BkSp
Enter Area Name
01 Kitchen area
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z ' . ­0 1 2 3 4 5 6 7 8 9
Fig. 23
CAP
OK
DEL
BkSp
ESC
ESC
Press OK to con rm the selections made before exiting from the screen with ESC.
The default setting establishes that: Each input (zone) is assigned to the first Area.
31
Page 32
INPUT TYPES
2
Fig. 24
setting the control panel
Fig. 25
Input Setting
4 IN Module 01.4 01 Area Burglar Alarm Entry Delay=000 Exit Delay =000 NC contact
OK
Input Setting
4 IN Module 01.4 01 Area Burglar Alarm Entry Delay=000 Exit Delay =000 NC contact
OK
ESC
ESC
The input types can be selected by pressing the icons
Burglar Alarm Tamper Alarm Silent Alarm Panic Alarm Rescue Alarm Generic Alarm Auxiliary Alarm from 1 to 8 Burglar Alarm Pulse Arming Input Level Arming Input
For each input de ned as a Delay” and “Exit Delay” can also be de ned ( g. 25).
As the name suggests, the “Entry Delay” allows the user time to enter the protected area and deactivate the system by entering the proper code, without activating the alarm system. The “Exit Delay” allows the user time to exit the pro­tected area after having entered the activation code. During the time interval denominated as “Entry Delay” or “Exit Delay”, the control panel and auxil- iary keypads emit an intermittent buzzer sound to advise the user of the imminent activation of the alarm system. The “Entry Delay” or “Exit Delay” can be adjust- ed from 0 to 255 seconds by pressing the icons
( g. 24), and these can be:
“Burglar Alarm”, an “Entry
.
32
The “Entry Delay” and “Exit Delay” are active ONLY for “Burglar Alarm” inputs.
When in standby, the system ignores signals from inputs with an “Output Time” other than 0, which therefore do not cause a “Not Ready” area or sys­tem signal. Upon activation o the system, they are inserted at the end of the “Output Time” independ­ently of their status. Therefore, these inputs cannot be excluded with the “Forced Insertion” function or with the “Automatic Insertion” function.
Page 33
Input Setting
Modulo 4 IN 01.4
Level Arming Input
For the setting of inputs de ned as “Pulse Arming Input” and “Level Arming Input”, the input setting
window will appear as shown in  gure 26.
8 9 1071 2 3 4 5 6
This function allows you to arm/disarm the areas selected using equipment outside the system.
Entry Delay = 000 Exit Delay = 000
NC contact
OK
Fig. 26
ESC
For more information on the meaning of these parameters, see the section entitled “General Setting Information”.
2
setting the control panel
33
Page 34
2
4 IN Module 01.4 01 Area Burglar Alarm Entry Delay=000 Exit Delay =000 NC contact
OK
Fig. 27
4 IN Module 01.4
Input Setting
Input Setting
ESC
TYPES OF BALANCING
The types of balancing can be selected by pressing the icons able (fig. 27):
NC contact (Normally Closed) NO contact (Normally Open) One Resistance Mode Two Resistance Mode Vibration Sensor Rolling Shutter Sensor
For the “Vibration Sensor” type of balancing, the pulse length will also have to be specified.
- Pulse Length
minimum amplitude that the pulse coming from the sensor must have in order to be considered as an alarm.
and the following types are avail-
, the value that value determines the
01 Area Burglar Alarm
setting the control panel
Entry Delay=000 Exit Delay =000 Vibration Sensor
Fig. 28
4 IN Module 01.4
Gong OFF Pulse Lenght =000 Pulse Number =000
OK
Input Setting
ESC
For the “Rolling Shutter Sensor” type of balancing, the following will also have to specified:
- Pulse Number, the value that determines the
number of the pulses that must be reached in order to cause the alarm condition.
- Time Interval, the value that determines the dura-
tion of the time interval in which must be recorded the set number of pulses in order to cause the alarm condition (fig. 29).
In order to do this, it is necessary to access the next page of the screen “Input Setting”, by pressing the icon (fig. 28).
Time Interval =000 Tamper OFF
OK
Fig. 29
34
ESC
For more information on the meaning of these parameters, see the section entitled “General Setting Information”.
Page 35
Input Setting
4 IN Module 01.4
Gong OFF Pulse Lenght =000 Pulse Number =000 Time Interval =000 Tamper OFF
In this same window it is also possible to activate or deactivate the “Tamper” and “Gong” options ( g. 30).
2
OK
Fig. 30
Input Setting
Wall IR01
01 Area Burglar Alarm Entry Delay =000 Exit Delay =000
Tamper OFF
OK
Fig. 31
ESC
ESC
IR SENSOR SETTING
The IR sensors can also be assigned an ID name just like the inputs, and the sensors can be associated with one of the available areas (which can also be named as desired). Using the arrows of alarm to be associated with the sensor and the Entry Delay and Exit Delay ( g. 31).
The “Entry Delay” or “Exit Delay” can be adjust- ed from 0 to 255 seconds by pressing the icons
.
The “Entry Delay” and “Exit Delay” are active ONLY for “Burglar Alarm” inputs.
, you can select the type
setting the control panel
Input Setting
Wall IR01
Gong OFF
Durata Impulso =000 Numero Impulsi =000 Durata Intervallo =000 Tamper OFF
OK
Fig. 32
ESC
pressing the icon where you can activate or deactivate the “Gong” option ( g. 32).
Press OK to con rm the selections made before exiting from the screen with ESC.
takes you to the next screen
35
Page 36
2
Input Setting
Wall DT01
01 Area Burglar Alarm Entry Delay =000 Exit Delay =000
IR and MW Function
OK
ESC
DUAL-TECHNOLOGY SENSOR SETTING
The dual-technology detector is able to detect the presence of a burglar using two types of sensors: An infrared sensor (IR), which detects the heat ema­nated from the person's body. A microwave sensor (radar) (MW), which detects motion. Thus the setting window includes additional func­tions which are not present for a normal infrared sensor.
Fig. 33
Wall DT01
Gong OFF MW Sensibility = 05
setting the control panel
Fig. 34
Input Setting
OK
ESC
With the parameter “Function”, by pressing the icons
, you can select ( g. 33) the operating mode
for the detector: IR or MW The alarm is activated even if only one of
the two sensors detects a presence.
IR and MW The alarm is activated only if both sen-
sors detect a presence.
MW The alarm is activated only by the
microwave sensor.
IR The alarm is activated only by the
infrared sensor.
Pressing the icon where you can activate or deactivate the “Gong” option ( g. 34). With the parameter “MW Sensibility”, by pressing the icons , you can adjust the detection capability of the microwave sensor. The values from 1 to 5 allow a proportional adjust­ment of the sensibility.
takes you to the next screen
36
1 = Minimum sensibility and minimum detection
distance.
5 = High sensibility and large detection distance. 0 = Adjustment off and maximum detection dis-
tance.
Press OK to con rm the selections made before exiting from the screen with ESC.
Page 37
Output Setting
2 OUT Module
01.2
Areas Not Ready Pulse 005 Normally Active
OK
Fig. 35
Enter Output Name
2 OUT Module
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z ' . -
01.2
Out
Out
Out
Out
OUTPUT SETTING
8 9 10 7 1 2 3 4 5 6
By pressing on the appropriate button, we will access the output setting section. If the commissioning has been carried out properly, on the first line of the window you will read the
2
name (which in any case can be changed) already assigned during the identification of the devices.
ESC
Pressing the icons
, we can scroll through
the outputs available ( g. 35).
For greater immediacy in the viewing of events, each output can be assigned an alphanumeric description of 14 characters (fig. 36). To do this, just press on the input or area in question.
The 4 outputs on the card of the power supplier or those belonging to the 2-output expansion modules can be activated by a series of events such as faults, alarms and system states that can also be differenti­ated by the area of the system in which the event
setting the control panel
was generated.
0 1 2 3 4 5 6 7 8 9
Fig. 36
CAP
OK
DEL
BkSp
Output Setting
2 OUT Module
01.2
Generic Alarm Level 000 Normally Disactive
OK
Fig. 37
If, for example, the areas 1-5 are selected (fig. 37),
ESC
then the output will be activated only if the event has been triggered by an input belonging to the areas 1-5.
8 9 10 7 1 2 3 4 5 6
For more information on the meaning of these
ESC
parameters, see the section entitled “General Setting Information”.
37
Page 38
2
Output Setting
PW. OUT
01.4
Tamper Alarm Level 000 Normally Disactive
OK
Not all events are affected by the "area of origin". The available events can be selected by pressing the icons ( g. 38).
8 9 10 7 1 2 3 4 5 6
ESC
The 4 outputs located on the power supplier are provided with a standard setting that automatically associates each output with an event: PW OUT 01 Burglar Alarm PW OUT 01.2 Tamper Alarm PW OUT 01.3 Fault PW OUT 01.4 Disarmed
Fig. 38
PW. OUT
Tamper Alarm
setting the control panel
Level 000 Normally Disactive
Fig. 39
Output Setting
01.4
OK
Output Setting
On the fourth line of the display, we can set (fig. 39) the output type which can be either level or pulse.
Level
The output remains activated for the entire time the triggering event is present.
Pulse
The output is activated by the presence of the event,
8 9 10 7 1 2 3 4 5 6
ESC
but remains active only for the set time.
On the next line of the display, we can set (fig. 40) the type of activation associated with the output, which has two options.
Normally Disactive
The output is normally inactive. It is activated when an event is present.
Normally Active
The output is normally active. It is deactivated when an event is present.
Press OK to con rm the selections made before exiting from the screen with ESC.
PW. OUT
01.4
Burglar Alarm
Pulse 005 Normally Active
OK
Fig. 40
38
8 9 10 7 1 2 3 4 5 6
For more information on the meaning of these
ESC
parameters, see the section entitled “General Setting Information”.
Page 39
User Setting
User 01
1 2 3 4
1 2 3 4 5 6 7 8 9 10
2
4
1 2 3 4
3
1
5 6 7 8 9 10
USER SETTING
By pressing on the appropriate button, we will access the User parameter setting section.
Pressing the icons
, we can scroll through
the various users that can be set.
2
OK
Fig. 41
Enter User Name
Marco
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z ' . ­0 1 2 3 4 5 6 7 8 9
Fig. 42
CAP
OK
DEL
BkSp
ESC
ESC
For greater immediacy in the viewing of events, each user can be assigned an alphanumeric description of 14 characters for certain identification. To do this, just press on the name of the User (fig. 41) and the keypad will appear (fig. 42).
Each User can be assigned a group of areas and/or sceneries that will be the only ones the User can arm and/or disarm (fig. 43).
To prevent malfunctions, all areas involved in the scenarios assigned to a user must in turn be assi­gned to the same user.
setting the control panel
User Setting
Marco
1 2 3 4
1 2 3 4 5 6 7 8 9 10
2
4
1 2 3 4
3
1
OK
Fig. 43
5 6 7 8 9 10
ESC
The default setting establishes that:
• All areas and all sceneries are assigned to all User Codes;
• The highest Level of Priority (4) is assigned to all User Codes (4)
• At the first start-up there is only one User Code, which will be “1 2 3 4”
• The setting of the assigned areas, the assigned sceneries and the level of priority for each User is carried out inside the “Installer Menu”; the assigning of the Keypad Codes and Key Codes for each User is carried out inside the “User Menu” by a User with Priority Level 4.
39
Page 40
2
User Setting
Marco
1 2 3 4
1 2 3 4 5 6 7 8 9 10
2
4
1 2 3 4
3
1
5 6 7 8 9 10
It is also possible to assign each user a priority level from 1 to 4, which will allow or not the user to
perform a series of operations ( g. 44), as speci ed in the tables on page 20.
Press
OK to con rm the selections made before
exiting from the screen with ESC.
Fig. 44
setting the control panel
OK
ESC
40
For more information on the meaning of these parameters, see the section entitled “General Setting Information”.
Page 41
Enter Keypad Name
Kitchen Keypad
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z ' . -
KEYPAD SETTING
Each auxiliary keypad can be assigned a symbolic description for certain identification of the device. To do this, just select the name of the device and the alphanumeric keypad will appear (fig. 45).
2
0 1 2 3 4 5 6 7 8 9
Fig. 45
CAP
OK
DEL
BkSp
Keypad Setting
01 Keypad
E/E Delay
Alarm
OK
Fig. 46
ESC
ESC
Pressing the icons the various keypads available ( g. 46).
For each keypad, you can set whether or not it should emit a sound signal during the Entry Time and Exit Time and during the Alarm Time (fig. 46).
Sound signal on
Sound signal off
Press OK to con rm the selections made before exiting from the screen with ESC.
, we can scroll through
setting the control panel
The default setting establishes that:
• for the keypads, the sound signal is enabled during the Entry and Exit Delay and during the Alarm Time;
• A maximum of 8 Keypads and 8 IR Receivers can be connected on the bus line to the Control Panel;
41
Page 42
2
Enter Zone Name
Garage Receiver
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z ' . -
IR RECEIVER SETTING
Each ir receiver can be assigned a symbolic descrip­tion for certain identification of the device. To do this, just select the name of the device and the alphanumeric keypad will appear (fig. 47).
0 1 2 3 4 5 6 7 8 9
CAP
Fig. 47
Garage Receiver
setting the control panel
Fig. 48
BkSp
DEL
OK
IR Receiver Setting
OK
ESC
ESC
Pressing the icons
, we can scroll through
the receivers available ( g. 48).
Press OK to con rm the selections made before exiting from the screen with ESC.
The default setting establishes that:
• A maximum of 8 Keypads and 8 IR Receivers can be connected on the bus line to the Control Panel;
General Parameters
PW restore State Previous
Supervision YES
GSM Control NO
Arming through Sceneries
Aut. Arming YES
OK
Fig. 49
42
ESC
0 123456789 0 123456789 0 123456789 0 123456789
Gen. Param.
GENERAL PARAMETERS
On the first line of this setting window, you can decide how the control panel should behave when the power supply returns after a power outage (fig. 49). Pressing the icons
, we can scroll through
the various options, which are:
Page 43
PW restore State
On In the event both the battery and mains power supply fails for the control panel, the control panel will be
automatically set in the armed state when the power supply voltage is restored.
Off In the event both the battery and mains power supply fails for the control panel, the control panel will be
automatically set in the disarmed state when the power supply voltage is restored.
Previous In the event both the battery and mains power supply fails for the control panel, the control panel will be
automatically set in the previous state when the power supply voltage is restored.
Supervision
This parameter allows you to select whether or not the system can be managed by external supervision
systems (for example the BPT Mitho terminal, the YDRA supervision system, etc...).
GSM Control (can be changed by the User)
This parameter allows you to select whether or not the system can be remotely managed by means of a
GSM dialler (BXGM0001).
Arming through Areas/Sceneries
This parameter allows you to select if the partial activation of the system can occur through the activation
of areas chosen one at a time by the User (Arming through Areas) or through the activation of predefined sceneries containing activation commands for groups of areas (Arming through Sceneries).
2
setting the control panel
Automatic Arming
When the function is active, if one or more inputs are in alarm during the arming of the system, these
will be temporarily excluded automatically and will return to being included only after the subsequent disarming of the system.
When the function is not active, if there are any inputs in a state of alarm, the control panel will interrupt
the arming of the system and wait for the causes of the alarm to be eliminated (closing an open window, for example). In any case, a priority level 3 or 4 user, bearing in mind the exception caused by inputs with an output time other than 0 as described on page 32 of this manual, can however “force” the insertion using the methods described in the “Forced Insertion” section of the B2UC0002 user manual.
Press OK to confirm the selections made before exiting from the screen with ESC and returning to the “Setting Menu”.
43
Page 44
Alarm Parameters Setting
Alarm Time=600
Alarm
ALARM PARAMETERS
2
Fig. 50
setting the control panel
Fig. 51
Alarm Number=010 Burglar Alarm Siren Enabled Panic Alarm Siren Disabled
OK ESC
Alarm Parameters Setting
Alarm Time=600 Alarm Number=010 Burglar Alarm Siren Enabled Panic Alarm Siren Disabled
OK ESC
Alarm Time.
Pressing the icons of the sounding of the siren for the “Burglar Alarm”, “Panic Alarm” and “Tamper Alarm” events, in a range from 0 to 600 seconds ( g. 50).
Alarm Number.
Pressing the icons mum number of “Burglar Alarm”, “ Panic Alarm” and “Tamper Alarm” events ( g. 51) that trigger the acti- vation of the Sirens for each individual arming cycle (maximum 20 times, 0= in nite number of times).
Burglar Alarm.
For this type of event it is possible to determine whether or not the event triggers the activation of the Sirens (fig. 52).
Panic Alarm.
For this type of event it is possible to determine whether or not the event triggers the activation of the Sirens (fig. 52).
Press OK to con rm the selections made before exiting from the screen with ESC.
, we can set the duration
, we can set the maxi-
Alarm Parameters Setting
Alarm Time=600 Alarm Number=010 Burglar Alarm Siren Enabled Panic Alarm Siren Disabled
OK ESC
Fig. 52
44
To fall under the parameters of the standard CEI 79-2, the minimum duration of the alarm must be at least 180 seconds.
Page 45
Fig. 53
GSM Communicator Menu
a
e
bf
c
g h
d
Messaggi
Rubrica
Param. Gen.
GSM Message Setting
Burglar Alarm
8 9 1071 2 3 4 5 6
Vocal Messages YES SMS No Personal Message
= –
ESC
GSM COMMUNICATOR MENU
From the Setting Menu (fig. 20), press the appro­priate button to access the “GSM Communicator Menu” which allows you to set the main parameters of the Brahms GSM communicator BXGM0001 (fig.
53).
Messages
GSM MESSAGE SETTING
Pressing the icons
next to the first item in the window (fig. 54), we can scroll through the list of events that generate a signal. For each event you can select which numbers, from the 10 possible numbers in the phone book, should receive the warning message when the selected event occurs. Using the icons
located on the next two lines, you can select the format in which the mes­sages should be sent. The “Personal Message function” is not active. Press OK to con rm the selections made before returning to the previous window with ESC.
2
setting the control panel
OK
Fig. 54
Phone Book Setting
Tel. Number = 01 Massimiliano
+3904225858585 032
SMS di conferma No
OK
Fig. 55
ESC
ESC
a
e
bf
c
g h
d
Phone Book
PHONE BOOK SETTING
From the “GSM Communicator Menu” (fig. 48), select the “Phone Book” icon to access the “Phone Book Setting” window (fig. 55). On the first line, you can select the position (1 through 10) in which to store the User's number in the phone book. The second line allows you to select which User and relative phone number is to be associated with the selected position. At this point, press on the first icon to call up the keypad with which to enter the phone number (fig. 56). If the phone number has more than 14 digits, you will have to enter the extra digits after pressing on the second icon .
45
Page 46
2
Fig. 56
setting the control panel
Fig. 57
Enter Phone Number
+393478
A B C D E F G H I J
K L M N O P Q R S T
BkSp
+
. -
ESC
U V W X Y Z
0 1 2 3 4 5 6 7 8 9
CAP
OK
DEL
Phone Parameters
Cyclic Sequence YES Cycle Stop YES ConfirmationTone YES Attempts = 3 Pause = 255 Vocal Header NO
OK ESC
The telephone commands sent to the control panel will be carried out only if the number from which they are sent is present in the phone book. Further­more, the User associated with the number must enter his “User Code” and be assigned a “Level of priority” that allows him to carry out the requested action. The last line in the “Phone Book Setting” window (fig. 55) allows you to select if the phone book number should receive SMS messages or not. Press OK to con rm the selections made before returning to the previous window with ESC.
The numbers MUST be preceded by the proper international prefix (+39 for Italy).
Gen. Param.
PHONE PARAMETERS
The settings described below concern the voice messages only. Pressing the icons list, you can set the following parameters ( g. 57):
Cyclic Sequence
“Cyclic Sequence YES” means that, if there is an unanswered call, the communicator will not make any other attempts but will go on to call the next number in the phone book.
Cycle Stop
With “Cycle Stop YES”, the call cycle stops as soon as one of the calls is successful.
Dial Tone
This allows to select whether or not there must be a dial tone before dialling the number.
Attempts
“Attempts" means the number of unanswered calls (from 1 to 20) after which the communicator dials the next number in the phone book.
Pause
“Pause” means the time that must pass (from 0 to 255 seconds) between one call and the next. The function “Vocal Header” is not active
next to the items in the
46246
Page 47
Setting Menu
Press OK to con rm the selections made before returning to the previous window with ESC.
Fig. 58
In
In
12V
In
In
12V
0 123456789 0 123456789 0 123456789 0 123456789
Gen. Param.
Learn
1
2
Out
Out
Out
Out
Alarm
Installer Menu
S
S
I I I
I
I I
I
Identify
S
MEM
S
S S S
View
ORY
TEST
P
P
P
Setting
P P
P
2
ESC
P
1 2 3 4 5 6 7 8 9
0
setting the control panel
Fig. 59
ESC
47247
Page 48
2
Fig. 60
setting the control panel
Fig. 61
Setting Menu
In
In
12V
0 123456789 0 123456789 0 123456789 0 123456789
Gen. Param.
In
12V
In
Out
Out
Alarm
Out
Out
Sceneries Setting
<Scenery Name 01>
1 X 3 4 5 6 7 8 X 10
<Scenery Name 02>
1 X 3 4 5 6 7 8 X 10
<Scenery Name 03>
1 X 3 4 5 6 7 8 X 10
OK
ESC
On
Off
Off
ESC
SCENERIES SETTING
From the “Installer Menu” (fig. 59), press the appro­priate icon to access the “Setting Menu” and then select the icon “Sceneries Setting”.
For each scenery, you can select a name (using the normal procedures) and the arming state for all 10 areas. Each area can be:
- Armed: area with white number on a black back-
ground;
- Disarmed: area with black number on a white
background in a square;
- Indi erent: “x”. This last state means that, when the scenery is armed, the area in question remains in the previous state, i.e., its state is not changed. As in the other menus, “clicking” on the centre of the icon showing the area number will rotate through the possible states. Each scenery can also be activated (
On) or deac-
tivated (Off). Only the “activated” sceneries can e ectively be used by the User for the Partial Arming. You MUST press “OK” to con rm the selection made, otherwise the changes will be lost. Press “ESC” to exit the window.
48
- To prevent malfunctions, all areas involved in the scenarios assigned to a user must in turn be assigned to the same user.
- By default, ALL THE SCENERIES ARM ALL THE AREAS (graphically all the areas are initially shown with a white number on a black background) i.e., THEY'RE THE SAME AS A FULL ARMING.
ALL THE SCENERIES ARE DEACTIVATED (O ).
The names of the sceneries are “Scenery 01”,
“Scenery 02”, …., “Scenery 09”, “Scenery 10”.
Page 49
Fig. 62
1 09:00 On 2 12:15 Off 3 14:30 On 4 19:45 Off 5 23:00 Off
Timer Setting
MON PROG01
TUE PROG02
WED PROG03 SAT PROG04 SAN PROG05
ESC
TIMER SETTING
From the “Installer Menu” ( g. 59), press the appro­priate icon to access the
“Setting Menu” and then
select the icon “Timer Setting”.
The icons in the “Timer Setting” menu represent the following (fig. 62):
1 09:00 On 2 12:15 Off 3 14:30 On 4 19:45 Off 5 23:00 Off
MON PROG01 TUE PROG02 WED PROG03
SAT PROG04 SAN PROG05
Automatic Programs (20 steps)
Weekly Timer Setting (mon-sun)
Holydays Setting (32 days)
2
Automatic Programs List
Setting 01 Setting 02 Setting 03 Setting 04 Setting 05 Setting 06
OK ESC
On
On Off Off
Off
On
Daylight Saving Time Setting
1 09:00 On 2 12:15 Off 3 14:30 On 4 19:45 Off 5 23:00 Off
AUTOMATIC PROGRAMS
From the “Timer Setting” menu ( g. 62), press on the appropriate icon to access the menu “Automatic
Programs list”. Pressing the icon “Automatic Programs”, the “Automatic Programs list” window appears which
contains the list of Programs. Clicking on the name of the Program (which cannot be changed), we pass to the window for setting the steps regarding the selected Program. Each Program can also be activated (On) or deac­tivated (O ). Only the “activated” Programs can e ectively be used. You MUST press “OK” to con rm the selec­tion made, otherwise the changes will be lost. Press “ESC” to exit the window.
setting the control panel
Fig. 63
49
Page 50
2
Automatic Programs Setting
01 Step 01
1 3 4 5 6 7 8 10
<Output Name> Off Hours 20 Minutes 30
OK
Fig. 64
Weekly Timer Setting
ESC
In the “Automatic Programs Setting” window, you can set each of the 20 steps forming each Program. For each step you can determine the arming state of the areas (with the same procedures used for set­ting a scenery with 3 possible states for each area), the output to be activated/deactivated and the time (hour/minutes) at which the actions should be carried out. The outputs that can be activated/deactivated are ONLY those that have been con gured as "No events" from the Output Setting menu. The option “No Output” is also provided for the outputs. On the  rst line appears the number of the Automatic Program being set and the step number being pro­grammed; the arrows can be used to scroll through the various steps of the Program. You MUST press “OK” to con rm the selections made, otherwise the changes will be lost. Press “ESC” to return to the “Automatic Programs list” window.
Thursday Program 01
setting the control panel
Fig. 65
<Holidays 01> Day 31 Month 12 Program 01
Fig. 66
OK
Holydays Setting
OK
ESC
ESC
MON PROG01 TUE PROG02 WED PROG03 SAT PROG04 SAN PROG05
WEEKLY TIMER SETTING
From the “Timer Setting” menu ( g. 62), press the appropriate icon to access the menu “Weekly
Timer Setting”.
This window allows you to associate one of the cre­ated Programs to each day of the week (from Monday to Sunday). The option “None” is also provided in the event no Program is to be associated with that day. Each selection made should be con rmed with “OK”, otherwise the changes will be lost. Press “ESC” to exit the window.
HOLYDAYS SETTING
From the “Timer Setting” menu ( g. 62), press on the appropriate icon to access the menu “Holydays
Setting”.
Each holiday (max 32) can be assigned a name (using the normal procedures), a date within the year (day and month) and one of the created Programs. The option "None" is also provided. Each selection made should be con rmed with “OK”, otherwise the changes will be lost. Press “ESC” to exit the window.
50
Page 51
Daylight Saving Time End
Day 31 Month 12
Hours 23 Minutes 59
OK
Fig. 67
Daylight Saving Time Start
Day 31 Month 12
Hours 23 Minutes 59
ESC
DAYLIGHT SAVING TIME SETTING
From the “Timer Setting” menu ( g. 62), press on the appropriate icon to access the menu “Daylight Saving Time Start” through which you can set the day and time at which the system should pass from solar time to daylight saving time and vice versa. Each selection made should be con rmed with “OK”, otherwise the changes will be lost. Press “ESC” to exit the window.
2
setting the control panel
Fig. 68
OK
ESC
51
Page 52
Date & Time Setting
1
2
Date and Time
2
Fig. 69
setting the control panel
Hours
Date & Time Setting
Hours
OK
18 55
19 58
ESC
From the “Installer Menu”, pressing the appropriate icon will take us to the window for the Date and Time Setting. Set the correct time by selecting the area to be modified (fig. 69) and using the arrows on the side. Proceed in the same manner to set the date after having pressed the arrow at the bottom of the win­dow (fig. 70) which allows access to the appropriate screen (fig. 71).
Press OK to con rm the selections made before exiting from the screen with ESC.
Fig. 70
Date
Month-Year
Fig. 71
OK
Date & Time Setting
Gio 17
Gen 08
OK
ESC
ESC
52
Page 53
Fig. 72
Test Menu
In
In
12V
In
12V
In
Out
Out
Out
Out
Input Test
In
4 IN MOD 01.1
In
4 IN MOD 01.2
In
4 IN MOD 01.4
IR
WALL IR SENSOR 01
IR
WALL IR SENSOR 02
ESC
TEST
Device Test
From the “Installer Menu” ( g. 59), pressing the icon
will take us to the “Test Menu” ( g. 72)
TEST
that allows us to test the correct operation of the inputs, outputs, alarms and batteries of the con­nected devices. Each individual test available is analyzed below.
In
In
12V
In
In
12V
INPUT TEST
Only the inputs that are in a state of alarm will appear in this window (fig. 73). Thus, by materially activating the inputs, we can check their correct operation, name and location.
2
setting the control panel
Fig. 73
Out
Out
Fig. 74
Input Test
A
A
A
A
PW. PW. PW. PW.
01/1 01/2 01/3
01/4 MOD. 2OUT 01/1 MOD. 2OUT
01/2
ESC
On Off
On Off On Off
ESC
Out
Out
Out
Out
OUTPUT TEST
All the connected outputs will appear in this win­dow, with the icon in the right column ( g. 74) on Off. By pressing the pen provided on the icon Off, the state of the output will change to On and the out­put will be activated in order to allow us to check its operation. When exiting from the window by pressing the icon ESC, any outputs that may have been left active will automatically be deactivated.
53
Page 54
Siren Test
EXT. SIREN 01
On
SIREN TEST
2
Fig. 75
setting the control panel
EXT. SIREN 02
Battery Test
A
PW.
EXT. SIREN
01
02
Off
ESC
The legend “ON” or “Off” next to the name of the device acts as a switch (fig. 75). By simply pressing on the legend we can turn the sirens on or off.
BATTERY TEST
By simply pressing on the name of the device, we will be informed about the state of the battery housed inside the device (figg. 76).
Fig. 76
Fig. 77
Transmission Speed
IR
Bedroom Sensor 9
IR
Bathroom Sensor 8
IR
Kitchen Sensor 9
IR
Garage Sensor 8
OK
ESC
ESC
TRANSMISSION QUALITY TEST
Pressing the appropriate icon, a list of the inputs will appear with a numerical value next to each that indicates the speed and quality of communication between the Control Panel and the device, on a scale from 1 to 10 (fig. 77). If the value is less than 7, check that the length of the connection is within the limits indicated in the section “General system information”.
54
Page 55
Fig. 78
Event Log
Mod 4 IN 03.4
Burglar
15/ 03/ 2006 EXT Siren 01
Tamper
14/ 03/ 2006 Door 03
Alarm
12/ 03/ 2006
Del Del
001
11:04
002
08:09
003
06:20
ESC
ORY
MEM
Event Log
The “Event Log” is structured so as to provide a precise picture of the events concerning the system, whether these are caused by burglar attempts, tampering, alarms and faults or simply due to a user arming or disarming the system. Pressing the icons the events and check their progression, indicated by the number next to the name of the device that generated the event. At the end of the list, the scroll­ing will start again from the beginning. The most recent event that occurred is marked by the number 001.
, we can scroll through
2
Fig. 79
Event Log
Bus PW
Fault
15/ 03/ 2006 Bus PW
Fault
15/ 03/ 2006
Del Del
Event Log
1 2 3
Mario
4 5 6 7 8 9
16/ 03/ 2006
0
1 2 3
Mario
4 5 6 7 8 9
15/ 04/ 2006
0
001
16:04
002
11:09
ESC
001
08:04
002
11:09
In the case of burglar, tamper or alarm events, for example (fig. 78), next to the icon showing the event, we can read the name of the input that gen­erated the event and the date and time in which it was activated.
setting the control panel
If the event is different from burglar, tamper or generic alarms, it will be divided into two parts (fig. 79, 80). The first part (with the icon in negative) reports the date and time of the end of the event; the second part (with the icon in positive) reports the date and time of the start of the event.
Adele 14/ 04/ 2006
Del Del
Fig. 80
002
10:09
ESC
55
Page 56
2
Event Log
Mod 4 IN 03.4
Burglar
15/ 03/ 2006 EXT Siren 01
Tamper
14/ 03/ 2006 Door 03
Alarm
12/ 03/ 2006
001
11:04
002
08:09
003
06:20
During the commissioning and setting of the con­trol panel, a large number of events will undoubt­edly be registered. It is best to remove these before handing the system over to the User. The “Event Log” can be cancelled partially or com­pletely using the icons
(fig. 81).
Del Del
Fig. 81
Event Log
Cancel all previous events from:
Mod 4 IN 03.4
setting the control panel
Burglar
15/ 03/ 2006
included?
Fig. 82
ESC
By pressing the  rst icon , you can cancel from the log ( g. 82) the events chronologically previous to the highlighted event ( g. 81).
001
11:04
ESC OK
Event Log
Cancel all subsequent events from:
Mod 4 IN 03.4
Burglar
15/ 03/ 2006
included ?
Fig. 83
56
001
11:04
ESC OK
By pressing the second icon from the log ( g. 83) the events chronologically subsequent to the highlighted event ( g. 81).
OK to con rm the selections made before
Press exiting from the screen with
, you can cancel
ESC.
Page 57
Default Restore Menu
P
P
P
Program
P P
P
1 2 3 4 5 6 7 8 9
P
0
Default Restore
This menu allows you to restore the system to the (default) factory settings.
Fig. 84
Factory settings
Start factory settings restore?
OK
ESC
ESC
Pressing on the first icon (fig. 84) and confirming the selection with
(fig. 85) will restore all the
OK
setting data to its original state at the time of the first start-up.
Pressing on the second icon (fig. 84) and confirming the selection with
(fig. 86) will restore the fac-
OK
tory-set code associated with the first user. This function is quite useful in the event the user loses his code.
Press OK to con rm the selections made before exiting from the screen with ESC.
NOTE. Should it not be possible to access the Restore Menu, in order to restore the factory set­tings, follow the procedure described on page 39 of the “Installation Manual”.
2
setting the control panel
Fig. 85
Factory settings
Start first user factory code restore with “1234”?
OK
Fig. 86
ESC
57
Page 58
2
Installer Menu
S
S
View
MEM
S
S S S
ORY
Learn
1
2
I I I
I
I I
I
Identify
TEST
Fig. 87
Change Installer Code
Enter Install. User Code
1 2 3 4 5 6 7 8 9
P
S
P
P
Setting
P P
P
P
1 2 3 4 5 6 7 8 9
0
0
Pressing the appropriate button (fig. 87) will call up a numerical keypad with which you can set a new Installer Code (fig. 88).
Change Installer Code
Press OK to con rm the selections made before exiting from the screen with ESC.
ESC
setting the control panel
Fig. 88
ID: 16777215 Ver.: 55.55
01
234
56789
012345
Code Not Valid
Control Panel Version
ESCOK
Control Panel Version
From the “Installer Menu” (fig. 87), pressing the but­ton “B2” will display the Firmware ID and version of the control panel (fig. 89); this information may be particularly useful in case you need to contact a service technician.
Fig. 89
58
ESC
Page 59
Table of the default settings of all the parameters
INPUTS
Parameter 4-Input Module Powered 1 Input Module Infrared Sensor
Description Area State Input Type Balancing Type Exit Delay Entry Delay Tamper
OFF OFF OFF Pulse Length Pulse Number Time Interval Gong option
POWER SUPPLIER OUTPUTS
<Module Type xx> <Module Type xx> <Module Type xx>
Area 01 Area 01 Area 01
Included Included Included
Burglar Alarm Burglar Alarm Burglar Alarm
NC contact One Resistance Mode NC contact
000 000
004 004 004 002 002 002 010 010 010
NO NO NO
2
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4
Description Alarm Tamper Fault Armed Associated Areas ALL ALL ALL ALL Activating Event Tamper Alarm Tamper Alarm Fault System Armed Type 1 of the Output Pulse 004 Pulse 004 Pulse 004 Pulse 004 Type 2 of the Output Normally Disactive Normally Disactive Normally Disactive Normally Disactive
OUTPUTS USERS
Description Output xx
Associated Areas Activating Event Type 1 of the Output Type 2 of the Output
Normally Disactive
All
No events
Pulse 004
KEYPADS
Description Keypad xx
Buzzer during T. Input/Output ON Buzzer during T. Alarm ON
Description User xx
Associated Areas All Priority Level 4 Keypad Code 1234 for User1 Key Code –
ALARM PARAMETERS
Alarm Time 40 seconds Alarm Number 10 Siren Active for Burglar Alarm YES Siren Active for Panic Alarm YES
setting the control panel
GENERAL PARAMETERS
When the power supply is restored, the control panel returns to the settings it had before the event.
59
Page 60
Tables of the default setting values
DEFAULT VALUES FOR EACH PROGRAM
Program Name Program State
Program 01 Off Program 02 Off Program 03 Off Program 09 Off
2
Program 10 Off
DEFAULT VALUES FOR EACH PROGRAM STEP
STEP NAME AREA STATE
12345678910
Step 01 X X X X X X X X X X None Activated 00 00 Step 02 X X X X X X X X X X None Activated 00 00 Step 03 X X X X X X X X X X None Activated 00 00 Step 19 X X X X X X X X X X None Activated 00 00 Step 20 X X X X X X X X X X None 00 00
“X” indifferent
Default values for the Weekly Timer Setting
setting the control panel
Day Associated Program
Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Default values for the Holidays Setting
Number Holiday name Day Month Associated program
01 02 03 31 32
Holiday 01 Holiday 02 Holiday 03 Holiday 31 Holiday 32
None None None None None None None
01 01 01 01 01 01 01 01 01 01
OUTPUT OUTPUT
STATE
HOUR MINUTES
None None None None None
Default values for Daylight Saving Time Start/End
Number Holiday name Day Month Associated program
01 02
60
Holiday 01 Holiday 02
01 01 01 01
None None
Page 61
2
setting the control panel
61
Page 62
Page 63
Page 64
BPT Spa Centro direzionale e Sede legale Via Cornia, 1/b 33079 Sesto al Reghena (PN) - Italia http://www.bpt.it - mailto: [email protected]
Loading...