BRAHMA CM11F, CM12F, CM31F, CM32F, SM31F Series Manual

...
MICROFLAT SERIES TYPES C...F S...F M...F T...F
AUTOMATIC CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN AND WITH BUILT-IN ANTI-EMISSIONS FILTER
APPLICATION
This range of electronic gas burner control systems has been specifically designed for atmospheric burners for intermittent operation (systems for non-permanent operation), with or without fan in the combustion circuit. These controls are provided with both non-volatile lockout and volatile lockout: in the first case restart from the safety shutdown condition can only be accomplished by a manual reset of the system; in the second case restart from the safety shutdown condition can only be accomplished by an interruption of the main power and its subsequent restoration. The automatic burner control units of this series are suitable for:
-combi boilers;
-heating boilers;
-warm air generators;
-radiant heaters;
-water heaters. Thanks to their design and variety of models, they can also be used for the automation of ovens, cookers and in gas firing installations with atmospheric burner in general.
FEATURES
Table 1 shows the main features of this series. Other important features are:
EC certification (CE Reg. N°0694BP0669) in accordance with Gas Appliance Directives 90/396 and 93/68;
in accordance with EN 298 (European standard for automatic gas burner control systems and flame detectors);
completely solid and high efficient inbuilt ignition device with built-in E.M. filter;
possibility of mounting a resistor (0 ÷ 220 ohm) in series to the valve output, in case the valves operate with direct current obtained through the rectification of the supply alternate current by means of one or more diodes.
This resistor allows to reduce electromagnetic disturbances generated by diodes switching;
possibility of mounting a resistor (0 ÷ 470 Kohm) in series to the lockout signal output, to avoid possible damages to the control in case the connections of the reset button and the connections of the lockout signal are inverted;
two independent safety contacts in series on the gas valve output (only for non-volatile lockout types);
auxiliary contact for low power ignition or main gas valve control for intermittent pilot systems; this contact is not isolated from the main supply voltage by reinforced isolation, therefore the relay contact is not suitable to supply SELV circuits - Safety Extra Low Voltage, e.g.24V;
flame monitoring by the rectification property of the flame (ionization).
3997_r02 1/13
Table 1
CM11F * * * * * * AMCLXN CM12F * * * * * * ATCLXN CM31F * * * * * * FMCLXN CM32F SM11F SM31F MM11F MM12F MM51F * * * * * * * * ATCLXN MM31F * * * * * * * FMCLXN MM32F * * * * * * * FTCLXN
TM11F TM12F TM31F TM32F CE11F CE12F * * * * * ATCVXN CE31F * * * * * FMCVXN CE32F * * * * * FTCVXN SE11F
SE31F ME11F ME12F ME51F ME31F * * * * * * FMCVXN ME32F * * * * * * FTCVXN
TE11F
TE12F
NOTE
This contact is not isolated from the main supply voltage by
reinforced isolation, therefore the relay contact is not suitable to supply SELV circuits – Safety Extra Low Voltage. Safety thermostat opening causes cycle repetition and
volatile/non-volatile lockout. Standard connectors are Stelvio-Stocko models, as shown in
Fig.2.
 
Flame failure durino TS causes spark restoration. Device is compliant only if the note “EN 298:2003 compliant” and the option “#” are report on the label.
Burner Features
Non-volatile lockout
Volatile lockout
Single flame
Dual flame
Atmospheric without fan
Atmospheric with fan
Monoelectrode
* * * * * * FTCLXN * * * * * * * ATCLXN * * * * * * * FTCLXN * * * * * * * AMCLXN * * * * * * * ATCLXN
* * * * * * AMCLXN * * * * * * * ATCLXN * * * * * * FMCLXN * * * * * * * FTCLXN
* * * * * AMCVXN
* * * * * * ATCVXN * * * * * * FTCVXN * * * * * * AMCVXN * * * * * * ATCVXN * * * * * * * ATCVXN
* * * * * AMCVXN * * * * * * ATCVXN
Safety thermostat provision
Auxiliary contact
Connector type molex
According to EN 298 :1993
According to EN 298 :2003
TECHNICAL DATA Supply voltage:
220/240V @ 50/60Hz
On request: 110/120V @ 50/60Hz
Operatine temperature range: Ambient humidity: Protection degree:
-20°C ÷ +60°C 95% MAX @ 40°C IP 00
Times:
- prepurge or waiting time (TW):
1.5 … 40 s
- safety time (TS): 3 ... 120 s
- response time on running flame failure (TR):
The times given on the burner control label correspond to the values guaranteed. The actual values slightly differ from the values given, pre-purge and waiting time is in fact longer and safety time shorter than their nominal values.
Classification code according to EN 298
Power consumption, at starting up:
< 1 s
types without burner 10VA types with burner 12VA
Power consumption, running:
types without burner 7VA types with burner 9VA
Contact rating:
- Thermostat:
- VG1:
- VG2:
- Fan motor:
- Lock-out signalling:
- Auxiliary contact:
4A cosϕ 0.4
0.5A cosϕ 0.4
0.5A cosϕ 0.4 1A cosϕ 0.4 1A cosϕ = 1
0.5A cosϕ 0.4
Max. length of the cables of external components:
Internal fuse rating: External fuse rating:
1 m 4A fast
3.15A fast
Flame control:
The ionization flame detection device makes use of the rectification property of the flame. The ionization flame detector device is not a safe to touch output (no provision with protective impedances).
- Minimum ionization current:
on request:
- Max ionization current @ 230V:
- Recommended ionization current:
0.5µA
1.2µA / 2.5µA
8.5µA DC 3÷5 times the minimum value
- Max. length of the cable: 1 m
- Minimum insulation resistance of the
50 M
cable and the flame
detector device to earth:
- Max. parasitic capacitance of the
1 nF
detection probe:
- Max. short circuit current:
< 200µA AC
2/13 3997_r02
Ignitor:
FUSE
bottom:
forming screw
forming screw
FEMALE CONNECTOR
TERMINALS
RESET
NEUTRAL
- Peak ignition voltage: 15KV con carico di 30pF
on request: 12/18 KV
- Peak current: 800 mA
- Spark repetition rate: 25 Hz
on request: 1 ... 8/10/12/16 Hz
- Max. length of the cable: 2 m
- Spark gap recommended: 2-4 mm
- Consumption: 2.5 VA
- Spark energy: 20 mJ
Weight:
170 g
CONSTRUCTION
The enclosure made of plastic material and the varnishing of the circuit board protect the control from mechanical damages, dust and dirt from the conditions of installation. Through the use of a board assembled with surface mounted components and of a new patented circuit generating the ignition spark which limits the EM to a minimum, it has been possible to reduce the printed circuit board dimensions and to realize even the most complex executions with extremely compact dimensions. A varistor protects the control from voltage transient on the main supply, caused for example by discharges such as thunderbolds. An internal fuse protects the relays of the control box in case of short circuits on the outputs (valves, fan and lockout signal). In any case the control must be protected with a fast blow external fuse suitable to the load connected and never exceeding 3.15 A.
OVERALL DIMENSIONS
The control units of the MICROFLAT series can be supplied in different executions but with the same enclosure. The following figure (Fig. 1) shows the overall dimensions of the controls.
RESET BUTTON
DRILLING PLAN
LOCK-OUT SIG.
Fig. 2
FEMALE CONNECTOR
TERMINALS
Fig. 3
CONNECTION
The use of non-reversible connectors with a different number of poles makes the connection easy and reliable. One-way fast-on connectors of different sizes for ignition and detection electrodes permit their easy installation and replacement. The dual output ignition device allows spark generation on one point (3a), two points (3b) or between two electrodes isolated from the metal frame of the burner (3c), see Fig.4. The configuration (3c) assures a limited EM emission.
CLIP TO EXTRACT THE INTERNAL
POSSIBLE FIXING
top: self-tapping screw UNI 6951AB 2,9x22
M3x22 screw UNI6107
Screwplast self-
Screwplast self-
ISO0003 F 3.5x13 ISO0003 F 3.9x13
Fig. 1
Provisions such as strain relieves, sufficient earth terminals and neutral terminals should be present in the appliance or in external connection boxes. With all types it is possible to execute the connection with a J3 connector as shown in Fig.5. Types TM..F are prearranged for the connection of a safety thermostat ST which stops the supply to the gas valve VG1 and causes a safety shutdown after a delay which is the sum of waiting (pre-purge) and safety times.
Fig. 4
ACCESSORI
The control units are usually supplied with a kit of female connectors and/or a reset button (see Fig.2 and Fig.3).
Do not fit terminals and female connectors of different types.
3997_r02 3/13
(4a) W ith safety t her mo stat (4 b) Wit hou t safety thermostat
Fig. 5
DIRECTIONS FOR USE
For technical and safety reasons a regulation shutdown
must occur every 24 hours (systems for non-permanent operation);
automatic controls are safety devices and must not be
opened. The manufacturer’s responsibility and guarantee are invalidated if the control is opened;
the control must be connected and disconnected only
after switching off the main power;
the control can be mounted in any position;
avoid exposing the control unit to dripping water;
ventilation and the lowest temperature ensures the
longest life of the control;
make sure that the type (code and times) you are using
is correct before installing or replacing the control;
the gas appliance on which the control is installed must
provide adequate protection against the risk of electrical shock (at least IP20).
ELECTRICAL INSTALLATION
The applicable national regulation and the European
standards (e.g. EN 60335-1/prEN 50165) regarding electrical safety must be respected;
live and neutral should be connected correctly, a
mistake could cause a dangerous situation, i.e. the valves would still be live with the thermostats and limits switched off. If live-neutral polarity is not respected the control performs a non-volatile lockout at the end of the safety time at starting up;
before starting the system check the cables carefully.
Wrong connections can damage the control and compromise the safety;
the earth terminal of the control, the metal frame of the
burner and the earth on the main supply must be well connected;
avoid putting the detection cable close to power or
ignition cables;
use a heat resistant cable for the detection probe, well
insulated to the ground and protected from possible moisture (or water in general);
use an ignition cable as short and straight as possible
and keep it far from other conductors to reduce the emission of interference (max.length <2m and
insulation voltage >25KV). In case of live-neutral network with unearthed neutral or live-live network (with centre of the star not earthed) the control can operate correctly by means of a built-in resistor. In case of "partial" short circuits or bad insulation between live and earth the voltage on the ionization probe can be reduced until it causes the lockout of the control, because of the impossibility of detecting the flame signal. In the presence of this kind of network it is advisable to use our step-up transformer type AR1.
CHECKING AT START Always check the control before the first start and also after any substitutions or a long period of non-operation of the system. Before any ignition attempt make sure that the combustion chamber is free from gas.
Then make sure that:
if the starting attempt occurs without gas supply the control performs a non-volatile lockout after TS;
when stopping the gas flow while the control is in running state the supply to the gas valve is interrupted within 1 second, and after a recycling the control proceeds to a non-volatile lockout;
operating times and sequence are suitable;
the level of the flame signal is sufficient, see Fig.6 for
the measuring test;
the ignition probe(s) is (are) adjusted in the most stable way for a spark gap between 2-4 mm;
the intervention of limiters or safety devices causes a safety shutdown according to the application.
Fig. 6
OPERATION
At every start the control unit proceeds to a self-checking of its own components. During the waiting or prepurge time (TW) the operation of the flame signal amplifier is checked: the internal circuit makes a test of the flame signal amplifier circuit. A parasitic flame signal or a fault in the amplifier prevent the control from starting. In the types with fan control, before the elapsing of the prepurge time, the air pressure switch contacts are checked to prove their "no air flow" state. Only if the test is positive the fan is started and with the air pressure switch in "air flow" state the prepurge time begins. At the end of the waiting or prepurge time the VG1 gas valve is energized and the ignition device is operated. In this way the safety time (TS) begins. If the presence of flame is detected during the safety time the ignition device is inhibited and, in the suitable models, the main valve (VG2) is supplied or the independent auxiliary contact will switch from off to flame detected position. On the contrary, if the control detect no presence of flame by the end of TS, it proceeds to non-volatile lockout, the VG1 gas valve and the ignition device are switched off while the lockout signal output is supplied. Flame failure during the safety time causes the ignition device to be activated within one second. The attached diagrams are useful to understand how each control operates.
NON-VOLATILE LOCKOUT - RESET OF THE CONTROL
When a control has gone to non-volatile lockout, a ten­second delay should be allowed before attempting to reset the control unit; if this time is not observed the control may not reset correctly.
VOLATILE LOCKOUT – RESET OF THE CONTROL
The restart from the safety shut-down condition can only be accomplished by an interruption of the main power and it subsequent restoration. This types of burner control units do not contain an independent manual reset function. The application of these types of controls is therefore restricted to only those appliances where resetting by switching off the heat demand is allowed by European standards.
4/13 3997_r02
In general, resetting of the appliance must occur in sight
R
and in the near vicinity of the appliance. Resetting must also occur by means of a conscious manual action and not by means of automatic device like thermostats or timers. Please note that it is allowed to combine the reset button together with the main switch on the appliance. In this case the alarm light will have to be installed too.
CONTROLS DENOMINATION
Type Options
(1) (2) (3) (4) F
Types description
(1) Installations
C
Wall boilers
S
General uses
M
Monoelectrode
T
(2) Reset
(3) Type of burner
(4) Gas valves
Options description
(5) Compliance
(6) Kind of connectors
(7) Internal fuse
(8) Resistor in series with VG2
(9) Resistor in series with VG1
(10) Protection against the inversion of the connections of the lockout signal and the connections of the reset button
(11) Protection against air pressure switch reversal connection
(12) Ignition coltage
(13) Spark repetition rate
With safety thermostat
M
Manual
E
Electrical
1
Without fan
3
With fan
5
Special types
1
Single flame
2
Dual flame
According to EN 298:1993
#
According to EN 298:2003
Stocco-Stelvio connectors
X
Molex connectors
Not-accessible internal fuse
F
Accessible internal fuse
Not present
W
Present
Not present
V
Present
Not present Present
P
H L
nn
Not present Present
15 Kv (standard) 18 kV 12 kV
25 Hz (standard) Number represents the discharge frequency
(5) (6) (7) (8) (9) (10)
(11) (12) (13)
3997_r02 5/13
CONNECTION DIAGRAM
THERMOSTAT FUSE BURNER LOCK
SIGNAL VALVE VALVE THERMOSTAT SWITCH
TYPE CM11F
TYPE SM11F
TYPE MM11F
TYPE TM11F
TYPE MM51F
TYPE CM12F
TYPE TM12F
TYPE MM12F
TYPES WITH MANUAL RESET WITHOUT FAN
-OUT FIRST GAS SECOND GAS SAFETY RESET MAIN
NOTA: the limit thermostat has to be wired in series to the live.
6/13 3997_r02
TYPES WITH MANUAL RESET AND FAN
THERMOSTAT FAN AIR PRESSURE FUSE BURNER LOCK
SIGNAL VALVE VALVE THERMOSTAT SWITCH
TYPE CM31F
TYPE SM31F
TYPE MM31F
TYPE TM31F
TYPE CM32F
TYPE MM32F
TYPE TM32F
NOTA: the limit thermostat has to be wired in series to the live.
-OUT FIRST GAS SECOND GAS SAFETY RESET MAIN
3997_r02 7/13
TYPE CE11F
TYPE SE11F
TYPE ME11F
TYPE TE11F
TYPE CE12F
TYPE ME51F
TYPE ME12F
TYPE TE12F
THERMOSTAT FUSE BURNE
TYPES WITH ELECTRICAL RESET WITHOUT FAN
R LOCK-OUT FIRST GAS SECOND GAS SAFETY MA IN
SIGNAL VALVE VALVE THERMOSTAT SWITCH
NOTA: the limit thermostat has to be wired in series to the live.
8/13 3997_r02
TYPES WITH ELECTRICAL RESET AND FAN
TYPE CE31F
TYPE SE31F
TYPE ME31F
TYPE TE31F
TYPE CE32F
TYPE ME32F
TYPE TE32F
THERMOS
TAT FAN AIR PRESSURE FUSE BURNER LOCK
-
OUT FIRST GAS SECOND GAS SAFETY MAIN
SIGNAL VALVE VALVE THERMOSTAT SWITCH
NOTA: the limit thermostat has to be wired in series to the live.
3997_r02 9/13
OPERATING CYCLES
TYPES WITH MANUAL RESET WITHOUT FAN
10/13 3997_r02
TYPES WITH MANUAL RESET AND FAN
3997_r02 11/13
TYPES WITH ELECTRICAL RESET WITHOUT FAN
12/13 3997_r02
BRAHMA S.p.A.
ATTE
N
TION ->Company
Brahma S.p.A.
declines any
respons
i
bility for any damage resulting from the Customer’s interfering with the device.
TYPES WITH ELECTRICAL RESET AND FAN
TYPE CE31F - ME31F
TYPE CE32F - ME32F
TYPE TE31F
TYPE TE32F
TYPE SE31F
THERMOSTAT FAN AIR PRESSURE
SWITCH
IGNITION FLAME
SIGNAL
LOCK-OUT
SIGNAL
FIST GAS
VALVE
SECOND GAS
VALVE
AUXILIARY
CONTACT
SAFETY
THERMOSTAT
Via del Pontiere, 31 37045 Legnago (VR) Tel. +39 0442 635211 - Telefax +39 0442 25683 07/04/04 Subject to amendments without notice http://www.brahma.it
3997_r02 13/13
Loading...