Braeburn Round Retrofit Damper User Manual

READ INSTRUCTIONS BEFORE INSTALLING
HELPFUL HINTS
When installing multiple dampers, before installing all dampers, wire each damper individually and cycle to confirm damper operation.
Ensure all ducts are round and the damper can move feely from open to closed once inside the duct.
Ensure the damper s u-frame is in-line with the center of the duct.
DO NOT OVER TIGHTEN the screws when securing the damper to the duct. Make sure the U-Channel seal and ends just meet the outside of the duct.
The Retrofit Round Damper is complete with Installation Mounting Template and four mounting screws.
CHECKOUT
To checkout the operation of the dampers place 24V across terminals
M1 and M4, the damper will open and the Green LED will light at the
end of the cycle. Place 24V to terminals M1 and M6 and the
damper will close and the Red LED will light at the end of the cycle. All
dampers are 100% factory tested.
TROUBLESHOOTING
After performing the checkout of the damper, check the motor terminals for 24V across terminals M1
and M4 if the damper is supposed to be open, and M1 and M6 if the
damper is to be closed. If power is not at the proper terminals, check
the wiring and control panel for power.
M1 M4 M6 OPEN CLOSE
M1 M4 M6 OPEN CLOSE
OPEN
OPEN
CLOSE
CLOSE
COMMON
COMMON
C
C
24 Volts AC
24 Volts AC
SPDT Switch
SPDT Switch
R
R
Minimum Position Adjustment
The damper travel can be set to a Minimum and Maximum position. To adjust these positions, remove the two side
screws holding the black cover and remove. See the photos at right and
above the motor there are two cams and a set screw. Loosen the set screw and
move the cams to adjust to a Min/Max position and re-tighten set screw.
RetroFIT Round
Installation Instructions
RetroFIT Round Installation Instructions
Peel off the back of the installation
template and align along the centerline of the duct and insure the template is straight before adhering to the duct.
Drill a 3/4 diameter holes, at the end of the cut area.
Drill another hole on the opposite end of the cut out area.
Using a pair of snips or shears, cut along the top and bottom of the cut out area to make the opening for the damper.
Ensure Template is straight along centerline
CORRECT
INCORRECT
CAUTION: If duct is too oval the duct can interfere
with the damper blade a n d not allow a full
rotation.
Wiring Diagram
Insert the damper into the duct. I t is recommended to plug-in each damper motor before securing the damper to the duct and cycle the damper. This will avoid possibly pulling the damper out of the duct later to check for proper alignment that may cause the damper to jam.
While keeping the damper in-line with the duct, secure using the screws provided. Tighten until the damper end plate meets the duct. DO NOT
SCREW IN TIGHT TO THE DUCT AS THIS MAY CAUSE THE DAMPER TO JAM. Dampers Only need to a snug fit to duct.
Screws Bend U-Channel
To Control Panel
Use standard three (3) conductor low voltage wiring from control panel motor terminals to each motor. Multiple Dampers are wired in parallel. Note: A maximum of 12 dampers can be powered from a 24V 40VA transformer.