Bradley SS-2/IR/JUV, SS-2/IR/STD, Express SS-3/IR/WH97, Express SS Series Installation Instructions Manual

IMPORTANT
Read this entire installation manual to ensure proper installation, then file these instructions with the owner or maintenance department.
Flush all the water supply lines before making connections.
Wall anchors used must have a minimum pull-out rating of 1,000 lbs.
Product warranties may be found under "Product Information" on our web site at www.bradleycorp.com.
SS-2/IR/STD SS-2/IR/JUV
Express® Lavatory System SS-Series
(Standard* and Juvenile Height) *Express® Lavatory Systems
are ADA compliant.
Table of Contents
Pre-Installation Information . . . . . . . . . . . . . . . .2
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
Installation Instructions . . . . . . . . . . . . . . . . 5-11
Cleaning and Maintenance Instructions . . . . . .12
Soap Dispenser Maintenance . . . . . . . . . . .13-14
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . .14
Assembly of Components . . . . . . . . . . . . . .15-16
Check Valve Troubleshooting . . . . . . . . . . . . . .17
Solenoid Valve Troubleshooting . . . . . . . . .17-18
Vernatherm™ Valve Maintenance & Service . .19
P.O. Box 309, Menomonee Falls, WI 53052-0309 TEL. 1-800-BRADLEY FAX 262-251-5817 http://www.bradleycorp.com
Installation Instructions
OBSOLETE
215-1243 Rev. E; EN 08-805 © 2008 Bradley Corporation Page 1 of 19 4/24/08
2
Express® Lavatory System SS-Series SS-2/IR/STD, SS-2/IR/JUV Installation - Obsolete
4/24/08 Bradley Corporation • 215-1243 Rev. E; EN 08-805
Pre-Installation Information
Barrier-free and ADA compliant - standard height mounting
The SS-2/IR/STD Express® Lavatory System must have a rim height of 34" above finished floor to be compliant with Americans with Disabilities Act (ADA). When mounted at 34" rim height, the Express® meets ADA, ANSI and UFAS requirements for barrier-free clearances, reaches and controls. Always check local codes and ordinances for compliance.
Barrier-free and ADA compliant - juvenile height mounting
The SS-2/IR/JUV Express® Lavatory System is compliant with Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities: Building Elements Designed for Children's Use; Final Rule.
Infrared sensor and solenoid
Each sprayhead is controlled by a separate sensor and solenoid valve, enabling each user to activate a single flow of water. Each valve uses less than half the maximum of hot water allowed by the ANSI/ASHRAE/IES 90A-1980 Standard.
Supplies required for installation:
• (6) 3/8" wall anchors, bolts and washers to mount frame and bowl to wall (minimum pull-out rating of 1,000 lbs.)
• 1/2" NPT hot and cold supply piping
• 1-1/2" NPT drain piping
• 110 volt electrical outlet for 110/24 VAC plug-in transformer (supplied)
3
Express® Lavatory System SS-Series
Installation - Obsolete SS-2/IR/STD, SS-2/IR/JUV
Bradley Corporation • 215-1243 Rev. E; EN 08-805 4/24/08
8"
(203)
22" (559)
34" (864
6"
(152)
50"
(1270)
8-1/2"
(216)
21"
(533)
10" (254)
Radius
8" (203)
Radius
30"
(762)
38-1/4"
(971)
SS-2/IR/STD Express® Lavatory System Dimensions
Standard Height Mounting
4
Express® Lavatory System SS-Series SS-2/IR/STD, SS-2/IR/JUV Installation - Obsolete
4/24/08 Bradley Corporation • 215-1243 Rev. E; EN 08-805
38"
(965)
34"
(864)
29"
(737)
11"
(279)
9"
(229)
6"
(152)
4"
(102)
30"
(762)
25"
(635)
11"
(279)
9"
(229)
6"
(152)
4"
(102)
34"
(864)
Standard Height
SS-2/IR/STD
Juvenile Height
SS-2/IR/JUV
5
Express® Lavatory System SS-Series
Installation - Obsolete SS-2/IR/STD, SS-2/IR/JUV
Bradley Corporation • 215-1243 Rev. E; EN 08-805 4/24/08
Installation Instructions
Step 1: Rough in
Note: See Figure 1a below (for Standard Height) and Figure 1b on page 6 (for Juvenile Height) when roughing in the Express®.
IMPORTANT: Flush the supply lines before making connections. Debris in supply
lines will cause the valves to malfunction.
IMPORTANT: Dimensions shown in Figure 1a are for a Standard Height
Express® only.
1. Rough in 1/2" NPT hot and cold supply lines through wall at dimensions shown.
2. Rough in 1-1/2" NPT drain waste connection through wall at dimensions shown.
(MM)
32"
(813)
28-5/8"
(727)
25"
(635)
11-3/8"
(289)
19-5/8"
(498)
(6) 3/8" WALLANCHORS WITH MINIMUM PULL­OUT RATING OF 1,000 LBS.
23-1/2"
(597)
9-3/8"
(238)
2-3/4"
(70)
13-1/2"
(343)
1" (25)
23-1/2"
(597)
9-3/8"
(238)
3"
(76)
1/2" NPT HOT AND COLD SUPPLIES, OR TEMPERED SUPPLY - STUB OUT 2" (50) FROM WALL
FINISHED FLOOR
CENTERLINE
15-1/4"
(387)
1-1/2" NPT DRAIN -
STUB OUT 2" (50)
FROM WALL
110 Volt GFCI ELECTRICAL OUTLET
Figure 1a
Installation Instructions continue . . .
SS-2/IR/STD Express® Lavatory System Dimensions
Standard Height Mounting
6
Express® Lavatory System SS-Series SS-2/IR/STD, SS-2/IR/JUV Installation - Obsolete
4/24/08 Bradley Corporation • 215-1243 Rev. E; EN 08-805
(MM)
28"
(711)
24-5/8"
(625)
21"
(533)
11-3/8"
(289)
15-5/8"
(397)
(6) 3/8" WALLANCHORS WITH MINIMUM PULL­OUT RATING OF 1,000 LBS.
23-1/2"
(597)
9-3/8"
(238)
2-3/4"
(70)
13-1/2"
(343)
1" (25)
23-1/2"
(597)
9-3/8"
(238)
3"
(76)
1/2" NPT HOT AND COLD SUPPLIES, OR TEMPERED SUPPLY - STUB OUT 2" (50) FROM WALL
FINISHED FLOOR
CENTERLINE
15-1/4"
(387)
1-1/2" NPT DRAIN -
STUB OUT 2" (50)
FROM WALL
110 Volt GFCI ELECTRICAL OUTLET
Figure 1b
Installation Instructions continue . . .
SS-2/IR/JUV Express® Lavatory System Dimensions
Juvenile Height Mounting