Bradford-White Corp S-SW2-75R 6DS, S-SW2-115R6DS, S-SW2-60R 6DS User Manual

Solar Water Heater With Electric Backup
Solar Saver® Heaters
SERVICE
MANUAL
Troubleshooting Guide
and Instructions for Service
(To be performed ONLY by
qualified service providers)
by This Manual:
S-SW2-60R6DS S-SW2-75R6DS S-SW2-115R6DS
Manual 238-47297-00A
Save this manual for future reference
Table of Contents
Page Service Procedure
Introduction ………………………………………………………………………. 2
Tools……………………………………………………………………………… 2
General Information ……………………………………………………………… 3 - - -
Sequence of Operation …………………………………………………………… 5 - - -
Troubleshooting ……………………………………………………………….…. 6 - - -
Line Voltage and High Limit (ECO) Testing…………………………………..… 8 RE-I
Heating Element Testing ……………................................................................... 9 RE-II
Thermostat Testing ……........................................................................................ 10 RE-III
Thermostat Removal and Replacement …………………………………………. 12 RE-IV
Heating Element Removal and Replacement ……………………………………. 13 RE-V
Dip Tube and Anode Inspection and Replacement ……………………………… 14 RE-VI
Generic Parts List ………………………………………………………………... 15 - - -
Page 2
This service manual is designed to aid service and maintenance professionals on the function, proper diagnosis and repair of Bradford White solar water heaters with electric backup. Required service for system components beyond the solar water heater should be directed to the system installer or directly to the system component manufacturer. System components include such items as the solar controller, solar collector and circulator.
The text and illustrations in this manual provide step by step instructions to facilitate proper operation and troubleshooting procedures. Contact the Bradford White Technical Support Group immediately for Bradford White supplied equipment if diagnosis can not be made using the methods described in this service manual. Contact the solar component manufacturer for assistance regarding other equipment.
Introduction
Solar Water Heater With
Electric Backup
Tools
- Multi Meter. - Phillips Head Screwdriver.
- 1-½ Deep Well Socket (element removal). - Thermometer.
- ¼" Nut Driver. - Drain Hose.
- Various Hand Tools: Pipe Wrench, Channel Locks, Pliers (common & needle nose), Wire Cutters, Wire Strippers, Flashlight.
2
G
ENERAL INFORMATION
240 VOLT
Ungrounded
Ungrounded
Grounding
BLACK
RED
GREEN
240 120
120
Service Wire Configuration
Single Phase Amps = Watts Example 4500W/240V = 18.75A
Volts
Watts = Amps x Volts Example 18.75A x 240V = 4500W
Ohms = Volts Example (240V) / 4500W = 12.8 Ohms
Watts
2
2
Commonly Used Formulas
Page 3
Wattage Limitation at 240 Volts
Solar Water Heater with Double Electric Element Backup Series (Non-Simultaneous operation)
Maximum
Wattage
Element
Upper/Lower
5,500
5,500/5,500
3
G
ENERAL INFORMATION
Upper thermostat
Surface Mount
With
ECO (high limit)
89T Series
Manual
ECO (high limit)
Reset button
Temperature
control Dial
Lower thermostat
Surface Mount
59T Series
Surface Mounted Thermostats
Surface mounted thermostats are mounted into a bracket which holds the thermostat against the side of the tank. Surface mounted thermostats respond to tank surface temperatures to sense a call for heat, set point temperature settings and high limit (ECO) activation. It is important that the entire back surface of the thermostat is in full contact or flush with the tank. Improperly mounted thermostat will lead to improper heater operation.
1-½ Hex Screw-in Flange
Terminal Block Screw
Terminal Block
Zinc Incoloy Sheath
Element Rating Ink Stamped on side of Terminal Block.
Direct Immersion “Screw-in” Type Heating Element
Page 4
4
Non-Simultaneous Operation
Non-Simul taneous Mode: Allows only one heating element to operate at a time. For example, when the tank is cold, the upper element is energized first, heating the top of the tank. Only when the upper thermostat is satisfied, the upper element is de-energized and power is directed to the lower thermostat, energizing the lower element and heating the b
ottom portion of the tank until the lower thermostat is satisfied. As hot water is drawn off the tank, it is replaced with cold water delivered through the dip tube to the bottom of the tank. When the tank cools at the lower thermostat level, the thermostat will call for heat energizing the lower element. If enough hot water is drawn from the tank, the top portion of the tank cools and the upper thermostat will call for heat, de-energizing the lower element and allowing only the top element to energize until the upper thermostat is satisfied.
The lower thermostat in the solar water heater is located above the internal heat exchanger. This design allows the heat exchanger to be in cooler water during short draws, providing more heat transfer from the solar heating system.
S
EQUENCE OF OPERATION
Sequence of Operation- Double Element, Non-Simultaneous Operation, Single Phase.
Line voltage is applied across terminals L1 & L3 of the upper thermostat. ECO is closed, so there is voltage at terminal L4 and to one side of the upper and lower elements.
Tank is cold. Therefore, the thermostats are closed at terminals T2 & 2 (calling for heat). The circuit is complete through the upper thermostat only, allowing current to flow through the upper element.
1
2
1 2
ECO
C
losed
Therm ostat closed
at terminal T2
When the upper thermostat is satisfied, it opens at terminal T2, interrupting current flow through the upper element. Terminal T4 closes, allowing voltage to pass to terminal 1 of the lower thermostat. This completes the circuit through the lower thermostat and allows current flow through the lower element.
3
3
Thermostat closed
at terminal T4
4
Thermostat open
between terminals
1 and 2
Upper T’stat
Upper
Element
Upper T’stat
Upper
Element
Lower T’stat
Lower
Element
Lower T’stat
Lower
Element
When the lower thermostat is satisfied, it opens at terminal 2, interrupting current flow through the lower element. The system is now in stand-by mode waiting for the next call for heat
4
The lower thermostat/element combination will generally cycle on and off more often then the upper. In some cases, such as a cold tank or in high demand periods, the upper thermostat will call for heat (opening at terminal T4 and closing at terminal T2) prior to the lower thermostat being satisfied. This will interrupt current flow through the lower thermostat and element and allow current to flow through the upper element only. When the upper thermostat is satisfied, it resumes operation as described in sequence #3 above.
5
5
Thermostat closed between terminals
1 and 2
Upper T’stat
Upper
Element
Lower T’stat
Lower
Element
Upper T’stat
Upper
Element
Lower T’stat
Lower
Element
Upper T’stat
Upper
Element
Lower T’stat
Lower
Element
Thermostat closed
at terminal 2
Therm ostat closed
at terminal T2
Page 5
Solar water heaters with double electric element backup are designed to operate using a single operating mode detailed as follows:
5
Loading...
+ 11 hidden pages