PDX INSTALLATION AND OPERATING
INSTRUCTION MANUAL
WARNING: If the information in these instructions is not
followed exactly, a fire or explosion may result causing
property damage, personal injury or death.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable,
combustible, or corrosive vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
•Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier's instructions.
INTERNET VERSION FOR REFERENCE ONLY
•If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
For your family’s comfort, safety and convenience we
recommend Bradford White water heaters to be installed and
serviced by a plumbing professional.
238-42047-00F REV 10/04
CONGRATULATIONS!
You have just purchased one of the finest water heaters
on the market today!
This installation, operation and instruction manual will
explain in detail the installation and maintenance of your
new Powered Direct Vent Series Gas-Fired Residential
Water Heater. We at Bradford White strongl y recommend
that you contact a plumbing professional for the
installation of this water heater.
We require that you carefully read this manual, as well as
the enclosed warranty, and refer to it when questions
arise. If you have any specific questions concerning your
warranty, please consult the plumbing professional from
whom your water heater was purchased. For your
records we recommend that you write the model, serial
number and installation date of your water heater in the
maintenance section in the back of this manual.
This manual should be kept with the water heater.
At Bradford White we’re committed to providing you with
INTERNET VERSION FOR REFERENCE ONLY
2
TABLE OF CONTENTS
page
GENERAL INFORMATION............................................................ 4
This gas -fired water heater’s design is certified by CSA International under the
American National Standard Z21.10.1 - (as indicated on the rating plate) and
CSA 4.1-M - (as indicated on the rating plate).
This water heater must be installed in accordance with local codes or, in the
absence of local codes, the National Fuel Gas Code, ANSI Z223.1-Latest
Edition) and/or in Canada CAN/CGA B149 Installation Codes (Latest Editions).
The warranty for this water heater is in effect only when the water heater is
installed, adjusted, and operated in accordance with these Installation and
Operating Instructions. The manufacturer will not be held liable for any damage
resulting from alteration and/or failure to comply with these instruc tions.
This water heater is not design certified for installation in a mobile home. Such an
installation may create a hazardous condition and will nullify the warranty.
CAUTION
Incorrect operation of this appliance may create a hazard to life and
property and will nullify the warranty.
Do not use this appliance if any part has been submerged in water. You should
contact a qualified service technician to inspect the appliance and to replace any
part of the control system including the combination gas control, which has been
submerged in water.
DANGER
Do not store or use gasoline or other flammable, combustible, or
corrosive vapors and liquids in the vicinity of this or any other
appliance.
IMPORTANT
Before proceeding, please inspect the water heater and its components for
possible damage. DO NOT install any damaged components. If damage is
evident then please contact the supplier where the water heater was
INTERNET VERSION FOR REFERENCE ONLY
purchased or the manufacturer listed on the rating plate for replacement parts.
Make sure that you check the rating plate and combination gas control on the
water heater to be certain that the type of gas being supplied corresponds with
the marking on the rating plate and combination gas control.
4
General Information continued -
A sacrificial anode is used to extend tank life. The removal of this anode, for any
reason, will nullify the warranty. In areas where water is unusually active, an odor
may occur at the hot water faucet due to a reaction between the sacrificial anode
and the impurities in the water. If this should happen, an alternative anode may
be purchased from the supplier that installed this water heater. This will minimize
the odor while protecting the tank. Additionally, the water heater should be
flushed with appropriate dissolvers to eliminate any bacteria.
INSTALLATION
Locating The Water Heater
WARNING
Water heaters are heat -producing appliances. To avoid damage or injury, do not
store materials against the water heater or vent -air intake system. Use proper
care to avoid unnecessary contact (especially by children) with the water heater
and ve nt-air intake components. UNDER NO CIRCUMSTANCES MUST
FLAMMABLE MATERIALS, SUCH AS GASOLINE OR PAINT THINNER BE
USED OR STORED IN THE VICINITY OF THIS WATER HEATER, VENT-AIR
INTAKE SYSTEM OR IN ANY LOCATION FROM WHICH FUMES COULD
REACH THE WATER HEATER OR VENT-AIR INTAKE SYSTEM.
DO NOT install the water heater in any location where gasoline or
flammable vapors are likely to be present.
CAUTION
The National Fuel Gas Code (ANSI Z233.1-or latest edition) and
CAN/CGA (B149.1-or latest edition), expressly prohibits the installation
of a water heater in a garage, unless the unit is installed so that the
burner and ignition devices are at least eighteen (18) inches (46 cm)
above floor level and protected to avoid damage by a moving vehicle.
The location of this water heater is of the utmost importance. Before installing
this water heater, read the installation section of these instructions. After reading
INTERNET VERSION FOR REFERENCE ONLY
these installation and operating instructions, select a location for the water heater
where the floor is level and is easily accessible to gas and water supply lines. DO
NOT locate the water heater where water lines could be subjected to
freezing temperatures. Make sure the cold water pipes are not located
directly above the gas control so that condensate during humid weather
does not drip on the controls.
5
Installation (Locating The Water Heater) continued -
Water heater corrosion and component failure can be caused by the heating and
breakdown of airborne chemical vapors. Examples of some typical compounds
that are potentially corrosive are: spray can propellants, cleaning solvents,
refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium
and sodium chloride, waxes and process chemicals. These materials are
corrosive at very low concentrat ion levels with little or no odor to reveal their
presence. NOTE: DAMAGE TO THE WATER HEATER CAUSED BY EXPOSURE
TO CORROSIVE VAPORS IS NOT COVERED BY THE WARRANTY. DO NOT
OPERATE THE WATER HEATER IF EXPOSURE HAS OR WILL OCCUR. DO
NOT STORE ANY POTENTIALLY CORROSIVE COMPOUNDS IN THE
VICINITY OF THE WATER HEATER.
WARNING
Liquefied petroleum gases/propane gases are heavier than air
and will remain at floor level if there is a leak. Basements, crawl
spaces, closets and areas below ground level will serve as
pockets for accumulation of leaking gas. Before lighting, smell
all around the appliance area for gas. Be sure to smell next to
the floor.
IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any telephone in
your building.
• Immediately call your gas supplier from a neighbor’s
telephone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
DO NOT OPERATE APPLIANCE UNTIL THE LEAKAGE IS
CORRECTED!
INTERNET VERSION FOR REFERENCE ONLY
6
Installation (Locating The Water Heater) continued -
WARNING
DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU ARE NOT
CERTAIN OF THE FOLLOWING:
• Liquefied petroleum gases/propane gas and natural gas have an
odorant added by the gas supplier that aids in the detection of the
gas.
• Most people recognize this odor as a “sulfur” or “rotten egg” smell.
• Other conditions, such as “odorant fade” can cause the odorant to
diminish in intensity, or ”fade”, and not be as readily detectable.
• If you have a diminished sense of smell, or are in any way unsure of
the presence of gas, immediately contact your gas supplier from a
neighbor’s telephone.
• Gas detectors are available. Contact your gas supplier, or plumbing
professional, for more information.
The water heater must be located close enough to the outside wall to keep the
venting distance within the maximum distance described in the installation
instructions. Read the venting section in this installation instruction manual
before locating the water heater.
This water heater must be located in an area where leakage of the tank or water
line connections and the combination temperature and pressure relief valve will
not result in damage to the area adjacent to the water heater or to lower floors of
the structure. When such locations cannot be avoided, a suitable drain pan
adequately piped for proper drainage, must be installed under the water heater.
The drain pan must be no greater than 1-½ inches (3.8 cm) deep and have a
minimum length and width of at least four (4) inches (10.2 cm) measured from the
jacket of the water heater. The drain pan, as described above, can be purchased
from your plumbing professional. The drain pan must be piped to an adequate
drain. The piping must be at least 3/4 inch (1.9 cm) in diameter and pitched for
proper drainage.
It is recommended that a minimum clearance of four (4) inches (10.2 cm) be
provided on the side of the water heater for servicing and maintenance of the
combination temperature and pressure relief valve.
INTERNET VERSION FOR REFERENCE ONLY
7
Installation (Minimum Clearances) continued -
Minimum Clearances
WARNING
Failure to adhere to these installation and operating instructions may
create a hazard to life and property and will nullify the warranty.
This installation must allow access to the front of the water heater and adequate
clearance must be provided for servicing and operating this water heater. The
water heater may be installed on either a combustible or non-combustible floor. If
the water heater is to be installed directly on carpeting, it must be installed on
top of a metal or wood panel extending beyond the full width and depth of the
appliance by at least three (3) inches (7.6 cm) in any direction or, if the appliance
is to be installed in an alcove or closet, the entire floor must be covered by the
panel. The minimum clearances to combustibles for this water heater is: zero (0)
inches (0 cm) from the sides and rear, five (5) inches (12.7 cm) from the front of
the jacket, zero (0) inches (0 cm) from the vent connector and fifteen (15) inches
(38.1 cm) from the jacket top.
Venting
The National Fuel Gas Code ANSI Z223.1-(Latest Edition), CGA/CAN B149
Installation Code, and local codes have specific requirements for the location of
the vent terminals on vertical walls. The guidelines listed below are from the
National Fuel Gas Code. Consult the local codes, and/or National Fuel Gas
Code ANSI Z223.1-(Latest Edition), or CGA/CAN B149 Installation Code to
determine if there are any additions or changes to the following specifications.
(A) The vent terminals must terminate at least 3 feet (.91 m) above any forced
air inlet duct located within 10 feet (3 m). Exception: This provision shall
not apply to the combustion air intake of a direct vent appliance.
(B) The vent terminals must terminate at least 12 inches (.31 m) below, 12
inches (.31 m) horizontally from, or 12 inches (.31 m) above any door,
window, or any gravity air inlet into the building.
(C) The bottom of the vent terminal and the air intake shall be located at least
12 inches (.31 m) above grade.
Note: Must be installed in a location where it will not be blocked by
INTERNET VERSION FOR REFERENCE ONLY
snow.
(D) The vent terminals must not terminate over a public walkway or over an
area where condensate or vapor could create a nuisance or hazard or
could be detrimental to the operation of regulators, relief valve, or other
equipment.
(E) The water heater location must provide easy access for the entire length
of the vent connector.
8
Venting continued -
(F) The vent system must be inspected at least once a year to ensure
against leakage of exhaust products.
Exceptions For Installations in Canada:
(A) The vent terminals must be located at least 1 foot (.31 m) from any
window or door, which can be opened in any building, any non-mechanical
air supply inlet to any building, or the combustion air inlet to any other
appliance.
(B) The vent terminals must be located at least 6 feet (1.8 m) from any
mechanical air supply inlet to the building.
(C) The vent terminals must not terminate above a meter/regulator assembly
or within 3 feet (.91 m) horizontally of the vertical centerline of the
regulator and must be at least 6 feet (1.8 m) from any gas service
regulator vent outlet.
(D) The vent terminals must be at least 7 feet (2.1 m) above a paved sidewalk
or a paved driveway located on public property.
(E) The vent terminals must not terminate above a paved sidewalk or a paved
driveway, which is located on adjacent private property.
(F) Underneath a verandah, porch or deck, unless:
(1.) Th e verandah, porch or deck is fully open on a minimum of two
sides beneath the floor, and
(2.) The distance between the top of the vent-air intake terminal and the
underside of the verandah, porch or deck is greater than 1 ft (30.5
cm).
INTERNET VERSION FOR REFERENCE ONLY
9
Venting continued -
Venting Installation Instructions For Supplied Intake Venting:
1. Refer to Figure 1, “Vent Assembly Illustration” to install intake venting
as described below.
2. Insert one end of the Vertical Pipe into Metal Boot on the lower
backside of the water heater.
3. Slide the Support Bracket over the Vertical Pipe, but do not fasten to
the Jacket Head.
4. Position the Intake Tee on top of the Vertical Pipe so that the short
straight section of the tee faces the Blower Intake Collar, and the
curve of the tee faces upward. Proper orientation of the curved
section of the tee is critical. Be sure it is facing upward. Refer
to “This End Up” label on Intake Tee.
5. Slide the Rubber Intake Elbow over the Blower Intake Collar and over
the short straight section of the Intake Tee.
6. Using a level to ensure that the Vertical Pipe is straight up and down,
secure the Vertical Pipe to the Jacket Head using the Support
Bracket and three (3) self-drilling screws provided. NOTE: Correct vertical positioning of the Vertical Pipe is Important.
7. After securing the Vertical Pipe to the Jacket Head with the Support
Bracket, tighten the clamps on the Rubber Intake Elbow.
8. Using the RTV sealant provided, place a bead of RTV around the
Vertical Pipe at the Metal Boot location, and at the Intake Tee
location. Smooth out the RTV to provide a seal at both locations.
9. Two 90° end terminal elbows are supplied. These must be installed at
the extreme ends of the intake and exhaust venting outside the
building. The end terminal with the external screen must be installed
on the intake vent as shown in Figure 7.
10. Proceed as necessary to complete the venting installation as
described in the venting section of this manual.
INTERNET VERSION FOR REFERENCE ONLY
10
Venting continued -
INTERNET VERSION FOR REFERENCE ONLY
Figure 1
Vent Assembly Illustration
11
Venting continued -
Venting System Condensation
Condensate formation does not occur in all installations of power vented heaters,
but should be protected against on installations where condensation can form in
the venting system.
Formation of condensation in the venting system of Power Vented water heaters
is dependent upon installation conditions including, but not limited to:
ambient temperature and humidity of installation location;
ambient temperature and humidity of venting space;
vent distance and slope;
and product usage.
In order to effectively control condensate from adversely affecting the mechanical
components of the water heater several methods may be employed:
1. For horizontal installations the vent pipe can be installed with a
downward slope (not less than 1/8" nor greater than ½” per foot
maximum) and away from the blower motor.
2. In order to prevent condensate from draining back into the blower (vertical
or horizontal runs), a fitting and drain hose is available as a condensate
trap kit (see Table 1 for service part numbers). The all rubber fitting with
drain outlet mounts directly to the blower motor outlet and is secured
with two hose clamps (one to the blower motor outlet and the other to the
vent connector). The plastic tubing is provided to drain any accumulated
condensate away from the water heater and to a suitable drain. The kit
comes complete with instructions for proper installation of the fitting.
3. In order to prevent condensate from draining back into the blower (vertical
or horizontal runs), a drain tee and condensate trap can be installed in
the horizontal vent as close as practical to the blower vent connection
(see Figure 2). The condensate disposal tube should be installed to
drain any accumulated condensate away from the water heater and to a
suitable drain. The drain tee and condensate hose are not available from
Bradford White, but should be available through your local distributor.
Figure 2