Bradford-White Corp D38T155 User Manual

COMMERCIAL 24 VOLT FLUE DAMPER
SERIES WATER HEATER
Gas Water Heaters
SERVICE
MANUAL
Troubleshooting Guide
and Instructions for Service
(To be performed ONLY by
qualified service providers)
by This Manual:
For The Bradford White “D” Series Models: D38T155 D75T(125,160,300) D65T(370,399) D80T(180,199,250) D80T(425,505) D100T(199,250) D80L(399,450,505) D100L(199,250,270,300) D100S(199,250)
Manual 47324A
Save this manual for future reference
Table of Contents
Page eF Service Procedure
Introduction 3 - - -
Tool required for service 3 - - -
Sequence of Operation 4 - - -
Troubleshooting 5 - - -
Thermostat Circuit Testing 6 D24-I
Pilot Operation Testing 8 D24-II
Main Burner Operation testing 10 D24-III
Main Burner & Pilot Removal & Inspection 12 D24-IV
Flue Baffle Removal & Inspection 14 D24-V
Anode Removal & Inspection 15 D24-VI
Generic Parts List 16 - - -
Glossary of Terms 19 - - -
Page 2
2
Tools Required for Service
It is intended for this manual to be used by qualified service personal for the primary purpose of troubleshooting analysis and repair of the Bradford White 24 Volt Flue Damper Series Water Heater. Understanding the sequence of operation section of this manual will contribute greatly to troubleshooting this product.
Troubleshooting begins simply by resetting the water heater and observing the lighting sequence to determine failure mode. This step by step procedure beginning on page 5 will direct the service provider to a series of test procedures to determine root cause of failure.
Contact Technical support immediately if diagnosis is not determined using the methods described in this service manual.
Page 3
Manometer: Two types available, a liquid “U” tube type or a digital (magna-helic)
type. This device is used to measure gas and/or air pressures and vacuum.
Multi-Meter: A digital type is strongly recommended. This device is used to measure
electrical values. The meter you select must have the capability to measure volts AC, volts DC, Amps, micro-amps and ohms.
Thermometer: Used to measure water temperature. An accurate thermometer is
recommended.
Water Pressure Gage: Used to measure water supply pressure. Also used to determine tank
pressure by adapting to the drain valve of the heater.
Jumper Leads: A length of wire (12" min.) with alligator clip at both ends.
Various Hand Tools: Pipe wrench, channel locks, open end wrench set, 12" crescent wrench,
Allen wrench set, torx bit set, screw drivers (common & phillips), long reach (12") magnetic tip phillips head screw driver #2 tip, ¼" nut driver, pliers (common & needle nose), socket set including a 1-1/16 deep well socket, wire cutters, wire strippers, wire crimpers, torpedo level, small shop vac, step ladder, and flashlight.
Introduction
3
1
Thermostat calls for heat. The relay closes on the thermostat board, sending 24 volts from the “COM” terminal of the thermostat board to the flue damper.
2
Flue damper begins to rotate open. Once damper is full open, 24 volts is allowed to continue through damper to the “
TH” terminal of ignition module.
3
LED on ignition module illuminates.
4
5
Once pilot flame is proven, sparking will stop.
Page 4
Sequence of Operation
Trial for ignition (90 second trials, 3 trials with 30 second pause between trials).
Ignition module simultaneously sends:
1. 24 volts from “MV/PV” terminal, to “MV/PV” terminal of gas valve (common terminal).
2. 24 volts from “PV” terminal, through the ECO located in the lower thermister, to “PV” terminal of gas valve to establish gas flow at pilot.
3. Low current high voltage from “spark” terminal, to generate spark at the pilot and ignite pilot gas flow.
4. Pilot flame proving signal (measured in micro-amps). from the “sense” terminal, to prove pilot flame.
6
Once sparking stops, 24 volts is sent from “MV” terminal on module, to “MV” terminal on gas valve to establish main burner gas flow. Main burners ignite from the pilot flame.
The ignition module constantly monitors pilot flame. If pilot flame is lost, pilot and main burner are shut down. After a 30 second purge period, module will attempt to re-light pilot beginning at sequence 4 above.
7
Main burner fires until the thermostat is satisfied. The relay on the thermostat board opens, interrupting 24 volts through the damper and ignition module. Pilot and main burner is turned off.
8
Flue damper rotates to the closed position.
WIRING DIAGRAM
LOCKOUT CONDITION
Ignition module will “lockout” if the pilot can not be lit after 3 ignition trials. The ignition module indicates a lockout condition by the continues flash of the LED located on the module.
Lockout reset is accomplished by interrupting 120 VAC to the unit for at least 5 seconds.
4
TROUBLESHOOTING
If LED on ignition module is flashing,
reset water h eater by turning “OFF”
power. Wa it 5 seconds and turn
p
ower back “ON”
R
otate thermostat dial to the
h
ighest setting.
Does damper vane Move to the full
o
pen position?
Does LED light on ignition module
illuminate?
Is there pilot flame?
Does Main burner o perate?
Does burne r continue until th ermostat
set point is reached?
Does flue damper rotate to the closed
position?
System oka y.
Y
Y
Y
Y
Y
Y
N
N
N
N
N
N
Remove damper from
h
eater and
J
ump black & yellow wires
o
f heater harness
(see photo 2)
D
oes LED light on i
gnition mod ule
i
lluminate?
C
heck for debris limiting
d
amper rotation, if no
d
ebris, replace damper
Y
N
See pilot will not light
(page 8)
See pilot lights, no flame
signal.
(page 9)
See main burner
short cycle
(page 11).
Verify Primary and secondary vo ltage
at the transfor mer
(
see pho to 1)
I
gnition Module LED Status
O
FF = No power to module
O
N = Module has power
F
lashing = Module is in lock-out
C
AUTION
Use Caution Not to Damage Connectors when making Voltage Measurements or Jumping Terminals
Is there 24 VAC between
terminals “TR” & “TH” of the
ignition module?
(see pho to 1A)
Check for debris limiting
damper rotation, if no
debris, replace damper
2
Damper van e show in op en position. If damper
is closed, disconnect from harness and
REMOVE damper from water hea ter.
Harness shown disconnected from damper
with BLACK and YELLOW wires jumped.
S
ee thermostat testing
(
page 6).
DANGER
120 volt exposure. Use Caution
To Avoid Personal Injury.
1
Rear ter minals
primary
(120 VAC)
Forward terminals
secondary
(24 VAC)
Ignition module
Page 5
1A
N
Y
Replace ignition module
Check damper harness
connection.
Check for 24 VAC
across ter minals
“TR” & “TH”
5
SERVICE PROCEDURE D24-I
Thermostat Circuit Testing
CAUTION
Be Careful When Making Voltage
Measurements or Jumping Terminals
Not to Damage or Deform Connectors or
Connector Pins.
DANGER
120 volt exposure. To avoid personal injury,
use caution while performing this procedure.
T
HERMOSTAT CIRCUIT BY-PASS
T
urn power “OFF” to water heater and
locate thermostat board inside control box
of water heater. Disconnect YELLOW wires
from the thermostat board at location
“N.O.” & “COM”. Use a jumper to connect
these two w ires together
(see photos 4 & 5).
Does pilot and main bu rner operate?
3
5
W
ith power on to water heater,
Verify Primary and secondary voltage at
the transformer
(see pho to 3)
Turn power on to water heater.
Does LED on ignition module illuminate?
(see photo 6)
T
his procedure assumes the flue damper is in working order. Be sure damper opens under its own power when the thermostat circuit is by-passed. Damper must be open or removed during this test. Do not force damper open using your hands or tools.
Y
N
Y
N
Verify tran sformer vo ltage
(see photo 3)
See pilot operation testing
(page 8)
Disconne ct ORANGE potentiometer (temp
adjustment dial) wires from thermostat
board (see photo 7)
DANGER
Do not leave thermostat jumper in
place for normal operation.
Turn power “OFF”.
Remove jumper and re-connect wires to
thermostat board. Wires are identifie d for
proper connection to b oard.
Check potentiometer for proper resistance values of:
Greater then 4800 Ohms with dial at minimum setting.
Less than 50 Oh ms with dial at maximum setting.
(see photo 8).
Are readings correct?
Replace potentiometer
Check Thermisters
(see page 7)
Y
N
7
8
4
Rear term inals
primary
(120 VAC)
Forward terminals
secondary
(24 VAC)
6
LED Location
Page 6
6
Loading...
+ 14 hidden pages