Bradford-White Corp 9kW, 900kW User Manual

Commercial Electric
Water Heaters
9kW – 900kW Input Models
CHP-I&S-01
INSTALLATION AND SERVICE MANUAL
1
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life
.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
USE THIS APPLIANCE IF ANY PART HAS BEEN UNDER WATER. THE POSSIBLE DAMAGE TO A FLOODED APPLIANCE CAN BE EXTENSIVE AND PRESENT NUMEROUS SAFETY HAZARDS. ANY APPLIANCE THAT HAS BEEN UNDER WATER MUST BE REPLACED.
Installation and service must be performed by Qualified Service Personnel Only
.
Factory warranty (shipped with unit) does not apply to units improperly installed or improperly operated.
Experience has shown that improper installation or system design, rather than faulty equipment, is the cause of most operating problems.
Excessive water hardness causing a lime/scale build-up in the heater and/or on the immersion heating elements is not the fault of the equipment and is not covered under the manufacturer’s warranty. (See Water Treatment and Water Chemistry)
Do not energize electrical system before heater is completely filled with water.
Damage caused to the immersion heating elements by dry fire is not covered under the manufacturer’s warranty. Follow start up procedure in the manual. Water heater corrosion and component failure caused by air-borne chemical vapors is not covered under the manufacturer’s warranty. Corrosion damage caused by current leakage due to improper grounding of electrical systems or electronic components to the storage tank and related piping is not covered by the manufacturer’s warranty. Under no circumstance will the manufacturer be liable for consequential damages resulting from the installation or use of this equipment. Correct installation procedure and local codes must be adhered to.
This manual supplies information for the installation, operation and servicing of the appliance. It is strongly recommended that this manual be reviewed completely before proceeding with an installation. Upon receiving equipment, check for signs of shipping damage. Pay particular attention to parts accompanying the water heater, which may show signs of being hit or otherwise being mishandled. Verify total number of pieces shown on packing slip with those actually received. In case there is damage or a shortage, immediately notify carrier.
CHECKING EQUIPMENT
WARNING:
NOTE: Retain this manual for future reference.
WARNING:
Improper Installation, Adjustment, Alteration, Service or Maintenance
can cause injury or property damage. Refer
to this manual. For assistance or additional
information consult a qualified installer,
service agency or the electric utility.
SPECIAL INSTRUCTIONS
TO OWNER
WARRANTY
DO NOT
2
CONTENTS
Star
t-Up Procedure
Filling the Water Heater . . . . . . . . .22
Start-Up Checks . . . . . . . . . . . . . . .23
Shutdown Procedure . . . . . . . . . . . .24
Maintenance
T&P Relief Valve . . . . . . . . . . . . . .24
Water Chemistry . . . . . . . . . . . . . . .25
Flushing the Tank . . . . . . . . . . . . . .25
Sediment Removal . . . . . . . . . . . . .25
Scale Removal - Elements . . . . . . .25
T
rouble Shooting
Not Enough Hot Water . . . . . . . . . .27
Water Is Too Hot . . . . . . . . . . . . . .27
Water Heater Sounds . . . . . . . . . . .27
Leakage . . . . . . . . . . . . . . . . . . . . .27
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . .1
Safety Warnings . . . . . . . . . . . . . . . .1
Checking the Equipment . . . . . . . . . .1
Codes . . . . . . . . . . . . . . . . . . . . . . . .4
Installation Requirements
Location . . . . . . . . . . . . . . . . . . . . . .4
Drain Pan Requirements . . . . . . . . . .5
Clearances . . . . . . . . . . . . . . . . . . . .6
Mounting . . . . . . . . . . . . . . . . . . . . .7
Water Connections . . . . . . . . . . . . . .7
Tank Construction . . . . . . . . . . . . . .8
Relief Valve . . . . . . . . . . . . . . . . . . .8
Thermal Expansion . . . . . . . . . . . . .8
Cathodic Protection . . . . . . . . . . . . .9
Electrical Ser
vice
Electrical Connection . . . . . . . . . . .9
Wire Sizing . . . . . . . . . . . . . . . . . . .9
Fusing . . . . . . . . . . . . . . . . . . . . . .9
Electrical Connection . . . . . . . . . . . .9
Jacket Assembly . . . . . . . . . . . . . . .10
Standard and Optional Controls . . .10
Components and Contr
ols
Terminal Block . . . . . . . . . . . . . . . .11
Fuses and Fuse Blocks . . . . . . . . . .12
Contactors . . . . . . . . . . . . . . . . . . .12
Transformer . . . . . . . . . . . . . . . . . .12
Immersion Thermostat . . . . . . . . . .13
Temperature Regulation . . . . . . . . .13
Risk of Scald Warnings . . . . . . . . .14
Temperature Control Sequencer . . .14
Display . . . . . . . . . . . . . . . . . . . . . .16
Temperature Adjustment . . . . . . . . .17
Error Messages . . . . . . . . . . . . . . . .18
Temperature Limit Control . . . . . . .18
Immersion Heating Elements . . . . .19
Safety Door Lock . . . . . . . . . . . . . .19
Low Water Cut-Off . . . . . . . . . . . . .20
Low Water Pressure Switch . . . . . .20
High Water Pressure Switch . . . . . .20
Manual Limiting Switches . . . . . . .20
Time Clock . . . . . . . . . . . . . . . . . . .21
Pilot Lights . . . . . . . . . . . . . . . . . . .21
Alarm Bell . . . . . . . . . . . . . . . . . . .21
3
FIG. 2 Front View Vertical Square Models
FIG. 1 Front View Vertical Round Models
FIG. 3 Front View Horizontal Models
To minimize the possibility of serious personal injury, fire or damage to your appliance, never violate the following safety rules.
1. Always keep the area around your
appliance free of combustible materials, gasoline, and other flammable liquids and vapors.
2. Never cover your appliance, lean
anything against it, store trash or debris near it, stand on it or in any way block the access to your appliance.
Be sure to turn off power when working on or near the electrical system of the water heater. Never touch electrical components with wet hands or when standing in water. When replacing fuses, always use the correct size for the circuit. Do not test electrical system before the water heater is completely filled with water. Follow the start-up procedure.
Consult and follow local Electrical Codes, Building and Fire Regulations and other Safety Codes that apply to this installation. Consult local codes officials and electric utility company to authorize and inspect all field installed electrical connections.
The equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made.
These shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made. In the absence of such requirements, the installation shall conform to the latest edition of the National Electrical Code, NFPA 70. When the appliance is installed in Canada, it must conform to the CAE C22.1, Canadian Electrical Code, Part 1 and/or local Electrical Codes.
This complete appliance is design certified and Listed by Underwriters Laboratories as a commercial storage electric water heater. This water heater bears the UL certification for the United States as tested under the Standard for Electric Booster and Commercial Storage Tank Water Heaters, UL1453 and C-UL in Canada as tested under the Standard for Construction and Test of Electric Storage Tank Water Heaters, CAN/CSA-C22.2 No. 110-M90. All water heater storage tanks conform to the latest edition of the ASME Boiler and Pressure Vessel Code, Section IV.
1. Locate the appliance so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the unit. Under no circumstances is the manufacturer to be held responsible for water damage in connection with this unit, or any of its components.
2. Insure that the appliance is located near an acceptable drain so that the vessel can be properly drained when performing service or maintenance. The drain must also provide adequate drainage in the event of leakage the tank or related piping. The drain must prevent water damage to the adjacent area and lower floors of the structure.
4
INSTALLATION PROCEDURE
LOCATION OF UNIT
OWNER WARNING
IMPORTANT:
CAUTION:
WARNING:
CODES
APPROVALS
The information contained in this manual is intended for use by qualified professional installers, service technicians or the electric utility. Consult your local expert for proper installation or service procedures.
3. The appliance must be installed so that the electrical components are protected from water (dripping, spraying, etc.) during appliance operation and service (replacing of fuses, elements, etc.)
4. Appliances located in a garage or parking structure shall be installed so that the jacket and all piping shall be located or protected so that it is not subject to physical damage by a moving vehicle.
5. The appliance must be installed on a level floor. Shim the base as necessary if leveling is required.
6. The floor on which the appliance is installed must be capable of supporting the total weight of the water heater when completely filled with water. Combustible floor locations may be used. Maintain required clearances from combustible surfaces.
7. The appliance must not be installed on carpet.
8. The appliance must be installed indoors where it is protected from exposure to wind, rain and weather.
9. Locate the appliance as close as possible to the point of major hot water usage, the water piping and branch electrical circuit wiring.
10. Insulate water piping to control heat loss and possible condensation.
11. The appliance must be located in an area that is not subject to freezing. The ambient temperature of the space where the appliance is installed must not go below 32° F (0° C) or above 104° F (40° C).
The lower pan of the horizontal water heater jacket or vertical square water heater jacket is specially constructed to function as a drain pan. A water discharge opening is located in either end of the pan. The discharge opening(s) used must be piped to a suitable floor drain. If only one discharge opening in the jacket pan is piped to a floor drain, the unused opening must be plugged. This jacket pan provides an extra margin of protection against water damage on vertical square or horizontally constructed models.
5
Drain Pan on Horizontal Models
and Vertical Square Models
1250 Gallons and Larger
CAUTION:
This water heater, as well as all water heaters will eventually leak. Installation of the water heater should be accomplished in such a manner that if the tank, piping or any connections should leak, the flow of water will not cause damage to the structure. For this reason, it is not advisable to install the water heater in an attic or upper floor. When such locations can not be avoided, a suitable drain pan must be installed under the water heater. Drain pans may be fabricated or purchased from your plumbing wholesaler. The drain pan must be piped to an adequate drain. Under no circumstances is the manufacturer to be held liable for any water damage in connection with this water heater.
Right Side - 6" (15cm) (24" (0.61m) for high kW vertical square models with an
additional control panel on right side)
Rear - 0" Left Side - 0" Front - 36" (0.91m) for service access to controls and heating elements Top - 12" (30cm) for service access to electrical service, water connections and piping Water Pipes - 1" (25.4mm)
6
FIG. 5 Clearances from Combustible Construction
12"
36"
6"
FIG. 4 Clearances from Combustible Construction
CLEARANCES FROM COMBUSTIBLE CONSTRUCTION
6"
12"
FIG. 6 Clearances from Combustible Construction
TABLE A
CLEARANCES FROM COMBUSTIBLE CONSTRUCTION
12"
6"
36"
7
Maintain minimum specified clearances for adequate operation. All installations must allow sufficient space for servicing the electrical components, water pipe connections, piping and other auxiliary equipment, as well as the appliance.
Multiple appliances may be installed in a modular water heater installation. Multiple appliances may be installed side by side with minimum clearance between the sides of adjacent appliances because no service access is required from the sides on most models. Note that high kW input vertical square water heaters may have an additional control access panel located on the right side of the jacket requiring an additional service access from the right side.
The water heater should be mounted to the floor following applicable architectural and local code requirements or accepted standards for the specific site and model purchased. In areas prone to seismic activity, it is recommended that the water heater be mounted to the floor according to recommended procedures for the site. In some geographic areas, additional strapping or braces may be required, consult local codes for specific requirements. Proper mounting will help to make the water heater less susceptible to seismic damage.
WATER CONNECTIONS
HANDHOLE CLEANOUT
DRAIN
HOT WATER OUTLET
TEMPERATURE & PRESSURE RELIEF VALVE
COLD WATER INLET
FIG. 7 Water Connections- Vertical Round Models
TEMPERATURE & PRESSURE RELIEF VALVE
HOT WATER OUTLET
DRAIN PAN CONNECTION
COLD WATER INLET
FIG. 8 Water Connections- Vertical Square Models
MOUNTING
WATER CONNECTIONS
TEMPERATURE & PRESSURE RELIEF VALVE
HOT WATER OUTLET
COLD WATER INLET
MANWAY (OPTIONAL)
DRAIN
FIG. 9 Water Connections- Horizontal Models
Before making any connections to the cold water inlet or hot water outlet, insure that all piping is clean and free of material or scale. This can usually be accomplished by blowing out the pipe.” Any foreign material or scale entering the water heater can adversely affect operation and performance.
Inlet and Outlet Connections
For ease of service, install unions on the cold water inlet and hot water outlet of the water heater. The cold water inlet connection is located on the lower right side of the water heater. A manual shutoff valve should be installed upstream on the cold water source as an isolation device. The hot water outlet connection is located on the top center of the water heater. A manual shutoff valve should be installed downstream on the hot water outlet source as an isolation device in case the water heater must be disconnected from the system.
This appliance uses a glass lined steel tank to store the heated water for use. The storage tank is constructed in accordance with the ASME Boiler and Pressure Vessel Code requirements, stamped and registered with the National Board of Boiler and Pressure Vessel Inspectors. The tank is furnished with threaded connections for cold water inlet, hot water outlet, a relief valve and a drain connection. The storage tank has a hand hole for ease of inspection, cleanout and service. An optional manhole may be specified for greater ease of inspection. The interior of the storage tank is glass lined and fired to 1600˚F
(871˚C) to insure a molecular fusing of glass and steel to protect the steel base metal against corrosion . A magnesium anode(s) is standard to help prevent dissipation of the tank material by electrolytic action.
This water heater is supplied with a temperature and pressure relief valve(s) sized in accordance with ASME Boiler and Pressure Vessel Code, Section IV. Some water heaters may be supplied with an optional pressure only relief valve. The relief valve(s) is installed in the vertical position and mounted in the tapping provided in the storage tank. No valve is to be placed between the relief valve and the water heater. To prevent water damage, the discharge from the relief valve must be piped to a suitable floor drain for disposal when relief occurs. No reducing couplings or other restrictions shall be installed in the discharge line. The discharge line shall allow complete drainage of the valve and line. Relief valves should be manually operated at least once a year. A relief valve that fails to completely reseat and continues to discharge water must be immediately replaced with a new, properly sized, temperature and pressure relief valve.
A relief valve that discharges periodically may be due to thermal expansion in a closed system. A water heater installed in a closed system, such as one with a backflow preventer or check valve installed in the cold water supply, shall be provided with means to control expansion. Contact the water supplier or local plumbing inspector on how to correct this situation.
DO NOT plug or cap the relief valve.
8
STORAGE TANK
NOTE:
When using copper tubing, solder tubing to an adapter before attaching to the threaded nipple connection provided on the water heater. Soldering directly to the threaded connection may harm a lining in the nipple or damage the tank lining.
NOTE:
RELIEF VALVE
Avoid contact with hot discharge water. Insure that no one is in front of or around the relief valve discharge line. Make sure that the extremely hot water manually discharged from the relief valve will not cause bodily injury or property damage.
CAUTION:
THERMAL EXPANSION OF WATER
discharge!
Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To prevent the possibility of injury under these conditions, we recommend the hot water faucet be open for several minutes at a sink close to the water heater before you use any electrical appliance which is connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipe as the hot water begins to flow. There should be no smoking or open flames near the faucet at the time it is open.
All installation procedures involving electric power connection should only be performed by a trained, certified electrician.
9
HINGED DOOR TO ELECTRIC CONTROL COMPARTMENT
ELECTRIC ACCESS
FIG. 11 Electric Power Connections –
Electrical Control Panel – Square Models
HINGED DOOR TO ELECTRICAL COMPARTMENT
ELECTRIC ACCESS
FIG. 10 Electric Power Connections –
Electrical Control Panel – Round Models
The appliance, when installed, must be electrically grounded in accordance with the requirements of the authority having jurisdiction or in the absence of such requirements, with the latest edition of the National Electrical Code, NFPA No. 70. When the appliance is installed in Canada, it must conform to the CAE C22.1, Canadian Electrical Code, Part 1 and/or local Electrical Codes.
1. Use copper conductors only. All wiring between the appliance and field installed devices shall be made with copper wire suitable for at least 75° C (167° F) temperature rating. If the wiring from an old water heater installation was aluminum, replace the old wire with copper wire.
2. The factory internal wiring is attached to a terminal block inside the unit. The branch circuit is connected to the terminal block through an opening provided on the top of the water heater electrical access panel.
3. Line voltage wire exterior to the appliance must be enclosed in approved conduit or approved metal clad cable.
4. To avoid serious damage,
DO NOT energize the appliance until the system is full of water
. Ensure that all air is removed from the
storage tank and piping before beginning
CATHODIC PROTECTION
ELECTRICAL CONNECTIONS
WATER HEATER IS EQUIPPED FOR OPERATION ON ONE VOLTAGE ONLY.
Check the rating plate on the front of the control panel access for the correct voltage and phase.
DO NOT use this
water heater with any other voltage other than the voltage specified on the rating plate. Failure to use the correct voltage can cause problems that can result in death, serious bodily injury or property damage.
DO NOT CONNECT THE WATER HEATER TO AN IMPROPER SOURCE OF ELECTRICITY!
CAUTION:
WARNING:
Loading...
+ 19 hidden pages