Bradford White U-4-XRTW65T6FRN User Manual

Page 1
SUPPLEMENT TO INSTRUCTION MANUAL
P/N 238-45637-00 and 238-48933-00
(Replaces pg. 32 (238-45637-00) or pg. 28 (238-48933-00) in
instruction manual.)
Wiring Diagram
Honeywell
VERY
C
B
A
LOW
Figure 10 or Figure 6
238-48214-00B REV 11/09
Page 2
Burner Flame Check
(Replaces pg. 36 (238-45637-00) or pg. 32 (238-48933-00) in
instruction manual.)
These models are equipped with self adjusting air mixture and do not have an adjustable air shutter (See Figure 12). At periodic intervals a visual check of the main burner and pilot flames should be made to determine if they are burning properly. The main burner flame should light smoothly from the pilot.
Figure 12 or Figure 8
2
Page 3
(Replaces pg. 42 (238-45637-00) or pg. 38 (238-48933-00) in
instruction manual.)
Troubleshooting continued-
LED Status Control Status Proba b le Cause
Six flashes-three flashes, three second pause (Soft lockout)
Six flashes-four flashes, three second pause
Seven flashes, three second pause
Eight flashes-one flash, three second pause
Eight flashes-three flashes, three second pause
Eight flashes-four flashes, three second pause
Pilot flame extinguished. System re s et s afte r 5 minutes.
Undesired-false pilot flame sensed. System auto resets.
Flammable vapor sensor fault detected, see warning label
Flammable vapor sensor out of specification. Possible short.
T'stat well & sensor damaged or unplugged
or Gas valve electronics fault detected
Gas valve fault detected.
1. Unstable pilot.
2. Pilot tube blocked or restricted.
3. Oxidation build up on pilot electrode.
4. Wire damage to pilot assembly or bad connection at gas valve.
5. Insufficient combustion air.
Pilot valve stuck in open position.
1. Flammable vapor present
2. Flammable vapor sensor exposed to excessive moisture
3. Flammable vapor sensor exposed to extreme ambient temp
4. Resettable thermal switch open.
1. Flammable vapor sensor out of specification
2. Possible short in flammable vapor sensor or resettable thermal switch wiring.
1. Damage to thermowell wire.
2. Thermowell sensor resistance out of range.
3. Replace thermowell.
4. Verify control is not wet or physically damaged
5. Reset control on/off switch.
6. Replace electronic module if 8-3 error persists
1. Verify control is not wet or physically damaged
2. Reset control on/off switch.
3. Replace gas control if 8-4 error persists
Fault Probable Cause
Resettable thermal switch tripped (open)
Control Sequence of Operation
1. Burner failure.
2. Flammable vapor present.
Start up Sequence
Upon powering up, the control checks for the presence of the vapor sensor, if the resistance is in the expected range the control will begin normal operation after 5 to 8 seconds. Normal Heating Sequence
1. The thermostat senses a need for heat.
2. The control checks the pressure switch condition.
3
Page 4
(Replaces pg. 43 (238-45637-00) or pg. 39 (238-48933-00) in
instruction manual.)
PARTS LIST DRAWING
4
Page 5
PARTS LIST
PART NAME AND DESCRIPTION
1. Blower Assembly 17. Drain Valve
2. Temperature Switch 18. Gas Valve
3. Pressure Switch 19. Thermal Well
4. Jacket Head Pan 20. Wire Harness
5. Jacket 21. Radiant Burner
6. Outer Door 22. Orifice
7. Mag. Anode- Hot Water Outlet 23. Manifold Mount
8. Flue Baffle Assembly 24. High Temp. Limit Switch
9. Dip Tube-Cold Water Inlet 25. Gas Feedline to Burner
10. Temp. & Pressure Relief Valve 26. Gas Feedline to Pilot
11. Glass Lined Tank 27. Spark Igniter
12. Flue Reducer 28. Mounting Plate
13. Combustion Chamber Assembly 29. Pilot Assembly
14. Jacket Base Pan 30. Flammable Vapor Sensor
15. Inner Door Gasket 31. Flam. Vapor Sensor Clip
16. Inner Door Assembly 32. Dilution Air Clip
(Continued)
(Replaces pg. 44 (238-45637-00) or pg. 40 (238-48933-00) in
instruction manual.)
THE FOLLOWING INSTRUCTIONS ARE FOR INSTALLATION OF:
GAS WATER HEATERS SUITABLE FOR WATER (POTABLE)
HEATING AND SPACE HEATING
1. All piping components connected to this water heater for space heating applications must be suitable for use with potable water. In Massachusetts, space heating piping length must not exceed 50 feet (15.24 meters).
2. Toxic chemicals, such as those used for boiler treatment, must not be
introduced into potable water used for space heating.
3. This water heater must not be connected to an existing heating system or
component(s) previously used with a non-potable water heating appliance.
4. When the system requires water for space heating at temperatures higher than required for other means, such as an ASSE approved mixing valve must be installed to temper the water for those uses in order to reduce the scald hazard potential.
Please refer to the illustrations on the following pages for the suggested piping arrangements.
5
Page 6
Suggested piping arrangement (Continued)
6
Page 7
Suggested piping arrangement (Continued)
7
Page 8
Notes:
8
Loading...