Bradford White U-4-XRTW65T6FRN User Manual

SUPPLEMENT TO INSTRUCTION MANUAL
P/N 238-45637-00 and 238-48933-00
(Replaces pg. 32 (238-45637-00) or pg. 28 (238-48933-00) in
instruction manual.)
Wiring Diagram
Honeywell
VERY
C
B
A
LOW
Figure 10 or Figure 6
238-48214-00B REV 11/09
Burner Flame Check
(Replaces pg. 36 (238-45637-00) or pg. 32 (238-48933-00) in
instruction manual.)
These models are equipped with self adjusting air mixture and do not have an adjustable air shutter (See Figure 12). At periodic intervals a visual check of the main burner and pilot flames should be made to determine if they are burning properly. The main burner flame should light smoothly from the pilot.
Figure 12 or Figure 8
2
(Replaces pg. 42 (238-45637-00) or pg. 38 (238-48933-00) in
instruction manual.)
Troubleshooting continued-
LED Status Control Status Proba b le Cause
Six flashes-three flashes, three second pause (Soft lockout)
Six flashes-four flashes, three second pause
Seven flashes, three second pause
Eight flashes-one flash, three second pause
Eight flashes-three flashes, three second pause
Eight flashes-four flashes, three second pause
Pilot flame extinguished. System re s et s afte r 5 minutes.
Undesired-false pilot flame sensed. System auto resets.
Flammable vapor sensor fault detected, see warning label
Flammable vapor sensor out of specification. Possible short.
T'stat well & sensor damaged or unplugged
or Gas valve electronics fault detected
Gas valve fault detected.
1. Unstable pilot.
2. Pilot tube blocked or restricted.
3. Oxidation build up on pilot electrode.
4. Wire damage to pilot assembly or bad connection at gas valve.
5. Insufficient combustion air.
Pilot valve stuck in open position.
1. Flammable vapor present
2. Flammable vapor sensor exposed to excessive moisture
3. Flammable vapor sensor exposed to extreme ambient temp
4. Resettable thermal switch open.
1. Flammable vapor sensor out of specification
2. Possible short in flammable vapor sensor or resettable thermal switch wiring.
1. Damage to thermowell wire.
2. Thermowell sensor resistance out of range.
3. Replace thermowell.
4. Verify control is not wet or physically damaged
5. Reset control on/off switch.
6. Replace electronic module if 8-3 error persists
1. Verify control is not wet or physically damaged
2. Reset control on/off switch.
3. Replace gas control if 8-4 error persists
Fault Probable Cause
Resettable thermal switch tripped (open)
Control Sequence of Operation
1. Burner failure.
2. Flammable vapor present.
Start up Sequence
Upon powering up, the control checks for the presence of the vapor sensor, if the resistance is in the expected range the control will begin normal operation after 5 to 8 seconds. Normal Heating Sequence
1. The thermostat senses a need for heat.
2. The control checks the pressure switch condition.
3
Loading...
+ 5 hidden pages