Bradford-White U2TW65T-FRN, UTW450S60FR-N, U1TW50S-FRN, UTW465S60FR-N, U1TW60T-FRN User Manual

...
Page 1
®
TTW Eco-Defender
Residential Ultra Low NOx Gas Water Heaters
SERVICE
MANUAL
Troubleshooting Guide
and Instructions for Service
(To be performed ONLY by
qualified service providers)
by This Manual:
U1TW40S*FRN U1TW50S*FRN U1TW60T*FRN U2TW50T*FRN U2TW65T*FRN UTW450S60FR*N UTW465S60FR*N
(*) Denotes Warranty Years
Manual 238-48385-00A
Save this manual for future reference
Page 2
Page 2
Table of Contents
Section Page
Introduction ______________________________________________5 How to Use this Manual _____________________________________6 Tools Required for Service ___________________________________7 Specifications _____________________________________________8 Sequence of Operation_____________________________________ 12 Power Up Sequence
Normal Heating Sequence Abnormal Operation Troubleshooting __________________________________________ 17 Burner Maintenance _______________________________________ 20 Burner Inspection
Burner Cleaning Procedure Pilot Maintenance _________________________________________ 22
Pilot Inspection Testing and Replacement Pressure Switch Testing and Replacement _____________________ 25 Blower Testing and Replacement _____________________________ 28 Blower Temperature Switch Testing and Replacement ____________ 31 Thermal Well Testing ______________________________________ 34 Determine Water Temperature Inside Tank_____________________ 35 Gas Control and Thermal Well Testing and Replacement __________ 36 Flammable Vapor Sensor Testing and Replacement ______________ 40 115 VAC Circuit Trace _____________________________________ 40 Safety Circuit Voltage Trace_________________________________ 42 Flue Baffle Inspection and Replacement _______________________ 43 Diptube Inspection and Replacement _________________________ 44 Anode Inspection and Replacement___________________________ 45 Inner Door Removal, Inspection and Replacement _______________ 46 Inner Door Gasket Replacement _____________________________ 47 Inner Door Installation_____________________________________ 48 ScreenLok ® Flame Arrestor Cleaning_________________________ 49 Common Terms __________________________________________ 50 Notes __________________________________________________ 50 Parts List _______________________________________________ 51
2
Page 3
WARNING
If the information in these instructions is not followed exactly, a fire or ex­plosion may result causing property damage, personal injury, or death.
What to do if you smell gas:
x Do not try to light any appliance x Do not touch any electrical switch; do not use any phone in your build-
ing
x Immediately call your gas supplier from a neighbor’s phone. Follow the
gas supplier’s instructions.
x If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
CAUTION
Incorrect operation of this water heater may create a hazard to life and property and will nullify the warranty.
If sweat fittings are to be used, DO NOT apply heat to the nipples on top of the water heater. Sweat the tubing to the adapter before fitting the adapter to the water connections. It is imperative that heat is not applied to the nipples containing a plastic liner.
Turn off or disconnect the electrical power supply to the water heater be­fore servicing. Label all wires prior to disconnection when servicing con­trols. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
DANGER
Do not store or use gasoline or other flammable, combustible, or corrosive vapors and liquids in the vicinity of this or any other appliance.
NOTICE
Before proceeding, please inspect the water heater and its components for possible damage. DO NOT install any water heater with damaged compo­nents. If damage is evident, then please contact the supplier where the water heater was purchased or the manufacturer listed on the rating plate for replacement parts.
Page 3
3
Page 4
Page 4
WARNING
Water heaters are heat producing appliances. To avoid damage or injury, do not store materials against the water heater or any of its components. Use proper care to avoid unnecessary contact, especially by children, with the water heater and its components. Under no circumstances must flam­mable materials, such as gasoline or paint thinner be used or stored in the vicinity of this water heater or in any location in which the fumes could reach the water heater.
Hydrogen gas can be produced in an operating water heater that has not had water drawn from the tank for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To prevent the possibility of injury under these conditions, we recommend a hot water fau­cet to be open for several minutes at the kitchen sink before you use any electrical appliance which is connected to the hot water system. If hydro­gen is present, there will be an unusual sound such as air escaping through the pipes as hot water begins to flow. Do not smoke or have open flame near the faucet at the time it is open.
DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU ARE NOT CER­TAIN OF THE FOLLOWING:
Liquefied petroleum gases/propane gas and natural gas have an odorant added by the gas supplier that aids in the detection of the gas. Most peo­ple recognize this odor as a “sulfur” or “rotten egg” smell. Other condi­tions, such as “odorant fade” can cause the odorant to diminish in intensity, or ”fade,” and not be as readily detectable. If you have a diminished sense of smell, or are in any way unsure of the presence of gas, immediately con­tact your gas supplier from a neighbor's telephone. Gas detectors are available. Contact your gas supplier, or plumbing professional for more in­formation.
FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED 3/4” X 3/4” TEM­PERATURE AND PRESSURE RELIEF VALVE WILL RELEASE THE MANUFAC­TURER FROM ANY CLAIM THAT MIGHT RESULT FROM EXCESSIVE TEM­PERATURE AND PRESSURES.
4
Page 5
Page 5
The Bradford White ECO-DEFENDER Safety System
®
The Bradford White ECO-DEFENDER Safety System was designed to resist the ignition of flammable vapors that can occur outside of the water heater and produce Ultra Low NOx emissions. Use and installation are nearly iden­tical to previous versions of atmospherically fired and vented water heaters. A number of exclusive design features are incorporated in the system that will require additional knowledge on the part of the qualified service pro­vider. The following information will instruct service professionals on the function, proper diagnosis, and repair of water heaters employing the Brad­ford White ECO-DEFENDER Safety System.
Introduction
The new Bradford White TTW ECO-DEFENDER water heaters are designed to provide reli­able performance with enhanced standard features. New design features include reliable spark to pilot ignition system, enhanced diagnostics, simplified servicing, quiet operation, additional vent lengths, Bradford White ECO-DEFENDER Safety System ® and Ultra Low NOx emis­sions.
Spark-to-Pilot Ignition System - Employing the spark-to-pilot ignition system promotes reli­able and consistent pilot and main burner ignitions to provide hot water on demand.
Integrated Immersion Thermal Well/Gas Control with LED - Was developed for ease of troubleshooting by providing simple diagnostic codes to pinpoint an installation or component performance issue.
New Powerful Blower - Will eliminate problems with difficult venting situations.
Quieter and Cooler Blower Operation - Blower noise is significantly reduced for both inte-
rior and exterior environments. Cooler operation increases blower life by reducing bearing wear and noise.
Rugged Wiring Connections - receptacle type connections promote error free wiring.
Increased Vent Lengths - Increased venting performance is achieved while maintaining En-
ergy Factor and FHSR performance.
The TTW1, TTW2 & TW4 water heaters use a combustion system were flue gases are com­bined with dilution air to reduce the flue gas temperature in the blower. The diluted flue gases are evacuated to the exterior through low temperature vent materials. The gas control main­tains water temperature, ignition sequence and regulates gas flow. A safety circuit consisting of a pressure switch and blower temperature switch verifies proper conditions exist for safe and reliable operation. If a situation outside of normal operating parameters exists, the gas control
Introduction
5
Page 6
Page 6
diagnostic LED will flash a code to positively identify an operational issue.
This service manual is designed to facilitate problem diagnosis and enhance service efficiency. To further promote quicker service times the new gas valve can be removed and replaced with­out draining the water heater. A special tool is required and will be provided with each gas valve kit shipped from our Service Parts department.
Please read the service manual completely before attempting service on this new series of power
How the Safety System Works
During normal operation, most air for combustion is drawn into the water heater through the openings in the jacket door. This air travels into the burner venturi, mixing with the gas jet. This air is then mixed with gas inside the burner and drawn to the burner screen and is effi­ciently combusted producing Ultra Low NOx emissions. Additional air is drawn through the openings in the jacket. This air travels down and around the combustion chamber and enters through holes in the bottom of the corrosion-resistant combustion chamber. The air then travels up through the oriented flame arrestor plate louvers, where the velocity of the air is increased and its direction altered. The air then mixes in a normal manner with the combustion products from the burner.
In the case where trace amounts of flammable vapors are present in the air flowing into the combustion chamber and burner venturi, the vapors are harmlessly ignited by the burner / pilot flame. If flammable vapors are in sufficient quantity to prevent normal combustion, the burner and pilot flames are designed to shut down.
Should the flammable vapors continue to the burner, the flame arrestor plate and burner screen prevent the flames from traveling backwards and igniting vapors outside of the combustion chamber. This causes the thermopile to overheat and shuts down the main pilot and burner. The thermopile powers the intelligent diagnostic control which is capable of recognizing restricted airflow conditions caused by severe lint, dust and oil accumulation on the burner screen and arrestor plate. The intelligent diagnostic control will deactivate the burner and pilot in the unlikely event of restricted airflow.
How to Use this Manual
It is intended for this manual to be used by qualified service personnel for the primary purpose of troubleshooting and repair of the Bradford White Residential Flue Damper water heaters. Understanding the sequence of operation section of this manual will contribute greatly to trou­bleshooting the water heater.
The Honeywell WV4460E Electronic Gas Control will display error codes in the event of ab­normal operation. Error codes are listed in the troubleshooting chart beginning on page 13 of this service manual. The troubleshooting chart will also indicate the probable cause for the error code and direct the service professional to a service procedure to properly diagnose the abnor­mal operation.
How to Use this Manual
6
Page 7
Page 7
Contact the Bradford White technical support group immediately if diagnosis cannot be made using the methods described in this service manual.
Tools Required for Service
Manometer: A liquid “U” tube type or a digital (magna-helic) type can be used. This device is
used to measure gas and/or air pressure and vacuum.
Multi-Meter: A digital type is strongly recommended. This device is used to measure electrical values. The meter you select must have the capability to measure volts AC, volts DC, amps, micro-amps and ohms.
Electronic Probes: In some cases, standard multi-meter probes will damage or simply not be effective to obtain certain voltage and ohm reading. It will be necessary to have special elec­tronic “pin” type multi-meter probes. These probes are available at most electronic wholesale outlets.
Thermometer: Used to measure water temperature. An accurate thermometer is recommended.
Water Pressure Gage: Used to measure water supply pressure. Also used to determine tank
pressure by adapting to the drain valve of the heater.
Gas Control Service Tool: BWC part number 239-45991-00. A specialized tool designed to remove the gas control from gas control thermal well. Available from your Bradford White parts supplier.
Various Hand Tools: Pipe wrench, channel locks, open end wrenches (3/8", 7/16", 1/2"), 12" crescent wrench, Allen wrench set, screw drivers (common & Phillips), 1/4" nut driver, pliers (common & needle nose), socket set, side cutters, wire cutters, wire strippers, wire crimpers, torpedo level, small shop vac, step ladder, flashlight, and 5 gallon pail.
Tools Required
7
Page 8
Page 8
P
ower Supply Dedicated 115VAC, 60 Hz, 15A.
G
as Supply Pipe Minimum 1/2” NPT (schedule 40 black iron pipe recommended).
A
pproved Gas Type Natural Gas.
G
as Pressure 6.0” W.C. minimum, 11.0” W.C. maximum.
Venting System Power vent through the wall or vertical through the roof.
Approved Vent Materials PVC, CPVC or ABS.
Minimum clearance for Servicing
1
8” from top, 24” from front, 4” sides and rear.
Water Supply Pressure
150 PSI maximum allowable working pressure. Check local codes for supply pressure.
TCO Limit Residential 118
o
F (87oC), Commercial 199oF (93oC).
Residential Temperature Set Point Range
60
o
F (16oC) to 160oF (71oC) (approximate temperatures).
Commercial Tempera­ture Set Point Range
80oF (27oC) to 180oF (82oC) (approximate temperatures).
Blower Temperature Switch
Normally closed, opens @ 165oF (74oC), auto reset @130oF (54oC)
Pressure Switch
UTW1 Models:
Normally open, closes on vacuum increase @ -0.68, opens on vacuum decrease @ -0.65
U2TW Models:
Normally open, closes on vacuum increase @ -1.28, opens on vacuum decrease @-1.25
Blower
UTW1 Models:
115VAC, 60Hz, 3.1 amps, 3000 RPM, 42 CFM @ 1.5” W.C.
U2TW Models:a,
115VAC, 60Hz, 3.1 amps, 3000 RPM, 68 CFM @ 0.4” W.C.
Specifications
8
Page 9
Page 9
Vent Tables
Venting Specifications for:
40 Gallon—40,000 BTU/hr.
50 Gallon—40,000 BTU/hr.
6
0 Gallon—42,000 BTU/hr.
2” Diameter (5.1 cm) PVC Vent Connector Lengths
Terminating # of Elbows
Maximum Straight
L
ength ft (m)
Minimum Straight
L
ength ft (m)
T
hrough the Wall 1 45 (13.7) 2 (0.6)
Through the Wall 2 40 (12.2) 2 (0.6)
Through the Wall 3 35 (10.7) 2 (0.6)
Through the Wall 4 30 (9.2) 2 (0.6)
Through the Roof 0 50 (15.2) 7 (2.1)
Through the Roof 1 45 (13.7) 7 (2.1)
Through the Roof 2 40 (12.2) 7 (2.1)
Through the Roof 3 35 (10.7) 7 (2.1)
Through the Roof 4 30 (9.2) 7 (2.1)
3” Diameter (7.6 cm) PVC Vent Connector Lengths
Terminating # of Elbows
Maximum Straight
Length ft (m)
Minimum Straight
Length ft (m)
Through the Wall 1 115 (35.0) 10 (3.1)
Through the Wall 2 110 (33.5) 10 (3.1)
Through the Wall 3 105 (32.0) 10 (3.1)
Through the Wall 4 100 (30.5) 10 (3.1)
Through the Wall 5 95 (29.0) 10 (3.1)
Through the Roof 0 120 (36.6) 15 (4.6)
Through the Roof 1 115 (35.0) 15 (4.6)
Through the Roof 2 110 (33.5) 15 (4.6)
Through the Roof 3 105 (32.0) 15 (4.6)
Through the Roof 4 100 (30.5) 15 (4.6)
Specifications
9
Page 10
Page 10
Vent Tables
Venting Specifications for:
48 Gallon—60,000 BTU/hr.
65 Gallon—60,000 BTU/hr.
3” Diameter (7.6 cm) PVC Vent Connector Lengths
Terminating # of Elbows
Maximum Straight
Length ft (m)
Minimum Straight
Length ft (m)
Through the Wall 1 55 (16.8) 2 (0.6)
Through the Wall 2 50 (15.2) 2 (0.6)
Through the Wall 3 45 (13.7) 2 (0.6)
Through the Wall 4 40 (12.2) 2 (0.6)
Through the Roof 0 60 (18.3) 7 (2.1)
Through the Roof 1 55 (16.8) 7 (2.1)
Through the Roof 2 50 (15.2) 7 (2.1)
Through the Roof 3 45 (13.7) 7 (2.1)
4” Diameter (10.2 cm) PVC Vent Connector Lengths
Terminating # of Elbows
Maximum Straight
Length ft (m)
Minimum Straight
Length ft (m)
Through the Wall 1 175 (53.3) 10 (3.1)
Through the Wall 2 170 (51.8) 10 (3.1)
Through the Wall 3 165 (50.3) 10 (3.1)
Through the Wall 4 160 (48.8) 10 (3.1)
Through the Wall 5 155 (47.2) 10 (3.1)
Through the Roof 0 180 (54.9) 15 (4.6)
Through the Roof 1 175 (53.3) 15 (4.6)
Through the Roof 2 170 (51.8) 15 (4.6)
Through the Roof 3 165 (50.3) 15 (4.6)
Through the Roof 4 160 (48.8) 15 (4.6)
Specifications
10
Page 11
Page 11
Specifications
Wiring Diagram
Control Timings
Ignition State Timing
Pre-purge 15 seconds
Trial for Ignition 90 seconds
Flame Stabilization Period 3 seconds
Inter-purge 15 seconds
F
lame Failure Response Time 1.5 seconds (2 second maximum, 1 second minimum)
Post-purge 15 seconds
PS Fault Delay (failed open/close) Retry after 2 minutes
Soft Lockout Retry after 5 minutes
TCO Limit Lockout Indefinite (see page 34 to reset)
Verify Resistive Delay Retry after 2 minutes (repeats 5 times)
Simulated Resistive Load Lockout Indefinite (cycle power to reset)
Hardware Error Lockout Indefinite (self clears if fault clears for at least 15 seconds)
M
BLOWER
BK
W
R
BL
W
BK
Honeywell
W
PILOT
G
Y
G
SWITCH
BLOWER
SWITCH
PRESSURE
R
BL
Y
TEMPERATURE
BLOWER
G
W
MOTOR
FLAMMABLE VAPOR SENSOR
WATER TEMPERATURE SENSOR
Y
PLUG
BK
BK
BK
RESETTABLE THERMAL
11
Page 12
Page 12
Power Up Sequence
1. Start-up: Upon power up, the gas control runs a safe start check with a
typical delay of 5 seconds.
2. Flammable Vapor Verification: The gas control verifies that the Flamma-
ble Vapor Sensor is in the proper operating range prior to energizing any components. If the sensor is within the proper range, the gas control resumes normal operation. If the Flammable Vapor Sensor is out of range, the gas control LED immediately flashes 7 times with a 3 second pause.
Normal Heating Sequence
1. Thermostat Calls for Heat: Prior to energizing the blower, the gas control
checks the safety circuit to insure the circuit is open. In the safety circuit the pressure switch is normally open and the blower temperature switch is normally closed.
2. If the safety circuit is closed, the gas control waits 4 seconds, the gas
control LED flashes 2 times with a 3 second pause. The gas control waits 2 minutes. Then, the blower runs for 30 seconds. This cycle re­peats until the safety circuit opens.
3. Blower energizes.
4. Pressure switch proves blower/vent system operation: If the pressure
switch does not close within 30 seconds, the gas control LED flashes 3 times with 3 second pause. The blower runs for 30 seconds every 2 min­utes trying to get the pressure switch or blower temperature switch to close. This cycle repeats as long as there is a call for heat.
5. Blower pre-purge period (15 seconds).
6. Trial for Pilot Ignition (90 seconds): The gas control lights the pilot by
activating the spark igniter and gas flow to the pilot burner. If flame is not sensed within 90 seconds, the spark igniter and gas flow are deacti­vated. The blower will post-purge, and the gas control LED flashes 6 times with a 3 second pause.
Sequence of Operation
12
Page 13
Page 13
Normal Heating Sequence (cont’d)
7. Main Burner Ignition: After pilot flame is sensed, the gas control acti­vates the main valve for main burner ignition. The gas control will ig­nore flame and pressure switch signals for 3 seconds to allow for the main burner to stabilize.
8. Steady State Operation: During steady state operation, the gas control monitors:
Thermostat Temperature Sensor: When the setpoint temperature is sat­isfied, the gas control is shutdown, and the blower will post-purge for 15 seconds. The gas control LED flashes a short flash once every 4 seconds (Idle status code).
Pressure switch/blower temperature switch: If either switch opens, the pilot valve and the main valve are shut down. The blower continues to run for 30 seconds attempting to close the circuit. The gas control LED flashes 3 times with 3 second pause.
Flame Sensor: If flame is lost, the pilot and main valves are shutdown. The blower runs for 15 seconds. The gas control attempts to re-light the pilot 4 times. If unsuccessful, the blower is shutdown, and the gas con­trol proceeds to a 5 minute lockout. The gas control re-attempts to light the pilot starting at Normal Heating Sequence #2.
9. Thermostat Satisfies: Gas control LED flashes once every 4 seconds.
10.Burner Off.
11.Blower post-purge (15 seconds).
Abnormal Operation
1. Flammable Vapor Sensor Fault:
A) If the resistance is greater than 70,000 ohms: The gas control imme­diately turns off all outputs. The gas control waits and monitors resis­tance for 30 seconds. If the resistance is greater than 65,000 ohms af­ter 30 seconds, the gas control proceeds to verify resistive delay for 2 minutes and flashes 7 times then 1 time with a three second pause. This process is repeated 5 times until the control either returns to normal op­eration or proceeds to flammable vapor lockout.
Sequence of Operation
13
Page 14
Page 14
Abnormal Operation (cont’d)
B) If the resistance is below 3000 ohms: The gas control immediately turns off all outputs and proceeds to flash 8 times then 1 time with a three second pause. The error self clears if the resistance returns to nor­mal range for at least 15 seconds.
2. Temperature Sensor Fault:
A) Temperature Sensor Open Circuit: The gas control immediately turns off all outputs and proceeds to flash 8 times then 3 times with a three second pause. The error self clears if the fault clears for at least 15 sec­onds.
B) Thermal well sensors not reading the same temperature within ±5.5°F: The gas control immediately turns off all outputs and proceeds to flash 8 times then 3 times with three second pause. The error self clears if the fault clears for at least 15 seconds.
C) Water Temperature in excess of ECO (Energy Cut Off) Limit: The gas control immediately turns off the pilot and main valves. The gas control LED proceeds to flash 4 times with a 3 second pause.
To reset the gas control, rotate the setpoint knob to the minimum set­ting for at least 6 seconds before returning to desired temperature set­ting.
3. Pressure Switch/Blower Temperature Fault:
A) Pressure switch closed at start of call for heat: The gas control waits 4
seconds then, proceeds to flash 2 times with a 3 second pause. The gas control waits 2 minutes and then turns on the blower for 30 sec­onds. The blower turns off after 30 seconds and the control waits for the pressure switch to open. Any time the pressure switch opens, the blower turns on (or stays on) and the control proceeds to wait for the pressure switch to close.
Sequence of Operation
14
Page 15
Page 15
Abnormal Operation (cont’d)
B) Pressure switch or blower temperature switch failed to close: The gas
control runs the blower for 30 seconds waiting for the pressure switch and/or the blower temperature switch to close. If either switch does not close in 30 seconds, the blower turns off and the control flashes 3 times with a 3 second pause. The gas control waits 2 minutes before turning on the blower for another 30 seconds to see the circuit close. This cycle repeats as long as there is a call for heat or until the circuit closes.
C) Pressure switch or blower temperature switch opens during operation:
The gas control turns off the pilot and main valve, runs the blower for 15 seconds (inter-purge) waiting for the pressure switch and/or the blower temperature switch to close. If either switch fails to close, the gas control proceeds as described in 3b above. If the circuit closes again by the end of the inter-purge, the recycle counter is incre­mented, if the recycle count has not reached its limit (4), another trial for ignition begins. If the recycle count has been reached, the gas control turns off the blower and flashes 6 times, then 2 times with a 3 second pause. The gas control waits 5 minutes before repeating ig­nition sequence.
4. Trial for Ignition Fault:
A) Pressure switch opens during trial: The gas control turns off the ig-
niter and pilot valve. The gas control proceeds as described in 3b above. If the pressure switch closes within 30 seconds the gas control will continue with a trial for ignition starting at blower pre-purge.
B) Flame Not Sensed: The gas control energizes the spark igniter at-
tempting to light the pilot and prove flame. If flame is not sensed within 90 seconds, the spark igniter turns off, the pilot valve is closed. The gas control LED flashes 6 times then 1 time with 3 sec­ond pause. The control waits 5 minutes before repeating the ignition sequence.
Sequence of Operation
15
Page 16
Page 16
Abnormal Operation (cont’d)
5. Flame Sensing Fault:
A) Flame Lost During Run: The gas control turns off the pilot and main valves and runs the blower for 15 seconds (inter-purge) The gas control increments the recycle count, if the recycle count has not reached its limit (4), another trial for ignition begins. If the recycle count has been reached, the gas control LED flashes 6 times then 3 times with a 3 sec­ond pause. The gas control waits 5 minutes before repeating the igni­tion sequence.
B) Flame Sensed Out of Sequence: The gas control only looks for pilot flame when the blower is running. If flame is present when the pilot valve is not open, the gas control proceeds to wait for flame loss and flashes 5 times with 3 second pause. This continues until flame is lost, once the flame signal is lost, the control flashes 6 times then 4 times with a 3 second pause. The control waits 5 minutes before repeating the ignition sequence.
Sequence of Operation
16
Page 17
Page 17
LED Status Control S tatus Probable C ause Service Procedure
None (LED
not on or
flash in
g)
No e le ctrica l p o w e r
Co n trol pow er sw itch in "OFF" position. Su
pply
voltage inte rrupted.
Turn P o w er O n
One short
flash every
four seconds
Stand-by mode,
Thermostat is
satisfied
(
no faults
)
Temperature demand is satisfied (no ca ll for heat)
Normal ope ra tio n
Alternates bright and
dim
(
heartbeat
)
The rmo s tat ca llin g
for he a t (no fault)
Tank temperature below setpoint of thermostat
Normal ope ra tio n
Sho rt flash
once every
second
Weak pilot signal
on la s t call for he a t
1. Uns ta ble p ilo t
2. P ilo t tub e b lo cked o r re s tricted
3. O xid a tion b uild-up o n pilot electrode
4. W ire d a mage to pilo t assembly or bad connection at ga s co ntrol
1. See Burner Inspection on page 20 2-4. See Pilot Inspection, Testing and Replacement on page 22
Tw o fla s hes,
three second
pause
Pressure switch not
working-closed
po s itio n
1. Pressure switch tubing kinked or blocked
2. Blocked pressure tap on sw itch o r b lo w er
3. Fault
yp
ress ure sw itch
1-3. See Pressure Switch Testing on page 25
Three
flashes,
three second
pause
Pressure switch or
blower temperature
switch not working-
open position
1. Vent blockage or improper vent configuration
2. Pressure switch tubing kinked or blocked
3. Faulty pressure switch
4. Blower not spinning up to speed
5. Blower temperature or exhaust temperature too high
6. Faulty blow er temperature switch
1. Check vent or vent tables 2-3. See Pressure Switch Testing on page 25
4. See Blower Testing on page 28 5-6. See blower Temperature Sw itch Te s ting on p a ge 31
Four flashes,
three second
pause
Excessive tank
temperature,
system must be
reset
1. Thermal well sensor out of calibra tion
2. Faulty gas control
1. Te s t Ga s Contro l & Thermal Well
2. Re p la ce g a s co n trol if necessar
y
Five flashes,
three second
pause
Fa ls e pilot fla me
present
Pilot va lve stu ck in open p o s ition Re place g a s contro l
O
bserve the green LED on the water heater gas con­trol. Error codes are displayed with a 3 second pause before repeating. Once the error code is known, check and repair the water heater, as recommended in the table below.
Troubleshooting
Green LED
17
Page 18
Page 18
L
ED S tatus Control S tatus P robable Cause Service P rocedure
Six flas h e s,
one flash,
three second
pause (Soft
Lockout)
Failed to lig ht pilot,
system resets after
(5) min u tes
1. Unstable pilot
2. Pilot tube block or restricted
3. O xid a tion b uild-up o n pilot electrode
4. Wire damage to pilot
assembly or bad connection at
gas valve
1. See Burner Inspection on page 20 2-4. See Pilot Inspection, Testing and Replacement on page 22
S
ix flas h e s ,
two flashes,
three second
pause (Soft
Lockout)
Pressure switch or
b
lower temperature
s
witch opened
during burner
operation. System
resets after (5)
minutes
1. Vent blockage or improper vent configuration
2. Pressure switch tubing kinked or blocked
3. Faulty pressure switch
4. Vent termination being a
ffecte d by w in d
5. Blower not spinning up to speed
6. Blower temperature or exhaust temperature too high
7. Faulty blower temperature switch
1. Check vent o r ve nt tables 2-3. See Pressure Switch Testing on page 25 4
. Refer to venting section
of ins tallatio n manu a l
5. See Blower Testing on page 28 6-7. See Blower Tempe ra ture Sw itch Testing on page 31
Six flas h e s,
three
flashes,
three second
pause (Soft
Lockout)
Pilot flame
extinguished,
system auto resets
after (5) minutes
1. Unstable pilot
2. Pilot tube block or restricted
3. O xid a tion b uild-up o n p ilo t electrode
4. Wire damage to pilot assembly or bad connection at gas control
5. Insufficient combustion air
6. Insufficient
gasp
ress ure
1. See Burner Inspection on page 20 2-4. See Pilot Inspection, Testing and Replacement on page 22
5. Refer to Installation & Operation Manual
Six flas h e s,
four flashes,
three second
pause
Undesired false
pilot flame sensed,
system auto resets
Pilot va lve stu ck in o p e n positio n Re pla ce ga s co n trol
Seven
flashes,
three second
pause
Flammable vapor
sensor or
resettable thermal
switch fault
detected, see
warning label
1. Flammable vapor present
2. Flammable vapor sensor exposed to excessive moisture
3. Flammable vapor sensor exposed to extreme ambient temperature
4. Resettable thermal switch o
p
en
See Flammable Vapor Sensor Testing on page 40
Eight
flashes, one
flash, three
second
pause
Flammable vapor
sensor out of
spe cification,
possible short
1. Flammable vapor sensor out of spe cification; ve rify Fla mmab le Vapo r Se nsor (FVS) re s ista nce is not below 25 k
.
2. P o s s ib le s h o rt in fla mmable vapor sensor or resettable thermal switch wirin
g
See Flammable Vapor Sensor Testing on page 40
Troubleshooting
18
Page 19
Page 19
L
ED Status Control Status Probable Cause Service Procedure
Eight flashes, t
hree flashes,
three second
pause
Thermal well sensor
damaged or un­plugged or gas con­t
rol electronics fault
detected
1. Damage to thermal well wires
2. Thermal well sensor resistance out of range
3. Replace thermal well
4. Verify control is not wet or physically damaged
5. Reset control on/off switch
6. Replace gas control if 8-3 error persists
See Thermal Well Testing on page 34
Eight flashes,
f
our flashes,
t
hree second
pause
G
as control fault
detected
1. Verify control is not wet or physically damaged
2. Reset control on/off switch
3. Replace gas control if 8-4 error persists
1. Replace gas control if wet or physically damaged 2
. Cycle power
3. Replace gas control
Troubleshooting
19
Page 20
Page 20
Burner Inspection
At periodic intervals (every 6 months), a visual inspection should be made of the pilot and main burner for proper operation and to assure no debris is accumulating. The pilot flame should be stable. Some causes for an unsta­ble pilot flame are:
a) Gas pressure is out of specification.
b) Pilot flame not fully engulfing spark/flame sensor.
The main burner should light smoothly from the pilot and burn with a blue flame with a minimum of yellow tips. After 5 minutes of operation the burner screen will become radiant and the flame will soften and turn or­ange. If the burner screen does not become radiant after 5 minutes of op­eration it must be cleaned (see burner cleaning procedure below).
Burner Cleaning Procedure
Step 1. Move the gas control power switch to the “OFF” position.
Step 2. Unplug the water heater from the wall outlet.
Step 3. Turn off the gas supply to the water heater.
Step 4. Remove the outer door.
Burner Maintenance
Gas control power
switch
TTW (water heater)
power cord
Outer door
20
Page 21
Page 21
Burner Cleaning Procedure (cont’d)
Step 5. Remove the (4) 1/4” hex drive screws holding the right side inner door in place.
Step 6. Remove the (3) 1/4” hex drive screws holding the left side burner door in place.
Step 7. Disconnect the pilot tube using a 7/16” wrench and the main burner feedline with a 3/4” wrench from the gas control.
Step 8. Disconnect the spark igniter/flame sensor wire from gas control.
Step 9. Remove the burner assembly from the com­bustion chamber.
Step 10. Remove manifold mount from burner inner door by removing (2) 1/4” hex drive screws.
Burner Maintenance
(4) 1/4” hex drive
screws
Pilot and main
feedlines
Spark igniter/flame
sensor wire
Gas control
Burner assembly
Right side
inner door
(3) 1/4” hex drive screws
Left side
burner door
(2) 1/4” hex drive screws
21
Page 22
Page 22
Burner Cleaning Procedure (cont’d)
Step 11. Thoroughly inspect burner screen and burner venturi and remove any loose debris accumu­lation. Inspect burner screen for any openings larger than the normal screen openings.
Step 12. Use compressed air and/or a vacuum to remove any scale or other debris accumulation from the burner screen and venturi.
Step 13. Disconnect (unscrew) manifold mount from feed line. Use a stiff brush, compressed air and/or vac­uum to remove any debris build up from the manifold mount.
Step 14. Remove main burner orifice from feed line (3/8” wrench). Inspect and clean if necessary.
Step 15. Reassemble the burner assembly and reinstall into the water heater. Restore gas supply and check for gas leaks.
Step 16. To resume operation, follow the instructions located on the wa­ter heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
Pilot Inspection, Testing and Replacement
Step 1. Move the gas control power switch to the “OFF” position
Pilot Maintenance
Gas control power
switch
Burner screen
Burner venturi
Manifold mount
Feedline
Main burner orifice
22
Page 23
Page 23
Pilot Inspection, Testing and Replacement (cont’d)
Step 2. Unplug the water heater from the wall outlet.
Step 3. Turn off the gas supply to the water heater.
Step 4. Remove the outer door.
Step 5. Remove the (4) 1/4” hex drive screws holding the right side inner door in place.
Step 6. Disconnect the pilot tube using a 7/16” wrench and the main burner feedline with a 3/4” wrench from the gas control.
Step 7. Disconnect the spark igniter/flame sensor wire from gas control.
Pilot Maintenance
Pilot and main
feedlines
Outer Door
TTW (water heater)
power cord
(4) 1/4” hex drive
screws
Right side
inner door
Spark igniter/flame
sensor wire
Gas control
23
Page 24
Page 24
Pilot Inspection, Testing and Replacement (cont’d)
Step 8. Remove the burner assembly from the com­bustion chamber.
Step 9. Remove the pilot assembly from the main feedline using a 1/4" nut driver.
Step 10. Visually inspect the spark igniter/flame sense wire for damage. Replace the pilot assembly, if damage is found.
Step 11. With a multi-meter set to the ohms setting, check continuity through the spark igniter/flame sense wire. Replace the pilot, if there is no continuity.
Step 12. Visually inspect the spark igniter/flame sense electrode for de­terioration. Replace the pilot assembly, if necessary. The electrode should not be in contact with pilot hood. If it is in contact with the pilot hood, carefully adjust electrode to a gap distance of 3/32" from the pilot hood.
Step 13. Visually inspect the spark igniter/flame sense electrode for oxi­dation build up. Carefully clean any oxidation using very fine emery cloth.
Step 14. Visually inspect the pilot tubing for kinks or cracks. If damage is found, replace the pilot assembly.
Pilot Maintenance
Multi-meter
Burner assembly
Pilot assembly
1/4” nut driver
24
Page 25
Page 25
Pilot Inspection, Testing and Replacement (cont’d)
Step 15. Inspect the pilot tubing and pilot orifice for blockages:
a) Remove ferrule nut from the bottom of the pilot assembly using a 7/16" wrench.
b) Remove the pilot tube and pilot orifice.
c) Inspect the pilot tubing and pilot orifice for blockages. Clean or replace, as neces­sary.
Step 16. Reassemble the pilot assembly and install it on the main burner. Reinstall the burner assembly into the combustion chamber. Re­store the gas supply and check for gas leaks.
Step 17. To resume operation, follow the instructions located on the wa­ter heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
Pressure Switch Testing
Step 1. Move the gas control power switch to the “OFF” position.
Step 2. Remove the three screws (Phillips screw driver) from the con­trol access cover on the blower assembly and remove cover (see photo 1).
Step 3. Carefully remove pres­sure switch from blower housing (see photo 2).
Pressure Switch Testing
Gas control power
switch
WARNING
115 volt potential exposure. Use caution making voltage checks to avoid
personal injury.
1 2
Pressure Switch
25
Page 26
Page 26
Pressure Switch Testing (cont’d)
Pressure Switch Testing
Pressure switch
wire leads
W
ith steps 1,2 & 3
complete, discon-
nect wire leads
from pressure
switch.
Use a multi-meter
set to the ohms
setting. With
blower off, check
across the pres-
sure switch termi-
nals. Are the
switch contacts
open (no electrical
continuity)?
Position the gas
control power
switch to the “ON”
position and adjust
the thermostat to call for heat. This
will start the
blower. Check with
the multi-meter.
Do the pressure
switch contacts
close with the
blower running?
The switch contacts
are OK. See safety
circuit trace (page
40).
Check the tubing and
pressure tap on switch
for blockage. Is there
a blockage?
Check the tub­ing and pressure tap on switch for
blockage. Is
there a block-
age?
Clear blockage
Replace switch (see page 27).
Is the vent
system
blocked?
Is vent system
length within the
vent table specifi-
cations listed on
pages 9 & 10?
Reconfigure vent
system to be
compliant with
vent tables.
See blower
testing (page
28). Is the
Blower OK?
Correct the
blower prob-
lem.
Y
N
N
N
N
N
N
Y
Y
N
Y
Y
Y
26
Page 27
Page 27
Pressure Switch Replacement
Step 1. Move the gas control power switch to the “OFF” position.
Step 2. Remove the three screws (Phillips screw driver) from the control access cover on the blower as­sembly and remove cover.
Step 3. Carefully remove pressure switch from blower housing.
Step 4. Disconnect tubing from the pressure switch.
Pressure Switch Replacement
Gas control power
switch
WARNING
115 volt potential exposure. Use caution making voltage checks to avoid
personal injury.
Control access
cover
Slide pressure switch
in direction of arrow
while tilting slightly
away from blower
housing
Control access
cover
Pressure switch
tubing
27
Page 28
Page 28
Step 5. Disconnect yellow wires from the pres­sure switch.
Step 6. Reconnect wires from step 5 to new pressure switch.
Step 7. Reconnect tubing to new pressure switch.
Step 8. Carefully position pressure switch into blower housing.
Step 9. Position gas control power switch to the “ON” postion and verify proper heater operation.
Step 10. Replace control access cover form step 2.
Blower Testing
Step 1. Move the gas control power switch to the “ON” position and adjust control to call for heat.
Step 2. Remove the three screws (Phillips screw driver) from the control access cover on the blower as­sembly and remove cover.
Blower Testing
Gas control power
switch
Yellow pressure
switch wires
WARNING
115 volt potential exposure. Use caution making voltage checks to avoid
personal injury.
Control access
cover
28
Page 29
Page 29
Blower Testing (cont’d)
Does blower
energize within
2 minutes?
Disconnect pres­sure switch tub-
ing from blower
(see photo 3).
Connect manome-
ter to pressure tap
of blower (see
photo 3).
Disconnect vent
system from top of
blower and remove
vent adapter (see
photo 5).
Does blower
e
nergize after 2 minutes, run for 30 seconds
and shut
down?
Disconnect
cord set in
photo 9. Is
there 115VAC
across termi-
nals shown in
photo 11?
Is there
115VAC at
wall outlet?
Replace blower.
Repair or replace
power cord.
Determine
power source
problem and
correct.
Is there 115VAC
across termi-
nals shown in photo 7?
Incorrect supply voltage polarity.
Reconnect cord set
shown in photo 4.
Is there 115VAC
between blue wire
and ground wire
(see photo 8).
Replace blower.
Does cord set
have electrical
continuity?
Replace cord
set.
Replace gas
control.
See pressure
switch testing
on page 25.
With blower running and
exhaust adapter removed
from top of blower, is there
a negative pressure of –
2.15” to –2.30” W.C.
Blower OK.
Is there 115VAC across blue
and green wires (see photo 8).
Replace blower.
Determine volt-
age problem and
correct.
5
Remove exhaust
adapter
4
3
P
ressure tap.
Pressure
switch tubing
6 7
8
Green ground
wire
Blue wire
Shown with pressure
switch removed
Blower Testing
Y
Y
Y
Y
Y Y
Y
Y
Y
N
Check power cord
for damage.
Y
N
N
N
N
N
N
N
N
N
29
Page 30
Page 30
Blower Removal
Step 1. Move the gas control power switch to the “OFF” position.
Step 2. Unplug the water heater from the wall out­let.
Step 3. Disconnect vent system from exhaust adapter on top of blower.
Step 4. Remove exhaust adapter from blower (blade screw driver) and retain for use on new blower.
Step 5. Remove dilution air clip from air in­take boot and retain for use on new blower.
Step 6. Unplug cord sets from blower.
Step 7. Remove the three blower mounting screws (1/4” nut driver).
Step 8. Remove blower with gasket from water heater.
Blower Installation
Step 9. Clean any debris from jacket head of water heater
Step 10. Set new blower with gasket in place using locating pins on blower flange to line up with location holes in jacket head. Be sure not to damage gasket.
Gas control power
switch
TTW (water heater)
power cord
Blower cord
sets
Blower mount-
ing screws
Remove exhaust
adapter and retain
for use on new
blower
Remove dilution air
clip and retain for
use on new blower
Locating pins on
blower flange
Pin location holes
in jacket head
Blower Replacement
30
Page 31
Page 31
Blower Installation (cont’d)
Step 11. Secure blower in place using mounting screws from step 7.
Step 12. Reinstall exhaust adapter from step 4.
Step 13. Reinstall dilution air clip from step 5.
Step 14. Reconnect vent system to exhaust adapter.
Step 15. Reconnect cords from step 6.
Step 16. Position gas control power switch to the “ON” position.
Step 17. Verify proper blower operation.
Blower Temperature Switch Testing
Step 1. Move the gas control power switch to the “OFF” position.
Step 2. Remove the three screws (Phillips screw driver) from control access cover on blower and remove cover.
Step 3. Locate the blower temperature switch.
Gas control power
switch
Control access
cover
Blower temperature
switch location
Air mixing
inlet
WARNING
115 volt potential exposure. Use caution making voltage checks to avoid
personal injury.
Blower Temperature Switch Testing
31
Page 32
Page 32
Blower Temperature Switch Testing (cont’d)
S
witch Setting
Opens on rise @ approximately 165oF
A
uto resets on fall @ approximately 160
o
F
Cool switch to
below 160
o
F
Reconnect wire leads and ob-
serve heater operation. Do
exhaust gas temperatures
rise to or above 170
o
F with
vent connected?
Replace switch (see page 33).
Disconnect wire leads to
switch. Using multi-meter set
to the ohms setting. Is there
continuity between the switch
terminals?
Do switch
contacts
open?
Exhaust
temperature
is too hot.
Do switch con-
tacts open?
Replace switch (see page 33).
Switch OK
Common causes for high
exhaust temperature
1. Vent length is below mini­mum allowable
2. Vent diameter not to speci­fication
3. Restricted dilution air inlet
4. Missing or deteriorated flue baffle
5. Gas pressure is out of specification
N
N
N
N
Y
Y
Y
Y
Blower Temperature Switch Testing
32
Page 33
Page 33
Blower Temperature Switch Replacement
Step 1. Move the gas control power switch to the “OFF” position.
Step 2. Remove the three screws (Phillips screw driver) from the control access cover on the blower as­sembly and remove cover.
Step 3. Locate blower temperature switch.
Step 4. Disconnect red and yellow wire leads from the switch.
Step 5. With an appropriate tool such as side cut­ters, snip the retaining lug from the blower housing to allow removal of temperature switch.
Step 6. Remove switch from blower housing.
Step 7. Install new switch. Be sure switch is prop­erly seated in mounting area.
Step 8. Reconnect red and yellow wires to new switch. Wires are inter­changeable with either terminal.
Step 9. Position the gas control power switch to the “ON” position and verify proper heater operation.
Step 10. Replace control access cover from step 2.
WARNING
115 volt potential exposure. Use caution making voltage checks to avoid
personal injury.
Gas control power
switch
Control access
cover
Blower temperature
switch location
Snip retaining lug from
blower housing
Blower Temperature Switch Replacement
33
Page 34
Page 34
Thermal Well Testing
Follow the procedure, below, if the water heater gas control has gone into a ECO lock­out (4 flash, 3 second pause). Reset the gas control by rotating the setpoint knob to the minimum setting for at least 6 seconds before returning to the desired water tem­perature setting.
Step 1. Unplug the thermal well connector from the gas control.
Step 2. With a multi-meter set to the ohms setting, meas­ure the resistance between the middle and right side wires.
Step 3. With a multi-meter set to the ohms setting, meas­ure the resistance between the middle and left side wires.
Thermal Well Testing
CAUTION
Do not use standard multi-meter probes for this testing. Doing so will damage the connector. Use special pin type e
lectronic probes or small diameter wire pins inserted into connector.
Thermal well connector
34
Page 35
Page 35
Thermal Well Testing (cont’d)
Determine the correct resistance values using the Determine the Water Temperature Inside the Tank procedure on page 23. If the values are correct, replace the gas con­trol, otherwise replace the thermal well.
Determine Water Temperature Inside Tank
Note: It is important to understand once the resistance for the thermal well is deter­mined using the Thermal Well Testing Procedure on page 21, water flow through the water heater should not occur. Prior to performing the steps below, turn off the cold water supply to the water heater. This will prevent cold water flow into the tank affect­ing the resistance value of thermal well.
Step 1. Move the gas control power switch to the “OFF” position.
Step 2. Draw approximately 4 gallons of water from the drain valve into a con­tainer and discard. Draw an additional gallon and immediately measure the water tem­perature using an accurate thermometer. It may be necessary to open a hot water fau­cet to allow heater to drain.
Step 3. Using the chart on page 23, determine the correct resistance value for the water temperature from Step 2.
Example: If temperature of water is 84°F, then the resistance through the sensor would be 8449 (see shaded area). NOTE: Sensor resistance increases as the tem­perature falls.
Determine Tank Temperature
WARNING
Stored water may be HOT when performing the following steps in this procedure. Take necessary precaution to pre­vent personal injury.
Gas control power
switch
35
Page 36
Page 36
Sensor Resistance at Various Temperatures
Gas Control & Thermal Well Removal From Water Heater
Step 1. Move the gas control power switch to the “OFF” po­sition.
Step 2. Unplug the water heater from the wall outlet.
Step 3. Drain the water heater to a point below the gas control level.
Step 4. Turn off the gas supply to the water heater and disconnect the gas piping from the gas control.
Component Disassembly
°F012345678 9 40 26109 25400 24712 24045 23399 22771 22163 21573 21000 20445 50 19906 19383 18876 18383 17905 17440 16990 16553 16128 15715 60 15314 14925 14548 14180 13823 13477 13140 12812 12494 12185 70 11884 11592 11308 11032 10763 10502 10248 10000 9760 9526 8
0 9299 9078 8862 8653 8449 8250 8057 7869 7685 7507
90 7333 7165 7000 6839 6683 6531 6383 6238 6098 5961
100 5827 5697 5570 5446 5326 5208 5094 4982 4873 4767 110 4663 4562 4464 4368 4274 4183 4094 4006 3922 3839 120 3758 3679 3602 3527 3453 3382 3312 3244 3177 3112 130 3048 2986 2925 2866 2808 2752 2697 2643 2590 2538 140 2488 2439 2391 2344 2298 2253 2209 2166 2124 2083 150 2043 2004 1966 1928 1891 1856 1820 1786 1753 1720 160 1688 1656 1625 1595 1566 1537 1509 1481 1454 1427 170 1402 1376 1351 1327 1303 1280 1257 1235 1213 1191 180 1170 1150 1129 1110 1090 1071 1053 1035 1017 999 190 982 965 949 933 917 901 886 871 857 842 200 828 814 801 788 775 762 749 737 725 713
I
n Degrees F
Gas control power
switch
TTW (water heater)
power cord
36
Page 37
Page 37
Gas Control & Thermal Well Removal From Water Heater (cont’d)
Step 4. Disconnect the pilot tube using a 7/16” wrench and the main burner feedline with a 3/4” wrench from the gas control.
Step 5. Disconnect the wire harnesses and spark igniter/ flame sense wire from the gas control.
Step 6. Remove the gas control & thermal well by rotating the flats of the Thermal Well counter clockwise using a 1-5/16” wrench.
Gas Control Removal From Thermal Well
Following the steps below allows for the removal of the gas control from the thermal well without removing the thermal well from the tank.
Step 1. Move the gas control power switch to the “OFF” position.
Step 2. Unplug the water heater from the wall outlet.
Gas Control Removal
Pilot and main
feedlines
Spark igniter/flame
sensor wire
Gas control
Flats of thermal
well
Gas control power
switch
TTW (water heater)
power cord
37
Page 38
Page 38
Gas Control Removal From Thermal Well (cont’d)
Step 3. Turn off the gas supply to the water heater and disconnect the gas piping from the gas control.
Step 4. Disconnect the pilot tube using a 7/16” wrench and the main burner feedline with a 3/4” wrench from the gas control.
Step 5. Disconnect the wire harnesses and spark igniter/ flame sense wire from the gas control.
Step 6. Using the gas control service tool, p/n 239-45991­00, available from your BWC parts supplier, insert the tool into the back of the gas control.
Step 7. Pivot the tool towards the water heater, as far as possible. Lift straight up on the gas control. The gas control should move about 1/8". Hold the gas control in position and remove the tool. Lift straight up on the gas control to remove it completely from the thermal well.
Gas Control Assembly to the Thermal Well
Step 1. Install the threaded end of the thermal well into the tank. Be sure the thermal well flange is positioned properly to allow for proper gas control installation. Tighten the thermal well using a 1-5/16” wrench.
Gas Control Assembly
P
ilot and main
feedlines
Spark igniter/flame
sensor wire
Gas control
Gas control service
tool
38
Page 39
Page 39
Gas Control Assembly to the Thermal Well (cont’d)
Step 2. Route the wire leads back into relief opening.
Step 3. Align the slots located on the thermal well flange with the tabs located on the back of the gas control.
Step 4. Carefully push the gas control back onto the thermal well flange as far as possible towards the water heater. Then, slide the gas control down to lock into posi­tion.
Step 5. Install the burner assembly and connect the pilot and main feedlines to the gas control using a 7/16” and 3/4” wrench, respectively.
Step 6. Reconnect the wire harnesses to the gas control.
Step 7. Reconnect the gas piping to the gas control. Re­store the gas supply and check for gas leaks.
Gas Control Assembly
Wire leads on
thermal well
Relief opening
Slots in thermal well
Tabs on back of gas
control
Pilot and main
feedlines
Wire harnesses
39
Page 40
Page 40
Gas Control Assembly to the Thermal Well (cont’d)
Step 8. To resume operation, follow the instructions located on the water heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
Flammable Vapor Sensor Testing
Step 1. Move the gas control power switch to the “OFF” position.
Step 2. Disconnect the flammable vapor sensor harness from the gas control.
Step 3. Using a multi-meter set to the ohms setting, measure the resistance of the flammable vapor sensor and resettable ther­mal switch. The resistance must be between 3,000 and 48,000 ohms. If the resistance is out of this range, verify that the re­settable thermal switch has not been tripped. If it hasn’t, replace the thermal switch.
115 VAC Circuit Trace
Step 1. Verify 115VAC and proper polarity are at the wall outlet.
Step 2. With the water heater plugged in and the gas control power switch in the “ON” position verify LED status.
Flammable Vapor Sensor Testing
CAUTION
Do not use standard multi-meter probes for this testing. Doing so will damage the connector. Use special pin type electronic probes or small diameter wire pins inserted into connector.
Gas control power
switch
Flammable vapor
sensor harness
Flammable vapor
sensor harness
40
Page 41
Page 41
115 VAC Circuit Trace
WARNING
115 volt potential exposure. Use caution making voltage checks to avoid
personal injury.
LED status:
N
one, control
LED not on or
flashing.
LED status:
S
hort flash
once every four
seconds.
LED status:
Heartbeat”,
alternates
bright/dim.
LED status:
V
arious flash-
ing error codes.
Waiting for call
for heat.
Thermostat call-
ing for heat.
Verify error
code as listed
on page 17.
Disconnect cord
set as shown in
photo 9.
Using a volt meter
set to volts AC, is
there 115VAC across
terminals shown in
photo 10?
Check for damage
to AC supply
power cord.
Repair damage.
Replace blower.
Is there 115VAC across terminals
shown in photo 11?
Incorrect supply voltage polarity.
Reconnect cord set
shown in photo 9.
Disconnect wire har-
ness from gas control
(see photo 12).
Locate black & white wires at connector, it
may be necessary to pull back wire sheath to
identify wire colors (see photo 13).
Is there 115VAC across
black & white wire as
shown in photo 13?
Call for technical support.
Replace gas control.
N
N
N
Y
N
Y
N
Y
Wire harness
Check for 115VAC between black and white wires.
-NOTE-
Electronic meter probes required. Use car not to
damage connector during this check.
Wire sheath pulled back to
identify wire colors
9
11
12
13
10
41
Page 42
Page 42
Safety Circuit Voltage Trace
Note: This procedure assumes a cold tank.
Step 1. Remove three screws (Phillips screw driver) from control access cover on blower and remove
cover.
Safety Circuit Voltage Trace
WARNING
115 volt potential exposure. Use caution making voltage checks to avoid
personal injury.
Control access
cover
Position gas control switch to the “ON”
position and adjust the thermostat dial
to call for heat. Is there 10 to 13VAC
between the red wire leading to the
blower temperature switch and the
green ground wire? Blower must be
running during this voltage check (see
photo 15).
Is LED on gas valve flash-
ing the “heartbeat” code
(alternating bright/dim)?
No voltage from gas control.
Call for technical support.
Verify 115VAC to gas con-
trol (see page 41).
Is there 10 to 13VAC between
the yellow wire leading from the
pressure switch and the green
ground wire (see photo 27)?
Is there continuity through
the blower temperature
switch (see page 31)?
Check for loose or broken wire connection at switch
terminals.
Do you hear or can you
see the igniter sparking?
Check igniter/sensor (see page
22). Is igniter/sensor OK?
Correct igniter/
sensor problem
Determine cause of blower temperature switch activa-
tion and correct.
Faulty cord set
or gas control
Safety circuit
voltage is OK.
If burner does not light, ob-
serve LED flash code on gas
control and refer to trouble-
shooting section on page 17.
Green ground wire
Red sire leading to
blower temp. switch
Yellow wire leading
from pressure switch
15
14
N
N
Y
Y
N
Y
N
Y
N Y
Y
42
Page 43
Page 43
Remove the Blower to Gain Access to the Flue Baffle
Step 1. Move the gas control p ow e r switch to the “OFF” position.
Step 2. Unplug the water heater from the wall outlet.
Step 3. Disconnect the vent system from the exhaust adapter on top of blower.
Step 4. Unplug the cord sets from the blower.
Step 5. Remove the three blower mounting screws (1/4” nut driver).
Step 6. Remove the blower with gasket from the top of the water heater.
Step 7. Remove the flue baffle from the
Blower Removal
G
as control power
switch
TTW (water heater)
power cord
Exhaust adapter
Blower mounting
screws
Blower cord sets
Flue baffle
43
Page 44
Page 44
water heater.
Remove the Blower to Gain Access to the Flue Baffle (cont’d)
Step 8. Inspect the baffle for deterioration and missing restrictors. Clean any scale or debris build-up. Replace with a new baffle, as necessary.
Step 9. Reinstall the baffle into the flue. Be sure the baffle hanger tab is inserted into the notch locations at the top of the flue.
Step 10. Check the burner to ensure no scale has accumulated during operation. See the Burner Cleaning Procedure on page 20, if accumulation has occurred.
Step 11. Secure the blower in place using the screws from Step 5.
Step 12. Reconnect the vent system to the exhaust adapter.
Step 13. Reconnect the cord sets from Step 4.
Step 14. Plug the water heater into the wall outlet.
Step 15. To resume operation, follow the instructions located on the water heater
lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
Dip Tube Inspection and Replacement
Step 1. Move the gas control power switch to the “OFF” position
Step 2. Unplug the water heater from the wall outlet.
Step 3. Turn off the cold water supply to the water heater. Connect a hose to the drain valve of the water heater and route to an open drain. Open a nearby hot water faucet to vent the water heater for draining. Open the drain valve of water heater and allow the water heater to drain to a point below the inlet connection nipple.
Step 4. Disconnect the inlet nipple from the plumbing system.
Step 5. With an appropriate tool, such as a pipe wrench, remove the inlet nipple/ diptube from the water heater. Use caution not to damage pipe threads.
Step 6. Visually inspect the inlet nipple/diptube. The inlet nipple/diptube should
Dip Tube Inspection
WARNING
Water heater components and stored water may be HOT when performing the following steps in this procedure. Take necessary precaution to prevent personal injury.
44
Page 45
Page 45
be free of cracks and any blockage. Hydro-jet slots should be open and free of any blockage. Any damage, such as cracks, restriction due to deformation, or uninten­tional holes are not field repairable and the inlet nipple/diptube must be replaced.
Step 7. Upon completion of the inspection or subsequent replacement, reinstall the inlet nipple/diptube into the water heater. Connect the nipple to the plumbing system, resume water supply to the water heater, and refill the water heater.
Step 8. To resume operation, follow the instructions located on the water heater
lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
Anode Inspection and Replacement
Step 1. Move the gas control power switch to the “OFF” position
Step 2. Unplug the water heater from the wall outlet.
Step 3. Turn off the cold water supply to the water heater. Connect a hose to the drain valve of the water heater and route to an open drain. Open a nearby hot water faucet to vent the water heater for draining. Open the drain valve of water heater and allow the water heater to drain to a point below the outlet connection nipple.
Step 4. Disconnect the outlet nipple from the plumbing system.
Step 5. With an appropriate tool, such as a pipe wrench, remove the outlet nip­ple/anode from the water heater. Use caution not to damage the pipe threads.
Step 6. Visually inspect the outlet nipple/anode. The outlet nipple/anode should show signs of depletion, which is normal. If depletion is one-half the original anode diameter (approximately 3/4” diameter), replacement is recommended. If any of the steel core of the anode is exposed, replacement is recommended.
Step 7. Upon completion of the inspection or subsequent replacement, reinstall the outlet nipple/anode into the water heater. Connect the nipple to the plumbing system, resume water supply to the water heater, and refill the water heater.
Anode Inspection
WARNING
Water heater components and stored water may be HOT when performing the following steps in this procedure. Take necessary precaution to prevent personal injury.
45
Page 46
Page 46
Step 8. To resume operation, follow the instructions located on the water heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
Inner Door Removal Procedure
Step 1. Move the gas control power switch to the “OFF” po­sition.
Step 2. Unplug the water heater from the wall outlet.
Step 3. Remove the outer door.
Step 4. Remove (4) 1/4” hex drive screws from the right side inner door.
Step 5. Remove (3) 1/4” drive screws from the left side burner door.
Inner Door Removal
G
as control power
switch
Blower (water
heater) power cord
Connectors attached to
resettable thermal switch
Outer door
(3) 1/4” hex drive screws
(4) 1/4” hex drive
screws
Right side
inner door
46
Page 47
Page 47
Step 6. Remove the connectors attached to the re­settable thermal switch on the manifold mount.
Inner Door Removal Procedure (cont’d)
Step 7. Remove the flammable vapor sensor from the clip by pushing down on the tab to open the clip.
Step 8. Inspect both inner doors for any of the following imperfections: tears, missing material, cracks, dirt or debris, lack of adhesion to the inner door, material left
on combustion chamber, or any other imperfections that will inhibit a proper seal.
If any of the imperfections above are present, replace the inner door gasket following the Inner Door Gasket Replacement Procedure. If not, replacement of the inner door gaskets is not necessary.
Inner Door Gasket Replacement Procedure
Step 1. Completely remove all gasket and adhesive residue from the right and left side inner doors, as needed.
Step 2. U s i n g
RTV sealant, apply a 1/8” bead to secure
the
Inner Door Gasket Replacement
Flammable vapor
sensor
Flammable vapor
sensor clip
WARNING
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death.
Recommended pattern for RTV sealant
Expanded view Slice gasket here to slide over burner venturi
Gasket overlap must be
as shown ± 1/32
Enlarged
view of
flange
area
Gasket overlap must be
as shown ± 1/32
47
Page 48
Page 48
inner door gasket to the inner door sections. Refer to the illustration for proper applica-
tion. Note the overlap configuration in the flange area of the inner door. Set the flange section first, and this will help to achieve the proper overlap position.
Inner Door Installation with Gasket
Step 1. Clean any residual gasket residue or other debris from the combustion chamber surface before installing the inner door/gasket assembly.
Step 2. Place the left side inner door into position first, being sure to firmly posi­tion the concave channel of the inner door around the feedline.
Step 3. Using the 1/4” hex drive screws removed in Step 5 of the Inner Door Re­moval Procedure on page 32, secure the left side inner door in place. Do not over­tighten the screws.
Step 3. Position the pilot tube and spark igniter wire against the left side inner door flange gasket. Do not route these through the concave channel with the feedline.
Step 4. Firmly place the right side inner door flange against the left side inner door flange.
Step 5. Using the 1/4” hex drive screws removed in Step 4 of the Inner Door Re­moval Procedure on page 32, secure the two flanges together. Do not over-tighten the screws.
Step 6. Align the right side inner door to the combustion chamber and verify the fastener holes of the combustion chamber are aligned with the right side inner door slotted openings. Verify seal integrity around the combustion chamber opening.
Step 7. Using the 1/4” hex drive screws removed in Step 3 of the Inner Door Re­moval Procedure on page 32, secure the right side inner door. Do not over-tighten the
Inner Door Installation
WARNING
Stripped fastener connections may allow for an inner door seal breach. A seal breach may result in a fire or explosion, causing property damage, personal injury, or death. Do not over tighten screws. If a fastener connection is stripped, contact the manufacturer listed on the water heater rating plate.
48
Page 49
Page 49
screws. Verify that both the left and right side inner doors are properly positioned and sealed against the combustion chamber.
Step 8. Re-install the outer door.
Step 9. To resume operation, follow the instructions located on the water heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
ScreenLok
®
Flame Arrestor Cleaning Procedure
Step 1. Move the gas control power switch to the “OFF” position and unplug the water heater from the wall outlet.
Step 2. Remove the outer door.
Step 3. Remove the right side inner door per the Inner Door Removal Procedure on page 32.
Step 4. Disconnect the pilot tube using a 7/16” wrench and the main burner feedline with a 3/4” wrench from the gas control.
Step 5. Disconnect the spark igniter/flame sensor wire from gas control.
Step 6. Remove the burner assembly from the combustion chamber.
Step 7. Clean the ScreenLok® flame arrestor using a stiff brush, compressed air, and/or a shop vacuum to remove any scale or other debris accumulation. Using a soft brush, clear jacket openings from any dirt, dust, restrictions, or other obstructions.
Step 8. Remove any debris from the burner assembly following the Burner Cleaning Procedure on page 15.
Step 9. Re-install the burner assembly.
Step 10. Reconnect the main and pilot tubing and spark igniter wire to the gas control.
Step 11. Re-install the inner door per the Inner Door Installation with Gasket Pro­cedure on page 34.
Step 12. To resume operation, follow the instructions located on the water heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
Arrestor Cleaning
49
Page 50
Page 50
Common Terms
BTU British Thermal Units
ECO Energy Cut Off
GPM Gallons per Minute
Hz Hertz
KWh Kilowatts per hour
LED Light Emitting Diode
NPT National Pipe Thread
Ohms Ohms of resistance
PSI Pounds per Square Inch
RPM Revolutions per Minute
VAC Volts Alternating Current
W.C. Inches of Water Column
°C Degrees Centigrade
°F Degrees Fahrenheit
NOTES
____________________________________________________________
____________________________________________________________
____________________________________________________________
Common Terms
50
Page 51
Page 51
Parts List
3
3
32
3
0
39
34
3
5
36
29
18
3
1
2
1
20
1
2
3
4
5
12
1
3
9
10
1
1
1
4
1
5
1
9
2
2
2
3
2
7
28
7
25
24
6
26
16
1
7
29
1
8
1
8
18
18
40
37
38
Part Name and Description
1. Blower Complete 15. T&P Valve 29. Burner Assembly
2. Air Mixing Inlet 16. Outer Door 30. Flexible Gas Feedline
3. Pressure Switch 17. Right Side Inner Door 31. Thermal Switch
4. Blower Temperature Switch 18. Screw #10-12 x 3/4” 32. Screw #8-18 x 1/2”
5. Blower Gasket 19. Brass Drain Valve 33. Burner
6. Blower Power Cord 20. Flammable Vapor Sensor Clip 34. Pilot Assembly
7. Vent Adapter w/ Vent Term. 21. Flammable Vapor Sensor 35. Screw #8-18 x 1/2”
8. Condensate Hose Kit 22. Flammable Vapor Sensor Harness 36. Pilot Orifice
9. Heat Trap Outlet 23. Thermowell 37. Manifold Mount
10. Hot Water Outlet Anode 24. Gas Control 38. FVIR Sensor Plate
11. Flue Baffle 25. Gas Control Service Tool 39. Orifice
12. Heat Trap Inlet 26. 3/4” NPT Pipe Plug 40. Dilution Air Clip
13. Inlet Dip Tube 27. ASSE Approved Mixing Valve
14. Wire Harness 28. Kit—Heat Trap Insert
51
Page 52
Email
parts@bradfordwhite.com
techserv@bradfordwhite.com
www.bradfordwhite.com
Loading...