A Spanish language version of these instructions is available by contacting
the company listed on the rating plate.
La version espanola de estas instrucciones se puede obtener al escribirle
a la fabrica cuyo nombre aparece en la placa de especificaciones.
INSTALLATION AND OPERATING
INSTRUCTION MANUAL
WARNING: If the information in these instructions is not
followed exactly, a fire or explosion may result causing
property damage, personal injury or death.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable,
combustible, or corrosive vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
For your family’s comfort, safety and convenience we
recommend water heaters to be installed and serviced by a
plumbing professional.
238-42956-00E REV 03/07
CONGRATULATIONS!
You have just purchased one of the finest water heaters
on the market today!
This installation, operation and instruction manual will
explain in detail the installation and maintenance of your
new Powered Direct Vent Series Gas-Fired Water Heater.
We strongly recommend that you contact a plumbing
professional for the installation of this water heater.
We require that you carefully read this manual, as well as
the enclosed warranty, and refer to it when questions
arise. If you have any specific questions concerning
your warranty, please consult the plumbing professional
from whom your water heater was purchased. For your
records we recommend that you write the model, serial
number and installation date of your water heater in the
maintenance section in the back of this manual.
This manual should be kept with the water heater.
2
TABLE OF CONTENTS
page
GENERAL INFORMATION ............................................................ 4
This gas-fired water heater’s design is certified by CSA International under the
American National Standard Z21.10.1 - (as indicated on the rating plate) and
CSA 4.1-M - (as indicated on the rating plate).
This water heater must be installed in accordance with local codes or, in the
absence of local codes, the National Fuel Gas Code, ANSI Z223.1-Latest
Edition) and/or in Canada CAN/CGA B149 Installation Codes (Latest Editions).
The warranty for this water heater is in effect only when the water heater is
installed, adjusted, and operated in accordance with these Installation and
Operating Instructions. The manufacturer will not be held liable for any damage
resulting from alteration and/or failure to comply with these instructions.
This water heater is not design certified for installation in a mobile home. Such
an installation may create a hazardous condition and will nullify the warranty.
CAUTION
Incorrect operation of this appliance may create a hazard to life and
property and will nullify the warranty.
Do not use this appliance if any part has been submerged in water. You should
contact a qualified service technician to inspect the appliance and to replace
any part of the control system including the combination gas control which has
been submerged in water.
DANGER
Do not store or use gasoline or other flammable, combustible, or
corrosive vapors and liquids in the vicinity of this or any other
appliance.
IMPORTANT
Before proceeding, please inspect the water heater and its components for
possible damage. DO NOT install any damaged components. If damage is
evident then please contact the supplier where the water heater was
purchased or the manufacturer listed on the rating plate for replacement
parts.
Make sure that you check the rating plate and combination gas control on the
water heater to be certain that the type of gas being supplied corresponds with
the marking on the rating plate and combination gas control.
4
General Information continued-
A sacrificial anode is used to extend tank life. The removal of this anode, for
any reason, will nullify the warranty. In areas where water is unusually active,
an odor may occur at the hot water faucet due to a reaction between the
sacrificial anode and the impurities in the water. If this should happen, an
alternative anode may be purchased from the supplier that installed this water
heater. This will minimize the odor while protecting the tank. Additionally, the
water heater should be flushed with appropriate dissolvers to eliminate any
bacteria.
INSTALLATION
Locating The Water Heater
WARNING
Water heaters are heat producing appliances. To avoid damage or injury, do
not store materials against the water heater or vent-air intake system. Use
proper care to avoid unnecessary contact (especially by children) with the
water heater and vent-air intake components. UNDER NO CIRCUMSTANCES
SHALL FLAMMABLE MATERIALS, SUCH AS GASOLINE OR PAINT
THINNER BE USED OR STORED IN THE VICINITY OF THIS WATER
HEATER, VENT-AIR INTAKE SYSTEM OR IN ANY LOCATION FROM
WHICH FUMES COULD REACH THE WATER HEATER OR VENT-AIR
INTAKE SYSTEM.
This water heater MUST be installed indoors out of the wind and weather.
DO NOT install the water heater in any location where gasoline or
flammable vapors are likely to be present.
CAUTION
The National Fuel Gas Code (ANSI Z233.1-or latest edition) and CAN/CGA
(B149.1-or latest edition), expressly prohibits the installation of a water
heater in a garage, unless the unit is installed so that the burner and
ignition devices are at least eighteen (18) inches (46 cm) above floor level
and protected to avoid damage by a moving vehicle.
The location of this water heater is of the utmost importance. Before installing
this water heater, read the installation section of these instructions. After
reading these installation and operating instructions, select a location for the
water heater where the floor is level and is easily accessible to gas and water
supply lines. DO NOT locate the water heater where water lines could be
subjected to freezing temperatures. Make sure the cold water pipes are
not located directly above the gas control so that condensate during
humid weather does not drip on the controls.
5
Installation (Locating The Water Heater) continued-
Water heater corrosion and component failure can be caused by the heating
and breakdown of airborne chemical vapors. Examples of some typical
compounds that are potentially corrosive are: spray can propellants, cleaning
solvents, refrigerator and air conditioning refrigerants, swimming pool
chemicals, calcium and sodium chloride, waxes and process chemicals. These
materials are corrosive at very low concentration levels with little or no odor to
reveal their presence. NOTE: DAMAGE TO THE WATER HEATER CAUSED
BY EXPOSURE TO CORROSIVE VAPORS IS NOT COVERED BY THE
WARRANTY. DO NOT OPERATE THE WATER HEATER IF EXPOSURE
HAS OR WILL OCCUR. DO NOT STORE ANY POTENTIALLY CORROSIVE
COMPOUNDS IN THE VICINITY OF THE WATER HEATER.
WARNING
Liquefied petroleum gases/propane gas are heavier than air and
will remain at floor level if there is a leak. Basements, crawl
spaces, closets and areas below ground level will serve as
pockets for accumulation of leaking gas. Before lighting, smell
all around the appliance area for gas. Be sure to smell next to
the floor.
IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electric switch; do not use any telephone in
your building.
Immediately call your gas supplier from a neighbor’s
telephone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire
department.
DO NOT OPERATE APPLIANCE UNTIL THE LEAKAGE IS
CORRECTED!
6
Installation (Locating The Water Heater) continued-
WARNING
DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU ARE NOT
CERTAIN OF THE FOLLOWING:
Liquefied petroleum gases/propane gas and natural gas have an
odorant added by the gas supplier that aids in the detection of the
gas.
Most people recognize this odor as a “sulfur” or “rotten egg” smell.
Other conditions, such as “odorant fade” can cause the odorant to
diminish in intensity, or ”fade”, and not be as readily detectable.
If you have a diminished sense of smell, or are in any way unsure of
the presence of gas, immediately contact your gas supplier from a
neighbor’s telephone.
Gas detectors are available. Contact your gas supplier, or plumbing
professional, for more information.
The water heater must be located close enough to the outside wall to keep the
venting distance within the maximum distance described in the installation
instructions. Read the venting section in this installation instruction manual
before locating the water heater.
This water heater must be located in an area where leakage of the tank or
water line connections and the combination temperature and pressure relief
valve will not result in damage to the area adjacent to the water heater or to
lower floors of the structure. When such locations cannot be avoided, a suitable
drain pan adequately piped for proper drainage, must be installed under the
water heater. The pan must not restrict combustion airflow. The drain pan
must have a minimum length and width of at least 4 in. (10.2 cm) greater than
the diameter of the water heater and must not restrict proper combustion air
flow to the water heater. The drain pan, as described above, can be purchased
from your plumbing professional. The drain pan must be piped to an adequate
drain. The piping must be at least 3/4 inch (1.9 cm) in diameter and pitched for
proper drainage.
It is recommended that a minimum clearance of four (4) inches (10.2 cm) be
provided on the side of the water heater for servicing and maintenance of the
combination temperature and pressure relief valve.
Note: For California installation this water heater must be braced,
anchored, or strapped to avoid falling or moving during an earthquake.
See instructions for correct installation procedures. Instructions may be
obtained from California Office of the State Architect, 400 P Street,
Sacramento, CA 95814.
7
Installation (Minimum Clearances) continued-
Minimum Clearances
WARNING
Failure to adhere to these installation and operating instructions may
create a hazard to life and property and will nullify the warranty.
This installation must allow access to the front of the water heater and
adequate clearance must be provided for servicing and operating this water
heater. The water heater may be installed on either a combustible or noncombustible floor. If the water heater is to be installed directly on carpeting, it
must be installed on top of a metal or wood panel extending beyond the full
width and depth of the appliance by at least three (3) inches (7.6 cm) in any
direction or, if the appliance is to be installed in an alcove or closet, the entire
floor must be covered by the panel. The minimum clearances to combustibles
for this water heater is: zero (0) inches (0 cm) from the sides and rear, five (5)
inches (12.7 cm) from the front of the jacket, zero (0) inches (0 cm) from the
vent connector and fifteen (15) inches (38.1 cm) from the jacket top.
Venting
Canadian
A= Clearance above grade, veranda,
porch, deck or balcony
B= Clearance to widow or door that may
be opened
C= Clearance to permanently closed
widow
D= Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (61 cm)
from the center line of the terminal
E= Clearance to unventilated soffit 12 inches (30
F= Clearance to outside corner *b *b
G= Clearance to inside corner *b *b
Direct Vent Terminal Clearances
Installations
12 inches (30
12 inches (30
12 inches (30
1
cm)
cm)
*b *b
cm) *a
cm) *a
8
Figure 1
US Installations
12 inches
(30 cm)
12 inches (30 cm)
12 inches (30
cm) *a
12 inches (30
cm) *a
2
Venting continued-
Canadian
H= Clearance to each side of center line
extended above meter/regulator
assembly
I= Clearance to service regulator vent
outlet or oil tank vent
J= Clearance to non-mechanical air
supply inlet to building or the
combustion air inlet to any other
appliance
K= Clearance to a mechanical air supply
inlet
L= Clearance above paved sidewalk or
paved driveway located on public
property
M= Clearance under a veranda, porch,
1
2
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single‡ Permitted only if a veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the
floor.
*a) A minimum clearance value determined by testing in accordance with section 2.20.
*b) “Clearance in accordance with local installation codes and the requirements of the gas supplier”.
deck, or balcony
In accordance with the current CAN/CGA-B149 Installation Codes.
In accordance with the current ANSI Z223.1-(Latest edition)/NFPA 54 National Fuel Gas Code.
family dwellings and serves both dwellings.
Installations
3 feet (91 cm)
within a height
15 feet (4.6 m)
above the
meter/regulator
assembly
36 inches
(91 cm)
12 inches
(30 cm)
6 feet
(1.83 m)
7 feet
(2.13 m)†
12 inches (30
cm) ‡
US Installations
1
3 feet (91 cm) above if
within 10 feet
12 inches
(30 cm)
horizontally
2
*b
*b
*b
*b
The vent system must terminate so that proper clearances are maintained as
cited in local codes or the latest edition of the National Fuel Gas Code, ANSI
Z223.1.73.4e and 7.8a, b as follows:
1. Do not terminate near soffit vents or crawl space or other area where
condensate or vapor could create a nuisance or hazard or cause
property damage.
2. Do not terminate the exhaust vent terminal where condensate or
vapor could cause damage or could be detrimental to the operation of
regulators, relief valves, or other equipment.
3. Do not terminate the exhaust vent terminal over public area or
walkways where condensate or vapor can cause nuisance or hazard.
4. The vent shall terminate a minimum of 12 inches above expected
snowfall level to prevent blockage of vent termination.
Vent pipes serving power vented appliances are classified by building codes as
“vent connectors”. Required clearances from combustible materials must be
provided in accordance with information in this manual under LOCATION OF
WATER HEATER and CLEARANCES, and with National Fuel Gas Code and
local codes.
9
Venting continued-
Venting Installation Instructions For Supplied Intake Venting:
1. Refer to Figure 2, “Vent Assembly Illustration” to install intake venting
as described below.
2. Insert one end of the Vertical Pipe into Metal Boot on the lower
backside of the water heater.
3. Slide the Support Bracket over the Vertical Pipe, but do not fasten to the
Jacket Head.
4. Position the Intake Tee on top of the Vertical Pipe so that the short
straight section of the tee faces the Blower Intake Collar, and the curve
of the tee faces upward. Proper orientation of the curved section of
the tee is critical. Be sure it is facing upward. Refer to “This End
Up” label on Intake Tee.
5. Slide the Rubber Intake Elbow over the Blower Intake Collar and over
the short straight section of the Intake Tee.
6. Using a level to ensure that the Vertical Pipe is straight up and down,
secure the Vertical Pipe to the Jacket Head using the Support Bracket
and three (3) self-drilling screws provided. NOTE: Correct vertical positioning of the Vertical Pipe is Important.
7. After securing the Vertical Pipe to the Jacket Head with the Support
Bracket, tighten the clamps on the Rubber Intake Elbow.
8. Using the RTV sealant provided, place a bead of RTV around the
Vertical Pipe at the Metal Boot location, and at the Intake Tee location.
Smooth out the RTV to provide a seal at both locations.
9. Two 90° end terminal elbows are supplied. These must be installed at
the extreme ends of the intake and exhaust venting outside the building.
The end terminal with the external screen must be installed on the
intake vent as shown in Figure 8.
10. Proceed as necessary to complete the venting installation as described
in the venting section of this
manual.
10
Venting continued-
Figure 2
Vent Assembly Illustration
11
Venting continued-
NOTICE
For installations in Canada, field supplied plastic vent piping must comply
with CAN/CGA B149.1 (latest edition) and be certified to ULC S636. The
supplied vent connector and vent termination are certified as part of the
water heater.
Venting System Condensation
Condensate formation does not occur in all installations of power vented
heaters, but should be protected against on installations where condensation
can form in the venting system.
Formation of condensation in the venting system of Power Vented water
heaters is dependent upon installation conditions including, but not limited to:
ambient temperature and humidity of installation location;
ambient temperature and humidity of venting space;
vent distance and slope;
and product usage.
In order to effectively control condensate from adversely affecting the
mechanical components of the water heater several methods may be
employed:
1. For horizontal installations the vent pipe can be installed with a
downward slope (not less than 1/8" nor greater than ½” per foot
maximum) and away from the blower motor.
2. In order to prevent condensate from draining back into the blower
(vertical or horizontal runs), a fitting and drain hose is available as a
condensate trap kit (see Table 1 for service part numbers). The tubing
provided is to drain any accumulated condensate away from the water
heater and to a suitable drain. The kit comes complete with instructions
for proper installation of the fitting. If a Bradford White drain kit is not
purchased, the drain hose material must be either flexible PVC or
silicone hose with inside diameters as specified below. Hose clamps
that will ensure a leak proof connection at the drain hose must also be
used. Hose clips will be required to create a 6” diameter loop in the
drain hose routing below the jacket head.
50, 65 and 75 gallon powered direct vent models use 3/8” I.D. flexible
PVC or silicone hose.
Table 1
Model Service Part
3” (7.6 cm) Blower Outlet (exhaust) 239-43870-00
12