TW450S65F (B)*(N,X)
TW465S65F (B)*(N,X)
(*) Denotes Warranty Years
Manual 238-46238A-00B
Page 2
Table of Contents
2
PageTTW Service Procedure
Introduction4- - -
How to use this manual5- - -
Tool required for service5- - -
Specifications6- - -
Control Timings9- - -
Sequence of Operation10- - -
Troubleshooting13- - -
Burner Inspection, Cleaning and Replacement17I
Pilot Testing, Cleaning and Replacement19II
Pressure Switch Testing and Replacement 20III
Blower Testing and Replacement22IV
Blower Temperature Switch Testing and Replacement24V
Gas Control & Thermal well Testing & Replacement26VI
Simulated Resistive Device Testing and Replacement30VII
Safety Circuit Voltage Trace31VIII
115VAC Circuit Trace32IX
Dip Tube inspection and Replacement33X
Anode Inspection and Replacement34XI
Flue Baffle Inspection and Replacement35XII
Glossary of Terms36- - -
Parts List37- - -
Page 2
Page 3
WARNING: If the information in these instructions is
3
not followed exactly, a fire or explosion may result
causing property damage, personal injury, or death.
Incorrect operation of this appliance may
CAUTION
create a hazard to life and property and
will nullify the warranty.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable,
combustible, or corrosive vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor's phone.
Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
WARNING
Water heatersare heat producingappliances. Toavoid
damageor injury, donotstore materialsagainstthe
water heater or vent-air intakesystem. Use proper care
to avoid unnecessary contac
the water heater and vent-air intake components.
UNDER NO CIRCUMSTANCES MUST FLAMMABLE
MATERIALS, SUCH AS GASOLINE OR PAINT THINNER BE
USED OR STORED IN THE VICINITY OF THIS WATER
HEATER, VENT-AIR INTAKE SYSTEM OR IN ANY
LOCATION FROM WHICH FUMES COULD REACH THE
WATER HEATER OR VENT-AIR INTAKE SYSTEM.
t (especially by children) with
CAUTION
If sweat fittings are to be used DO NOT apply heat to the
nipples on top of the water heater. Sweat the tubing to
the adapter before fitting the adapter to the water
connections. It is imperative that heat is not appli
the nipples containing a plastic liner.
ed to
WARNING
Hydrogengas canbe produced in an operating water
heater that hasnot had water drawnfrom thetank for a
long period of time (generally two weeks or more).
Hydrogengas is extr
possibility of injury under these conditions, we
recommend the hot water faucettobeopenfor several
minutes at the kitchensink before you useany electrical
app
liance which is connected to the hot water system. If
hydrogen is present, there will be an unusual sound such
as air escaping through the pipes as hot water begins to
flow. Do not sm
emely flammable. To prevent the
oke or have open flame near the faucet
at the time it is open.
Do not store or use gasoline or other
flammable, combustible, or corrosive
vapors and liquids in the vicinity of this
Before proceeding, please inspectthe
water heater and its componentsfor
possible damage. DO NOT installany
water heater with damaged components.
If damage isevidentthen please contactthesupplie
purchased or the manufacturer listed on
the rating platefor replacement parts.
DANGER
or any other appliance.
IMPORTANT
r where the water heater was
WARNING
DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU
ARE NOT CERTAIN OF THE FOLLOWING:
Liquefied petroleum gases/propane gas and natural gas
have an odorant added by the gas supplier that aids in
the detection of the gas.
Most people recognize this odor as a “sulfur” or “rotten
egg” smell.
Other conditions, such as “odorant fade” can cause the
odorant to diminish in intensity, or ”fade”, and not be
as readily detectable.
If you have a diminished sense of smell, or are in any
way unsure of the presence of gas, immediately contact
your gas supplier from a neighbor's telephone.
Gas detectors are available. Contact your gas supplier, or
plumbing professional, for more information.
WARNING
FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED 3/4” X
3/4” TEMPERATURE AND PRESSURE RELIEF VALVE WILL
RELEASE THE MANUFACTURER FROM ANY CLAIM THAT
MIGHT RESULT FROM EXCESSIVE TEMPERATURE AND
PRESSURES.
CAUTION
Turnoffor disconnecttheelectrical power supply tothe
water heater beforeservicing. Labelall wires prior to
disconnection whenservicing controls. Wiringerrors can
cause improper and d
operation after servicing.
angerous operation. Verify proper
Page 3
Page 4
4
Introduction
4
The new Bradford White TTW1, TTW2 & TW4 water heaters are designed to provide reliable
performance with enhanced standard features. New design features include reliable spark to pilot
ignition system, enhanced diagnostics, simplified servicing, significantly quiet operation and additional
vent lengths and Bradford White Defender Safety System®.
Spark to Pilot Ignition System - employing thespar
consistent pilot and main burner ignitions to provide hot water on demand.
Integrated Immersion Thermostat/Gas Control Valve with LED - was developed for ease of
troubleshooting by providing simple diagnostic codes to pinpoint an installation or component
performance issue.
New Powerful Blower - will eliminate problems with difficult venting situations.
Quieter and Cooler Blower Operation - blower noise is
exterior environments. Cooler operation increases blower life by reducing bearing wear and noise.
Increased Vent Lengths - increased venting performance is achieved while maintaining Energy Factor
& FHSR performance.
The TTW1, TTW2 & TW4 water heaters use a combustion system
dilution air to reduce the flue gas temperature in the blower. The diluted flue gases are evacuated to the
exterior through low temperature vent materials. The gas control maintains water temperature, ignition
sequence and regulates gas flow. A safety circuit consisting of a
temperature switch verifies proper conditions exist for safe and reliable operation. If a situation outside
of normal operating parameters exists, the gas control diagnostic LED will flash a code to positively
identify an operational issue.
This service manual is designed to facilitate problem diagnosis
further promote quicker service times the new gas valve can be removed and replaced without draining
the water heater. A special tool is required and will be provided with each gas valve kit shipped from
our Service Parts department.
k to pilot ignition system promotes reliable and
significantly reduced for both interior and
where flue gases are combined with
pressure switch and blower
and enhance service efficiency. To
Please read the service manual
models.
During normal operation, air for combustion is drawn into the water heater through the opening in the
jacket. This air travels down and around the combustion chamber and enters through holes in the very
bottom of the corrosion-resistant combustion chamber. The air then travels up through the oriented
flame arrestor plate louvers, where the velocity of air is increased and its direction altered. The air then
mixes in a normal manner with supplied gas and is efficiently combusted, producing very low Nox
emissions.
In the unlikely event trace amounts of flammable vapors are present in the air
combustion chamber, the vapors are harmlessly ignited by the burner. If flammable vapors are in
sufficient quantity to main burner. Should be flammable vapors continue to burn, the flame arrestor
plate prevents the flames from traveling backwards and igniting vapors outside of the combustion
chamber.
completely before attempting service on this new series of power vent
How the Safety System Works
flowingintothe
Page
Page 5
How to Use This Manual
5
It is intended for this manual to be used by qualified service personal for the primary purpose of
troubleshooting and repair of the Bradford White TTW Series water heaters. Understanding the
sequence of operation section of this manual will contribute greatly to troubleshooting the water
heater.
The Honeywell WV4460E Electronic Gas Control will display error codes in the event of abnormal
operation. Error codes are listed in the troubleshooting chart beginning on page 13 of this service
manual. The troubleshooting chart will also indicate the probable cause for the error code and
direct the service professional to a service procedure to properly diagnose the abnormal operation.
In some difficult to diagnose conditions, it may be necessary to isolate the heater from the vent
system to determine the problem.
Contact the Bradford White technical support group immediately if diagnosis can not be made
using the methods described in this service manual.
Tools RequiredforService
Manometer:A liquid “U” tube type or a digital (magna-helic) type can be used. This
Multi-Meter:A digital type is strongly recommended. This device is used to measure
electrical values. The meter you select must have the capability to
measure volts AC, volts DC, Amps, micro-amps and ohms.
Electronic Probes:In some cases, standard multi-meter probes will damage or simply
not be effective to obtain certain voltage and ohm reading. It will be
necessary to have special electronic “pin” type multi-meter probes.
These probes are available at most electronic wholesale outlets.
Thermometer:Used to measure water temperature. An accurate thermometer is
recommended.
Water Pressure Gage:Used to measure water supply pressure. Also used to determine tank
pressure by adapting to the drain valve of the heater.
Gas Control Service Tool:BWC part number 239-45991-00. A specialized tool designed to remove
the gas control from gas control thermal well. Available from
your Bradford White parts supplier.
Various Hand Tools:Pipe wrench, channel locks, open end wrenchs (3/8", 7/16", 1/2"),
Uponpower up, the control runs a safe-start check with a typical start-updelay of 5 seconds.
2
Flammable Vapor.
To assure no outputs are energized if the “Flammable Vapor Sensor” is out of range, the control will test the
the “Flammable Vapor Sensor” for proper operating range. If the “Flammable Vapor Sensor” is out of range, the
control LED immediately flashes 7 times with 3 secondpause.
1
Thermostat calls for heat.
Prior to energizingblower, gas control checks safety circuit to insure the circuit is open. Normal switch positions
in the safety circuit are as follows:
a) Pressure switch normally open.b) Blower temperature switch normally closed.
If the safety circuit is closed, the co
ntrol waits 4 seconds, gas control LED flashes 2 times with 3 second pause.
Gas control waits 2 minutes then, blower runs for 30 seconds. This cycle repeats until safety circuit opens.
2
Blower energizes.
3
Pressure switch proves blower/vent system operation.
If the pressure switch does not close within30 seconds, the control LED Flashes 3 times with 3 second pause.
The blower runs for 30 seconds every 2 minutes trying to get the pressure switch or blower temperature switch to
close. This cycle repeats as long as there is a call for heat.
4
Blower pre-purge period (2 seconds).
5
Trial for pilot ignition (90 seconds).
a) The gas control lights the pilot by activating spark igniter and gas flow to pilot burner.b) If flame is not sensedwithin 90 seconds, igniter andgas flow are deactivated,blower will post purge and
control LED flashes 6 times with 3 secondpause.
6
Mainburner Ignition
After pilot flame is sensed,gas control activates mainvalve for mainburner ignition. The gas control will ignore
flame and pressure switch signals for 3 seconds allowing for main burner to stabilize.
Page10
Page 11
Steady state operation.
11
7
8
Thermostat satisfies. (Control LED flashing once every 4 seconds).
9
Burner off.
During Steady State Operation the Control Monitors:
Thermostattemperaturesensor- When set point temperature is satisfied, gas valve is shut down and
blower will post purge for 15 seconds. Control LED flashes a short flash once every 4 seconds (idle) status
code.
Pressureswitch / Blowertemperatureswitch- If either switch opens, pilot valve and main valve is shut
down. The blower continues to runs for 30 seconds attempting to close the circuit. The control LED Flashes
3 times with3 second pause.
Flame Sensor- Ifflame is lost, pilot & main valve are shut down, blower runs for 15 seconds. Control attempts
to re-light pilot 4 times. If unsuccessful, Blower is shut down and control proceeds to 5 minute lockout. Control
re-attempts to light pilot starting at normal heating sequence #2.
Sequence of Operation
10
Blower post purge (15 seconds).
1. Flammable Vapor Sensor Fault: (For water heaters with serial numbers that begin with “K” or
later see page X.)
a) If theresistanceis greaterthan 70,000 Ohms - the gas control immediately turns off all outputs. Control waits
and monitors resistance for 30 seconds. If the resistance is greater than 65,000 ohms after 30 seconds, the
gas control proceeds to verify resistive delay for 2 minutes and flashes 7 times then once
with a three secondpause. This process is repeated 5 times until the control either returns to normal operation or proceeds to
flammable vapor lockout.
b) If theresistanceis below 3000ohms - The gas control immediately turns off all outputs and proceeds to flash
8 times then once with three second pause. The error selfclears if t
he resistance returns to normal range for at
least 15 seconds.
2. Temperature Sensor Fault: (For water heaters with serial numbers that begin with “K” or later
see page X.)
a) Temperaturesensor detected opencircuit - The gas control Immediately turns off all outputs and proceeds to
flash 8 times then 3 times with three second pause. The error self clears if the fault clears for at least 15 seconds.
b) Thermal well sensor not reading the same temperature within ±5.5 °F - The gas control Immediately turns off
all outputs and proceeds to flash 8 times then 3 times twice with three second pause.
fault clears for at least 15 seconds.
c) Watertemperatureinexcessof TCO (Temperature Cut Off) limit - The gas control immediately turns off pilot &
main valve and proceeds to flash 4 times with 3 second pause. Blower continues to run until gas control is reset.
To reset control, rotate knob of temperature control to the minimum setting for at least 6 seconds before returning
to desired temperature setting.
The error self clears if the
Page 11
Page 12
Sequence of Operation
12
3. Pressure Switch/Blower Temperature Fault:
a) Pressure switch closed at start of call for heat - The gas control waits four seconds then, proceeds to flash
2 times with 3 second pause. The control waits 2 minutes and then turns on blower for 30 seconds. The blower
turns off after 30 seconds and the control waits for pressure switch to open. Any time the Pressure switch opens,
the blower turns on (or stays on) and the control proceeds to waitingfor pressure switch to close.
b) Pressure switch or blower temperature switch failed to close - The gas control runs the blower for 30 seconds
waitingfor the pressure switch and/or blower temperature switch to close. If either switch does not close in 30
seconds, the blower turns off and the control flashes 3 times with 3 second pause. The gas control waits two
minutes before turning on the blower for another 30 seconds to see the circuit close. This cycle repeats as long
there is a call for heat or until the circuit closes.
c) Pressure switch or blower temperature switch opens during burner operation - The gas control turns off the
pilot and main valve, runs blower for 15 seconds (inter-purge) waiting for pressure switch and/or blower
temperature switch to close. If either switch fails to close, the control proceeds as described in 3b above. If the
circuit closes again by the end of the i
not reached its limit (4), another trial for ignition begins. If the recycle count has been reached, the gas control
turns off the blower and flashes 6 times then 2 times with 3 second pause. The gas control waits 5 minutes before
repeating ignition sequence.
nter-purge, the recycle counter is incremented, if the recycle count has
as
4. Trail For Ignition Fault:
a) Pressure switch opens during trial - The gas control turns off igniter and pilot valve. The gas control proceeds
as described in 3b above. If the pressure switch closes within 30 seconds the gas control will continue with trial for
ignition starting at blower pre-purge.
b) Flame Not Sensed - The gas control energizes the spark igniter attempting to light the pilot and prove flame. If
flame is not sensed within 90 seconds, the igniter turns off, the pilot valve is closed and the gas control runs the
blower through post purge and flashes 6 times then once with 3 second pause. The control waits 5 minutes before
repeating the ignition sequence.
5. Flame Sensing Fault:
b) Flame lost during run - The gas control turns off pilot and main valves, runs blower for 15 seconds (inter purge).
The gas control increments the recycle count, if the recycle count has not reached its limit (4), another trial for
ignitionbegins. If the recycle count has been reached, the gas control turns off the blower andthen 3 times with 3 second pause. The gas control waits 5 minutes before repeating the ignition sequence.
c) Flame sensed out of sequence - the gas control only looks for pilot flame when the blower is running. If flame is
present when the pilot valve is not open, the gas control proceeds to wait for flame loss andflashes 5 times with 3
second pause. This continues until flame is lost,
times with 3 second pause. The control waits 5 minutes before repeating the ignition sequence.
once the flame signal is lost, the control flashes 6 times then 4
flashes 6 times
Page12
Page 13
Troubleshooting
13
Green LED
Indicator
Observe green LED indicator on Electronic gas
control. Error flash codes are displayed with a
three second pause before repeating. Check
and repair the system as noted in the
troubleshooting table below.
This chart is for water heaters with serial numbers that begin with “J” or sooner for water
heaters with serial numbers that begin with “K” or later see page 15.
LED Status
None, control LED not on
or flashing
Short flash, once every
four seconds
“Heartbeat”, alternates
bright/dim
ControlStatus
Noelectrical
power
Stand-by mode,
Waitingfor callfor
heat (nofault).
Thermostat calling
for heat (no fault).
Probable Cause
Control power switch in“OFF” position.
Supply voltage interrupted.
Temperature demand is satisfied
Tank temperature below set point of thermostat.
Service
Procedure
Turn power on
Normaloperation.
Adjust thermostat to
temp level
Normal operation.
Adjustthermostatto
temp level
Shortflash once per
second
Two flash, three second pause
Three flash, three second
pause
Four flash, threesecond
pause
Five flash, threesecond
pause
Weak pilotsignalon last callfor heat.
Pressureswitch not
working-closed
position.
Pressureswitch or
blower temp.
switch not working
-open position.
Excessive tank
temperature.
System must be
reset.
Undesired-false
pilot flame present.
1. Unstablepilot.
2. Pilot tube block or restricted.
3. Oxidationbuilduponpilotelectrode.
4. Wiredamagetopilotassemblyorbad
connection at gas valve.
1. Pressure switch tubing kinked or blocked.
2. Blocked pressure tap on switch or blower.
3. Faulty pressure switch.
1. Vent blockage or improper vent configuration.
2. Pressure switch tubing kinked or blocked.
3. Faulty pressure switch.
4. Blower not spinning up to speed.
5. Blower temp or exhaust temp too high
6. Faulty blower temperature switch.
1. Thermal well sensor out of calibration.
2. Faulty gas control.
3. Pluming leak
1. Pilot valve stuck in open position.
1.Page 15
2-4. Page 17
Page 18
1. Check vent or vent tables.
2 & 3 Page 18
4. Page 20
5 & 6 Page 22
1. Page 24
2. Replace gas control,
page 24
Replace gas control,
page 24
Page13
Page 14
Troubleshooting
14
This chart is for water heaters with serial numbers that begin with “J” or sooner for water
heaters with serial numbers that begin with “K” or later see page X.
LED StatusControl Status
Six-one flash, three
second pause
Six-two flash, three
second pause
Six-three flash, three
second pause
Six-four flash, three
second pause
Sevenflash, threesecond
pause
Eight-one flash, three
second pause
Eight-two flash, three
second pause
Eight-three flash, three
second pause
Failed tolight pilot.
System auto resets.
Pressure switch
or blower temp
switch opened
during burner
operation.
System auto
resets.
Pilot flame
extinguished.
System auto
resets.
Undesired-false
pilot flame
sensed.
System auto
resets.
Simulated
Resistive Device
Harness out of
specification.
Simulated resistive device out of specification.Page28
Simulated resistive device out of specification.Page28
1. Damage to thermal well wire.
2. Thermal well sensor resistance out of range.
1. Control needs to be reset.
2. Control is wet or physically damaged.
Page 24
1. Interrupt power supply
2. Replace gas control,
page 26
Service
Eight-four flash, three
second pause
Gas valve fault
detected.
1. Control needs to be reset.
2. Control is wet or physically damaged.
1. Interrupt power supply
2. Replace gas control,
page 26
Page14
Page 15
Observe green LED indicator on Electronic gas
15
control. Error flash codes are displayed with a
three second pause before repeating. Check
and repair the system as noted in the
troubleshooting table below.
Troubleshooting
Green LED
Indicator
LED Status
None, control LED not on
or flashing
Short flash, once every
four seconds
“Heartbeat”, alternates
bright/dim
Short flash once per
second
Two flash, three second
pause
Three flash, three second
pause
Fourflash, threesecond
pause
Control Status
Noelectrical
power
Stand-by mode,
Waitingforcallfor
heat (nofault).
Thermostat calling
for heat (no fault).
Weak pilot signal
on last call for heat.
Pressure switch not
working-closed
position.
Pressure switch or
blower temp.
switch not working
-open position.
Excessive tank
temperature.
System must be
reset.
Probable Cause
Control powerswitch in“OFF” position.
Supply voltageinterrupted.
Temperature demand is satisfied
Tank temperature below set point of thermostat.
1. Unstablepilot.
2. Pilot tube block or restricted.
3. Oxidationbuilduponpilotelectrode.
4. Wiredamagetopilotassemblyorbad
connection at gas valve.
1. Pressure switch tubing kinked or blocked.
2. Blocked pressure tap on switch or blower.
3. Faulty pressure switch.
1. Vent blockage or improper vent configuration.
2. Pressure switch tubing kinked or blocked.
3. Faulty pressure switch.
4. Blower not spinning up to speed.
5. Blower temp or exhaust temp too high
6. Faulty blower temperature switch.
1. Thermal well sensor out of calibration.
2. Faulty gas control.
3. Pluming leak
Service
Procedure
Turn poweron
Normaloperation.
Adjust thermostat to
temp level
Normal operation.
Adjustthermostatto
temp level
1. Page 15
2-4. Page 17
Page 18
1. Checkventorventtables.
2 &3Page 18
4. Page 20
5 &6Page 22
1. Page 24
2. Replace gas control,page 24
Fiveflash, threesecond
pause
Undesired-false
pilotflame present.
1. Pilot valve stuck in open position.
Replace gas control,
page24
Page15
Page 16
Troubleshooting
16
LED StatusControl Status
Six-one flash, three
second pause
Six-twoflash, three
second pause
Six-three flash, three
second pause
Six-four flash, three
second pause
Sevenflash, threesecond
pause
Eight-one flash, three
second pause
Eight-two flash, three
second pause
Eight-three flash, three
second pause
Failed tolight pilot.
System auto resets.
Pressure switch
or blower temp
switch opened
during burner
operation.
System auto
resets.
Pilot flame
extinguished.
System auto
resets.
Undesired-false
pilot flame
sensed.
System auto
resets.
Simulated
Resistive Device
Harness out of
specification.
Simulated resistive device out of specification.Page28
Simulated resistive device out of specification.Page28
1. Damage to temperature sensor.
2. Temperature sensor resistance out of range.
1. Control needs to be reset.
2. Control is wet or physically damaged.
Page 24
1. Interrupt power supply
2. Replace gas control,
page 26
Service
Eight-four flash, three
second pause
Gas valve fault
detected.
1. Control needs to be reset.
2. Control is wet or physically damaged.
1. Interrupt power supply
2. Replace gas control,
page 26
Page16
Page 17
TTW SERVICE PROCEDURE I
17
Burner Operation Inspection,
Adjustment, Cleaning and Replacement
Burner Inspection and Air Shutter Adjustment.
At periodic intervals (every 6 months) a visual inspection should be made of the pilot and main burner for proper
operation and to assure no debris is accumulating.
Pilot flame should be stable, some causes for an unstable pilot flame are:
a) Water heater vent is less than the allowable vent length.
b) Gas pressure is out of specification.
c) Pilot flame not fully engulfing spark/flame sensor.
Main burner should light smoothly from pilot and burn with a blue flame with a minimum of yellow tips.
Steel burner models self adjust air to gas ratio mixture and do not have an adjustable air shutter. Cast iron burner can
have the gas and air mixture properly proportioned by adjusting the air shutter on the mixer face of the main burner
(see cast iron burner adjustment below).
Main burner must be free from any debris accumulation that may effect burner operation (see burner cleaning
procedure on page 15).
Cast Iron Burner Air Shutter Adjustment
WARNING
Inner door andburner components may be HOT when performing this operation. Take
necessary precaution to prevent personal injury.
Step 1.With main burner in operation, remove outer jacket door and slide inner door from left to right to open.
Step 2.To adjust for proper burning, loosen the air shutter nut, rotate the air shutter to close the opening in the
burner, then slowly rotate the air shutter open until flame becomes as blue as possible with a minimum of
yellow tips. Tighten the air shutter nut.
Too much air will cause the flame to lift off the burner ports and create noisy burner operation.
Too little air will result in soot formation.
Step 3.Close inner door and observe burner operation. Burner should operate as adjusted in step 2. If not,
repeat air shutter adjustment compensating for proper burner operation with inner door closed.
AirShutter
AirShutterNut
Page17
Page 18
TTW SERVICE PROCEDURE I
18
Burner Operation Inspection,
Adjustment, Cleaning and Replacement
Burner Cleaning
Remove Outer
door.
Step 1.Position gas control power switch to the
“OFF” position and unplug heater from wall
outlet.
Step 2.Turn off gas supply to water heater.
Step 3.Remove outer jacket door and slide inner door open from left to
right.
Step 4.Disconnect pilot tube (7/16 wrench) and
Igniter/flame
sense wire
feedline (¾ wrench) from gas control.
Step 5.Disconnect igniter/flame sensor wire from gas control.
Step 6.Remove burner assembly from combustion chamber.
Step 7.Thoroughly inspect burner surface area and burner port area and
remove any loose debris.
Step 8.For cast iron burners, inspect for any debris build up inside
burner casting.
Burner
surface area
Slide inner door open
from left to right.
Feedline nut
Pilot tubing nut
Burner
port area
Step 9.Unscrew burner from main burner
orifice. On cast iron burners, loosen
air shutter nut and unscrew feedline
from burner.
Step 10.Remove main burner orifice from
feedline (½" wrench on steel
burners, 3/8" wrench on cast iron)
inspect orifice, clean or replace if
necessary.
Step 11.Reassemble burner and reinstall into water heater. Restore gas supply
and check for gas leaks.
Step 12To resume operation follow the instruction located on the lighting
instruction label or the lighting instruction located in the installation
and operating manual.
Main burner
orifice
L.P. Main burner
orifice. Left hand
thread
Page18
Page 19
TTW SERVICE PROCEDURE II
19
Pilot testing, Cleaning and Replacement
Pilot Inspection, Testing and Replacement
Step 1.Position gas control power switch to the
“OFF” position and unplug heater from wall
outlet.
Step 2.Turn off gas supply to water heater.
Step 3.Remove outer jacket door and slide inner door open from left to
right.
Remove Outer
door.
Igniter/flame
sense wire
Slide inner door open
from left to right.
Step 4.Disconnect pilot tube nut (7/16 wrench) and feedline nut
(¾ wrench) from gas control.
Step 5.Disconnect igniter/flame sense wire from gas control.
Step 6.Remove burner assembly from combustion chamber.
Step 7.Remove pilot assembly from feedline (¼" nut driver).
Step 8.Visually inspect igniter/flame sense wire for damage. Replace
pilot if damage is found.
Step 9.With a multi-meter set to the ohms setting, check continuity
through igniter/flame sense wire. Replace pilot if no continuity.
Step 10.Visually inspect igniter/flame sense electrode for deterioration.
Replace pilot as necessary. Electrode should not be in contact
with pilot hood, If so, carefully adjust electrode to a gap
distance of 3/32" (.09) from pilot hood.
Step 11.Visually inspect igniter/flame sense electrode for oxidation
build up. Carefully clean any oxidation using very fine emery
cloth.
Step 12.Visually inspect pilot tubing for kinks or cracks. If damage is
found replace pilot.
Ferrule
nut
Pilot
tubing
Igniter/flame sense
wire
Pilot
orifice
Feedline nut
Pilottubing nut
Pilot
hood
Igniter/flame sense
electrode
Step 13.Inspect pilot tubing and pilot orifice for blockage:
a) Remove ferrule nut from bottom of pilot assembly (7/16" wrench).
b) Remove pilot tube and pilot orifice.
c) Inspect pilot tubing and pilot orifice for blockage. Clean
or replace as necessary.
Step 14.Reassemble pilot and install to feedline. Reinstall burner assembly to water heater. Restore gas supply
and check for gas leaks.
Step 15To resume operation follow the instruction located on the lighting instruction label or the lighting
instruction located in the installation and operating manual.
Page19
Page 20
TTW SERVICE PROCEDURE III
20
Pressure Switch Testing and
Replacement
Pressure Switch Testing
WARNING
120 volt potential exposure. Use caution
Step 1.Position power switch on gas control
making voltage checks to avoid personal injury.
to the “OFF” position.
Step 2.Remove the three screws (Phillips screw driver) from control access cover on blower assembly and
remove cover (see photo 1).
Step 3.Carefully remove pressure switch from blower housing (see photo 2)
With steps 1,2 & 3 complete,
disconnect wire leads from
pressure switch.
1
Pressure switch
wire leads
Slide pressure switch in direction of
arrow while tilting slightly away
from blower housing.
2
PressureSwitch
Use a multi-meter set to the
ohms setting. With blower off,
check across pressure
switch terminals.
Are switch contacts open?
(no electrical continuity)
Y
Position gasvalvepower
switch to the “ON” position
and adjust thermostat
to call for heat,
this will start the blower.
Check with multi-meter, do
pressure switch contacts close
with blower running?
Y
Switch contacts are OK.
See safety circuit trace
(page 29)
N
N
switch for blockage.
Y
Check tubing and
pressure tap on
Is there blockage?
Check tubing and pressure tap
on switch for blockage.
Is there blockage?
Y
Clearblockage
Y
N
Is vent
system
blocked
N
N
Is vent system length
listed on pages 7 & 8
Replace switch
(see page 19)
within vent table
specifications
Reconfigure vent
system to be
compliant with
vent tables.
Y
Y
N
See blower testing
(page 20)
Is blower OK?
N
Correct blower
problem.
Page 20
Page 21
TTW SERVICE PROCEDURE III
21
Pressure Switch Testing and
Replacement
Pressure Switch Replacement
WARNING
120 volt potential exposure. Use caution
to avoid personal injury.
Step 1.Position gas control power switch
to “OFF” position.
Step 2.Remove the three screws (Phillips screw driver) from control access cover on blower assembly and
remove cover (see photo 3).
PressureSwitch
34
Step 3.Carefully remove pressure
switch from blower
housing (see photo 4)
Slide pressure switch in direction of
arrow while tilting slightly away
from blower housing.
5
Step 4.Disconnect tubing from
pressure switch.
(see photo 5)
6
Step 5.Disconnect yellow wires
from pressure switch
(see photo 6)
Step 6.Reconnect wires from step 5 to new pressure switch.
Step 7.Reconnect tubing to new pressure switch.
Step 8.Carefully position pressure switch into blower housing.
Step 9.Position gas control power switch to “ON” position and verify proper heater operation.
Step 10.Replace control access cover from step 2.
Page 21
Page 22
TTW SERVICE PROCEDURE IV
22
Blower Testing and Replacement
Blower Testing
115 volt potential exposure. Use caution when
making voltage checks to avoid personal injury.
Step 1.Position gas control power switch
to “ON” position and adjust control to call for heat.
Step 2.Remove the three screws (Phillips Screw driver)
from control access cover on blower assembly and
remove cover (see photo 7).
Does blower energize Within 2
minutes?
N
89
Does blower energize after 2
minutes, run for 30 seconds
and shut down?
pressure switch
Y
tubing fromblower.
Pressuretap
Pressureswitch
Seepressureswitch
Y
Disconnect
(see photo 8)
tubing
testing
Page 18
manometer to
pressure tap of
(see photo 8)
Determine voltage
problem and correct.
7
Connect
blower.
1112
Disconnect vent
system from top of
blower and remove
With blower running, and exhaust
adapter removed from top of blower,
is there a negative pressure of -2.15"
N
WARNING
vent adapter.
(see photo 10)
to -2.30" W.C.?
N
Is there 115vac across blue
and green wires
(see photo 13)
Y
Y
Remove exhaust
adapter
10
Blower OK
Replace blower
N
Disconnect cord set
shown in photo 9. Is
there 115VAC across
terminals shown in photo
11
N
Is there 115 VAC at
wall outlet?
Y
Check power cord
for damage.
N
Replace blower
Y
N
Y
Is there 115VAC across
terminals shown in
photo 12 ?
Incorrect supply
voltage polarity
Determine
power source
problem and
correct.
Repair or replace
power cord
Y
N
Replace
cord set
Reconnect cord set shown
in photo 9, is there
115VAC between blue wire
and green ground wire
(see photo 13)
N
Does cord set
N
have electrical
continuity?
Y
Replace gas
control
Y
Replace blower
Green ground
wire
Shown with pressure
switch removed.
13
Blue wire
Page 22
Page 23
Blower removal
23
Step 1.Position gas control power switch to the “OFF” position.
Step 2.Unplug blower power cord from wall outlet.
Remove exhaust adapter
and retain for use on
new blower.
Step 3.Disconnect vent system from exhaust adapter on top of
blower.
Step 4.Remove exhaust adapter from blower (blade screw driver)
and retain for use on new blower
Step 5.Unplug cord sets from blower.
Step 6.Remove the three blower mounting screws
(¼" nut driver).
TTW SERVICE PROCEDURE IV
Blower Testing and Replacement
Blower Mounting
Screws
Step 7.Remove blower with gasket from water heater.
Blower Installation
Step 8.Clean any debris from jacket head of water heater.
Step 9.Set new blower with gasket in place using locating pins on
blower flange to line up with location holes in jacket head.
Be sure not to damage gasket.
Step 10Secure blower in place using mounting screws from step 6.
Step 11.Re-install exhaust adapter from step 4.
Step 12.Reconnect vent system to
exhaust adapter.
Step 13.Reconnect cord sets from step 5.
Step 14.Plug blower power cord into wall outlet.
Locating Pins
on blower flange
Pin location holes in
jacket head
Blower
Cord Sets
Step 15.Position gas control power switch to the “ON” position.
Step 16. Verify proper blower operation.
Page 23
Page 24
TTW SERVICE PROCEDURE V
24
Blower Temperature Switch Testing
and Replacement
Blower Temperature Switch
Testing.
Step 1.Position power switch on gas control
to the “OFF” position.
Step 2.Remove the three screws (Phillips screw driver) from
control access cover on blower and remove cover (see
photo 14).
Step 3.Locate blower temperature switch (see photo 15)
Switch Setting
Opens on rise @ approximately 165°F
Auto resets on fall @ approximately 130°F
Cool switch to
below 130°F
120 volt potential exposure. Use caution
WARNING
to avoid personal injury.
14
15
Air mixing inlet
Blower temperature
switch location
Disconnect wire leads to
switch. Using a multi-meter
set to the ohms setting, is
there continuity between the
switch terminals?
Y
Reconnect wire leads and
observe heater operation. Do
exhaust gas temperatures rise
to or above 165°F?
N
Do switch contacts
open?
N
Switch OK
Y
N
Y
Replace switch
(see page 23)
Replace switch
(see page 23)
N
Do switch contacts
open?
Y
temperature is too
Exhaust
hot.
Common causes for
high exhaust temperature
1. Vent length is below minimum allowable.
2. Vent diameter not to specification.
3. Restricted dilution air inlet.
4. Missing or deteriorated flue baffle.
5. Gas pressure is out of specification.
Page 24
Page 25
TTW SERVICE PROCEDURE V
25
Blower Temperature Switch Testing
and Replacement
Blower Temperature Switch
Replacement.
Step 1.Position gas control power switch to the “OFF” position
and unplug heater from wall outlet.
Step 2.Remove the three screws (Phillips screw driver) from the
control access cover on blower and remove cover.
(see photo 16)
Step 3.Locate blower temperature switch (see photo 17)
Step 4.Disconnect red and yellow wire leads from switch.
120 volt potential exposure. Use caution
WARNING
to avoid personal injury.
17
Blower temperature
switch location
16
Step 5.With an appropriate tool such as side cutters, snip the
retaining lug from the blower housing to allow removal of
temperature switch (see photo 18).
Step 6.Remove switch from blower housing.
Step 7.Install new switch. Be sure switch is properly seated in
mounting area.
Step 8.Reconnect red and yellows wires to new switch. Wires are
interchangeable with either terminal.
Step 9.Position gas control power switch to the “ON” position
and verify proper heater operation.
Step 10.Replace control access cover from step 2.
18
Snip retaining lug
from blower housing
Page 25
Page 26
TTW SERVICE PROCEDURE VI
26
Gas Control/Thermal Well Testing and
Replacement
Gas Control Testing
See pages 29 & 30 for gas control
input & output testing.
Thermal Well Testing (For water heaters with serial numbers that begin
with “J” or sooner.)
Position gas valve power
switch to the “OFF” position
and disconnect thermal well
harness from gas control.
Using a multi-meter set to
the Ohms setting,
determine the resistance of
thermal well sensors 1 & 2
(see photos 19 & 20)
Disconnect thermal
well wire harness
19
20
Using a multi-meter set to the ohms setting, insert one meter probe into center wire
position of thermal well connector, insert the second probe into either of the outside
wire positions (see photo 19).
Alternate the probe on the outside position to the opposite outside wire position
(see photo 20).
Once the thermal well resistance values are known, the water
temperature must also be known to determine if the resistance
values are correct. See page 25 to obtain water temperature.
Are thermal well resistance values correct?
Y
ThermalwellOK
N
Replace thermal well
(see page 26)
Page 26
Page 27
TTW SERVICE PROCEDURE VI
27
Gas Control/Thermal Well Testing and
Replacement
WARNING
Stored water may be HOT when performing the following steps in this procedure.
Take necessary precaution to prevent personal injury.
Determine Water Temperature Inside Tank (For water heaters with
serial numbers that begin with “J” or sooner.)
Note: It is important to understand once the resistance for the thermal well is determined from page 24, water flow
through the heater should not occur. Prior to performing the steps below, turn off the cold water supply to the
water heater. This will prevent cold water flow into the tank affecting the resistance value of thermal well.
Step 1.Position gas control power switch to “OFF” position.
Step 2.Draw approximately 4 gallons of water from drain valve into a container and discard. Draw an
additional gallon and immediately measure water temperature using an accurate thermometer. It may
be necessary to open a hot water faucet to allow heater to drain.
Step 3.Using the chart below, determine correct resistance value for the water temperature from step 2.
Example: If temperature of water is 84°F, then the resistance through the sensor would be
8449 (see shaded area). NOTE: Sensor resistance increases as the temperature
GasControl & Thermal Well Removal From WaterHeater(For
water heaters with serial numbers that begin with “J” or sooner.)
Gas Control
Step 1.Position gas valve power switch to the “OFF”
position and Unplug Heater from power supply.
Thermal
Well
Step 2.Drain heater to a point below the gas
control level.
Step 3.Turn off gas supply to water heater and
disconnect gas piping from gas control.
Step 4.Disconnect wire harnesses and burner assembly
from gas control.
Step 5.Remove gas control & thermal well by rotating flats of Thermal Well counter clockwise (1-5/16"wrench).
GasControlRemoval FromThermalWell(For water heaters with
serial numbers that begin with “J” or sooner.)
Follow the steps below allows removal gas control from thermal wellwithout removing thermal wellfrom tank.
Step 1.Position gas control power switch to the “OFF” position and unplug water heater from power supply.
Step 2.Turn off gas supply to water heater and disconnect gas piping from gas control.
Step 3.Disconnect wire harnesses & burner assembly from gas control.
Step 4.Using gas control service tool (239-45991-00) available from your BWC parts supplier, Insert tool into
back of gas control (see photos below)
View from back of
control for clarity
Insert tool from
back of control
Service tool shown
inserted in to back
of control
Step 5.Pivot tool towards heater as far as possible (see photo below). Lift straight up on gas control. The
control should move about 1/8". Hold control in position and remove tool. Lift straight up on control to
remove completely from Thermal Well.
With servicetool inserted, pivottool back towards heater as
far as possible. Lift straight up on control, control will move
1/8". Removetool and continue to lift straight up on control
to removefrom Thermal Well.
Page 28
Page 29
TTW SERVICE PROCEDURE VI
29
Gas Control & Thermal Well Testing
and Replacement
GasControl AssemblytoThermal Well (For water heaters with serial
numbers that begin with “J” or sooner.)
Step 1.Install threaded end of thermal well into tank. Be sure
thermal well flange is positioned as shown in photo 24
for proper control alignment.
Step 2.Route wire leads back into relief opening.
(see photo 24)
Step 3.Align slots located on thermal well flange with tabs
located on back of gas control (see photos 24 & 25)
Thermal well flange
slots
24
Route wires
through relief opening
Step 4.Carefully push control back onto thermal well flange
as far as possibletowards water heater. Slide control
down to lock into position.
Step 5.Install burner and connect pilot and feedline to gas
control.
Igniter/sensor
connection
Step 6.Reconnect wire harnesses to gas control
Step 7.Reconnect gas piping to gas control.
Ground Wire
connection
Step 8.To resume operation, follow the
5 pin
blower harness connection
3 pin
thermal well connection
25
Gas controlTabs
per the illustration.
Restore gas supply and check for gas
leaks.
instruction located on the lighting
instruction label or the lighting instruction
located in the installation and operation
manual.
Simulated Resistive
device
Page 29
Page 30
Simulated Resistive Device Testing
30
TTW SERVICE PROCEDURE VII
Simulated Resistive Device Testing
Step 1.Position power switch on gas control to the
“OFF” position.
Step 2.Disconnect simulated resistive device from
gas control.
Step 3.Using a multi-meter set to the ohms setting
check resistance of simulated resistive
device. Resistance must be within 25,000
ohms and 45,000 ohms. If outside of this
range replace simulated resistive device.
Multi-meter set to
ohms setting
Electronic
“pin type”
Meter Probes
For water heaters with serial numbers
that begin with “J” or sooner.
Simulated Resistive
device
Simulated Resistive
device
Multi-meter set to
ohms setting
Electronic
“pin type”
Meter Probes
For water heaters with serial numbers
that begin with “K” or later.
Simulated Resistive
device
Page 30
Page 31
TTW SERVICE PROCEDURE VIII
31
Safety Circuit Voltage Trace
Safety Circuit Voltage
Trace
NOTE: This procedure assumes a cool tank.
Step 2.Remove three screws (Phillips Screw driver) from control
access cover on blower and remove cover (see photo 26).
Position gas control switch to the “ON”
position and adjust thermostat dial to call
for heat, Is there 10 to 13 VAC between red
wire leading to blower temperature switch
and green ground wire?
Blower must be running during this
voltage check.
(see photo 27)
Y
N
Is LED on gas valve flashing the
“heartbeat” code (alternating
bright/dim)
Verify 120VAC to gas
control (see page 30)
120 volt potential exposure. Use caution
making voltage checks to avoid personal injury.
Y
N
WARNING
26
No voltage from gas control,
call for technical support.
Is there 10 to 13 VAC between yellow wire
leading from pressure switch and green
ground wire?
(see photo 27)
Y
Do you hear or can you see
the igniter sparking?
Y
Safety circuit
voltage is OK.
If burner does not light,
observe LED flash code on
gas valve and refer to
troubleshooting section on
page 13
N
N
Correct igniter/
sensor problem.
Check igniter/sensor
(see page 17)
is igniter/sensor OK?
27
Is there continuity
through blower
temperature switch?
(see page 22)
Determine cause of blower
temperature switch activation
and correct.
Faulty cord set or
Y
gascontrol.
Y
N
Yellow wire
leading from
pressure switch
Check for loose or
broken wire connection
at switch terminals
Green ground wire
Red wire leading to
blower temp. switch
Page 31
Page 32
TTW SERVICE PROCEDURE IX
32
120 VAC Trace
120 VAC Circuit Trace
120 volt potential exposure. Use caution
WARNING
making voltage checks to avoid personal injury.
Step 1.Verify 120VAC and proper polarity at wall outlet.
Step 2.With unit plugged in and control power switch in the “ON” position verify LED status.
LED status
None, Control LED not
on or flashing.
Disconnect cord set as
shown in photo 28
Using a volt meter set to
volts AC, is there 120VAC
across terminals shown
in photo 29 ?
Y
Is there 120VAC across
terminals shown in
photo 30 ?
N
Incorrect supply
voltage polarity
N
Y
LED status
Short flash, once every
four seconds.
Waiting for
call for heat.
Reconnect cord set
shown in photo 28.
Disconnect wire harness
from gas control
(see photo 31).
LED status
“Heartbeat”, alternates
bright/dim.
Thermostat calling
for heat
28
Check for damage to AC
supply power cord.
N
Replace Blower
29
Y
Wire harness
LED status
Various flashing error
codes.
Verify error code as
listed on page 13
30
Repair damage
31
Locate black & white wires at connector, It
may be necessary to pull back wire sheath
to identify wire colors.
(see photo 32)
Is there 120VAC across
black & white wires as
shown in photo 32?
N
Call for technical
support.
Y
Replace gas
control.
32
Wire sheath pulled back to
identify wire colors
Check for 120VAC between black & white wires.
-NOTE-
Electronic meter probes required. Use care not to
damage connector during this check.
Page 32
Page 33
TTW SERVICE PROCEDURE X
33
Dip Tube
Inspection and replacement
Dip Tube Inspection and Replacement
WARNING
Water Heater components and stored water may be HOT when performing the following
steps in this procedure. Take necessary precaution to prevent personal injury.
Step 1.Position on/off switch of gas control valve to “OFF” position and unplug water heater from wall outlet.
Step 2.Turn off cold water supply to water heater. Connect hose to drain valve of water heater and route to an
open drain. Open a nearby hot water faucet to vent heater for draining. Open drain valve of water
heater and allow heater to drain to a point below the inlet connection nipple.
Step 3.Disconnect inlet nipple from plumbing system.
Step 4With an appropriate tool such as a pipe wrench, remove inlet nipple/dip tube from the water heater.
Use caution not to damage pipe threads.
Step 5.Visually inspect inlet nipple/dip tube. Inlet nipple/dip tube should be free of cracks and any blockage.
Hydro-jet slots should be open and free of any blockage.
Any damage such as cracks, restriction due to deformation or unintentional holes are not field
repairable and the inlet nipple/dip tube must be replaced.
Step 6.Upon completion of inspection or subsequent replacement, reinstall inlet nipple/dip tube into water
heater. Connect nipple to plumbing system, resume water supply and refill with water.
Step 7.To resume operation follow the instructions located on the lighting instruction label or the lighting
instructions located in the installation and operation manual.
Page 33
Page 34
TTW SERVICE PROCEDURE XI
34
Anode
Inspection and replacement
AnodeInspectionandReplacement
WARNING
Water Heater components and stored water may be HOT when performing the following
steps in this procedure. Take necessary precaution to prevent personal injury.
Step 1.Position on/off switch of gas control valve to the “OFF” position and unplug water heater from wall
outlet.
Step 2.Turn off cold water supply to water heater. Connect hose to drain valve of water heater and route to an
open drain. Open a nearby hot water faucet to vent water heater for draining. Open drain valve of
water heater and allow water heater to drain to a point below the outlet connection nipple.
Step 3.Disconnect outlet nipple from plumbing system.
Step 4With an appropriate tool such as a pipe wrench, remove outlet nipple/anode from the water heater. Use
caution not to damage pipe threads.
Step 5.Visually inspect outlet nipple/anode. Outlet nipple/anode should show signs of depletion, this is
normal. If depletion is ½ of the original anode diameter (approximately ¾” diameter), replacement is
recommended. If any of the steel core of the anode is exposed, replacement is recommended.
Step 6.Upon completion of inspection or subsequent replacement, reinstall outlet nipple/anode into water
heater. Connect nipple to plumbing system, resume water supply and refill with water.
Step 7.To resume operation, follow the instructions located on the lighting instruction label or the lighting
instructions located in the installation and operation manual.
Page 34
Page 35
TTW SERVICE PROCEDURE XII
35
Flue Baffle
Inspection and replacement
Remove blower to gain access to
Disconnect vent system
from exhaust adapter.
flue baffle
Step 1.Position gas control power switch to the “OFF” position
and unplug blower from wall outlet.
Step 2.Disconnect vent system from exhaust adapter on top of
blower.
Step 3.Unplug cord sets from blower. (see photo 33).
Step 4.Remove the three blower mounting screws
(¼" nut driver) (see photo 33).
Step 5.Remove blower with gasket from water heater.
Step 6.Remove flue baffle from Heater (see photo 34).
Step 7.Inspect baffle for deterioration, missing restrictors.
Clean any scale or debris build up. Replace with new
baffle as necessary.
Step 8.Reinstall baffle into flue tube. Be sure baffle
hanger tab are inserted into notch location at the
top of the flue tube (see photos 35 & 36).
33
Blower
Cord Sets
34
Blower Mounting
Screws
Flue Baffle
Step 9Check Burner to insure no scale has accumulated during
this operation. See burner cleaning procedure on page 15.
Step 10.Reinstall blower on water heater. Connect vent
system and cords set to blower. Plug water heater
into wall outlet.
Step 11.To resume operation follow the lighting instruction
located on the lighting instruction label or the lighting
instruction located in the installation and operation
manual.
Fluetube
35
notch
36
Baffle shown
installed in flue
tube notch.
Page 35
Page 36
BTUBritish Thermal Units
36
GPMGallons per Minute
HzHertz
KW/hKillo-watts per hour
LEDLight Emitting Diode
NPTNational Pipe Thread
OhmsOhms of resistance
PSIPounds per Square Inch
RPMRevolutions per Minute
TCOTemperature Cut Off
VACVolts Alternating Current
W.C.Inches of Water Column
°CDegrees Centigrade
°FDegrees Fahrenheit
GlossaryofTerms
NOTES
Page 36
Page 37
NOTES
37
Page 38
NOTES
38
Page 39
NOTES
39
Page 40
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.