TW450S65F (B,C,S)*(N,X)
TW465S65F (B,C,S)*(N,X)
(*) Denotes Warranty Years
Through-The-Wall Gas Water Heaters
TTW Series
®
Page 2
The Bradford White
2
Through-The-Wall Gas Water Heaters
PageTTW Service Procedure
Introduction 4- - -
How to use this manual 5- - -
Tool required for service 5- - -
Specifications 6- - -
Control Timings 9- - -
Sequence of Operation 10- - -
Troubleshooting 13- - -
Burner Inspection, Cleaning and Replacement 15I
Pilot Testing, Cleaning and Replacement 17II
Pressure Switch Testing and Replacement 18III
Blower Testing and Replacement 20IV
Blower Temperature Switch Testing and Replacement 22V
Gas Control & Thermal well Testing & Replacement 24VI
Flammable Vapor Sensor Testing and Replacement 28VII
Safety Circuit Voltage Trace 29VIII
115VAC Circuit Trace 30IX
Dip Tube inspection and Replacement 31X
Anode Inspection and Replacement 32XI
Flue Baffle Inspection and Replacement 33XII
Inner Door Removal, Inspection & Replacement
®
ScreenLok
Flame Arrestor Cleaning
Glossary of Terms
Parts List
34XIII
37XIV
38- - -
39- - -
Page 2
Page 2
Page 3
WARNING: If the information in these instructions
3
is not followed exactly, a fire or explosion may
result causing property damage, personal injury, or
death.
Incorrect operation of this appliance
CAUTION
may create a hazard to life and
property and will nullify the warranty.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable,
combustible, or corrosive vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
WARNING
Water heaters are heat producing appliances. To
avoid damage or injury, do not store materials
against the water heater or vent-air intake system.
Use proper care to avoid unnecessary contact
(especially by children) with the water heater and
vent-air intake components. UNDER NO
CIRCUMSTANCES MUST FLAMMABLE
MATERIALS, SUCH AS GASOLINE OR PAINT
THINNER BE USED OR STORED IN THE VICINITY
OF THIS WATER HEATER, VENT-AIR INTAKE
SYSTEM OR IN ANY LOCATION FROM WHICH
FUMES COULD REACH THE WATER HEATER OR
VENT-AIR INTAKE SYSTEM.
CAUTION
If sweat fittings are to be used DO NOT apply heat to
the nipples on top of the water heater. Sweat the
tubing to the adapter before fitting the adapter to the
water connections. It is imperative that heat is not
applied to the nipples containing a plastic liner.
WARNING
Hydrogen gas can be produced in an operating
water heater that has not had water drawn from the
tank for a long period of time (generally two weeks or
more). Hydrogen gas is extremely flammable.
prevent the possibility of injury under these
conditions, we recommend the hot water faucet to be
open for several minutes at the kitchen sink before
you use any electrical appliance which is connected
to the hot water system. If hydrogen is present,
there will be an unusual sound such as air escaping
through the pipes as hot water begins to flow. Do
not smoke or have open flame near the faucet at the
time it is open.
To
Do not store or use gasoline or other
DANGER
flammable, combustible, or corrosive
vapors and liquids in the vicinity of this
or any other appliance.
IMPORTANT
Before proceeding, please inspect the
water heater and its components for
possible damage. DO NOT install any
water heater with damaged
components. If damage is evident
then please contact the supplier where
the water heater was purchased or the
manufacturer listed on the rating plate
for replacement parts.
WARNING
DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE
IF YOU ARE NOT CERTAIN OF THE FOLLOWING:
Liquefied petroleum gases/propane gas and natural
gas have an odorant added by the gas supplier that
aids in the detection of the gas.
Most people recognize this odor as a “sulfur” or
“rotten egg” smell.
Other conditions, such as “odorant fade” can cause
the odorant to diminish in intensity, or ”fade”, and not
be as readily detectable.
If you have a diminished sense of smell, or are in
any way unsure of the presence of gas, immediately
contact your gas supplier from a neighbor's
telephone.
Gas detectors are available. Contact your gas supplier,
or plumbing professional, for more information.
WARNING
FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED
3/4” X 3/4” TEMPERATURE AND PRESSURE RELIEF
VALVE WILL RELEASE THE MANUFACTURER FROM
ANY CLAIM THAT MIGHT RESULT FROM EXCESSIVE
TEMPERATURE AND PRESSURES.
CAUTION
Turn off or disconnect the electrical power supply to the
water heater before servicing. Label all wires prior to
disconnection when servicing controls. Wiring errors
can cause improper and dangerous operation. Verify
proper operation after servicing.
Page 3
Page 3
Page 4
4
Introduction
4
The new Bradford White TTW1, TTW2 & TW4 water heaters are designed to provide reliable
performance with enhanced standard features. New design features include reliable spark to
pilot ignition system, enhanced diagnostics, simplified servicing, significantly quiet operation
and additional vent lengths.
Spark to Pilot Ignition System - employing the spark to pilot ignition system promotes
reliable and consistent pilot and main burner ignitions to provide hot water on demand.
Integrated Immersion Thermostat/Gas Control Valve with LED - was developed for ease
of troubleshooting by providing simple diagnostic codes to pinpoint an installation or
component performance issue.
New Powerful Blower - will eliminate problems with difficult venting situations.
Quieter and Cooler Blower Operation - blower noise is significantly reduced for both
interior and exterior environments. Cooler operation increases blower life by reducing bearing
wear and noise.
Increased Vent Lengths - increased venting performance is achieved while maintaining
Energy Factor & FHSR performance.
The TTW1 (M1TW), TTW2 (M2TW) & TW4 water heaters use a combustion system were
flue gases are combined with dilution air to reduce the flue gas temperature in the blower. The
diluted flue gases are evacuated to the exterior through low temperature vent materials. The
gas control maintains water temperature, ignition sequence and regulates gas flow. A safety
circuit consisting of a pressure switch and blower temperature switch verifies proper conditions
exist for safe and reliable operation. If a situation outside of normal operating parameters
exists, the gas control diagnostic LED will flash a code to positively identify an operational
issue.
This service manual is designed to facilitate problem diagnosis and enhance service efficiency.
To further promote quicker service times the new gas valve can be removed and replaced
without draining the water heater. A special tool is required and will be provided with each gas
valve kit shipped from our Service Parts department.
Please read the service manual completely before attempting service on this new series of
power vent models.
Page
Page 5
How to Use This Manual
5
It is intended for this manual to be used by qualified service personal for the primary purpose of
troubleshooting and repair of the Bradford White TTW Series water heaters. Understanding the
sequence of operation section of this manual will contribute greatly to troubleshooting the water
heater.
The Honeywell WV4460E Electronic Gas Control will display error codes in the event of abnormal
operation. Error codes are listed in the troubleshooting chart beginning on page 13 of this service
manual. The troubleshooting chart will also indicate the probable cause for the error code and
direct the service professional to a service procedure to properly diagnose the abnormal operation.
In some difficult to diagnose conditions, it may be necessary to isolate the heater from the vent
system to determine the problem.
Contact the Bradford White technical support group immediately if diagnosis can not be made
using the methods described in this service manual.
Manometer:A liquid “U” tube type or a digital (magna-helic) type can be used. This
device is used to measure gas and/or air pressure and vacuum.
Multi-Meter:A digital type is strongly recommended. This device is used to measure
electrical values. The meter you select must have the capability to
measure volts AC, volts DC, Amps, micro-amps and ohms.
Electronic Probes:In some cases, standard multi-meter probes will damage or simply
not be effective to obtain certain voltage and ohm reading. It will be
necessary to have special electronic “pin” type multi-meter probes.
These probes are available at most electronic wholesale outlets.
Thermometer:Used to measure water temperature. An accurate thermometer is
recommended.
Water Pressure Gage:Used to measure water supply pressure. Also used to determine tank
pressure by adapting to the drain valve of the heater.
Gas Control Service Tool: BWC part number 239-45991-00. A specialized tool designed to remove
the gas control from gas control thermal well. Available from
your Bradford White parts supplier.
Various Hand Tools:Pipe wrench, channel locks, open end wrenchs (3/8",7/16",½"),
PS Fault Delay (failed open/close)Retry after 2 Minutes
Soft LockoutRetry after 5 Minutes
TCO Limit LockoutIndefinite (See Page 24 to reset)
Verify Resistive DelayRetry after 2 Minutes (repeats 5 times)
Simulated Resistive Load LockoutIndefinite (cycle power to reset)
Hardware Error LockoutIndefinite (self clears if fault clears for at least 15 seconds)
Specifications
Pilot
Pilot
Wiring Diagram
Wiring Diagram
Blower
Blower
Housing
Housing
B
B
Thermal
Thermal
Well
Well
Blower
Blower
Temperature
Temperature
Switch
Switch
Pressure
Pressure
Switch
Switch
C
C
Simulated
Flammable
Resistive
Vapor
Device
Sensor
Blower
Blower
Motor
Motor
Page 9
Page 9
Page 10
Sequence of Operation
10
1
Start Up.
Upon power up, the control runs a safe-start check with a typical start-up delay of 5 seconds.
2
Flammable Vapor.
To assure no outputs are energized if the “Flammable Vapor Sensor” is out of range, the control will test the
“Flammable Vapor Sensor” for proper operating range. If the “Flammable Vapor Sensor” is within range the
control resumes normal operation with no perceptible delay. If the “Flammable Vapor Sensor” is out of range,
the control LED immediately flashes 7 times with 3 second pause.
1
Thermostat calls for heat.
Prior to energizing blower, gas control checks safety circuit to insure the circuit is open. Normal switch positions
in the safety circuit are as follows:
a) Pressure switch normally open.
b) Blower temperature switch normally closed.
If the safety circuit is closed, the control waits 4 seconds, gas control LED flashes 2 times with 3 second pause.
Gas control waits 2 minutes then, blower runs for 30 seconds. This cycle repeats until safety circuit opens.
2
Blower energizes.
3
Pressure switch proves blower/vent system operation.
If the pressure switch does not close within 30 seconds, the control LED Flashes
The blower runs for 30 seconds every 2 minutes trying to get the pressure switch or blower temperature switch to
close. This cycle repeats as long as there is a call for heat.
4
Blower pre-purge period (2 seconds)
5
Trial for pilot ignition (90 seconds).
a) The gas control lights the pilot by activating spark igniter and gas flow to pilot burner.
b) If flame is not sensed within 90 seconds, igniter and gas flow are deactivated, blower will post purge and
control LED flashes 6 times with 3 second pause.
6
Main burner Ignition
After pilot flame is sensed, gas control activates main valve for main burner ignition. The gas control will ignore
flame and pressure switch signals for 3 seconds allowing for main burner to stabilize.
.3 times with 3 second pause
Page 10
Page 10
Page 11
Steady state operation.
11
7
During Steady State Operation the Control Monitors:
Thermostat temperature sensor-
blower will post purge for 15 seconds. Control LED flashes a short flash once every 4 seconds (idle) status
code.
Sequence of Operation
When set point temperature is satisfied, gas valve is shut down and
Pressure switch / Blower temperature switch-
If either switch opens, pilot valve and main valve is shut
down. The blower continues to runs for 30 seconds attempting to close the circuit. The control LED Flashes
3 times with 3 second pause.
Flame Sensor-
If flame is lost, pilot & main valve are shut down, blower runs for 15 seconds. Control attempts
to re-light pilot 4 times. If unsuccessful, Blower is shut down and control proceeds to 5 minute lockout. Control
re-attempts to light pilot starting at normal heating sequence #2.
8
Thermostat satisfies
9
Burner off.
10
Blower post purge (15 seconds).
(Control LED flashing once every 4 seconds).
1. Flammable Vapor Sensor Fault:
a) If the resistance is greater than 70,000 Ohms - the gas control immediately turns off all outputs. Control waits
and monitors resistance for 30 seconds. If the resistance is greater than 65,000 ohms after 30 seconds, the
gas control proceeds to verify resistive delay for 2 minutes and flashes 7 times then once with a three second
pause. This process is repeated 5 times until the control either returns to normal operation or proceeds to
flammable vapor lockout.
b) If the resistance is below 3000 ohms - The gas control immediately turns off all outputs and proceeds to flash
8 times then once with three second pause. The error self clears if the resistance returns to normal range for at
least 15 seconds.
2. Temperature Sensor Fault:
a) Temperature sensor detected open circuit - The gas control Immediately turns off all outputs and proceeds to
flash 8 times then three times with three second pause. The error self clears if the fault clears for at least 15 seconds.
b) Thermal well sensors not reading the same temperature within ±5.5 °F - The gas control Immediately turns off
all outputs and proceeds to flash 8 times then three times with three second pause. The error self clears if the fault
clears for at least 15 seconds.
c) Water temperature in excess of TCO (Temperature Cut Off) limit - The gas control immediately turns off pilot
main valve and proceeds to flash 4 times with 3 second pause. Blower continues to run until gas control is reset.
To reset control, rotate knob of temperature control to the minimum setting for at least 6 seconds before returning
to desired temperature setting.
Page 11
Page 11
Page 12
Sequence of Operation
12
3. Pressure Switch/Blower Temperature Fault:
a) Pressure switch closed at start of call for heat - The gas control waits four seconds then, proceeds to flash
2 times with 3 second pause. The control waits 2 minutes and then turns on blower for 30 seconds. The blower
turns off after 30 seconds and the control waits for pressure switch to open. Any time the Pressure switch opens,
the blower turns on (or stays on) and the control proceeds to waiting for pressure switch to close.
b) Pressure switch or blower temperature switch failed to close - The gas control runs the blower for 30 seconds
waiting for the pressure switch and/or blower temperature switch to close. If either switch does not close in 30
seconds, the blower turns off and the control flashes 3 times with 3 second pause. The gas control waits two
minutes before turning on the blower for another 30 seconds to see the circuit close. This cycle repeats as long as
there is a call for heat or until the circuit closes.
c) Pressure switch or blower temperature switch opens during burner operation - The gas control turns off the
pilot and main valve, runs blower for 15 seconds (inter-purge) waiting for pressure switch and/or blower
temperature switch to close. If either switch fails to close, the control proceeds as described in 3b above. If the
circuit closes again by the end of the inter-purge, the recycle counter is incremented, if the recycle count has
not reached its limit (4), another trial for ignition begins. If the recycle count has been reached, the gas control
turns off the blower and flashes 6 times then 2 times with 3 second pause. The gas control waits 5 minutes before
repeating ignition sequence.
4. Trial For Ignition Fault:
a) Pressure switch opens during trial - The gas control turns off igniter and pilot valve. The gas control proceeds
as described in 3b above. If the pressure switch closes within 30 seconds the gas control will continue with trial for
ignition starting at blower pre-purge.
b) Flame Not Sensed - The gas control energizes the spark igniter attempting to light the pilot and prove flame. If
flame is not sensed within 90 seconds, the igniter turns off, the pilot valve is closed and the gas control runs the
blower through post purge and flashes 6 times then once with 3 second pause. The control waits 5 minutes before
repeating the ignition sequence.
5. Flame Sensing Fault:
b) Flame lost during run - The gas control turns off pilot and main valves, runs blower for 15 seconds (inter purge).
The gas control increments the recycle count, if the recycle count has not reached its limit (4), another trial for
ignition begins. If the recycle count has been reached, the gas control turns off the blower and flashes 6 timesthen 3 times with 3 second pause. The gas control waits 5 minutes before repeating the ignition sequence.
c) Flame sensed out of sequence - the gas control only looks for pilot flame when the blower is running. If flame is
present when the pilot valve is not open, the gas control proceeds to wait for flame loss and flashes 5 times with 3
second pause. This continues until flame is lost, once the flame signal is lost, the control flashes 6 times then 4times with 3 second pause. The control waits 5 minutes before repeating the ignition sequence.
Page 12
Page 12
Page 13
Observe green LED indicator on
13
Electronic gas control. Error flash codes
are displayed with a three second pause
before repeating. Check and repair the
system as noted in the troubleshooting
table below.
Troubleshooting
Green LED
Indicator
LED Status
None, control LED not
on or flashing
Short flash, once every
four seconds
“Heartbeat”, alternates
bright/dim
Short flash once per
second
Two flash, three
second pause
Three flash, three
second pause
Four flash, three
second pause
Five flash, three
second pause
Control
Status
No electrical
power
Stand-by mode,
Waiting for call for
heat (no fault).
Thermostat calling
for heat (no fault).
Weak pilot signal
on last call for
heat.
Pressure switch
not workingclosed position.
Pressure switch
or blower temp.
switch not working
-open position.
Excessive tank
temperature.
System must be
reset. (See Pg. 24)
Undesired-false
pilot flame
present.
Probable Cause
Control power switch in “OFF” position.
Supply voltage interrupted.
Temperature demand is satisfied
Tank temperature below set point of thermostat.
1. Unstable pilot.
2. Pilot tube block or restricted.
3. Oxidation build up on pilot electrode.
4. Wire damage to pilot assembly or bad
connection at gas valve.
1. Pressure switch tubing kinked or blocked.
2. Blocked pressure tap on switch or blower.
3. Faulty pressure switch.
1. Vent blockage or improper vent configuration.
2. Pressure switch tubing kinked or blocked.
3. Faulty pressure switch.
4. Blower not spinning up to speed.
5. Blower temp or exhaust temp too high
6. Faulty blower temperature switch.
1. Thermal well sensor out of calibration.
2. Faulty gas control.
3. Pluming leak.
4. Tank not filled with water.
1. Pilot valve stuck in open position.
Service
Procedure
Turn power on
Normal operation.
Adjust thermostat to
temp level
Normal operation.
Adjust thermostat to
temp level
1. Page 15
2-4. Page 17
Page 18
1. Check vent or vent tables.
2 & 3 Page 18
4. Page 20
5 & 6 Page 22
1. Page 24
2. Replace gas control,
page 24
Replace gas control,
page 24
Page 13
Page 13
Page 14
Troubleshooting
14
LED Status
Six-one flash, three
second pause
Six-two flash, three
second pause
Six-three flash, three
second pause
Six-four flash, three
second pause
Seven flash, three
second pause
Eight-one flash, three
second paus
Control
Status
Failed to light
pilot.
System auto
resets.
Pressure switch
or blower temp
switch opened
during burner
operation.
System auto
resets.
Pilot flame
extinguished.
System auto
resets.
Undesired-false
pilot flame
sensed.
System auto
resets.
Flammable
Vapor Sensor
fault detected.
Flammable
Vapor Sensor
out of
specification.
Probable Cause
1. Unstable pilot.
2. Pilot tube blocked or restricted.
3. Oxidation build up on pilot electrode.
4. Wire damage to pilot assembly or bad
connection at gas valve.
1. Vent blockage or improper vent configuration.
2. Pressure switch tubing kinked or blocked.
3. Faulty pressure switch.
4. Vent termination being affected by wind
5. Blower not spinning up to speed.
6. Blower temp or exhaust temp too high
7. Faulty blower temperature switch.
1. Unstable pilot.
2. Pilot tube blocked or restricted.
3. Oxidation build up on pilot electrode.
4. Wire damage to pilot assembly or bad
connection at gas valve.
5. Insufficient combustion air.
6. Gas pressure is out of specification.
Pilot valve stuck in open position.
WARNING: EXPLOSION HAZARD
• Indicates gasoline vapors were detected at potentially
explosive levels.
• Verify no gasoline vapors are still present.
• Reset the control by cycling power to the appliance or by
cycling the ON/OFF switch.
• Replace the Flammable Vapor Sensor element if a gasoline
spill event occurred.
• Very Flammable Vapor Sensor (FVS) resistance is not below
25 KΩ.
• Check wiring to FVS and insure it is not shorted.
• Replace control if everything above checks out OK.
Service
Procedure
1. Page 15
2-4. Page 17
1. Check vent or vent tables.
2 & 3 Page 18
4. Refer to venting section of
installation manual
5. Page 20
6 & 7 Page 22
1. Page 15
2-4. Page 17
5. Refer to installation manual
Replace gas control,
page 26
Page 28
Page 28
Eight-three flash, three
second pause
Eight-four flash, three
second pause
Page 14
Thermal well
sensor damaged
or unplugged
Gas valve fault
detected.
1. Damage to thermal well wire.
2. Thermal well sensor resistance out of range.
1. Control needs to be reset.
2. Control is wet or physically damaged.
Page 24
1. Interrupt power supply
2. Replace gas control,
page 26
Page 14
Page 15
TTW SERVICE PROCEDURE I
15
Burner Operation Inspection,
Adjustment, Cleaning and Replacement
Burner Inspection and Air Shutter Adjustment.
At periodic intervals (every 6 months) a visual inspection should be made of the pilot and main burner for proper
operation and to assure no debris is accumulating.
Pilot flame should be stable, some causes for an unstable pilot flame are:
a) Water heater vent is less than the allowable vent length.
b) Gas pressure is out of specification.
c) Pilot flame not fully engulfing spark/flame sensor.
Main burner should light smoothly from pilot and burn with a blue flame with a minimum of yellow tips.
Steel burner models self adjust air to gas ratio mixture and do not have an adjustable air shutter. Cast iron burner can
have the gas and air mixture properly proportioned by adjusting the air shutter on the mixer face of the main burner
(see cast iron burner adjustment below).
Main burner must be free from any debris accumulation that may effect burner operation (see burner cleaning
procedure on page 16).
Cast Iron Burner Air Shutter Adjustment
WARNING
Inner door and burner components may be HOT when performing this operation. Take
necessary precaution to prevent personal injury.
Step 1.With main burner in operation, remove outer jacket door and inner door per service procedure XIII on
page 34.
Step 2.To adjust for proper burning, loosen the air shutter nut, rotate the air shutter to close the opening in the
burner, then slowly rotate the air shutter open until flame becomes as blue as possible with a minimum of
yellow tips. Tighten the air shutter nut.
Too much air will cause the flame to lift off the burner ports and create noisy burner operation.
Too little air will result in soot formation.
Step 3.Reinstall inner door and observe burner operation. Burner should operate as adjusted in step 2. If not,
repeat air shutter adjustment compensating for proper burner operation with inner door closed.
Air Shutter Nut
Air Shutter Nut
Air Shutter
Air Shutter
Page 15
Page 15
Page 16
TTW SERVICE PROCEDURE I
Burner Cleaning
Step 1.Position gas control power switch to the
“OFF” position and unplug heater from wall
outlet.
Step 2.Turn off gas supply to water heater.
Step 3.Remove outer jacket door and inner door per service
procedure XIII on Page 34.
Step 4.Disconnect pilot tube (7/16 wrench) and
feedline (¾ wrench) from gas control.
Step 5.Disconnect igniter/flame sensor wire from gas control.
Step 6.Remove burner assembly from combustion chamber.
Step 7.Thoroughly inspect burner surface area and burner port area and
remove any loose debris.
16
Burner Operation Inspection,
Adjustment, Cleaning and Replacement
Burner Cleaning
Remove Outer
door.
Step 1.Position gas control power switch to the
“OFF” position and unplug heater from walloutlet.
Step 2.Turn off gas supply to water heater.
Step 3.Remove outer jacket door and slide inner door open from left to
right.
Step 4.Disconnect pilot tube (7/16 wrench) and
Igniter/flame
sense wire
feedline (¾ wrench) from gas control.
Step 5.Disconnect igniter/flame sensor wire from gas control.
Step 6.Remove burner assembly from combustion chamber.
Step 7.Thoroughly inspect burner surface area and burner port area and
remove any loose debris.
Step 8.For cast iron burners, inspect for any debris build up inside
burner casting.
Burner
surface area
Slide inner door open
from left to right.
Feedline nut
Pilot tubing nut
Burner
port area
Step 9.Unscrew burner from main burner
orifice. On cast iron burners, loosen
air shutter nut and unscrew feedline
Step 10.Remove main burner orifice from
from burner.
feedline (½" wrench on steel
burners, 3/8" wrench on cast iron)
inspect orifice, clean or replace if
necessary.
Step 11.Reassemble burner and reinstall into water heater. Restore gas supply
and check for gas leaks.
Step 12To resume operation follow the instruction located on the lighting
instruction label or the lighting instruction located in the installation
and operating manual.
Page 16
Main burner
orifice
L.P. Main burner
orifice. Left hand
thread
Page 16
Page 17
TTW SERVICE PROCEDURE II
Pilot Inspection, Testing and Replacement
Step 1.Position gas control power switch to the
“OFF” position and unplug heater from wall
outlet.
Step 2.Turn off gas supply to water heater.
Step 3.Remove outer jacket door and inner door per service
procedure XIII on page 34.
17
Pilot testing, Cleaning and Replacement
Pilot Inspection, Testing and Replacement
Step 1.Position gas control power switch to the
“OFF” position and unplug heater from walloutlet.
Step 2.Turn off gas supply to water heater.
Step 3.Remove outer jacket door and slide inner door open from left to
right.
Remove Outer
door.
Igniter/flame
sense wire
Slide inner door open
from left to right.
Step 4.Disconnect pilot tube nut (7/16 wrench) and feedline nut
(¾ wrench) from gas control.
Step 5.Disconnect igniter/flame sense wire from gas control.
Step 6.Remove burner assembly from combustion chamber.
Step 7.Remove pilot assembly from feedline (¼" nut driver).
Step 8.Visually inspect igniter/flame sense wire for damage. Replace
pilot if damage is found.
Step 9.With a multi-meter set to the ohms setting, check continuity
through igniter/flame sense wire. Replace pilot if no continuity.
Step 10.Visually inspect igniter/flame sense electrode for deterioration.
Replace pilot as necessary. Electrode should not be in contact
with pilot hood, If so, carefully adjust electrode to a gap
distance of 3/32" (.09) from pilot hood.
Step 11.Visually inspect igniter/flame sense electrode for oxidation
build up. Carefully clean any oxidation using very fine emery
cloth.
Step 12.Visually inspect pilot tubing for kinks or cracks. If damage is
found replace pilot.
Ferrule
nut
Pilot
tubing
Igniter/flame
sense wire
Pilot
orifice
Feedline nut
Pilot tubing nut
Pilot
hood
Igniter/flame
sense electrode
Step 13.Inspect pilot tubing and pilot orifice for blockage:
a) Remove ferrule nut from bottom of pilot assembly (7/16" wrench).
b) Remove pilot tube and pilot orifice.
c) Inspect pilot tubing and pilot orifice for blockage. Clean
or replace as necessary.
Step 14.Reassemble pilot and install to feedline. Reinstall burner assembly to water heater. Restore gas supply
Step 15To resume operation follow the instruction located on the lighting instruction label or the lighting
and check for gas leaks.
instruction located in the installation and operating manual.
Page 17
Page 17
Page 18
TTW SERVICE PROCEDURE III
18
Pressure Switch Testing and
Replacement
Pressure Switch Testing
WARNING
115 volt potential exposure. Use caution
Step 1.Position power switch on gas control
making voltage checks to avoid personal injury.
to the “OFF” position.
Step 2.Remove the three screws (Phillips screw driver) from control access cover on blower assembly and
remove cover (see photo 1).
Step 3.Carefully remove pressure switch from blower housing (see photo 2)
With steps 1,2 & 3
complete,
disconnect wire leads from
pressure switch.
Use a multi-meter set to the
ohms setting. With blower off,
check across pressure
switch terminals.
Are switch contacts open?
(no electrical continuity)
Y
1
Pressure switch
wire leads
N
Check tubing and pressure
tap on switch for blockage.
Is there blockage?
Y
Slide pressure switch in direction
of arrow while tilting slightly away
from blower housing.
N
Replace switch
(see page 19)
2
Pressure Switch
Position gas valve power
switch to the “ON” position
and adjust thermostat
to call for heat,
this will start the blower.
Check with multi-meter, do
pressure switch contacts
close with blower running?
Y
Switch contacts are OK.
See safety circuit trace
(page 29)
Check tubing and
N
pressure tap on
switch for blockage.
Is there blockage?
Page 18
Clear blockage
Y
N
Y
Is vent
system
blocked
Is vent system length
N
within vent table
specifications
listed on pages 7 & 8
N
Reconfigure vent
system to be
compliant with
vent tables.
Y
See blower testing
Y
(page 20)
Is blower OK?
N
Correct blower
problem.
Page 18
Page 19
TTW SERVICE PROCEDURE III
19
Pressure Switch Testing and
Replacement
Pressure Switch Replacement
WARNING
115 volt potential exposure. Use caution
to avoid personal injury.
Step 1.Position gas control power switch
to “OFF” position.
Step 2.Remove the three screws (Phillips screw driver) from control access cover on blower assembly and
remove cover (see photo 3).
Pressure Switch
34
Step 3.Carefully remove pressure
switch from blower
housing (see photo 4)
Slide pressure switch in direction
of arrow while tilting slightly away
from blower housing.
Step 4.Disconnect tubing from
5
pressure switch.
(see photo 5)
6
Step 5.Disconnect yellow wires
from pressure switch
(see photo 6)
Step 6.Reconnect wires from step 5 to new pressure switch.
Step 7.Reconnect tubing to new pressure switch.
Step 8.Carefully position pressure switch into blower housing.
Step 9.Position gas control power switch to “ON” position and verify proper heater operation.
Step 10.Replace control access cover from step 2.
Page 19
Page 19
Page 20
TTW SERVICE PROCEDURE IV
20
Blower Testing and Replacement
Blower Testing
115 volt potential exposure. Use caution when
making voltage checks to avoid personal injury.
Step 1.Position gas control power switch
to “ON” position and adjust control to call for heat.
Step 2.Remove the three screws (Phillips Screw driver)
from control access cover on blower assembly and
remove cover (see photo 7).
Does blower energize
Within 2 minutes?
N
89
Does blower energize after
2 minutes, run for 30
seconds and shut down?
N
pressure switch
Y
tubing from blower.
(see photo 8)
Pressure tap
Pressure
switch tubing
Y
See pressure
switch testing
Disconnect
Page 18
manometer to
pressure tap of
(see photo 8)
Determine voltage
problem and correct.
7
Connect
blower.
1112
Disconnect vent
system from top of
blower and remove
With blower running, and exhaust
adapter removed from top of
pressure of -2.15" to -2.30" W.C.?
N
WARNING
vent adapter.
(see photo 10)
blower, is there a negative
N
Is there 115vac across
blue and green wires
(see photo 13)
Y
Y
Remove exhaust
adapter
10
Blower OK
Replace blower
Disconnect cord set
shown in photo 9. Is
there 115VAC across
terminals shown in
photo 11
N
Is there 115 VAC
at wall outlet?
Y
Check power cord
for damage.
N
Replace blower
Y
N
Y
Is there 115VAC
across terminals
shown in photo 12 ?
Incorrect supply
voltage polarity
Determine
power source
problem and
correct.
Repair or replace
power cord
Page 20
Y
Reconnect cord set
N
Replace
cord set
shown in photo 9, is
there 115VAC between
blue wire and green
ground wire
(see photo 13)
N
Does cord set
N
have electrical
continuity?
Y
Replace
gas control
Y
Replace blower
Green ground
wire
Shown with pressure
switch removed.
13
Blue wire
Page 20
Page 21
Blower removal
21
Step 1.Position gas control power switch to the “OFF” position.
Step 2.Unplug blower power cord from wall outlet.
Remove exhaust
adapter and retain for
use on new blower.
Step 3.Disconnect vent system from exhaust adapter on top of
blower.
Step 4.Remove exhaust adapter from blower (blade screw driver)
and retain for use on new blower
Step 5.Unplug cord sets from blower.
Step 6.Remove the three blower mounting screws
(¼" nut driver).
TTW SERVICE PROCEDURE IV
Blower Testing and Replacement
Blower Mounting
Screws
Step 7.Remove blower with gasket from water heater.
Blower Installation
Step 8.Clean any debris from jacket head of water heater.
Step 9.Set new blower with gasket in place using locating pins on
blower flange to line up with location holes in jacket head.
Be sure not to damage gasket.
Step 10Secure blower in place using mounting screws from step 6.
Step 11.Re-install exhaust adapter from step 4.
Step 12.Reconnect vent system to
exhaust adapter.
Step 13.Reconnect cord sets from step 5.
Step 14.Plug blower power cord into wall outlet.
Step 15.Position gas control power switch to the “ON” position.
Locating Pins
on blower flange
Pin location holes in
jacket head
Blower
Cord Sets
Step 16. Verify proper blower operation.
Page 21
Page 21
Page 22
TTW SERVICE PROCEDURE V
22
Blower Temperature Switch Testing
and Replacement
Blower Temperature Switch
Testing.
Step 1.Position power switch on gas control
to the “OFF” position.
Step 2.Remove the three screws (Phillips screw driver) from
control access cover on blower and remove cover (see
photo 14).
Step 3.Locate blower temperature switch (see photo 15)
Switch Setting
Opens on rise @ approximately 165°F
Auto resets on fall @ approximately 130°F
Cool switch to
below 130°F
115 volt potential exposure. Use caution
WARNING
to avoid personal injury.
15
Air mixing inlet
Blower temperature
14
switch location
Disconnect wire leads to
switch. Using a multi-meter
set to the ohms setting, is
there continuity between
the switch terminals?
Y
Reconnect wire leads and
observe heater operation.
Do exhaust gas
temperatures rise to or
above 170°F
with vent connected?
N
Do switch
contacts open?
N
Switch OK
N
Y
Replace switch
Y
contacts open?
Replace switch
(see page 23)
(see page 23)
N
Do switch
Y
Exhaust
temperature is
too hot.
Common causes for
high exhaust temperature
1. Vent length is below minimum allowable.
2. Vent diameter not to specification.
3. Restricted dilution air inlet.
4. Missing or deteriorated flue baffle.
5. Gas pressure is out of specification.
Page 22
Page 22
Page 23
TTW SERVICE PROCEDURE V
23
Blower Temperature Switch Testing
and Replacement
Blower Temperature Switch
Replacement.
Step 1.Position gas control power switch to the “OFF” position
and unplug heater from wall outlet.
Step 2.Remove the three screws (Phillips screw driver) from the
control access cover on blower and remove cover.
(see photo 16)
Step 3.Locate blower temperature switch (see photo 17)
Step 4.Disconnect red and yellow wire leads from switch.
WARNING
115 volt potential exposure. Use caution
to avoid personal injury.
16
17
Blower temperature
switch location
Step 5.With an appropriate tool such as side cutters, snip the
retaining lug from the blower housing to allow removal of
temperature switch (see photo 18).
Step 6.Remove switch from blower housing.
Step 7.Install new switch. Be sure switch is properly seated in
mounting area.
Step 8.Reconnect red and yellows wires to new switch. Wires are
interchangeable with either terminal.
Step 9.Position gas control power switch to the “ON” position
and verify proper heater operation.
Step 10.Replace control access cover from step 2.
18
Snip retaining lug
from blower housing
Page 23
Page 23
Page 24
Gas Control Testing
24
See pages 29 & 30 for gas control
voltage testing.
TTW SERVICE PROCEDURE VI
Gas Control/Thermal Well Testing and
Replacement
Thermal Well Testing
If Control has gone into TCO lockout due to
excessive tank temperature (four flash, 3 second
pause) reset control by rotating knob of temperature
control to the minimum setting for at least 6 seconds
before returning to desired temperature setting.
Observe heater operation. If control
continues to lockout due to
excessive tank temperature,
proceed to thermal well testing to
determine cause.
Thermal well testing
Position gas control power switch to
the “OFF” position and disconnect
thermal well harness from gas
control.
Using a multi-meter set to the
Ohms setting, determine the
resistance of thermal well sensor
(see caution photos 19 & 20)
Disconnect thermal
well wire harness
19
20
CAUTION
DO NOT use standard multimeter probes for this test.
Doing so will damage connector. Use special pin type
electronic probes or small diameter wire pins inserted
into connector.
Using a multi-meter set to the ohms setting, insert one meter probe (see caution)
into center wire position of thermal well connector, insert the second probe (see
caution) into either of the outside wire positions (see photo 19).
Once the thermal well resistance values are known, the water
temperature must also be known to determine if the resistance
values are correct. See page 25 to obtain water temperature.
Are thermal well resistance values correct?
Y
Replace gas control
(see page 26)
Page 24
Alternate the probe on the outside position to the opposite outside wire position
(see photo 20).
N
Replace thermal well
(see page 26)
Page 24
Page 25
TTW SERVICE PROCEDURE VI
25
Gas Control/Thermal Well Testing and
Replacement
WARNING
Stored water may be HOT
when performing the following steps in this procedure.
Take necessary precaution to prevent personal injury.
Determine Water Temperature Inside Tank
Note: It is important to understand once the resistance for the thermal well is determined from page 24, water flow
through the heater should not occur. Prior to performing the steps below, turn off the cold water supply to the
water heater. This will prevent cold water flow into the tank affecting the resistance value of thermal well.
Step 1.Position gas control power switch to “OFF” position.
Step 2.
Draw approximately 1 quart of water from drain valve into container and immediately measure water
temperature using an accurate thermometer. It may be necessary to open a hot water faucet to allow
heater to drain.
Step 3.Using the chart below, determine correct resistance value for the water temperature from step 2.
Example: If temperature of water is 84°F, then the resistance through the sensor would be
8449 (see shaded area). NOTE: Sensor resistance increases as the temperature
falls.
Gas Control & Thermal Well Removal From Water Heater
Gas Control
Gas Control
Step 1.Position gas valve power switch to the “OFF”
position and Unplug Heater from power supply.
Thermal
Thermal
Well
Well
Step 2.Drain heater to a point below the gas
control level.
Step 3.Turn off gas supply to water heater and
disconnect gas piping from gas control.
Step 4.Disconnect wire harnesses and burner assembly
from gas control.
Step 5.Remove gas control & thermal well by rotating flats of Thermal Well counter clockwise (1-5/16"wrench).
Gas Control Removal From Thermal Well
Follow the steps below allows removal gas control from thermal well without
removing thermal well from tank.
Step 1.Position gas control power switch to the “OFF” position and unplug water heater from power supply.
Step 2.Turn off gas supply to water heater and disconnect gas piping from gas control.
Step 3.Disconnect wire harnesses & burner assembly from gas control.
Step 4.Using gas control service tool (239-45991-00) available from your BWC parts supplier, Insert tool into
back of gas control (see photos below)
Insert tool from
back of control
Service tool shown
inserted in to back
of control
Step 5.Pivot tool towards heater as far as possible (see photo below). Lift straight up on gas control. The
control should move about 1/8". At this point, remove tool not allowing the control to fall back. With
tool removed, lift straight up on control to remove completely from Thermal Well.
With service tool inserted, pivot tool back towards
heater as far as possible. Lift straight up on control,
control will move 1/8". Remove tool and continue to lift
straight up on control to remove from Thermal Well.
Page 26
View from back of
control for clarity
Page 26
Page 27
Gas Control Assembly to Thermal Well
27
Step 1.Install threaded end of thermal well into tank. Be sure
thermal well flange is positioned as shown in photo 24
for proper control alignment.
Step 2.Route wire leads back into relief opening.
(see photo 24)
Step 3.Align slots located on thermal well flange with tabs
located on back of gas control (see photos 24 & 25)
TTW SERVICE PROCEDURE VI
Gas Control & Thermal Well Testing
and Replacement
24
Thermal well
flange slots
Step 4.Carefully push control back onto thermal well flange
as far as possible towards water heater. Slide control
down to lock into position.
Step 5.Install burner and connect pilot and feedline to gas
control.
Igniter/sensor
Igniter/sensor
connection
connection
Step 6.Reconnect wire harnesses to gas control
Step 7.Reconnect gas piping to gas control.
Ground Wire
Ground Wire
connection
connection
Step 8.To resume operation, follow the
5 pin
blower harness connection
blower harness connection
5 pin
3 pin
3 pin
thermal well connection
thermal well connection
Route wires
through relief
opening
25
Gas control Tabs
per the illustration.
Restore gas supply and check for gas
leaks.
instruction located on the lighting
instruction label or the lighting instruction
located in the installation and operation
manual.
Flammable Vapor
Flammable Vapor
Sensor
Sensor
Page 27
Page 27
Page 28
Flammable Vapor Device Testing
28
Step 1.Position power switch on gas control to the
“OFF” position.
Step 2.Disconnect flammable vapor sensor from
gas control.
Step 3.Using a multi-meter set to the ohms setting
check resistance of flammable vapor sensor.
(see caution below)
Resistance must be within 3,000 ohms and
48,000 ohms. If outside of this range replace
flammable vapor sensor.
TTW SERVICE PROCEDURE VII
Flammable Vapor Device Testing
Multi-meter set to
ohms setting
Electronic
“pin type”
Meter Probes
Flammable Vapor
Sensor
CAUTION
DO NOT use standard multimeter probes for this test.
Doing so will damage connector. Use special electronic
“pin type” probes or small diameter wire pins inserted
into connector.
Flammable Vapor
Sensor
Page 28
Page 28
Page 29
TTW SERVICE PROCEDURE VIII
29
Safety Circuit Voltage Trace
Safety Circuit Voltage
Trace
NOTE: This procedure assumes a cool tank.
Remove three screws (Phillips Screw driver) from control access
cover on blower and remove cover (see photo 26).
Position gas control switch to the “ON”
position and adjust thermostat dial to call
for heat, Is there 10 to 13 VAC between
red wire leading to blower temperature
switch and green ground wire?
Blower must be running during this
voltage check.
(see photo 27)
Y
Is there 10 to 13 VAC between yellow
wire leading from pressure switch and
green ground wire?
(see photo 27)
Y
Is LED on gas valve flashing
N
N
the “heartbeat” code
(alternating bright/dim)
Verify 115VAC to gas
control (see page 30)
115 volt potential exposure. Use caution
making voltage checks to avoid personal injury.
N
Y
Is there continuity
through blower
temperature switch?
(see page 22)
WARNING
26
No voltage from gas control,
call for technical support.
Y
N
Check for loose or
broken wire
connection at switch
terminals
Do you hear or can you
see the igniter sparking?
Y
Safety circuit
voltage is OK.
If burner does not light,
observe LED flash code
on gas valve and refer to
troubleshooting section
on page 13
Determine cause of blower
Correct igniter/
sensor problem.
N
Check igniter/sensor
(see page 17)
is igniter/sensor OK?
27
Y
temperature switch
activation and correct.
Faulty cord set or
gas control.
Green ground wire
Red wire leading to
blower temp. switch
Yellow wire
leading from
pressure switch
Page 29
Page 29
Page 30
TTW SERVICE PROCEDURE IX
30
115 VAC Trace
115 VAC Circuit Trace
115 volt potential exposure. Use caution
WARNING
making voltage checks to avoid personal injury.
Step 1.Verify 115VAC and proper polarity at wall outlet.
Step 2.With unit plugged in and control power switch in the “ON” position verify LED status.
LED status
None, Control LED not
on or flashing.
Disconnect cord set as
shown in photo 28
Using a volt meter set
to volts AC, is there
115VAC across
terminals shown in
photo 29 ?
Y
Is there 115VAC
across terminals
shown in photo 30 ?
N
Incorrect supply
voltage polarity
N
Y
LED status
Short flash, once every
four seconds.
Waiting for
call for heat.
28
Reconnect cord set
shown in photo 28.
Disconnect wire harness
from gas control
(see photo 31).
LED status
“Heartbeat”, alternates
bright/dim.
Thermostat calling
for heat
Check for damage to
AC supply power cord.
N
Replace Blower
29
Y
Wire harness
LED status
Various flashing error
codes.
Verify error code as
listed on page 13
30
Repair damage
31
Locate black & white wires at
connector, It may be necessary to pull
back wire sheath to identify wire colors.
(see photo 32)
Is there 115VAC
across black & white
wires as shown in
photo 32?
N
Call for technical
support.
Y
Replace gas
control.
Page 30
32
Wire sheath pulled back to
identify wire colors
Check for 115VAC between black & white wires.
-NOTE-
Electronic meter probes required. Use care not to
damage connector during this check.
Page 30
Page 31
TTW SERVICE PROCEDURE X
31
Dip Tube
Inspection and replacement
Dip Tube Inspection and Replacement
WARNING
Water Heater components and stored water may be HOT
steps in this procedure. Take necessary precaution to prevent personal injury.
Step 1.Position on/off switch of gas control valve to “OFF” position and unplug water heater from wall outlet.
Step 2.Turn off cold water supply to water heater. Connect hose to drain valve of water heater and route to an
open drain. Open a nearby hot water faucet to vent heater for draining. Open drain valve of water
heater and allow heater to drain to a point below the inlet connection nipple.
Step 3.Disconnect inlet nipple from plumbing system.
Step 4With an appropriate tool such as a pipe wrench, remove inlet nipple/dip tube from the water heater.
Use caution not to damage pipe threads.
when performing the following
Step 5.Visually inspect inlet nipple/dip tube. Inlet nipple/dip tube should be free of cracks and any blockage.
Hydro-jet slots should be open and free of any blockage.
Any damage such as cracks, restriction due to deformation or unintentional holes are not field
repairable and the inlet nipple/dip tube must be replaced.
Step 6.Upon completion of inspection or subsequent replacement, reinstall inlet nipple/dip tube into water
heater. Connect nipple to plumbing system, resume water supply and refill with water.
Step 7.To resume operation follow the instructions located on the lighting instruction label or the lighting
instructions located in the installation and operation manual.
Page 31
Page 31
Page 32
TTW SERVICE PROCEDURE XI
32
Anode
Inspection and replacement
Anode Inspection and Replacement
WARNING
Water Heater components and stored water may be HOT when performing the following
steps in this procedure. Take necessary precaution to prevent personal injury.
Step 1.Position on/off switch of gas control valve to the “OFF” position and unplug water heater from wall
outlet.
Step 2.Turn off cold water supply to water heater. Connect hose to drain valve of water heater and route to an
open drain. Open a nearby hot water faucet to vent water heater for draining. Open drain valve of
water heater and allow water heater to drain to a point below the outlet connection nipple.
Step 3.Disconnect outlet nipple from plumbing system.
Step 4With an appropriate tool such as a pipe wrench, remove outlet nipple/anode from the water heater. Use
caution not to damage pipe threads.
Step 5.Visually inspect outlet nipple/anode. Outlet nipple/anode should show signs of depletion, this is
normal. If depletion is ½ of the original anode diameter (approximately ¾” diameter), replacement is
recommended. If any of the steel core of the anode is exposed, replacement is recommended.
Step 6.Upon completion of inspection or subsequent replacement, reinstall outlet nipple/anode into water
heater. Connect nipple to plumbing system, resume water supply and refill with water.
Step 7.To resume operation, follow the instructions located on the lighting instruction label or the lighting
instructions located in the installation and operation manual.
Page 32
Page 32
Page 33
Remove blower to gain access to
33
flue baffle
TTW SERVICE PROCEDURE XII
Flue Baffle
Inspection and replacement
Disconnect vent
system from exhaust
adapter.
Step 1.Position gas control power switch to the “OFF” position
and unplug blower from wall outlet.
Step 2.Disconnect vent system from exhaust adapter on top of
blower.
Step 3.Unplug cord sets from blower. (see photo 33).
Step 4.Remove the three blower mounting screws
(¼" nut driver) (see photo 33).
Step 5.Remove blower with gasket from water heater.
Step 6.Remove flue baffle from Heater (see photo 34).
Step 7.Inspect baffle for deterioration, missing restrictors.
Clean any scale or debris build up. Replace with new
baffle as necessary.
Step 8.Reinstall baffle into flue tube. Be sure baffle
hanger tab are inserted into notch location at the
top of the flue tube (see photos 35 & 36).
Step 9Check Burner to insure no scale has accumulated during
this operation. See burner cleaning procedure on page 15.
Step 10.Reinstall blower on water heater. Connect vent
system and cord sets to blower. Plug water heater
into wall outlet.
33
Blower
Cord Sets
34
35
Blower Mounting
Screws
Flue Baffle
Step 11.To resume operation follow the lighting instruction
located on the lighting instruction label or the lighting
instruction located in the installation and operation
manual.
Flue tube
notch
36
Baffle shown
installed in flue
tube notch.
Page 33
Page 33
Page 34
Inner Door Removal Procedure
34
Step 1. Position gas control power switch to the “OFF” position.
Step 2. Remove outer jacket burner access door
Step 3. Inner Door Removal.
a) Remove (2) 1/4" hex drive screws from right side inner door.
b) Remove (2) 1/4" drive screws from flange section of inner door.
c) Remove (2) 1/4" drive screws from left side inner door.
d) Remove inner door and inspect per step 4.
TTW SERVICE PROCEDURE XIII
Inner Door/Gasket Removal, Inspection
Replacement and Reinstallation
¼" Hex Drive Screws
Right and Left Side Inner Door.
¼" Hex Drive Screws at
Flange Area of Inner Door
Step 4. Fully inspect inner door gaskets for the following:
>Tears>Other imperfections that will inhibit proper seal
>Missing Material >Gasket adhesion to inner door
>Cracks>Material left on combustion chamber (around opening)
>Dirt or debris
If the gasket is not effected by any of the above, gasket replacement is not required. If replacement is
required,
proceed to Inner Door Gasket Replacement Procedure.
Inner Door Gasket Replacement
Procedure.
WARNING
If the information in these instructions is not
followed exactly, a fire or explosion may result causing
property damage, personal injury or death.
Step 5. After inspection of inner door as noted in step 4, completely remove gasket and adhesive residue from right
and left side inner doors as needed.
Step 6. Use RTV sealant (recommended bead size 1/8") to secure the inner door gasket to the inner door sections
(right & left). Refer to illustration on next page for proper application. Note the overlap configuration in the
flange area of the inner door. Set the flange section first, this will help to achieve the proper over lap position.
Page 34
Page 34
Page 35
TTW SERVICE PROCEDURE XIII
35
Inner Door/Gasket Removal, Inspection
Replacement and Reinstallation
Installation of Inner Door With Gasket.
Step 7.Clean any residual gasket residue or other debris
from combustion chamber surface before
installing the inner door/gasket assembly.
Step 8.Place the left side inner door into position first.
Firmly position the radiused channel of the inner
door around the feedline. Using the 1/4” hex drive
screws from step 3c, secure left side inner door in
place. DO NOT OVER TIGHTEN SCREWS.
Step 9Position pilot tube and igniter/sensor wire
against left side inner door flange gasket.
DO NOT ROUTE
CHANNEL WITH FEEDLINE.
THROUGH RADIUSED
WARNING
Stripped fastener connections may allow
for seal breach of inner door. A seal
breach may result in a fire or explosion
causing property damage, personal injury
or death. Do not over tighten screws in
steps 8, 10 and 11.
If a fastener connection is stripped,
contact the manufacturer listed on the
water heater rating plate.
Position pilot tubing and
igniter/sensor wire.
Radiused Channel
for Feedline
Page 35
Page 35
Page 36
TTW SERVICE PROCEDURE XIII
36
Inner Door/Gasket Removal, Inspection
Replacement and Reinstallation
Step 10.Firmly place right side inner door flange against the left side inner door flange and secure with two ¼” drive
screws from step 3b. DO NOT OVER TIGHTEN SCREWS.
Step 11.Align right side inner door to combustion chamber and verify the fastener holes of the combustion
chamber are aligned with the right side inner door slotted opening. Verify seal integrity around
combustion opening. Secure right side inner door using 1/4” hex drive screws from step 3a. DO NOTOVER TIGHTEN SCREWS. Verify both left and right sides of the inner door are properly positioned and
sealed against the combustion chamber.
Secure flange with
¼" drive screws.
Verify threaded hole
alignment with slotted
openings in inner door.
Step 12.Replace outer jacket burner access door.
Step 13.To resume operation follow the instructions located on the lighting instruction label or the lighting instructions
located in the installation and operation manual.
Page 36
Page 36
Page 37
ScreenLok®Flame Arrestor Cleaning
37
ScreenLok®Flame Arrestor Cleaning:
Step 1.Position Gas Control Power Switch to the OFF position.
Step 2.Remove outer jacket.
Step 3.Remove inner door per TTW SERVICE PROCEDURE XIII, step 3a through step 3d.
Step 4.Disconnect main burner feed line (3/4 wrench), pilot tube (7/16 wrench) and igniter/flame sensor wire
from gas control and remove burner assembly from combustion chamber.
®
Step 5.Clean ScreenLok
scale or other debris accumulation. Using a soft brush, clear jacket openings from any dirt, dust,
restrictions or other obstructions.
Step 6.Remove any debris from burner assembly per TTW SERVICE PROCEDURE I and reinstall burner
assembly into combustion chamber.
Flame Arrestor using stiff brush, compressed air and/or shop vacuum to remove any
Step 7.Reconnect feedline, pilot tube and igniter/flame sensor wire to the gas control.
Step 8.Reinstalll inner door per TTW SERVICE PROCEDURE XIII, step 7 through step 12.
Step 9.To resume operation follow the instructions located on the lighting instruction label or the lighting
instruction located in the installation and operation manual.
Page 37
Page 38
BTUBritish Thermal Units
38
GPMGallons per Minute
HzHertz
KW/hKillo-watts per hour
LEDLight Emitting Diode
NPTNational Pipe Thread
OhmsOhms of resistance
PSIPounds per Square Inch
RPMRevolutions per Minute
TCOTemperature Cut Off
VACVolts Alternating Current
W.C.Inches of Water Column
°CDegrees Centigrade
°FDegrees Fahrenheit
Glossary of Terms
NOTES
Page 38
Page 34
Page 39
Parts List
39
1. Blower Complete
2. Air Mixing Inlet cover
3. Pressure Switch
4. Blower Temp. Switch
5. Blower Gasket
6. Blower Power Cord
7. Vent Adapter w/vent term.
8. Condensate Hose Kit
9. Flue Reducer (M2 only)
10. Heat Trap Outlet
11. Hot Water Outlet Anode
12. Flue Baffle
13. Heat Trap Inlet
14. Inlet Dip Tube
15. Wire Harness
16. T&P Valve
17. ¾ NPT Plug
18. Burner Assy. (Nat)
19. Burner Head
20. Main Burner Orifice
21. Pilot Assy. (Nat)
22. Pilot Orifice
23. Feedline
24. Burner Assy. (L.P.)
25. Cast Iron Burner
26. Pilot Assy. (L.P.)
27. Pilot Orifice (L.P.)
28. Feedline
29. Jam Nut
30. Air Shutter
31. Main Burner Orifice (L.P.)
32. Outer Door
33. Right Side Inner Door
34. Screw #8-15 x 3/4
35. Left Side Inner Door
36. Screw #10-12 x 3/4
37. Brass Drain Valve
38. Flammable Vapor Sensor Clip
39. Flammable Vapor Sensor
40. Sensor Harness
41. Thermal Well
42. Gas Control
43. Gas Control Service Tool
44. Kit-Gas Control
45. Inner Door Gasket Kit
46. ASSE App’vd Mixing Valve
47. Kit-Heat Trap Insert
Page 35
Page 39
Page 40
Email
parts@bradfordwhite.com
techserv@bradfordwhite.com
www.bradfordwhite.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.